Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

Back to

Subindex

The power advantage ...


Rectifier DPR 1200B-48

Features
• Very high power density 1100 W/l - 18 W/in3
• High efficiency ≥ 91%
• Hot pluggable, all connectors at the rear
• Fan cooled with air flow monitoring
• Wide input voltage range: 88 - 300 Vrms
• Power factor ~ 1.0 (sinusoidal input current)
• Constant output power characteristic
• System bus: analogue / digital
• Operating temperature range up to 75°C

Applications
• Digital subscriber line (DSL)
• Transmission
• PBX
• Wireless base stations
• Network components

Description
The rectifier DPR 1200B-48 is a single phase, hot-pluggable, fan-cooled rectifier. The outstanding
power density of this product offers the optimum 1U or 3U shelf solution for space critical
applications. The constant output power characteristic supplies the specified power over the full
output voltage range. The benefit is an optimised modular system design (fewer number of
modules) and matches the supply requirements for state-of-the-art telecom equipment. These
performances as well as the extended temperature range, wide input voltage range and advanced
technology (patented solution) are the key factors of the success of this rectifier and it offers a cost
effective and reliable solution.
The typical applications for this rectifier are both in indoor and outdoor environments, which is a
perfect solution for digital subscriber line (DSL), transmission, PBX, wireless base stations, core
network components, telecommunication networks and data networks.
The rectifier meets the requirements set by the telecommunication standards.

lf_dpr1200b-48_en.doc / rev. 1.0 / 01. 06 2004 / HPG


Back to
Subindex

DPR 1200B-48: Technical specifications

General User interface


Efficiency ≥ 91 % Output current display LED bar
Losses, max. 135 W Status indication LED «ok»
Safety EN 60 950, class I LED «OVP»*
UL 60 950 LED «Overtemp»*
CAN / CSA – C22.2 LED «Fan failure»*
EMI, radiated EN 55 022, class B * Status indication integrated in the LED bar
Compliant with EN 300 386-2
Cooling Fan cooled Power system controller
Power density 1100 W / l 18 W / in3 PSC 1000 Voltage programming
Accoustic noise 48 dB(A) Rectifier fail alarm
PSC 3 Voltage programming
Input
Curr. limit programming
Voltage range 88 ... 300 Vrms
Power limit programming
Volt. range, red. power 88 ... 184 Vrms
Rectifier fail alarm
Volt. range, no PFC 276 … 300 Vrms
Rectifier start up
Inrush current 10.6 Apeak
Rectifier on/off
Current maximum 7.5 Arms
Line current Meets IEC 1000-3-2
Harmonic distort. THD <5% Mechanics
Power factor ~ 1.0 Width, overall 40.8 mm (1U)
EMI, conducted EN 55 022, class B Height, overall 132 mm (3U)
Mains connector Rear side Depth, overall 232.5 mm
Input protection Internal fuse 2 x 10 A Weight 1.25 kg
Input switch None
Environment
Output Ambient temperature -25 ... + 75 °C
Voltage, nominal 53.5 Vdc Reduced power 65 ... + 75 °C
Voltage adjust range 42 ... 58 Vdc Relative humidity 95 % max, non cond.
Voltage error, static ± 250 mVdc
Overvoltage protection 59 V ± 1 V Accessories
Ripple + spikes ≤ 100 mVp-p Single backplane P/N: D0106218
Psophometric noise ≤ 1.0 mVrms (weighted) Triple backplane P/N: D0112006
EMI, conducted EN 55 022, class A Blank panel P/N: D0112127
Current limit, nominal 28 Adc
Limit adjustment range 0 ... 28 Adc
Load sharing < ± 2 Adc
Power limit 1200 W, fixed
Output connector Rear side
Output protection Internal fuse 40 A

Output characteristic:
Uout [V]
58 1200 W
53.5
control range
43
42

Iout [A]
20.7 22.4 28

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

The power advantage ...


Rectifier FR 48 V - 2000 W - E

Features
• Efficiency ≥ 91%
• Compact (500 W / l) and light (4.4 kg)
• Hot pluggable, all connectors at the rear
• Fan cooled with air flow monitoring
• Wide input voltage range: 88 - 276 Vrms
• Power factor ~ 1.0 (sinusoidal input current)
• Constant output power characteristic
• System bus: analogue / with PSC 3: digital
• Operating temperature range up to 70°C

Applications
• Indoor and outdoor
• Medium to large power systems
• Shelf power solutions
• Telecom, wireless, datacom

Description
The rectifier FR 48 V - 2000 W - E is a single phase, hot-pluggable, fan-cooled rectifier. The
constant output power characteristic supplies the specified power over the full output voltage
range. The benefit is an optimised modular system design (fewer number of modules) and
matches the supply requirements for state-of-the-art telecom equipment. This performance as well
as the extended temperature range, wide input voltage range, high power density and advanced
technology are the key factors of the success of this rectifier and it offers a cost effective and
reliable solution.
The typical applications for this rectifier are both in indoor and outdoor environments, which is a
perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The rectifier meets the requirements set by the telecommunications standards.

leaflet_fr_48_2k_e_en.doc / rev. 1.3 / 10. 11. 2003 / mb


Back to
Subindex

FR 48 V - 2000 W - E: Technical specifications

General User interface


Efficiency ≥ 91 % Output current display LED bar
Losses, max. 200 W Status indication LED «ok»
Safety EN 60 950, class I
UL 60 950 Power system controller
CAN / CSA – C22.2 PSC 1000 Voltage programming
EMI, radiated EN 55 022, class B Rectifier fail alarm
Compliant with EN 300 386-2 PSC 3 do. plus additional
Cooling Fan cooled remote control functions
Power density 500 W / l 8.2 W / in3
Mechanics
Input Width, overall 65 mm
Voltage range 88 ... 276 Vrms Depth, overall 346 mm
Volt. range, red. power 88 ... 184 Vrms Height, body 200 mm
Inrush current < 15 Apeak Height, front panel 212 mm
Current maximum 12 Arms Weight 4.4 kg
Line current Meets IEC 1000-3-2
Harmonic distort. THD <5% Environment
EMI, conducted EN 55 022, class B Ambient temperature -25 ... + 70 °C
Mains connector Rear side Reduced power 60 ... + 70 °C
Input protection Internal fuse 2 x 15 A Relative humidity 95 % max, non cond.
Input switch None
Accessories
Output Single back plane P/N: D0100298
Voltage, nominal 53.5 Vdc
Voltage adjust range 42 ... 58 Vdc
Voltage error, static ± 250 mVdc
Overvoltage protection 59 V ± 1 V
Ripple + spikes ≤ 200 mVp-p
Psophometric noise ≤ 1.0 mVrms (weighted)
EMI, conducted EN 55 022, class A
Current limit, nominal 46.5 Adc
Limit adjustment range 0 ... 46.5 Adc
Load sharing < ± 3 Adc
Power limit 2000 W, fixed
Output connector Rear side
Output protection Internal fuse 50 A

Output characteristic:
Uout [V]
58 2000 W
53.5
control range
43
42

Iout [A]
34.5 37.4 46.5

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

The HDS 7200 series ...


Rectifier ESR 48 V - 7200 W - A

Features
• 3 Phase, 380/480 Vrms input
• Efficiency 90 %
• Low THD <5%
• Hot swappable, no system shutdown for maintenance
• Wide input voltage range: 264 - 530 Vrms
• Power factor correction (0.99)
• Constant output power characteristic
• User friendly LCD Display
• Intelligent micro-processor controlled

Applications
• Bulk power system
• Telecom, wireless, datacom

Description
The rectifier ESR 48 V - 7200 W - A is a three phase, hot-pluggable, fan-cooled rectifier. The constant output power
characteristic supplies the specified power over the full output voltage range. The rectifier employs the
state-of-the-art technology and provides excellent performance in the extended temperature range, wide input
voltage range, and low THD. The advanced technology is the key factor of the success of this rectifier and it offers a
cost effective and reliable solution.

The typical application for this rectifier is indoor environments, which is a perfect solution for core network
components, telecommunications networks and data networks.

Leaflet_esr48_7200waa/rev. 1.0/26.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

ESR 48 V - 7200 W - A: Technical specifications


General User Interface
Efficiency, 380/480Vrms 90 % Status indication LCD Display
Safety EN 60950 LED «AC ON»
IEC 60950 LED «ALM»
UL 60950 LED «CL»
CAN/CSA-C22.2 No. 60950
EMI, radiated FCC Part 15, class B Power system controller
Compliant with EN 55022, class B Intelligent CSU
Cooling Fan cooled
Acoustic noise 55 dB(A) Mechanics
Power density 4.7 W / in3, 288 W / l Width, overall 19” / 483 mm
Depth, overall 18.9” / 480 mm
Input Height, overall 5.2” / 131 mm
Voltage range 264 ... 530 Vrms Weight 48.8 lb / 22 kg
Inrush current < 18 Apeak
Current maximum 20 Arms at 264V Environment
Power factor > 0.99 Operating temperature - 5 ... + 55 °C
Line current Meets IEC 1000-3-2 Relative humidity 95 % max, non condensing
Harmonic distort. THD 5% Altitude - 500 ~ 10000 feet
EMI, conducted FCC Part 15, class B
Compliant with EN 55022, class B *Specifications are subject to change due to technical progress
Mains connector Rear side
Input protection NFB 25 A x 1
Internal fuse 30 A x 3
Input switch Yes

Output
Voltage, nominal 54 Vdc
Voltage adjust range 40 ... 60 Vdc
Load regulation < ± 0.5 %
Line regulation < ± 0.1 %
Overvoltage protection 60 Vdc
Ripple + spikes ≤ 100 mVp-p
Psophometric noise ≤ 2.0 mVrms (weighted)
Current limit, nominal 150 Adc
Load sharing < ± 2%
Power limit 7200 W, fixed
Output connector Rear side
Output protection Internal fuse 180 A x 1
Output characteristic:
Uout [V]
60 7200 W
54
48

40

Iout [A]
120 133 150

Leaflet_esr48_7200waa/rev. 1.0/26.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 48/2000-6 19''

Features
• Modular structure
• 19’’ rectifier shelf / 5 U
• Easy to stack shelves
• Up to 12 kW installed power
• Fan cooled rectifiers FR 48 V – 2000 W – E
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
• Integrated 3 phase AC terminal (3L+N+PE)

Applications
• Indoor and outdoor
• Medium to large power systems
• Shelf power solutions
• Telecom, wireless, datacom

Description
The AMS 48/2000-6 19’’ is a very compact 19’’ / 5U shelf for the rectifier FR 48 V - 2000 W – E.
The modular design allows flexible power system solutions in 19’’ standard cabinets and is the key
factor of the success of this power system and it offers a cost effective and reliable solution.
The typical applications for this rectifier shelf are both in indoor and outdoor environments, which is
a perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.

