DOC NO:ED/130181/GTP/01/R0

BIDDING
SCHEDULE
(To be filled in and signed by the Manufacturer) SCHEDULE ‘A’
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 220/66 kV
63MVA THREE PHASE AUTO TRANSFORMERS
No. Particulars Offered
A General Data of Manufacturer
1 Name of Manufacturer TELK, ANGAMALLY, KERALA
2 Country of Origin INDIA
3 Business Type of Company (e.g. Manufacturer/ Contractor etc.) Manufacturer

B General Data of the Transformer


1 Conforming Applicable Standards (including Bushing &other) IS 2026 / IEC 60076 - Power Transformer
IS 2099 / IS 3347 - Bushings/Applicable standards as per specification
2 Conceptual Design of Transformer Outdoor / Oil immersed core type
(E.g. Outdoor /oil immersed /core type /Indoor /etc.)

3 Type of Operation of the Transformer (e.g. Interconnection - Interconnection - Auto Transformer


Autotransformer/ Distribution/ Generator step-up)

4 Rated Frequency (in Hz) 50 Hz


6 Rated MVA Capacity Of the Transformer HV - 63 MVA
 HV LV - 63 MVA
 LV

7 Rated No-load Voltage of the Transformer HV - 220 kV


 HV LV - 66 kV
 LV

8 No Load Current in percent of Full Load current at rated KV &rated 0.06% with IS tol.
frequency at Normal Tap

9 Vector Group YNaO


10 Type of Cooling ONAN/ODAN/ODAF
11 Method of Neutral Grounding Solidly grounded
12 Rated No load Voltages of windings in kV HV winding - 220 kV
 HV Winding LV winding - 66 kV
 LV Winding

13 Normal ratio of transformation 220/66 kV


14 Rated Current in Ampere. 165.33 (line value)
 HV Winding 330.66 (line value)
 LV Winding
15 Overload capacity As per IS 2026 Part 7/IS 6600
16 Width of Track gauge (in mm) 1676 x 1676
C Thermal Data
1 Temperature rise of top oil (in °C) measured by thermometer with 45
ONAN/ODAN/ODAF cooling
2 Temperature rise of winding measured by resistance : With 50
ONAN/ODAN/ODAF cooling, in °C

3 Limit of hot spot temperature in ° C for which the transformer is 98 deg.C based on yearly weighted average ambient temperature of 32 deg.C
designed
4 Temperature gradient between Oil &Winding. 18 deg.C(Approx)

5 Limit for hot spot temperature For which transformer is designed. 98 deg.C based on yearly weighted average ambient temperature of 32
deg.C.Tank hot spot less than 80 deg Cabove ambient of 50 deg C
D Impedance Data

# Sensitivity: LNT Construction Internal Use
1 Percentage Impedance (HV-LV)at rated 12.3 (Approx) on 63 MVA base HV-LV loading
current and frequency at 75 °C(with tolerance) 12.5 With IS tolerance on 63 MVA base HV-LV loading
 At maximum tap 13.0 (Approx) on 63 MVA base HV-LV loading
 At Normal tap
 At Lowest tap
2 Percentage reactance (HV-LV) at 75 °C 12.29% on 63 MVA base(HV-LV) approx.
 At maximum tap 12.499% on 63 MVA base (HV-LV) approx.
 At Normal tap 12.99% on 63 MVA base (HV-LV) approx.
 At Lowest tap
3 Resistance of windings in ohm at 75 °C HV                                                                        IV
 At maximum tap 0.78 ohm (Max.)                                0.08  (Max.)         
 At Normal tap 0.73ohm (Max.)                                 0.08  (Max.)         
 At Lowest tap 0.78 ohm  (Max.)                                0.08  (Max.)         

