Excitation Systems, DMPC-PE, Rudolf Moeckli / 7 January 2016

UNITROL® 1010, UNITROL® 1020


Benchmark digital voltage regulators
for brushless generators & motors
© ABB Group
April 13, 2018 | Slide 1
Doc no. 3BHS666181 E01 Rev. C
ABB Global Product Line Excitation Systems
Products, systems and applications

Industries
Power; Chemical, Oil Power; Marine; Power; Chemical, Oil Power Marine
& Gas; Pulp & Paper; & Gas; Minerals &
Traction; Wind
Sugar Mining; Metals

Power Applications
xx Power xx
§ Generator synchronization § Synchronous generators § Synchronous generators § Gas turbine starter § Onboard DC-grid systems
§ Paralleling of lines and motors and motors § Generator excitation
§ Rotating compensators and § Synchronous compensators
converters

SYNCHROTACT® UNITROL® 1000 UNITROL® 6000 MEGATROL UNIREC

© ABB Group
April 13, 2018 | Slide 2

§ SYNCHROTACT 5 § UNITROL 1005 (AVR) § UNITROL 6000 Light § MEGATROL Light § UNIREC Basic
§ UNITROL 6000 Medium
§ SYNCHROTACT CSS § UNITROL 1010 (AVR) § MEGATROL Medium § UNIREC GENREC
§ UNITROL 6000 Power
§ SYNCHROTACT MSP § UNITROL 1020 (AVR) § MEGATROL Power § UNIREC EXC
§ UNITROL 6000 X-power
§ UNITROL 6000 Nuclear

§© ABB Group
§April 13, 2018 | Slide 2
UNITROL 1000 family
Applications

Power Marine

Wind Traction

© ABB Group
April 13, 2018 | Slide 3
UNITROL 1000 history and references
Main customer

§ Engine manufacturer (power plant / marines)


è UNITROL 1000 used as standard
§ ABB Marines
§ Wärtsilä (Diesel)
§ Siemens (Gas Turbine)
§ Rolls Royce (Diesel)
§ GE Jenbacher
§ Generator manufacturer
§ ABB Machines
§ Cummins AVK
§ Leroy Somer
§ Retrofit / engineered projects
© ABB Group
April 13, 2018 | Slide 4
UNITROL 1000 history and references
Diesel applications, land based power plants
Diesel engines up
to 15 MW Benefits and used functions
§ Reactive load sharing via RS485
§ Paralleling up to 31 machines for reactive
load sharing
§ Power plant up to 400 MW
§ Synchronization

CMT1000
§ Very fast
Synchroscope
§ Self synchronization after start up
§ PSS
§ IEEE compliant PSS
§ Certified by 3rd parties companies for
§ Russian / USA

© ABB Group
April 13, 2018 | Slide 5
UNITROL 1000 history and references
Diesel applications, Marines
Diesel engines up
to 15 MW Benefits and used functions
§ Reactive load sharing via RS485 (VDC)
§ Support for ring bus structure
§ Accurate load sharing over time and
temperature range
§ Synchronization

CMT1000
§ Very fast
Synchroscope
§ Self synchronization after start up
§ Enhanced monitoring functions
§ Event and data logging
§ GL / DNV class approval

© ABB Group
April 13, 2018 | Slide 6
UNITROL 1000 history and references
Gas turbine applications
Gas turbine up to
50 MW Benefits and used functions
§ Dual channel systems
§ Increased availability
§ Various monitoring functions like PT/CT
failures

§ Temperature influence limiters


CMT1000 dual
§ Adjusted Limits according measured
channel cooling media temperature
configuration

§ Remote Control (Modbus)


§ Extend digital IO over fieldbus

© ABB Group
April 13, 2018 | Slide 7
ABB Global Product Line Excitation Systems
Most common types today

Field circuit supply:


- PMG
- shunt transformer
- auxiliary power

AVR

AVR

SM E SM

Rotating exciter: 1 – 400 A Static excitation: 100 – 12,000 A


+ brushless (mostly) + fast response
- slow response for transients - brushes

© ABB Group
April 13, 2018 | Slide 8
UNITROL 1000 family
Automatic voltage regulator (AVR)

