JATUH TEGANGAN
JALUR DISTRIBUSI TEGANGAN RENDAH LVMDP 1000KVA
Rumus Perhitungan
Branch Office
Jl. Berbek Industri II No. 21 Sidoarjo 60293
(Kawasan Rungkut Industri Surabaya)
Telp. : (62-31) 8431952, 8434224, 8417399 Faks.: (62-31) 8436672
e-mail : sby-sales@teco-indonesia.com
Representative Office
Kompleks Semarang Indah C-XII No. 5 Semarang Barat 50144 Telp.
: (62-24) 7612310 Faks.: (62-24) 7612363
Certified ISO 9001 by
Factory
Jl. Mayor Oking Km. 2,7 - Gunung Putri, Citeureup 16961
Telp. : (62-21) 875-3401/3405, 8754982 Faks.: (62-21) 8752843
008
www.teco-indonesia.com Certificate No. 167861
Motor types AEEB and AEVB, Class F insulation, 380/ 415V - 50HZ
1
Motor types AEEB and AEVB, Class F insulation, 380/ 415V - 50HZ
1480 315MB 93.6 92.4 90.2 88.5 88.5 81.5 340 2190 311 2005 122 110 96 210 14.3 1070 1180
2
3
4
5
6
Standard Specification and Features
We supply a full range of general purpose induction motors, and also produce made-to-order motors to
answer special needs ranging up to 100.000 HP 13.8 kv
CONSTRUCTION DATA
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight
trunking and outdoors if increased mechanical PVC Insulation
Section protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or
PVC Inner Sheath
mm� operation.
mm kg/km
1.5 17.9 611 Special Features on Request : Steel Flat Wire Armor
• Fire Resistance Steel Tape
2.5 18.0 630
• Oil Resistance PVC Sheath
4 17.8 648 • UV Resistance
6 18.1 687 • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
10 20.5 881
• Heat Resistance
16 22.5 1,085 • Anti Termite
25 25.5 1,428 • Anti Rodent
• Low Smoke Zero Halogen
35 27.5 1,753
50 31.0 2,120
70 35.0 2,716 Note :
95 39.5 3,528 Conductor Shape
120 43.0 4,177 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
150 47.0 5,012 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
185 52.0 6,116 25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
240 58.0 7,695
Standard Packing
300 64.0 9,384 1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available
length Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
CONSTRUCTION DATA
Application :
Nom. Overall Cable Copper Conductor
Cross Diameter Weight For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
Section PVC Insulation
protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or
operation. PVC Inner Sheath
mm� mm kg/km
Steel Flat Wire Armor
1.5 17.8 620 Special Features on Request : Steel Tape
• Fire Resistance
2.5 18.0 648
• Oil Resistance PVC Sheath
4 18.0 681 • UV Resistance
• Flame Retardant Cat. A, B, C
6 19.0 789
• Flame Retardant Non Category
10 21.5 997 • Heat Resistance
• Anti Termite
16 23.5 1,280
• Anti Rodent
25 27.0 1,709 • Low Smoke Zero Halogen
35 29.5 2,123
50 32.0 2,444
70 36.0 3,217 Note :
Conductor Shape
95 40.5 4,171 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
120 43.5 4,957 conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 48.0 6,011 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
185 52.5 7,319 50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
CONSTRUCTION DATA
Application :
Nom. Overall Cable
Cross Diameter Weight For installation in the ground, indoors, cable Copper Conductor
trunking and outdoors if increased mechanical
Section PVC Insulation
protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or
operation. PVC Inner Sheath
mm� mm kg/km
1.5 17.9 630 Special Features on Request : Steel Flat Wire Armor
• Fire Resistance Steel Tape
2.5 18.0 662
• Oil Resistance
4 19.0 773 PVC Sheath
• UV Resistance
6 20.5 912 • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
10 23.0 1,174
• Heat Resistance
16 25.5 1,520 • Anti Termite
25 29.0 2,053 • Anti Rodent
• Low Smoke Zero Halogen
35 32.0 2,584
50 37.5 3,173
70 40.5 4,087 Note :
95 46.5 5,359 Conductor Shape
120 50.5 6,459 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
150 56.5 7,868 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
185 61.0 9,556 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
240 68.0 12,138
300 74.5 14,773 Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
CONSTRUCTION DATA
Application : PVC Filler
Nom. Overall Cable
Cross Diameter Weight For installation in the ground, indoors, cable Copper Conductor
trunking and outdoors if increased mechanical
Section PVC Insulation
protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or
operation. PVC Inner Sheath
mm� mm kg/km
1.5 17.8 642 Special Features on Request : Steel Flat Wire Armor
• Fire Resistance Steel Tape
2.5 17.9 682 • Oil Resistance
PVC Sheath
4 20.5 891 • UV Resistance
• Flame Retardant Cat. A, B, C
6 22.0 1,056 • Flame Retardant Non Category
• Heat Resistance
10 24.5 1,391 • Anti Termite
16 27.5 1,778 • Anti Rodent
• Low Smoke Zero Halogen
25 32.0 2,463
35 35.0 3,106
50 40.0 3,904 Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
CONSTRUCTION DATA
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight Copper Conductor
and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is PVC Insulation
mm� unlikely.
