Professional Documents
Culture Documents
Dedicated To All Spark Members
Dedicated To All Spark Members
P.K.PATTANAIK
Deputy. General Manager (Elect. )
E&MR Division,
OPTCL (Formerly GRIDCO)
BHUBANESWAR- ODISHA- 751022
P.K.Pattanaik
Mobile : 9438907492
WhatsApp : 9438907492
Email : ppk110.pp@gmail.com
P.K.PATTANAIK.
CONTENTS
SL. PARTICULARS PAGE NO
NO
4.
NAME PLATE SAMPLES OF (110-116)
ELECTRICAL EQUIPMENT
1. Circuit Breaker
1.1 132 KV SF6 Circuit Breaker 110
1.2 220 KV SF6 Circuit Breaker 111
1.3 33 KV Vacuum Circuit Breaker 111
2. Current Transformer
5
TRANSMISSION LINE DATA (117-127)
1. Electrical Span for Transmission Lines 117
2. Parameters for Different Soils for 117
Tower foundation
3. Wind Zone 117
4. Permissible Weight Span 118
5. Disc Insulators for EHT Lines 118
6. Insulators String for 132 KV, 220 KV 119
and 400 KV lines
7. Air Clearance and Swing angle 120
8. Formulae for Clearance 120
9. Typical Sag-Tension Calculation 121-122
( AAAC-Zebra
10. Span Versus Sag Table 122
11. Line Loading ( SIL ) 122
12. Transmission Towers
12.1Type and Shape of Tower 123
12.2Slope of Tower Legs and Shield angle 123
12.3Tower Spotting Data 124
12.4Standard Steel Section used in Tower 125
12.5Dimensions for various Category of 126-127
Tower
3. SYMBOLS USED
SL. No Symbols Meanings
1. Over Current
2 V Over Voltage
ů
3 V Under Voltage
4 Z Distance Relay
6 Over Frequency
7 Under Frequency
8 T Over Temp.
9 Ф Balanced Phase
10 X Pilot Wire
PW
11 Dirr. O/C
12 Z Dir. Distance
13 CC Carrier Pilot
Protection
*
EN
relay with Coil with no flag
enable input
Isolator Link
Breaker C.T.
Note: for study of drawing: always refer the index legends etc.
5. CODE OF PRACTICE BY M/S ABB LTD.
5.1 TERMINAL BLOCKS
EXTERNAL CIRCUIT INTERNAL CIRCUIT
TB PURPOSE TB PURPOSE
X01 CT Circuit X11 CT Circuit
X02 PT Circuit X12 PT Circuit
X03 DC Supply X13 DC Supply
X04 Control Circuit X14 Control Circuit
X05 AC Supply X15 AC Supply
X07 Annunciation, AlarmCircuit X17 Annunciation, AlarmCircuit
01 17 25 37
1
2. GENERATOR PROTECTION
GCB (OPEN)
STATER CONDN. Class B Trip Relay TRIP UAT CB
HIGH 86T
THYRISTOR
COOLING
FAN SUPPLY FAIL
FCB CLOSE
TRANS. OIL TEMP. ARM.REHEATER
& WINDING PROTECTION
3. MOTOR PROTECTION
1 O/L Protection
2 S.C. Protections
3 E/F Protections
4 Start Protections
5 Prolonged starts
6 Stalling protections During starting
During running
7 Loss of load
8 Under voltage protection
4.3.1 Data:
Type of winding Top oil find temp rise Winding temp rise on
on F.L condition F.L. condition
OA, OW 50ºC 55ºC
OA / FA 50ºC 55ºC
OA / FA / FOA 45ºC 50ºC 50ºC
FOA
FOW
4.6 .1 DATA: 1 Bellow (Bourdon tube) and shunt network, being connected to
WCT (Winding Ct), simulates the temp. Gradient,
(proportionate with load current) and provides reading on the
scale.