System duties
§ Supply variable DC current to the field
winding of exciter machine
§ Control of generator terminal voltage
with specified accuracy
§ Keep machine within permissible
operating range
§ Ensure a stable operation with other
E AVR machines and network
§ Contribute to transient stability at a
grid fault by field forcing
§ Communicate with the power plant
control

© ABB Group
April 13, 2018 | Slide 9
UNITROL 1000 portfolio in 2016
Device overview

UNITROL 1005

UNITROL 1010
UNITROL 1020

© ABB Group
April 13, 2018 | Slide 10
UNITROL 1000 portfolio 2016
Hardware overview
*) at 70°C ambient
temperature
8A at 55°C
UNITROL UNITROL UNITROL
**) Ie > 15 A requires
1005 1010 1020
external capacitor
Excitation current 5 A cont. * 10 A cont. 20 A cont. **
at 55 °C 10 A ceiling 20 A ceiling 38 A ceiling

Separate terminals for


NO YES YES
aux power supply

HMI NO NO YES
4 digital outputs 8 digital I/Os 8 digital I/Os
8 digital input 4 digital input 4 digital input
I/Os 2 analog inputs 3 analog inputs 3 analog inputs
2 analog outputs 2 analog outputs

USB USB USB


Ethernet RS485 RS485
Interfaces Ethernet Ethernet
(CAN) (CAN)

IP20 IP20 IP20


Mechanicals Suitable for machine Suitable for machine Suitable for machine
mounting mounting mounting

CE, (DNV/GL), CE, cUL, DNV, GL, CE, cUL, DNV, GL,
Certificates (cUL), Traction CCS, Traction CCS, Traction
© ABB Group
April 13, 2018 | Slide 11
UNITROL 1000 portfolio 2016
Software overview

UNITROL UNITROL UNITROL


Software functions 1005 1010 1020

AVR/FCR/PF/VAR
Limiters
Protection / Monitoring

ECO
Soft start
LIGHT Voltage matching

LIGHT

LIGHT
History logger
Modbus TCP
Rotating diode monitoring

BASIC

BASIC
Reactive load sharing via RS485
BASIC
Dual channel
Auto-synchronization (SYNC)

FULL + PSS
Event logger

FULL
FULL Data logger
Real-time clock
Time synchronization by SNTP

Option Power System Stabilizer (PSS)

© ABB Group
April 13, 2018 | Slide 12
Technical data UNITROL 1010 /20
Device overview

§ Robust mechanical design


§ Spring tension terminals for power and
measurement
§ Plug-in type terminal blocks for digital and
analog I/O’s
§ Status information by 3 LED’s
§ Equipped with industrial USB
§ Ethernet, CAN and RS485 ports
§ Human Machine Interface, HMI
(model UNITROL 1020)

© ABB Group
April 13, 2018 | Slide 13
Technical data UNITROL 1010 /20
Connection overview

External capacitor if
Ie > 15 A

© ABB Group
April 13, 2018 | Slide 14
Technical data UNITROL 1010 /20
Technical data

§ Control supply voltage rage


9 – 300 VAC 3-phase (min. to max. )
16 – 300 VAC 1-phase (min. to max. )
18 – 420 VDC (min. to max. )
è Nominal voltage must not exceed 250 VAC
§ Power electronics supply 0 – 300 VAC or 0 – 420 VDC
è Nominal voltage must not exceed 250 VAC m
è Max filed forcing voltage 350Vdc (depending on input voltage)
§ Excitation output 20 ADC cont. 38 ADC 10 sec
è Excitation current above 15 A requires external capacitor
§ 3-phase or single phase stator voltage measurement up 500 VAC
è earthed at secondary side of PT
§ Single phase current measurement (1 to 5 A)
§ Single phase measurement of line voltage for synchronization
up 500 VAC
§ Measurement accuracy 0.1%
§ Control accuracy typically < 0.5% (depending on Vp)
§ AVR response time < 20 ms with 3 phase measurement
< 50 ms with 1 phase measurement

© ABB Group
April 13, 2018 | Slide 15
Supply modes
®
UNITROL 1000, most
flexible AVR