4 Zero Sequence Impedance(HV-LV) at 75 a) 9.84% (approx).


°C at 100% rating b) 10% (approx.)
a. At maximum tap c) 10.4% (approx.)
b. At Normal tap
c. At Lowest tap

E Guaranteed Loss
1 Guaranteed maximum no load loss (KW) on principal tap at rated 22.5 kW (max.)
voltage and Frequency

2 No load loss at rated voltage and frequency at highest tap (max.) 22.5 kW (at max tap position and voltage corresponding to max tap)

3 Guaranteed maximum load loss at rated current at rated voltage, rated


frequency and 75°C average winding temperature, kW (excluding aux. 115 kW (max.) HV-LV 63 MVA Base
losses). 125 kW H tap HV-LV 63MVA Base(Approx)
At principal tap For ODAF cooling 135 kW L tap HV-LV 63MVA Base(Approx)
At maximum tap For ODAF cooling At
minimum tap For ODAF cooling

4 Maximum Auxiliary Loss (KW) 4.5 kW (max.)

5 Total losses at normal ratio, rated output, rated voltage, rated frequency 148 kW (Max) 63 MVA Base
and maximum attainable temperature at site including auxiliary losses.

6 Time for which the transformer can run at full load without exceeding 10 minutes without exceeding calculated winding hot spot temperature of 140 ⁰C.
the max. permissible temperature at reference temperature when power
supply to fans
&pumps is cut off (in minutes)

7 Exciting current and power factor 0.2 with IS tolerance p.f - 0.6(approx).
F Efficiency &Regulation
1 Efficiency (in percent) at unity power factor at 75°C

At 110% Load 99.76 (approx.)


At 100% Load 99.78 (approx.)
2 Efficiency (in percent) at 0.85 power factor (Lag) at 75°C

At 110% Load 99.71 (approx.)


At 100% Load 99.74 (approx.)
At 75% Load 99.78 (approx.)
At 50% Load 99.81 (approx.)
At 25% Load 99.79 (approx.)

3 Maximum Efficiency % 99.84%(approx.)


4 % Load and power factor 44.23 %load(approx) at upf
at which Max efficiency occurs
5 Regulation at Unity Power factor 0.96% (approx.)
6 Regulation at 0.8 lagging Power factor 8.13% (approx.)
G Radiators
1 Overall dimensions l x b xh ,mm 1275x540x2690 (approx.)

2 Total weight with oil, Kg 767 kg/Radiator (approx.)


3 Total weight without oil 615 kg/Radiator (approx.)

# Sensitivity: LNT Construction Internal Use
4 Vacuum withstand capacity, Tor As per CBIP
5 Number of radiator banks 2x50%
6 Mounting of radiators in each bank Separaterly mounted radiator banks
7 Number of radiators in each bank 3No
8 Type &size of individual radiator valve 80mm Butterfly valve

9 Total radiating surface, sq. M 72 sq.m/Radiator (approx.)


10 Thickness of radiator tubes, mm 1.2mm (approx.)
11 Oil drain plug and air release plug provided on each radiator Yes/No Yes

12 Schematic flow diagram of the cooling system furnished (Yes/No) Ref OGA drawing No TK 110811 Latest revision

H Cooling System

Cooling Fans
1 Make and type Marathon(Alstom)/Khaitan/Equivalent, Propeller type
1.1 No. of fans in each group excluding standby fans 2 Nos

1.2 No. of connected units in each bank 2 Nos working + 1 no standby


1.3 No. of standby units in each bank 1 No. (approx.) in each group
1.4 Rated power input, watts 240 (approx.)
1.5 Capacity ( cum/minute) 90 (approx.)
1.6 Rated voltage, 415 V
1.7 Locked rotor current, 0.5A(approx.)full load current
1.8 Efficiency of motor at full load, % 85% (approx.)
1.9 Temp.rise of motor at full load, °C 40 deg.C
1.10 Temperature range over which the control is adjustable, °C 40 ~ 150 deg.C
1.11 Whether fans suitable for continuous operation Yes
1.12 Period of continuous working at full load without fan for ONAN/ 10 minutes
ODAF
1.13 Continuous MVA rating without fan for ONAN/ODAN 37.8 MVA

2 Cooling Oil pumps


2.1 Make and type Axial flow, Glandless,Monoblock, M/s. Flow Oil Pumps Pvt Ltd
2.2 No. of oil pumps on each bank 1 No.
2.3 Whether oil pumps suitable for continuous operation Yes