mm kg/km
1.5 6.1 53 Special Features on Request :
• Fire Resistance PVC Sheath
2.5 6.6 67
4 7.6 94 • Oil Resistance
• UV Resistance
6 8.1 117 • Flame Retardant Cat. A, B, C
10 9.1 166 • Flame Retardant Non Category
16 10.1 229 • Heat Resistance
• Anti Termite
25 11.9 345
• Anti Rodent
35 13.0 444 • Low Smoke Zero Halogen
50 15.0 600 • Nylon Coated
70 16.9 815
95 19.1 1,079
120 21.0 1,325 Note :
150 23.0 1,604 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
185 25.5 2,020
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
240 29.0 2,636 25 - 800 sqmm supplied in non compacted circular stranded (rm) or
300 32.0 3,219 compacted circular stranded (cm) conductor shape
400 35.5 4,087
Standard Packing
500 39.5 5,213 1.5 - 10 sqmm supplied in coil @ 100 m
630 44.0 6,712 16 - 300 sqmm supplied in wooden drum @ 1000 m
800 48.5 8,368 400 - 800 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Capacity at 30° C * Short
circuit current
Nom. DC AC Trefoil Flat
at
Cross Resistance Resistance formation formation in air in ground in air in ground 1 sec
Sect. at 20°C at 70°C
CONSTRUCTION DATA
Application :
Nom. Overall Cable Copper Conductor
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight
and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
PVC Insulation
Area approx. approx. supply networks, if mechanical damage is
mm� unlikely. PVC Inner Sheath
mm kg/km
1.5 12.5 200 Special Features on Request :
• Fire Resistance
2.5 13.4 242 PVC Sheath
• Oil Resistance
4 15.4 330 • UV Resistance
• Flame Retardant Cat. A, B, C
6 16.5 399
• Flame Retardant Non Category
10 18.4 538 • Heat Resistance
• Anti Termite
16 20.5 713
• Anti Rodent
25 24.0 1,001 • Low Smoke Zero Halogen
• Nylon Coated
35 26.0 1,274
50 29.5 1,536
70 33.0 2,066
Note :
95 37.5 2,787 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
120 41.0 3,371
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 45.0 4,114 25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
185 50.0 5,128
Standard Packing
240 56.0 6,581 1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
300 62.0 8,130
Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
in air in ground
Sect. at 20°C at 70°C
CONSTRUCTION DATA
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Copper Conductor
Cross Diameter Weight
and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. PVC Insulation
supply networks, if mechanical damage is
mm� unlikely.
mm kg/km PVC Inner Sheath
1.5 13.0 224 Special Features on Request :
• Fire Resistance
2.5 14.0 277 PVC Sheath
• Oil Resistance
4 16.1 383 • UV Resistance
• Flame Retardant Cat. A, B, C
6 17.3 471
• Flame Retardant Non Category
10 19.4 649 • Heat Resistance
• Anti Termite
16 22.0 875
• Anti Rodent
25 25.0 1,248 • Low Smoke Zero Halogen
• Nylon Coated
35 27.5 1,606
50 30.0 1,857
70 34.0 2,556
Note :
95 38.5 3,428 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
120 41.5 4,152
conductor shape
150 46.0 5,115 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
185 50.5 6,330
50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
240 57.0 8,215
Standard Packing
300 62.5 10,116
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
400 69.0 12,765 120 - 400 sqmm will be suplied in wooden drum on available
length Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
CONSTRUCTION DATA
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Copper Conductor
Cross Diameter Weight
and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. PVC Insulation
supply networks, if mechanical damage is
mm� unlikely.
mm kg/km PVC Inner Sheath
1.5 13.8 259 Special Features on Request :
• Fire Resistance
2.5 15.0 324 PVC Sheath
• Oil Resistance
4 17.3 453 • UV Resistance
• Flame Retardant Cat. A, B, C
6 18.7 563
• Flame Retardant Non Category
10 21.5 794 • Heat Resistance
• Anti Termite
16 23.5 1,083
• Anti Rodent
25 27.5 1,558 • Low Smoke Zero Halogen
• Nylon Coated
35 30.0 2,018
50 35.5 2,466
70 39.0 3,334
Note :
95 44.5 4,491 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
120 48.5 5,504
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 54.5 6,787 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
185 59.0 8,392 50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
CONSTRUCTION DATA
Application :
Nom. Overall Cable PVC Filler
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight Copper Conductor
and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is PVC Insulation
mm� unlikely.
mm kg/km
PVC Inner Sheath
1.5 14.8 302 Special Features on Request :
• Fire Resistance
2.5 16.0 382 • Oil Resistance PVC Sheath
35 33.0 2,478
50 38.0 3,161
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%
ELECTRICAL DATA
Conductor Inductance Current - Carrying Short
Nom. DC AC Capacity circuit current
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
DOCUMENT TITLE LAPORAN ANALISIS JATUH TEGANGAN PADA SISTEM JARINGAN TEGANGAN
MENENGAH (JTM) DAN JARINGAN TEGANGAN RENDAH (JTR)
PDM ATRYA
DAFTAR ISI
DAFTAR TABEL.......................................................................................................... 2
DAFTAR LAMPIRAN .................................................................................................... 2
1. DESKRIPSI PROJECT .............................................................................................. 3
2. UMUM .............................................................................................................. 3
3. DATA TEKNIS ...................................................................................................... 4
3.1 Jenis Kabel ................................................................................................. 4
i. Kabel Tegangan Menengah ............................................................................... 4
• SKUTM (Saluran Kabel Udara Tegangan Menengah) ....................................... 4
• SKTM (Saluran Kabel Tanah Tegangan Menengah) ....................................... 4
ii. Kabel Tegangan Rendah .................................................................................. 4
• SUTR (Saluran Udara Tegangan Rendah) .................................................. 4
• SKTR (Saluran Kabel Tanah Tegangan Rendah) .......................................... 8
3.2 Daftar Kabel Listrik ...................................................................................... 14
i. Kabel Tegangan Menengah .............................................................................. 14
ii. Kabel Tegangan Rendah .................................................................................. 14