leaflet_ams_48_2000_6_19''_en.doc / rev. 2.4 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems
AMS 48/2000-6 19'': Technical specifications
General Mechanics
Efficiency ≥ 91 % Construction steel frame
Losses, max. 1200 W (6 rectifiers) Cabinet standard 19’’
Safety IEC/EN 60 950 Height, overall 225 mm / 5 U
EMC EN 300 386-2 Width, body 432 mm
Cooling Fan cooled Depth, overall 437 mm
Weight, shelf 10 kg
Input Weight, rectifiers 6 x 4.4 kg
AC connection 3L + N + PE
Nominal voltage 3 x 230 Vrms (L-N) Environment
Range, full power 184 ... 276 Vrms Ambient temperature -25 ... + 70 °C
Range, reduced power 88 ... 184 Vrms Reduced power 60 ... + 70 °C
Frequency range 45 ... 66 Hz Relative humidity 95 % max, non cond.
Current nominal 3 x 19 Arms @ 12kW Protection IP 20
Current maximum 3 x 24 Arms @ 12kW
Inrush current < 30 Apeak per phase Options
Line current Meets IEC 1000-3-2 Number of rectifiers 1 ... 6
Harmonic distort. THD <5% AC connection 3L+N+PE
Mains terminal AC cord 5 x 6mm2 / 5 m 3L+PE (220/240Vrms L-L)*
Input protection, recomm. MCB 3 x 25 A / C-curve
Main switch External Accessories
Distribution DFU 300-DC 19’’
Output
*
Voltage, nominal 53.5 Vdc on request
Voltage adjust range 42 ... 58 Vdc
Voltage error, static ± 250 mVdc Subject to change due to technical progress
Overvoltage protection 59 V ± 1 V
Ripple + spikes ≤ 200 mVp-p
Psophometric noise ≤ 1.0 mVrms (weighted)
Nominal current 224 Adc @ 12kW, 53.5V
Current limit, maximum 279 Adc @ 12kW, 43V
Power, nominal 12 kW
Power, redundant 10 kW
Power, reduced min. 4800 W
Output terminal Copper bar, rear side
Output protection Internal fuse each rect.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Rectifier Shelf
DPS 1200B-48-3RS 19IN

Features
• Modular structure
• 19’’ rectifier shelf / 1 U
• Short depth
• Easy to stack shelves
• Up to 3.6 kW installed power
• Fan cooled rectifiers DPR 1200B-48
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%

Applications
• Indoor and outdoor
• Digital subscriber line (DSL)
• Transmission, PBX
• Telecom, wireless, datacom

Description
The DPS 1200B-48-3RS 19IN is a very compact and short 19’’ / 1U shelf for three DPR 1200B-48
rectifiers. The modular design allows flexible power system solutions in 19’’ standard cabinets,
offering a cost effective and reliable solution. The DPS 1200B-48-3RS 19IN can be applied with
various types of standard or customised distribution units with PSC 1000 or PSC 3 power system
controllers.
The typical applications for this rectifier shelf are both in indoor and outdoor environments, which is
a perfect solution for digital subscriber line (DSL), transmission, PBX, wireless base stations, core
network components, telecommunications networks and data networks.

lf_dps-1200b-48-3rs-19in_en.doc / rev. 1.2 / 24.06.2004 / MHa


Back to
Subindex

Energy Systems
DPS 1200B-48-3RS 19IN: Technical specifications
General Mechanics
Efficiency ≥ 91 % Construction Steel frame
Losses, max. 405 W (3 rectifiers) Cabinet standard 19’’
Safety IEC/EN 60 950 Height, overall 44.45 mm / 1 U
EMC EN 300 386-2 Width, body 444 mm / 19’’
Cooling Fan cooled Depth, overall 280 mm
Weight, shelf TBD
Input Weight, rectifiers 3 x 1.25 kg
AC connection 3 / 400 V / N / PE
Nominal voltage 230 Vrms (L-N) Environment
Voltage range 88 ... 300 Vrms Ambient temperature - 25 ... + 75 °C
Range, reduced power 88 ... 184 Vrms Reduced power + 65 ... + 75 °C
Volt. range, no PFC 276 … 300 Vrms Relative humidity 95 % max, non cond.
Frequency range 45 ... 66 Hz Protection IP 20
Current nominal 5.8 Arms @ 1.2kW / phase
Current maximum 7.5 Arms @ 1.2kW / phase Options
Inrush current < 10.6 Apeak per phase Number of rectifiers 1 ... 3
Line current Meets IEC 1000-3-2 Alternative AC connect. 3 / 120 V / PE
Harmonic distort. THD <5%
Mains terminal max. 5 x 2.5 mm2 Accessories
Input protection, recomm. Internal fuse in each rect. Distribution DPD 200 19IN-3U
DPD 250 19IN-5U
Output
Voltage, nominal 53.5 Vdc Subject to change due to technical progress.
Voltage adjust range 42 ... 58 Vdc
Voltage error, static ± 250 mVdc
Overvoltage protection 59 V ± 1 V
Ripple + spikes ≤ 200 mVp-p
Psophometric noise ≤ 1.0 mVrms (weighted)
Nominal current 67 Adc @ 3.6 kW, 53.5 V
Current limit, maximum 84 Adc @ 3.6 kW, 43.0 V
Power, nominal 3.6 kW
Power, redundant 2.4 kW
Output terminal Varies
- Direct copper busbar or
- Cable connection points
Output protection Internal fuse in each rect.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 48/2000-8 GFE
Main features
• Up to 16 kW installed power
• Fan cooled rectifiers FR 48 V – 2000 W – E
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
• LVD option
• Up to 3 LVLD option
• Power system controller PSC 1000 or PSC 3
• Different mounting options (wall or mountable on
battery cabinet)

Typical applications
• Medium power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks

Description
The AMS 48/2000-8 GFE is a compact medium power system for power up to 16 kW. The stable
construction is based on a sheet metal design. The system contains a rectifier shelf for up to 8
rectifiers FR 48 V – 2000 W – E and one distribution unit with configurable elements for AC-, DC
distribution, LVD, LVLD and a power system controller. The power system can be mounted on top
of the battery cabinet or to the wall.
The typical applications for this power system are wireless base stations, core network
components, telecommunications and data networks.
This compact, high power density power system is the perfect choice for space-critical solutions.

leaflet_ams_48_2000_8_gfe_en.doc / rev. 2.5 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems
AMS 48/2000-8 GFE: Technical specifications
General Battery connection
Efficiency ≥ 91 % MCB 1 ... 6 x 125 A
Losses, max. 1600 W (8 rectifiers) LVD Option
Safety IEC/EN 60 950
EMC EN 300 386-2 Mechanics
Cooling Fan cooled Construction sheet metal
Cabinet standard GFE
Input Width, body 600 mm
AC connection 3L + N + PE Depth, overall 480 mm
8 x L+N+PE Height, overall 680 mm
Nominal voltage 3 x 230 Vrms (L-N) Weight, system 80 kg
Range, full power 184 ... 276 Vrms Weight, rectifiers 8 x 4.4 kg
Range, reduced power 88 ... 184 Vrms
Frequency range 45 ... 66 Hz Environment
Current nominal 3 x 28,5 Arms @ 16kW Ambient temperature -25 ... + 70 °C
Current maximum 3 x 36 Arms @ 16kW Reduced power 60 ... + 70 °C
Inrush current < 90 Apeak per phase Relative humidity 95 % max, non cond.
Line current Meets IEC 1000-3-2 Protection IP 20
Harmonic distort. THD <5%
Mains terminal Terminal blocks Control and monitoring
Input protection, recomm. 3 x 40 A Power system controller PSC 1000
8 x 16 A (8 x 1~) PSC 3*
Main switch External See leaflet for power system controller.
Transient OVP Option
Options
Output Number of rectifiers 1 ... 8
Voltage, nominal 53.5 Vdc AC connection 3L+N+PE
Voltage adjust range 42 ... 58 Vdc 2 x (3L+N+PE)
Voltage error, static ± 250 mVdc L+N+PE (single AC
Overvoltage protection 59 V ± 1 V feed for each rect)
Ripple + spikes ≤ 200 mVp-p 3L+PE (220/240VrmsL-L)*
Psophometric noise ≤ 1.0 mVrms (weighted) Power system controller PSC 1000
Nominal current 299 Adc @ 16kW, 53.5V PSC 3*
Current limit, maximum 372 Adc @ 16kW, 43V LVD 350 A
Power, nominal 16 kW LVLD 350 A
Power, redundant 14 kW Transient OVP
Power, reduced min. 6400 W
Accessories
Load distribution Rectifier front cover
MCB 1 ... 24 pcs / 1 ... 63 A Battery cabinets
LVLD Option See leaflet for battery cabinets

* on request

Subject to change due to technical progress.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 48/2000-8 ETS
Main features
• Up to 16 kW installed power
• Up to 14 kW with redundancy
• Fan cooled rectifiers FR 48 V – 2000 W – E
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
• LVD (low voltage disconnect) option
• Up to 3 LVLD (low voltage disconnect) option
• Integrated battery shelves
• Power system controller PSC 1000 or PSC 3

Typical applications
• Medium power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks

Description
The AMS 48/2000-8 ETS is a modular large power
system for power up to 16 kW. The stable construction
is based on a frame cabinet design. The system
contains one rectifier shelf for up to 8 FR 48 V – 2000 W
– E rectifiers and a distribution unit with configurable
elements for AC-, DC distribution, LVD, LVLD and a
power system controller.
The modular design allows flexible power system
solutions in the ETS cabinet line and is the key factor of
the success of this power system and it offers a cost
effective and reliable solution.
The typical applications for this power system are
wireless base stations, core network components,
telecommunications and data networks.

This compact, high power density power system is the


perfect choice for space-critical solutions.

leaflet_ams_48_2000_8 ets_en.doc / rev. 2.4 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems

AMS 48/2000-8 ETS: Technical specifications

General Battery connection


Efficiency ≥ 91 % MCB 1 - 6 x 125 A
Losses, max. 1600 W (8 rectifiers) LVD optional
Safety IEC/EN 60 950 Battery shelves 4 pcs, space for 4 x 150
EMC EN 300 386-2 Ah front polebatteries
Cooling Fan cooled
Mechanics
Input Construction sheet metal
AC connection 3L + N + PE Cabinet standard ETS
Nominal voltage 3 x 230 Vrms (L-N) Width, body 600 mm
Range, full power 184 ... 276 Vrms Depth, overall 600 mm
Range, reduced power 88 ... 184 Vrms Height, overall 2000 mm
Frequency range 45 ... 66 Hz Weight, system 120 kg
Current nominal 3 x 28,5 Arms @ 16kW Weight, rectifiers 8 x 4.4 kg
Current maximum 3 x 36 Arms @ 16kW
Inrush current < 90 Apeak per phase Environment
Line current Meets IEC 1000-3-2 Ambient temperature -25 ... + 70 °C
Harmonic distort. THD <5% Reduced power 60 ... + 70 °C
Mains terminal Terminal blocks Relative humidity 95 % max, non cond.
Input protection, recomm. 3 x 40 A Protection IP 20
Main switch External
Transient OVP optional Control and monitoring
Power system controller PSC 1000
Output PSC 3*
Voltage, nominal 53.5 Vdc Technical data: see leaflet for power system
Voltage adjust range 42 ... 58 Vdc controller
Voltage error, static ± 250 mVdc
Overvoltage protection 59 V ± 1 V Options
Ripple + spikes ≤ 200 mVp-p Number of rectifiers 1 ... 8
Psophometric noise ≤ 1.0 mVrms (weighted) AC connection 3L+N+PE
Nominal current 299 Adc @ 16kW, 53.5V Power system controller PSC 1000
Current limit, maximum 372 Adc @ 16kW, 43V PSC 3*
Power, nominal 16 kW LVD 350 A
Power, redundant 14 kW LVLD 350 A
Power, reduced min. 6400 W Transient OVP for 3L+N+PE
Output terminal Copper bar, rear side
Output protection Internal fuse each rect. Accessories
Rectifier front cover
Load distribution
MCB 1 - 18 pc * on request
LVLD optional
Subject to change due to technical progress