2.4 No. of standby units for each group. 1 No.

2.5 No. Of radiator/ cooling groups 2x50% banks


2.6 Rated power input of each pump, watts 1500 (approx.)

2.7 Capacity ( cum/minute) 1500 lpm (approx.)


2.8 Rated voltage, 415 V
2.9 Locked rotor current, 3.5 A(approx) full load current

2.10 Efficiency of motor at full load, % 45%(Approx)


2.11 Temp.rise of motor at full load, °C Temperature rise above oil temperature
2.12 Temperature range over which the control is adjustable, °C Temperature rise above oil temperature is minimum. Hence no controls required

2.13 Estimated time constant in hours for 1) 10.5 (approx.)


1. Natural cooling (ONAN) 2) 8.5 (approx.)
2. Forced air cooling (ONAF) 3) 8(approx.)
3. Forced oil cooling (ODAF)
I Core
1 Type of core construction Core type, 3 limb
2 Type of core joints Mitred/Steplapped
3 Net core area in sq. meter 0.3156(Min)
4 Core material &grade of sheet HIB or better Cold rolled grain oriented silicon steel HiB or better
5 Thickness of lamination mm Max. 0.27mm with insulation coating on both sides
6 Insulation of core lamination, mm Inorganic coating provided by steel manufacturers

# Sensitivity: LNT Construction Internal Use
7 Specific loss of core material (Watts/Kg) at 1.6 Tesla 0.67 W/kg. (approx.)

8 Insulation between core laminations Insulation of core material


9 Details of oil duct Adequate
10 Whether in the plane and at right angle to the plane of winding As per TELK design standard
11 Across the plane of laminations As per TELK design standard
12 Design flux density of the core at rated voltage &frequency at principal
tap, Tesla
13.1 1. Core 1.6 T (max.)
13.2 2. Yoke 1.6 T (max.)
14 Maximum flux density allowed 1.76 T (max.)
in the core at extreme over excitation / over fluxing , Tesla

14.1 Power factor of Magnetizing current at normal ratio and frequency

14.2 85 % of rated voltage 0.74(approx.)


14.3 100 % of rated voltage 0.6(approx.)
14.4 105 % of rated voltage 0.55(approx.)
14.5 110 % of rated voltage 0.50(approx.)
15 Power factor of Mag. Current at normal voltage ratio and frequency 0.6 (approx.)

16 Over Excitation withstand time (sec) at 110% / 125% /140% 110% - Continuous
125% - 1 minute
140% - 5 seconds
17 Materials of core clamping plate Mild Steel
18 Thickness of core clamping plate 16mm (minimum)
19 Insulation of core clamping plate Press board
20 Describe Location/ method of core grounding Single point earthing(Terminal board provided for accessability)

21 Details of oil ducts in core As per TELK design standard


22 Guaranteed No load current at 90% /100% /110% rated voltage & 90% 100% 110%
frequency(Amp )
22.1 HV 0.07 (approx.) 0.1 with IS tol. 0.18 (approx.)
22.2 LV 0.13(approx.) 0.2with IS tol. 0.36 (approx.)
23 Noise level (in dB) when energized at normal voltage and normal 83 dB
frequency at no load.

J Winding
1 No. of windings Two
2 Type of Winding ( e.g. Helical / Disc/ layer /pancake) HV - Disc
HV LV - Disc
LV

3 Arrangement of main windings &Geometrical sequence CORE-IV-TAP-HV

4 Winding material HV - Electrolytic Grade copper


HV LV - Electrolytic grade copper
LV
5 Maximum current density allowed, Amp per mm2 HV - 2.5 A/sq.mm (max.) at R Tap
HV LV - 2.5 A/sq.mm (max.) at R Tap
LV

