System Checksums: Packaged Terminal Air Conditioner Sub C Heating Coil Peak CLG Space Peak Cooling Coil Peak Temperatures

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

System Checksums

By Trane
SUB C Packaged Terminal Air Conditioner

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: Sum of Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 37 / 29 / 23 OADB: Peaks OADB: 21 SADB 12.8 20.0
Ra Plenum 35.0 20.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 34.2 20.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 35.7 20.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.4 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 6.49 0.00 6.49 2.11 6.14 4.34 Roof Cond 0.58 0.58 12.01
Glass Solar 0.82 0.00 0.82 0.27 0.82 0.58 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.13 0.00 0.13 0.04 0.11 0.08 Glass/Door Cond 0.08 0.08 1.66
Cooling Heating
Wall Cond 14.89 0.00 14.89 4.84 17.87 12.63 Wall Cond 2.00 2.00 41.41
Diffuser 5,950 5,950
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00
Floor -7.56 -7.56 -2.46 -8 -5.55 Floor 4.50 4.50 93.17 Terminal 5,950 5,950
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 5,950 5,950
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 14.77 0.00 14.77 4.80 17.09 12.08 Sub Total ==> 7.16 7.16 148.24 Nom Vent 3,471 0
AHU Vent 3,471 0
Internal Loads Internal Loads Infil 0 0
Lights 14.88 0.00 14.88 4.83 14.88 10.52 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.00 0 0 0.00 0.00 0.00 People 0.00 0 0.00 Return 5,950 5,950
Misc 88.16 0.00 88.16 28.63 88.16 62.30 Misc 0.00 0.00 0.00 Exhaust 3,471 0
Sub Total ==> 103.04 0.00 103.04 33.46 103.04 72.81 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.00 0.00 0.00 0.00 0.00 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 164.33 53.37 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 21.38 21.38 6.94 21.38 15.11 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 38.83 803.93
Sup. Fan Heat 4.39 1.43 RA Preheat Diff. -41.16 -852.17 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 58.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 Lps/m² 4.00 4.00
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 16.95
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.24
W/m² 235.67 0.00
Grand Total ==> 139.19 0.00 307.91 100.00 141.51 100.00 Grand Total ==> 7.16 4.83 100.00 No. People 0

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 350.90 180.64 5,950 36.3 25.9 16.8 12.2 11.0 7.6 Floor 1,488 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 1,488
Total 350.90 Roof 1,488 0 0 Humidif 0.0 0 0.0 0.0
Wall 829 4 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 51 0 0 Total 0.0

Project Name: Long Son MEPF TRACE® 700 v6.2.5 calculated at 08:33 AM on 09/04/2020
Dataset Name: Long Son-Check Emergency.trc Alternative - 2 System Checksums Report Page 4 of 6

PDF created with pdfFactory Pro trial version www.pdffactory.com


System Checksums
By Trane
SUB E Packaged Terminal Air Conditioner

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 4 / 15 Mo/Hr: Sum of Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 37 / 29 / 23 OADB: Peaks OADB: 21 SADB 12.8 20.0
Ra Plenum 35.0 20.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 34.3 20.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 36.1 20.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.4 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 8.20 0.00 8.20 2.26 7.51 4.38 Roof Cond 0.72 0.72 12.57
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.13 0.00 0.13 0.04 0.13 0.08 Glass/Door Cond 0.08 0.08 1.40
Cooling Heating
Wall Cond 17.55 0.00 17.55 4.84 22.51 13.14 Wall Cond 2.58 2.58 45.03
Diffuser 7,158 7,158
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00
Floor -9.50 -9.50 -2.62 -10 -5.84 Floor 5.57 5.57 97.21 Terminal 7,158 7,158
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 7,158 7,158
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 16.38 0.00 16.38 4.52 20.14 11.76 Sub Total ==> 8.95 8.95 156.20 Nom Vent 4,113 0
AHU Vent 4,113 0
Internal Loads Internal Loads Infil 0 0
Lights 18.45 0.00 18.45 5.09 18.45 10.77 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.00 0 0 0.00 0.00 0.00 People 0.00 0 0.00 Return 7,158 7,158
Misc 107.24 0.00 107.24 29.56 107.24 62.61 Misc 0.00 0.00 0.00 Exhaust 4,113 0
Sub Total ==> 125.69 0.00 125.69 34.65 125.69 73.38 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.00 0.00 0.00 0.00 0.00 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 189.93 52.36 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 25.46 25.46 7.02 25.46 14.86 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 42.99 750.26
Sup. Fan Heat 5.29 1.46 RA Preheat Diff. -46.21 -806.46 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 57.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 Lps/m² 3.88 3.88
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 17.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.46
W/m² 223.93 0.00
Grand Total ==> 167.53 0.00 362.75 100.00 171.29 100.00 Grand Total ==> 8.95 5.73 100.00 No. People 0