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 48/2000-16 ETS
Main features
• Up to 32 kW installed power
• Expandable with a 2nd cabinet up to 64 kW
• Fan cooled rectifiers FR 48 V – 2000 W – E
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
• LVD option
• Up to 3 LVLD option
• Power system controller PSC 1000 or PSC 3

Typical applications
• Large power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks

Description
The AMS 48/2000-16 ETS is a modular large power
system for power up to 32 kW. The stable
construction is based on a frame cabinet design. The
system contains two rectifier shelves for up to 16
rectifiers FR 48 V – 2000 W – E and different
distribution units with configurable elements for AC-,
DC distribution, LVD, LVLD and a power system
controller.
The modular design allows flexible power system
solutions in the ETS cabinet line and is the key factor
of the success of this power system and it offers a
cost effective and reliable solution. This power
system is expandable with a 2nd cabinet.
The typical applications for this power system are
wireless base stations, core network components,
telecommunications and data networks.
This compact, high power density power system is
the perfect choice for space-critical solutions.

leaflet_ams_48_2000_16_ets_en.doc / rev. 2.4 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems

AMS 48/2000-16 ETS: Technical specifications


General Battery connection
Efficiency ≥ 91 % EFEN3, fuse 2 or 4 x 630 A
Losses, max. 3200 W (16 rectifiers) MG motor contactor 2 or 4 x (3x250A/pole)
Safety IEC/EN 60 950 LVD Option
EMC EN 300 386-2
Cooling Fan cooled Mechanics
Construction Frame cabinet
Input Cabinet standard ETS
AC connection 2 x 3L + N + PE Width, body 600 mm
16 x L+N+PE Depth, overall 600 mm
Nominal voltage 3 x 230 Vrms (L-N) Height, overall 2000/2200 mm
Range, full power 184 ... 275 Vrms Weight, system 200 kg
Range, reduced power 88 ... 184 Vrms Weight, rectifiers 16 x 4.4 kg
Frequency range 45 ... 66 Hz
Current nominal 3 x 57 Arms @ 32kW Environment
Current maximum 3 x 72 Arms @ 32kW Ambient temperature -25 ... + 70 °C
Inrush current < 90 Apeak per phase Reduced power 60 ... + 70 °C
Line current Meets IEC 1000-3-2 Relative humidity 95 % max, non cond.
Harmonic distort. THD <5% Protection IP 20
Mains terminal Terminal blocks
Input protection, recomm. 2 x 3 x 40 A (2 x 3~) Control and monitoring
16 x 16 A (16 x 1~) Power system controller PSC 1000
Main switch External PSC 3*
Transient OVP Option See leaflet for power system controller

Output Options
Voltage, nominal 53.5 Vdc Number of rectifiers 1 ... 16
Voltage adjust range 42 ... 58 Vdc AC connection 3L+N+PE (AC feed/shelf)
Voltage error, static ± 250 mVdc L+N+PE (single AC
Overvoltage protection 59 V ± 1 V feed for each rect)
Ripple + spikes ≤ 200 mVp-p 3L+PE (220/240Vrms L-L)*
Psophometric noise ≤ 1.0 mVrms (weighted) Power system controller PSC 1000
Nominal current 598 Adc @ 32kW, 53.5V PSC 3*
Current limit, maximum 744 Adc @ 32kW, 43V LVD 600 A / battery fuse
Power, nominal 32 kW LVLD 600 A / distribution unit
Power, redundant 30 kW Transient OVP
Power, reduced min. 12.8 kW
Accessories
Load distribution Rectifier front cover
Three/four rows DFU 29xMCB Cable channel
DFU 12x00
*
DFU 7x01 on request
DFU 7x02
DFU 5x03
Subject to change due to technical progress.
LVLD Option
See leaflet for distribution units.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 48/2000-24 ETS
Main features
• Up to 48 kW installed power
• Expandable with a 2nd cabinet up to 96 kW
• Fan cooled rectifiers FR 48 V – 2000 W – E
• Hot pluggable, all connectors at the rear
• Efficiency ≥ 91%
• LVD option
• Up to 3 LVLD option
• Power system controller PSC 1000 or PSC 3

Typical applications
• Large power systems
• Wireless base stations
• Core network components
• Telecommunications/data networks

Description
The AMS 48/2000-24 ETS is a modular large power
system for power up to 48 kW. The stable
construction is based on a frame cabinet design. The
system contains three rectifier shelves for up to 16
rectifiers FR 48 V – 2000 W – E and different
distribution units with configurable elements for AC-,
DC distribution, LVD, LVLD and a power system
controller.
The modular design allows flexible power system
solutions in the ETS cabinet line and is the key factor
of the success of this power system and it offers a
cost effective and reliable solution. This power
system is expandable with a 2nd cabinet.
The typical applications for this power system are
wireless base stations, core network components,
telecommunications and data networks.
This compact, high power density power system is
the perfect choice for space-critical solutions.

leaflet_ams_48_2000_24_ets_en.doc / rev. 2.4 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems

AMS 48/2000-24 ETS: Technical specifications


General Battery connection
Efficiency ≥ 91 % EFEN3, Fuse 2 or 4 x 630 A
Losses, max. 4800 W (24 rectifiers) MG motor contactor 2 or 4 x (3 x 250 A/pole)
Safety IEC/EN 60 950 LVD Option
EMC EN 300 386-2
Cooling Fan cooled Mechanics
Construction Frame cabinet
Input Cabinet standard ETS
AC connection 3L + N + PE Width, body 600 mm
Nominal voltage 3 x 230 Vrms (L-N) Depth, overall 600 mm
Range, full power 184 ... 276 Vrms Height, overall 2200 mm
Range, reduced power 88 ... 184 Vrms Weight, system 220 kg
Frequency range 45 ... 66 Hz Weight, rectifiers 24 x 4.4 kg
Current nominal 3 x 85,5 Arms @ 48kW
Current maximum 3 x 108 Arms @ 48kW Environment
Inrush current < 90 Apeak per phase Ambient temperature -25 ... + 70 °C
Line current Meets IEC 1000-3-2 Reduced power 60 ... + 70 °C
Harmonic distort. THD <5% Relative humidity 95 % max, non cond.
Mains terminal Terminal blocks Protection IP 20
Input protection, recomm. 3 x 3 x 40 A (3 x 3~)
Main switch External Control and monitoring
Transient OVP Option Power system controller PSC 1000
PSC 3*
Output See leaflet for power system controller
Voltage, nominal 53.5 Vdc
Voltage adjust range 42 ... 58 Vdc Options
Voltage error, static ± 250 mVdc Number of rectifiers 1 ... 24
Overvoltage protection 59 V ± 1 V AC connection 3L+N+PE (AC feed/shelf)
Ripple + spikes ≤ 200 mVp-p 3L+PE (220/240VrmsL-L)*
Psophometric noise ≤ 1.0 mVrms (weighted) Power system controller PSC 1000
Nominal current 897 Adc @ 48kW, 53.5V PSC 3*
Current limit, maximum 1116 Adc @ 48kW, 43V LVD 600 A / battery fuse
Power, nominal 48 kW LVLD 600 A / distribution row
Power, redundant 46 kW Transient OVP
Power, reduced min. 19.2 kW
Accessories
Load distribution Rectifier front cover
Three rows DFU 29xMCB Cable channel
DFU 12x00
DFU 7x01 * on request
DFU 7x02
DFU 5x03
LVLD Option Subject to change due to technical progress

See leaflet for distribution units.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

The power advantage ...


Power system controller PSC 1000

Features
• Reliable and user-friendly smart controller
• Parameter entry via key-pad
• User configurable alarms and settings
• Programmable DC output voltage
• Temperature compensated float charge
• Smart battery management
• Essential functions protected by password
• Remote monitoring (option)

Applications
• Medium power systems

Description
The power system controller PSC 1000 is a powerful microprocessor unit intended to supervise
and control modular power systems. The product complies to all important requirements and
standards of the telecommunication market. The superior features make this controller a prime
choice for your telecom power systems.
The PSC 1000 provides a full set of control and supervision functions. This means user
configurable alarms and settings which are well readable on the liquid crystal display with plain text
indication. The smart battery management with regularly accomplished capacity tests is one of the
key factors for the availability of a power system. The controller allows alarming by means of
potential-free relay contacts and remote supervision with modem and the PC based power system
manager PSM magic.

leaflet_psc_1000_en.doc / rev. 1.4 / 09. 09. 2003 / mb


Back to
Subindex

PSC 1000: Technical specifications

General Mechanics
System voltages 24 / 36 / 48 / 60 Vdc Width 116 mm
Accuracy of system voltage measurement Height 180 mm
0.2 % Depth 30 mm
Nominal system current 0 ... 2000 Adc Weight 0.4 kg
Accuracy of system current measurement
2% Environment
User definable alarms and thresholds Ambient temperature 0 ... + 50 °C (operation)
yes - 40 ... + 70°C (storage)
Power supply 18 ... 75 Vdc / 50 mA Relative humidity 95 % max, non cond.
Remote monitoring Option Protection IP 20
System reliability in case All rectifiers operate at
of controller failure their preset default values Operation
Display (LCD) 2 lines of 16 char each
Connections Local alarms (LEDs) Urgent alarm
Load 3 independent strings Non-urgent alarm
Battery 2 independent strings Alarm stop
Mains failure
Rectifier modules 24 maximum Service not automatic
Alarm relays 4, with potential free Mode of operation Menu controlled
contacts
Menu languages English, Swedish,
Low battery disconnect. 1, with potential free German, Chinese,
changeover contact Spanish, Finnish, Polish,
Italian, Hungarian,
Battery control French, Catalan
Accuracy of battery voltage measurement
0.5 %
Temperature compensated float charging voltage
0 ... - 200 mV / °C
Automatic boost charging Option
Low battery disconnect Option
Periodic battery test Option
Separate charging Option

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

The power advantage ...