4. ANALISIS JATUH TEGANGAN .................................................................................. 16
4.1 Definisi .....................................................................................................
16
4.2 Kriteria dan Batasan ...................................................................................... 16
4.3 Rumus Perhitungan Jatuh Tegangan ................................................................... 17
4.4 Tabel Analisis Jatuh Tegangan (Kabel Penghantar Tiga Fasa) ...................................... 19
4.5 Tabel Analisis Jatuh Tegangan (Kabel Penghantar Satu Fasa) ...................................... 21
5. KESIMPULAN...................................................................................................... 21
6. LAMPIRAN ........................................................................................................ 22
PDM Analisis Fasilitas Adaro Page 2 of 22
DAFTAR GAMBAR
Gambar 1 Kabel N2XSY 1 x 35 mm2 12/20kV..........................................................................................................3
Gambar 2 Kabel N2XSEBY 3 x 35 mm2 12/20kV.....................................................................................................4
Gambar 3 Kabel NYY 1 x 150 mm2 0.6/1kV............................................................................................................4
Gambar 4 Kabel NYY 1 x 240 mm2 0.6/1kV............................................................................................................4
Gambar 5 Kabel NYY 1 x 300 mm2 0.6/1kV............................................................................................................5
Gambar 6 Kabel NYY 3 x 1.5 mm2 0.6/1kV.............................................................................................................5
Gambar 7 Kabel NYY 3 x 2.5 mm2 0.6/1kV.............................................................................................................5
Gambar 8 Kabel NYY 3 x 95 mm2 0.6/1kV..............................................................................................................5
Gambar 9 Kabel NYY 4 x 1.5 mm2 0.6/1kV.............................................................................................................6
Gambar 10 Kabel NYY 4 x 2.5 mm2 0.6/1kV...........................................................................................................6
Gambar 11 Kabel NYY 4 x 6 mm2 0.6/1kV..............................................................................................................7
Gambar 12 Kabel NYY 4 x 10 mm2 0.6/1kV............................................................................................................7
Gambar 13 Kabel NYFGBY 4 x 16 mm2 0.6/1kV.....................................................................................................7
Gambar 14 Kabel NYFGBY 4 x 25 mm2 0.6/1kV.....................................................................................................7
Gambar 15 Kabel NYFGBY 2 x 1.5 mm2 0.6/1kV....................................................................................................8
Gambar 16 Kabel NYFGBY 2 x 4 mm2 0.6/1kV.......................................................................................................8
Gambar 17 Kabel NYFGBY 2 x 6 mm2 0.6/1kV.......................................................................................................8
Gambar 18 Kabel NYFGBY 2 x 10 mm2 0.6/1kV.....................................................................................................8
Gambar 19 Kabel NYFGBY 3 x 4 mm2 0.6/1kV.......................................................................................................9
Gambar 20 Kabel NYFGBY 3 x 10 mm2 0.6/1kV.....................................................................................................9
Gambar 21 Kabel NYFGBY 3 x 16 mm2 0.6/1kV.....................................................................................................9
Gambar 22 Kabel NYFGBY 4 x 1.5 mm2 0.6/1kV....................................................................................................9
Gambar 23 Kabel NYFGBY 4 x 2.5 mm2 0.6/1kV....................................................................................................10
Gambar 24 Kabel NYFGBY 4 x 4 mm2 0.6/1kV.......................................................................................................10
Gambar 25 Kabel NYFGBY 4 x 6 mm2 0.6/1kV.......................................................................................................10
Gambar 26 Kabel NYFGBY 4 x 10 mm2 0.6/1kV.....................................................................................................10
Gambar 27 Kabel NYFGBY 4 x 16 mm2 0.6/1kV.....................................................................................................11
Gambar 28 Kabel NYFGBY 4 x 25 mm2 0.6/1kV.....................................................................................................11
Gambar 29 Kabel NYFGBY 4 x 35 mm2 0.6/1kV.....................................................................................................11
Gambar 30 Kabel NYFGBY 4 x 70 mm2 0.6/1kV.....................................................................................................11
Gambar 31 Kabel NYFGBY 4 x 95 mm2 0.6/1kV.....................................................................................................11
Gambar 32 Kabel NYFGBY 4 x 120 mm2 0.6/1kV...................................................................................................11
Gambar 33 Kabel NYFGBY 4 x 185 mm2 0.6/1kV...................................................................................................11
Gambar 34 Kabel NYFGBY 4 x 240 mm2 0.6/1kV...................................................................................................11
DAFTAR TABEL
Tabel 1 Perhitungan Drop Voltase Kabel Penghantar tiga fasa...........................................................................14
Tabel 2 Perhitungan Drop Voltase Kabel Penghantar satu fasa.......................................................................... 17
DAFTAR LAMPIRAN
Lampiran 1 Bagan Distribusi Panel Elektrikal
Lampiran 2 Brosur Kabel Metal Indonesia
Lampiran 3 Regulasi Teknis
PDM Analisis Fasilitas Adaro Page 3 of 22
1 DESKRIPSI PROJECT
Project Name : Pembangunan Dockyard PT. Barito Galangan Nusantara dan
Fasilitasnya secara EPC (Engineering, Procurement & Construction)
Project Location : Desa Tinggiran II, Kec. Tamban, Kab. Barito Kuala, Provinsi
Kalimantan Selatan
Main Contractor : PT. PILAR DASAR MEMBANGUN
Name Tag : SNJ, AVK
Reference : I. SNI 0225:2011 tentang Persyaratan Umum Instalasi Listrik
2011 (PUIL 2011)
II. SNI IEC 60502-1:2009 Kabel daya dengan insulasi terektrusi
dan lengkapan- nya untuk voltase pengenal dari 1 kV (Um = 36
kV) - Bagian 1: Kabel untuk voltase pengenal 1 kV (Um = 1,2
kV) dan 3 kV (Um = 3,6 kV)
III. SNI IEC 60502-2:2009 tentang Kabel daya dengan insulasi
terekstruksi dan lengkapnya untuk voltase pengenal dari 1 kV
(Um = 1,2 kV) sampai dengan 30 kV (Um = 36 kV) - Bagian 2:
Kabel untuk voltase pengenal 6 kV (Um = 7,2 kV) ampai dengan
30 kV (Um = 36 kV)
IV. SPLN 43-2 Tahun 1994 tentang Kabel Tanah Berisolasi dan
Berselubung.