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 413.34 215.64 7,158 36.9 26.1 16.8 12.8 11.7 8.1 Floor 1,845 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 1,845
Total 413.34 Roof 1,864 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,066 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 71 0 0 Total 0.0

Project Name: Long Son MEPF TRACE® 700 v6.2.5 calculated at 08:33 AM on 09/04/2020
Dataset Name: Long Son-Check Emergency.trc Alternative - 2 System Checksums Report Page 5 of 6

PDF created with pdfFactory Pro trial version www.pdffactory.com


System Checksums
By Trane
SUB F Packaged Terminal Air Conditioner

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 4 / 15 Mo/Hr: Sum of Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 37 / 29 / 23 OADB: Peaks OADB: 21 SADB 12.8 20.0
Ra Plenum 35.0 20.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 34.4 20.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 35.7 20.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.4 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 1.18 0.00 1.18 1.82 0.98 2.79 Roof Cond 0.10 0.10 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 0.09 0.05 0.14 Glass/Door Cond 0.03 0.03 0.00
Cooling Heating
Wall Cond 6.90 0.00 6.90 10.62 8.29 23.60 Wall Cond 0.83 0.83 0.00
Diffuser 1,472 1,472
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00
Floor -1.20 -1.20 -1.85 -1 -4.21 Floor 0.80 0.80 0.00 Terminal 1,472 1,472
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 1,472 1,472
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.94 0.00 6.94 10.68 7.84 22.32 Sub Total ==> 1.76 1.76 0.00 Nom Vent 632 0
AHU Vent 632 0
Internal Loads Internal Loads Infil 0 0
Lights 2.65 0.00 2.65 4.08 2.65 7.55 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.00 0 0 0.00 0.00 0.00 People 0.00 0 0.00 Return 1,472 1,472
Misc 21.80 0.00 21.80 33.56 21.80 62.07 Misc 0.00 0.00 0.00 Exhaust 632 0
Sub Total ==> 24.45 0.00 24.45 37.64 24.45 69.62 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.00 0.00 0.00 0.00 0.00 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 29.65 45.64 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 2.83 2.83 4.36 2.83 8.06 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 7.07 0.00
Sup. Fan Heat 1.09 1.68 RA Preheat Diff. -7.96 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 42.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 Lps/m² 5.55 5.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 19.81
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.57
W/m² 280.04 0.00
Grand Total ==> 34.22 0.00 64.96 100.00 35.12 100.00 Grand Total ==> 1.76 0.87 100.00 No. People 0

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 74.28 43.66 1,472 36.1 24.5 14.5 12.2 11.4 8.0 Floor 265 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 265
Total 74.28 Roof 265 0 0 Humidif 0.0 0 0.0 0.0
Wall 351 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 31 0 0 Total 0.0

Project Name: Long Son MEPF TRACE® 700 v6.2.5 calculated at 08:33 AM on 09/04/2020
Dataset Name: Long Son-Check Emergency.trc Alternative - 2 System Checksums Report Page 6 of 6

PDF created with pdfFactory Pro trial version www.pdffactory.com