4.6.2 DATA: 2 Max. Heater coil current ≤ 2 Amps
4.6.3 DATA: 3 Standard bellow heater = (2.5 ± 0.1) Ω at 30ºC
TEMP RESISTANCE OUT PUT SIGNAL OUT PUT SIGNAL OUT PUT SIGNAL
IN O C 0-5mA 0-20mA 4-20mA
L0 Nom. Hi L0 Nom. Hi L0 Nom. Hi
0 100.00 - 0 0.050 - 0 0.200 3.800 4.000 4.200
10 103.90 0.283 0.333 0.383 1.333 1.333 1.533 4.867 5.067 5.267
20 107.79 0.617 0.667 0.717 2.467 2.667 2.867 5.933 6.133 6.333
30 111.67 0.950 1.000 1.050 3.800 4.000 4.200 7.000 7.200 7.400
40 115.54 1.283 1.333 1.383 5.333 5.333 5.533 8.067 8.267 8.467
50 119.40 1.617 1.667 1.717 6.467 6.667 6.867 9.133 9.333 9.533
60 123.24 1.950 2.000 2.050 7.800 8.000 8.200 10.200 10.400 10.600
70 127.07 2.283 2.333 2.383 9.333 9.333 9.533 11.267 11.467 11.667
80 130.89 2.617 2.667 2.717 10.467 10.667 10.867 12.333 12.533 12.333
90 134.70 2.950 3.000 3.050 11.800 12.000 12.200 13.400 13.600 13.800
100 138.50 3.283 3.333 3.383 13.333 13.333 13.533 14.467 14.667 14.867
110 142.29 3.617 3.667 3.717 14.467 14.667 14.867 15.573 15.733 15.933
120 146.06 3.950 4.000 4.050 15.800 16.000 16.200 16.600 16.800 17.000
130 149.82 4.283 4.333 4.383 17.333 17.333 17.533 17.667 17.867 18.067
140 153.58 4.617 4.667 4.717 18.467 18.667 18.867 18.733 18.933 19.133
150 157.31 4.950 5.000 5.050 19.800 20.000 20.200 19.800 20.000 20.200
(Fault
Occurrence )
(1 ) ( 2) (3) Margin
Breaker
Fail Relay Starts
Total Clearing time of LBB Relay
Maxim. Fault clearing time before system Instability
7. LINE PROTECTION
1 Main Protection (Distance Protection)
2 B/U Protection (O/C, E/F Protn.)
2nd. Method
For available of the following data zone selection
standard should be as follows
a3 = 0.85 ( a + k b2)
a2 = 0.85 ( a + k b1)
a1 = 0.85 a b1
a b2
A B C
NOTE Z1 :- a1 = 0.85 a ( Zone 1 ), Z2 :- a2 = 0.85 ( a + k b1 )
Z3 :- A3 = 0.85 ( a + k b2) = Zone 3
k = ( IA + IB ) / IA ,
Where IA = Service current on Station A
IB = Service current on Station B
1st Method: -
2nd Method: -
Line Voltage R X Yc
ohm/ ohm/ µ mho/ph/km
ph/km ph/km
132kv Panther 0.151 0.401 1.43
220kv Zebra 0.078 0.402 1.44
400kv Twin Moose 0.031 0.327 1.73
Z L =(U² / MVA)
i. Ph - Ph fault
2 During PS (Δ Z / Δ t) Slow
7.2.1 TYPE
Type K C
NI 0.14 0.02
VI 13.5 1.0
EI 80 2.0
LTI 120 1.0
Connection
Relay MTA
Aph Bph Cph
connec
tion Curr Volt Curre Volta Curren Voltage
angle ent age nt coil ge coil t coil coil
coil coil
30º 0º Ia Vac Ib Vba Ic Vcb
60º 0º Iab Vac Ibc Vba Ica Vcb
Type 1
60º 0º Ia - Vc Ib - Va Ic - Vb
Type 2
90º 30º Ia Vbc Ib Vca Ic Vab
Lead
90º 45º Ia Vbc Ib Vca Ic Vab
Lead
Relay Connection
characteristic Current coil Voltage coil
angle
12.5º (lag) Residual Current Residual Voltage
14º (lag) I0 = IA + IB + = Open Delta Secondary
45º (lag) IC Voltage
60º (lag)
Trip
Volt
Make
Type
Alarm
Standar
DC
d
Aux.
