Precast Design Reference As Per SEC

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 43

1997 

UBC VOLUME 2           
(SEISMIC ZONE)
1997 UNIFORM BUILDING CODE APPENDIX CHAPTER 16
APPENDIX CHAPTER 16

Division III—SEISMIC ZONE TABULATION

NOTE: This division has been revised in its entirety.

SECTION 1653 — FOR AREAS OUTSIDE THE UNITED


STATES
Location Seismic Zone Location Seismic Zone
AFRICA Mali
Algeria Bamako 0
Alger 3 Mauritania
Oran 3 Nouakchott 0
Angola Mauritius
Luanda 0 Port Louis 0
Benin Morocco
Cotonou 0 Casablanca 2A
Botswana Port Lyautcy 1
Gaborone 0 Rabat 2A
Burundi Tangier 3
Bujumbura 3 Mozambique
Cameroon Maputo 2A
Douala 0 Niger
Yaounde 0 Niamey 0
Cape Verde Nigeria
Praia 0 Ibadan 0
Central African Republic Kaduna 0
Bangui 0 Lagos 0
Chad Republic of Rwanda
Ndjamena 0 Kigali 3
Congo Senegal
Brazzaville 0 Dakar 0
Djibouti 3 Seychelles
Egypt Victoria 0
Alexandria 2A Sierra Leone
Cairo 2A Freetown 0
Port Said 2A Somalia
Equatorial Guinea Mogadishu 0
Malabo 0 South Africa
Ethiopia Cape Town 3
Addis Ababa 3 Durban 2A
Asmara 3 Johannesburg 2A
Gabon Natal 1
Libreville 0 Pretoria 2A
Gambia Swaziland
Banjul 0 Mbabane 2A
Ghana Tanzania
Accra 3 Dar es Salaam 2A
Guinea Zanzibar 2A
Bissau 1 Togo
Conakry 0 Lome 1
Ivory Coast Tunisia
Abidjan 0 Tunis 3
Kenya Uganda
Nairobi 2A Kampala 2A
Lesotho Upper Volta
Maseru 2A Ougadougou 0
Liberia Zaire
Monrovia 1 Bukavu 3
Libya Kinshasa 0
Tripoli 2A Lubumbashi 2A
Wheelus AFB 2A Zambia
Malagasy Republic Lukasa 2A
Tananarive 0 Zimbabwe
Malawi Harare (Salisbury) 3
Blantyre 3 ASIA
Lilongwe 3 Afghanistan
Zomba 3 Kabul 4
2–401
APPENDIX CHAPTER 16 1997 UNIFORM BUILDING CODE
APPENDIX CHAPTER 16

Location Seismic Zone Location Seismic Zone


Bahrain Laos
Manama 0 Vientiane 1
Bangladesh Lebanon
Dacca 3 Beirut 3
Brunei Malaysia
Bandar Seri Begawan 1 Kuala Lumpur 1
Burma Nepal
Mandalay 3 Kathmandu 4
Rangoon 3 Oman
China Muscat 2A
Beijing 4 Pakistan
Chengdu 3 Islamabad 4
Guangzhou 2A Karachi 4
Nanjing 2A Lahore 2A
Qingdao 3 Peshawar 4
Shanghai 2A Qatar
Shengyang 4 Doha 0
Taiwan Saudi Arabia
All 4 Al Batin 1
Tihwa 4 Dharan 1
Wuhan 2A Jiddah 2A
Xianggang 2A Khamis Mushayf 1
Cyprus Riyadh 0
Nicosia 3 Singapore
India All 1
Bombay 3 South Yemen
Calcutta 2A Aden City 3
Madras 1 Sri Lanka
New Delhi 3 Colombo 0
Indonesia Syria
Bandung 4 Aleppo 3
Jakarta 4 Damascus 3
Medan 3 Thailand
Surabaya 4 Bangkok 1
Iran Chiang Mai 2A
Isfahan 3 Songkhla 0
Shiraz 3 Udorn 1
Tabriz 4 Turkey
Tehran 4 Adana 2A
Ankara 2A
Iraq
Ismir 4
Baghdad 3
Istanbul 4
Basra 1
Karamursel 3
Israel United Arab Emirates
Haifa 3 Abu Dhabi 0
Jerusalem 3 Dubai 0
Tel Aviv 3
Viet Nam
Japan Ho Chi Minh (Saigon) 0
Fukuoka 3 Yemen Aran Republic
Itazuke AFB 3 Sanaa 3
Misawa AFB 3
Naha, Okinawa 4 ATLANTIC OCEAN AREA
Osaka/Kobe 4 Azores
Sapporo 3 All 2A
Tokyo 4 Bermuda
Wakkami 3 All 1
Yokohama 4 CARIBBEAN SEA
Yokota 4 Bahama Islands
Jordan All 1
Amman 3 Cuba
Korea All 2A
Kimhae 1 Dominican Republic
Kwangju 1 Santo Domingo 3
Pusan 1 French West Indies
Seoul 0 Martinique 3
Kuwait Grenada
Kuwait 1 Saint Georges 3
2–402
1997 UNIFORM BUILDING CODE APPENDIX CHAPTER 16
APPENDIX CHAPTER 16

Location Seismic Zone Location Seismic Zone


Haiti Paris 0
Port au Prince 3 Strasbourg 2A
Jamaica Germany, Federal Republic
Kingston 3 Berlin 0
Leeward Islands Bonn 2A
All 3 Bremen 0
Trinidad & Tobago Dusseldorf 1
All 3 Frankfurt 2A
Hamburg 0
CENTRAL AMERICA Munich 1
Belize Stuttgart 2A
Belmopan 2A Vaihigen 2A
Canal Zone Greece
All 2A Athens 3
Costa Rica Kavalla 4
San Jose 3 Makri 4
El Salvador Rhodes 3
San Salvador 4 Sauda Bay 4
Guatemala Thessaloniki 4
Guatemala 4 Hungary
Honduras Budapest 2A
Tegucigalpa 3 Iceland
Mexico Keflavick 3
Ciudad Juarez 2A Reykjavik 4
Guadalajara 3 Ireland
Hermosillo 3 Dublin 0
Matamoros 0 Italy
Mazatlan 2A Aviano AFB 3
Merida 0 Brindisi 0
Mexico City 3 Florence 3
Monterrey 0 Genoa 3
Nuevo Laredo 0 Milan 2A
Tijuana 3 Naples 3
Nicaragua Palermo 3
Managua 4 Rome 2A
Panama Sicily 3
Colon 3 Trieste 3
Galeta 2B Turin 2A
Panama 3 Luxembourg
Luxembourg 1
EUROPE
Malta
Albania Valleta 2A
Tirana 3
Netherlands
Austria All 0
Salzburg 2A Norway
Vienna 2A Oslo 2A
Belgium Poland
Antwerp 1 Krakow 2A
Brussels 2A Poznan 1
Bosnia-Herzegovina Warszawa 1
Belgrade 2A Portugal
Bulgaria Lisbon 4
Sofia 3 Opporto 3
Croatia Romania
Zagreb 3 Bucharest 3
Czechoslovakia Russia
Bratislava 2A Moscow 0
Prague 1 St. Petersburg 0
Denmark Spain
Copenhagen 1 Barcelona 2A
Finland Bilbao 2A
Helsinki 1 Madrid 0
France Rota 2A
Bordeaux 2A Seville 2A
Lyon 1 Sweden
Marseille 3 Goteborg 2A
Nice 3 Stockholm 1
2–403
APPENDIX CHAPTER 16 1997 UNIFORM BUILDING CODE
APPENDIX CHAPTER 16

Location Seismic Zone Location Seismic Zone


Switzerland Peru
Bern 2A Lima 4
Geneva 1 Piura 4
Zurich 2A Uruguay
Ukraine Montevideo 0
Kiev 0 Venezuela
United Kingdom Caracas 4
Belfast 0 Maracaibo 2A
Edinburgh 1 PACIFIC OCEAN AREA
Edzell 1 Australia
Glasgow/Renfrew 1 Brisbane 1
Hamilton 1 Canberra 1
Liverpool 1 Melbourne 1
London 2A Perth 1
Londonderry 1 Sydney 1
Thurso 1 Caroline Islands
NORTH AMERICA Koror, Palau Is. 2A
Greenland Ponape 0
All 1 Fiji
Suva 3
Canada
Argentia NAS 2A Johnson Island
Calgary, Alb 1 All 1
Churchill, Man 0 Mariana Islands
Cold Lake, Alb 1 Guam 3
Edmonton, Alb 1 Saipan 3
E. Harmon AFB 2A Tinian 3
Fort Williams, Ont 0 Marshall Islands
Frobisher N.W. Ter. 0 All 1
Goose Airport 1 New Zealand
Halifax 1 Auckland 3
Montreal, Quebec 3 Wellington 4
Ottawa, Ont 2A Papau New Guinea
St. John’s Nfd 3 Port Moresby 3
Toronto, Ont 1 Phillipine Islands
Vancouver 3 Baguio 3
Winnepeg, Man 1 Cebu 4
SOUTH AMERICA Manila 4
Argentina Samoa
Buenos Aires 0 All 3
Wake Island
Bolivia
All 0
La Paz 3
Santa Cruz 1 The above compilation is a partial listing of seismic zones for
Brazil cities and countries outside of the United States. It has been pro-
Belem 0 vided in this code primarily as a source of information, and may
Belo Horizonte 0 not, in all cases, reflect local ordinances or current scientific in-
Brasilia 0 formation.
Manaus 0
Porto Allegre 0 When an authority having jurisdiction requires seismic design
Recife 0 forces that are higher than would be indicated by the above zones,
Rio de Janeiro 0 the local requirements shall govern. When an authority having ju-
Salvador 0 risdiction requires seismic design forces that are lower than
Sao Paulo 1 would be indicated by the above zones, and these forces have
Chile been developed with consideration of regional tectonics and up-
Santiago 4 to-date geologic and seismologic information, the local require-
Valparaiso 4 ments may be used.
Colombia When no local seismic design requirements exist, properly de-
Bogota 3 termined information on site-specific ground motions may be
Ecuador used to justify a lower seismic zone. Such site-specific ground
Guayaquil 3 motions shall have been developed with proper consideration of
Quito 4 regional tectonics and local geologic and seismologic informa-
Paraguay tion, and shall have no more than a 10 percent chance of being ex-
Asuncion 0 ceeded in a 50-year period.

2–404
TES‐P‐119.19 REV.01           
(SEISMIC ZONE)
TRANSMISSION ENGINEERING STANDARD TES-P-119.19, Rev. 01

7.1.4. Seismic Load

The lateral seismic load shall be computed as per 01-TMSS-01 and


parameters based on KACST's seismic zone category on various regions of
Saudi Arabia. However, in the event that the structure location is located in
Zone 0, the applicable seismic zone shall be Zone 1 category. Moreover,
Importance factor of 1.25 shall be adopted in calculating seismic load.

7.1.5 Soil and Hydrostatic Pressure

In the design of substation basement wall and vertical structures below grade,
provision shall be made for the lateral pressure of adjacent soil. In addition,
allowances shall be made for possible surcharge from fixed or moving loads.
When a portion or whole of the adjacent soil is below a free water surface,
computations shall be based on weight of soil diminished by buoyancy, plus
hydrostatic pressure.

7.1.6 Load Factor and Combination of Loads

Substation structure shall be designed for the worst combination of dead,


imposed and equipment loads with temperature, wind, seismic, and other
effects. The load factor and load combinations to be considered as basis of
design shall conform to the applicable codes of ASCE, ACI, IBC and UBC.

7.2 Substation Building

7.2.1 Foundations

Foundation types for Substation building structures and outdoor equipments


shall be base on the recommendations of the soil investigation agency and as
per good engineering practice and requirements.

