PBAT-61 Cell Sensor: Installation & Operation Manual V1.0
PBAT-61 Cell Sensor: Installation & Operation Manual V1.0
V1.0
珠海横琴派诺技术有限公司
PILOT (HENGQIN) CO., LTD.
Danger and warning!
This device can be installed only by professionals.
The manufacturer shall not be held responsible for any accident caused by the
Before operating the device, isolate the voltage input and power supply and
Use appropriate voltage tester to make sure the voltage has been cut-off.
Put all mechanical parts, doors, or covers in their original positions before
Always supply the device with the correct working voltage during its operation.
injuries to people.
Contents
Chapter 1 Product Overview .................................................................................................... 1
1
Chapter 2 Installation and Wiring
2.1 Environment
2
Note: wire length 30cm
3
Positive power supply, connected directly with the
6 V+ Bat
battery positive pole.
b
7 COM1 DL-BUS communication,RJ11 interface
b
8 COM2 DL-BUS communication,RJ11 interface
Note:
a. The cell sensor uses four-line method to measure the internal
node.
4
2.2 Order Information
Model: PBAT61
measurement
Internal resistance
measurement
DL-BUS Communication
measurement
Internal resistance
measurement
DL-BUS Communication
measurement
Internal resistance
measurement on line
PBAT61-02-B For 2V battery
Negative pole temperature
measurement
DL-BUS Communication
Balancing function
5
Real-time cell voltage
measurement
Internal resistance
measurement on line
PBAT61-02-B For 12V battery
Negative pole temperature
measurement
DL-BUS Communication
Balancing function
6
2.3 Power Supply
2.4 Wiring
PBAT61 could be pasted on the battery surface, and connected with the
battery poles by the standard 6pin cable securely, and cascaded with another
sensor through RJ11.
7
Connect to Previous node
6 V+ Sense
5 V+ Bat COM1
4
3
PTC
PTC
PBAT61
2 V- Sense COM2
1 V- Bat
PBAT61 could measure the real-time voltage of VRLA battery cell. The
measuring range of PBAT61-2 is from DC 1.6~2.6V , and PBAT61-12 is form
DC 7.5~15.6V.
PBAT61 could measure the internal resistance of VRLA battery cell. The
measuring range of PBAT61 is from 0.1 to 100mΩ.
Note: The interval between two internal resistance measurements should
not be less than two minutes, otherwise the sensor will be damaged because of
overheat.
PBAT61 could measure the negative pole temperature of VRLA battery cell
with the range from -20°C~+85°C.
8
Chapter 4 Accessibility Features
4.1 Communication
4.2 Dormancy
If the communication bus is idle for more than 20 minutes, the sensor will go into
sleep mode, and could be woken up by the waking command sent from PBAT-Gate
Alarm OFF
Alarm Flash
9
Chapter 6 Maintenance and Trouble shooting
Problems Causes Solutions
10
Chapter 7 Technical Specifications
Dimension Main-body:65mm(L)×65mm(W)×28.8mm(H)
2V battery:1.6V~2.6V
Resolution:
Voltage ±0.2%
12V battery:7.5V~15.6V 0.001V
Consistency:
2V battery:0.1~100mΩ ±(1.5%+25μΩ) Resolution:
Resistance
12V battery:0.1~100mΩ Repeatability: 0.001mΩ
±(1.0%+25μΩ)
Dielectric
Test voltage AC 3750V, Test time 1minute, leakage current< 1mA
strength
Impulse
voltage
11
Item Reference Standard Class
Electrostatic GB/T17626.2-2006
IV
discharge immunity (IEC61000-4-2:2001)
GB/T17626.3-2006
RFEMS IV
(IEC61000-4-3:1998)
Electrical fast
GB/T17626.4-2008
transient burst III
(IEC61000-4-4:1998)
immunity
GB/T17626.5-2008
Surge Immunity III
(IEC61000-4-5:2005)
RF conducted GB/T17626.6-2008
III
immunity (IEC61000-4-6:1998)
Electromagnetic GB/T14598.16-2002
OK
emission limits (IEC60255-25:2000)
GB/T17626.12-1998
Sasser immunity III
(IEC61000-4-12:1995)
12
Notice:
PILOT reserves the right to modify this manual without prior notice in view of
continued improvement.