HT Side LT Side (BIAS) Operating Point
(COMMON)
R Y B r y b R0 Y0 B0
ER 4C21 Single unit / 1,2 3,4 10 10 10 9 9 9 7 7 7 -
Case
DUO- Multi unit / Module 2 (RL1, 3 6 13 3 6 13 1+1 4+4 11+11 220 V
BIAS M Case RL2) General DC
Command During Test both HT & LT
Terminals to be shorted (Ex.
1+1)
ABB RADSB -do- 15, 16 17,18 6 7 8 3 4 5 12 13 14 1,2
DTH31 -do- 1,2 3,4 14 18 10 11 15 7 12 16 8 5- 110 V
EE 6- 220 V
ALST 19- 30V
OM 20 - --ve
DTH32 -do- 1,2 3,4 7 17 27 10 20 30 8 or 9 18 or 19 28 or 29 11- 30 V
Short Short Short 13- 110 V
(8 +9) (18 + (28 15–220 V
19) +29) 12 - - ve
EE DDT Single unit / 1,2 3,4 10 10 10 5 5 5 7 7 7 3- + ve
ALST Case 8 --- ve
OM DDT Multi unit / 1,2 3,4 5 18 13 10 20 11 6 16 14 3- + ve
Case 8 --- ve
MBCH Single unit / 9, 11 1,3 25 25 25 23 23 23 27 27 27 13- + ve
12 (2 Case 14 -- ve
Winding Short (24 +26 +28) 220 V
MBCH -do- 9,11 1,3 25 25 25 23 23 23 27 27 27 13- + ve
13 (3 or or or 14 --- ve
Winding 21 21 21 220 V
TECHNICAL PARTICULARS
Sl.no Particulars 33KV 132KV 220KV 400KV
1 System voltage (kv) 36 145 245 420
2 System frequency (H2) 50 50 50 50
Oil,
Vacuum, Oil, Air blast SF6 (Puffer)
Quenching medium Air blast
Oil SF6 (puffer) Air blast
3 SF6
Spring
Spring
Hydraulic Air
Operating medium Spring Hydraulic
Air Pressure
Air pressure
4 pressure
5 Insulation standard
2.4.2.1. ALSTOM
V K >2I f (R CT +2R L )
Example :V K >2x10(3+4) >140V
Where ,I f =sec. equivalent of Fault Current
Ie =Is-Ir =(0.15-0.10) /2 =25 m A at V K /2
For voltage dependent, over current , field failure and negative phase,
sequence protection
V K >20In (R CT +2R L )
l For stator earth fault protection
V K >Is (R CT +2R L +RR)
2.For generator differential protection:
Low impedance diff. V K >50In (R CT +2R L )
High impedance diff V K >2 Vs
where Vs =1.5I f (R CT +2R L ), Rs =Vs/Is
2.4.2.2. ABB
1. Relay type: RADHA /RADHD (High impedance )
2.4.3.1. ABB
Where: K=(1.2/40)x(I CC /I N )
I N =Main CT primary rated current, I CC =Max short-circuit current delivered
to bus bar via the input Where MCT is installed.
