SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 220/66 kV
63MVA THREE PHASE AUTO TRANSFORMERS
No. Particulars Offered
A General Data of Manufacturer
1 Name of Manufacturer TELK, ANGAMALLY, KERALA
2 Country of Origin INDIA
3 Business Type of Company (e.g. Manufacturer/ Contractor etc.) Manufacturer
8 No Load Current in percent of Full Load current at rated KV &rated 0.06% with IS tol.
frequency at Normal Tap
3 Limit of hot spot temperature in ° C for which the transformer is 98 deg.C based on yearly weighted average ambient temperature of 32 deg.C
designed
4 Temperature gradient between Oil &Winding. 18 deg.C(Approx)
5 Limit for hot spot temperature For which transformer is designed. 98 deg.C based on yearly weighted average ambient temperature of 32
deg.C.Tank hot spot less than 80 deg Cabove ambient of 50 deg C
D Impedance Data
# Sensitivity: LNT Construction Internal Use
1 Percentage Impedance (HV-LV)at rated 12.3 (Approx) on 63 MVA base HV-LV loading
current and frequency at 75 °C(with tolerance) 12.5 With IS tolerance on 63 MVA base HV-LV loading
At maximum tap 13.0 (Approx) on 63 MVA base HV-LV loading
At Normal tap
At Lowest tap
2 Percentage reactance (HV-LV) at 75 °C 12.29% on 63 MVA base(HV-LV) approx.
At maximum tap 12.499% on 63 MVA base (HV-LV) approx.
At Normal tap 12.99% on 63 MVA base (HV-LV) approx.
At Lowest tap
3 Resistance of windings in ohm at 75 °C HV IV
At maximum tap 0.78 ohm (Max.) 0.08 (Max.)
At Normal tap 0.73ohm (Max.) 0.08 (Max.)
At Lowest tap 0.78 ohm (Max.) 0.08 (Max.)
E Guaranteed Loss
1 Guaranteed maximum no load loss (KW) on principal tap at rated 22.5 kW (max.)
voltage and Frequency
2 No load loss at rated voltage and frequency at highest tap (max.) 22.5 kW (at max tap position and voltage corresponding to max tap)
5 Total losses at normal ratio, rated output, rated voltage, rated frequency 148 kW (Max) 63 MVA Base
and maximum attainable temperature at site including auxiliary losses.
6 Time for which the transformer can run at full load without exceeding 10 minutes without exceeding calculated winding hot spot temperature of 140 ⁰C.
the max. permissible temperature at reference temperature when power
supply to fans
&pumps is cut off (in minutes)