Power system controller PSC 3

Features
• Modular power system controller
• Flexible system configuration
• Easy system expansion
• Digital system bus IMBUS
• Different add on functions
• Different front end modules
• Smart battery management
• Remote monitoring with modem or LAN

Applications
• Medium to large power systems
• Decentralised data acquisition

Description
The PSC 3 is a 3rd generation of power system controller. This product is an optimum solution for
medium to very large and complex power systems. It consists of a central unit, which provides
basic I/O periphery and a very robust and reliable CAN standard based communication bus. This
concept provides easy expansion by means of different front end modules as user interface with
LCD, rectifiers, inverters, different sensors, I/O modules, customised gateways etc.
The front end modules are located close to the elements to be monitored like shunts or fuses. The
benefit is an easy wiring instead of a large cable harness, which is perfect for expandable medium
power systems or high power solutions with decentralised distributions (BDFB) and monitoring
batteries in separate rooms.
The smart battery management with regularly accomplished capacity tests is one of the key factors
for the availability of a power system.
The PSC 3 allows alarming by means of potential-free relay contacts and remote supervision with
a standard web browser via modem or LAN / Ethernet.

leaflet_psc_3_en.doc / rev. draft / 14. 11. 2003 / mb


Back to
Subindex

PSC 3: Technical specifications

General Remote configuration supervision


Safety EN 60 950, class I Computer Web browser
UL 60 950
CAN / CSA – C22.2 Functions
EMI, radiated EN 55 022, class B Flexible, modular system configurations
Compliant with EN 300 386-2 Configurable I/O periphery
Cooling convection Float voltage control
Temperature compensation
Input Battery current limit
Voltage range 18 ... 75 VDC Low voltage disconnect (LVD)
Current maximum 0.75 ADC Low voltage load disconnect (LVLD)
EMI, conducted EN 55 022, class B Battery test
Input protection External fuse 2A Supports + and – grounded systems
Input switch None Language, default English
2nd language Configurable
Basic configuration
Terminal RS 232 Mechanics
Relays, dry contacts 4 changeover (form Width, overall 86.5 mm
C) Depth, overall 180 mm
Digital inputs 2 Height, body 43 mm
Sensors 0 ... 3 SENSN Weight 0.75 kg
1 voltage-, current-,
temperature-, fuse Environment
monitoring per SENSN Ambient temperature -25 ... + 70 °C
voltage sense resolution < 0.5 % Relative humidity 95 % max, non cond.
current sense resolution < 0.5 % Protection IP 20
temperature resolution < 1 °C
System communication IMBUS / CAN Options: add on functions
0 ... 200 rectifiers Analogue rectifier bus 0 ... 32 rectifiers
Modem interface RS 232
Maximum configuration with front end modules Ethernet LAN TCP/IP
Relays, dry contacts 100 changeover (form C) Real time clock
Digital inputs 258 Inverter communication INVBUS / CAN
Sensors 99 SENSN
1 voltage-, current-, See document PSC 3 accessories
temperature-, fuse
monitoring per SENSN Accessories, front end modules
See document PSC 3 accessories
Basic user interface
Status indication LED «power» Customised functions
LED «alarm» On request

Local configuration, supervision


Computer Web browser
User interface module 0 ... 2 UIM
LCD display
Keypad
status indication LED

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

Energy Systems

The power advantage...


Battery cabinets
for GFE power systems
Main features
• 2, 3 or 4 battery shelves
• Height 900 mm or 1200 mm
• Depth 480 mm or 600 mm
• Installed below GFE power system or separately
• Roof as an option in separate installation
• Delivery as a kit, assembly on a site

Description
The battery cabinet is compatible with the GFE system
cabinet line. Depending on the cabinet height and
amount of shelves there is space for two to four battery
strings in the cabinet.
The modular design offers a complete solution together
with a power system from the GFE product line which
can be mounted onto this battery cabinet family.
For separate installation an optional roof is available.
The battery cabinet will be delivered as a kit and it is
easy to assemble on a site.

leaflet_battery_cabinets_gfe_en.doc / rev. 1.0 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems
Battery cabinet: Technical specifications
Battery cabinet IFE (depth 480 mm) and IFF (depth 600 mm)

Front view 3 shelves Front view 2 shelves Side view, depth 480/600

41,5

8
282,33

432

900 282,33

558 432

Battery cabinet LFE (depth 480 mm) and LFF (depth 600 mm)

Front view 4 shelves Front view 3 shelves Side view, depth 480/600

39,5

282,5
382,33

282,5

1200 382,33

558

Options: roof
All measurements in millimeters.

Subject to change due to technical progress.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Distribution Unit DPD 200 19IN-3U

Features
• Modular structure
• 19’’ distribution unit / 3 U
• Easy to install,
all user connections on the front
• LVD and PLD option
• Controller PSC 3
• 3-phase AC-terminal
• AC and DC-connections for rectifier shelves

Applications
• Indoor and outdoor
• Medium to large power systems
• Shelf power solutions
• Telecom, wireless, datacom

Description
The DPD 200 19IN-3U is a very compact 19’’ / 3U distribution unit applicable with various rectifier
shelves. The stable construction is based on sheet metal design. The system contains connections
for up to 4 rectifier shelves of the DP 1200B Series, AC- and DC-connections, battery connection and
power system controller PSC 3. The modular design allows flexible power system solutions in 19’’
standard cabinets, offering a cost effective and reliable solution.
The typical applications for this distribution unit are both in indoor and outdoor environments, which is
a perfect solution for wireless base stations, core network components, telecommunications networks
and data networks.

lf_dpd-200-19in-3u_en.doc / rev. 1.1 / 22.06.2004 / MHa


Back to
Subindex

Energy Systems
DPD 200 19IN-3U: Technical specifications
General Battery connection
Safety IEC/EN 60 950 MCB 4 x C120 series
EMC EN 300 386-2 LVD Optional 200 A
Cooling Convection cooled Cable size, max. 35 mm2

AC connection Mechanics
Input 3 / 400 V / N / PE Construction Steel rack
Mains terminal Terminal block Height, overall 131 mm (3 U)
Max. current 36A / phase Width, body 444 mm (19'')
Cable size, max. 6 mm2 Depth, overall 275 mm
Mains switch External Protection IP 20
Lightning protection External
Environment
Output Optimized connection Ambient temperature - 25... + 67 °C
board for Reduced power + 65 ... + 67 °C
DPS 1200B-48-3RS 19IN Relative humidity 95 % max, non cond.
Connector 4 x Phoenix GICV
2,5/5-G-7,62 Control & alarms
Max. current 12 A Power system controller PSC 3
Cable size, max. 2,5 mm2 PSC 200*

DC connection Accessories
Voltage, nominal 53.5 Vdc Rectifier shelf DPS 1200B-48-9RS 19IN
Current, maximum 200 A DPS 1200B-48-3RS 19IN
Input connection AMS 48/2000-6 19''
- Copper bars DPS 1200B-48-3RS 19IN AMS 48/540-9 19’’
- Cables Others
* on request
Load distribution
MCB 12 x 1...63 A (C60 series)
PLD Optional 125 A Subject to change due to technical progress.
- disconnects 3 / 6 / 9 MCBs
Cable size, max.
- MCB 1 A ... 32 A 16 mm2
- MCB 40 A ... 63 A 35 mm2

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


External DC distribution fuse unit
Main features
• Wall or rack mounted
• 12 DC output breakers (MCB) with LVLD or
18 DC output breakers (MCB) without LVLD
• LVLD 200 A disconnects 6 MCBs
• Dimensions
Height 220 mm (5U)
Width 444 mm (19’’)
Depth 210 mm
• Feeding cable 70 mm2

Description
The distribution fuse units (DFU) are designed for 19’’ rack or wall mounting. The modular
structure allows flexible configurations according to the customer needs. Partial load disconnection
LVLD is an option.
The DFU can be equipped with 18 magnetic circuit breakers (MCB) or 12 MCB with LVLD, which
disconnects 6 MCBs.
The fuse fault alarm is detected by the power system controller.

leaflet_external_dfu_en.doc / rev. 2.2 / 17.02.2003 / MHa


Back to
Subindex

Energy Systems
External DFUs: Technical specifications
Load distribution
DFU DFU 12 x MCB + LVLD 200A 19’’ (W/R)
1 A, 2 A, 3 A, 4 A, 6 A,
10 A, 16 A, 20 A, 25 A,
32 A, 40 A, 50 A, 63 A,
100 A (2p), 150 A (3p)
LVLD 200 A
Max current per DFU 200 A
Feeding cable 70 mm2

Load distribution
DFU DFU 18 x MCB 19’’ (W/R)
MCB 1 A, 2 A, 3 A, 4 A, 6 A,
0 A, 16 A, 20 A, 25 A,
32 A, 40 A, 50 A, 63 A,
100 A (2p), 150 A (3p)
LVLD -
Max current per DFU 200 A
Feeding cable 70 mm2

Subject to change due to technical progress.

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Distribution fuse units for ETS

Main features
• Applicable in ETS cabinet line
• Breaker (MCB) or fuse (00, 01 , 02, 03)
• Flexible, configurable power system distribution
• LVLD option per distribution unit

Description
The distribution fuse unit (DFU) is compatible with Delta
Energy Systems ETS system cabinet line. The modular
structure allows flexible configurations according to the
customer needs. LVLD for each distribution row is an
option.
The DFU can be equipped with magnetic circuit
breakers (MCB) or fuses (00, 01, 02, and 03).
The fuse fault alarm is detected by the power system
controller.

leaflet_dfus_for_ets_en.doc / rev. 2.3 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems
DFUs for ETS: Technical specifications
Load distribution
DFU DFU 30xMCB ETS
MCB 1 A, 2 A, 3 A, 4 A, 6 A,
10 A, 16 A, 20 A, 25 A,
32 A, 40 A, 50 A, 63 A,
100 A (2p), 150 A (3p)
LVLD Option 600 A
max current per DFU 600 A

DFU DFU 12x00 ETS


00-fuse 2 A, 6 A, 10 A, 25 A,
35 A, 50 A, 63 A, 80 A,
100 A, 125 A, 160 A
LVLD Option 600 A
max current per DFU 600 A

DFU DFU 7x01 ETS


01-fuse 63 A, 100 A, 160 A, 250 A
LVLD Option 600 A
max current per DFU 600 A

DFU DFU 7x02 ETS


02-fuse 200 A, 315A, 400 A
LVLD Option 600 A
max current per DFU 600 A

DFU DFU 5x03 ETS


03-fuse 400 A, 500 A, 630 A
LVLD Option 600 A
max current per DFU 600 A

Subject to change due to technical progress

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

The DCS series ...


Converter DD 48 V - 480 W - A

Features
• Module design for scaleable, cost effective expansion

• High efficiency

• Automatic load share, N+1 redundancy

• Hot swappable, no system shutdown for maintenance

• Reverse polarity protection design

• EMC Class B

• UL/cUL, TUV/CE Certificated

Applications
• 3G Co-station requirement

Description
Delta DD 48 V - 480 W - A is a hot-pluggable, fan-cooled converter which converts typical 24 Vdc input into -48
Vdc for various telecommunication applications. The high power density DD module employs the start-of-the-art
technology and provides high performance in efficiency, power density and extended operation temperature
range. Up to 4 DD power modules can be equipped into one 23” width power shelf and parallel up to 3 shelves.
The maximum capability can provide more than 5.5kW output power.

The typical application for this converter is 3G co-station environments, which is a perfect solution for core
network components, telecommunications networks and data networks.
.