RTCP=Rest. of secondary of MCT, R F =Rest. of link loop between MCT and
auxiliary CT, n=Ratio of auxiliary CT , Rd/n 2 =Value of differential
resistance transposed to ACT primary
CT Class: PS , V K >2I f (R CT +R L )
2.4.4.3. ABB
For all application at or above 220 kV where X/R ratio are large:
V K >NxK1xIn(R CT +XR L )
Magnetizing current<0.05xIn at 10/In V
2.4.6.1. ALSTOM
Class:5P10, Burden:5VA
2.4.6.2. ABB
CT class: PS V K =50/ In + (I f / N) (R CT +R L)
In -Rated Current
I f -Maximum primary steady state through fault current
N -CT ratio, R CT -CT resistance, R L -Lead Resistance
4. LIGHTNING ARRESTER
4.1 MAXIMUM SWICHING SURGE LEVEL IN pu (pu = √2 V line (max) / √ 3)
Highest System Voltage Typical Switching Surge pu Highest System Voltage Typical Switching Surge pu
KV, RMS KV, RMS
72.5 245
Sl.No Particulars Unit 36 KV KV 145 KV KV
1 System BIL KVp 170 325 650 1050
2 Rated voltage (RMS), (system voltage x √ 2) KV 30 60 120 198
√3
3 Max. Continuous operating voltage (MCOV) KV 25 52 102 168
4 Nominal Discharge current (NDC) KAp 10 10 10 10
5 High current with stand KAp 100 100 100 100
6 PROTECTION LEVELS
(A) Impulse residual voltage (KVp)
(i) Steep current @ NDC 94 185 380 600
(ii) Lightning current
@ 0.5 NDC 80 156 330 510
@ 1.0 NDC 84 165 350 550
@ 2.0 NDC 94 185 390 610
@1
(iii) Switching current KAp 70 136 290 450
(B) Temp. Over voltage (KVp)
(i) For 0.1 sec 60 120 254 404
(ii) For 1 sec 55 111 234 372
(iii) For 10 sec 52 105 222 353
(iv) For 100 sec 51 102 215 31
Particulars Value
Type Out door, Air Cored,
Air Cooled
Continuous Current Rating at 50 0 C ambient 1250 Amp
Continuous Current Rating at 65 0 C ambient 1125Amp
Max. Symmetrical Short Circuit Current For 1 31.5 KA
Sec
Asymmetrical peak value of first half of rated 80.5 KA
short time Current
Rated Inductance 0.5 H
Blocking Range 150-500 KHz
Min. Resistive Component in Blocking 570 Ohm
frequency range
Radio Interference voltage < 500 µ V
Mounting Suspension
Basic Insulation Level 32.37 KVp
Standard Nominal Discharge Current for 8/20 10 KA
micro Sec. Wave impulse
Rated Voltage of Arrestor 6 KV
Max. 1.2/50 micro sec. Impulse Spark over 21.6 KVP
voltage
Min. value of power frequency Spark over 9 KV rms
voltage
Virtual steepness and max. Front of wave 49.8 KV / micro S
Impulse Spark over voltage 24.9 KVp
Tuning Broad Band
Visual Corona Extinction Voltage 156 KV
Max. Residual Discharge Voltage for 8/20
micro Sec. Impulse Discharge current
1. 5000 A 21.6 KVp
2. 10000 A 21.6 KVp
No of Turns in Main coil 28 (2 in Parallel
Particulars Value
Type Air break, Off load
Standards used 1SS 9921/85
Highest System Voltage 245 KV
Nominal System Voltage 220 KV
Max. Continuous Current Rating 2000 Amp
Rated Short time Current for 3 Sec 40 KA
Max. Magnetizing current 0.7 A at 0.15 p F
Rated Peak Short time Current 100KAp
1.2/50 µ Sec. Impulse Withstand 1200 KV
Voltage
Radio Interference voltage 1000 µ V
Earthing SWITCH Rated Current 50 % of Main switch
Capacity
Minimum Clearance in
1. Between Live parts and 2400mm
ground 1600mm
2. Fixed Contact and blade
in Open condition
Operating Time
1. Opening 10-12 Sec
2. Closing 10-12 Sec
Continuous Rating of Aux. 10 A
Contact
Temp. Rise 55 above Ambient
Insulation Level 530 KV
Ub ≤ 36KV Ub> 36 KV
Rated KVA
ISS/IN t UC% ISS/IN t UC%
Upto 630 25 2 4 - - -
630 – 3150 16.7 4 6 - - -
3150 – 10000 12.5 5 8 10 6 10
10000 – 40000 10.0 6 10 9.1 7 11
Above 40000 - - - 8 8 12.5
Type of cooling Top oil final temp. Rise on Winding temp (Final) rise on
F.L. Condition F.L. Condition
OA, OW 500C 550C
OA / FA 500C 550C
OA / FA / FOA 450C 500C
FOA 450C 500C
FOW
7.9 STANDARD RANGE OF IMPEDANCE FOR TWO-
WINDING POWER TRANSFORMER, RATED AT 550C
RISE.
