Professional Documents
Culture Documents
Differential Protection: City of Umhlathuze 24 - 27 October 2017
Differential Protection: City of Umhlathuze 24 - 27 October 2017
Differential Protection: City of Umhlathuze 24 - 27 October 2017
City of uMhlathuze
24 – 27 October 2017
DIFFERENTIAL PROTECTION
• Differential protection is a form of Unit Protection,
which is protection that is restricted or confined to a
defined physical area determined by the CT locations.
• As the name implies, the protection operates as a
result of a DIFFERENCE between quantities or
compared to what went in to an area versus what
came out of the area.
• It is practical implementation of Kirchhoffs Current Law
which considers the sum of current into a node.
• A fault inside the defined area will cause the protection
to operate and isolate the fault, while a fault just
outside of this area will not result in any protection
operation and the fault will not be isolated.
• Differential protection can be used on Overhead Lines,
Cables, Transformers, Motors, Bus Bars, Reactors
Generators or any other piece of equipment.
• This protection has the distinct advantage in that it can
be set very fast with no intentional time delays thereby
limiting any damage which is especially important for
areas with high fault levels and currents (remembering
that thermal damage is directly proportional to the
square of the current i.e. I2).
• Differential protection has evolved over the years from
an analogue balanced voltage and current scheme to
the current systems that make use of digital
communication over fiber optic.
• The analogue differential protection using copper pilot
wires has steadily declined in application with most
applications these days being digital numerical systems
over fibre optic.
Advantages of Differential Protection
• Improve protection co-ordination in large
interconnected networks where there is not enough
grading margin between different circuits or current in-
feeds are problematic.
• Protection of short lines and cables where impedance is
too small to provide enough current discrimination
between different points.
• Improved fault resistance coverage.
• Protection of lines with in-zone equipment installed (eg.
transformers).
• Three (multi) terminal applications.
• Applications with series connected capacitors.
• Protection where tripping times are critical and needs
to be fast.
Circulating Current Scheme
• The circulating current scheme is based upon the
principle established by Merz and Price (Charles
Hestermann Merz and Bernhard Price) and used as
early as 1906 – 1907, with South Africa having one of
the first schemes in 1911.
• The circulating current principle involves the currents
being placed such that currents circulate between the
CTs with the relay being placed across the electrical
mid-point of the secondary circuit.
• Out of Zone faults results in no current flowing through
the relay and the protection is therefore stable with no
operation.
Out of zone fault
𝑉𝑟𝑒𝑠𝑢𝑙𝑡𝑎𝑛𝑡 = 𝑉𝐴 − 𝑉𝐵 = 0
• For a fault internal to the protected zone the CT
secondary voltages at either end of the zone is
equal but opposite in polarity (i.e. VA = -VB). The
resultant voltage is then:
𝑉𝑟𝑒𝑠𝑢𝑙𝑡𝑎𝑛𝑡 = 𝑉𝐴 − −𝑉𝐵 = 𝑉𝐴 + 𝑉𝐵
• This voltage difference then drives current
between the 2 points and the relay can operate.
• For a through fault no current flows in the CT
secondary and it is then effectively open circuited.
• The scheme design is modified in order to prevent CT
saturation.
• This is achieved through the use of a transactor which
is the summation transformer that has distributed air
gaps in the core and a few primary turns with a high
number of secondary turns.
• The primary currents then results in a secondary
voltage being produced which is required in the
balanced voltage scheme.
Translay H04 relay
𝑅𝑝𝑖𝑙𝑜𝑡 𝑅𝑝𝑖𝑙𝑜𝑡
2𝑅𝑝𝑎𝑑 + + = 1000 𝛺
2 2
1000 − 𝑅𝑝𝑖𝑙𝑜𝑡
∴ 𝑅𝑝𝑎𝑑 = 𝛺
2
Pilot Wire Capacitance
• We had previously described the capacitance present in
the primary circuit, but there is also a capacitance in the
secondary system between the pilot-wires themselves.
• For a circulating current system the pilot-wire capacitance
appears in parallel with the relay operating coil. At the
electrical midpoint of the pilot-wire circuit, there is a zero
voltage and consequently zero voltage across the
capacitance.
• The capacitive reactance for a capacitor is:
1
𝑋𝑐 = 𝛺
2𝜋𝑓𝐶
C-N z
A-B x
B-C y
C-A x+y
A-B-C √(y2 + y + x)
• From this we can see that the relay is not as sensitive for
phase-phase faults as what it is for phase-ground faults.
• This is not too much of a concern as there is usually lots of
current for phase-phase faults as it is only the inherent line
impedance that limits current and this is designed to be as
low as possible to keep losses low.
Capacitive Line Charging Currents
• Cables and Overhead Lines have an inherent capacitance,
with the capacitance values for lines generally being low
and for cables they are substantially higher.
• Due to this capacitance, a charging current flows in the
primary system which is then seen at one end of a line /
cable but not at the other end.
• As an example the charging current for a 132kV Overhead
Line is approximately 0.3 A/km while for a 132kV cable it is
in the region of 9 A/km.
• Since the charging current is seen at one end of the line
and not at the other, differential protection would need to
be set not to operate for these measured differences.
• This capacitive charging current can be determined from
the equation:
2𝜋𝑓𝐶𝑈
𝐼𝑐ℎ𝑎𝑟𝑔𝑖𝑛𝑔 = 𝐴/𝑘𝑚
√3 ∙ 106
• From the Metrosil equation it can be seen that Vpeak and Ipeak are given
parameters and only C and β can be chosen or specified.
• To limit the leakage current through the unit the value for C needs to
be specified such that the current is within an acceptable level which
for a 1A CT is in the region of 30mA.
• The Metrosil equation can be re-written for the AC
waveforms as:
𝑰𝑹𝑴𝑺 𝜷
𝟐 ∙ 𝑽𝒔𝒆𝒕𝒕𝒊𝒏𝒈 = 𝑪 ∙
𝟎.𝟓𝟐
• To minimize the spill current for load, heavy through fault
currents and transient conditions, the CTs need to be
matched with identical magnetization characteristics.
• A mismatch in the CT magnetization curves results in a
false differential current being measured by the High
Impedance Differential relay.
• Many incorrect relay trips are as a result of this mismatch
of CTs.
• From the analysis and equivalent circuits above, we have
seen that there are a number of shunt impedances in
parallel with the stabilizing and high impedance relay eg.
magnetizing branch for each CT and Metrosils connected to
limit voltage levels.
• Each of these devices results in current having to flow in
these parallel paths and this current is then not available to
be used to operate the differential relay or it can be said
that the effective primary current is then the sum of all of
these currents.
• The effective primary setting is then:
𝐼𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 = 𝐶𝑇𝑅 ∙ (𝐼𝑟𝑒𝑙𝑎𝑦 + 𝐼𝑚𝑒𝑡𝑟𝑜𝑠𝑖𝑙 + 𝑛 ∙ 𝐼𝑚 )
Where n = number of CTs connected in parallel
Im = CT magnetizing current
Imetrosil = metrosil current
Irelay = relay branch current
Low Impedance Differential
𝐼1 − 𝐼2
∴𝐾=
𝐼1 + 𝐼2
2
• We can plot this characteristic with (I1 – I2) on
the vertical axis and (|I1| + |I2|)/2) on the
horizontal axis for different values: