PROCEDURE

PERTAMINA
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev. 0

U2003-004-PYY-C07-NOO09 AWS D1.1 Page 1 of 41

PEMBERI KERJA :PT PERTAMINA (PERSERO) RU-VI BALONGAN

KONTRAKTOR : PT NINDYA KARYA (PERSERO)

NAMA PROYEK PEMBANGUNAN NEW cONSTRUCTION JETTY &TEMPORARY ACCESS ROAD


PROYEK REVITALISASI RCCRUVI- BALONGAN
LOKASI PT PERTAMINA (PERSERO) RU-VI BALONGAN, INDRAMAYU-JAWA BARAT
NO. KONTRAK SP-19168

19/05/2021 All Issued For Review DAM SS


Prepared Checked Approved Approved
Rev. Date Page Description
PT Nindya Karya |PT Pertamina
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-CO7-N0009 AWS D1.1 Page 2 of 41

REVISI TABULASI
REVISI LAMPIRAN KETERANGAN
HAL KETERANGAN HAL 0
PERTAMINA PROCEDURE
NINDYA
ULTRASONIC EXAMINATION Rev. 0
Nomor Dokumen
U2003-004-PYY-CO7-NO009 AWS D1.1 Page 3 of 41

LEMBAR RESPON

DOKUMEN REF.
No.
Dokumen/ Hal. Komen Inisial Respon Inisial Keterangan
Ref.
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-C07-NO009 AWS D1.1
Page 3 of 41
Daftar Isi Table of Content
Par.
|Uraian Par. Description Page
Tujuan Purpose
Ruang Lingkup 2 Scope
Persyaratan Keselamatan Safety Requirements
Documen Rcferensi Reference Documcnts
Definisi-Definisi Definitions
6 Kualifikasi dan Tanggung Jawab Qualification and Responsibility
7 Perlengkapan Tools, Gages, Fixtures
7.1 Alat alat Ultrasonic 7.1
7.1.1 UT instrument
Ultrasonic Equipments
7.1.2
7.1.1 The UT instrument
Syarat untuk pengujian Instrumen 7.1.2 Requirement for Test Instruments.
7.1.3 Kalibrasi dari Pengujian Instrumen. 7.1.3 Calibration of Test Instruments.
7.1.4 Linearitas Horizontal
7.1.4 Horizontal Linearit
7.2 Search Units. 7.2 Search Units.
7.2.2 Resolusi untuk Probe Normal. 7.2.2 Resolution for Straight-Beam.
7.2.3 Search Units Probe Sudut. | 7.2.3 Angle-Beam Search Units.
7.2.4 Frekuensi. 7.2.4 Frequency.
|7.2.5 Dimensi Transducer. 7.2.5 Transducer Dimensions.
7.2.6 Sudut. 7.2.6 Angles.
| 7.2.7 Resolusi untuk Probe Sudut. 7.2.7 Resolution for Angle-Beam.
7.2.8 Penandaan 7.2.8 Marking. 8
Jarak Ujung Probe
7.2.9 7.2.9 Edge Distance.
7.3 Standar Acuan 7.3 Reference Standards.
8 Procedure 8 Procedure 9
8.1 Prosedur Kalibrasi dan Kualifikasi | 8.1 Equipment Calibration and 9
Peralatan Qualification Procedure
8.1.1 Linearitas Horizontal. 8.1.1 Horizontal Linearity._
8.1.2 Gain Control (dB Accuracy ). 8.1.2 Gain Control (dB Accuracy ). 10
8.1.3 Rumus Decibel. 8.1.3 Decibel Equation. 12
8.1.4 Prosedure Refleksi Internal. 8.1.4 Internal Reflections Procedure 13
8.2 Kalibrasi dari Search Units. 8.2 Calibration of Search Units. 13
8.2.1 Kalibrasi dari Search Units probe | 8.2.1 Calibration of Angle-Beam Search 13
sudut. Units.
8.2.2 Titik Index. 8.2.2 Indexpoint. 13
8.2.3 Sudut 8.2.3 Angles. 14
8.2.4 Persyaratan untuk resolusi dari probe | 8.2.4 Angle Beam Resolution 14
sudut. Requirements.
8.2.5 Kalibrasi dari Search Units Probe 8.2.5 Calibration of Straight-Beam Search 15
Normal (Longitudinal Mode ). Units (Longitudinal Mode).
8.2.6 Persyaratan Resolusi Probe Normal 8.2.6 Straight-Beam Resolution 15
Requirement
8.2.7 Kualifikasi Lincaritas Horizontal. 8.2.7 Horizontal Linearity Qualification 15
8.2.8 Kualifikasi Gain Control|8.2.8 Gain Control (Atenuaion) 15
(Altenuation). Qualificaion.
8.3 Kalibrasi untuk Pengujian 8.3 Calibrationfor Testing 16
PROCEDURE
PERTAMINA
NINDYA
ULTRASONIC EXAMINATION Rev.
Nomor Dokumen 4 of 41
U2003-004-PYY-CO7-NOO09 AWS D1.1 Page

8.3.1 Posisi Kontrol Reject. 8.3.1 Position of Reject Control. 16

8.3.2 Reflcctor yang dilarang. 8.3.2 Prohibitcd Reflectors. 6


8.3.3 8.3.3 Technique. 16
Teknik. 16
8.3.4 Kalibrasi Ulang. 8.3.4 Recalibration.
8.4 Pengujian Probe Normal untuk Base | 8.4 Straight-Beam Testing of Base 16
Metal. Metal.
8.5 Kalibrasi untuk Pengujian Probe | 8.5 Calibration for Angle-Beam Testüng. 16
Sudut.
8.5.1 HorizontalSweep. 8.5.1 Horizontal Sweep.
8.5.2 Zero Reference Level. 8.5.2 Zero Reference Level.
18
8.6 Prosedur Pengujian. 8.6 Testing Procedures
8.6.1 X" Line. 8.6.1 "X"Line.
Y Linc. 8.6.2 y" Lin. 8
8.6.2
8
8.6.3 Kebersihan. 8.6.3 Cleanliness.
8.6.4 Couplants. 8.6.4 Couplants. 18
18
8.6.5 Maksud dari pengujian. 8.6.5 Extent of Testing.
19
8.6.6 Kesulitan Akses. 8.6.6 Inaccessibility.
8.7 Pengujian Lasan. 8.7 Testing of Welds. 9

8.8 8.8 Scanning. 20


Scanning 20
8.8.1 Longitudinal Discontinuities 8.8.1 Longitudinal Discontinuities_
20
8.8.2 Transverse Discontinuities 8.8.2 Transverse Discontinuities
8.9 Butt Joints. 8.9 Butt Joints. 20
9 Prosedure Evaluasi Ukuran|9 Discontinuity Size Evaluation 21

Discontinuities Procedures
9.1 Pengujian dengan Probe Normal 9.1 Straight-Beam (Longitudinal)
(Longitudinal) Testing 22
9.2 Pengujian dengan Probe Sudut 9.2 Angle-Beam (Shear) Testing.
(Shear).
Kriteria Penerimaan 10 Acceptance Criteria 23
10 Acceptance Criteria for Statically 23
10.1 Kriteria Penerimaan untuk Statically | 10.1
Loaded Nontubular Connections. Loaded Nontubular Connections.
10.2 Kriteria Penerimaan untuk Cyclically 10.2 Acceptance Criteria for Cyclically 23
Loaded Nontubular Connections. Loaded Nontubular Connections.
11 Identifikasi pada Area yang di Reject. 11 Identification of Rejected Area. 25
12 Perbaikan. 12 | Repair.
13 Steel Backing. 13 Steel Backing. 24

Dokumentasi 14 |Documentation 25
15 Laporan PengujianUlang. 15 | Retest Reports. 25
27-41
Lampiran Attachments
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev. 0

U2003-004-PYY-C07-NOO09 AWS D1.1


Page 5 of 41

1 Tujuan Purpose
1.1 Prosedur ini dipakai untuk petunjuk 1.1 This procedure provides guidance during
sewaktu mclakukan Pengujian Ultrasonic the conduct Direct Contact Ultrasonic
Kontak Langsung untuk Structural Steel Examination of Structural Steel welds and
welds dan HAZ(s), menggunakan pulse HAZS), using pulse echo type.
echo typec.
1.2 Prosedur ini terdiri dari versi Inggris dan 1.2
This procedure consists of English and
Indonesia, jika ada konflik antara Indonesian versions, should there is
keduanya maka versi Inggris yang dipakai conflict between these versions the
English version shall govem.

2 Ruang Lingkup 2 Scope


2.1 Prosedur ini berisi syarat -syarat dan 2.1 This procedure provides the requirements
acceptance standards Pengujian Ultrasonic and acceptance standards for the contact
Kontak Langsung untuk Structural Steel ultrasonic examination for full
full penetration groove welds dari ferrous penetration groove welds of ferrous
material (carbon steel, low alloy steel and material (carbon steel, low alloy steel and
stainless steel material) dengan thickness stainless steel material) with thickness
antara 5/16 inch (8.0 mm) sampai 8.0 between 5/16 inch (8.0 mm) upto 8.0 inch
inch (200 mm). (200 mm).
2.2 Prosedur ini tidak dimaksudkan untuk 2.2 This procedure is not intended for
pelaksanaan pengujian ultrasonic pada ultrasonic examination of tubular
sambungan terbuat dari pipa. connections.

3 Persyaratan Keselamatan 3 Safety Requirements


3.1 Peraturan safety PT. INTERGY 3.1 PT. NTERGY INDONESIA's safety
INDONESIA harus ditaati selama dalam regulation shall be followed during
pengujian. examination.
3.2 SAFETY ( S.H.E INSTRUCTION) 3.2 SAFETY (S.H.E INSTRUCTION )
Selalu menggunakan PPE such as Always use PPE such as Safety shoes,
Safety shoes, hand glove, safety glass, hand glove, safety glass, and helmet.
dan helmet.
.Waspada tempat yang licin dan benda .Watch out for slippery and falling
jatuh object..
.Waspada benda berbahaya sekitar Watch out for the hazard around the
lempat keja arcas.
.Berhenti kerja dan lapor ke client an Stop the activities and report to client
supervisor untuk tempat kerja yang and supervisor for unsafe working
tidak aman condition.
.Pakai alat pengaman ketinggian jika Use fall protection equipment if
kerja diatas 2 m working above 2 m.
Pungut sampah dan buang ditempat Collect all waste and put it in agreed
yang tersedia place.
Jangan membuang pelumas, oli atau D o not expose any lubricant, oil or test
cairan bekas lest ke lantai fluid to the ground.
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-C07-NOO09 AWS D1.1 Page 6 of 41
4 Dokumen Referensi Reference Documents
4.1 PT. INTERGY INDONESIA Written 4.1 PT. INTERGY INDONESTA 's Written
Practicc Practice
4.2 A WSDI.1-2015Edition; Scction 6. Part 4.2 AWSDI.1- 2015 Edition; Section 6, Part
C(6.13), Part F. (SNI 13-6985-2004) C(6.13), Part F. (SNI 13-6985-2004)
4.3 ASTM E 164. 2014 Edition: Standard 4.3 ASTM E 164, 2014 Edition: Standard
Practice for Ultrasonic Contact Examination Practice for Ultrasonic Contact Examination
of Wcldments of Weldments

5 Definisi - Definisi
5 Definitions
5.1 Zero reference level: respond dari 5.1 Zero reference level: the ultrasonic
ultrasonic dari refector 0.060" (1.59 mm) response from the 0.060" (1.59 mm)
di blok kalibrasi IIW - V1, secara reflector in the IW - Vi Standard Block

electronic di atur sampai persen tertentu Calibration, electronically adjusted to a


dari ketinggian screen. specified percentage of the full screen
height.
5.2 Search Unit : sebuah alat electro acoustic 5.2 Search Unit: an Electro acoustic device
digunakan untuk meneruskan atau used to transmit or receive ultrasonic
menerima ultrasonic energy. energy.
5.3 Kalibrasi : hubungan dari respon sistem 5.3 Calibration: corelation of the ultrasonic
ultrasonic dengan reflektor kalibrasi. system response with calibration reflector
(s).
5.4 Transducer ( Probe ) sebuah alat 54 Transducer Probe an
electro acoustical untuk merubah energi electroacoustical device for converting
listrik ke energi getaran dan sebaliknya. electrical energy into acoustical energy
and vice versa.
5.5 Probe Normalsebuah gelombang 5.5 Straight beam : a vibrating pulse wave
getaran pulsa yang berjalan normal (tegak train travelling normal to the test surface.
lurus) dengan permukaan yang di tes.
5.6 Probe Sudut : sebuah terminologi yang 5.6 Angle beam : a term used to describe an
digunakan untuk menyatakan sebuah angle of incidence or refraction other than
sudut datang atau pembengkokan selain normal to the surface of the test object, as
normal (tegak lurus) dengan permukaan an angle beam examination, angle beam
yang di tes, seperti sudut pengujian, sudut search unit, angle beam longitudinal
probe, sudut beam gelombang wave, and angle beam shear waves.
longitudinal, dan gelombang beam shear.

6 Kualifikasi dan Tanggung Jawab Qualification and Responsibility


6.1 Personel yang melakukan pengujian untuk 6.1 Personnel performing examinations to the
memenuhi syarat syarat dari spesifikasi requirements of this specification shall be
ini harus diqualifikasi sesuai dengan qualified in accordance with PT.
procedure PT. INTERGY INDONESIA INTERGY INDONESIA's Written
Written Practice Practice
6.2 Ujian untuk qualifikasi harus termasuk 6.2 The examination for qualificaion shall
demonstrasi kemampuan UT operator include UT operator demonstration his
dalam pengaplikasian aturan di Code yang ability to apply the rules of the Code
sudah di adopt dan dimasukkan kedalam which has been adopted and included in
prosedure ini, dalam mendeteksi dan this procedure, in accurate detection and
PROCEDURE
PERTAMINA
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-CO7-NO009
AWS D1.1 Page 7 of 41

mendesposisi cacat - cacat. disposition of discontinuitis.


Personel yang melaksanakan tes dan 6.3 Personnel performing examinations and
6.3
ini harus evaluation to the requirements of this
mengevaluasi dengan prosedure
memiliki Level lI atau Level II. procedure shall be Level II or Level II

1 Tools, Gages, Fixtures


Perlengkapan
7.1 Alat alat Ultrasonic 7.1 Ultrasonic Equipments
7.1.1 UT instrument 7.1.1 The UT instrument
UT instrument harus pulse ccho type The UT instrument shall be the pulse
ccho type suitable for use with transducer
cocok untuk digunakan dengan transducecr
dengan oscilasi pada frekwensi antara 1 oscillating at frequencies between 1 MHz
MHz to 6 MHz. Display harus "A" scan to 6 MHz. Display shall be "A" scan

rectified video trace. rectified video trace.


Dinamic range display instrument harus The dynamic range of the instrument's
difference of1
sedemikian rupa sehingga dengan mudah display shall be such that a
dB of amplitude can be easily detected on
perbedaan dari 1 db amplitude dengan
mudah bisa dideteksi di display. the display.
UT instrument yang operasi frekwensinya
diluar range tersebut mungkin bisa The UT instrument operating at other
digunakan jika sensitivitinya sama atau frequencies may be used if equal or better
lebih bagus bisa demonstrasikan dan sensitivity can be demonstrated and
didokumentasikan. documented
7.1.2 Syarat untuk pengujian Instrumen 7.1.2 Requirement for Test Instruments.
Test Instrument harus termasuk internal Test instruments shall include intermal
stabilisasi sehingga setelah pemanasan, stabilization so that after warm-up, no
tidak akan terjadi ada respon variasi lebih variation in response greater than I dB
besar dari +1 dB dengan perubahan suply occurs with a supply voltage change of
voltage 15% dari nominal atau, terjadi 15% nominal or, in the case of a battery,
masalah dengan baterey, selama throughout the charge operating life.
perubahan lama operasinya. Harus ada There shall be an alarm or meter to signal
sebuah alarm atau signal jika voltage a drop in battery voltage prior to
baterey drop sebelum instrument mati instrument shutoff due to battery
dikarenakan baterey habis. exhaustion.
7.1.3 Kalibrasi dari Pengujian Instrumen. 7.1.3 Calibration of Test Instruments.
Test Instrument harus mempunyai gain The test instrument shall have a calibrated
kontrol (attenuator) yang terkalibrasi yang gain control (attenuator) adjustable in
bisa di atur pada setiap step l atau 2 dB discrete 1 or 2 dB steps over a range of at
seluruh range dan paling sedikit 60 dB. least 60 dB. The accuracy of the
Keakuratan seting attenuator harus dalam attenuator settings shall be within plus or
range plus atau minus 1 dB. Prosedur ini minus dB. The procedure are detailed in
akan didetail pada paragraf 8.1.2. par. 8.1.2.
7.1.4 Linearitas Horizontal 7.1.4 Horizontal Linearity
Lineariti horizontal dari instrument harus The horizontal lincarity of the instrument
diqualifikasi seluruh sound path distance shall be qualified over the full sound path
yang digunakan, prosedur ini akan didetail distance to be used in testing the
pada paragraf 8.1.1. procedure are detailed in par. 8.1.1.
7.2 Search Units. 7.2 Search Units.
7.2.1 Search Units untuk Probe Normal 7.2.1 Straight-Beam (Longitudinal Wave)
PROCEDURE
PERTAMINA NINDYA
Rev. 0
Nomor Dokumen ULTRASONIC EXAMINATION
AWS D1.1 Page 8 of 41
U2003-004-PYY-CO7-NO009

Search Units.
(ongitudinal Wave)
Straight-beam (longitudinal wave) search
Straight-beam (longitudinal wavc) scarch unit transducers shall have an active area
unit transducers harus mempunyai aktive
of not less than 1/2 in. [323 mm*] nor
area tidak kurang dari 1/2 in. [323 mm
atau lcbih dari 1 in. 1645 mm9. more than 1 in. [645 mm].
Tranducer harus bundar atau persegi. The transducer shall be round or square
7.2.2 Resolusi untuk Probe Normal. 7.2.2 Resolution for Straight-Beam.
Transducers harus mampu membedakan Transducers shall be capable of resolving
the threc reflections, the procedure are
tiga reflcktor, proscdur ini akan didctail
pada paragraf 8.2.6. detailed in par. 8.2.b.
7.2.3 Search Units Probe Sudut. 7.2.3 Angle-Beam Search Units.
Probe Sudut harus terdiri dari sebuah Angle-beam search units shall consist of a
tranducer dan wedge yang bersudut. transducer and an angle wedge.
Unit bisa terpisah maupun menjadi satu The unit may be comprised of the two
kesatuan jadi satu unit. separate elements or may be an integral
unit.
7.2.4 Frequency. 7.2.4 Frequency.
Frequensi probe harus antara 2 and 2.5 The transducer frequency shall be
MHz. between 2 and 2.5 MHz, inclusive.
7.2.5 Dimensi Transducer. 7.2.5 Transducer Dimensions.
Crystal probe harus berbentuk persegi The transducer crystal shall be square or
atau persegi panjang dan bervariasi dari rectangular in shape and may vary from
5/8 in. sampai 1 in. [15 sampai 25 mm] 5/8 in. to l in. [15 to 25 mm] in width and
lebar dan dari 5/8 sampai 13/16 in. [155 from 5/8 to 13/16 in. [15 to 20 mm] in
sampai 20 mm] tinggi (lihat Figure 6.11). height (see Figure 6.11).
Perbandingan antara lebar dan panjang The maximum width to height ratio shall
maximum harus diantara 1.2 ke 1.0, dan be 1.2 to 1.0, and the minimum width-to-
lebar dan panjang minimum harus height ratio shall be 1.0 to 1.0.
diantara 1.0 ke 1.0.
7.2.6 Sudut. 7.2.6 Angles.
Search unit harus menghasilkan sound The search unit shall produce a sound
beam dalam material yang ditest dalam beam in the material being tested within
range plus atau minus 2" dari salah satu plus or minus 2° of one of the following
sudut berikut : 70°, 60°, atau 45. proper angles: 70°, 60°, or 45.
7.2.7 Resolusi untuk Probe sudut. 7.2.7 Resolution for Angle-Beam.
Transducers harus mampu membedakan Transducers shall be capable of resolving
iga reflektor, prosedur ini akan didetail the three reflections, the procedure are
pada paragraf 8.2.4. detailed in par. 8.2.4.
7.2.8 Penandaan 7.2.8 Marking.
Setiap Search Unit harus ditandai dengan Each search unit shall be marked to
jelas unuk mengindikasikan frekuensi clearly indicate the frequency of the
dari tranduser, sudut nominal refleksi, transducer, nominal
serta index point yang digunakan and index point.
angle of refraction
7.2.9 Jarak Ujung Probe 7.2.9 Edge Distance.
Dimensi dari Search Unit harus diatur The dimensions of the search unit shall be
jaraknya dari sudul leading dari Search such that the distance from the
Unit sampai index leading
point tidak boleh edge of the search unit to the index point
nelcbihil in. [25 mm). shall not exceed I in. [25 mm].
PROCEDURE
PERTAMINA
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev. 0
AWS D1.1 Page 9 of 41
U2003-004-PYY-CO7-NO009

7.3 Standar Acuan 7.3 Reference Standards.


Standard IIw The 7.3.1 ITW Standard. Any of The International
7.3.1 Sctiap type
Intemational Tnstitute of Welding (IIW) Institute of Welding (ITw) type UT
reference blocks may be used as the
blok reference UT dapat digunakan
standar untuk kalibrasi jarak dan standard for both distance and sensitivity
sebagai
sensitivity, asalkan blok terdapat lubang calibration, provided the block includes
sesuai the 0.060 in [1.5 mm] diameter hole
dengan diameter 0.060 in. [1.5 mm]
Gambar 6.13 dan fitur verifikasi jarak, shown in Figure 6.13 and distance,
resolusi dan sudut sesuai gambar 6.16 resolution, and angle verification features
(posisi A sampai G). Blok tipe IIW harus of Figurc 6.16 (position A through G).
sesuai dengan ASTM E 164. Block IIW type blocks shall conform to ASTM1
E 164. Other portable blocks may be
portable lain boleh digunakan, sebagai
level acuan dari kombinasi sensitif+tas used, provided the reference level
instrument/ Search Unit yang harus di sensitivity for instrument / search unit
combination shall be adjusted to be the
sesuaikan dengan nilai yang sama pada
IIW Block (Lihat Annex H dari AWS D equivalent of that achieved with the IIW
1.1, sebagai contoh). type Block (see Annex H of AWS D 1.1,
for examples).
Resolution reference test block (RC) 7.3.2 The resolution reference test block (RC )
7.3.2
seperti pada Gambar 6.14 A. shown in Figure 6.14 A.
Distance and Sensitivity Reference Block 7.3.3 The Distance and Sensitivity Reference
7.3.3
(DS) seperti Gambar 6.14 B. lock ( DS ) shown in Figure 6. 14 B.

Procedure 8 Procedure
Prosedur Kalibrasi dan Kualifikasi 8.1 Equipment Calibration and Qualifi-
8.1
Peralatan (lihat Table 6.8) cation Procedure ( see Table 6.8)
8.1.1 Linearitas Horizontal. 8.1.1 Horizontal Linearity.
Linearitas Horizontal dari instrumen The horizontal linearity of the tes

harus di rekualifikasi pada dua instrument shall be requalified at two-


penguji
bulan dalam setiap range jarak pada saat month in each of the distance ranges that
instrumen itu akan digunakan. the instrument will be used.
Prosedur Kualifikasi (lihat Annex G- The qualification procedure (see Annex G
AWS D 1.1, untuk metode alternative) - AWS D 1.1, for alternative method)

harus seperti ini : shall be as follows:


Catatan: Note:
kualifikasi im Since this qualification procedure is
Karena prosedur
unit performed with a straightbeam search unit
menggunakan straightbeam search
which produces longitudinal waves with a
yang menghasilkan gelombang
dengan sound velocity sound velocity of almost double that of
longitudinal
shear waves, it is necessary to double the
hampir dua kali gelombang shear,
diperlukan untuk menggandakan range shear wave distance ranges to be used in
shear untuk aplikasi dari applying this procedure.
jarak gelombang
prosedur ini.
Contoh: Penggunaan 10 in. [250 mm] Example: The use of a 10 in. [250 mm]
screen kalibrasi dalam gelombang shear screen calibration in shear wave would
akan meminta 20 in. [500 mm] kalibrasi require a 20 in. [500 mm) screen
screen untuk kualifikasi prosedur ini calibration for this
qualification
menggunakan straight-beam. procedure using straight-beam.
PROCEDURE
PERTAMINA
NINDYA
Rev. 0
Nomor Dokumen ULTRASONIC EXAMINATION
AWS D1.1 Page 10 of 41
U2003-004-PYY-C07-NOO09

Prosedur berikut harnus digunakan untuk The following procedure shall be used for
kalibrasi instrument (lihat Annex H, H3, instrument qualification (see Annex H,
untuk metode alternatif): H3, for alternative method):
(1) Probe Normal memenuhi syarat par. () A straight-beam search unit meeting
7.2.1 harus ditempatkan pada blok the requirements of par. 7.2.1 shall be
tipe IIW atau DS block Posisi G, T, coupled to the IIW type block or DS
atau U (lih. Figure 6.16) sedemikian block in Position G, T, or U (see
sehingga mendapatkan lima Figure 6.16) as necessary to attain
rupa
reflcksi balik (pulsa) pada range five back reflections in the
certified
kualifikasi yang tclah disertifikasikan qualification range being
(lih. Figure 6.16). (see Figure 6.16).
(2) Refleksi balik pertama dan kelima (2) The first and fifth back reflections
shall be adjusted to their proper
harus disesuaikan ke lokasi yang
locations with use of the distance
tepat dengan menggunakan kalibrasi
jarak dan penyesuaian kelambatan calibration and zero delay
nol. adjustments.
indikasi harus disesuaikan (3) Each indication shall be adjusted to
(3) Setiap reference level with the gain or
terhadap level referensi dengan gain
attenuation control for horizontal
atau kontrol atenuasi untuk
pengamatan lokasi horizontal location examination.
(4) Each intermediate trace deflection
(4) Setiap defleksi lokasi pada sisa location shall be correct within 2% of
intermediate harus di disesuaikan
2% dari lebar the screen width.
dengan sreen.

8.1.2 Gain Control (dB Accuracy ). 8.1.2 Gain Control (dB Accuracy ).
Gain kontrol instrumen (attenuator) harus The instrument's gain control (attenuator)
shall be checked for correct calibration at
dicek untuk kebenaran kalibrasinya setiap
interval 2 (dua) bulan. 2 (two) month intervals.
Prosedur qualifikasi harus dilaksanakan The qualification procedure shall be
seperti berikut performed as follows:

Note Note:
Untuk supaya menghasilkan keakurasian In order to attain the required accuracy (
indikasi yang 1%) in reading the indication height, the
pembacaan ketinggian
diinginkan (+ 1% ), display vertikal harus display shall be graduated vertically at
di atur secara bertahap interval pada 2%, 2% intervals, or 2.5% for instruments
atau 2.5% untuk instrument dengan with digital amplitude readout, at
bacaan digital amplitude, pada ketinggian horizontal mid-sereen height.
horizontal tengah sereen.
Cara lain bisa digunakan untuk kalibrasi Alternative methods may be used for
gain kontrol (attenuator) qualifikasi jika calibrated gain control (attenuator)
hasilnya minimum sama dengan prosedur qualification if proven at least equivalent
ini. with this procedure.
Tahapan ini harus diletakkan pada display These graduations shall be placed on the
antara 60% dan 100% dari tinggi screen. display between 60% and 100% of screen
Ini bisa dilaksanakan dengan height.
menggunakan selembar lapisan transparan This may be accomplished with use of a
pada screen. Jika lapisan transparan ini di graduated transparent screen overlay. If
this overlay is applied as a permanent part
aplikasikan sebagai bagian permanent dari
PERTAMINA PROCEDURE
NINDYA

ULTRASONIC EXAMINATION Rev.


Nomor Dokumen
11 of 41
U2003-004-PYY-C07-NOO09
AWS D1.1
Page
of the UT unit, care should be taken that
UT unit, harus diperhatikan supaya
the overlay does not obscure normal
lapisan tidak mengganggu display
sewaktu test. testing displays.
dari (1)A straight-beam search unit meeting
(1) Probe normal sesuai requirement
the requirements of par. 7.2.1 shall be
par. 7.2.1 harus di letakkan ke Blok
kalibrasi DS terlihat pada Figure 6.14 coupled to the DS block kalibrasi
shown in Figure 6.14 and position " T
dan pada posisi " T ", Figure 6.16.

(2) Kalibrasi jarak harus diatur sehingga , Figure 6.16.


reflcksi indikasi back wall yang (2) The distance calibration shall be
pertama dari 2 in. [50 mm] (yang adjusted so that the first 2 in. [50 mm]
kemudian dinamakan indikasi) ada back reflection indication (hereafter
called the indication) is at horizontal
ditengah screen horizontal.
(3) Gain atau attenuator kontrol yan mid-screen.
terkalibrasi harus diatur sehingga (3) The calibrated gain or attenuation
indikasi tepat atau sedikit diatas 40% control shall be adjusted so that the
screen height. indication is exactly at or slightly
(4) Search unit harus digeser kearah posisi above 40% screen height.
U, lihat Figure 6.16, sampai indikasi (4) The search unit shall be moved
tepat pada 40% screen height. toward position U, see Figure 6.16,
(5) Amplitude sound harus dinaikkan 6 until the indication is at exactly 40%
dB dengan gain atau attenuator kontrol screen height.
(5) (The sound mplitude shall be
yang terkalibrasi. Indikasi level secara
teori seharusnya tepat pada 80% increased 6 dB with the calibrated
screen height. gain or attenuation control. The
indication level theoretically should
be exactly at 80% screen height.
(6) Pembacaan dB harus di record dengan (6) The dB reading shall be recorded
"a" dan actual % screen height under "a and actual % screen height
dengan "b dari step 5 pada laporan under "b" from step 5 on the
certifikasi (Annex M, Form M-8), certification report (Annex M, Form
Line 1. M-8), Line 1.
(7) Search unit harus digerakkan lebih (7) The search unit shall be moved
mengarah ke posisi U, Figure 6.16, further toward position U, Figure
sampai indikasi tepat pada 40% screen 6.16, until the indication is at exactly
height. 40% screen height.
(8) Step 5 harus diulangi. (8) Step 5 shall be repeated.
9) Step 6 harus diulangi
kecuali 9) Step 6 shall be repeated; except,
informasi seharusnya di aplikasikan ke information should be applied to the
line berikutnya pada Annex M, Form next consecutive line on Annex M,
M-8 Form M-8.
(10) Step 7, 8, dan 9 harus diulangi secara (10) Steps 7, 8, and 9 shall be repeated
urut sampai seluruh range dari gain consecuively until the full range of
kontrol (atlenuator) mencapai (60 dB the gain control (attenuator) is
minimum). reached (60 dB minimum).
" " " "
(1) Informasi dari row a dan b (11)The information from Rows "a" and
harus di aplikasikan ke rumus par. b" shall be applied to equation par.
8.1.3 untuk menghitung dß yang 8.1.3 to calculate the corrected dB
betul. (12)Corected dB from step 11 to Row
PROCEDURE
PERTAMINA
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
AWS D1.1 Page 12 of 41
U2003-004-PYY-CO7-NOO09
betul dari step 1l diisikan "c" shall be applied.
(12)DB yang "c
"
value shall be subtracted
ke row "c". (13)Row
from Row "a " value and the
*

harus dikurangi dari


(13) Nilai
"

row c
nilai row " a" dan perbedaan di row difference in Row "d," dB error shall
d, dB eror harus diisi. be applied.
Note Nilai ini bisa positive maupun Note: These values may be either positive
negative.Contoh applikasi ada di Annex or negative and so noted. Examples of
M. Foms M-8, M-9, and M-10. Application of Forms M-8, M-9, and M-
10 are found in Annex M.
(14) Informasi harus di tabulasikan dalam (14) Information shall be tabulated on a
scbuah Form, termasuk minimum form, including minimum equivalent
information as displayed on Form D-
persamaan informasi seperti yang
ditampakkan Form D-8, dan unit di 8, and the unit evaluated in
conformance with instructioons shown
evaluasi sesuai dengan instruksi yang
ditunjukkan pada form ini. on that form.
(15) Form M-9 menyajikan cara relative (15) Form M-9 provides a relatively
lebih sederhana untuk mengevaluasi simple mneans of evaluating data from
data dari item (14). Instruksi untuk item (14). Instructions for this
evaluasi ini diberikan pada (16) evaluation are given in (16) through
sampai (18). (18).
e "(Form M-
"
(16) ThedB information from Row "e"
(16) DB informasi dari row
8) harus diisikan vertikal dan (Form M-8) shall be applied vertically
pembacaan dB dari Row "a" (Form and dB reading from Row "a" (Form
M-8) horizontally as X and Y
M-8) secara horizontal seperti X and
Y coordinates untuk ploting dB curve coordinates for plotting a dB curve on
pada Form M-9. Form M-9.
(17) Panjang horizontal terpanjang, seperti (17) The longest horizontal length, as
dipresentasikan oleh pembacaan represented by the dB reading
di tentukan dalam difference, which can be inscribed in
perbedaan dB, yang
sebuah segi panjang dalam tinggi 2 a rectangle representing 2 dB in
height, denotes the dB range in which
dB, menyatakan range dB dimana
equipment memenuhi syarat Code. the equipment meets the code
(18)Minimum range dB yang diizinkan requirements.
adalah 60 dB. (18)The minimum allowable range is 60

(19)Equipment yang tidak memenuhi dB


syarat mungkin bisa digunakan, (19)Equipment that does not meet this
asalkan faktor koreksi dicatat dan minimum requirement may be used,
digunakan untuk evaluasi cacat provided correction factors are

linearity developed and used for discontinuity


menyimpang range
instrument yang acceptable, atau evaluation outside the instrument
evaluasi test lasan dan cacat acceptable linearity range, or the weld
dipertahankan dalam range vertikal testing and discontinuity evaluation is
linearity dari equipment. kept within the acceptable vertical
Note DB error gambar ( Row "d") linearity range of the equipment
bisa digunakan untuk sebagai faktor Note: The dB error figures (Row "d')
koreksi gambar. may be used as correction factor igures.
8.1.3 Rumus Decibel. 8.1.3 Decibel Equation.
Rumus berikut harus digunakan untuk The following equation shall be used to
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-C07-NOO09 AWS D1.1 Page 13 of 41

kalkulasi decibel: calculate decibels:


Seperti dihubungkan dengan Annex M, As related to Annex M, Form M-8
Form M-88
d B = Row "a" dB= Row "a"
dB = Row "c" dB2 = Row "C"

o1 = Row "b" o =Row "b"


o2 = Defined on Fom M-8 o2 = Defined on Form M-8

dB -dB, = 20xlog dB, dB,


-
=
20xlog 2o
olo

dB = 20xlog 2+ dB dB,=20xlog +dB

8.1.4 Procedure Refleksi Internal. 8.1.4 Internal Reflections Procedure.


Maximum internal reflections dari Maximum internal reflections from each
masing unit harus di ferifikasi maximum search unit shall be verified at a
waktu interval 40 jam selama instrument maximum time interval of 40 hours of
digunakan. instrument use in
(1) Kalibrasi equipment sesuai dengan (1) Calibrate the equipment in

par. 8.5. conformance with par. 8.5.


(2) Pindahkan search unit lari blok (2) Remove the search unit from the
kalibrasi tanpa merubah pengatur calibration block kalibrasi without
equipment apapun. changing any other equipment
(3) Naikkan gain kontrol yang terkalibrasi adjustments.
atau attenuator 20 dB lebih sensitive (3) Increase the calibrated gain or
dari reference level. attenuation 20 dB more sensitive than
reference level.
(4) Area screen diluar 1/2 in. [12 mm] (4) The screen area beyond 1/2 in. [12
sound path dan diatas tinggi reference mm] sound path and above reference
level harus bebas dari indikasi apapun. level height shall be free of any
indication.
8.2 Kalibration dari Search Units. 8.2 Calibration of Search Units.
8.2.1 Kalibrasi dari Search Unit probe sudut 8.2.1 Calibration of Angle-Beam Search
Units.
Dengan menggunakan Blok Kalibrasi With the use of an approved calibration
block, each angle - beam search unit shall
yang diaprove, setiap angle beam search
-

unit harus dicek setiap delapan jam be checked after each eight hours of use
setelah digunakan, bahwa angle beam to determine that the contact face is tlat,
search unit masih betul, dan bahwa sudut that the sound entry point is correct, and
probe masih dalam toleransi yang that the beam angle is within the allowed
diizinkan plus atau minus 2°. plus or minus 2° tolerance .

Search unit yang tidak memenuhi syarat The Search units which do not meet these
harus dibetulkan atau dibuang. requirements shall be corected or

replaced.
8.2.2 Titik Index. 8.2.2 Index point.
Index point dari Iransducer harus The transducer sound entry point shall be
ditentukan atau dicek dengan procedure located or checked by the following
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
AWS D1.1 Page 14 of 41
U2003-004-PYY-CO07-NO009

procedure:
sebagaiberikut: (d) The transducer shall be set in
Transducer harus di set pada posisi D
()
pada the IW block. position D on the IIW block.
(2) Transducer harus di gerakkan sampai (2) The transducer shall be moved until
dari radius maximum. the signal from the radius is
signal menjadi
Titik pada transducer dimana segaris maximized. The point on the
calibration transducer which aligns with the
dengan garis radius pada radius line on the calibration block is
block adalah titik masuknya Ultrasonic
(Index point ). thc point ofsound entry.
8.2.3 Sudut 8.2.3 Angles.
Search unit harus menghasilkan sound The scarch unit shall produce a sound
beam in the material being tested within
beam dalam material yang ditest dalam
range plus atau minus 2° dari salah satu plus o r minus 2° of one of the following
or 45°.
dari sudut yang betul sebagai : 70°, 60°, proper angles: 70°, 60°,
atau 45°. The transducer sound-path angle shall be
Sound path transducer harus dicek atau checked or determnined by one of the

ditentukan dengan procedure berikut following procedures:


(1) The transducer shall be set in position
(1) Transducer harus di set pada posisi B B on IIW block for angles 40° through
pada IIW block untuk sudut 40
sampai 60°, atau pada posisiC pada 60°, or in position C on IIW block for
IIW block untuk sudut 60° sampai 70° angles 60° through 70° (see Figure

lih. Figure 6.16). 6.16).


(2) For the selected angle, the transducer
shall be moved back and forth over
(2) Untuk sudut yang ditentukan,
transducer harus di gerakkan ke muka the line indicative of the transducer
dan ke belakang diatas garis - garis angle until the signal from the radius
is maximized.
sudut yang diperkirakan sampai signal
dari radius menjadi maximumn. The sound entry point on the
transducer shall be compared with the
Index point pada transducer harus di
bandingkan dengan sudut yang tertera angle mark on the calibration block
pada calibration block (tolerance +2°) (tolerance+2°)
8.2.4 Angle Beam Resolution Require-ments.
8.2.4 Persyaratan untuk resolusi dari probe
sudut.
Kombinasi search unit dan instruments The combination of search unit and
instrument shall resolve three holes in the
harus bisa membedakan tiga lubang dalamn
block
test
RC resolution reference test block shown
RC resolution reference
kalibrasi ditunjukkan pada Figure 6.14. in Figure 6.14.
Posisi search unit seperti berikut The search unit position as follows:
(1) Transducer harus di set pada (1) The transducer shall be set on
resolution block RC posisi Q for 70° resolution block RC position Q for
70° angle, position R for 60° angle, or
angle, posisi R unuk 60° angle, atau
posisi S untuk 45° angle. position S for 45° angle.
(2) Transducer and instrument shall
(2) Transducer dan instrument harus bisa resolve the three lest holes, at least to
membedakan tiga lubang, paling tidak
membedakan ujung indikasi dari tiga the extent of distinguishing the peaks
of the indications from the three holes.
lubang. The resolution shall be evaluated with the
Resolution harus dievaluasi dengan
instrument control diset pada normal instrument controls set at normal test
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION- Rev.
U2003-004-PYY-CO07-NO009 AWS D1.1
Page 15 of 41
setting dan dengan indikasi dari lubang settings and with indications from the
dibawa kc tengah screen height. holes brought to midscreen
Resolution harus cukup membedakan
height.
Resolution shall be sufficient to
ujung indikasi dari tiga lubang. distinguish at least the peaks of
Menggunakan RC resolution reference indications from the three holes. Use of
block kalibrasi untuk kalibrasi harus the RC resolution reference block for
dilarang. Setiap kombinasi dari instrument calibration shall be prohibited. Each
search unit (shoe dan transducer) harus combination of instrument search unit
dicck scbelum pertama kali
dipergu- (shoe and transducer) shall be checked
nakan. Equipment verification ini harus prior to its initial use. This equipment
dikerjakan pertama kali dengan setiap verification shall be done initially with
search unit adan UT combinasi. each search unit and UT unit
combination.
Verifikasi tidak perlu dikerjakan lagi The verification need not be done again
asalkan dokumentasi di sinpan yang provided documentation is maintained
merekord seperti dibawah ini : that records the following items:
(1) UT machine's make, model and
(1) Merk alat UT, model dan nomor seri. serial number
(2) Pabrik pembuat search unit , tipe, (2) Search unit's manufacturer, type,
ukuran, sudut, dan nomor seri. size, angle, and serial number
(3) Tanggal verivikasi dan nama yang (3) Date of verification and technician's
melakukan. name

8.2.5 Kalibrasi dari Search Units Probe 8.2.5 Calibration of Straight-Beam Search
Normal Longitudinal Mode). Units (Longitudinal Mode).
Kalibrasi Jarak. Lihat See Annex H, H1 Distance Calibration. Sec Annex H, HI
untuk alternative method. for alternative method.
(1) Transducer harus diset pada posisi G (1) The transducer shall be set in position
pada the IIW block. G on the IIW block.
(2) Instrument harus diatur untuk bisa (2) The instrument shall be adjusted to
meng-hasilkan indikasi pada 1 in. [25 produce indications at 1 in. [25 mm on
mm pada a metric block], 2 in. [50 a metric block], 2 in. [50 mm on a
mm pada a metric block], 3 in. [75 metric block], 3 in. [75 mm on a
mm pada a metric block], 4 in. [100 metric block], 4 in. [100 mm on a
mm pada a metric block], etc., pada metric block], etc., on the display.
display.
Amplitude. Lihat Annex H, H1.2 untuk Amplitude. See Annex H, H1.2 for
alternative method. alternative method.
(1) Transducer harus diset pada posisi (1) The transducer shall be set in
Gain pada IIW block. position G on the IIW block.
(2) Gain harus diatur sampai indikasi (2) The gain shall be adjusted until the
maximum dari back reslection yang maximized indication from first back
pertama mencapai 50 sampai 75% reflection attains 50 to 75% screen
Screen height. height.
8.2.6 Persyaratan Resolution Probe Normal 8.2.6 Straight-Beam Resolution Requi
rement
1) Transducer harus diset pada posisi F (1) The transducer shall be set in
pada IIW block. position F on the IIW block.
PROCEDURE
PERTAMINA
NINDYA
ULTRASONIC EXAMINATION Rev.
Nomor Dokumen
U2003-004-PYY-C07-NO009
AWS D1.1
Page 16 of 41

(2) Transducer and instrument shall


(2) Transducer dan instrument harus bisa
membedakan semua tiga jarak. resolve all three distances.
8.2.7 Kualifikasi Linearitas Horizontal 8.2.7 Horizontal Linearity Qualification.
Procedure Qualifikasi harus seperti par. Qualification procedure shall be per par.
8.1.1 8.1.1.
8.2.8 Kualifikasi Gain Control (Attenuation). 8.2.8 Gain Control (Attenuation) Qualifi
cation.
Procedure Qualifikasi harus seperti par. The qualification procedure shall be in
8.1.2. conformance with par. 8.1.2.

8.3 Kalibration untuk Pengujían 8.3 Calibration for Testing


8.3.1 Posisi Kontrol Reject. 8.3.1 Position of Reject Control.
Semua kalibrasi dan test harus dibuat All calibrations and tests shall be made
dengan reject (clipping or suppression) with the reject (clipping or suppression)
control pada posisi mati. Menggunakan control turned off. Use of the reject
reject (clipping or suppression) control (clipping or suppression) control may
bisa mengubah amplitude linearity dari alter the amplitude linearity of the
the instrumen dan hasil test yang tidak instrument and invalidate test results.
valid.
8.3.2 Reflector yang dilarang. 8.3.2 Prohibited Reflectors.
Menggunakan reflector pojok (corner) The use of a "coner" reflector for
untuk kalibrasi tidak diperbolehkan. calibration purposes shall be prohibited.

8.3.3 Teknik. 8.3.3 Techniqune.


Kalibrasi untuk sensitivity dan horizontal Calibration for sensitivity and horizontal
Sweep ( jarak ) harus dibuat oleh UT sweep (distance) shall be made by the UT
operator sesaat sebelum dan pada lokasi operator just prior to and at the location
dimana testing lasan dimulai. of testing of each weld.
8.3.4 Kalibrasi Ulang. 8.3.4 Recalibration.
Re kalibrasiharus dibuat setelah Recalibration shall be mnade after a
penggantian operator, setiap dua jam change of operators, each two-hour
waktu maximum interval, atau aliran maximum time interval, or when the
listrik terganggu dengan meliputi : electrical circuitry is disturbed in any way
(1) Penggantian transducer which includes the following:
(2) Penggantian baterei (1) Transducer change
(3) Penggantian kabel listrik (2) Battery change
4) Penggantian kabel probe (3) Electrical outlet change
(5) Power outage (kegalalan ) (4) Coaxial cable change
(5) Power outage (failure)

8.4 Pengujian Probe Normal untuk Base 8.4 Straight-Beam Testing of Base Metal.
Metal.
8.4.1 Kalibrasi untuk straight - beam testing 84.1 Calibration for straight-beam lesting of
dari base metal harus dibuat dengan base metal shall be nmade with the search
search unit dari pernmukaan A dari base unit applied to Face A of the base metal
metal dan dikerjakan sebagai berikut: and performed as follows:
8.4.2 Sweep Horizontal. 8.4.2 Horizontal Sweep.
Horizontal sweep harus diatur untuk jarak The horizontal sweep shall be adjusted
PROCEDURE
PERTAMINA
NINDYA
ULTRASONIC EXAMINATION - Rev.
Nomor Dokumen
AWS D1.11 Page 17 of 41
U2003-004-PYY-CO7-NOO09

kalibrasi dengan setara minimum dua for distance calibration to present the
kalibrasi ketebalan plate pada display. equivalent of at least two plate
thicknesses on the display.
8.4.3 Sensitivity 8.4.3 Sensitivity
Sensitivity harus diatur pada lokasi yang The sensitivity shall be adjusted at a
bebas dari cacat schingga back wall location free of indications so that the
indikasi dari plate akan berada pada 50 % first back reflection from the far side of
to 75 % full screen height the plate will be 50 % to 75 % of ful1
Screen height
8.5 Kalibrasi untukAngle-Beam Testing. 8.5 Calibration for Angle-Beam Testing.
Kalibrasi untuk angle - beam harus dibuat Calibration for angle-beam testing shal
seperti berikut (see Annex H, H2.4 for be performed as follows (see Annex H,
alternative method). H2.4 for alternative method).
8.5.1 Horizontal Sweep. 8.5.1 Horizontal Sweep.
Horizontal sweep harus diatur untuk The horizontal sweep shall be adjusted to
mewakili actual jarak sound-path dengan represent the actual sound-path distance
menggunakan IIW block, dengan by using the IW block, with transducer
transducer diset pada posisi dengan pada shall be set in position D on the IIW
IIW block. Jarak kalibrasi harus dibuat block. The distance calibration shall be
menggunakan salah satu 5 in. [125 mm] made using either the 5 in. [125 mm]
scale atau 10 in. [250 mm] scale pada scale or 10 in. [250 mm] scale on the
display, yang mana yang lebih pantas. display, whichever is appropriate. f,
Jika joint konfigurasi atau tebal tidak however, the joint configuration or
memungkinkan untuk pengujian secara thickness prevents full examination of the
full dari lasan dari masing masing weld at either of these settings, the
seting,kalibrasi jarak harus di buat distance calibration shall be made usingg
menggunakan skala 15 in. atau 20 in. [400 15 in. or 20 in. [400 mm or 500 mm]
mm atau 500 mm] sesuai kebutuhan. Scale as required.
Note: Lokasi horizontal dari indikasi Note: The horizontal location of all
screen didasarkan pada lokasi dimana sisi screen indications is based on the location
kiri dari deflection memotong garis at which the left side of the trace
horizontal. deflection breaks the horizontal base line.
8.5.2 Zero Reference Level. 8.5.2 Zero Reference Level.
Zero reference level sensitivity yangg The zero reference level sensitivity used
digunakan untuk evaluasi cacat ("6° on for discontinuity evaluation ("b" on the
the Ultrasonic Test AWS, terlampir) harus Ultrasonic Test AWS, attached) shall be
dihasilkan dengan mengatur gain kontrol attained by adjusting the calibrated gain
kalibrasi (attenuator) detector cacat, control (attenuator) of the discontinuity
memenuhi persyaratan dari par. 8.1.2, detector, meeting the requirements of par.
sehingga maximum horizontal trace 8.1.2, so that a maximized horizontal
deflection (diatur ke horizontal ketinggian trace deflection (adjusted to horizontal
reference line dengan gain kontrol yang reference line height with calibrated gain
Lerkalibrasi fattenuator)) lerlihat pada control [attenuator]) results on the display
display. between 40% and 60% screen height.
Amplitude atau Sensitivity Calibration Amplitude or Sensitivity Calibration
Procedure, seperti berikut: Procedure, as follow
Transducer harus diset A
pada posisi pada The transducer shall be set in position A
ITW block (sembarang sudut). Sinyal yang on the ITW block (any angle). The
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-C07-NOO09 AWS D1.1 Page 18 of 41

maximum dari lubang 0.060 in. [ 1.59 mm] maximized signal shall then be adjusted
kemudian harus diatur untuk from the 0.060 in. [1.59 mm] hole to
menghasilkan ketinggian indikasi attain a horizontal reference-line height
horizontal reference-line (lihat Annex H, indication (see Annex H, H2.4 for
H2.4 untuk alternative method). alternative method). The maximum
Maximum pembacaan decibel yang decibel reading obtained shall be used as
dihasilkan harus digunakan sebagai the "Reference Level, b" reading on the
pembacaan "Reference Level, b" pada Test Report sheet (Ultrasonic Test AWS,
Test Report sheet (Ultrasonic Test AWS, attached).
attached).

8.6 Procedur Pengujian 8.6 Testing Procedures


8.6.1 Line.
Sebuah garis " X " untuk lokasi cacat
8.6.1 XLine.
An "X line for discontinuity location
harus ditandai pada permukaan test dari shall be marked on the test face of the
lasan sejajar dengan arah dari garis tengah weldment in a direction parallel to the
lasan. Jarak lokasi tegak lurus dengan weld axis. The location distance
garis tengah lasan harus didasarkan pada perpendicular to the weld axis shall be
dimensi gambar pada detail drawing dan based on the dimensional figures on the
biasanya jatuh pada centerline dari lasan detail drawing and usually falls on the
butt joint, dan selalu jatuh pada centerline of the butt joint welds, and
permukaan terdekat connecting member always falls on the near face of the
dari Testing dan lasan corner joint connecting member of T and corner joint
(dibaliknya Permukaan C). welds (the face opposite Face C).
8.6.2 Y Line. 8.6.2 Y Line.
Sebuah garis" Y" bersama nomor A "Y" accompanied with a weld
identifikasi lasan harus jelas ditandai pada identification number shall be clearly
base metal dekat dengan lasan yang ditest marked on the base metal adjacent to the
dengan UT. Marking ini digu-nakan untuk weld that is subject to UT. This marking
maksud sebagai berikut: is used for the following purposes:
(1) Identifiksai lasan (1) Weld identification
(2) Identifikasi dari permukaan A (2) Identification of Face A
(3) Jarak pengukuran dan arah (+ atau ) (3) Distance measurements and direction
dari garis "X" (+or ) from the "X" line
(4) Pengukuran lokasi dari ujung dan (4) Location measurement from weld
akhir lasan ends or edges
8.6.3 Kebersihan. 8.6.3 Cleanliness.
Semua permukaan mana search unit All surfaces to which a search unit is
akan digunakan harus bebas dari spatter applied shall be free of weld spatter, dirt,
lasan, debu, grease, oil (selain yang grease, oil (other than that used as a
digunakan sebagai couplant), cat, dan couplant), paint, and loose scale and shall
kerak yang mengelupas dan harus have a contour allowing inimate
inempunyai contour yang menmungkinkan coupling.
menempel bagus.
8.6.4 Couplants. 8.6.4 Couplants
Couplant materialharus digunakan A couplant material shall be used
diantara search unit dan material yng between the search unit and the test
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.

U2003-004-PYY-CO7-NO009 AWS D1.1 Page 19 of 41

ditest. Couplant harus dari salah satu material. The couplant shall be either
glycerin atau campuran yang merata dari glycerin or cellulose gum and water
cellulose gum dan air. Pelumas bisa mixture of a suitable consistency. A
ditambahkan jika diperlukan. wetting agent may be added if needed.
Oli mesin yang encer bisa digunakan Light machine oil may be used for
untuk couplant pada block kalibrasi. couplant on calibration blocks.
8.6.5 Maksud dari pengujian. 8.6.5 Extent of Testing.
Seluruh base metal dimana harus dilalui The entire base metal through which
olch ultarasound untuk pengujian lasan ultrasound must travel to test the weld
harus diuji kemungkinan laminasi shall be tested for laminar reflectors using
menggunakan straight beam search unit a straight-beam search unit conforming to
sesuai persyaratan dari par. 7.2.1 dan di the requirements of par. 7.2.1 and
kalibrasi sesuai dengan par. 8.4. Jika ada calibrated in conformance with par. 8.4. If
area dari base metal menunjukkan back any area of base metal exhibits total loss
reflection hilang total atau ada indikasi of back reflection or an indication equal
yang sama dengan atau lebih besar dari to or greater than the original back
ketinggian original back reflection yang reflection height is located in a position
terletak pada posisi dimana akan that will interfere with the normal weldd
mengganggu procedure scaning normal scanning procedure, its size, location, and
lasan, maka ukurannya, lokasinya, dan depth from the A face shall be determined
kedalamannya dari permukaan A harus and reported on the UT report, and an
ditentukan dan dilaporkan pada UT report, alternate weld scanning procedure shall
alternative procedure scaning lasan harus be used.
digunakan.
8.6.6 Kesulitan access. 8.6.6 Inaccessibility.
Jika bagian dari lasan susah di access If part of a weld is inaccessible to testing
untuk pengujian sesuai dengan in conformance with the requirements of
persyaratan dari Table 6.7, karena adanya Table 6.7, due to laminar content
record laminasi sesuai dengan par. 8.6.5, recorded in conformance with par. 8.6.5,
pengujian harus dilaksanakan the testing shall be conducted using one
menggunakan satu atau lebih procedure or more of the following alternative
alternative sesuai kebutuhan untuk procedures as necessary to attain full
mengahasilkan seluruh lasan tercover: weld coverage:
(1) Permukaan lasan harus digerinda rata. (1) Weld surface(s) shall be ground
Jika finishing permukaan diperlukan , flush. Where surface finishing is
nilai kekasaran ( lihat ASME B46.1) required, roughnesS values (see
tidak boleh lebih dari 250 ASME B46.1) shall not exceed 250
microinches [6.3 micrometers]. Nilai microinches [6.3 micrometers].
Surface finish melebihi 125 micro Surfaces finished to values of over
inche [3.2 micrometer] sampai 250 125 microinches (3.2 micrometers
microinches harus dikerjakan sejajar through 250 microinches shall be
dengan arah dari primary stress. Nilai finished parallel to the direction of
Surface finish 125 microinches atau primary stress. Surfaces finished to
kurang bisa dikerjakan pada values of 125 microinches or less
sembarang arah. may be finished in any direction.
(2) Pengujian dari permukaan A dan B 2) Testing from Faces A and B shall be
harus dilakukan. performed.
(3) Sudut Search unit lain harus (3) Other search unit angles shall be
PERTAMINA PROCEDUJRE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-C07-NO009 AWS D1.1
Page 20 of 41
digunaka. uscd.

8.7 Pengujian Lasan. 8.7 Testing of Welds.


8.7.1 Lasan harus diuji dengan menggunakan 8.7.1 Welds shall be tested using an angle beam
probe sudut sesuai dengan persyaratan search unit conforming to the
dari par. 7.2.3- 7.2.9 dengan instrument requirements of par. 7.2.3 -7.2.9 with the
yang terkalibrasi sesuai dengan par. 8.2.1 instrument calibrated in conformance
menggunakan sudut seperti ditunjukkan with par. 8.2.1 using the angle as shown
dalam Tablc 6.7. Sctelah kalibrasi dan in Table 6.7. Following calibration and
sclama pengujian, pengaturan kontrol
during testing, the only instrument
instrument yang dipcrbolchkan hanya adjustment allowed is the sensitivity level
pengaturan sensitivity dengan gain kontrol adjustment with the calibrated gain
yang terkalibrasi (attenuator). control (attenuator)
8.7.2 Reject (clipping or suppression) kontrol 8.7.2 The reject (clipping or suppression)
harus dimatikam. Sensitivity harus control shall be turned off. Sensitivity
dinaikan dari reference level untuk shall be increased from the reference level
scaning lasan sesuai dengan Table 6.2 for weld scanning in conformance with
atau 6.3, yang sesua. Table 6.2 or 6.3, as applicable.

8.8 Scanning. 8.8 Scanning.


Sudut pengujian dan procedure scaning The testing angle and scanning procedure
harus sesuai dengan yang ditunjukan shall be in conformance with those shown
dalam Table 6.7. in Table 6.7.
Scaning Patern (lihat Figure 6.15) Scanning Patterns (See Figure 6.15)

8.8.1 Longitudinal Discontinuities: 8.8.1 Longitudinal Discontinuities:


(1) Scaning Movement A. Sudur putar, a (1) Scanning Movement A. Rotation
10. angle, a = 10°.
(2) Scaning Movement B. Scaning (2) Scanning Movement B. Scanning
distance b harus mengcover semua distance b shall be such that the
bagian dari lasan. section of weld being tested is
covered.
3) Scanning Movement C. Jarak maju c 3) Scanning Movement C. Progression
harus kira kira setengah lebar distance c shall be approximately
transducer. one-half the transducer width.
Note pergerakan A, B dan C bisa Note: movements A, B, and C may be
dikombinasikan menjadi satu scaning combined into one scanning pattern.
patern.
8.8.2 Transverse Discontinuities 8.8.2 Transverse Discontinuities
(1) Lasan yang digerinda. (1) Ground Welds. Scanning pattern D
Scaning palern D harus digunakan shall be used when welds are ground
jika lasan digerinda rala. lush.
(2) Lasan yang tidak digerinda. (2) Unground Welds. Scanning pattern
Scanning paltern E harus digunakan E shall be used when the weld
jika weld reinforcement tidak reinforcement is not ground flush.
digerinda rata. Scanning angle, e = I5° max.
Scaning angle, e = 15" max.
Note: Scaning patern harus mengcover Note: The scanning pattern shall cover
PERTAMINA PROCEDURE
NINDYA

Nomor Dokumen ULTRASONIC EXAMINATION Rev.


U2003-004-PYY-CO7-NO009 AWS D1.1 Page 21 of 41

scmua bagian lasan. the full weld section.

8.9 Butt Joints. 8.9 Butt Joints.


8.9.1 Semua butt joint harus diuji dari sctiap sisi 8.9.1 All butt joint welds shall be tested from
dari lasan dari garis tengah lasan. Lasan cach side of the weld axis. Corner and T-
comer dan T joint harus diuji pertama dari joint welds shall be primarily tested from
satu sisi dari garis tengah lasan saja. one side of the weld axis only.
8.9.2 Semua lasan harus diuji menggunakan 8.9.2 All welds shall be tested using the
Scaning paterm yang cocok atau patern applicable scanning pattern or patterns
yang ditunjukkan di Figurc 6.15 jika shown in Figure 6.15 as necessary to
diperlukan untuk mendeteksi kedua detect both longitudinal and transverse
duanya cacat memanjang dan melintang. discontinuities.
8.9.3 Jika diperlukan, minimum, semua lasan 8.9.3 It is intended that, as a minimum, all
diuji dengan sound melewati seluruh welds be tested by passing sound through
volume lasan dan HAZ dalam dua arah the entire volume of the weld and the
yang berpotongan, jika memungkinkan HAZ in two crossing directions, wherever
untuk dilaksanakan. practical.
8.9.4 Indikasi Maximum. 8.9.4 Maximum Indication.
Jika sebuah indikasi cacat kelihatan di When a discontinuity indication appears
layar, maximum indikasi yang dihasilkan on the screen, the maximum attainable
dari cacat harus diatur untuk indication from the discontinuity shall be
menghasilkan horizontal reference level adjusted to produce a horizontal reference
trace deflection pada display. Pengaturan level trace deflection on the display. This
ini harus dibuat dengan gain kontrol adjustment shall be made with the
terkalibrasi (attenuator), dan pembacaan calibrated gain control (attenuator), and
decibel instruments harus digunakan the instrument reading in decibels shall be
sebagai Indication Level, a," untuk used as the "Indication Level, a," for
kalkulasi "Indication Rating, d," seperti calculating the "Indication Rating, d,"
ditunjukkan pada test report (Utrasonic as shown on the test report (Utrasonic
Test AWS, attached). Test AWS, attached).
8.9.5 Attenuation Factor. 8.9.5 Attenuation Factor.
Attenuation Factor, c," pada test report The "Attenuation Factor, e," on the test
harus dihasilkan dengan mengurangi 1 report shall be attained by subtracting 1
inch (25 mm) dari jarak sound-path dan in. [25 mm] from the sound-path distance
mengalikan sisanya dengan 2 untuk U.S. and multiplying the remainder by 2 for
Customary units atau 0.08 untuk SI Units. U.S. Customary Units or be 0.08 for SI
Factor ini harus dibulatkan ke nilai dB Units. This factor shall be rounded out to
the nearest dB value. Fractional values
yang terdekat. Nilai pecahan kurang dari
1/2 dB harus dikurangi ke dB level yang less than 1/2 dß shall be reduced to the
lebih rendah dan nilai pecahan 1/2 dB atau lower dB level and those of 1/2 dB or
lebih besar dinaikkan ke level yang lebih greater increased to the higher level.
inggi.
8.9.6 Indication Rating. 8.9.6 Indication Rating.
Indication Rating, d," pada Urasonic The Indication Rating, d," in the
Test AWS, atlached, menggambarkan Utrasonic Test AWS, attached,
perbedaan perhitungan decibel antara represents the algebraic difference in
indication level dan reference level decibels between the indication level and
dengan koreksi untuk atenuasi seperti the reference level with correction for
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev. 0
U2003-004-PYY-C07-NOO09 AWS D1.1
Page 22 of 41

ditujukkan dibawah ini. attenuation as indicated in the following


cxpressions.
Instruments dengan gain pada dB: Instruments with gain in dB:
d= a-b-c d= a - b-c