7.2.2 Cable Basement/Cable Entry room

Cable basement/Cable Entry Room shall be provided at all Substations


without regard to water table. Basement interior concrete surfaces shall be
coated with two (2) coats of cementitious elastomeric impermeable
membrane after thirty-five (35) days of concrete placement. The second coat
shall be applied within the time interval (between successive coating
application), specified by the manufacturer. Total wet film thickness shall not
be less than 1mm (minimum). Drainage sump shall also be provided.

a. Cable basements shall be provided with drainage sump pits measuring


900mm length x 900mm width x 750mm height. The sump shall be
formed with reinforced concrete at the lowest part of the basement
and shall be covered with an effectively grounded galvanized steel
grating. A collecting channel of minimum 75mm wide x 75mm deep
shall be formed all around the edges of the basement floor at its
junction with the basement walls allowing any water penetrating the
TESP11919R01/ECP Date of Approval: January 21, 2013 PAGE NO. 21 OF 44
1997 UBC VOLUME 2           
(SEISMIC ZONE FACTORS)
CHAP. 16, DIV. IV
1630.1.2 1997 UNIFORM BUILDING CODE
1630.3.2

and strength of elements, which are significant to the distribution 2. Method B: The fundamental period T may be calculated us-
of forces, and shall represent the spatial distribution of the mass ing the structural properties and deformational characteristics of
and stiffness of the structure. In addition, the model shall comply the resisting elements in a properly substantiated analysis. The
with the following: analysis shall be in accordance with the requirements of Section
1630.1.2. The value of T from Method B shall not exceed a value
1. Stiffness properties of reinforced concrete and masonry ele-
30 percent greater than the value of T obtained from Method A in
ments shall consider the effects of cracked sections.
Seismic Zone 4, and 40 percent in Seismic Zones 1, 2 and 3.
2. For steel moment frame systems, the contribution of panel The fundamental period T may be computed by using the fol-
zone deformations to overall story drift shall be included. lowing formula:
1630.1.3 PD effects. The resulting member forces and moments
and the story drifts induced by PD effects shall be considered in
the evaluation of overall structural frame stability and shall be
evaluated using the forces producing the displacements of DS . PD
T + 2p Ǹǒȍ Ǔ ǒ ȍ Ǔ
n

i+1
wi di 2 B g
n

i+1
fi di (30-10)

need not be considered when the ratio of secondary moment to pri- The values of fi represent any lateral force distributed approxi-
mary moment does not exceed 0.10; the ratio may be evaluated for mately in accordance with the principles of Formulas (30-13),
any story as the product of the total dead, floor live and snow load, (30-14) and (30-15) or any other rational distribution. The elastic
as required in Section 1612, above the story times the seismic drift deflections, δi , shall be calculated using the applied lateral
in that story divided by the product of the seismic shear in that forces, fi .
story times the height of that story. In Seismic Zones 3 and 4, PD
need not be considered when the story drift ratio does not exceed 1630.2.3 Simplified design base shear.
0.02/R. 1630.2.3.1 General. Structures conforming to the requirements
1630.2 Static Force Procedure. of Section 1629.8.2 may be designed using this procedure.
1630.2.3.2 Base shear. The total design base shear in a given
1630.2.1 Design base shear. The total design base shear in a direction shall be determined from the following formula:
given direction shall be determined from the following formula:
3.0 C a
Cv I V + W (30-11)
V + W (30-4) R
R T
where the value of Ca shall be based on Table 16-Q for the soil pro-
The total design base shear need not exceed the following: file type. When the soil properties are not known in sufficient
detail to determine the soil profile type, Type SD shall be used in
2.5 C a I (30-5) Seismic Zones 3 and 4, and Type SE shall be used in Seismic Zones
V + W
R 1, 2A and 2B. In Seismic Zone 4, the Near-Source Factor, Na , need
The total design base shear shall not be less than the following: not be greater than 1.3 if none of the following structural irregular-
ities are present: Type 1, 4 or 5 of Table 16-L, or Type 1 or 4 of
V + 0.11 C a I W (30-6) Table 16-M.
In addition, for Seismic Zone 4, the total base shear shall also 1630.2.3.3 Vertical distribution. The forces at each level shall
not be less than the following: be calculated using the following formula:
0.8 ZN v I 3.0 C a
V + W (30-7) Fx + wi (30-12)
R R
where the value of Ca shall be determined in Section 1630.2.3.2.
1630.2.2 Structure period. The value of T shall be determined
from one of the following methods: 1630.2.3.4 Applicability. Sections 1630.1.2, 1630.1.3, 1630.2.1,
1630.2.2, 1630.5, 1630.9, 1630.10 and 1631 shall not apply when
1. Method A: For all buildings, the value T may be approxi- using the simplified procedure.
mated from the following formula:
EXCEPTION: For buildings with relatively flexible structural
systems, the building official may require consideration of PD effects
T + C t (h n) 3ń4 (30-8) and drift in accordance with Sections 1630.1.3, 1630.9 and 1630.10. Ds
shall be prepared using design seismic forces from Section 1630.2.3.2.
WHERE: Where used, DM shall be taken equal to 0.01 times the story
Ct = 0.035 (0.0853) for steel moment-resisting frames. height of all stories. In Section 1633.2.9, Formula (33-1) shall read
3.0 C a
Ct = 0.030 (0.0731) for reinforced concrete moment-resist- Fpx = w px and need not exceed 1.0 Ca wpx , but shall not be
ing frames and eccentrically braced frames. R
less than 0.5 Ca wpx. R and Wo shall be taken from Table 16-N.
Ct = 0.020 (0.0488) for all other buildings.
1630.3 Determination of Seismic Factors.
Alternatively, the value of Ct for structures with concrete or ma-
1630.3.1 Determination of Wo . For specific elements of the
sonry shear walls may be taken as 0.1/ ǸA c (For SI: 0.0743ń ǸA c structure, as specifically identified in this code, the minimum
for Ac in m2). design strength shall be the product of the seismic force over-
The value of Ac shall be determined from the following for- strength factor Wo and the design seismic forces set forth in Sec-
mula: tion 1630. For both Allowable Stress Design and Strength Design,
the Seismic Force Overstrength Factor, Wo , shall be taken from
A c + SA e ƪ0.2 ) (D eńh n) 2ƫ (30-9) Table 16-N.
1630.3.2 Determination of R. The notation R shall be taken from
The value of De /hn used in Formula (30-9) shall not exceed 0.9. Table 16-N.
2–14
TABLE 16-I 1997 UNIFORM BUILDING CODE
TABLE 16-K

TABLE 16-I—SEISMIC ZONE FACTOR Z


ZONE 1 2A 2B 3 4

Z 0.075 0.15 0.20 0.30 0.40


NOTE: The zone shall be determined from the seismic zone map in Figure 16-2.

TABLE 16-J—SOIL PROFILE TYPES


AVERAGE SOIL PROPERTIES FOR TOP 100 FEET (30 480 mm) OF SOIL PROFILE
SOIL PROFILE SOIL PROFILE NAME/GENERIC Shear Wave Velocity, v s Standard Penetration Test, N [or NCH for Undrained Shear Strength, s u psf
TYPE DESCRIPTION feet/second (m/s) cohesionless soil layers] (blows/foot) (kPa)
SA Hard Rock > 5,000
(1,500)
— —
SB Rock 2,500 to 5,000
(760 to 1,500)
SC Very Dense Soil and Soft Rock 1,200 to 2,500 > 50 > 2,000
(360 to 760) (100)
SD Stiff Soil Profile 600 to 1,200 15 to 50 1,000 to 2,000
(180 to 360) (50 to 100)
SE 1 Soft Soil Profile < 600 < 15 < 1,000
(180) (50)
SF Soil Requiring Site-specific Evaluation. See Section 1629.3.1.
1Soil Profile Type S
E also includes any soil profile with more than 10 feet (3048 mm) of soft clay defined as a soil with a plasticity index, PI > 20, wmc w 40 percent
and s u < 500 psf (24 kPa). The Plasticity Index, PI, and the moisture content, wmc , shall be determined in accordance with approved national standards.

TABLE 16-K—OCCUPANCY CATEGORY


SEISMIC SEISMIC WIND
IMPORTANCE IMPORTANCE1 IMPORTANCE
OCCUPANCY CATEGORY OCCUPANCY OR FUNCTIONS OF STRUCTURE FACTOR, I FACTOR, Ip FACTOR, Iw
1. Essential Group I, Division 1 Occupancies having surgery and emergency treatment 1.25 1.50 1.15
facilities2 areas
Fire and police stations
Garages and shelters for emergency vehicles and emergency aircraft
Structures and shelters in emergency-preparedness centers
Aviation control towers
Structures and equipment in government communication centers and other
facilities required for emergency response
Standby power-generating equipment for Category 1 facilities
Tanks or other structures containing housing or supporting water or other
fire-suppression material or equipment required for the protection of Category
1, 2 or 3 structures
2. Hazardous Group H, Divisions 1, 2, 6 and 7 Occupancies and structures therein housing or 1.25 1.50 1.15
facilities supporting toxic or explosive chemicals or substances
Nonbuilding structures housing, supporting or containing quantities of toxic or
explosive substances that, if contained within a building, would cause that
building to be classified as a Group H, Division 1, 2 or 7 Occupancy
3. Special Group A, Divisions 1, 2 and 2.1 Occupancies 1.00 1.00 1.00
occupancy Buildings housing Group E, Divisions 1 and 3 Occupancies with a capacity
structures3 greater than 300 students
Buildings housing Group B Occupancies used for college or adult education
with a capacity greater than 500 students
Group I, Divisions 1 and 2 Occupancies with 50 or more resident incapacitated
patients, but not included in Category 1
Group I, Division 3 Occupancies
All structures with an occupancy greater than 5,000 persons
Structures and equipment in power-generating stations, and other public utility
facilities not included in Category 1 or Category 2 above, and required for
continued operation
4. Standard All structures housing occupancies or having functions not listed in Category 1.00 1.00 1.00
occupancy 1, 2 or 3 and Group U Occupancy towers
structures3
5. Miscellaneous Group U Occupancies except for towers 1.00 1.00 1.00
structures
1The limitation of I for panel connections in Section 1633.2.4 shall be 1.0 for the entire connector.
p
2Structural observation requirements are given in Section 1702.
3For anchorage of machinery and equipment required for life-safety systems, the value of I shall be taken as 1.5.
p

2–30
TABLE 16-N 1997 UNIFORM BUILDING CODE
TABLE 16-N

TABLE 16-N—STRUCTURAL SYSTEMS1


HEIGHT LIMIT FOR
SEISMIC ZONES 3
AND 4 (feet)

BASIC STRUCTURAL SYSTEM2 LATERAL-FORCE-RESISTING SYSTEM DESCRIPTION R o  304.8 for mm


1. Bearing wall system 1. Light-framed walls with shear panels
a. Wood structural panel walls for structures three stories or less 5.5 2.8 65
b. All other light-framed walls 4.5 2.8 65
2. Shear walls
a. Concrete 4.5 2.8 160
b. Masonry 4.5 2.8 160
3. Light steel-framed bearing walls with tension-only bracing 2.8 2.2 65
4. Braced frames where bracing carries gravity load
a. Steel 4.4 2.2 160
b. Concrete3 2.8 2.2 —
c. Heavy timber 2.8 2.2 65
2. Building frame system 1. Steel eccentrically braced frame (EBF) 7.0 2.8 240
2. Light-framed walls with shear panels
a. Wood structural panel walls for structures three stories or less 6.5 2.8 65
b. All other light-framed walls 5.0 2.8 65
3. Shear walls
a. Concrete 5.5 2.8 240
b. Masonry 5.5 2.8 160
4. Ordinary braced frames
a. Steel 5.6 2.2 160
b. Concrete3 5.6 2.2 —
c. Heavy timber 5.6 2.2 65
5. Special concentrically braced frames
a. Steel 6.4 2.2 240
3. Moment-resisting frame 1. Special moment-resisting frame (SMRF)
system a. Steel 8.5 2.8 N.L.
b. Concrete4 8.5 2.8 N.L.
2. Masonry moment-resisting wall frame (MMRWF) 6.5 2.8 160
3. Concrete intermediate moment-resisting frame (IMRF)5 5.5 2.8 —
4. Ordinary moment-resisting frame (OMRF)
a. Steel6 4.5 2.8 160
b. Concrete7 3.5 2.8 —
5. Special truss moment frames of steel (STMF) 6.5 2.8 240
4. Dual systems 1. Shear walls
a. Concrete with SMRF 8.5 2.8 N.L.
b. Concrete with steel OMRF 4.2 2.8 160
c. Concrete with concrete IMRF5 6.5 2.8 160
d. Masonry with SMRF 5.5 2.8 160
e. Masonry with steel OMRF 4.2 2.8 160
f. Masonry with concrete IMRF3 4.2 2.8 —
g. Masonry with masonry MMRWF 6.0 2.8 160
2. Steel EBF
a. With steel SMRF 8.5 2.8 N.L.
b. With steel OMRF 4.2 2.8 160
3. Ordinary braced frames
a. Steel with steel SMRF 6.5 2.8 N.L.
b. Steel with steel OMRF 4.2 2.8 160
c. Concrete with concrete SMRF3 6.5 2.8 —
d. Concrete with concrete IMRF3 4.2 2.8 —
4. Special concentrically braced frames
a. Steel with steel SMRF 7.5 2.8 N.L.
b. Steel with steel OMRF 4.2 2.8 160
5. Cantilevered column building 1. Cantilevered column elements 2.2 2.0 357
systems
6. Shear wall-frame interaction 1. Concrete8 5.5 2.8 160
systems
7. Undefined systems See Sections 1629.6.7 and 1629.9.2 — — —
N.L.—no limit
1See Section 1630.4 for combination of structural systems.
2Basic structural systems are defined in Section 1629.6.
3Prohibited in Seismic Zones 3 and 4.
4Includes precast concrete conforming to Section 1921.2.7.
5Prohibited in Seismic Zones 3 and 4, except as permitted in Section 1634.2.
6Ordinary moment-resisting frames in Seismic Zone 1 meeting the requirements of Section 2211.6 may use a R value of 8.
7 Total height of the building including cantilevered columns.
8Prohibited in Seismic Zones 2A, 2B, 3 and 4. See Section 1633.2.7.