© ABB Group
April 13, 2018 | Slide 16
Supply modes
Permanent Magnet Generator (PMG)

AVR

UNITROL 1000

AVR System

PMG SM E

§ 3 phase PMG è Most save supply mode for extended operational life
time
§ Easy to simulate
© ABB Group
April 13, 2018 | Slide 17
Supply modes
Auxiliary winding

AVR

UNITROL 1000

AVR System

SM E

§ Attention must be paid to none sinusoidal voltage


è Peak level must never exceed 420Vp
§ Difficult to simulate, voltage dependent on machine load
© ABB Group
April 13, 2018 | Slide 18
Supply modes
Axillary power, e.g. UPS

DC AC

AVR

UNITROL 1000

SM E

§ Attention must be paid to max inrush current


è Max 200A for 10ms, limit current by resistor
§ Easy to simulate
© ABB Group
April 13, 2018 | Slide 19
Supply modes
Shunt supplied

AVR

UNITROL 1000

SM E

§ No support for short circuit at grid connection point


§ Easy to simulate

© ABB Group
April 13, 2018 | Slide 20
Supply modes
Shunt supplied with DC or AC boost at AVR input

AVR

Station
battery UNITROL 1000
Voltage
relay

SM E

§ Attention must be paid to max inrush current


è Max 200A for 10ms, limit current by resistor
© ABB Group
April 13, 2018 | Slide 21
§ Easy to simulate
Supply modes
Shunt with AC boosting for field forcing

AVR
Boost for short
circuit support

UNITROL 1000

boost

SM E

§ Machine short circuit capability defined by CT’s

© ABB Group
§ Difficult to engineer and simulate
April 13, 2018 | Slide 22
Supply modes
Calculating kceiling for UNITROL 1000
3 phase PMG Internal DC voltage:
UPMG= (UDC + 8) /1.35 UDC = Ue max.
UPMG= 127 VAC = kceiling * Ue no load
AVR
= 10 * 16.4 V = 164 VDC

UNITROL 1000

AVR System

PMG SM E

Excitation voltage:
Ue no load = 16.4 V
kceiling = Ue max. / Ue no load

© ABB Group
kceiling= 5…10… 15
April 13, 2018 | Slide 23
SW Functions
®
UNITROL 1000 provides
widest range of integrated
SW functions

© ABB Group
April 13, 2018 | Slide 24
Software functions
ECO package (1/4)

§ Start up functions
§ Soft start
§ Field flashing off / voltage relay function
§ Fast line voltage matching
§ Regulator modes
§ Voltage control mode with PID control algorithm
§ Power factor controller with PID control algorithm
§ Reactive power (VAR) controller with PID control
algorithm
§ Super imposed PF/VAR controller
§ Excitation current controller (manual control) with PID
control algorithm

© ABB Group
April 13, 2018 | Slide 25
Software functions
ECO package (2/4)

§ Limiters
§ V/Hz limiter
§ Minimum excitation current limiter
§ Underexcited reactive current limiter as a function of
active power (P/Q)
§ Three step delayed maximum excitation current limiter,
generator cooling media temperature depending
§ Stator current limiter, generator cooling media
temperature dependent
§ Machine voltage min. / max. limiters
(Only used in PF/VAR mode)
Power chart

© ABB Group
April 13, 2018 | Slide 26
Power chart with operational limits

max. field current


limiter
P

min. field current


limiter

underexcitation
P,Q limiter

max. stator
current limiter

-Q 1/Xd +Q
UNITROL 1020 will keep
operation point inside
permissible range
© ABB Group
April 13, 2018 | Slide 27
UNITROL 1000 family
Power Chart and operational limits
Under-excited Over-excited
(leading) +P (lagging) Limiter:
1 Rotor current limiter
Stability limit Driving limit P/Q limiter

Generator Minimum field current limiter

Stator current limiter

§IGn The excitation system keeps the


generator within thermal and stability
limits
§j
§d Protection:
-Q -1 1 1 +Q Excitation over current
xd

UNITROL 1020 will keep


Motor
operation point inside
permissible range
-1
1 p.u. = nominal
-P
© ABB Group
April 13, 2018 | Slide 28
Software functions
ECO package (3/4)

§ Monitoring / protection functions


§ Device supervision functions grouped to 2 supervision
alarm signals /1 trip output
§ Watchdog / communication / PT / CT
§ PWM (excessive excitation / loss of excitation)
§ DSP temperature / control supply voltage / digital
output
§ External monitoring functions grouped to 3 monitor
alarm signals
§ Rotating diode monitoring RDM
§ Generator voltage (min. / max.)
§ Excitation current (max.)