6 Whether windings are Interleaved (HV/LV) No

7 Whether HV windings are Preshrunk (HV/LV) Yes

8 Whether electro-static shields are provided to obtain uniform voltage Yes


distribution in the windings

9 Gauge/area of cross section of conductor, mm2 HV - 66 min (Approx)


HV LV - 154 min (Approx)
LV

# Sensitivity: LNT Construction Internal Use
10 Maximum current density achieved in winding Amps/ mm2 HV - 2.5A/sqmm at R-tap
 HV LV - 2.5A/sqmm at R-tap
 LV
11 Insulating material used for: Kraft
HV turn paper. Kraft paper
LV turn Kraft paper/Press board Press board
Tap winding to earth Kraft paper/Press board
LV to core
Between HV &LV

12 Insulation material thickness in mm used for: As per TELK design standard


HV turn
LV turn
Tap winding to earth
Between HV &LV

13 Type of coil axial support Press board spacers


 HV winding
 LV winding
14 Type of coil radial support Press board spacers and Insulation cylinders
 HV winding
 LV winding

15 Weight of support insulators including insulation cylinders 3000 kg. (approx.)


16 Maximum allowable torque on coil clamping bolts As per TELK manufacturing standard

17 Inter-turn insulation As per TELK manufacturing standard


18 Extent of extreme end turns reinforcement As per TELK manufacturing standard

19 Extent of end turns reinforcement As per TELK manufacturing standard


20 Extent of turns adjacent to tapping As per TELK manufacturing standard
L Minimum design clearance , mm
1 HV to earth in air 2150
2 HV to earth in oil As per TELK design standard
3 LV to earth in air 660
4 LV to earth in oil As per TELK design standard
7 Between HV &LV in Air 2150
8 Between HV &LV in Oil As per TELK design standard
13 Top winding &Yoke As per TELK design standard
14 Bottom winding &Yoke As per TELK design standard
M Insulating Oil
1 Governing standard As per IS 335 - 1993
2 Type of oil As per IS 335 - 1993
3 Spec. resistance (ohmscm) at 27°C /90° C As per IS 335 - 1993
4 Tan delta As per IS 335 - 1993
5 Water content , ppm As per IS 335 - 1993
6 Dielectric strength (BDV), kV As per IS 335 - 1993
7 Characteristics of oil after ageing test As per IS 335 - 1993
8 Sludge content As per IS 335 - 1993
9 Neutralization number As per IS 335 - 1993
10 Quantity of oil Ltrs
11 In the transformer tank 32700 L (approx.)
12 In each radiator 185 Ltrs. (approx.)
13 Total quantity 36000 L (approx.)
14 10% excess oil furnished? Yes
N Conservator
1 Details of oil preservation equipment offered Air cell type conservator with silicagel breather

2 Oil preservation system provided (Yes/No) Yes

3 Total volume of conservator (Ltr) 3000 (approx.)

# Sensitivity: LNT Construction Internal Use
4 Volume between highest and lowest visible oil levels (Ltr) 2700 (approx.)

5 Details of Air cell .


 Make Unirub / Equiv.
 Type Air cell type
 Material Nitrile Rubber
 Capacity Suitable for above conservator

O Bushing Particulars
1 Manufacturer TELK, Kerala
HV TELK, Kerala
LV
Neutral TELK, Kerala
2 Type of bushings ( .
HV (oil-air type or oil-oil type ) OIPoil to air - type
ondenser RIP Bushing
bushing
LV (oil-air type or oil-oil type ) OIPoil to air - RIP
Condenser Bushing
type bushing
Neutral Plain Porcelain type bushing

3 Reference Standard .
HV IS 2099
LV IS 2099
Neutral IS 2099

4 Rated Voltage in kV HV LV Neutral


245 72.5 36
5 Rated Current in Amp. 1250 1250 1000
6 Lightning impulse voltage (1.20/50µSec.) in kVp 1050 325 95

7 Switching impulse voltage in kV


8 Power Frequency Withstand Voltage (Dry) 460 140 38
9 Power Frequency Withstand Voltage(Wet) 460 140 38

9.1 Wet Flash over voltage, kV NA as per IS 2099


9.2 Dry Flash over voltage, kV NA as per IS 2099
10 Partial discharge level 10 pc 10 pc -
11 Creepage distance in mm 6125 1810 900
12 Creepage distance (protected) NA
13 Whether test tap is provided? If so, power frequency withstand test Yes Yes (Rated for test voltage of 2 KV) -
voltage of test tap,