Leaflet_dd48_480waa/rev. 1.0/03.11.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

DD 48 V - 480 W - A: Technical specifications


General Environment
Efficiency > 83 % Operating temperature 0 ... + 50 °C
Safety EN 60950 Relative humidity 95 % max, non condensing
UL 1950 Altitude - 500 ~ 10000 feet
CAN/CSA-C22.2 No.950-95
EMI, radiated EN 55022, class B *Specifications are subject to change due to technical progress
Compliant with
Cooling Fan cooled
Acoustic noise 55 dB(A)
MTBF > 150 K hours

Input
Voltage range 20 ... 30 Vdc
Inrush current < 200 A
Current maximum 75 A
EMI, conducted EN55022, class B
Compliant with
Mains connector Rear side
Input protection Breaker 60 A x 1
Input switch Yes
Polarity protection Yes

Output
Voltage, nominal 48 Vdc,
Voltage adjust range 42 ... 57.5 Vdc
Load regulation <±1V
Line regulation < ± 0.2 %
Overvoltage protection 59 ± 1V
Ripple ≤ 100 mVp-p
Current limit, nominal 20 Adc ± 5%
Load sharing < ± 5%
Power limit 480 W
Output connector Rear side
Short circuit protection Yes

User Interface
Status indication LED «DC O.K.»
LED «50% LOAD»
LED «100% LOAD»
LED «Converter Fail Alarm»
LED «Fan Fail»
O/P Voltage Adjustment Variable Resistor

Mechanics
Width, overall 5.1” / 130 mm
Depth, overall 11.7” / 297 mm
Height, overall 3.1” / 80 mm
Weight 2.22 lb / 1 kg

Leaflet_dd48_480waa/rev. 1.0/03.11.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

DD 1300 series ...


Converter DD 55 V - 1300 W - A

Features
• Compact size (9.1W/in3) and light weight
• High efficiency 88 %
• Hot swappable, no system shutdown for maintenance
• Wide operation temperature: -10~60 °C
• Reverse polarity protection design
• EMC Class B
• UL/cUL, TUV/CE Certificated

Applications
• 3G Co-station requirement

Description
Delta DD 55 V - 1300 W - A is a hot-pluggable, fan-cooled converter which converts typical 24 Vdc input into –55
Vdc for various telecommunication applications. The high power density DD module employs the start-of-the-art
technology and provides high performance in efficiency, power density and extended operation temperature range.
Up to 6 DD power modules can be equipped into one 19” width power shelf and can provide total 7.8KW output
power.

The typical application for this converter is 3G co-station environments, which is a perfect solution for core network
components, telecommunications networks and data networks.
.

Leaflet_dd55_1300wac/rev. 1.0/30.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

DD 55 V - 1300 W - A: Technical specifications


General Environment
Efficiency 88 % Operating temperature - 10 ... + 60 °C
Safety EN 60950 Relative humidity 95 % max, non condensing
IEC 60950 Altitude - 500 ~ 10000 feet
UL 60950
CAN/CSA-C22.2 No. 60950 *Specifications are subject to change due to technical progress
EMI, radiated FCC Part 15, class B
Compliant with CISPR 22, class B
Cooling Fan cooled
Acoustic noise 60 dB(A)
Power density 9.1 W / in3, 553 W / l
MTBF 760 K hours

Input
Voltage range 20 ... 31 Vdc
Inrush current < 200 A
Current maximum 75 A
EMI, conducted CISPR 14
Compliant with
Mains connector Rear side
Input protection Internal fuse 160 A x 1
Input switch No
Polarity protection Yes

Output
Voltage, nominal 55 Vdc, fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8V
Ripple ≤ 150 mVp-p
Current limit, nominal 26 Adc ± 5%
Load sharing < ± 5%
Power limit 1300 W, fixed
Output connector Rear side
Short circuit protection Yes

User Interface
Status indication LED «Input OK»
LED «Output Fail»
LED «Fan Fail»

Mechanics
Width, overall 2.6” / 65 mm
Depth, overall 9.8” / 250 mm
Height, overall 6.7” / 170 mm
Weight 6.67 lb / 3 kg

Leaflet_dd55_1300wac/rev. 1.0/30.09.2003/JHsieh
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

The DD 1300 series ...


DD System DD 55/1300W-6 KBA

Features
• 20 – 31 Vdc input; at 7.8 kW / 55 Vdc output
• High Efficiency 88%
• 4U high in 19" and ETSI rack standard format
• Hot swappable 1.3 kW DC/DC power modules
• EMC Class B
• UL/CUL, TUV approvals, CE mark and CB report

Applications
• 3G Co-station requirement

Description
The DD 55/1300W-6 KBA Power system combines a
compact modular design with intelligent power features
and state-of-the-art technology. The DD 55/1300W-6 KBA
is capable of providing power up to 7.8 kW. It contains up
to 6 converters DD 55 V - 1300 W - A, as well as different
distribution units with configurable elements for DC.

The DD Power System will be converting 24Vdc power to


-55Vdc. The Power Shelf can be configured into an
external rack system or work as an external stand-alone
DC power system.

Leaflet_dd55_1300w_6_kbaxx / rev. 1.0/13.10.2003 / JHsieh


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

DD 55/1300W-6 KBA: Technical specifications


General Environment
Efficiency 88 % Operating temperature - 5 ... + 50 °C
Safety EN 60950 Relative humidity 95 % max, non condensing
IEC 60950 Altitude - 500 ~ 10000 feet
UL 60950
CAN/CSA-C22.2 No.60950 Power module
EMI, radiated FCC Part 22, class B Converter DD 55 V - 1300 W - A
Compliant with EN 55022, class B
*Specifications are subject to change due to technical progress
Input
DC connection Single-Feeder
Voltage range 20 ... 31 Vdc
Current maximum 6 x 75 A
EMI, conducted FCC Part 14, class B
Compliant with EN 55022, class B
DC terminal Screw terminal
DC switch None

Output
Voltage, nominal 55 Vdc ,fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8 V
Maximum power 7800 W, max.
Current limit 138 A ± 5%
Load sharing < ± 5%

Options
Aux. Breaker Module 20A

Power system controller


Alarm Unit
Interface RS-232
Status indication LED «DC IN ALM»
LED «DC OUT ALM»
LED «MAJ ALM»
LED «MIN ALM»
LED «HVSD ALM»
LED «OT ALM»
LED «FB ALM»
Test Pointer DC Output voltage «V+, V-»
Relay outputs Up to 9 relay outputs
Mechanics
Construction Shelf
Width, overall 19” / 482 mm
Depth, overall 14.7” / 372 mm
Height, overall 6.9” / 176 mm
Weight, system (empty) 8.22 lb / 3.7 kg
Weight, converter 6.67 lb / 3 kg per converter

Leaflet_dd55_1300w_6_kbaxx / rev. 1.0/13.10.2003 / JHsieh


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

The DD 1300 series ...


DD System DD 55/1300W-6 KDA01

Features
• 20 - 31 Vdc input; at 7.8 kW / 55Vdc output
• High Efficiency 88%
• 8U high in 19" and ETSI rack standard format
• Hot swappable 1.3 kW DC/DC power modules
• UL/CUL, TUV approvals, CE mark and CB report

Applications
• 3G Co-station requirement

Description
The DD 55/1300W-6 KDA01 Power system combines a
compact modular design with intelligent power features
and state-of-the-art technology. The DD 55/1300W-6
KDA01 is capable of providing power up to 7.8 kW. It
contains up to 6 converters DD 55 V - 1300 W - A, as well
as different distribution units with configurable elements
for DC.

The DD Power System will be converting 24Vdc power to


-55Vdc. The Power Shelf can be configured into an
external rack system or work as an external stand-alone
DC power system.

Leaflet_dd55_1300w_6_kda01 / rev. 1.0/13.10.2003 / JHsieh


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

DD 55/1300W-6 KDA01: Technical specifications


General Power module
Efficiency 88 % Converter DD 55 V - 1300 W - A
Safety EN 60950
IEC 60950 *Specifications are subject to change due to technical progress
UL 60950
CAN/CSA-C22.2 No.60950
EMI, radiated FCC Part 22, class A
Compliant with EN 55022, class A

Input
DC connection Single/Multi-Feeder(s)
Voltage range 20 ... 31 Vdc
Current maximum 6 x 75 A
EMI, conducted FCC Part 14,
Compliant with EN 55022, class A
DC terminal Screw terminal
DC switch None

Output
Voltage, nominal 55 Vdc ,fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8 V
Maximum power 7800 W, max.
Current limit 138 A ± 5%
Load sharing < ± 5%

Options
PDU Box 10 ... 100 A, 16 positions
400 A maximum

Power system controller


Alarm Board
Alarm Interface DB 9
Relay outputs Up to 9 relay outputs

Mechanics
Construction Shelf
Width, overall 18.3” / 465 mm
Depth, overall 14.3” / 365 mm
Height, overall 13.6” / 347 mm
Weight, system (empty) 35.6 lb / 16 kg
Weight, converter 6.67 lb / 3 kg per converter

Environment
Operating temperature - 5 ... + 50 °C
Relative humidity 95 % max, non condensing
Altitude - 500 ~ 10000 feet

Leaflet_dd55_1300w_6_kda01 / rev. 1.0/13.10.2003 / JHsieh


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

The DD 1300 series ...


DD System DD 55/1300W-6 KDA06

Features
• 20 – 31 Vdc input; at 7.8 kW / 55 Vdc output
• High Efficiency 88%
• 4U high in 19" and ETSI rack standard format
• Hot swappable 1.3 kW DC/DC power modules
• EMC Class B
• UL/CUL, TUV approvals, CE mark and CB report

Applications
• 3G Co-station requirement

Description
The DD 55/1300-6 KDA06 Power system combines a
compact modular design with intelligent power features
and state-of-the-art technology. The DD 55/1300-6 KDA06
is capable of providing power up to 7.8 kW. It contains up
to 6 converters DD 55 V - 1300 W - A, as well as different
distribution units with configurable elements for DC.

The DD Power System will be converting 24Vdc power to


-55Vdc. The Power Shelf can be configured into an
external rack system or work as an external stand-alone
DC power system.

Leaflet_dd55_1300w_6_kda06 / rev. 1.0/13.10.2003 / JHsieh


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

DD 55/1300W-6 KDA06: Technical specifications


General Power module
Efficiency 88 % Converter DD 55 V - 1300 W - A
Safety EN 60950
IEC 60950 *Specifications are subject to change due to technical progress
UL 60950
CAN/CSA-C22.2 No.60950
EMI, radiated FCC Part 22, class B
Compliant with EN 55022, class B

Input
DC connection Multi-Feeders
Voltage range 20 ... 31 Vdc
Current maximum 6 x 75 A
EMI, conducted FCC Part 22,
Compliant with EN 55022, class B
Mains terminal Screw terminal
Main switch None

Output
Voltage, nominal 55 Vdc ,fixed
Load regulation <±1%
Line regulation < ± 0.2 %
Overvoltage protection 58.5 ± 0.8 V
Maximum power 7800 W, max.
Current limit 138 A ± 5%
Load sharing < ± 5%

Options
Aux. Breaker Module 20A

Power system controller


Alarm Board
Alarm Interface DB9
Relay outputs Up to 9 relay outputs

Mechanics
Construction Shelf
Width, overall 18.3” / 465 mm
Depth, overall 14.3” / 365 mm
Height, overall 6.9” / 176 mm
Weight, system (empty) 8.9 lb / 4 kg
Weight, converter 6.67 lb / 3 kg per converter

Environment
Operating temperature - 5 ... + 50 °C
Relative humidity 95 % max, non condensing
Altitude - 500 ~ 10000 feet

Leaflet_dd55_1300w_6_kda06 / rev. 1.0/13.10.2003 / JHsieh


Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314; http://www.deltaww.com
Back to
Subindex

The power advantage ...