V. SPLN I, No, 475.K/DIR/2010, 11 Agustus 2010 tentang
Konstruksi Jaringan Distribusi Listrik.
VI. SPLN III, No 473.K/DIR/2010, 11 Agustus 2010 tentang Standar
Konstruksi Jaringan Tegangan Rendah Tenaga Listrik.
VII. SPLN V, No 606.K/DIR/2010, 11 Agustus 2010 tentang Standar
Konstruksi Jaringan Tegangan Menengah Tenaga Listrik.
VIII. SPLN 72 : 1987, Lampiran Surat Keputusan Direksi PLN No.
060/DIR/87, 04 Juli 1987 tentang Spesifikasi Design untuk
Jaringan Tegangan Menengah (JTM) dan Jaringan Tegangan
Rendah (JTR).
2 UMUM
Laporan mencakup hasil analisis spesifikasi kabel listrik untuk instalasi Jaringan Tegangan
Menengah (JTM) dan Jaringan Tegangan Rendah (JTR) pada Proyek Pembangunan Dokcyard
PT. Barito Galangan Nusantara beserta fasilitasnya. Secara umum, konsep desain yang
disajikan meliputi perhitungan jatuh tegangan untuk penentuan spesifikasi kabel listrik
tegangan menengah dan tegangan rendah dalam mendukung fungsi jaringan distribusi
kelistrikan sesuai standar PLN maupun SNI yang berlaku.
PDM Analisis Fasilitas Adaro Page 4 of 22
3 DATA TEKNIS
3.1 JENIS KABEL
I. KABEL TEGANGAN MENENGAH
• SKUTM (Saluran Kabel Udara Tegangan Menengah)
1) Jenis Kabel : N2XSY 1 x 35 mm2 12/20 kV
Material : Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed
Standar Spec. : SNI IEC 60502-1:2009
GAMBAR 1
GAMBAR 2
GAMBAR 3
PDM Analisis Fasilitas Adaro Page 5 of 22
GAMBAR 4
GAMBARBAR45
GAMBAR 6
GAMBAR 7
PDM Analisis Fasilitas Adaro Page 6 of 22
GAMBAR 8
GAMBAR 9
GAMBAR 10
GAMBAR 11
PDM Analisis Fasilitas Adaro Page 7 of 22
GAMBAR 12
GAMBAR 13
GAMBAR 14
PDM Analisis Fasilitas Adaro Page 8 of 22
GAMBAR 15
GAMBAR 16
GAMBAR 17
PDM Analisis Fasilitas Adaro Page 9 of 22
GAMBAR 18
GAMBAR 19
6) Jenis Kabel : NYFGBY 3 x 10 mm2 0.6/1 kV
Material : Copper Conductor, PVC Insulated, Steel Flat Wire Armor, PVC Sheathed
Standar Spec. : SNI IEC 60502-1:2009
GAMBAR 20
GAMBAR 21
PDM Analisis Fasilitas Adaro Page 10 of 22
GAMBAR 22
9) Jenis Kabel : NYFGBY 4 x 2.5 mm2 0.6/1 kV
Material : Copper Conductor, PVC Insulated, Steel Flat Wire Armor, PVC Sheathed
Standar Spec. : SNI IEC 60502-1:2009
GAMBAR 23
GAMBAR 24
GAMBAR 25
PDM Analisis Fasilitas Adaro Page 11 of 22
GAMBAR 26
\
GAMBAR 27
GAMBAR 28
GAMBAR 29
PDM Analisis Fasilitas Adaro Page 12 of 22
GAMBAR 30
GAMBAR 31
GAMBAR 32
GAMBAR 33
PDM Analisis Fasilitas Adaro Page 13 of 22
GAMBAR 34
PDM Analisis Fasilitas Adaro Page 14 of 22
Catatan :
SKTM : Saluran Kabel Tanah Tegangan Menengah
SKUTM : Saluran Kabel Udara Tegangan Menengah
79. PP/LP Workshop ke MCB Box Container 1 NYY 3 x 1.5 mm2 SUTR
80. PP/LP Workshop ke MCB Box Container 2 NYY 3 x 1.5 mm2 SUTR
Catatan :
SKTR : Saluran Kabel Tanah Tegangan Rendah
SUTR : Saluran Udara Tegangan Rendah
4. ANALISIS JATUH
Jatuh tegangan merupakan besarnya tegangan yang hilang pada suatu penghantar. Jatuh
tegangan pada saluran tenaga listrik secara umum berbanding lurus dengan panjang saluran
dan beban serta berbanding terbalik dengan luas penampang penghantar. Besarnya jatuh
tegangan dinyatakan dalam persen atau dalam besaran Volt. Besarnya batas atas dan bawah
ditentukan oleh kebijaksanaan perusahaan kelistrikan. Perhitungan jatuh tegangan praktis
pada batas-batas tertentu dengan hanya menghitung besarnya tahanan masih dapat