Note (2) Height of working area < 1000 m (3300 ft) above the sea
level.
% Winding
Transformer under gone Standard No. Of tap
Tap change from normal tap
1. Distribution 10% +5% Up, -5% Below
Transformer 15% +5% Up, -10% Below
(11/0.4 or 11/6.6
KV)
2. 33/11KV 20% +10% Up, -10% Below
20% +5% Up, -15% Below
Method-I
Method-II
SUGGESTED FAULT CH4/ C2H6 C2H4/ C2H2/
DIAGNOSIS H2 /CH4 C2H6 C2H4
If CH4 /H2 <0.1, then P.D other 0 0 0 0
wise Normal Deterioration
Slight Over Heating 1 0 0 0
Below 150 0 c
Slight Over Heating 1 1 0 0
Below 150 0 c to 200 0 c
Slight Over Heating 0 1 0 0
Below 200 0 c to 300 0 c
General Conductor Overheating 0 0 1 0
Circulating Currents / 1 0 1 0
Overheated
Flashover without power flow 0 0 0 1
current
Tap Changer selector breaking 0 1 0 1
current
Arc with Power flow 0 0 1 1
REMARKS
Ratio <1.0 is taken as 0, Ratio >1.0 is taken as 1
A given Ratio can be taken for Diagnosis if the concentration of one
gas is at least equal to the limit values as below
Value in ppm
H2=200, CH4= 50, C2H6=15, C2H4=60, C2H2=15
TDCG INTERPRETATIONS
LIMITS in
ppm
(0 – 720) Satisfactory operation – Unless individual gas
acceptance values are exceeded
(721 – 1920) Normal Ageing / Slight Decomposition Unless
individual gas acceptance values are exceeded
(1921 – 4630) Significant Decomposition fault is to be monitored
>4630 Very Substantial decomposition of oil. Immediate
action to be taken
$ Subtract 5 0 C from each of the ambient column heading for water cooled transformer. Minimum water
temp. must be above 0 0 C
Example :- Assume a load cycle which resolves to a constant value of 50 % followed by a 100 % peak
load for 2 Hrs. using the above table if the ambient Temp. is 30 0 C , a self cooled (OA ) , a water cooled
( OW ) transformer will carry 1.32 times name plate rating for 2 Hrs following an equivalent continuous
load up to 70 % of name plate rating , if the equivalent 2 Hrs peak load from the load cycle is 10 MVA .
The constant equivalent load before the peak is 5 MVA which is 66.6 % of the name plate rating of the
transformer . Therefore a 7.5 MVA transformer is suitable for this daily load cycle.
Peak Cooling – Forced Air cooled Rated 133 % or less of Self Cooled Rating or Water cooled ( OA / FA )
Load Continuous equivalent Load in %tage of rated KVA preceding the peak Load
Time 50 percent 70 percent 90 percent
In Ambient in degree C Ambient in degree C Ambient in degree C
Hrs
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
1/2 2.00 2.00 1.97 1.82 1.66 1.49 2.00 2.00 1.89 1.74 1.58 1.40 2.00 1.92 1.77 1.61 1.43 1.25
1 1.90 1.77 1.64 1.50 1.35 1.19 1.84 1.71 1.57 1.43 1.28 1.11 1.77 1.63 1.49 1.35 1.19 1.00
2 1.64 1.53 1.42 1.29 1.16 1.02 1.61 1.50 1.38 1.26 1.12 0.97 1.58 1.46 1.34 1.21 1.08 0.91
4 1.46 1.36 1.26 1.15 1.03 0.90 1.45 1.35 1.24 1.13 1.01 0.88 1.44 1.34 1.23 1.11 1.00 0.85
8 1.37 1.27 1.17 1.07 0.96 0.84 1.37 1.27 1.17 1.07 0.96 0.83 1.36 1.27 1.17 1.06 0.95 0.83