Inverter FI 48 / 230 V - 1000 VA

Features
• High efficiency (88 %)
• Compact (153 VA/l) and light (6 kg)
• All connectors on front panel
• Fan cooled with air flow monitoring
• Universal input for 48 V and 60 V systems
• Overload capability and protections
• Wide cosϕ range
• Outstanding dynamic performance
• Parallel operation up to 15 inverter modules
• Operating temperature range up to 60°C

Applications
• Indoor and outdoor
• Small to medium AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom

Description
The inverter FI 48 / 230 V - 1000 VA is a single phase, fan-cooled inverter. It converts all direct
voltages from 48 and 60 V battery systems to an uninterruptible, stabilised AC voltage of 230 V / 50
Hz. The outstanding dynamic performance matches the supply requirements for state-of-the-art
telecom equipment. This performance as well as the advanced technology are the key factors of
the success of this inverter and it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup and static switch products.
The typical applications for this inverter are both in indoor and outdoor environments, which is a
perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The inverter meets the requirements set by the telecommunications standards.

leaflet_inv_1kva_en.doc / rev. 1.3 / 30. 07. 2003 / mb


Back to
Subindex

FI 48 / 230 V – 1000 VA: Technical specifications

General User interface


Efficiency, typ 88 % Output power display LED bar
Losses, max. 120 W Status indication LED «ok»
Safety EN 60 950, class I LED «system config»
EMI, radiated EN 55 022, class B Status «redundancy»
Compliant with EN 300 386-2
Cooling Fan cooled Power system controller
Power density 153 VA / l PSC 1000 Inverter fail alarm

Input Mechanics
Voltage range 40 ... 72 Vdc Width, overall 70 mm
Current maximum (60s) 26 Adc Depth, overall 350 mm
Current maximum (3s) 47 Adc Height, body 266 mm
EMI, conducted EN 55 022, class B Height, front panel 311 mm
Input connector D SUB, front side Weight 6 kg
Input protection External protection 32 A
Input switch None Environment
Ambient temperature 0 ... + 60 °C
Output Red. peak current limit + 50 ... + 60 °C
Voltage, nominal 230 Vrms ± 1% (1/2 load) Relative humidity 95 % max, non cond.
Frequency, nominal 50 Hz ± 0.05 Hz
THD, linear load < 1% Accessories
Voltage error, static ± 2.5 % INVBUSD P/N: D0005980
Current, nominal 4.4 Arms
Peak current limit 12.2 Apeak Static switch products
Crest factor, maximum 2.8 SSW 230 V – 6 kVA P/N: D0006119
Power, nominal 1000 VA / 800 W SSW 230 V – 20 kVA P/N: D0100400
Power, maximum (60s) 1100 VA / 880 W
Power, maximum (3s) 2000 VA / 1600 W
cos ϕ, range 0 .. 1 ind. and cap.
EMI, conducted EN 55 022, class B
Output connector 3 pole (L+N+PE), front
Output protection Internal fuse 6.3 A (L)
Internal relay (L+N)
Output characteristic:
Pout

1600 W

880 W
800 W

3s 60 s

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

The power advantage ...


Inverter FI 48 / 230 V - 3000 VA

Features
• High efficiency (88 %)
• Compact (238 VA/l) and light (12 kg)
• All connectors on front panel
• Fan cooled with air flow monitoring
• Universal input for 48 V and 60 V systems
• Overload capability and protections
• Wide cosϕ range
• Outstanding dynamic performance
• Parallel operation up to 15 inverter modules
• Operating temperature range up to 55°C

Applications
• Indoor and outdoor
• Medium to large AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom

Description
The inverter FI 48 / 230 V - 3000 VA is a single phase, fan-cooled inverter. It converts all direct
voltages from 48 and 60 V battery systems to an uninterruptible, stabilised AC voltage of 230 V / 50
Hz. The outstanding dynamic performance matches the supply requirements for state-of-the-art
telecom equipment. This performance as well as the advanced technology are the key factors of
the success of this inverter and it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup and static switch products.
The typical applications for this inverter are both in indoor and outdoor environments, which is a
perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The inverter meets the requirements set by the telecommunications standards.

leaflet_inv_3kva_en.doc / rev. 1.3 / 30. 07. 2003 / mb


Back to
Subindex

FI 48 / 230 V – 3000 VA: Technical specifications

General User interface


Efficiency, typ 88 % Output power display LED bar
Losses, max. 360 W Status indication LED «ok»
Safety EN 60 950, class I LED «system config»
EMI, radiated EN 55 022, class B Status «redundancy»
Compliant with EN 300 386-2
Cooling Fan cooled Power system controller
Power density 238 VA / l Alarm signals Inverter fail alarm

Input Mechanics
Voltage range 40 ... 72 Vdc Width, overall 135 mm
Current maximum (60s) 78 Adc Depth, overall 385 mm
Current maximum (3s) 125 Adc Height, body 266 mm
EMI, conducted EN 55 022, class B Height, front panel 311 mm
Input connector D SUB, front side Weight 12 kg
Input protection Ext. fuse / MCB 80 A
Input switch None Environment
Ambient temperature 0 ... + 55 °C
Output Red. peak current limit + 50 ... + 55 °C
Voltage, nominal 230 Vrms ± 1% (1/2 load) Relative humidity 95 % max, non cond.
Frequency, nominal 50 Hz ± 0.05 Hz
THD, linear load < 1% Accessories
Voltage error, static ± 2.5 % INVBUSD P/N: D0005980
Current, nominal 13.3 Arms
Peak current limit 36.6 Apeak Static switch products
Crest factor, maximum 2.8 SSW 230 V – 6 kVA P/N: D0006119
Power, nominal 3000 VA / 2400 W SSW 230 V – 20 kVA P/N: D0100400
Power, maximum (60s) 3300 VA / 2640 W
Power, maximum (3s) 6000 VA / 4800 W
cos ϕ, range 0 .. 1 ind. and cap.
EMI, conducted EN 55 022, class B
Output connector 3 pole (L+N+PE), front
Output protection Internal fuses 20 A (L+N)
Internal relay (L only)
Output characteristic:
Pout

4800 W

2640 W
2400 W

3s 60 s

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

The ESI series ...


Inverter ESI 48 / 230 V - 1000 VA
ESI 48 / 230 V - 2000 VA

Features
• Standard 19”, 23”and 25” rack
• 1 kVA/800 W, 2 kVA/1600 W
• Selectable 208/220/230/240 V system output
• High efficiency
• Pure sine wave output
• Compact, lightweight modular design
• Bypass function
• RS-232 communication
• User friendly LED and LCD display

Applications
• Indoor and outdoor
• Telecom, wireless, datacom

Description
The inverter ESI 48 / 230 V inverters are single phase, fan-cooled inverters. They convert all direct voltages from 48
V battery systems to an uninterruptible, stabilized AC voltage. The outstanding dynamic performance matches the
supply requirements for state-of-the-art telecom equipment. This performance as well as the advanced technology
is the key factors of the success of this inverter and it offers a cost effective and reliable solution.

The typical applications for this inverter are both in indoor and outdoor environments, which is a perfect solution for
wireless base stations, core network components, telecommunications networks and data networks.

Leaflet_esi48_230_1000_2000va/rev. 1.0/01.10.2003/LChen
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314;http://www.deltaww.com
Back to
Subindex

ESI 48 / 230 V - 1k & 2k VA: Technical specifications


General
Efficiency, at 230Vrms 85 % User Interface
Safety UL 60950 Status display LCD display
EN 60950 Status indication LED «Inverter ON»
CAN/CSA-C22.2 No. 60950 LED «Overload»
EMI, radiated FCC Part 15, class A LED «DC abnormal»
Compliant with EN 55022, class A LED «Fault»
Cooling Fan cooled Communication RS 232
Acoustic noise 55 dB(A) Dry contact
On/Off Switch Yes
MTBF 450K Hours Mechanics
Width, overall 17.3” / 440 mm
DC Input Depth, overall 11.8” / 300 mm
Input voltage 40 … 60 Vdc Height, overall 3.5” / 88.0 mm
Rated current 25 A (1k VA) / 50 A (2k VA) Weight 17.6 lb / 8.0 kg (1k VA)
Inrush current 180 A 18.7 lb / 8.5 kg (2k VA)
EMI, conducted EN 55022, class A
Input protection Fuse and DC breaker Environment
Operating temperature 0 ... + 45 °C
AC Input( Bypass) Relative humidity 20 ~ 90 %, non condensing
Input voltage 208 / 220 / 230 / 240 Vrms ± Altitude - 500 ~ 10000 feet
20 Vrms
Frequency 50 / 60 Hz ± 5 Hz *Specifications are subject to change due to technical progress
EMI, conducted EN 55022, class A
Mains connector Rear side
Input protection AC circuit breaker
Connection Terminal block (3 P)

Output
Output voltage 208 / 220 / 230 / 240 Vrms
Voltage regulation <±2%
Frequency 50 / 60 Hz ± 0.2 Hz
THD 3 %: 100% linear load
5 %: 100% SPS load
Current, nominal 5 Arms (1k VA)
10 Arms (2k VA)
Crest factor 3:1
Power, nominal 1000 VA / 800 W
2000 VA / 1600 W
Receptacles IEC-320 x 4
Overload protection:
Pout [VA]
1500
1490
1250

1000

t [s]
1 30 180

Leaflet_esi48_230_1000_2000va/rev. 1.0/01.10.2003/LChen
Delta Electronics, Inc. Tel:+886-3-4526107; Fax:+886-3-4527314;http://www.deltaww.com
Back to
Subindex

The power advantage ...