9 Procedures Evaluasi Ukuran 9 Discontinuity Size Evaluation


Discontinuities. Procedures
9.1 Pengujian dengan Probe Normal 9.1 Straight-Beam (Longitudinal) Testing.
(Longitudinal)
9.1.1 Ukuran dari cacat laminasi tidak sclalu 9.1.1 The size of lamellar discontinuities is not
mudah ditcntukan, terutama yang always easily determined, especially
ukurannya lebih kecil dari ukuran those that are smaller than the transducer
transducer. size.
9.1.2 Jika cacat lebih besar dari transducer, 9.1.2 When the discontinuity is larger than the
kehilangan total dari back reflection akan transducer, a full loss of back reflection
terjadi dan 6 dB kehilangan amplitude will occur and a 6 dB loss of amplitude
(50% screen height) dan pengukuran ke and measurement to the centerline of the
centerline dari transducer biasanya transducer 1s usually reliable for
dipercaya untuk menentukan ujung cacat. determining discontinuity edges.
9.1.3 Walaupun begitu, ukuran kira - kira dari 9.1.3 However, the approximate size evaluation
evaluasi reflector, yang lebih kecil dari of those reflectors, which are smaller than
transducer, harus dibuat dengan cara the transducer, shall be made by
mulai dari arah luar cacat dengan beginning outside of the discontinuity
instruments yang terkalibrasi with equipment calibrated moving the
menggerakkan transducer kearah area transducer toward the area of
cacat sampai indikasi terlihat pada discontinuity until an indication on the
display. Pada point ujung dari search unit display begins to form. The leading edge
ini adalah dianggap ujung dari cacat. of the search unit at this point is
indicative of the edge of the discontinuity.
9.2 Pengujian dengan Probe Sudut (Shear). 9.2 Angle-Beam (Shear) Testing.
9.2.1 Procedure berikut ini harus digunakan 9.2.1 The following procedure shall be used to
untuk menentukan panjang dari indikasi determine lengths of indications which
yang mempunyai dB rating yang lebih have dB ratings more serious than for a
serius dari indikasi Class D. Panjang dari Class D indication. The length of such
indikasi harus ditentukan dengan indication shall be detemined by
mengukur jarak antara lokasi centerline measuring the distance between the
transducer dimana amplitude indication transducer centerline locations where the
rating turun (drop) 50% (6 dB) dibawah indication rating amplitude drops 50% (6
rating untuk clasifikasi cacat yang cocok. dB) below the rating for the applicable
discontinuity classification. This length
Panjang ini harus direcord pada kolom shall be recorded under "discontinuity
discontinuity length" pada test report. length" on the test report.
Jika diperlukan karena memandang Where warranted by discontinuity
amplitude cacat procedure ini harus amplitude, this procedure shall be
repeated determine the length of Class
to
diulangi untuk menentukan panjang cacal
dari clas A, B dan Cacat. A, B, and C discontinuities.
9.2.2 Indikasi dari cacat yang lelap ada pada 9.2.2 Indications of discontinuities that remain
display selama search unit digerakkan on the display as the search unit is moved
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-C07-NOO09 AWS D1.1 Page 23 of 41

maju dan mundur dari cacat (scanning towards and away from the discontinuity
movement "b") bisa jadi menunjukkan (scanning movement "b) may be
dimensi indicative of planar discontinuities with
cacat planar dengan cenderung8
kearah throat. significant through-throat dimension.
9.2.3 Karena major reflecting surface dari cacat 9.2.3 Since the major reflecting surface of the
yang critical minimum orientasinya 20° most critical discontinuities is oriented a
(untuk 70° scarch unit) dan 45° (untuk minimun of 20° (for a 70° search unit) to
45° scarch unit) dari tegaklurus ke sound 45° (for a 45° search unit) from
beam, maka amplitude evaluasi (dB perpendicular to the sound beam,
rating) tidak memungkinkan disposisi amplitude evaluation (dB rating) does not
secara tepat. allow reliable disposition.
9.2.4 Jika indikasi menunjukkan ciri - ciri 9.2.4 When indications exhibiting these planar
planar ada pada scaning sensitivity, characteristics are present at scanning
evaluasi lebih detail dari cacat dengan sensitivity, a more detailed evaluation of
cara lain sangat diperlukan (seperti the discontinuity by other means shall be
alternative UT tehnik, RT, grinding atau required (e-g., alternate UT techniques,
gouging untuk visual inspection, etc.). RT, grinding o r gouging for visual
inspection, etc.)

10 Kriteria Penerimaan. 10 Acceptance Criteria.


a. Pengujian lasan dengan Utrasonic adalah a. Ultrasonically tested welds are evaluated
dievaluasi berdasarkan refleksi ultrasound on the basis of a discontinuity reflecting
ultrasound in proportion to its effect on
dari cacat yang secara proporsional
menimbulkan effect pada intregitas dari the integrity of the weld.
lasan
b. Setiap lasan harus di terima
cacat b. Each weld discontinuity shall be accepted
(accepted) atau ditolak (rejected) berdasar or rejected on the basis of its indication
pada indication ratingnya dan panjangnya, rating and its length, in conformance with
sesuai dengan Table 6.2 untuk statically Table 6.2 for statically loaded
loaded structures atau Table 6.3 untuk structures or Table 6.3 for cyclically
cyclically loaded structures, mana yang loaded structures, whichever is
cocok. applicable.
c. Hanya cacat- cacat yang direject perlu c. Only those discontinuities which are
direcord pada test report, kecuali untuk rejectable need be recorded on the test
lasan yang disebut di kontrak sebagai report, except that for welds designated in
"Fracturc Critical, rating acceptable the contract documents as being "Fracture
dalam range 6 dB, inclusive, minimum Critical", acceptable ratings that are
rating rejectable harus direcord pada test within 6 dB, inclusive, of the minimurm
rejectable rating shall be recorded on the
report.
test report.

10.1 Kriteria Penerimaan untuk Statically 10.1 Acceptance Criteria for Statically
Loaded Nontubular Connections. Loaded Nontubular Connections.
10.1.1 Acceplance criteria untuk lasan yang 10.1.1 The acceptance criteria for welds subject
dipersyaratkan UT sebagai tambahan dari to UT in addition to visual inspection
visual inspection harus memenuhi shall meet the requirements of Table 6.2
persyaratan dari Table 6.2
10.1.2 Untuk lasan CJP web-to flange, 10.1.2 For CJP web-to flange welds, acceptance
PERTAMINA PROCEDURE
NINDYA
Nomor Dokumen ULTRASONIC EXAMINATION Rev.
U2003-004-PYY-CO7-NO009 AWS D1.1 Page 24 of 41

acceptance dari cacat yang terdeteksi of discontinuities detected by scanning


dengan pergerakan scaning sclain dari movements other than scanning pattern
scaning patem 'E' (lihat par. 8.8 ) bisa E' (see par. 8.8) may be based on weld
berdasarkan pada kctcbalan lasan sama thickness equal to the actual web
dengan actual web thickness plus I in. [25 thickness plus 1 in. 25 mm.
mm). Cacat yang terdeteksi dengan Discontinuities detected by scanning
scaning patem 'E' harus dicvaluasi pattcrn E' shall be evaluated to the
kepada criteria dari Table 6.2 untuk criteria of Table 6.2 for the actual web
actual web thickness. thickness.
10.1.3 Jika lasan CJP web-to flange mcnanggung 10.1.3 When CJP web-to-flange welds are
bcban tarik (tensile stress) tegak lurus ke subject to calculated tensile stress normal
lasan. mereka harus sesuai dengan to the weld, they should be so designated
persyaratan di Table 6.2. on the design drawing and shall conform
to the requirements of Table 6.2.

10.2 Kriteria Penerimaan untuk Cyelically 10.2 Acceptance Criteria for Cyclically
Loaded Nontubular Connections. Loaded Nontubular Connections.
10.2.1 Acceptance criteria untuk lasan yang 10.2.1 The acceptance criteria for welds subject
dipersyaratkan UT sebagai tambahan dari to UT in addition to visual inspection
visual inspection harus memenuhi shall meet the following requirements:
persyaratan berikut: (1) Welds subject to tensile stress under
(1) Lasan yang menerima beban tensile any condition of loading shall
dengan segala kondisi dari beban conform to the requirements of Table
harus sesuai dengan persyaratan dari 6.3.
Table 6.3. (2) Welds subject to compressive stress
(2) Lasan yang menerima beban tekan shall conform to the requirements of
harus sesuai dengan persyaratan dari Table 6.2.
Table 6.2.
10.2.2 Lasan CJP web-to-flange harus sesuai 10.2.2 CJP web-o-flange welds shall conform to
dengan persyaratan dari Table 6.2. the requirements of Table 6.2.
10.2.3 Acceptance untuk cacat yang terdeteksi 10.2.3 Acceptance for discontinuities detected
dengan gerakan scaning selain dari by scanning movements other than
Scaning patern "E (lihat par. 8.8) bisa scanning pattern 'E' (see par. 8.8) may be
berdasarkan pada ketebalan lasan sama based on a weld thickness equal to the
dengan actual web thickness plus 1 in. [25 actual web thickness plus I in. [25 mm].
mm.
10.2.4 Cacat yang dideteksi dengan
scaning 10.2.4 Discontinuities detected by scanning
dengan criteria
harus dievaluasi pattern 'E' shall be cvaluated to the
patern 'E criteria of par. 10.5 for the actual web
par. 10.5 untuk aktual ketebalan web.
thickness.
10.2.5 Jika lasan CJP web-to lange menerima 10.2.5 When such web-toflange welds are
beban tarik (lensile stress) legak lurus ke subject to calculated tensile stress normal
lasan, mereka harus dijelaskan di drawing to the weld, they shall be so designated on
design dan harus sesuai dengan design drawings and shall conform to the
persyaratan di Table 6.3. requirements of Table 6.3.