24 1.31 1.21 1.11 1.00 0.89 0.78 1.31 1.21 1.11 1.00 0.89 0.78 1.31 1.21 1.11 1.00 0.89 0.78
Note:- The peak load in this table are calculated on the basis of all cooling in use during the period preceding
the peak load. When operating with out fans, use this table for OA transformer
Peak Cooling – Forced Air cooled Rated 133 % or less of Self Cooled Rating or Water cooled ( OA / FA )
Load Continuous equivalent Load in %tage of rated KVA preceding the peak Load
Time 50 percent 70 percent 90 percent
In Ambient in degree C Ambient in degree C Ambient in degree C
Hrs
0 10 20 30 40 50 0 10 20 30 40 50 0 10 20 30 40 50
1/2 2.00 1.91 1.78 1.65 1.52 1.37 1.96 1.84 1.71 1.58 1.43 1.28 1.89 1.77 1.64 1.50 1.35 1.19
1 1.73 1.62 1.51 1.38 1.25 1.12 1.68 1.58 1.46 1.33 1.20 1.06 1.64 1.53 1.41 1.28 1.15 1.01
12 1.53 1.43 1.33 1.22 1.11 0.98 1.51 1.41 1.30 1.19 1.07 0.95 1.49 1.39 1.28 1.17 1.06 0.93
4 1.40 1.31 1.21 1.11 1.00 0.89 1.40 1.31 1.21 1.10 1.00 0.88 1.39 1.30 1.20 1.09 0.99 0.87
8 1.34 1.35 1.16 1.06 0.96 0.84 1.34 1.25 1.16 1.06 0.96 0.84 1.34 1.25 1.15 1.05 0.95 0.84
24 1.30 1.20 1.10 1.00 0.90 0.79 1.30 1.20 1.10 1.00 0.90 0.79 1.30 1.20 1.10 1.00 0.90 0.79
$ Subtract 5 0 C from each of the ambient column heading for water cooled transformer. Minimum water
temp. must be above 0 0 C
8.1 DATA
% Voltage dip = (Starting KVA X 100) / fault KVA at point of supply
Size of Starting KVA (Approx) for
Size of Approx condition of starting
PVC
motor current
Aluminum D.O.L Star/delt Auto
(400V, (Amp) at
cable 6 F.L a 2F.L Transformer
50Hz) 0.8 P.F
(mm2) current current 1.5 F.L 1.35 F.L
5 H.P 8 2.5 33.25 - - -
10 H.P 15 4 62.35 20.78 - -
15 H.P 22 10 91.44 30.48 - -
20 H.P 29 16 120.54 40.18 30.14 25.11
30 H.P 42 25 174.58 58.19 43.65 36.37
BALANCE LOAD
IS 13779: 1993 IEC 1036:1996
% Load P.F Class % Load P.F Class
(Ib) (Cos φ) (Ib) (Cos φ)
1.0 2.0 Direct T/F 1 2
Connected Operated
5 - < 10 1.0 ±1.5 ±2.5 5 - < 10 2 - <5 1.0 ±1.5 ±2.5
10- < Imax 1.0 ±1.0 ±2.0 10- < Imax 5- <Imax 1.0 ±1.0 ±2.0
10- < 20 0.5 Lg ±1.5 ±2.5 10- < 20 5- <10 0.5 Lg ±1.5 ±2.5
0.8 Ld ±1.5 - 0.8 Ld ±1.5 -
20- < Imax 0.5 Lg ±1.0 ±2.0 20- < Imax 10- < Imax 0.5 Lg ±1.0 ±2.0
0.8 Ld ±1.2 - 0.8 Ld ±1.0 -
* Spl. Request 0.25Lg ±3.5 - * Spl. * Spl. 0.25Lg ±3.5 -
20- < 100 0.5 Ld ±2.5 - Request Request 0.5 Ld ±2.5 -
20- < 100 10- <100
UNBALANCE LOAD
10- < Imax 1.0 ±2.0 ±3.0 10- < Imax 5- < Imax 1.0 ±2.0 ±3.0
(20- < Imax 0.5 Lg ±2.0 ±3.0 (20- < Imax 10- < Imax 0.5 Lg ±2.0 ±3.0
Cos Φ
Nominal Ratio Nominal Ratio
K= ARCT = ARPT =
Cos ( Φ – θ ± δ ) 1 – (e/100 ) 1 – (p/100 )
Where
Φ = Load Factor angle , θ = Phase angle error of CT , δ = Phase angle error of PT
e = CT Ratio Error , p = PT Ratio Error
MULTIFYING FACTOR ( MF )
400/1 x 300
-/1 100
= 1200 for WH Reading ( Because meter is WH Meter )
RATIO 400-200-100/1-1-1-1-1
PRI/SEC 400/1 200/1 100/1
CURRENT (A)
PRI. CONN. P1C1– P2C2 C1-C2 C1-C2
SEC. CONN.