dipertimbangkan, namun pada sistem jaringan khususnya pada sistem tegangan menengah
masalah induktansi dan kapasitansinya diperhitungkan karena nilainya cukup berarti.” (Buku
I, PT.PLN (Persero),2010: Kriteria Disain Enjinering Konstruksi Jaringan Distribusi Tenaga
Listrik, Bag 2.1 tentang Jatuh Tegangan)
a. Sesuai standar SPLN 72:1987 tentang Spesifikasi desain untuk Jaringan Tegangan Menengah
(JTM) dan Jaringan Tegangan Rendah (JTR), pengaturan tegangan dan turun tegangan
ditentukan sebagai berikut :
i. Turun tegangan pada JTM dibolehkan 2% dari tegangan kerja untuk sistem Spindel dan
Gugus.
ii. Turun tegangan pada JTM dibolehkan 5% dari tegangan kerja untuk sistem radial.
iii. Turun tegangan pada Transformator distribusi dibolehkan 3% dari tegangan kerja.
iv. Turun tegangan pada Saluran Tegangan Rendah (STR) dibolehkan sampai 4% dari
tegangan kerja.
b. Besarnya jatuh tegangan antar terminal pelanggan dan sembarang titik dari instalasi tidak
boleh melebihi 4 % dari voltase pengenal pada terminal pelanggan.” (SNI PUIL 2011, 2.2.3
Drop Voltase)
c. Direkomendasikan bahwa secara praktis drop voltase antara awal instalasi pelanggan dan
perlengkapan sebaiknya tidak lebih dari 4 % dari voltase nominal instalasi. Kondisi temporer
seperti transien voltase dan varian voltase karena operasi abnormal dapat diabaikan.” (SNI
PUIL 2011, Bag 525 Drop Voltase dalam instalasi pelanggan)
d. Untuk konduktor, arus pengenal dianggap sama dengan KHA. Arus pengenal (untuk perlengkapan)
adalah arus yang ditentukan oleh pabrikan untuk kondisi operasi yang ditentukan dari suatu
perlengkapan rated current. Kapasitas hantar arus (KHA) (kontinu) merupakan arus maksimum yang
dapat dihantarkan secara kontinu oleh suatu konduktor, gawai atau apparatus,
pada kondisi yang ditentukan tanpa suhu kondisi tunaknya melebihi nilai yang ditentukan
(continuous) current-carrying capacity.” (SNI PUIL 2011, 14 MOD istilah dan definisi)
e. Konduktor sirkit akhir yang menyuplai motor tunggal tidak boleh mempunyai KHA kurang dari 125 %
arus pengenal beban penuh. Konduktor sirkit akhir yang mensuplai dua motor atau lebih, tidak
boleh mempunyai KHA kurang dari jumlah arus beban penuh semua motor itu ditambah
PDM Analisis Fasilitas Adaro Page 17 of 22
25 % dari arus beban penuh motor yang terbesar dalam kelompok tersebut. Yang dianggap
motor terbesar ialah yang mempunyai arus beban penuh tertinggi.” (SNI PUIL 2011, Bag
510.5.3 Sirkit motor)
(Buku I, PT.PLN (Persero),2010: Kriteria Disain Enjinering Konstruksi Jaringan Distribusi Tenaga
Listrik, Bag 2.2 tentang Perhitungan Jatuh Tegangan)
maka
=Ṙ
Ṙ : Resistansi per satuan unit panjang (Ω/m), yang nilainya diperoleh dari spesifikasi pabrikan kabel/penghantar
Sistem 1 fasa
PDM Analisis Fasilitas Adaro Page 18 of 22
∆ =
dan
∆ Sistem= 3. fasa Ṙ Ф
Dalam keadaan dimana reaktansi menjadi begitu signifikan dan dipersyaratkan khusus, rumusan
dapat dikembangkan menjadi
∆ Sistem= 3. fasa (Ṙ Ф+Ẋ Ф)
Ẋ = Reaktansi per satuan unit Panjang kabel per kilometer (Ω/m)
PDM Analisis Fasilitas Adaro Page 19 of 22
Tegangan(Volt)
Rc(Ω/km)
l(meter)
Xc(Ω/km)
Beban(A)
Daya(kVA)
ΔV(Volt
(cosF)
%ΔV(%)
NO. DESKRIPSI SPESIFIKASI KABEL
I.
1 MV Cubicle PLN ke MV-01 Konsumen N2XSEbY 3 x 35 Sqmm 20,000 5,540 1.00 160 16 0.67 0.10 2.96 0.01%
II.