14 Quantity of oil used in bushing &specification of oil used. 58 L (approx.) 8 L (approx.) -

15 Weight of assembled bushing, Kg 475 kg (approx.) 77 kg.(approx.) 27 kg (approx.)


16 Minimum clearance height for removal of bushings, mm 8200 (approx.)

17 Cantilever strength 1600 N 1250 N 1250 N


18 Terminal connections Through Bushings fitted with terminal connector
P Details of bushing CT
1 Purpose WTI CT
2 Installed on which phase bushing HV/LV HV / LV

3 No. of bushing CTs installed 1 No. in each wdg. i.e. HV-1 No.,LV-1 No.

4 Type Oil immersed ring type


5 Make TELK
6 Reference standard IS 2705
9 CT ratio 179/1.5 -HV,394/1.5-LV
10 Burden, VA 15
11 Class of accuracy Class 3
Q On Load Tap Changer
1 Make TELK/EASUN MR/BHEL/CTR
2 Type High Speed Resistor Transition type
3 Total Tap Range ( + ) percent to ( - ) percent of Voltage +5% to -7.5% in 1.25% steps

# Sensitivity: LNT Construction Internal Use
4 Percent of Voltage per tap step 1.25%
5 No. of steps 10
6 Time (in second) for total tap change 6 sec. (approx.) for 1 step
7 Diverter selector switch transient time, cycles 35~48 milisec.
8 Power flow-uni directional/ bidirectional/restricted bi directional Bidirectional

9 Rated voltage to earth, kV 123


10 Rated currents, Amp 350
11 Control – Manual/Local electrical/ Remote electrical Manual / Local Electrical/Remote Electrical

12 Is suitable for Parallel operation Suitable for parallel opertion with similar transformers
13 Protective devices OSR
14 Auxiliary supply details 415V, 3 Phase, 50 Hz
15 Value of maximum short circuit current, kA 6 kA for 2 sec.(Thermal)
16 Maximum impulse withstand test voltage with 1.2/50μS, full wave 550 kVp
between switch assembly and ground, kV peak

17 Maximum Power frequency test voltage between switch assembly 230 kVrms
and earth, kV rms
18 Maximum impulse withstand test voltage with 1.2/50μs, across the
tapping range, kV peak

19 Approx. overall dimensions of the tap changer (in case of separate NA Since in tank type
tank type), mm
20 Approx. overall weight, (in case of separate tank type), Kg NA Since in tank type

21 Approx. mass of oil ((in case of separate tank type),Kg NA Since in tank type

22 Particulars of the OLTC control panel for installation in the control As per specification
room (RTCC panel)

23 Driving Mechanism box As per specification


24 Make and Type TELK/EASUN MR/BHEL/CTR
25 Details of apparatus proposed Drive motor & Control accessories
R Details of protective devices
1 Pressure release device
1.1 Make &Type Sukrut/Viat. , Auto resealing type
1.2 Minimum pressure the Device is set to rupture. 0.42±0.07 kg/sq.cm

1.3 Rain hood provided or not Not required


1.4 Number of PRD 2
2 FO Temperature measurement system
2.1 Number of channels Not required as per prebid clarification
2.2 Auxiliary supply Not required as per prebid clarification
2.3 No. of auxiliary contacts Not required as per prebid clarification
2.4 Type and make
3 Bucholz relay of main tank
3.1 Type &make I&C/Viat/Sukrut., Double float type
3.2 No. of contacts 2 Nos.
4 Oil Surge relay
4.1 Type &make Provided by OLTC supplier
4.2 No. of contacts 1 No.
5 OTI
5.1 Make &Type Perfect Control/Precimeasure Liquid in metal expansion type
5.2 No. of contacts 2 Nos.
5.3 Setting range 20 ~ 140 deg.C / 0~150 deg.C
6 WTI
6.1 Make &Type Perfect Control/Precimeasure.Thermal image type
6.2 No. of contacts 4 Nos.
6.3 Setting range 30 ~ 150 deg.C / 0~150 deg.C
7 Oil Level gauge
7.1 Type &make Viat / Sukrut /Equivalent Magnetic type