© ABB Group
April 13, 2018 | Slide 29
Software functions
ECO package (4/4)

§ Network short circuit support functions


§ Boost function
§ Fault ride-through (FRT) detection
§ Voltage SP reduction at load application
§ High Initial Response controller to improve performance
with high ceiling factor
§ AVR Gain dependency on frequency and power input
to improve stability over wide range of operations
conditions
§ Commissioning
§ Open loop control of output voltage for test purposes
§ Built-in step test function for regulator tuning, together
with CMT1000
© ABB Group
April 13, 2018 | Slide 30
Software functions
LIGHT package (includes all function of ECO)

§ History Logger
§ Records last 2 hour of operation for claim investigation
§ Modbus TCP (Ethernet) / RTU (RS485)
§ Access to all measurement status information and
parameters
§ Remote control, alternative for digital I/Os
§ Easy extension of I/Os
§ Rotating diode monitoring
§ Supervision of rotating diode on the exciter machine to
prevent damage on the machine

© ABB Group
April 13, 2018 | Slide 31
Software functions
BASIC package (1/2)

§ Voltage droop compensation (VDC) mode for island


operation è See more information
§ Reactive load sharing at constant bus bar voltage
§ Up to 31 machines
§ Support for 2 tie breaker or ring structure
§ Analog input from superimposed regulator to summing
point of voltage regulator

© ABB Group
April 13, 2018 | Slide 32
Voltage droop compensation (VDC)
VDC principles
Load A Load B

U = 100 %
RS-485

AVR 1 AVR 2 AVR 3 AVR 4


SM SM SM SM

§ Reactive load sharing at constant bus bar voltage


§ Fix to 100% in range of min. / max. VAR set point
§ Outside min. / max. VAR set point in static droop mode
§ Interaction between units based on digital serial bus
communication RS485
§ Up to 31 machines
§ Only for island operation
© ABB Group
April 13, 2018 | Slide 33
Voltage droop compensation (VDC)
VDC for bus bar with 2 tie breaker

§ Support for 4 Net ID’s


§ Status of generator breaker defines whether
AVR is joining load sharing
§ Tie breaker status is routed to every AVR to
define load sharing groups (Sec. Net 1 & 2
inputs)

© ABB Group
April 13, 2018 | Slide 34
Voltage droop compensation (VDC)
VDC for bus bar with 2 tie breaker

§ Baud rate 59.9 kBaud / 56.7 kBaud (standard baud rate à


standard repeater can be used)
§ Bus length
§ Mixed installations with UNITROL 1000-15 à 250m
§ Only UNITROL1020 à 500m
§ Max. devices on bus 31 machines

© ABB Group
April 13, 2018 | Slide 35
Voltage droop compensation (VDC)
VDC for ring structure

§ Based on segments, max 6 segments


§ Tie breaker status only wired inside segment
§ Status of local tie breaker is send over RS485 to
other AVR’s
§ Algorithm defines which AVR’s are on the same bus
§ Algorithm defines which AVR’s are on same bus
§ Define numbers of segments
§ Define in segment AVR is

© ABB Group
April 13, 2018 | Slide 36
Voltage droop compensation (VDC)
VDC for ring structure

§ Based on sections with 2 breakers


§ Sec.Net 1 & 2

© ABB Group
April 13, 2018 | Slide 37
Software functions
BASIC package (2/2)

§ Dual channel functions


§ Setpoint follow up of second channel over CAN
§ Blocking of channel switch over in case of redundant
channel failure
§ Configurable switch over logic
§ Internal trip logic and forcing logic
§ Configurable forcing excitation off (trip) or to Manual
mode depending on monitor status
§ Automatic synchronizing
§ Generating close command for GCB (breaker closing
time as parameter)
§ Analog output or higher / lower pulses to governor
§ Dead bus synchronizing
© ABB Group
April 13, 2018 | Slide 38
Software functions
FULL package (1/1)