2 MV-01 Konsumen ke Transformer 1000kVA N2XSY 3 x (1 x 35) Sqmm 0.67 0.12 0.02%
20,000 1,000 1.00 29 13 0.43
3 MV-01 Konsumen ke Transformer 2500kVA N2XSY 3 x (1 x 35) Sqmm 20,000 2,500 1.00 72 17 0.67 0.12 1.42 0.02%
4 MV-01 Konsumen ke Transformer 1600kVA N2XSEbY 3 x 35 Sqmm 0.67 0.10 0.13%
20,000 1,600 1.00 46 429 22.93
5 MV-01 Konsumen ke Transformer 200kVA N2XSEbY 3 x 35 Sqmm 20,000 200 1.00 6 394 0.67 0.10 2.63 0.03%
III.
1 Transformer 1000kVA ke LVMDP 1000kVA NYY 16 x (1 x 240) Sqmm 0.02 0.02 0.53%
380 1,000 0.82 1,519 25 2.02
2 Transformer 2500kVA ke LVMDP 2500kVA NYY 32 x (1 x 300) Sqmm 380 2,500 0.81 3,798 26 0.01 0.01 2.32 0.61%
3 Transformer 1600kVA ke LVMDP 1600kVA NYY 24 x (1 x 240) Sqmm 0.02 0.01 0.41%
380 1,600 0.83 2,431 18 1.55
4 Transformer 200kVA ke LVMDP 200kVA NYY 4 x (1 x 150) Sqmm 380 200 0.80 304 16 0.15 0.08 1.43 0.38%
IV.
5 LVMDP 1000kVA ke PP Hydrant Pump NYFGbY 4 x 95 Sqmm 0.23 0.07 2.47%
380 128 0.906 195 90 7.35
6 LVMDP 1000kVA ke SDP WTP & Pump House NYFGbY 4 x 4 Sqmm 380 16 0.86 24 56 5.52 0.10 11.13 3.46%
7 LVMDP 1000kVA ke MCB Box Highmast NYFGbY 4 x 35 Sqmm 0.63 0.08 1.05%
Dockyard 1,2,3,4 380 21 0.90 31 61 1.97
LVMDP 1000kVA ke SDP Winch & Comp. NYFGbY 4 x (4 x 120)
8 House Sqmm 380 623 0.80 946 59 0.05 0.02 4.62 1.75%
9 LVMDP 1000kVA ke SDP Facility 1 NYFGbY 4 x 25 Sqmm 0.87 0.08 0.93%
380 48 0.94 75 14 1.49
NYFGbY 3 x (4 x 240)
10 LVMDP 2500kVA ke SDP Dockyard Barge-1 Sqmm 380 551 0.90 838 113 0.03 0.02 6.30 2.28%
11 LVMDP 2500kVA ke SDP Dockyard Barge-2 NYFGbY 4 x (4 x 70) Sqmm 0.08 0.02 2.67%
380 552 0.80 839 71 7. 84
12 LVMDP 2500kVA ke SDP Dockyard Barge-3 NYFGbY 4 x (4 x 70) Sqmm 380 552 0.80 839 84 0.08 0.02 9.27 3.05%
NYFGbY 4 x (4 x 185)
13 LVMDP 2500kVA ke SDP Dockyard Barge-4 0.03 0.02 2.33%
Sqmm 380 551 0.90 838 127 6.53
14 LVMDP 1600kVA ke SDP Dockyard Tugboat & NYFGbY 2 x (4 x 95) Sqmm 0.12 0.04 3.27%
HEA 380 263 0.80 400 136 10.86
15 LVMDP 1600kVA ke LP Highmast Tugboat 1,2,3 NYFGbY 4 x 6 Sqmm 3.69 0.09 1.39%
380 5 0.90 8 82 3.72
16 LVMDP 1600kVA ke SDP Main Off. & WS NYFGbY 4 x 95 Sqmm 380 148 0.96 225 60 0.23 0.07 5.70 1.91%
17 LVMDP 1600kVA ke SDP MBP Equipment NYFGbY 2 x (4 x 70) Sqmm 0.16 0.04 1.62%
380 199 0.90 299 55 4.58
18 LVMDP 1600kVA ke SDP BGN Equipment NYFGbY 4 x 25 Sqmm 380 49 0.90 74 80 0.87 0.08 8.41 2.62%
19 LVMDP 1600kVA ke SDP Facility 2 NYY 4 x 25 Sqmm 0.87 0.08 0.68%
380 76 0.99 115 6 1.05
20 LVMDP 200kVA ke PP Ship to Shore Connection NYFGbY 4 x 25 Sqmm 0.87 0.08 2.50%
1 380 75 1.00 114 47 8.07
LVMDP 200kVA ke PP Ship to Shore Connection
21 NYFGbY 4 x 25 Sqmm 0.87 0.08 3.00%
2 380 75 1.00 114 58 9.96
22 LVMDP 200kVA ke LP Highmast Jetty NYY 4 x 1.5 Sqmm 380 2 0.90 3 12 14.48 0.10 0.71 0.56%
V.