# Sensitivity: LNT Construction Internal Use
7.2 No. of contacts 1 No.
S Lifting Jacks
1 No. of jacks in one set Not Applicable as per specification
2 Type and make Not Applicable as per specification
3 Capacity (tons) Not Applicable as per specification
4 Pitch, mm Not Applicable as per specification
5 Lift, mm Not Applicable as per specification
6 Height in closed position, mm Not Applicable as per specification
7 Mean dia. Of thread, mm Not Applicable as per specification
T Alarm and trip contact ratings of protective devices

1 Rated/making/ breaking currents , Amp &voltage for

1.1 PRD for main tank and OLTC tank 5A, 240V, AC/0.7A, 240V DC (for main tank)
1.2 Bucholz relay 2A, 250V AC/DC
1.3 OTI 5A, 250V AC/DC
1.4 WTI 5A, 250V AC/DC
1.5 Magnetic oil level gauge 5A, 240V AC, 0.25A, 240V DC
U Fittings accessories for each transformer are furnished as per Confirmed that fittings and accessories will be furnished as per
different clauses in the specification (separate sheet giving details, specification..Refer GA drawing TK110811 for bill of materials.
make and bill of materials to be attached)
V Painting: as per annexure –D for the transformer, radiator, Yes
marshalling box, etc. (Yes/No)

W Details of Tank
1 Material Mild Steel
2 Approximate thickness of sheet
3 Sides, mm 10 (approx.)
4 Bottom, mm 12 (approx.) with stiffner
5 Cover (Top), mm 12 (approx.) with stiffner
6 Radiators, mm 1.2(approx.)
7 Pressure mm of Hg As per CBIP
8 Vacuum recommended for Hot oil Circulation <1 torr
9 Vacuum to be maintained during oil filling in transformer tank <1 torr
10 Vacuum to which the tank can be subjected without distortion as per As per CBIP
specification
11 Confirmation of tank designed and tested for vacuum pressure (Ref: Yes
CBIP manual ) (Yes/No)

12 Is the tank lid slopped? Yes


13 Inspection cover provided(Yes/No) Yes
14 Location of inspection cover (Yes/No) Ref: GA Drawing 110811
15 Min. dimensions of inspection cover (provide list of all inspection cover Ref: GA Drawing 110811
with dimension), mm x mm

16 No. of bi-directional wheels provided 4 Nos.


17 Track gauge required for the wheels in transverse axis 1676mm

18 Track gauge required for the wheels in longitudinal axis 1676mm

20 Minimum clearance height for lifting core and winding from tank, mm 8000 (approx.)

21 Minimum clearance height for lifting tank cover, mm 8000 (approx.)

22 Over all transformer dimensions


22.1 Length , mm 11400 (approx.)
22.2 Breadth , mm 6600 (approx.)
22.3 Height , mm 6900 (approx.)
23 Transformer tank dimensions
23.1 Length , mm 6000 (approx.)
23.2 Breadth , mm 3800 (approx.)
23.3 Height , mm 4100 (approx.)
24 Marshalling box dimensions