Static switch SSW 230 V - 6 kVA

Features
• 230 Vrms / 50 Hz / 6000 VA single phase
• ON LINE or OFF LINE mode selection
• High performance AC line quality monitoring
• Quick detection of AC faults
• Configurable switching criteria
• Load transfer of up to 6 kVA
• Synchronisation of the Delta inverter group
• Convection cooled
• Compact and light
• Power connectors on the rear

Applications
• Indoor and outdoor container
• Small to medium AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom

Description
The static switch SSW 230 V - 6 KVA is a microcontroller driven state of the art switch between the AC
mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a
mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A
communication and synchronisation bus is responsible for the system performance and the Delta
inverters are synchronised to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE mode can be realised in combination with
Delta inverters and DC power systems with battery backup.
The typical applications for this static switch are both in indoor and outdoor containers, which is a
perfect solution for UPS, wireless base stations, core network components, telecommunications
networks and data networks.
The static switch meets the requirements set by the telecommunications standards.
Product versions:
Static switch SSW 230 V - 20 kVA

leaflet_ssw_230v_6kva_en.doc / rev. 1.1 / 30. 07. 2003 / mb


Back to
Subindex

SSW 230 V - 6 kVA: Technical specifications

General Load transfer


Losses, max. 40 W Detection time 1.3 ms
Safety EN 60 950, class I Transfer time ≤ 10 ms
EMI, radiated EN 55 022, class B (depending on load type)
Compliant with EN 300 386-2
Cooling Convection cooled User interface
Indication LEDs: «ok»
Public AC input «Inverter supply»
Voltage range 184 – 276 Vrms «On line mode»
Frequency range 45 - 55 Hz «Off line mode»
EMI, conducted EN 55 022, class B «Load on inverter»
Input connector Rear side «Load on public»
Input protection External fuse 35 A «Overload»
i2t ≤ 9000 A2s
Switches: Line mode selection
Inverter on - off
Inverter AC input Switching criteria
Voltage range 230 Vrms ± 1%
Frequency 50 Hz
Controller, system bus
EMI, conducted EN 55 022, class B PSC 1000 Static switch fail alarm
Input connector Rear side Inverter system bus Synchronization and
Input protection None communication
AC output Mechanics
Voltage, nominal 230 Vrms Width, overall 70 mm
Frequency, nominal 50 Hz Depth, overall 350 mm
Maximum power 6000 VA Height, body 266 mm
cos ϕ, range 0 .. 1 ind. and cap. Height, front panel 311 mm
EMI, conducted EN 55 022, class B Weight 3.5 kg
Output connector Rear side
Output protection None
Environment
Ambient temperature 0 ... + 50 °C
Switching criteria Relative humidity 95 % max, non cond.
According to ETS 300 132-1
Static rms deviation ± 10 %
Accessories
Dynamic rms deviation ± 15 % for max. 500 ms
INVBUSD P/N: D0005980
Instantaneous values
deviation ± (20 % + 90 V)
Static freq. deviation ± 2Hz Inverter products
Dynamic freq. deviation ± 2Hz for 5 s maximum FI 48 / 230 V - 1000VA P/N: D0006203
Switching criteria Configurable by switch FI 48 / 230 V - 3000VA P/N: D0100555
Static rms deviation ± 12%, ± 15%, ±20%
Dynamic rms deviation ± 17%, ± 20%, ±25%

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

The power advantage ...


Static switch SSW 230 V - 20 kVA

Features
• 230 Vrms / 50 Hz / 20 kVA single phase
• ON LINE or OFF LINE mode selection
• High performance AC line quality monitoring
• Quick detection of AC faults
• Configurable switching criteria
• Load transfer of up to 20 kVA
• Synchronisation of the Delta inverter group
• Convection cooled
• Compact and light
• Power connectors on the rear

Applications
• Indoor and outdoor container
• Medium to large AC power systems
• Modular UPS configurations
• Telecom, wireless, datacom

Description
Static switch SSW 230 V - 20 kVA is a microcontroller driven state of the art switch between the AC
mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a
mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A
communication and synchronisation bus is responsible for the system performance and the Delta
inverters are synchronised to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE mode can be realised in combination with
Delta inverters and DC power systems with battery backup.
The typical applications for this static switch are both in indoor and outdoor containers, which is a
perfect solution for UPS, wireless base stations, core network components, telecommunications
networks and data networks.
The static switch meets the requirements set by the telecommunications standards.
Product versions:
Static switch SSW 230 V - 6 kVA

leaflet_ssw_230v_20kva_en.doc / rev. 1.1 / 30. 07. 2003 / mb


Back to
Subindex

SSW 230 V - 20 kVA: Technical specifications

General Load transfer


Losses, max. 120 W Detection time 1.3 ms
Safety EN 60 950, class I Transfer time ≤ 10 ms
EMI, radiated EN 55 022, class B (depending on load type)
Compliant with EN 300 386-2
Cooling Convection cooled User interface
Indication LEDs: «ok»
Public AC input «Inverter supply»
Voltage range 184 – 276 Vrms «On line mode»
Frequency range 45 - 55 Hz «Off line mode»
EMI, conducted EN 55 022, class B «Load on inverter»
Input connector Rear side «Load on public»
Input protection External fuse 100 A «Overload»
i2t ≤ 50000 A2s
Switches: Line mode selection
Inverter on - off
Inverter AC input Switching criteria
Voltage range 230 Vrms ± 1%
Frequency 50 Hz
Controller, system bus
EMI, conducted EN 55 022, class B PSC 1000 Static switch fail alarm
Input connector Rear side Inverter system bus Synchronization and
Input protection None communication
AC output Mechanics
Voltage, nominal 230 Vrms Width, overall 135 mm
Frequency, nominal 50 Hz Depth, overall 350 mm
Maximum power 20000 VA Height, body 266 mm
cos ϕ, range 0 .. 1 ind. and cap. Height, front panel 311 mm
EMI, conducted EN 55 022, class B Weight 8.6 kg
Output connector Rear side
Output protection None
Environment
Ambient temperature 0 ... + 50 °C
Switching criteria Relative humidity 95 % max, non cond.
According to ETS 300 132-1
Static rms deviation ± 10 %
Accessories
Dynamic rms deviation ± 15 % for max. 500 ms
INVBUSD P/N: D0005980
Instantaneous values
deviation ± (20 % + 90 V)
Static freq. deviation ± 2Hz Inverter products
Dynamic freq. deviation ± 3 Hz for 5 s maximum FI 48 / 230 V - 1000VA P/N: D0006203
Switching criteria Configurable by switch FI 48 / 230 V - 3000VA P/N: D0100555
Static rms deviation ± 12%, ± 15%, ±20%
Dynamic rms deviation ± 17%, ± 20%, ±25%

Subject to change due to technical progress

Delta Energy Systems (Switzerland) AG Telephone: +41 31 998 53 11 www.deltaenergysystems.com


Freiburgstrasse 251 Telefax: +41 31 998 53 53
CH-3018 Bern - Bümpliz
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 230/1000-1 19''

Features
• Complete 1 kVA power supply system
• Fan cooled inverter FI 48 / 230 V – 1000 VA
• Sinusoidal output voltage with low THD
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 130 x 485 x 395 mm
(19'', 3 U)

Applications
• Stand alone inverter system
• Indoor and outdoor container
• Telecom, wireless, datacom

Description
The AMS 230/1000-1 19’’ is a single phase, fan-cooled, stand alone inverter system. The stable
construction is based on a sheet metal design with one FI 48 / 230 V – 1000 VA inverter and DC-
and AC-distribution and provides an easy installation into 19‘‘ standard cabinets. The outstanding
dynamic performance matches the supply requirements for state-of-the-art telecom equipment. This
feature, as well as the advanced technology, are the key factors of the success of this inverter
system and it offers a cost effective and reliable solution.

The typical applications for this inverter system are both in indoor and outdoor containers, which is
a perfect solution for wireless base stations, core network components, telecommunications
networks and data networks. The inverter system meets the requirements set by the
telecommunications standards.

leaflet_ams_230_1000_1_19''_en.doc / rev. 2.3 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems

AMS 230/1000-1 19'': Technical specifications


General Mechanics
Efficiency ≥ 88% Material EN 10142 DX51D +
Losses, max. 120 W Z275MAC
Safety IEC/EN 60 950 Height, overall 130 mm (3U)
EMC EN 300 386-2 Width, overall 485 mm (19'')
Cooling Fan cooled inverter Depth, overall 395 mm
Weight, system 10 kg
DC Input Weight, inverter 6 kg
Voltage, nominal 53.5 VDC
Voltage range 40 ... 72 VDC Environment
Maximum current (60s) 26 ADC Ambient temperature 0 ... + 60 °C
Maximum current (3s) 47 Apeak Red. peak current limit + 50 ... + 60 °C
Connection plus pole Terminal 35 mm2 Relative humidity 95 % max, non cond.
Connection minus pole Terminal 35 mm2 Protection class IP 20
Fuse 32 A (MCB)
User interface
Output Signalling LED
Voltage, nominal 230 Vrms ± 1 % See inverter leaflet FI 48 / 230 V – 1000 VA
Frequency, nominal 50 Hz ± 0.05 Hz
Current, nominal 4.4 Arms
Current, peak limit 12.2 A
Crest factor 2.8
Power, nominal 1000 VA / 800 W
Power, maximum (60s) 1100 VA / 880 W
Power, maximum (3s) 2000 VA / 1600 W
Power factor 0 .. 1 ind. and cap.
THD, at linear load <1%

Load distribution
Residual current
circuit breaker 2 x 16 A/ 30 mA
Service socket 1 (L + N + PE)
Connections 2.5 mm2 (L + N + PE)

Subject to change due to technical progress

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 230/1000-3 19''

Features
• Complete 3 kVA power supply system
with static switch
• Manual bypass switch
• Sinusoidal output voltage with low THD
• Fan cooled inverters FI 48 / 230 V – 1000 VA
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 311 x 483 x 430 mm
(19'', 7 U)

Applications
• Modular UPS configurations
• Indoor and outdoor container
• Telecom, wireless, datacom

Description
The AMS 230/1000-3 19’’ is a single phase, fan-cooled inverter system with an integrated static
switch. The stable construction is based on a sheet metal design with a maximum of 3 parallel
connected FI 48 / 230 V – 1000 VA inverters, a static switch and DC- and AC-distribution and
provides an easy installation into 19‘‘ standard cabinets or to a wall. The outstanding dynamic
performance matches the supply requirements for state-of-the-art telecom equipment. This feature,
as well as the advanced technology, are the key factors of the success of this inverter system and
it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup.
The typical applications for this inverter system are both in indoor and outdoor containers, which is
a perfect solution for wireless base stations, core network components, telecommunications
networks and data networks.
The inverter system meets the requirements set by the telecommunications standards.

leaflet_ams_230_1000_3_19''_en.doc / rev. 2.4 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems
AMS 230/1000-3 19'': Technical specifications
General Configuration
Efficiency ≥ 88% Operating mode On line mode
Losses, max. 400 W Off line mode
Safety IEC/EN 60 950
EMC EN 300 386-2 Load distribution
Cooling Fan cooled inverter Manual bypass 7 position switch
Convection cooled SSW MCB (DPN) 3 pcs / 1 ... 16 A
Connections 2.5 mm2 (L + N + PE)
DC Input
Voltage, nominal 53.5 VDC Mechanics
Voltage range 40 ... 72 VDC Material EN 10142 DX51D +
Maximum current (60s) 3 x 26 ADC Z275MAC
Maximum current (3s) 3 x 47 Apeak Height, overall 311 mm (7U)
Connection plus pole Terminal 35 mm2 Width, overall 483 mm (19'')
Connection minus pole Terminal 35 mm2 Depth, overall 430 mm
Fuse 3 x 32 A (MCB) Weight, system 19 kg
Weight, inverter 3 x 6 kg
AC Input Weight, static switch 3.5 kg
Voltage, nominal 230 Vrms
Frequency, nominal 50 Hz Environment
Power, maximum (60s) 3300 VA Ambient temperature 0 ... + 60 °C
Power, maximum (3s) 6000 VA Red. peak current limit + 50 ... + 60 °C
Connections L + N + PE Relative humidity 95 % max, non cond.
Fuse 16 A (MCB) Protection class IP 20