23 PP Hydrant Pump ke Pompa Hydrant Electric NYY 3 x 95 Sqmm 0.23 0.07 2.69%
380 121 0.91 184 11 0.85
24 PP Hydrant Pump ke Pompa Jockey NYY 3 x 1.5 Sqmm 380 5 0.87 7 12 14.48 0.10 1.84 2.95%
PP Hydrant Pump ke Transfer Pump fr. Intake
25 NYY 3 x 1.5 Sqmm 14.48 0.10 2.60%
Basin to WTP 380 3 0.80 4 6 0.51
26 SDP WTP & Pump House ke PP Transfer Clean NYY 3 x 2.5 Sqmm 8.87 0.10 3.69%
Water 380 9 0.83 14 5 0.88
27 SDP WTP & Pump House ke Mesin WTP NYY 4 x 1.5 Sqmm 14.48 0.10 3.93%
380 3 0.80 4 23 1.76
PDM Analisis Fasilitas Adaro Page 20 of 22
28 MCB Box Highmast Dockyard 1,2,3,4 ke NYFGbY 4 x 16 Sqmm 1.38 0.08 1.25%
Highmast #1 380 10 0.90 16 22 0.76
MCB Box Highmast Dockyard 1,2,3,4 ke
29 NYFGbY 4 x 16 Sqmm 1.38 0.08 2.26%
Highmast #2 380 10 0.90 16 134 4.61
30 SDP Winch & Compressor House ke PP Winch-1 NYFGbY 2 x (4 x 70) Sqmm 380 169 0.80 256 82 0.16 0.04 5.49 3.19%
31 SDP Winch & Compressor House ke PP Winch-2 NYFGbY 2 x (4 x 70) Sqmm 0.16 0.04 1.87%
380 169 0.80 256 7 0.47
SDP Winch & Compressor House ke JB
32 Compressor 1 NYFGbY 4 x 70 Sqmm 380 94 0.80 142 43 0.32 0.07 3.20 2.59%
SDP Winch & Compressor House ke JB
33 NYFGbY 4 x 70 Sqmm 0.32 0.07 2.69%
Compressor 2 380 94 0.80 142 48 3.57
34 SDP Winch & Compressor House ke JB NYFGbY 4 x 70 Sqmm 0.32 0.07 2.77%
Compressor 3 380 94 0.80 142 52 3.87
35 SDP Facility 1 ke PP/LP Waste Storage Solid NYFGbY 4 x 1.5 Sqmm 14.48 0.10 3.04%
380 6 0.99 10 34 8.04
36 SDP Facility 1 ke PP/LP Waste Storage Liquid NYFGbY 4 x 4 Sqmm 380 6 0.99 9 86 5.52 0.10 6.17 2.55%
37 SDP Facility 1 ke PJU Group 1 (#1 - 3) NYFGbY 4 x 1.5 Sqmm 14.48 0.11 1.40%
380 0 0.98 1 101 1.76
38 SDP Facility 1 ke PJU Group 2 (#4 - 6) NYFGbY 4 x 2.5 Sqmm 380 2 0.98 3 93 8.87 0.10 3.97 1.97%
39 SDP Facility 1 ke PJU Group 6 (#16 - 18) NYFGbY 4 x 6 Sqmm 3.69 0.09 2.13%
380 3 0.98 5 140 4.56
40 SDP Facility 1 ke PP/LP Blasting Shed NYFGbY 4 x 10 Sqmm 380 23 0.89 34 86 2.19 0.08 10.11 3.59%
41 SDP Dockyard Barge-1 ke PP Dockyard Barge-4 NYFGbY 4 x 70 Sqmm 0.32 0.07 3.47%
380 89 0.80 135 65 4.53
42 SDP Dockyard Barge-1 ke PP Dockyard Barge-5 NYFGbY 4 x 95 Sqmm 380 88 0.80 134 122 0.23 0.07 6.46 3.98%
43 SDP Dockyard Barge-1 ke PP Dockyard Barge-6 NYFGbY 4 x 185 Sqmm 0.12 0.07 3.81%
380 89 0.80 135 180 5.83
44 SDP Dockyard Barge-4 ke PP Dockyard Barge-1 NYFGbY 4 x 70 Sqmm 380 89 0.80 135 64 0.32 0.07 4.46 3.50%
45 SDP Dockyard Barge-4 ke PP Dockyard Barge-2 NYFGbY 4 x 95 Sqmm 0.23 0.07 3.99%
380 89 0.80 135 120 6.32
46 SDP Dockyard Barge-4 ke PP Dockyard Barge-3 NYFGbY 4 x 185 Sqmm 380 88 0.80 134 176 0.12 0.07 5.68 3.82%
47 LP Highmast Dockyard Tugboat 1,2,3 ke NYFGbY 4 x 4 Sqmm 5.52 0.10 1.48%
Highmast #1 380 5 0.90 8 5 0.34
48 SDP Main Off. & WS ke PP/LP Office lt. 1 NYY 4 x 6 Sqmm 380 33 0.99 50 16 3.69 0.09 5.05 3.24%
49 SDP Main Off. & WS ke PP/LP Office lt. 2 NYY 4 x 16 Sqmm 1.38 0.08 3.48%
380 45 1.00 68 37 5.97
50 SDP Main Off. & WS ke PP/LP Workshop NYY 4 x 16 Sqmm 380 51 0.96 77 21 1.38 0.08 3.78 2.90%
51 SDP Main Off. & WS ke PP Overhead Crane 1 NYY 4 x 2.5 Sqmm 8.87 0.10 3.54%