§ Real time clock, time synchronizing over SNTP server


§ Event logging, up to 500 events
§ Time stamped with 1ms time resolution
§ Export to text file
§ Readout via Modbus
§ Data logger
§ Up to 10 data logs, each containing 12 signals with
2,000 samples (5 signals free configurable)
§ Sampling time between 10ms and 500ms
§ Configurable triggering (event)
§ Export to text file or as COMTRADE format
§ Read out via Modbus
© ABB Group
April 13, 2018 | Slide 39
Software functions
Options and further developments

§ Power system stabilizer (IEEE PSS2A/2B/2C, optional)


§ Injection points for frequency, active power and input of
lead lag filter
§ 2 configurable test points for CMT1000 and external
measurement devices
§ Configurable damping of engine firing frequncy to
reduce noise at AVR output
§ Future development (Rel 6.4 not yet scheduled)
§ Supprot for IEC61850
§ CAN 1939 fieldbus

© ABB Group
April 13, 2018 | Slide 40
Commissioning &
maintenance tool CMT100
Best of class operating tool

© ABB Group
April 13, 2018 | Slide 41
Commissioning & Maintenance Tool CMT1000
Benefits
User-friendly
tool for all
UNITROL 1000
products

§ Intuitive commissioning and maintenance tool


è Easy to learn how to operate
§ Build-in step and real time recording functions
è No additional measuring devices needed
§ Extended debug functions
è Fast commissioning and trouble shooting
è Enables precise and focused remote support
© ABB Group
April 13, 2018 | Slide 42
Commissioning & Maintenance Tool CMT1000
Quick start

§ Main Window
§ OFFLINE Not connected
§ MONITROR Read only
§ CONTROL Read / Write
§ EEPROM Green indicates
parameter saved into
Flash
§ Help è About CMT1000…
§ Revision of CMT
§ Serial number of device
§ Target SW release

© ABB Group
April 13, 2018 | Slide 43
Commissioning & Maintenance Tool CMT1000
Intuitive I/O setup windows

§ Digital I/O
§ Input / output
§ Select signal with drop down menu
§ Select polarity
§ Green LED è terminal voltage is high

§ Analog input
§ Select signal with drop down menu
§ Select scaling
§ Terminal voltage directly shown

© ABB Group
April 13, 2018 | Slide 44
Commissioning & Maintenance Tool CMT1000
Step function and real time recording

§ Step function
§ All regulator modes
§ Define step size
§ Down or up (10 sec)

§ Real time recording


§ Simultaneously 16 signals recorded
(50ms)
§ Additional status information like
modes, I/Os, limiters
§ Save waveform to PC

© ABB Group
April 13, 2018 | Slide 45
Commissioning & Maintenance Tool CMT1000
Required data for remote support

§ Single line diagram


§ Parameter file
§ Waveform file of oscilloscope

Analyzing of waveform files, CMT in offline


§ Load parameter file and open waveform file
§ All other CMT windows are following cursor A
§ Measuring window
§ PQ-diagram
§ Adjust setpoint window
§ I/O setup windows

© ABB Group
April 13, 2018 | Slide 46
Scope of supply
List of items coming with every unit on a CD - free

§ CMT1000
§ Easy to use commissioning tool

§ PID tuning tool


§ Calculation and verification of optimized PID
setting for stable and reliable operation

§ E-learning
§ Interactive learning of
§ Excitation basics
§ UNITROL 1010 / 1020 functions and features
§ Module interfaces

§ Manuals
§ Presently available in English, French, Spanish
and German

© ABB Group
April 13, 2018 | Slide 47
Components around the
AVR
Systems designed by ABB
is based on over 100 years
of experience