2–32
TABLE 16-O 1997 UNIFORM BUILDING CODE
TABLE 16-Q

FOOTNOTES TO TABLE 16-O—(Continued)


12Seismic restraints may be omitted from electrical raceways, such as cable trays, conduit and bus ducts, if all the following conditions are satisfied:
12.1 Lateral motion of the raceway will not cause damaging impact with other systems.
12.2 Lateral motion of the raceway does not cause loss of system vertical support.
12.3 Rod-hung supports of less than 12 inches (305 mm) in length have top connections that cannot develop moments.
12.4 Support members cantilevered up from the floor are checked for stability.
13Piping, ducts and electrical raceways, which must be functional following an earthquake, spanning between different buildings or structural systems shall be
sufficiently flexible to withstand relative motion of support points assuming out-of-phase motions.
14Vibration isolators supporting equipment shall be designed for lateral loads or restrained from displacing laterally by other means. Restraint shall also be provided,
which limits vertical displacement, such that lateral restraints do not become disengaged. ap and Rp for equipment supported on vibration isolators shall be taken
as 2.5 and 1.5, respectively, except that if the isolation mounting frame is supported by shallow or expansion anchors, the design forces for the anchors calculated
by Formula (32-1), (32-2) or (32-3) shall be additionally multiplied by a factor of 2.0.
15Equipment anchorage shall not be designed such that lateral loads are resisted by gravity friction (e.g., friction clips).
16Expansion anchors, which are required to resist seismic loads in tension, shall not be used where operational vibrating loads are present.
17Movement of components within electrical cabinets, rack- and skid-mounted equipment and portions of skid-mounted electromechanical equipment that may
cause damage to other components by displacing, shall be restricted by attachment to anchored equipment or support frames.
18Batteries on racks shall be restrained against movement in all directions due to earthquake forces.
19Seismic restraints may include straps, chains, bolts, barriers or other mechanisms that prevent sliding, falling and breach of containment of flammable and toxic
materials. Friction forces may not be used to resist lateral loads in these restraints unless positive uplift restraint is provided which ensures that the friction forces
act continuously.

TABLE 16-P—R AND o FACTORS FOR NONBUILDING STRUCTURES


STRUCTURE TYPE R o
1. Vessels, including tanks and pressurized spheres, on braced or unbraced legs. 2.2 2.0
2. Cast-in-place concrete silos and chimneys having walls continuous to the foundations. 3.6 2.0
3. Distributed mass cantilever structures such as stacks, chimneys, silos and skirt-supported vertical vessels. 2.9 2.0
4. Trussed towers (freestanding or guyed), guyed stacks and chimneys. 2.9 2.0
5. Cantilevered column-type structures. 2.2 2.0
6. Cooling towers. 3.6 2.0
7. Bins and hoppers on braced or unbraced legs. 2.9 2.0
8. Storage racks. 3.6 2.0
9. Signs and billboards. 3.6 2.0
10. Amusement structures and monuments. 2.2 2.0
11. All other self-supporting structures not otherwise covered. 2.9 2.0

TABLE 16-Q—SEISMIC COEFFICIENT Ca


SEISMIC ZONE FACTOR, Z
SOIL PROFILE TYPE Z = 0.075 Z = 0.15 Z = 0.2 Z = 0.3 Z = 0.4
SA 0.06 0.12 0.16 0.24 0.32Na
SB 0.08 0.15 0.20 0.30 0.40Na
SC 0.09 0.18 0.24 0.33 0.40Na
SD 0.12 0.22 0.28 0.36 0.44Na
SE 0.19 0.30 0.34 0.36 0.36Na
SF See Footnote 1
1Site-specific geotechnical investigation and dynamic site response analysis shall be performed to determine seismic coefficients for Soil Profile Type S .
F

2–34
1997 UNIFORM BUILDING CODE TABLE 16-R
TABLE 16-U

TABLE 16-R—SEISMIC COEFFICIENT Cv


SEISMIC ZONE FACTOR, Z
SOIL PROFILE TYPE Z = 0.075 Z = 0.15 Z = 0.2 Z = 0.3 Z = 0.4
SA 0.06 0.12 0.16 0.24 0.32Nv
SB 0.08 0.15 0.20 0.30 0.40Nv
SC 0.13 0.25 0.32 0.45 0.56Nv
SD 0.18 0.32 0.40 0.54 0.64Nv
SE 0.26 0.50 0.64 0.84 0.96Nv
SF See Footnote 1
1Site-specific geotechnical investigation and dynamic site response analysis shall be performed to determine seismic coefficients for Soil Profile Type S .
F

TABLE 16-S—NEAR-SOURCE FACTOR Na 1


CLOSEST DISTANCE TO KNOWN SEISMIC SOURCE2,3
SEISMIC SOURCE TYPE v 2 km 5 km w 10 km
A 1.5 1.2 1.0
B 1.3 1.0 1.0
C 1.0 1.0 1.0
1The Near-Source Factor may be based on the linear interpolation of values for distances other than those shown in the table.
2The location and type of seismic sources to be used for design shall be established based on approved geotechnical data (e.g., most recent mapping of active faults by
the United States Geological Survey or the California Division of Mines and Geology).
3The closest distance to seismic source shall be taken as the minimum distance between the site and the area described by the vertical projection of the source on the
surface (i.e., surface projection of fault plane). The surface projection need not include portions of the source at depths of 10 km or greater. The largest value of the
Near-Source Factor considering all sources shall be used for design.

TABLE 16-T—NEAR-SOURCE FACTOR Nv 1


CLOSEST DISTANCE TO KNOWN SEISMIC SOURCE2,3
SEISMIC SOURCE TYPE v 2 km 5 km 10 km w 15 km
A 2.0 1.6 1.2 1.0
B 1.6 1.2 1.0 1.0
C 1.0 1.0 1.0 1.0
1The Near-Source Factor may be based on the linear interpolation of values for distances other than those shown in the table.
2The location and type of seismic sources to be used for design shall be established based on approved geotechnical data (e.g., most recent mapping of active faults by
the United States Geological Survey or the California Division of Mines and Geology).
3The closest distance to seismic source shall be taken as the minimum distance between the site and the area described by the vertical projection of the source on the
surface (i.e., surface projection of fault plane). The surface projection need not include portions of the source at depths of 10 km or greater. The largest value of the
Near-Source Factor considering all sources shall be used for design.

TABLE 16-U—SEISMIC SOURCE TYPE1


SEISMIC SOURCE DEFINITION2
SEISMIC
SOURCE TYPE SEISMIC SOURCE DESCRIPTION Maximum Moment Magnitude, M Slip Rate, SR (mm/year)
A Faults that are capable of producing large magnitude events and that M w 7.0 SR w 5
have a high rate of seismic activity
B All faults other than Types A and C M w 7.0 SR t 5
M t 7.0 SR u 2
M w 6.5 SR t 2
C Faults that are not capable of producing large magnitude earthquakes M < 6.5 SR v 2
and that have a relatively low rate of seismic activity
1Subduction sources shall be evaluated on a site-specific basis.
2Both maximum moment magnitude and slip rate conditions must be satisfied concurrently when determining the seismic source type.

2–35
ASCE/SEI 7‐10                  
(WIND LOAD)
CHAPTER 1 GENERAL

Table 1.5-1 Risk Category of Buildings and Other Structures for Flood, Wind, Snow, Earthquake,
and Ice Loads

Use or Occupancy of Buildings and Structures Risk Category


Buildings and other structures that represent a low risk to human life in the event of failure I

All buildings and other structures except those listed in Risk Categories I, III, and IV II

Buildings and other structures, the failure of which could pose a substantial risk to human life. III
Buildings and other structures, not included in Risk Category IV, with potential to cause a substantial
economic impact and/or mass disruption of day-to-day civilian life in the event of failure.
Buildings and other structures not included in Risk Category IV (including, but not limited to, facilities that
manufacture, process, handle, store, use, or dispose of such substances as hazardous fuels, hazardous
chemicals, hazardous waste, or explosives) containing toxic or explosive substances where their quantity
exceeds a threshold quantity established by the authority having jurisdiction and is sufficient to pose a threat
to the public if released.

Buildings and other structures designated as essential facilities. IV


Buildings and other structures, the failure of which could pose a substantial hazard to the community.
Buildings and other structures (including, but not limited to, facilities that manufacture, process, handle, store,
use, or dispose of such substances as hazardous fuels, hazardous chemicals, or hazardous waste) containing
sufficient quantities of highly toxic substances where the quantity exceeds a threshold quantity established by
the authority having jurisdiction to be dangerous to the public if released and is sufficient to pose a threat to
the public if released.a
Buildings and other structures required to maintain the functionality of other Risk Category IV structures.
a
Buildings and other structures containing toxic, highly toxic, or explosive substances shall be eligible for classification to a lower Risk Category
if it can be demonstrated to the satisfaction of the authority having jurisdiction by a hazard assessment as described in Section 1.5.2 that a
release of the substances is commensurate with the risk associated with that Risk Category.

exceed the member design strength (also called “load R Rain load.
and resistance factor design”). S Snow load.
TEMPORARY FACILITIES: Buildings or
other structures that are to be in service for a limited
time and have a limited exposure period for environ- 1.3 BASIC REQUIREMENTS
mental loadings.
TOXIC SUBSTANCE: As defined in 29 CFR 1.3.1 Strength and Stiffness
1910.1200 Appendix A with Amendments as of Buildings and other structures, and all parts
February 1, 2000. thereof, shall be designed and constructed with
adequate strength and stiffness to provide structural
1.1.2 Symbols and Notations stability, protect nonstructural components and
systems from unacceptable damage, and meet the
Fx A minimum design lateral force applied to level
serviceability requirements of Section 1.3.2.
x of the structure and used for purposes of
Acceptable strength shall be demonstrated using
evaluating structural integrity in accordance with
one or more of the following procedures:
Section 1.4.2.
Wx The portion of the total dead load of the struc- a. the Strength Procedures of Section 1.3.1.1,
ture, D, located or assigned to Level x. b. the Allowable Stress Procedures of Section 1.3.1.2,
D Dead load. or
L Live load. c. subject to the approval of the authority
Lr Roof live load. having jurisdiction for individual projects,
N Notional load used to evaluate conformance with the Performance-Based Procedures of Section
minimum structural integrity criteria. 1.3.1.3.

2
Chapter 29
WIND LOADS ON OTHER STRUCTURES AND
BUILDING APPURTENANCES—MWFRS

29.1 SCOPE 29.1.4 Shielding


There shall be no reductions in velocity pressure
29.1.1 Structure Types due to apparent shielding afforded by buildings and
This chapter applies to the determination of wind other structures or terrain features.
loads on building appurtenances (such as rooftop
structures and rooftop equipment) and other structures
of all heights (such as solid freestanding walls and 29.2 GENERAL REQUIREMENTS
freestanding solid signs, chimneys, tanks, open signs,
lattice frameworks, and trussed towers) using the 29.2.1 Wind Load Parameters Specified in
Directional Procedure. Chapter 26
The steps required for the determination of wind The following wind load parameters shall be
loads on building appurtenances and other structures determined in accordance with Chapter 26:
are shown in Table 29.1-1. – Basic Wind Speed V (Section 26.5)
– Wind directionality Factor Kd (Section 26.6)
User Note: Use Chapter 29 to determine wind pressures – Exposure category (Section 26.7)
on the MWFRS of solid freestanding walls, freestanding – Topographic factor Kzt (Section 26.8)
solid signs, chimneys, tanks, open signs, lattice frame- – Enclosure classification (Section 26.10)
works and trussed towers. Wind loads on rooftop
structures and equipment may be determined from the
provisions of this chapter. The wind pressures are 29.3 VELOCITY PRESSURE
calculated using specific equations based upon the
Directional Procedure. 29.3.1 Velocity Pressure Exposure Coefficient
Based on the exposure category determined in
Section 26.7.3, a velocity pressure exposure coeffi-
29.1.2 Conditions
cient Kz or Kh, as applicable, shall be determined from
A structure whose design wind loads are deter-
Table 29.3-1.
mined in accordance with this section shall comply
For a site located in a transition zone between
with all of the following conditions:
exposure categories that is near to a change in ground
1. The structure is a regular-shaped structure as surface roughness, intermediate values of Kz or Kh,
defined in Section 26.2. between those shown in Table 29.3-1, are permitted,
2. The structure does not have response characteris- provided that they are determined by a rational
tics making it subject to across-wind loading, analysis method defined in the recognized literature.
vortex shedding, or instability due to galloping or
flutter; or it does not have a site location for which 29.3.2 Velocity Pressure
channeling effects or buffeting in the wake of Velocity pressure, qz, evaluated at height z shall
upwind obstructions warrant special consideration. be calculated by the following equation:
qz = 0.00256 KzKztKdV2 (lb/ft2) (29.3-1)
29.1.3 Limitations
2 2
The provisions of this chapter take into consider- [In SI: qz = 0.613 KzKztKdV (N/m ); V in m/s]
ation the load magnification effect caused by gusts in
where
resonance with along-wind vibrations of flexible
structures. Structures not meeting the requirements of Kd = wind directionality factor defined in Section 26.6
Section 29.1.2, or having unusual shapes or response Kz = velocity pressure exposure coefficient defined in
characteristics, shall be designed using recognized Section 29.3.1
literature documenting such wind load effects or shall Kzt = topographic factor defined in Section 26.8.2
use the Wind Tunnel Procedure specified in Chapter 31. V = basic wind speed from Section 26.5

307
TES‐P‐119.19 REV.01           
(WIND SPEED)
TRANSMISSION ENGINEERING STANDARD TES-P-119.19, Rev. 01

7.1.2. Live Loads

The minimum live load values used for structural calculation shall be as
follows:

a. Roof

Not Access : 1.0 kN/m²


Access : 1.5 kN/m²

b. Floor (live load) : 4.8 kN/m²

* Live load at Control & Communication Room shall also be


considered as follows:

Concentrated Load - 5000 N (minimum)

Distributed Load - 7500 N/m2 (minimum, including floor,


Equipment, maintenances and forklift
live loads)

* Live Load at GIS Room shall be considered as follows:

Distributed Load - 12000N/m2 (minimum, including


floor, Equipment, maintenances and
forklift live loads)

* Live Load at Switchgear Room shall be considered as follows:

Distributed Load - 7500N/m2 (minimum, including floor,


Equipment, maintenances and
forklift live loads)

c. Equipment load : To be obtained from the Equipment


Manufacturer

Equipment load shall be treated as live load and floor shall be designed for
the heaviest intensity of equipment load or live load, whichever is higher.
Impact load factor due to dynamic and operating loads shall be per
ASCE/SEI 7.