CORE 1 1S1-1S3 1S1-1S3 1S1-1S2
CORE2 2S1-2S3 2S1-2S3 2S1-2S2
CORE3 3S1-3S3,S’ 3S1-3S3,S’ 3S1-3S2,S’
CORE4 4S1-4S3 4S1-4S3 4S1-4S2
CORE5 5S1-5S3 5S1-5S3 5S1-5S2
CORE 1 2 3 4 5
OUT PUT* - - 40 - -
ACC. CLASS* PS PS 0.5 PS PS
ISF/ALF* - - ≤5 - -
Vk (V) Min* 1200 1200 - 1200 1200
I exc@Vk *(mA) 25 25 - 25 25
Max *
Rct at 75 0 C 5 5 - 5 5
Max*
* AT 400/1 AND 200/1 RATIO ONLY
P1 C2
C1 P2
S1 S2 S3
CONNECTION DIAGRAM
P1 C2
C1 P2
S1 S2 S3
3 WIND ZONE
Properties of Conductor
CALCULATION
F =[ f1 – ( w2 l2 E / 24 T12 )] - α E ( θ2 – θ1 )
= [6.88 x106 – (1.34552 x 3502 x 5608x106 / 24 x 3355.52 ) ] - 23
x10-6 x 23 x10-6 ( 90 -32 )
= - 5.20041 x 106
T2 = Tension = f2 x A
But f22 ( f2 - F ) = G = w2 l2 E / 24 A2
f22( f2 + 5.20041 x 106) =1.34552x 3502 x5608x106 /24x487.5x10-12
Now f2 = 4.7006 x 106 Kg/m2
T2 = Tension = f2 x A = 4.7006 x 106 x487.5x10- 6 = 2292 KG
SAG = D2 = w l2 / 8 T2= 8.989 Mtr
F =[ f1 – ( w2 l2 E / 24 T12 )] - α E ( θ2 – θ1 )
= [6.88 x106 – (1.34552 x 3502 x 5608x106 / 24 x 3355.52 ) ] - 23
x10-6 x 23 x10-6 ( 0 -32 )
= 6.40815 x 106
T3 = Tension = f3 x A
But f32 ( f3 - F ) = G = w2 l2 E / 24 A2
f32( f3 - 6.40815 x 106) =1.34552x 3502 x5608x106 /24x487.5x10-12
Now f3 = 9.0629x 106 Kg/m2
T3 = Tension = f3 x A = 4418 KG
SAG = D3 = w l2 / 8 T3= 4.663 Mtr
SPAN HOT SAG COLD SAG SPAN HOT SAG COLD SAG
( D2 ) ( D3 ) ( D2 ) ( D3 )
w l2 / 8 T2 w l2 / 8 T3 w l2 / 8 T2 w l2 / 8 T3
10 0.00733 0.0038 300 6.60422 3.20157
50 0.18345 0.09517 350 8.98907 4.663415
100 0.73380 0.38068 400 11.7408 6.090991
150 1.65105 0.85654 450 14.8594 7.708910
200 2.93520 1.52274 500 18.3450 9.51717
250 4.58626 2.37929 550 22.1975 11.51578
Tower Dimension A B C D E F G H I
Type of Tower
DA (0 to 2 Deg.) 28908 4193 4170 4230 16315 2455 7606 6100+150 3150
DB (2 to 15 Deg.) 27550 5890 3900 3900 13860 0 7606 6100+150 2600
DC (15 to 30 Deg.) 27810 6150 3900 3900 13860 0 7606 6100+150 2660
DD (30 to 60 Deg.) 28280 5990 4130 4300 13880 0 7607 6100+150 2475
J K M N O P Q R S L
DA (0 to 2 Deg.) 850 3150 3028 1024 3028 3045 1200 3045 5890
DB (2 to 15 Deg.) 1600 2600 2525 1750 2525 2560 1900 2560 6700
DC (15 to 30 Deg.) 1800 2360 2770 1900 2130 2905 2000 2100 7000
DD (30 to 60 Deg.) 1860 2475 2291 2217 2291 2665 2600 2665 8600
220 KV(Normal Span-350 mtrs, Conductor-37/4mm AAA, Earthwire-7/3.15mm GS wire)
A B C D E F G H I