Output, on line mode User interface


Voltage, nominal 230 Vrms ± 1 % Signalling LED
Frequency, nominal 50 Hz ± 0.05 Hz See inverter leaflet FI 48 / 230 V – 1000 VA
Current, nominal 13.2 Arms See static switch leaflet SSW 230 V – 6 kVA
Current, peak limit 36.6 A
Crest factor 2.8 Control and monitoring
Power, nominal 3000 VA / 2400 W Remote alarm Potential free contact
With redundancy 2000 VA / 1600 W
Power, maximum (60s) 3300 VA / 2640 W
Power, maximum (3s) 6000 VA / 4800 W Subject to change due to technical progress
Power factor 0 .. 1 ind. and cap.
THD, at linear load <1%

Output, off line mode


Voltage range ETS 300 132-1
Frequency range ETS 300 132-1
See static switch leaflet SSW 230 V – 6 kVA

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 230/1000-6 GFE

Features
• Complete 6 kVA power supply system
with static switch
• Manual bypass switch
• Sinusoidal output voltage with low THD
• Fan cooled inverters FI 48 / 230 V – 1000 VA
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 680 x 600 x 480 mm

Applications
• Modular UPS configurations
• indoor and outdoor container
• Telecom, wireless, datacom

Description
The AMS 230/1000-6 GFE is a single phase, fan-cooled inverter system with an integrated static
switch. The stable construction is based on a sheet metal design. The system can be mounted on
top of the battery cabinet or to the wall.
The outstanding dynamic performance matches the supply requirements for state-of-the-art telecom
equipment. This feature, as well as the advanced technology, are the key factors of the success of
this inverter system and it offers a cost effective and reliable solution.
Modular UPS configurations can be realised in combination with Delta DC power systems with
battery backup.
The typical applications for this inverter system are in indoor environment, which is a perfect
solution for wireless base stations, core network components, telecommunications networks and
data networks.
The inverter system meets the requirements set by the telecommunications standards.

leaflet_ams_230_1000_6_gfe_en.doc / rev. 2.3 / 17.02.2004 / MHa


Back to
Subindex

Energy Systems
AMS 230/1000-6 GFE: Technical specifications
General Output, off line mode
Efficiency ≥ 88% Voltage range ETS 300 132-1
Losses, max. 760 W Frequency range ETS 300 132-1
Safety IEC/EN 60 950 See static switch leaflet SSW 230 V – 6 kVA
EMC EN 300 386-2
Cooling Fan cooled inverter Configuration
Convection cooled SSW Operating mode On line mode
Off line mode
DC Input
Voltage, nominal 53.5 VDC Load distribution
Voltage range 40 ... 72 VDC Manual bypass 7 position switch
Maximum current (60s) 6 x 26 ADC MCB 20 pcs / 1 ... 63 A
Maximum current (3s) 6 x 47 Apeak Connections 2.5 mm2 (L + N + PE)
Connection plus pole Terminal 1 x 70 mm2 /
6x16 mm2 Mechanics
Connection minus pole Terminal 70 mm2 / Material EN 10142 DX51D +
6x16 mm2 Z275MAC
Fuse 6 x 32 A (MCB) Height, overall 680 mm
Width, overall 600 mm
AC Input Depth, overall 480 mm
Voltage, nominal 230 Vrms Weight, system 40 kg
Frequency, nominal 50 Hz Weight, inverter 6 x 6 kg
Power, maximum (60s) 6600 VA Weight, static switch 3.5 kg
Power, maximum (3s) 8000 VA
Connections L + N + PE Environment
Fuse 35 A Ambient temperature 0 ... + 60 °C
Red. peak current limit + 50 ... + 60 °C
Output, on line mode Relative humidity 95 % max, non cond.
Voltage, nominal 230 Vrms ± 1 % Protection class IP 20
Frequency, nominal 50 Hz ± 0.05 Hz
Current, nominal 26.4 Arms User interface
Current, peak limit 73.2 A Signalling LED
Crest factor 2.8 See inverter leaflet FI 48 / 230 V – 1000 VA
Power, nominal 6000 VA / 4800 W See static switch leaflet SSW 230 V – 6 kVA
With redundancy 5000 VA / 4000 W
Power, maximum (60s) 6600 VA / 5280 W Control and monitoring
Power, maximum (3s) 8000 VA / 6400 W Remote alarm Potential free contact
Power factor 0 .. 1 ind. and cap.
THD, at linear load <1%

Subject to change due to technical progress

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 230/3000-7 ETS
Features
• Complete 20 kVA power supply system
with static switch
• Manual bypass switch
• Sinusoidal output voltage with low THD
• Fan cooled inverters FI 48 / 230 V – 3000 VA
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 2200 x 600 x 600 mm

Applications
• Modular UPS configurations
• indoor and outdoor container
• Telecom, wireless, datacom

The AMS 230/3000-7 ETS is a single phase, fan-cooled


inverter system with an integrated static switch. The
stable construction is based on a frame cabinet design.
The outstanding dynamic performance matches the
supply requirements for state-of-the-art telecom
equipment. This feature, as well as the advanced
technology, are the key factors of the success of this
inverter system and it offers a cost effective and reliable
solution.
Modular UPS configurations can be realised in
combination with Delta DC power systems with battery
backup.
The typical applications for this inverter system are in
indoor container, which is a perfect solution for wireless
base stations, core network components,
telecommunications networks and data networks.
The inverter system meets the requirements set by the
telecommunications standards.

lf_ams230-3000-7-ets_en.doc / rev. 2.5 / 07.05.2004 / MHa


Back to
Subindex

Energy Systems
AMS 230/3000-7 ETS: Technical specifications
General Configuration
Efficiency ≥ 88% Operating mode On line mode
Losses, max. 2640 W Off line mode
Safety IEC/EN 60 950
EMC EN 300 386-2 Load distribution
Cooling Fan cooled inverter Manual bypass 7 position switch
Convection cooled SSW MCB 18 pcs / 2 ... 6 A
Connections 2.5 mm2 (L + N + PE)
DC Input
Voltage, nominal 53.5 VDC Mechanics
Voltage range 40 ... 72 VDC Material EN 10142 DX51D +
Maximum current (60s) 7 x 78 ADC Z275MAC
Maximum current (3s) 7 x 125 Apeak Height, overall 2200 mm
Connection plus pole Terminal 7 x 35 mm2 Width, overall 600 mm
Connection minus pole Terminal 7 x 35 mm2 Depth, overall 600 mm
Fuse 7 x 100 A (MCB) Weight, system 150 kg
Weight, inverter 7 x 12 kg
AC Input Weight, static switch 8.6 kg
Voltage, nominal 230 Vrms
Frequency, nominal 50 Hz Environment
Power, maximum (60s) 22000 VA Ambient temperature 0 ... + 55 °C
Power, maximum (3s) 40000 VA Red. peak current limit + 50 ... + 55 °C
Connections L + N + PE Relative humidity 95 % max, non cond.
Fuse 100 A (MCB) Protection class IP 20

Output, on line mode User interface


Voltage, nominal 230 Vrms ± 1 % Signalling LED
Frequency, nominal 50 Hz ± 0.05 Hz See inverter leaflet FI 48 / 230 V – 3000 VA
Current, nominal 91.7 Arms See static switch leaflet SSW 230 V – 20 kVA
Current, peak limit 256.2 A
Crest factor 2.8 Control and monitoring
Power, nominal 20000 VA / 16000 W Remote alarm Potential free contact
With redundancy 18000 VA / 14400 W
Power, maximum (60s) 22000 VA / 18480 W
Power, maximum (3s) 40000 VA / 33600 W
Subject to change due to technical progress
Power factor 0 ...1 ind. and cap.
THD, at linear load <1%

Output, off line mode


Voltage range ETS 300 132-1
Frequency range ETS 300 132-1
See leaflet static switch SSW 230 V – 20 kVA

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com
Back to
Subindex

Energy Systems

The power advantage...


Power System AMS 230/3000-15 ETS
Features
• Complete 45 kVA power supply system
• Sinusoidal output voltage with low THD
• Fan cooled inverters FI 48 / 230 V – 3000 VA
• Efficiency > 88 %
• Integrated AC load distribution
• Dimensions (h x w x d) 2200 x 600 x 600 mm

Applications
• Large inverter system
• Indoor and outdoor container
• Telecom, wireless, datacom

Description
The AMS 230/3000-15 ETS is a single phase, fan-
cooled inverter system. The stable construction is based
on a frame cabinet design. The outstanding dynamic
performance matches the supply requirements for state-
of-the-art telecom equipment. This feature, as well as
the advanced technology, are the key factors of the
success of this inverter system and it offers a cost
effective and reliable solution.
The typical applications for this inverter system are in
indoor container, which is a perfect solution for wireless
base stations, core network components,
telecommunications networks and data networks.
The inverter system meets the requirements set by the
telecommunications standards.

lf_ams230-3000-15-ets_en.doc / rev. 2.4 / 07.05.2004 / MHa


Back to
Subindex

Energy Systems

AMS 230/3000-15 ETS: Technical specifications


General Load distribution
Efficiency ≥ 88% MCB 18 pcs / 1 ... 63 A
Losses, max. 5400 W Connections 16 mm2 (L + N + PE)
Safety IEC/EN 60 950
EMC EN 300 386-2 Mechanics
Cooling Fan cooled inverter Material EN 10142 DX51D +
Z275MAC
DC Input Height, overall 2200 mm
Voltage, nominal 53.5 VDC Width, overall 600 mm
Voltage range 40 ... 72 VDC Depth, overall 600 mm
Maximum current (60s) 15 x 78 ADC Weight, system 150 kg
Maximum current (3s) 15 x 125 Apeak Weight, inverter 15 x 12 kg
Connection plus pole Terminal 15 x 35 mm2
Connection minus pole Terminal 15 x 35 mm2 Environment
Fuse 15 x 100 A (MCB) Ambient temperature 0 ... + 55 °C
Red. peak current limit + 50 ... + 55 °C
Output Relative humidity 95 % max, non cond.
Voltage, nominal 230 Vrms ± 1 % Protection class IP 20
Frequency, nominal 50 Hz ± 0.05 Hz
Current, nominal 196.5 Arms User interface
Current, peak limit 549 A Signalling LED
Crest factor 2.8 See inverter leaflet FI 48 / 230 V – 3000 VA
Power, nominal 45000 VA / 36000 W
With redundancy 42000 VA / 33600 W Control and monitoring
Power, maximum (60s) 49500 VA / 39600 W Remote alarm Potential free contact
Power, maximum (3s) 90000 VA / 72000 W
Power factor 0 ... 1 ind. and cap.
THD, at linear load <1% Subject to change due to technical progress

Delta Energy Systems (Finland) Oy Telephone: +358 9 849 660


Juvan teollisuuskatu 15, P.O. Box 63 Telefax: +358 9 8496 6100
FIN-02921 Espoo, Finland www.deltaenergysystems.com

You might also like