7 Exciting current and power factor 0.2 with IS tolerance p.f - 0.6(approx).
F Efficiency &Regulation
1 Efficiency (in percent) at unity power factor at 75°C
# Sensitivity: LNT Construction Internal Use
4 Vacuum withstand capacity, Tor As per CBIP
5 Number of radiator banks 2x50%
6 Mounting of radiators in each bank Separaterly mounted radiator banks
7 Number of radiators in each bank 3No
8 Type &size of individual radiator valve 80mm Butterfly valve
12 Schematic flow diagram of the cooling system furnished (Yes/No) Ref OGA drawing No TK 110811 Latest revision
H Cooling System
Cooling Fans
1 Make and type Marathon(Alstom)/Khaitan/Equivalent, Propeller type
1.1 No. of fans in each group excluding standby fans 2 Nos
# Sensitivity: LNT Construction Internal Use
7 Specific loss of core material (Watts/Kg) at 1.6 Tesla 0.67 W/kg. (approx.)
16 Over Excitation withstand time (sec) at 110% / 125% /140% 110% - Continuous
125% - 1 minute
140% - 5 seconds
17 Materials of core clamping plate Mild Steel
18 Thickness of core clamping plate 16mm (minimum)
19 Insulation of core clamping plate Press board
20 Describe Location/ method of core grounding Single point earthing(Terminal board provided for accessability)
J Winding
1 No. of windings Two
2 Type of Winding ( e.g. Helical / Disc/ layer /pancake) HV - Disc
HV LV - Disc
LV
# Sensitivity: LNT Construction Internal Use
10 Maximum current density achieved in winding Amps/ mm2 HV - 2.5A/sqmm at R-tap
HV LV - 2.5A/sqmm at R-tap
LV
11 Insulating material used for: Kraft
HV turn paper. Kraft paper
LV turn Kraft paper/Press board Press board
Tap winding to earth Kraft paper/Press board
LV to core
Between HV &LV
# Sensitivity: LNT Construction Internal Use
4 Volume between highest and lowest visible oil levels (Ltr) 2700 (approx.)
O Bushing Particulars
1 Manufacturer TELK, Kerala
HV TELK, Kerala
LV
Neutral TELK, Kerala
2 Type of bushings ( .
HV (oil-air type or oil-oil type ) OIPoil to air - type
ondenser RIP Bushing
bushing
LV (oil-air type or oil-oil type ) OIPoil to air - RIP
Condenser Bushing
type bushing
Neutral Plain Porcelain type bushing
3 Reference Standard .
HV IS 2099
LV IS 2099
Neutral IS 2099
3 No. of bushing CTs installed 1 No. in each wdg. i.e. HV-1 No.,LV-1 No.
# Sensitivity: LNT Construction Internal Use
4 Percent of Voltage per tap step 1.25%
5 No. of steps 10
6 Time (in second) for total tap change 6 sec. (approx.) for 1 step
7 Diverter selector switch transient time, cycles 35~48 milisec.
8 Power flow-uni directional/ bidirectional/restricted bi directional Bidirectional
12 Is suitable for Parallel operation Suitable for parallel opertion with similar transformers
13 Protective devices OSR
14 Auxiliary supply details 415V, 3 Phase, 50 Hz
15 Value of maximum short circuit current, kA 6 kA for 2 sec.(Thermal)
16 Maximum impulse withstand test voltage with 1.2/50μS, full wave 550 kVp
between switch assembly and ground, kV peak
17 Maximum Power frequency test voltage between switch assembly 230 kVrms
and earth, kV rms
18 Maximum impulse withstand test voltage with 1.2/50μs, across the
tapping range, kV peak
19 Approx. overall dimensions of the tap changer (in case of separate NA Since in tank type
tank type), mm
20 Approx. overall weight, (in case of separate tank type), Kg NA Since in tank type
21 Approx. mass of oil ((in case of separate tank type),Kg NA Since in tank type
22 Particulars of the OLTC control panel for installation in the control As per specification
room (RTCC panel)
# Sensitivity: LNT Construction Internal Use
7.2 No. of contacts 1 No.
S Lifting Jacks
1 No. of jacks in one set Not Applicable as per specification
2 Type and make Not Applicable as per specification
3 Capacity (tons) Not Applicable as per specification
4 Pitch, mm Not Applicable as per specification
5 Lift, mm Not Applicable as per specification
6 Height in closed position, mm Not Applicable as per specification
7 Mean dia. Of thread, mm Not Applicable as per specification
T Alarm and trip contact ratings of protective devices
1.1 PRD for main tank and OLTC tank 5A, 240V, AC/0.7A, 240V DC (for main tank)
1.2 Bucholz relay 2A, 250V AC/DC
1.3 OTI 5A, 250V AC/DC
1.4 WTI 5A, 250V AC/DC
1.5 Magnetic oil level gauge 5A, 240V AC, 0.25A, 240V DC
U Fittings accessories for each transformer are furnished as per Confirmed that fittings and accessories will be furnished as per
different clauses in the specification (separate sheet giving details, specification..Refer GA drawing TK110811 for bill of materials.
