Model: P2500D5

Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model P2500D5
Power (kVA) 2250 2500
Engine brand Perkins
Power (kW) 1800 2000
Engine model 4016-61TRG3
Rated speed ( r.p.m) 1500
Speed control type Electronic
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage TBD
AU VE
RI
BURE

ISO 9001
TA S

BUREAU VERITAS
Certification
182 8
Frequency 50HZ
Engine speed (RPM) 1500
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 528
·2006/42/EC Machinery safety. Fuel
100% prime power 473
·2006/95/EC Low voltage Consumption
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 75% prime power 346
12601 : 2010 (L/H)
50% prime power 235
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
Standard reference Conditions
power sequence, which may be run for an unlimited number of hours per year, between
Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30%
stated maintenance intervals. The permissible average power output during at 24 hours
relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
period shall not exceed 80% of the prime power. 10% overload available for governing
conforming to BS 2869: 1998, Class A2
purposes only.

(2) ESP (Standby Power):


L L
According to ISO 8528-1, It is defined as the maximum power available, under the
agreed operating conditions, for which the generating set is capable of delivering for up
to 500 hours of operation per year (of which no more than 300 hours for continuative H
H
use) with the maintenance intervals and procedures being carried out as prescribed by W
W
the manufacturers. No overload capability is available.

Dimension and Weight


Dimension Open Silent
Powers ESP PRP Standby
Length (L) 6265mm 12192mm
Voltage (V) KVA KW KVA KW Amps
Width (W) 2240mm 2438mm
415/240 2500 2000 2250 1800 3478.1
Height (H) 3040mm 2896mm
400/230 2500 2000 2250 1800 3608.5 Net Weight 13700KG 20650KG
380/220 2500 2000 2250 1800 3798.5 Fuel Tank (L) - 2000
Note: This parameters allows for some acceptable deviations.

www.aggpower.co.uk
Engine Specification: 4016-61TRG3

Basic technical data Induction system

No. of cylinders 16 Clean filter 1.2kpa

Cylinder arrangement Vee 60° Dir ty filter 3.7kpa

Cycle 4 stroke Air filter type Donaldson

Induction system Turbocharged, air to water charge cooled

Compression ratio 13:1

Bore 160mm

Stroke 190mm Lubrication system


Displacement 61.1L TBD
Total lub capacity
All ratings cer tified to within TBD 157L
Sump minimum
Speed variation at constant load TBD Sump maximum 213L

Maximum engine operating angles

-front up, front down, right side TBD

Cooling system or left side

Total coolant capacity Lubricating oil pressure

-with radiator TBD -Relief valve opens TBD


-without radiator TBD - at maximum no-load speed TBD
Maximum top tank temp TBD Oil consumption at full load

Thermostat operation range 71-85℃ as a % of fuel consumption


TBD
Radiator face area TBD
Rows and material TBD
Pressure cap setting Electrical system
TBD
Fan diameter Type Insulated return
TBD
Drive ratio Alternator voltage 24 volts
TBD
Number of blades Alternator output 40 amps
TBD
Star ter motor voltage TBD

Star ter motor power 16.4 kW

Fuel system

Injection system Direct

Fuel injection pump General installation Prime power


Combined unit injector
Combustion air flow 160 m³/min
Fuel atomiser TBD
Exhaust gas temp 475℃
Nozzel opening pressure TBD
Exhaust gas flow, wet 490m³/ m i n
Fuel lift pump type Electronic
Engine coolant flow 23 I/s
- flow/hour TBD
Cooling fan air flow TBD
- pressure TBD

Maximum suction head:

-1500 rev/min TBD

www.aggpower.co.uk
Alternator Specification
Emergency voltage curve

Sudden increase warp


Alternator Sudden voltage warp Sudden decrease warp
520
Number of phase 3

Power factor (Cos Phi) 0.8 464

+1%
Poles 4 408 +1%
380
380
-1%
Winding Connections (standard) Star-serie 352

Terminals 12 296

Insulation type H class 240


0 1 2 3 4 5 6 7 8 9 10 11 12
δu%: -18.18 1.95s
Winding Pitch 2/3 δu%: 8.89
Benchmark phase: A
Benchmark phase: A
Min. voltage: 310.9V Recovery time:
Recovery time: 0..12ss
Max. voltage: 413.8V

IP rating IP23

Excitation system Self-excited

Bearing Single bearing Emergency frequency curve


Coating Vacuum impregnation Sudden increase warp
Sudden voltage warp Sudden decrease warp
70
Voltage regulator A.V.R

Couping Flexible disc 62

54 +1%
50
-1%
+1%
50
-1%
46

38

30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s

Options

Engine Alternator Generator Sets Fuel System

· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD

Canopy Lub oil system Cooling System Control Panel

· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay

www.aggpower.co.uk
Control Panel

Configuration Benefits

· Emergency stop button · Less wiring and components


· Integrated solution
· Protection MCB
· Less engineering and programming
· Battery charger · User friendly set-up and button layout
· Integrated aviation plug · Module can be configured to suit individual applications
· ATS connection · PC software for simplified configuration
· Digital control module · Wide range of communication capabilities

Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· Storage temp: -30 ˚C to + 80 ˚C
· Operating humidity: 95% w/o condensation
· Vibration: 5-25Hz, ±1.6 mm
5-1 00 Hz, a= 4g
· Shocks: a= 500m/s²

Options

· Ethernet interface (Remote monitoring and control)


· GSM modem/wireless internet (Remote monitoring and control)
· RS232-RS485 Dual por t interface
· Synchronizing control panel
· Distribution board with sockets kit and power busbar
· Battery trickle charge ammeter
· Ear th leakage protection
· Ear th fault protection
· Low fuel level alarm
· Low fuel level shutdown
· High fuel level alarm
· Fuel transfer system control
· Low coolant level shutdown
· High lube oil temp shutdown
· Overload via alarm switch on breaker
· Engine coolant heater controls
· Control panel heater
· S peed adjust switch
· Oil temp displayed on LCD screen
· Additional 8 inputs and outputs
Publication No. GYH0518N, ISSUE 1 @ AGG UK

AGG UK | AGG China | AGG USA | AGG UAE Distributed by

info@aggpower.co.uk | www.aggpower.co.uk

Follow us @facebook.com/aggpowergroup

Follow us @linkedin.com/company/agg-power

Follow us @ AGGPOWER

All information in the document is substantially correct a the time of printing


but may be subsequently altered by the company.

You might also like