© ABB Group
April 13, 2018 | Slide 48
New Hardware Features
n Design based on UNITROL 1000-7
n Power input voltage to 300V ac max.
n Exciter current up to 20A (max. 40A)
n Remote access over integrated Ethernet controller
n USB for local connection of CMT (serial port removed)
n Power up via USB port in case of no power supply available (easy
parameters downloading for spare AVR’s)
n Removable local panel for accessing AVR settings &
measurements (stores also AVR settings)
n Additional 4 digital I/O’s
n Easy wiring due to removable connectors (spring loaded
terminals for control wires)
n Natural cooling with heat sink
n Max operating temp 70ºC
Compatible with
n Plastic housing, IP20 existing hardware
n UL / DNV certified UN1000-15
n Wärtsilä mounting plate design with UL-components è same
footprint with exisiting UNITROL 1000-15 plate

© ABB Group
April 13, 2018 | Slide 49
New SW Features

n MODBUS / TCP interface


n Up to 10 connections
n Up to 60 free configurable signals
n Event logger
n Storage of up to 500 events, 1 ms time resolution
n Data recorder for 12 signals
n Sample rate between 2 and 100 Samples/sec
n Recording time between 2 and 100 seconds
n Configurable Triggers
n Time synchronization with SNTP server
n USB interface, shows up on PC as standard COM port
n Prepared for integrated Web server
n Reactive load sharing with ring bus support

© ABB Group
April 13, 2018 | Slide 50
UNITROL 1020 Prototype

© ABB Group
April 13, 2018 | Slide 51
UNITROL 1020 Front Side

© ABB Group
April 13, 2018 | Slide 52
UNITROL 1020 Wärtsilä Plate

© ABB Group
April 13, 2018 | Slide 53
UNITROL 1020 Plate Circuit Diagram

© ABB Group
April 13, 2018 | Slide 54
Components around the AVR
UNITROL 1020, 1 channel system

© ABB Group
April 13, 2018 | Slide 55
Components around the AVR
UNITROL 1020, 2 channel system

© ABB Group
April 13, 2018 | Slide 56
Components around the AVR
UNITROL 1020, 2 channel system

© ABB Group
April 13, 2018 | Slide 57
Configuration
UNITROL 1020, 2 channel system

© ABB Group
April 13, 2018 | Slide 58
Configuration
UNITROL 1020, 2 channel system

© ABB Group
April 13, 2018 | Slide 59
Configuration
UNITROL 1020, 2 channel system
Main features:
automatic change over to Redundant-AVR, but
manual resetting back to Main.
Þ MAIN AVR must detect the failure and
activate transfer

Monitoring conditions for change-over to redundant:


Potential Transformer Monitor (wire break, MCB trip)
Current Transformer Monitor (wire break)
Loss of Excitation (PWM high, but field current is low)
Loss of Control (control transistor short-circuit)
Loss of Auxiliary Supply (DC-supply lost)

Design considerations:

Generator should be equipped with:


• Own CT secondary's for both AVR’s current measuring
• Own VT secondary's + MCB’s for both AVR’s voltage measuring MAIN-AVR: REDUNDANT-AVR:
[SOFTSTART] [SOFTSTART]
Starting Level=25.0% Starting Level=25.0%
Notice! Hold Time=1.0s Hold Time=2.0s
Master & Redundant AVR parameters are NOT identical! Ramp Time=5.0s Ramp Time=8.0s

[DIGITAL I/O 3] [DIGITAL I/O 3]


Input=Standby Input=None
Polarity=Inverted Polarity=Normal
Main differences are listed here Output=System_OK
Direction=Out
Output=None
Direction=Out

[DIGITAL INPUT 5] [DIGITAL INPUT 5]


Input=None Input=Standby
Polarity=Normal Polarity=Normal

© ABB Group
April 13, 2018 | Slide 60
Configuration
UNITROL 1020, 2 channel system VT’s

Generator measuring transformer configuration


for 2-channel AVR

Own secondary's for both


Voltage Transformers AVR’s

CT’s

Current Transformer, x/1A

© ABB Group
April 13, 2018 | Slide 61
Synchronizing Function

n Voltage matching
n Speed control, analogue bias signal
n Breaker close command
n Synchrocheck UNET UNITROL 1000
Setpoint fSP = fNom
Command
CB
Fbias Sync
Speed Controller
Setpoint
UM
Regulator

T SM E

© ABB Group
April 13, 2018 | Slide 62

You might also like