7.1.3. Wind Load

The design wind loads for the building as a whole or for individual
components and cladding thereof shall be in accordance with ASCE/SEI 7,
with a basic wind speed of 150 km/h and exposure “C” category. Moreover,
Importance factor of 1.15 shall be adopted in calculating wind load.

TESP11919R01/ECP Date of Approval: January 21, 2013 PAGE NO. 20 OF 44


ASCE/SEI 7‐10                 
(WIND LOAD FACTORS)
MINIMUM DESIGN LOADS

Surface Roughness B: Urban and suburban areas, sures, as defined in Section 26.7.3, resulting in the
wooded areas, or other terrain with numerous closely highest wind loads for any wind direction at the site.
spaced obstructions having the size of single-family
dwellings or larger. 26.7.4.2 Envelope Procedure (Chapter 28)
Surface Roughness C: Open terrain with scattered Wind loads for the design of the MWFRS for all
obstructions having heights generally less than 30 ft low-rise buildings designed using the Envelope
(9.1 m). This category includes flat open country and Procedure of Chapter 28 shall be based on the
grasslands. exposure category resulting in the highest wind loads
Surface Roughness D: Flat, unobstructed areas for any wind direction at the site.
and water surfaces. This category includes smooth
mud flats, salt flats, and unbroken ice. 26.7.4.3 Directional Procedure for Building
Appurtenances and Other Structures (Chapter 29)
26.7.3 Exposure Categories Wind loads for the design of building appurte-
Exposure B: For buildings with a mean roof nances (such as rooftop structures and equipment) and
height of less than or equal to 30 ft (9.1 m), Exposure other structures (such as solid freestanding walls and
B shall apply where the ground surface roughness, as freestanding signs, chimneys, tanks, open signs, lattice
defined by Surface Roughness B, prevails in the frameworks, and trussed towers) as specified in
upwind direction for a distance greater than 1,500 ft Chapter 29 shall be based on the appropriate exposure
(457 m). For buildings with a mean roof height greater for each wind direction considered.
than 30 ft (9.1 m), Exposure B shall apply where
Surface Roughness B prevails in the upwind direction 26.7.4.4 Components and Cladding (Chapter 30)
for a distance greater than 2,600 ft (792 m) or 20 times Design wind pressures for components and
the height of the building, whichever is greater. cladding shall be based on the exposure category
Exposure C: Exposure C shall apply for all cases resulting in the highest wind loads for any wind
where Exposures B or D do not apply. direction at the site.
Exposure D: Exposure D shall apply where the
ground surface roughness, as defined by Surface
Roughness D, prevails in the upwind direction for a
26.8 TOPOGRAPHIC EFFECTS
distance greater than 5,000 ft (1,524 m) or 20 times
the building height, whichever is greater. Exposure D
26.8.1 Wind Speed-Up over Hills, Ridges,
shall also apply where the ground surface roughness
and Escarpments
immediately upwind of the site is B or C, and the site
Wind speed-up effects at isolated hills, ridges,
is within a distance of 600 ft (183 m) or 20 times the
and escarpments constituting abrupt changes in the
building height, whichever is greater, from an Expo-
general topography, located in any exposure category,
sure D condition as defined in the previous sentence.
shall be included in the design when buildings and
For a site located in the transition zone between
other site conditions and locations of structures meet
exposure categories, the category resulting in the
all of the following conditions:
largest wind forces shall be used.
EXCEPTION: An intermediate exposure between 1. The hill, ridge, or escarpment is isolated and
the preceding categories is permitted in a transition unobstructed upwind by other similar topographic
zone provided that it is determined by a rational features of comparable height for 100 times the
analysis method defined in the recognized literature. height of the topographic feature (100H) or 2 mi
(3.22 km), whichever is less. This distance shall be
26.7.4 Exposure Requirements. measured horizontally from the point at which the
height H of the hill, ridge, or escarpment is
26.7.4.1 Directional Procedure (Chapter 27) determined.
For each wind direction considered, wind loads 2. The hill, ridge, or escarpment protrudes above the
for the design of the MWFRS of enclosed and height of upwind terrain features within a 2-mi
partially enclosed buildings using the Directional (3.22-km) radius in any quadrant by a factor of two
Procedure of Chapter 27 shall be based on the or more.
exposures as defined in Section 26.7.3. Wind loads for 3. The structure is located as shown in Fig. 26.8-1 in
the design of open buildings with monoslope, pitched, the upper one-half of a hill or ridge or near the
or troughed free roofs shall be based on the expo- crest of an escarpment.

251
CHAPTER 26 WIND LOADS: GENERAL REQUIREMENTS

4. H/Lh ≥ 0.2. The summations are over the height of the building
5. H is greater than or equal to 15 ft (4.5 m) for where
Exposure C and D and 60 ft (18 m) for Exposure B.
hi is the height above grade of level i
Li is the building length at level i parallel to the wind
26.8.2 Topographic Factor
direction
The wind speed-up effect shall be included in the
calculation of design wind loads by using the factor
26.9.3 Approximate Natural Frequency
Kzt:
The approximate lower-bound natural frequency
Kzt = (1 + K1K2K3)2 (26.8-1) (na), in Hertz, of concrete or structural steel buildings
meeting the conditions of Section 26.9.2.1, is permit-
where K1, K2, and K3 are given in Fig. 26.8-1.
ted to be determined from one of the following
If site conditions and locations of structures do
equations:
not meet all the conditions specified in Section 26.8.1
For structural steel moment-resisting-frame
then Kzt = 1.0.
buildings:
na = 22.2/h0.8 (26.9-2)
26.9 GUST-EFFECTS
For concrete moment-resisting frame buildings:
26.9.1 Gust-Effect Factor: The gust-effect factor for na = 43.5/h0.9 (26.9-3)
a rigid building or other structure is permitted to be
For structural steel and concrete buildings with
taken as 0.85.
other lateral-force-resisting systems:
26.9.2 Frequency Determination na = 75/h (26.9-4)
To determine whether a building or structure is
For concrete or masonry shear wall buildings, it
rigid or flexible as defined in Section 26.2, the
is also permitted to use
fundamental natural frequency, n1, shall be established
using the structural properties and deformational na = 385(Cw)0.5/h (26.9-5)
characteristics of the resisting elements in a properly
where
substantiated analysis. Low-Rise Buildings, as defined
2
in 26.2, are permitted to be considered rigid. 100 n ⎛ h ⎞ Ai
Cw = ∑ ⎜ ⎟
AB i =1 ⎝ hi ⎠ ⎡ ⎛ hi ⎞ ⎤
2

26.9.2.1 Limitations for Approximate ⎢1 + 0.83 ⎜ ⎟ ⎥


⎣ ⎝ Di ⎠ ⎦
Natural Frequency
As an alternative to performing an analysis to where
determine n1, the approximate building natural
h = mean roof height (ft)
frequency, na, shall be permitted to be calculated in
n = number of shear walls in the building effective
accordance with Section 26.9.3 for structural steel,
in resisting lateral forces in the direction under
concrete, or masonry buildings meeting the following
consideration
requirements:
AB = base area of the structure (ft2)
1. The building height is less than or equal to 300 ft Ai = horizontal cross-section area of shear wall “i” (ft2)
(91 m), and Di = length of shear wall “i” (ft)
2. The building height is less than 4 times its effective hi = height of shear wall “i” (ft)
length, Leff.
26.9.4 Rigid Buildings or Other Structures
The effective length, Leff, in the direction under For rigid buildings or other structures as defined
consideration shall be determined from the following in Section 26.2, the gust-effect factor shall be taken as
equation: 0.85 or calculated by the formula:
n ⎛ 1 + 1.7 gQ I z Q ⎞
G = 0.925 ⎜
∑h L
i =1
i i
⎝ 1 + 1.7 gv I z ⎠
⎟ (26.9-6)
Leff = n
(26.9-1) 1/ 6
I z = c ⎛⎜ ⎞⎟
33
∑h
i =1
i
⎝ z ⎠
(26.9-7)

254
CHAPTER 29 WIND LOADS ON OTHER STRUCTURES AND BUILDING APPURTENANCES—MWFRS

Velocity Pressure Exposure Coefficients, Kh and Kz


Table 29.3-1

Height above Exposure


ground level, z
B C D
ft (m)
0-15 (0-4.6) 0.57 0.85 1.03
20 (6.1) 0.62 0.90 1.08
25 (7.6) 0.66 0.94 1.12
30 (9.1) 0.70 0.98 1.16
40 (12.2) 0.76 1.04 1.22
50 (15.2) 0.81 1.09 1.27
60 (18) 0.85 1.13 1.31
70 (21.3) 0.89 1.17 1.34
80 (24.4) 0.93 1.21 1.38
90 (27.4) 0.96 1.24 1.40
100 (30.5) 0.99 1.26 1.43
120 (36.6) 1.04 1.31 1.48
140 (42.7) 1.09 1.36 1.52
160 (48.8) 1.13 1.39 1.55
180 (54.9) 1.17 1.43 1.58
200 (61.0) 1.20 1.46 1.61
250 (76.2) 1.28 1.53 1.68
300 (91.4) 1.35 1.59 1.73
350 (106.7) 1.41 1.64 1.78
400 (121.9) 1.47 1.69 1.82
450 (137.2) 1.52 1.73 1.86
500 (152.4) 1.56 1.77 1.89

Notes:
1. The velocity pressure exposure coefficient Kz may be determined from the following
formula:
For 15 ft. ≤ z ≤ zg For z < 15 ft.
2/α
Kz = 2.01 (z/zg) Kz = 2.01 (15/zg)2/α
2. α and zg are tabulated in Table 26.9.1.
3. Linear interpolation for intermediate values of height z is acceptable.
4. Exposure categories are defined in Section 26.7.

310
CHAPTER 26 WIND LOADS: GENERAL REQUIREMENTS

Wind Directionality Factor, Kd


Table 26.6-1

Structure Type Directionality Factor Kd*

Buildings
Main Wind Force Resisting System 0.85
Components and Cladding 0.85

Arched Roofs 0.85

Chimneys, Tanks, and Similar Structures


Square 0.90
Hexagonal 0.95
Round 0.95

Solid Freestanding Walls and Solid


Freestanding and Attached Signs 0.85

Open Signs and Lattice Framework 0.85

Trussed Towers
Triangular, square, rectangular 0.85
All other cross sections 0.95

*Directionality Factor Kd has been calibrated with combinations of loads


specified in Chapter 2. This factor shall only be applied when used in
conjunction with load combinations specified in Sections 2.3 and 2.4.

250
CHAPTER 27 WIND LOADS ON BUILDINGS—MWFRS (DIRECTIONAL PROCEDURE)

qz = velocity pressure calculated using Eq. 27.3-1 at


Table 27.2-1 Steps to Determine MWFRS Wind
height z
Loads for Enclosed, Partially Enclosed and
qh = velocity pressure calculated using Eq. 27.3-1 at
Open Buildings of All Heights
mean roof height h.
Step 1: Determine risk category of building or other The numerical coefficient 0.00256 (0.613 in SI)
structure, see Table 1.4-1 shall be used except where sufficient climatic data are
Step 2: Determine the basic wind speed, V, for the available to justify the selection of a different value of
applicable risk category, see Figure 26.5-1A, B this coefficient for a design application.
or C
Step 3: Determine wind load parameters:
➢ Wind directionality factor, Kd , see Section 27.4 WIND LOADS—MAIN WIND
26.6 and Table 26.6-1 FORCE-RESISTING SYSTEM
➢ Exposure category, see Section 26.7
➢ Topographic factor, Kzt, see Section 26.8 and 27.4.1 Enclosed and Partially Enclosed
Table 26.8-1
Rigid Buildings
➢ Gust Effect Factor, G, see Section 26.9 Design wind pressures for the MWFRS of
➢ Enclosure classification, see Section 26.10
➢ Internal pressure coefficient, (GCpi), see buildings of all heights shall be determined by the
Section 26.11 and Table 26.11-1 following equation:
Step 4: Determine velocity pressure exposure p = qGCp – qi(GCpi) (lb/ft2) (N/m2) (27.4-1)
coefficient, Kz or Kh, see Table 27.3-1
where
Step 5: Determine velocity pressure qz or qh Eq. 27.3-1
q = qz for windward walls evaluated at height z
Step 6: Determine external pressure coefficient, Cp or CN above the ground
➢ Fig. 27.4-1 for walls and flat, gable, hip, q = qh for leeward walls, side walls, and roofs,
monoslope or mansard roofs
evaluated at height h
➢ Fig. 27.4-2 for domed roofs qi = qh for windward walls, side walls, leeward
➢ Fig. 27.4-3 for arched roofs walls, and roofs of enclosed buildings and
➢ Fig. 27.4-4 for monoslope roof, open building
➢ Fig. 27.4-5 for pitched roof, open building for negative internal pressure evaluation in
➢ Fig. 27.4-6 for troughed roof, open building partially enclosed buildings
➢ Fig. 27.4-7 for along-ridge/valley wind load qi = qz for positive internal pressure evaluation in
case for monoslope, pitched or troughed roof, partially enclosed buildings where height z is
open building defined as the level of the highest opening in
Step 7: Calculate wind pressure, p, on each building the building that could affect the positive
surface internal pressure. For buildings sited in
➢ Eq. 27.4-1 for rigid buildings wind-borne debris regions, glazing that is not
➢ Eq. 27.4-2 for flexible buildings impact resistant or protected with an impact
➢ Eq. 27.4-3 for open buildings resistant covering shall be treated as an
opening in accordance with Section 26.10.3.
For positive internal pressure evaluation,
27.3.2 Velocity Pressure
qi may conservatively be evaluated at height
Velocity pressure, qz, evaluated at height z shall
h(qi = qh)
be calculated by the following equation:
G = gust-effect factor, see Section 26.9
qz = 0.00256KzKztKdV2 (lb/ft2) (27.3-1) Cp = external pressure coefficient from Figs.
2 2 27.4-1, 27.4-2 and 27.4-3
[In SI: qz = 0.613KzKztKdV (N/m ); V in m/s]
(GCpi) = internal pressure coefficient from Table
where 26.11-1
Kd = wind directionality factor, see Section 26.6 q and qi shall be evaluated using exposure
Kz = velocity pressure exposure coefficient, see defined in Section 26.7.3. Pressure shall be applied
Section 27.3.1 simultaneously on windward and leeward walls and
Kzt = topographic factor defined, see Section 26.8.2 on roof surfaces as defined in Figs. 27.4-1, 27.4-2 and
V = basic wind speed, see Section 26.5 27.4-3.

