Professional Documents
Culture Documents
CRSI Manual To Design RC Diaphragms - Part28
CRSI Manual To Design RC Diaphragms - Part28
Therefore,
The in-plane wind forces are greater than the general structural integrity lateral forces. Because both types of forces
have a load factor equal to 1.0 (see the applicable load combinations in ASCE/SEI 2.3.1 and 2.6.1), the diaphragm is
designed for wind forces.
Wall stiffness calculations are given in Table 10.2 assuming that the walls are fixed at the top and pinned at the
bottom and are subjected to unit horizontal forces. The modulus of elasticity of the concrete, , is carried as a
constant through the calculations because it is the same for all walls.
Wall
(in.4) (in.2)
1 26,193,420 2,720 0.074 0.199 13.51 5.03 3.67
2 26,193,420 2,720 0.074 0.199 13.51 5.03 3.67
3 202,309,632 5,376 0.010 0.100 100.00 10.00 9.09
4 4,430,064 1,504 0.439 0.359 2.28 2.79 1.25
5 53,747,712 3,456 0.036 0.156 27.78 6.41 5.20
6 152,813,952 4,896 0.013 0.110 76.92 9.09 8.13
The location of the CR is determined by Equations (6.1) and (6.2) of this publication where the origin is taken at the
intersection of column lines A and 1:
10-7
Design Guide for Reinforced Concrete Diaphragms
The wind forces in each of the walls are determined using Equations (6.5) and (6.6) where
and .
Force calculations for the walls for wind in the south and west directions are given in Tables 10.3 and 10.4, respec-
tively, where it is assumed that the applied in-plane wind forces of 6.10 kips and 6.70 kips are negative in those
directions. The forces in these tables are in the directions that resist the applied in-plane forces and torsional
moments where positive forces act in the north and east directions. Sample calculations for Wall 2 for wind in the
south direction are given below.
Table 10.3 Wind Forces in the Walls for Wind in the South Direction
Term 1 Term 2
Wall
(ft) (ft) (ft) (ft) (kips)
(kips) (kips)
1 0.0 — 3.67 — 31.2 — 3,569 — 1.36 0.24 1.60
2 15.0 — 3.67 — 16.2 — 963 — 1.36 0.12 1.48
3 50.3 — 9.09 — 19.1 — 3,324 — 3.38 –0.36 3.02
4 — 27.7 — 1.25 — 5.6 — 39 — 0.02 0.02
5 — 55.3 — 5.20 — 33.2 — 5,738 — 0.36 0.36
6 — 0.0 — 8.13 — 22.1 — 3,971 — –0.38 –0.38
S 16.43 14.58 7,856** 9,748** 6.10 0.00 6.10
* For walls, 4, 5, and 6, replace with in this equation.
**
Table 10.4 Wind Forces in the Walls for Wind in the West Direction
Term 1 Term 2
Wall
(ft) (ft) (ft) (ft) (kips)
kips kips
1 0.0 — 3.67 — 31.2 — 3,569 — — (0.24) 0.24
2 15.0 — 3.67 — 16.2 — 963 — — 0.13 0.13
3 50.3 — 9.09 — 19.1 — 3,324 — — –0.37 –0.37
4 — 27.7 — 1.25 — 5.6 — 39 0.58 0.02 0.60
5 — 55.3 — 5.20 — 33.2 — 5,738 2.39 0.36 2.75
6 — 0.0 — 8.13 — 22.1 — 3,971 3.73 –0.38 3.35
S 16.43 14.58 7,856** 9,748** 6.70 0.00 6.70
* For walls, 1, 2, and 3, replace with in this equation.
**
10-8
Design Guide for Reinforced Concrete Diaphragms
Term 1 force:
(the resisting force in this wall due to direct shear force acts in
the north direction, which is positive)
Term 2 force:
Total force,
Depicted in Figures 10.2 and 10.3 are the Term 1 and Term 2 forces in each of the walls for wind in the south and
west directions, respectively. For wind forces in the north and east directions, the forces in the walls are in the op-
posite directions to those shown in the figure.
(c) D
etermine the equivalent in-plane distributed loads on the diaphragm and construct the corresponding shear and
moment diagrams.
The equivalent in-plane distributed loads for wind in the south and west directions are determined using the infor-
mation in Section 6.4.3 of this publication. The distributed loads are trapezoidal, which accounts for the eccentrici-
ties between the points of wind load application and the CR (see Figures 10.4 and 10.5 for wind in the south and
west directions, respectively).
6.1 kips
25� -2″
0.36 kips
0.12 kips
1.36 kips
②
0.36 kips
3.38 kips
④ N
𝑒𝑒� � 6.0�
③
0.02 kips
CR
0.24 kips
1.36 kips
𝑦𝑦�� � 22.1�
Term 1 force
①
Term 2 force
0.38 kips
⑥
𝑥𝑥�� � 31.2�
Figure 10.2 Force allocation to the walls for wind in the south direction.
10-9
Design Guide for Reinforced Concrete Diaphragms
⑤
2.39 kips
0.36 kips
0.13 kips
②
0.37 kips
𝑒𝑒� � 5.6�
④ ③ N
6.7 kips
0.58 kips
0.02 kips
CR
0.24 kips
𝑦𝑦�� � 22.1�
27� -8″
Term 1 force
①
Term 2 force
0.38 kips
3.73 kips
⑥
𝑥𝑥�� � 31.2�
Figure 10.3 Force allocation to the walls for wind in the west direction.
Therefore, and .
Therefore, and .
10-10