# Sensitivity: LNT Construction Internal Use
24.1 Length , mm 680 (approx.)
24.2 Breadth , mm 400 (approx.)
24.3 Height , mm 950 (approx.)
25 Weight data
25.1 Core, Kg 33300 (approx.)
25.2 Frame parts, Kg 3500 (approx.)
25.3 Core and frame, Kg 36800 (approx.)
25.4 Weight of core clamp kg -
25.5 Weight of winding kg HV - 8700 (approx.) Weight of copper conductor with paper insulation
HV LV-5600(approx.)
LV
25.6 Total winding Kg 19000(approx) Wt of coil assembly.
25.7 Core and frame winding, Kg 56000 (approx.)
25.8 Tank, Kg
12000 kg. (approx.)
25.9 Tank lid, Kg
25.10 Empty conservator tank, Kg 900 kg. (approx.)
25.11 Each radiator empty , Kg 615 (approx.)
25.12 Total weight of all radiator empty , Kg 3600 (approx.)
25.13 Weight of oil in tank , Kg 27000 (approx.)
25.14 Weight of oil in each conservator, Kg 700 (approx.)
25.15 Weight of oil in each radiators, Kg 152 (approx.)
25.16 Total weight of oil in radiator, Kg 912 (approx.)
25.17 OLTC gear including oil , Kg 700 (approx.)
25.18 Total transport weight of the transformer , Kg 73000 (approx.) excluding oil and main accessories ie, main body

25.19 Total transport weight of the transformer with OLTC and all 112000 (approx.)with all accessories and oil.
accessories, Kg
26 Volume data
26.1 Volume of oil in main tank, liters 32700 (approx.)
26.2 Volume of oil between highest and lowest levels of main conservator, 2700(approx.)
liters
26.3 Volume of oil between highest and lowest levels of OLTC conservator, 100 (approx.)
liters
26.4 Volume of oil in each radiator, liters 185 (approx.)
26.5 Total volume of oil in radiators, liters 1110 (approx.)
26.6 Volume of oil in OLTC, liters 170 (approx.)
26.7 Transformer total oil volume , liters 36000 kL (approx.)
27 Shipping data
27.1 Weight of heaviest package, kg 73000 (approx.) N2 filled
27.2 Dimensions of the largest package (L xB x H) mm 6800x4200x4300 (approx.)

X Tests
1 All in process tests confirmed as per Cl.26.2 &Annexure-E (Yes Yes,As per MQP
/No)
2 All types tests confirmed as per Cl. 26.3 and Annexures E (Yes /No) Yes,As per MQP

3 All routine tests confirmed as per 26.3and Annexures E (Yes /No) Yes,As per MQP

3 All special tests confirmed as per Annexure E and Cl. 26.3 (Yes Yes,As per MQP
/No)
Y Others
1 Transformer will be transported N2 filled
with oil/gas/dry air
2 Quality Assurance Plan: Quality Plan MQP 130181 will be submitted

3 An outline of quality assurance plan used Quality Plan MQP 130181 will be submitted
by the manufacturer attached

4 General warranty for the transformer as per specification As per commercial terms in Purchase order

# Sensitivity: LNT Construction Internal Use
5 Test procedure attached As per IS 2026 and approved quality plan
Z Important design parameters
1 Maximum no load loss at rated condition allowed without any positive 22.5 kW
tolerance (kW).

2 Maximum load loss at rated condition @ 75°C and principal tap 115 kW
allowed without any positive tolerance (kW).

3 Grade of core sheet, Hi-B or better HiB or better


4 Type of winding for HV/LV Disc
5 Design value of flux density 1.6 T (max.)
6 Design value of current density 2.5A/sq.mm (max.) at R Tap
7 Weight of HV winding 8600 (approx.)
8 Weight of LV winding 5400 (approx.)
10 Weight of support insulators including insulation cylinders 3000(approx.)

11 Weight of core(kg) 33300 (approx.)


12 Weight of core clamp 3500 (approx.)
13 Per turn voltage 112(Approx)
14 Conductor cross section HV-66 sq.mm (Min)
LV/HV LV-154 sq.mm (Min)
15 Winding stack height(mm) 1700(approx.)
16 Confirm that the weight of copper in winding and CRGO in core during
detailed design and manufacturing and supply of the transformer is not
less than the values mentioned above.

17 Transformer tank dimensions (mm)(lxbxh) 6000x3800x4100 (approx.)

18 Weight of tank (kg) 12000(Approx)


19 Total volume of oil in tank (Liters) 32700 (approx.)
20 Weight of core, winding and frame(kg) 56000 (approx.)

21 Overall dimensions of the transformer(mm)(lxbxh) 11400x6600x6900 (approx.)

# Sensitivity: LNT Construction Internal Use