260
CHAPTER 27 WIND LOADS ON BUILDINGS—MWFRS (DIRECTIONAL PROCEDURE)

27.4.2 Enclosed and Partially Enclosed where


Flexible Buildings
pp = combined net pressure on the parapet due to
Design wind pressures for the MWFRS of
the combination of the net pressures from
flexible buildings shall be determined from the
the front and back parapet surfaces. Plus
following equation:
(and minus) signs signify net pressure acting
p = qGfCp – qi(GCpi) (lb/ft2) (N/m2) (27.4-2) toward (and away from) the front (exterior)
side of the parapet
where q, qi, Cp, and (GCpi) are as defined in Section
qp = velocity pressure evaluated at the top of the
27.4.1 and Gf (gust-effect factor) is determined in
parapet
accordance with Section 26.9.5.
(GCpn) = combined net pressure coefficient
= +1.5 for windward parapet
27.4.3 Open Buildings with Monoslope, Pitched, = –1.0 for leeward parapet
or Troughed Free Roofs
The net design pressure for the MWFRS of open 27.4.6 Design Wind Load Cases
buildings with monoslope, pitched, or troughed roofs The MWFRS of buildings of all heights, whose
shall be determined by the following equation: wind loads have been determined under the provisions
of this chapter, shall be designed for the wind load
p = qhGCN (27.4-3)
cases as defined in Fig. 27.4-8.
where EXCEPTION: Buildings meeting the require-
ments of Section D1.1 of Appendix D need
qh = velocity pressure evaluated at mean roof height
only be designed for Case 1 and Case 3 of
h using the exposure as defined in Section 26.7.3
Fig. 27.4-8.
that results in the highest wind loads for any
The eccentricity e for rigid structures shall be
wind direction at the site
measured from the geometric center of the building
G = gust-effect factor from Section 26.9
face and shall be considered for each principal axis
CN = net pressure coefficient determined from Figs.
(eX, eY). The eccentricity e for flexible structures shall
27.4-4 through 27.4-7
be determined from the following equation and shall
Net pressure coefficients, CN, include contribu- be considered for each principal axis (eX, eY):
tions from top and bottom surfaces. All load cases
eQ + 1.7 I z ( gQ QeQ ) + ( gR ReR )
2 2
shown for each roof angle shall be investigated.
Plus and minus signs signify pressure acting toward e= (27.4-5)
1 + 1.7 I z ( gQ Q ) + ( gR R )
2 2
and away from the top surface of the roof,
respectively. where
For free roofs with an angle of plane of roof from
eQ = eccentricity e as determined for rigid structures
horizontal θ less than or equal to 5° and containing
fascia panels, the fascia panel shall be considered an in Fig. 27.4-8
inverted parapet. The contribution of loads on the eR = distance between the elastic shear center and
fascia to the MWFRS loads shall be determined using center of mass of each floor
Section 27.4.5 with qp equal to qh. I_z , gQ, Q, gR, and R shall be as defined in Section 26.9
The sign of the eccentricity e shall be plus or
27.4.4 Roof Overhangs minus, whichever causes the more severe load effect.
The positive external pressure on the bottom
surface of windward roof overhangs shall be deter- 27.4.7 Minimum Design Wind Loads
mined using Cp = 0.8 and combined with the top The wind load to be used in the design of the
surface pressures determined using Fig. 27.4-1. MWFRS for an enclosed or partially enclosed
building shall not be less than 16 lb/ft2 (0.77 kN/m2)
multiplied by the wall area of the building and 8 lb/ft2
27.4.5 Parapets
(0.38 kN/m2) multiplied by the roof area of the
The design wind pressure for the effect of
building projected onto a vertical plane normal to the
parapets on MWFRS of rigid or flexible buildings
assumed wind direction. Wall and roof loads shall
with flat, gable, or hip roofs shall be determined by
be applied simultaneously. The design wind force
the following equation:
for open buildings shall be not less than 16 lb/ft2
pp = qp(GCpn) (lb/ft2) (27.4-4) (0.77 kN/m2) multiplied by the area Af.

262
CHAPTER 26 WIND LOADS: GENERAL REQUIREMENTS

4. H/Lh ≥ 0.2. The summations are over the height of the building
5. H is greater than or equal to 15 ft (4.5 m) for where
Exposure C and D and 60 ft (18 m) for Exposure B.
hi is the height above grade of level i
Li is the building length at level i parallel to the wind
26.8.2 Topographic Factor
direction
The wind speed-up effect shall be included in the
calculation of design wind loads by using the factor
26.9.3 Approximate Natural Frequency
Kzt:
The approximate lower-bound natural frequency
Kzt = (1 + K1K2K3)2 (26.8-1) (na), in Hertz, of concrete or structural steel buildings
meeting the conditions of Section 26.9.2.1, is permit-
where K1, K2, and K3 are given in Fig. 26.8-1.
ted to be determined from one of the following
If site conditions and locations of structures do
equations:
not meet all the conditions specified in Section 26.8.1
For structural steel moment-resisting-frame
then Kzt = 1.0.
buildings:
na = 22.2/h0.8 (26.9-2)
26.9 GUST-EFFECTS
For concrete moment-resisting frame buildings:
26.9.1 Gust-Effect Factor: The gust-effect factor for na = 43.5/h0.9 (26.9-3)
a rigid building or other structure is permitted to be
For structural steel and concrete buildings with
taken as 0.85.
other lateral-force-resisting systems:
26.9.2 Frequency Determination na = 75/h (26.9-4)
To determine whether a building or structure is
For concrete or masonry shear wall buildings, it
rigid or flexible as defined in Section 26.2, the
is also permitted to use
fundamental natural frequency, n1, shall be established
using the structural properties and deformational na = 385(Cw)0.5/h (26.9-5)
characteristics of the resisting elements in a properly
where
substantiated analysis. Low-Rise Buildings, as defined
2
in 26.2, are permitted to be considered rigid. 100 n ⎛ h ⎞ Ai
Cw = ∑ ⎜ ⎟
AB i =1 ⎝ hi ⎠ ⎡ ⎛ hi ⎞ ⎤
2

26.9.2.1 Limitations for Approximate ⎢1 + 0.83 ⎜ ⎟ ⎥


⎣ ⎝ Di ⎠ ⎦
Natural Frequency
As an alternative to performing an analysis to where
determine n1, the approximate building natural
h = mean roof height (ft)
frequency, na, shall be permitted to be calculated in
n = number of shear walls in the building effective
accordance with Section 26.9.3 for structural steel,
in resisting lateral forces in the direction under
concrete, or masonry buildings meeting the following
consideration
requirements:
AB = base area of the structure (ft2)
1. The building height is less than or equal to 300 ft Ai = horizontal cross-section area of shear wall “i” (ft2)
(91 m), and Di = length of shear wall “i” (ft)
2. The building height is less than 4 times its effective hi = height of shear wall “i” (ft)
length, Leff.
26.9.4 Rigid Buildings or Other Structures
The effective length, Leff, in the direction under For rigid buildings or other structures as defined
consideration shall be determined from the following in Section 26.2, the gust-effect factor shall be taken as
equation: 0.85 or calculated by the formula:
n ⎛ 1 + 1.7 gQ I z Q ⎞
G = 0.925 ⎜
∑h L
i =1
i i
⎝ 1 + 1.7 gv I z ⎠
⎟ (26.9-6)
Leff = n
(26.9-1) 1/ 6
I z = c ⎛⎜ ⎞⎟
33
∑h
i =1
i
⎝ z ⎠
(26.9-7)

254
MINIMUM DESIGN LOADS

Main Wind Force Resisting System – Part 1 All Heights


Figure 27.4-1 External Pressure Coefficients, Cp
Enclosed, Partially Enclosed Buildings
Walls & Roofs

θ θ

263
CHAPTER 27 WIND LOADS ON BUILDINGS—MWFRS (DIRECTIONAL PROCEDURE)

Main Wind Force Resisting System – Part 1 All Heights


Figure 27.4-1 (cont.) External Pressure Coefficients, Cp
Enclosed, Partially Enclosed Buildings Walls & Roofs
Wall Pressure Coefficients, Cp
Surface L/B Cp Use With
Windward Wall All values 0.8 qz
0-1 -0.5
Leeward Wall 2 -0.3 qh
≥4 -0.2
Side Wall All values -0.7 qh

Roof Pressure Coefficients, Cp, for use with qh


Windward Leeward
Wind Angle, θ (degrees)
Direction Angle, θ (degrees)
h/L 10 15 20 25 30 35 45 ≥60# 10 15 ≥20
-0.7 -0.5 -0.3 -0.2 -0.2 0.0*
Normal ≤0.25 -0.18 0.0* 0.2 0.3 0.3 0.4 0.4 0.01 θ -0.3 -0.5 -0.6
to -0.9 -0.7 -0.4 -0.3 -0.2 -0.2 0.0*
ridge for 0.5 -0.18 -0.18 0.0* 0.2 0.2 0.3 0.4 0.01 θ -0.5 -0.5 -0.6
0 ≥ 10° -1.3** -1.0 -0.7 -0.5 -0.3 -0.2 0.0* -0.7 -0.6 -0.6
≥1.0 -0.18 -0.18 -0.18 0.0* 0.2 0.2 0.3 0.01 θ
Horiz distance from *Value is provided for interpolation
windward edge Cp
Normal purposes.
to 0 to h/2 -0.9, -0.18
ridge for ≤ 0.5 h/2 to h -0.9, -0.18 **Value can be reduced linearly with area
θ < 10 h to 2 h -0.5, -0.18 over which it is applicable as follows
and > 2h -0.3, -0.18
Parallel Area (sq ft) Reduction Factor
0 to h/2 -1.3**, -0.18
to ridge ≥ 1.0 ≤ 100 (9.3 sq m) 1.0
for all θ > h/2 -0.7, -0.18 250 (23.2 sq m) 0.9
≥ 1000 (92.9 sq m) 0.8
Notes:
1. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
2. Linear interpolation is permitted for values of L/B, h/L and θ other than shown. Interpolation shall only be
carried out between values of the same sign. Where no value of the same sign is given, assume 0.0 for
interpolation purposes.
3. Where two values of Cp are listed, this indicates that the windward roof slope is subjected to either positive
or negative pressures and the roof structure shall be designed for both conditions. Interpolation for
intermediate ratios of h/L in this case shall only be carried out between Cp values of like sign.
4. For monoslope roofs, entire roof surface is either a windward or leeward surface.
5. For flexible buildings use appropriate Gf as determined by Section 26.9.4.
6. Refer to Figure 27.4-2 for domes and Figure 27.4-3 for arched roofs.
7. Notation:
B: Horizontal dimension of building, in feet (meter), measured normal to wind direction.
L: Horizontal dimension of building, in feet (meter), measured parallel to wind direction.
h: Mean roof height in feet (meters), except that eave height shall be used for θ ≤ 10 degrees.
z: Height above ground, in feet (meters).
G: Gust effect factor.
qz,qh: Velocity pressure, in pounds per square foot (N/m2), evaluated at respective height.
θ: Angle of plane of roof from horizontal, in degrees.
8. For mansard roofs, the top horizontal surface and leeward inclined surface shall be treated as leeward
surfaces from the table.
9. Except for MWFRS’s at the roof consisting of moment resisting frames, the total horizontal shear shall not
be less than that determined by neglecting wind forces on roof surfaces.
#For roof slopes greater than 80°, use Cp = 0.8

264
CHAPTER 26 WIND LOADS: GENERAL REQUIREMENTS

Main Wind Force Resisting System and Components and All Heights
Cladding
Table 26.11-1 Internal Pressure Coefficient, (GCpi)
Enclosed, Partially Enclosed, and Open Buildings
Walls & Roofs

Enclosure Classification (GCpi )

Open Buildings 0.00

+0.55
Partially Enclosed Buildings
-0.55

+0.18
Enclosed Buildings
-0.18

Notes:
1. Plus and minus signs signify pressures acting toward and away
from the internal surfaces, respectively.
2. Values of (GCpi) shall be used with qz or qh as specified.