380 10 0.80 15 33 6.21
52 SDP Main Off. & WS ke PP Overhead Crane 2 NYY 4 x 6 Sqmm 380 10 0.80 15 73 3.69 0.09 5.77 3.43%
53 SDP Facility 2 ke PP/LP New Office NYFGbY 4 x 25 Sqmm 0.87 0.08 3.39%
380 71 1.00 108 63 10.27
VI. PP Transfer Clean Water ke Pompa Transfer AB-
54 01 NYY 3 x 2.5 Sqmm 380 9 0.83 14 6 8.87 0.10 1.06 3.97%
55 PP Transfer Clean Water ke Pompa Transfer AB- NYY 3 x 2.5 Sqmm 8.87 0.10 3.93%
02 380 9 0.83 14 5 0.88
56 Highmast #2 ke Highmast #3 NYFGbY 4 x 16 Sqmm 380 10 0.90 16 60 1.38 0.08 2.06 2.81%
57 Highmast #1 ke Highmast #6 NYFGbY 4 x 16 Sqmm 1.38 0.08 1.69%
380 10 0.90 16 49 1.69
58 PJU Group 2 (#4 - 6) ke PJU Group 3 (#7 - 9) NYFGbY 4 x 2.5 Sqmm 380 1 0.98 2 104 8.87 0.10 3.33 2.85%
59 PJU Group 6 (#16 - 18) ke PJU Group 7 (#19 - 21) NYFGbY 4 x 10 Sqmm 2.19 0.08 2.52%
380 2 0.98 4 114 1.51
PJU Group 6 (#16 - 18) ke PJU Group 12 (#34 -
60 36) NYFGbY 4 x 1.5 Sqmm 380 1 0.98 1 123 14.48 0.11 2.85 2.88%
61 Highmast #1 TBA ke Highmast #2 TBA NYFGbY 3 x 4 Sqmm 5.52 0.10 2.58%
380 5 0.90 8 62 4.19
VII.
62 Highmast #3 ke Highmast #4 NYFGbY 4 x 16 Sqmm 380 10 0.90 16 66 1.38 0.08 2.27 3.41%
63 Highmast #6 ke Highmast #7 NYFGbY 4 x 16 Sqmm 1.38 0.08 2.95%
380 10 0.90 16 139 4.78
64 PJU Group 3 (#7 - 9) ke PJU Group 4 (#10 - 12) NYFGbY 4 x 2.5 Sqmm 380 1 0.98 1 112 8.87 0.10 2.39 3.47%
65 PJU Group 7 (#19 - 21) ke PJU Group 8 (#22 - 24) NYFGbY 4 x 6 Sqmm 3.69 0.09 2.97%
380 2 0.98 3 96 1.71
66 PJU Group 12 (#34 - 36) ke PJU Group 13 (#37) NYFGbY 4 x 1.5 Sqmm 380 0 0.98 0 41 14.48 0.11 0.24 2.99%
PDM Analisis Fasilitas Adaro Page 21 of 22
70 PJU Group 4 (#10 - 12) ke PJU Group 5 (#13 - 15) NYFGbY 4 x 2.5 Sqmm 380 0 0.98 1 108 8.87 0.10 1.15 3.78%
71 PJU Group 8 (#22 - 24) ke PJU Group 9 (#25 - 27) NYFGbY 4 x 4 Sqmm 5.52 0.10 3.46%
380 1 0.98 2 93 1.85
VII.2
71 Highmast #8 ke Highmast #9 NYFGbY 3 x 16 Sqmm 380 5 0.90 8 62 1.38 0.08 1.07 3.50%
72 PJU Group 9 (#25 - 27) ke PJU Group 10 (#28 - NYFGbY 4 x 4 Sqmm 5.52 0.10 3.80%
30) 380 1 0.98 1 97 1.29
VII.3
73 Highmast #9 ke Highmast #10 NYFGbY 2 x 10 Sqmm 380 5 0.90 8 60 2.19 0.08 1.63 3.93%
PJU Group 10 (#28 - 30) ke PJU Group 11 (#31 -
74 NYFGbY 4 x 4 Sqmm 5.52 0.10 3.99%
33) 380 0 0.98 1 108 0.72
Tegangan(Volt)
l(meter)
Rc(Ω/km)
Xc(Ω/km)
Beban(A)
Daya(kVA)
ΔV(Volt
(cosF)
%ΔV(%)
NO. DESKRIPSI SPESIFIKASI KABEL
77 SDP Facility 1 ke MCB Box Bangunan PLN NYFGbY 2 x 1.5 Sqmm 220 1 1.00 3 86 14.48 0.11 6.45 3.86%
78 PP/LP Workshop ke MCB Box Container 1 NYY 3 x 1.5 Sqmm 14.48 0.10 3.80%
220 0 1.00 1 64 1.98
79 PP/LP Workshop ke MCB Box Container 2 NYY 3 x 1.5 Sqmm 220 0 1.00 1 63 14.48 0.10 1.95 3.79%
5. KESIMPULAN
Berdasarkan hasil yang diperoleh dari analisis ini,maka dapat disimpulkan bahwa kabel yang
digunakan pada instalasi Jaringan Tegangan Menengah (JTM) dan Jaringan Tegangan Rendah (JTR)
pada Proyek Pembangunan Dockyard PT. Barito Galangan Nusantara sudah sesuai dengan kaidah
kalkulasi dan spesifikasi teknis, standar, regulasi, dan kode nasional yang berlaku di wilayah
Republik Indonesia.
PDM Analisis Fasilitas Adaro Page 22 of 22