make and bill of materials to be attached)
V Painting: as per annexure –D for the transformer, radiator, Yes
marshalling box, etc. (Yes/No)
W Details of Tank
1 Material Mild Steel
2 Approximate thickness of sheet
3 Sides, mm 10 (approx.)
4 Bottom, mm 12 (approx.) with stiffner
5 Cover (Top), mm 12 (approx.) with stiffner
6 Radiators, mm 1.2(approx.)
7 Pressure mm of Hg As per CBIP
8 Vacuum recommended for Hot oil Circulation <1 torr
9 Vacuum to be maintained during oil filling in transformer tank <1 torr
10 Vacuum to which the tank can be subjected without distortion as per As per CBIP
specification
11 Confirmation of tank designed and tested for vacuum pressure (Ref: Yes
CBIP manual ) (Yes/No)
20 Minimum clearance height for lifting core and winding from tank, mm 8000 (approx.)
# Sensitivity: LNT Construction Internal Use
24.1 Length , mm 680 (approx.)
24.2 Breadth , mm 400 (approx.)
24.3 Height , mm 950 (approx.)
25 Weight data
25.1 Core, Kg 33300 (approx.)
25.2 Frame parts, Kg 3500 (approx.)
25.3 Core and frame, Kg 36800 (approx.)
25.4 Weight of core clamp kg -
25.5 Weight of winding kg HV - 8700 (approx.) Weight of copper conductor with paper insulation
HV LV-5600(approx.)
LV
25.6 Total winding Kg 19000(approx) Wt of coil assembly.
25.7 Core and frame winding, Kg 56000 (approx.)
25.8 Tank, Kg
12000 kg. (approx.)
25.9 Tank lid, Kg
25.10 Empty conservator tank, Kg 900 kg. (approx.)
25.11 Each radiator empty , Kg 615 (approx.)
25.12 Total weight of all radiator empty , Kg 3600 (approx.)
25.13 Weight of oil in tank , Kg 27000 (approx.)
25.14 Weight of oil in each conservator, Kg 700 (approx.)
25.15 Weight of oil in each radiators, Kg 152 (approx.)
25.16 Total weight of oil in radiator, Kg 912 (approx.)
25.17 OLTC gear including oil , Kg 700 (approx.)
25.18 Total transport weight of the transformer , Kg 73000 (approx.) excluding oil and main accessories ie, main body
25.19 Total transport weight of the transformer with OLTC and all 112000 (approx.)with all accessories and oil.
accessories, Kg
26 Volume data
26.1 Volume of oil in main tank, liters 32700 (approx.)
26.2 Volume of oil between highest and lowest levels of main conservator, 2700(approx.)
liters
26.3 Volume of oil between highest and lowest levels of OLTC conservator, 100 (approx.)
liters
26.4 Volume of oil in each radiator, liters 185 (approx.)
26.5 Total volume of oil in radiators, liters 1110 (approx.)
26.6 Volume of oil in OLTC, liters 170 (approx.)
26.7 Transformer total oil volume , liters 36000 kL (approx.)
27 Shipping data
27.1 Weight of heaviest package, kg 73000 (approx.) N2 filled
27.2 Dimensions of the largest package (L xB x H) mm 6800x4200x4300 (approx.)
X Tests
1 All in process tests confirmed as per Cl.26.2 &Annexure-E (Yes Yes,As per MQP
/No)
2 All types tests confirmed as per Cl. 26.3 and Annexures E (Yes /No) Yes,As per MQP
3 All routine tests confirmed as per 26.3and Annexures E (Yes /No) Yes,As per MQP
3 All special tests confirmed as per Annexure E and Cl. 26.3 (Yes Yes,As per MQP
/No)
Y Others
1 Transformer will be transported N2 filled
with oil/gas/dry air
2 Quality Assurance Plan: Quality Plan MQP 130181 will be submitted
3 An outline of quality assurance plan used Quality Plan MQP 130181 will be submitted
by the manufacturer attached
4 General warranty for the transformer as per specification As per commercial terms in Purchase order
# Sensitivity: LNT Construction Internal Use
5 Test procedure attached As per IS 2026 and approved quality plan
Z Important design parameters
1 Maximum no load loss at rated condition allowed without any positive 22.5 kW
tolerance (kW).
2 Maximum load loss at rated condition @ 75°C and principal tap 115 kW
allowed without any positive tolerance (kW).
# Sensitivity: LNT Construction Internal Use