3. Two cases shall be considered to determine the critical load


requirements for the appropriate condition:
(i) a positive value of (GCpi) applied to all internal surfaces
(ii) a negative value of (GCpi) applied to all internal surfaces

258
CHAPTER 27 WIND LOADS ON BUILDINGS—MWFRS (DIRECTIONAL PROCEDURE)

27.4.2 Enclosed and Partially Enclosed where


Flexible Buildings
pp = combined net pressure on the parapet due to
Design wind pressures for the MWFRS of
the combination of the net pressures from
flexible buildings shall be determined from the
the front and back parapet surfaces. Plus
following equation:
(and minus) signs signify net pressure acting
p = qGfCp – qi(GCpi) (lb/ft2) (N/m2) (27.4-2) toward (and away from) the front (exterior)
side of the parapet
where q, qi, Cp, and (GCpi) are as defined in Section
qp = velocity pressure evaluated at the top of the
27.4.1 and Gf (gust-effect factor) is determined in
parapet
accordance with Section 26.9.5.
(GCpn) = combined net pressure coefficient
= +1.5 for windward parapet
27.4.3 Open Buildings with Monoslope, Pitched, = –1.0 for leeward parapet
or Troughed Free Roofs
The net design pressure for the MWFRS of open 27.4.6 Design Wind Load Cases
buildings with monoslope, pitched, or troughed roofs The MWFRS of buildings of all heights, whose
shall be determined by the following equation: wind loads have been determined under the provisions
of this chapter, shall be designed for the wind load
p = qhGCN (27.4-3)
cases as defined in Fig. 27.4-8.
where EXCEPTION: Buildings meeting the require-
ments of Section D1.1 of Appendix D need
qh = velocity pressure evaluated at mean roof height
only be designed for Case 1 and Case 3 of
h using the exposure as defined in Section 26.7.3
Fig. 27.4-8.
that results in the highest wind loads for any
The eccentricity e for rigid structures shall be
wind direction at the site
measured from the geometric center of the building
G = gust-effect factor from Section 26.9
face and shall be considered for each principal axis
CN = net pressure coefficient determined from Figs.
(eX, eY). The eccentricity e for flexible structures shall
27.4-4 through 27.4-7
be determined from the following equation and shall
Net pressure coefficients, CN, include contribu- be considered for each principal axis (eX, eY):
tions from top and bottom surfaces. All load cases
eQ + 1.7 I z ( gQ QeQ ) + ( gR ReR )
2 2
shown for each roof angle shall be investigated.
Plus and minus signs signify pressure acting toward e= (27.4-5)
1 + 1.7 I z ( gQ Q ) + ( gR R )
2 2
and away from the top surface of the roof,
respectively. where
For free roofs with an angle of plane of roof from
eQ = eccentricity e as determined for rigid structures
horizontal θ less than or equal to 5° and containing
fascia panels, the fascia panel shall be considered an in Fig. 27.4-8
inverted parapet. The contribution of loads on the eR = distance between the elastic shear center and
fascia to the MWFRS loads shall be determined using center of mass of each floor
Section 27.4.5 with qp equal to qh. I_z , gQ, Q, gR, and R shall be as defined in Section 26.9
The sign of the eccentricity e shall be plus or
27.4.4 Roof Overhangs minus, whichever causes the more severe load effect.
The positive external pressure on the bottom
surface of windward roof overhangs shall be deter- 27.4.7 Minimum Design Wind Loads
mined using Cp = 0.8 and combined with the top The wind load to be used in the design of the
surface pressures determined using Fig. 27.4-1. MWFRS for an enclosed or partially enclosed
building shall not be less than 16 lb/ft2 (0.77 kN/m2)
multiplied by the wall area of the building and 8 lb/ft2
27.4.5 Parapets
(0.38 kN/m2) multiplied by the roof area of the
The design wind pressure for the effect of
building projected onto a vertical plane normal to the
parapets on MWFRS of rigid or flexible buildings
assumed wind direction. Wall and roof loads shall
with flat, gable, or hip roofs shall be determined by
be applied simultaneously. The design wind force
the following equation:
for open buildings shall be not less than 16 lb/ft2
pp = qp(GCpn) (lb/ft2) (27.4-4) (0.77 kN/m2) multiplied by the area Af.

262
ASCE/SEI 7‐10                  
( STORY DRIFT)
MINIMUM DESIGN LOADS

12.11.2.2.7 Walls with Pilasters Where pilasters are 12.12.3 Structural Separation
present in the wall, the anchorage force at the pilas- All portions of the structure shall be designed and
ters shall be calculated considering the additional load constructed to act as an integral unit in resisting
transferred from the wall panels to the pilasters. seismic forces unless separated structurally by a
However, the minimum anchorage force at a floor or distance sufficient to avoid damaging contact as set
roof shall not be reduced. forth in this section.
Separations shall allow for the maximum inelastic
response displacement (δM). δM shall be determined at
12.12 DRIFT AND DEFORMATION
critical locations with consideration for translational
and torsional displacements of the structure including
12.12.1 Story Drift Limit
torsional amplifications, where applicable, using the
The design story drift (Δ) as determined in
following equation:
Sections 12.8.6, 12.9.2, or 16.1, shall not exceed the
allowable story drift (Δa) as obtained from Table Cd δmax
δM = (12.12-1)
12.12-1 for any story. Ie
Where δmax = maximum elastic displacement at the
12.12.1.1 Moment Frames in Structures Assigned to
critical location.
Seismic Design Categories D through F
Adjacent structures on the same property shall be
For seismic force-resisting systems comprised
separated by at least δMT, determined as follows:
solely of moment frames in structures assigned to
Seismic Design Categories D, E, or F, the design
δ MT = ( δ M 1 ) + ( δ M 2 )
2 2
(12.12-2)
story drift (Δ) shall not exceed Δa/ρ for any story.
ρ shall be determined in accordance with Section where δM1 and δM2 are the maximum inelastic response
12.3.4.2. displacements of the adjacent structures at their
adjacent edges.
12.12.2 Diaphragm Deflection Where a structure adjoins a property line not
The deflection in the plane of the diaphragm, as common to a public way, the structure shall be set
determined by engineering analysis, shall not exceed back from the property line by at least the displace-
the permissible deflection of the attached elements. ment δM of that structure.
Permissible deflection shall be that deflection that will EXCEPTION: Smaller separations or property
permit the attached element to maintain its structural line setbacks are permitted where justified by rational
integrity under the individual loading and continue to analysis based on inelastic response to design ground
support the prescribed loads. motions.

Table 12.12-1 Allowable Story Drift, Δ aa,b

Risk Category

Structure I or II III IV
c
Structures, other than masonry shear wall structures, 4 stories or less above the base as 0.025hsx 0.020hsx 0.015hsx
defined in Section 11.2, with interior walls, partitions, ceilings, and exterior wall systems
that have been designed to accommodate the story drifts.
Masonry cantilever shear wall structuresd 0.010hsx 0.010hsx 0.010hsx
Other masonry shear wall structures 0.007hsx 0.007hsx 0.007hsx
All other structures 0.020hsx 0.015hsx 0.010hsx
a
hsx is the story height below Level x.
b
For seismic force-resisting systems comprised solely of moment frames in Seismic Design Categories D, E, and F, the allowable story drift shall
comply with the requirements of Section 12.12.1.1.
c
There shall be no drift limit for single-story structures with interior walls, partitions, ceilings, and exterior wall systems that have been designed
to accommodate the story drifts. The structure separation requirement of Section 12.12.3 is not waived.
d
Structures in which the basic structural system consists of masonry shear walls designed as vertical elements cantilevered from their base or
foundation support which are so constructed that moment transfer between shear walls (coupling) is negligible.

97
ACI 318M‐11                   
(FACTORED LOAD COMBINATIONS)
7869'896%0'32'6)8)&9-0(-2+'3() %'-1 %2('311)28%6= 

',%48)6{786)2+8,%2(7)6:-')%&-0-8=
6)59-6)1)287
'3() '311)28%6=
{+IRIVEP 6{+IRIVEP

 { 7XVYGXYVIW ERH WXVYGXYVEP QIQFIVW WLEPP FI -R XLI  'SHI XLI JEGXSVIH PSEH GSQFMREXMSRW ERH
HIWMKRIH XS LEZI HIWMKR WXVIRKXLW EX EPP WIGXMSRW EX WXVIRKXL VIHYGXMSR JEGXSVW SJ XLI  'SHI [IVI VIZMWIH
PIEWXIUYEPXSXLIVIUYMVIHWXVIRKXLWGEPGYPEXIHJSVXLI ERH QSZIH XS %TTIRHM\ ' 8LI  GSQFMREXMSRW [IVI
JEGXSVIHPSEHWERHJSVGIWMRWYGLGSQFMREXMSRWEWEVI VITPEGIH [MXL XLSWI SJ 7)-%7')  8LI WXVIRKXL
WXMTYPEXIHMRXLMW'SHI VIHYGXMSR JEGXSVW [IVI VITPEGIH [MXL XLSWI SJ XLI 
%TTIRHM\ ' I\GITX XLEX XLI JEGXSV JSV JPI\YVI [EW
 { 1IQFIVW EPWS WLEPP QIIX EPP SXLIV VIUYMVI MRGVIEWIH-RXLI'SHIXLIJEGXSVIHPSEHGSQFMREXMSRW
QIRXWSJXLMW'SHIXSIRWYVIEHIUYEXITIVJSVQERGIEX [IVIVIZMWIHJSVGSRWMWXIRG][MXL%7')7)-
WIVZMGIPSEHPIZIPW
8LIGLERKIW[IVIQEHIXSJYVXLIVYRMJ]XLIHIWMKRTVSJIWWMSR 
{(IWMKRSJWXVYGXYVIWERHWXVYGXYVEPQIQFIVW SRSRIWIXSJPSEHJEGXSVWERHGSQFMREXMSRWERHXSJEGMPMXEXI
YWMRK XLI PSEH JEGXSV GSQFMREXMSRW ERH WXVIRKXL XLI TVSTSVXMSRMRK SJ GSRGVIXI FYMPHMRK WXVYGXYVIW XLEX
VIHYGXMSR JEGXSVW SJ %TTIRHM\ ' WLEPP FI TIVQMXXIH MRGPYHI QIQFIVW SJ QEXIVMEPW SXLIV XLER GSRGVIXI ;LIR
9WI SJ PSEH JEGXSV GSQFMREXMSRW JVSQ XLMW GLETXIV MR YWIH[MXLXLIWXVIRKXLVIHYGXMSRJEGXSVWMRXLIHIWMKRW
GSRNYRGXMSR[MXLWXVIRKXLVIHYGXMSRJEGXSVWSJ%TTIRHM\ JSVKVEZMX]PSEHW[MPPFIGSQTEVEFPIXSXLSWISFXEMRIHYWMRK
'WLEPPRSXFITIVQMXXIH XLI WXVIRKXL VIHYGXMSR ERH PSEH JEGXSVW SJ XLI  ERH
IEVPMIV 'SHIW *SV GSQFMREXMSRW [MXL PEXIVEP PSEHW WSQI
HIWMKRW[MPPFIHMJJIVIRXFYXXLIVIWYPXWSJIMXLIVWIXSJPSEH
JEGXSVWEVIGSRWMHIVIHEGGITXEFPI

'LETXIV  HIJMRIW XLI FEWMG WXVIRKXL ERH WIVZMGIEFMPMX]


GSRHMXMSRWJSVTVSTSVXMSRMRKWXVYGXYVEPGSRGVIXIQIQFIVW

8LIFEWMGVIUYMVIQIRXJSVWXVIRKXLHIWMKRQE]FII\TVIWWIH
EWJSPPS[W

(IWMKR7XVIRKXL 6IUYMVIH7XVIRKXL

 2SQMREP7XVIRKXL  9

-R XLI WXVIRKXL HIWMKR TVSGIHYVI XLI QEVKMR SJ WEJIX] MW


TVSZMHIH F] QYPXMTP]MRK XLI WIVZMGI PSEH F] E PSEH JEGXSV
ERHXLIRSQMREPWXVIRKXLF]EWXVIRKXLVIHYGXMSRJEGXSV

{6IUYMVIHWXVIRKXL 6{6IUYMVIHWXVIRKXL

{6IUYMVIHWXVIRKXL9WLEPPFIEXPIEWXIUYEPXS 8LI VIUYMVIH WXVIRKXL 9 MW I\TVIWWIH MR XIVQW SJ JEGXSVIH
XLIIJJIGXWSJJEGXSVIHPSEHWMR)U  XLVSYKL   PSEHW SV VIPEXIH MRXIVREP QSQIRXW ERH JSVGIW *EGXSVIH
8LIIJJIGXSJSRISVQSVIPSEHWRSXEGXMRKWMQYPXERI PSEHW EVI XLI PSEHW WTIGMJMIH MR XLI KIRIVEP FYMPHMRK GSHI
SYWP]WLEPPFIMRZIWXMKEXIH QYPXMTPMIHF]ETTVSTVMEXIPSEHJEGXSVW

9!(  8LIJEGXSVEWWMKRIHXSIEGLPSEHMWMRJPYIRGIHF]XLIHIKVII


SJEGGYVEG]XS[LMGLXLIPSEHIJJIGXYWYEPP]GERFIGEPGYPEXIH
9!(0 0V SV7SV6   ERHXLIZEVMEXMSRXLEXQMKLXFII\TIGXIHMRXLIPSEHHYVMRK
XLI PMJIXMQI SJ XLI WXVYGXYVI (IEH PSEHW FIGEYWI XLI] EVI
9!( 0V SV7SV6  0SV;  QSVIEGGYVEXIP]HIXIVQMRIHERHPIWWZEVMEFPIEVIEWWMKRIHE
PS[IVPSEHJEGXSVXLERPMZIPSEHW0SEHJEGXSVWEPWSEGGSYRX
9!(;0 0VSV7SV6   JSV ZEVMEFMPMX] MR XLI WXVYGXYVEP EREP]WMW YWIH XS GSQTYXI
QSQIRXWERHWLIEVW
9!()07 
%QIVMGER'SRGVIXI-RWXMXYXI'ST]VMKLXIH1EXIVMEP{[[[GSRGVIXISVK
 7869'896%0'32'6)8)&9-0(-2+'3() %'-1 %2('311)28%6=

'3() '311)28%6=
9!(;  8LI'SHIKMZIWPSEHJEGXSVWJSVWTIGMJMGGSQFMREXMSRWSJPSEHW
-REWWMKRMRKJEGXSVWXSGSQFMREXMSRWSJPSEHMRKWSQIGSRWMHIV
9!()  EXMSR MW KMZIR XS XLI TVSFEFMPMX] SJ WMQYPXERISYW SGGYVVIRGI
;LMPIQSWXSJXLIYWYEPGSQFMREXMSRWSJPSEHMRKWEVIMRGPYHIH
I\GITXEWJSPPS[W MXWLSYPHRSXFIEWWYQIHXLEXEPPGEWIWEVIGSZIVIH

E 8LIPSEHJEGXSVSRXLIPMZIPSEH0MR)U  XS (YI VIKEVH MW XS FI KMZIR XS WMKR MR HIXIVQMRMRK 9 JSV
 WLEPPFITIVQMXXIHXSFIVIHYGIHXSI\GITXJSV GSQFMREXMSRW SJ PSEHMRKW EW SRI X]TI SJ PSEHMRK QE]
KEVEKIWEVIEWSGGYTMIHEWTPEGIWSJTYFPMGEWWIQFP] TVSHYGIIJJIGXWSJSTTSWMXIWIRWIXSXLEXTVSHYGIHF]ERSXLIV
ERHEPPEVIEW[LIVI0MWKVIEXIVXLERO2Q X]TI 8LI PSEH GSQFMREXMSRW [MXL ( EVI WTIGMJMGEPP]
MRGPYHIHJSVXLIGEWI[LIVIELMKLIVHIEHPSEHVIHYGIWXLI
F  ;LIVI ; MW FEWIH SR WIVZMGIPIZIP [MRH PSEHW IJJIGXWSJSXLIVPSEHW8LIPSEHMRKGEWIQE]EPWSFIGVMXMGEP
;WLEPPFIYWIHMRTPEGISJ;MR)U  ERH JSV XIRWMSRGSRXVSPPIH GSPYQR WIGXMSRW -R WYGL E GEWI E
 ERH;WLEPPFIYWIHMRTPEGISJ;MR VIHYGXMSR MR E\MEP PSEH ERH ER MRGVIEWI MR QSQIRX QE]
)U   VIWYPXMREGVMXMGEPPSEHGSQFMREXMSR

G  ;LIVI ) MW FEWIH SR WIVZMGIPIZIP JSVGIW ) 'SRWMHIVEXMSR WLSYPH FI KMZIR XS ZEVMSYW GSQFMREXMSRW SJ
WLEPPFIYWIHMRTPEGISJ)MR)U  ERH   PSEHMRKXSHIXIVQMRIXLIQSWXGVMXMGEPHIWMKRGSRHMXMSR8LMW
MWTEVXMGYPEVP] XVYI[LIRWXVIRKXLMWHITIRHIRXSRQSVIXLER
SRIPSEHIJJIGXWYGLEWWXVIRKXLJSVGSQFMRIHJPI\YVI ERH
E\MEPPSEHSVWLIEVWXVIRKXLMRQIQFIVW[MXLE\MEPPSEH

-J YRYWYEP GMVGYQWXERGIW VIUYMVI KVIEXIV VIPMERGI SR XLI


WXVIRKXL SJ TEVXMGYPEV QIQFIVW XLER IRGSYRXIVIH MR YWYEP
TVEGXMGIWSQIVIHYGXMSRMRXLIWXMTYPEXIHWXVIRKXLVIHYGXMSR
JEGXSVW  SV MRGVIEWI MR XLI WXMTYPEXIH PSEH JEGXSVW QE] FI
ETTVSTVMEXIJSVWYGLQIQFIVW

-RXLI'SHIVIQSZIHXLI[IMKLXSJWSMPERHSXLIVJMPP
QEXIVMEPW EW TEVX SJ XLI HIJMRMXMSR SJ , 'SRWMWXIRX [MXL
%7')7)-  XLI [IMKLX SJ XLIWI QEXIVMEPW MW TEVX SJ
HIEH PSEH ( 8LI PSEH JEGXSVW JSV ( EVI ETTVSTVMEXI
TVSZMHIHXLIYRMX[IMKLXERHXLMGORIWWSJIEVXLSVSXLIVJMPP
QEXIVMEPWEVI[IPPGSRXVSPPIH-JXLI[IMKLXSJIEVXLWXEFMPM^IW
XLIWXVYGXYVIEPSEHJEGXSVSJ^IVSQE]FIETTVSTVMEXI

6 E  { 8LI PSEH QSHMJMGEXMSR JEGXSV SJ  E  MW


HMJJIVIRXXLER XLI PMZI PSEH VIHYGXMSRWFEWIHSRXLI PSEHIH
EVIE XLEX QE] FI EPPS[IH MR XLI PIKEPP] EHSTXIH KIRIVEP
FYMPHMRK GSHI 8LI PMZI PSEH VIHYGXMSR FEWIH SR PSEHIH
EVIEEHNYWXWXLIRSQMREPPMZIPSEH 0MR%7')7)- XS0
8LI PMZI PSEHVIHYGXMSR EWWTIGMJMIH MR XLIPIKEPP] EHSTXIH
KIRIVEPFYMPHMRKGSHIGERFIYWIHMRGSQFMREXMSR[MXLXLI
PSEHJEGXSVWTIGMJMIHMR E 

6 F  { %7')7)- LEW GSRZIVXIH [MRH PSEHW XS


WXVIRKXLPIZIPERHVIHYGIHXLI[MRHPSEHJEGXSVXS%'-
VIUYMVIWYWISJXLITVIZMSYWPSEHJEGXSVJSV[MRHPSEHW
 [LIR WIVZMGIPIZIP [MRH PSEHW EVI YWIH *SV WIVZMGI
EFMPMX] GLIGOW XLI GSQQIRXEV] XS %TTIRHM\ ' SJ %7')
7)-TVSZMHIWWIVZMGIPIZIP[MRHPSEHW;E

6 G {-R%7')GSRZIVXIHIEVXLUYEOIJSVGIW
XS WXVIRKXL PIZIP ERH VIHYGIH XLI IEVXLUYEOI PSEH JEGXSV XS
1SHIPFYMPHMRKGSHIWJSPPS[IH%'-VIUYMVIW
YWISJXLITVIZMSYWPSEHJEGXSVJSVIEVXLUYEOIIJJIGXWETTVS\
MQEXIP][LIRWIVZMGIPIZIPIEVXLUYEOIIJJIGXWEVIYWIH
%QIVMGER'SRGVIXI-RWXMXYXI'ST]VMKLXIH1EXIVMEP{[[[GSRGVIXISVK
ASCE/SEI 7‐10                  
( SERVICE LOAD COMBINATIONS)
CHAPTER 2 COMBINATIONS OF LOADS

2.3.4. Load Combinations Including Atmospheric 4. D + 0.75L + 0.75(Lr or S or R)


Ice Loads 5. D + (0.6W or 0.7E)
When a structure is subjected to atmospheric ice 6a. D + 0.75L + 0.75(0.6W) + 0.75(Lr or S or R)
and wind-on-ice loads, the following load combina- 6b. D + 0.75L + 0.75(0.7E) + 0.75S
tions shall be considered: 7. 0.6D + 0.6W
8. 0.6D + 0.7E
1. 0.5(Lr or S or R) in combination 2 shall be replaced
by 0.2Di + 0.5S.
EXCEPTIONS:
2. 1.0W + 0.5(Lr or S or R) in combination 4 shall be
replaced by Di + Wi + 0.5S. 1. In combinations 4 and 6, the companion load S
3. 1.0W in combination 6 shall be replaced by shall be taken as either the flat roof snow load (pf)
Di + Wi. or the sloped roof snow load (ps).
2. For nonbuilding structures, in which the wind load
is determined from force coefficients, Cf, identified
2.3.5 Load Combinations Including in Figures 29.5-1, 29.5-2 and 29.5-3 and the
Self-Straining Loads projected area contributing wind force to a founda-
Where applicable, the structural effects of load T tion element exceeds 1,000 square feet on either a
shall be considered in combination with other loads. vertical or a horizontal plane, it shall be permitted
The load factor on load T shall be established consid- to replace W with 0.9W in combination 7 for
ering the uncertainty associated with the likely design of the foundation, excluding anchorage of
magnitude of the load, the probability that the the structure to the foundation.
maximum effect of T will occur simultaneously with 3. It shall be permitted to replace 0.6D with 0.9D in
other applied loadings, and the potential adverse combination 8 for the design of Special Reinforced
consequences if the effect of T is greater than Masonry Shear Walls, where the walls satisfy the
assumed. The load factor on T shall not have a value requirement of Section 14.4.2.
less than 1.0.
Where fluid loads F are present, they shall be
included in combinations 1 through 6 and 8 with the
2.3.6 Load Combinations for Nonspecified Loads same factor as that used for dead load D.
Where approved by the Authority Having Where load H is present, it shall be included as
Jurisdiction, the Responsible Design Professional is follows:
permitted to determine the combined load effect for
strength design using a method that is consistent with 1. where the effect of H adds to the primary variable
the method on which the load combination require- load effect, include H with a load factor of 1.0;
ments in Section 2.3.2 are based. Such a method must 2. where the effect of H resists the primary variable
be probability-based and must be accompanied by load effect, include H with a load factor of 0.6
documentation regarding the analysis and collection where the load is permanent or a load factor of 0
of supporting data that is acceptable to the Authority for all other conditions.
Having Jurisdiction. The most unfavorable effects from both wind
and earthquake loads shall be considered, where
appropriate, but they need not be assumed to act
simultaneously. Refer to Section 1.4 and 12.4
2.4 COMBINING NOMINAL LOADS USING
for the specific definition of the earthquake load
ALLOWABLE STRESS DESIGN
effect E.2
Increases in allowable stress shall not be used
2.4.1 Basic Combinations
with the loads or load combinations given in this
Loads listed herein shall be considered to act in
standard unless it can be demonstrated that such an
the following combinations; whichever produces the
increase is justified by structural behavior caused by
most unfavorable effect in the building, foundation, or
rate or duration of load.
structural member being considered. Effects of one or
more loads not acting shall be considered.
1. D 2
The same E from Sections 1.4 and 12.4 is used for both Sections
2. D+L 2.3.2 and 2.4.1. Refer to the Chapter 11 Commentary for the Seismic
3. D + (Lr or S or R) Provisions.

8
ACI 318M‐05                   
(CONCISE BEAM FACTOED LOADS )
',%48)6 

',%48)6{786)2+8,%2(7)6:-')%&-0-8=
6)59-6)1)287
'3() '311)28%6=
{+IRIVEP 6{+IRIVEP

 { 7XVYGXYVIW ERH WXVYGXYVEP QIQFIVW WLEPP FI -RXLIGSHIXLIPSEHJEGXSVGSQFMREXMSRWERHWXVIRKXL


HIWMKRIH XS LEZI HIWMKR WXVIRKXLW EX EPP WIGXMSRW EX VIHYGXMSRJEGXSVWSJXLIGSHI[IVIVIZMWIHERHQSZIH
PIEWXIUYEPXSXLIVIUYMVIHWXVIRKXLWGEPGYPEXIHJSVXLI XS%TTIRHM\'8LIGSQFMREXMSRWLEZIFIIRVITPEGIH
JEGXSVIHPSEHWERHJSVGIWMRWYGLGSQFMREXMSRWEWEVI [MXL XLSWI SJ 7)-%7')   8LI WXVIRKXL VIHYGXMSR
WXMTYPEXIHMRXLMWGSHI JEGXSVW[IVIVITPEGIH[MXLXLSWISJXLI%TTIRHM\'
I\GITXXLEXXLIJEGXSVJSVJPI\YVI[EWMRGVIEWIH
 { 1IQFIVW EPWS WLEPP QIIX EPP SXLIV VIUYMVI
QIRXWSJXLMWGSHIXSIRWYVIEHIUYEXITIVJSVQERGIEX 8LIGLERKIW[IVIQEHIXSJYVXLIVYRMJ]XLIHIWMKRTVSJIW
WIVZMGIPSEHPIZIPW WMSR SR SRI WIX SJ PSEH JEGXSVW ERH GSQFMREXMSRW ERH XS
JEGMPMXEXI XLI TVSTSVXMSRMRK SJ GSRGVIXI FYMPHMRK WXVYGXYVIW
{(IWMKRSJWXVYGXYVIWERHWXVYGXYVEPQIQFIVW XLEX MRGPYHI QIQFIVW SJ QEXIVMEPW SXLIV XLER GSRGVIXI
YWMRKXLIPSEHJEGXSVGSQFMREXMSRWERHWXVIRKXLVIHYG ;LIR YWIH [MXL XLI WXVIRKXL VIHYGXMSR JEGXSVW MR  XLI
XMSR JEGXSVW SJ %TTIRHM\' WLEPPFI TIVQMXXIH 9WI SJ HIWMKRW JSV KVEZMX] PSEHW [MPP FI GSQTEVEFPI XS XLSWI
PSEHJEGXSVGSQFMREXMSRWJVSQXLMWGLETXIVMRGSRNYRG SFXEMRIHYWMRKXLIWXVIRKXLVIHYGXMSRERHPSEHJEGXSVWSJXLI
XMSR[MXLWXVIRKXLVIHYGXMSRJEGXSVWSJ%TTIRHM\'WLEPP ERHIEVPMIVGSHIW*SVGSQFMREXMSRW[MXLPEXIVEPPSEHW
RSXFITIVQMXXIH WSQIHIWMKRW[MPPFIHMJJIVIRXFYXXLIVIWYPXWSJIMXLIVWIXSJ
PSEHJEGXSVWEVIGSRWMHIVIHEGGITXEFPI

'LETXIVHIJMRIWXLIFEWMGWXVIRKXLERHWIVZMGIEFMPMX]GSR
HMXMSRWJSVTVSTSVXMSRMRKWXVYGXYVEPGSRGVIXIQIQFIVW

8LIFEWMGVIUYMVIQIRXJSVWXVIRKXLHIWMKRQE]FII\TVIWWIH
EWJSPPS[W

(IWMKR7XVIRKXL 6IUYMVIH7XVIRKXL

 2SQMREP7XVIRKXL  9

-RXLIWXVIRKXLHIWMKRTVSGIHYVIXLIQEVKMRSJWEJIX]MWTVS
ZMHIHF]QYPXMTP]MRKXLIWIVZMGIPSEHF]EPSEHJEGXSVERH
XLIRSQMREPWXVIRKXLF]EWXVIRKXLVIHYGXMSRJEGXSV

{6IUYMVIHWXVIRKXL 6{6IUYMVIHWXVIRKXL

{6IUYMVIHWXVIRKXL9WLEPPFIEXPIEWXIUYEPXS 8LI VIUYMVIH WXVIRKXL 9 MW I\TVIWWIH MR XIVQW SJ JEGXSVIH
XLIIJJIGXWSJJEGXSVIHPSEHWMR)U  XLVSYKL   PSEHW SV VIPEXIH MRXIVREP QSQIRXW ERH JSVGIW *EGXSVIH
8LI IJJIGX SJ SRI SV QSVI PSEHW RSX EGXMRK WMQYPXE PSEHW EVI XLI PSEHW WTIGMJMIH MR XLI KIRIVEP FYMPHMRK GSHI
RISYWP]WLEPPFIMRZIWXMKEXIH QYPXMTPMIHF]ETTVSTVMEXIPSEHJEGXSVW

9! (*  8LIJEGXSVEWWMKRIHXSIEGLPSEHMWMRJPYIRGIHF]XLIHIKVII


SJ EGGYVEG]XS[LMGL XLIPSEHIJJIGXYWYEPP] GERFI GEPGY
9! (*8  0,  PEXIH ERH XLI ZEVMEXMSR XLEX QMKLX FI I\TIGXIH MR XLI PSEH
HYVMRK XLI PMJIXMQI SJ XLI WXVYGXYVI (IEH PSEHW FIGEYWI
 0V SV7SV6 XLI] EVIQSVIEGGYVEXIP]HIXIVQMRIHERHPIWWZEVMEFPIEVI
EWWMKRIH E PS[IV PSEH JEGXSV XLER PMZI PSEHW 0SEH JEGXSVW
9!( 0V SV7SV6  0SV;  EPWSEGGSYRXJSVZEVMEFMPMX]MRXLIWXVYGXYVEPEREP]WMWYWIHXS
GSQTYXIQSQIRXWERHWLIEVW
9!(;0 0VSV7SV6  8LI GSHI KMZIW PSEH JEGXSVW JSV WTIGMJMG GSQFMREXMSRW SJ
PSEHW-REWWMKRMRKJEGXSVWXSGSQFMREXMSRWSJPSEHMRKWSQI
'ST]VMKLX%QIVMGER'SRGVIXI-RWXMXYXI
4VSZMHIHF]-,7YRHIVPMGIRWI[MXL%'- 0MGIRWII!&PEGO
:IEXGL
2SVITVSHYGXMSRSVRIX[SVOMRKTIVQMXXIH[MXLSYXPMGIRWIJVSQ-,7 %'-&YMPHMRK'SHIERH'SQQIRXEV]
2SXJSV6IWEPI178
 ',%48)6

'3() '311)28%6=
9!()07  GSRWMHIVEXMSR MW KMZIR XS XLI TVSFEFMPMX] SJ WMQYPXERISYW
SGGYVVIRGI;LMPIQSWXSJXLIYWYEPGSQFMREXMSRWSJPSEH
9!(;,  MRKW EVI MRGPYHIH XLI HIWMKRIV WLSYPH RSX EWWYQI XLEX EPP
GEWIWEVIGSZIVIH
9!(), 
(YIVIKEVHMWXSFIKMZIRXSWMKRMRHIXIVQMRMRK9JSVGSQ
I\GITXEWJSPPS[W FMREXMSRWSJPSEHMRKWEWSRIX]TISJPSEHMRKQE]TVSHYGI
IJJIGXWSJSTTSWMXIWIRWIXSXLEXTVSHYGIH F]ERSXLIVX]TI
E 8LIPSEHJEGXSVSRXLIPMZIPSEH 0MR)U  XS 8LIPSEHGSQFMREXMSRW[MXL (EVIWTIGMJMGEPP]MRGPYHIH
 WLEPPFITIVQMXXIHXSFIVIHYGIHXSI\GITXJSV JSVXLIGEWI[LIVIELMKLIVHIEHPSEHVIHYGIWXLIIJJIGXWSJ
KEVEKIWEVIEW SGGYTMIH EW TPEGIWSJ TYFPMG EWWIQ SXLIVPSEHW8LIPSEHMRKGEWIQE]EPWSFIGVMXMGEPJSVXIRWMSR
FP]ERHEPPEVIEW[LIVI0MWKVIEXIVXLER2Q GSRXVSPPIH GSPYQR WIGXMSRW -R WYGL E GEWI E VIHYGXMSR MR
E\MEPPSEHERHERMRGVIEWIMRQSQIRXQE]VIWYPXMREGVMXMGEP
F ;LIVI[MRHPSEH ;LEWRSXFIIRVIHYGIHF]E PSEHGSQFMREXMSR
HMVIGXMSREPMX]JEGXSVMXWLEPPFITIVQMXXIHXSYWI;
MRTPEGISJ;MR)U  ERH   'SRWMHIVEXMSR WLSYPH FI KMZIR XS ZEVMSYW GSQFMREXMSRW SJ
PSEHMRKXSHIXIVQMRIXLIQSWXGVMXMGEPHIWMKRGSRHMXMSR8LMW
G ;LIVI)XLIPSEHIJJIGXWSJIEVXLUYEOIMWFEWIH MWTEVXMGYPEVP] XVYI[LIRWXVIRKXLMWHITIRHIRXSRQSVIXLER
SRWIVZMGIPIZIP WIMWQMG JSVGIW ) WLEPP FI YWIH SRIPSEHIJJIGXWYGLEWWXVIRKXLJSVGSQFMRIHJPI\YVIERH
MRTPEGISJ)MR)U  ERH   E\MEPPSEHSVWLIEVWXVIRKXLMRQIQFIVW[MXLE\MEPPSEH

H  8LI PSEH JEGXSV SR , PSEHW HYI XS [IMKLX ERH -J WTIGMEP GMVGYQWXERGIW VIUYMVI KVIEXIV VIPMERGI SR XLI
TVIWWYVI SJ WSMP [EXIV MR WSMP SV SXLIV QEXIVMEPW WXVIRKXL SJ TEVXMGYPEV QIQFIVW XLER IRGSYRXIVIH MR YWYEP
WLEPPFIWIXIUYEPXS^IVSMR)U  ERH  MJXLI TVEGXMGIWSQIVIHYGXMSRMRXLIWXMTYPEXIHWXVIRKXLVIHYGXMSR
WXVYGXYVEPEGXMSRHYIXS,GSYRXIVEGXWXLEXHYIXS; JEGXSVW  SV MRGVIEWI MR XLI WXMTYPEXIH PSEH JEGXSVW QE] FI
SV ) ;LIVI PEXIVEP IEVXL TVIWWYVI TVSZMHIW VIWMW ETTVSTVMEXIJSVWYGLQIQFIVW
XERGIXSWXVYGXYVEPEGXMSRWJVSQSXLIVJSVGIWMXWLEPP
RSX FI MRGPYHIH MR , FYX WLEPP FI MRGPYHIH MR XLI 8LI[MRHPSEHIUYEXMSRMR7)-%7')ERH-&'
HIWMKRVIWMWXERGI MRGPYHIWEJEGXSVJSV[MRHHMVIGXMSREPMX]XLEXMWIUYEPXS
JSVFYMPHMRKW8LIGSVVIWTSRHMRKPSEHJEGXSVJSV[MRHMRXLI
PSEHGSQFMREXMSRIUYEXMSRW[EWMRGVIEWIHEGGSVHMRKP] 
!VSYRHIHYTXS 8LIGSHIEPPS[WYWISJXLI
TVIZMSYW[MRHPSEHJEGXSVSJ[LIRXLIHIWMKR[MRHPSEH
MWSFXEMRIHJVSQSXLIVWSYVGIWXLEXHSRSXMRGPYHIXLI[MRH
HMVIGXMSREPMX]JEGXSV

1SHIPFYMPHMRKGSHIWERHHIWMKRPSEHVIJIVIRGIWLEZIGSR
ZIVXIHIEVXLUYEOIJSVGIWXSWXVIRKXLPIZIPERHVIHYGIHXLI
IEVXLUYEOI PSEHJEGXSV XS  %7') &3'%2&'
7&'9&'ERH-&' 8LIGSHI
VIUYMVIWYWISJXLITVIZMSYWPSEHJEGXSVJSVIEVXLUYEOIPSEHW
ETTVS\MQEXIP]  [LIR WIVZMGIPIZIP IEVXLUYEOI JSVGIW
JVSQIEVPMIVIHMXMSRWSJXLIWIVIJIVIRGIWEVIYWIH

 { -J VIWMWXERGI XS MQTEGX IJJIGXW MW XEOIR MRXS 6{-JXLIPMZIPSEHMWETTPMIHVETMHP]EWQE]FIXLI
EGGSYRXMRHIWMKRWYGLIJJIGXWWLEPPFIMRGPYHIH[MXL0 GEWI JSV TEVOMRK WXVYGXYVIW PSEHMRK HSGOW [EVILSYWI
JPSSVWIPIZEXSVWLEJXWIXGMQTEGXIJJIGXWWLSYPHFIGSRWMH
IVIH -R EPP IUYEXMSRW WYFWXMXYXI 0  MQTEGX  JSV 0 [LIR
MQTEGXWLSYPHFIGSRWMHIVIH

{)WXMQEXMSRWSJHMJJIVIRXMEPWIXXPIQIRXGVIIT 6{8LIHIWMKRIVWLSYPHGSRWMHIVXLIIJJIGXWSJHMJJIV
WLVMROEKI I\TERWMSR SJ WLVMROEKIGSQTIRWEXMRK IRXMEPWIXXPIQIRXGVIITWLVMROEKIXIQTIVEXYVIERHWLVMRO
GSRGVIXISVXIQTIVEXYVIGLERKIWLEPPFIFEWIHSR EKIGSQTIRWEXMRKGSRGVIXI8LIXIVQVIEPMWXMGEWWIWWQIRXMW
E VIEPMWXMG EWWIWWQIRX SJ WYGL IJJIGXW SGGYVVMRK MR YWIHXSMRHMGEXIXLEXXLIQSWXTVSFEFPIZEPYIWVEXLIVXLERXLI
WIVZMGI YTTIVFSYRHZEPYIWSJXLIZEVMEFPIWWLSYPHFIYWIH

'ST]VMKLX%QIVMGER'SRGVIXI-RWXMXYXI
4VSZMHIHF]-,7YRHIVPMGIRWI[MXL%'- 0MGIRWII!&PEGO
:IEXGL
2SVITVSHYGXMSRSVRIX[SVOMRKTIVQMXXIH[MXLSYXPMGIRWIJVSQ-,7 %'-&YMPHMRK'SHIERH'SQQIRXEV]
2SXJSV6IWEPI178

You might also like