DA (0 to 2 Deg.) 35506 5540 5175 5275 19515 2768 9582 7015+150 3600
DB (2 to 15 Deg.) 34490 7940 4900 4900 16750 0 9582 7015+150 3706
DC (15 to 30 Deg.) 35390 7940 5350 5350 16750 0 9582 7015+150 3466
DD (30 to 60 Deg.) 35255 8406 5050 5060 16750 0 9582 7015+150 3650
J K M N O P Q R S L
DA (0 to 2 Deg.) 1400 3600 3591 1598 3591 3900 1800 3900 7502
DB (2 to 15 Deg.) 1750 3025 3612 1975 3012 3475 2200 3096 7830
DC (15 to 30 Deg.) 2068 3166 3757 2285 2667 3950 2500 3180 8500
DD (30 to 60 Deg.) 2400 3650 3450 2800 3450 3250 3200 3250 9900
Sl. DESCRIPTION 400 KV, AAAC 61/3.45 400 KV, AAAC 61/3.45 400 KV, AAAC 61/3.45
No
Sl. CATEGORY OF CLEARANCES Unit 132 220 400 800 ±500 REMARK
KV KV KV KV KV
1 Clearances of Overhead Electrical Lines across Mtr 7.01 7.83 9.5 - - Rule 77 IE 1956
the street
2 Along the street Mtr 7.01 7.83 9.5 - - Rule 77 IE 1956
3 Else Where Mtr 6.41 7.23 8.9 - - Do
4 Minimum clearance between Conductor & Mtr 4.0 4.6 5.5 - - IS 5613
Tree
5 Clearance to Ground at Crossing with Tram- Mtr 3.57 3.85 - - - Rule 78 IE 1956
way / Trolley
6 Clearance to Ground at Crossing with Telecom Mtr 3.05 4.58 5.49 7.94 - IS 5613 ( Part II/
lines Sec-I ) 1985
7 Clearance to Ground at railway crossing
5. Inside Station Mtr 14.2 15.11 - - - IS 5613 ( Part II/
6. Out Side Station 13.11 - - - - Sec-I ) 1985
8 Clearance to Ground at Electrified railway
crossing Mtr 16.2 18.6615.11 - - - IS 5613 ( Part II/
7. Inside Station 14.2 - - - Sec-I ) 1985
8. Out Side Station
9 Vertical Clearance of Overhead Lines from any Mtr 4.6 5.4 7.04 Rule 77 &79 IE
building roof 1956
10 Horizo. Clearance of Overhead Lines from any Mtr 2.3 2.9 3.7 5.34 - Rule 79 & 80 IE
building roof 1956
11 Ground Clearance in Out Door Sub Station Mtr 4.6 5.5 8.8 - - Rule 64-2 (a) (ii)
IE 1956
12 Sectional Clearance in Out Door Sub Station Mtr 3.6 4.3 5.57 - - do
Where C s = Co- relation factor (As per IEEE 80 /1985), its value is
obtained according to thickness of crushed rock layer (hs)
and
Reflection factor K = (p – ps) / (p + ps)
P = Earth Resistivity in Ohm- Mtr,
ps = Surface layer resistivity in Ohm – Mtr
t = Duration of Allowable current in Sec.,
I = Maxm. Current to the grounding System.
n= Number of parallel conductor in the grid,
h = Depth of burial in Mtrs
L = Length of buried conductors in mtrs.
D = Spacing of conductors in grid in mtrs.
d = Dia of conductor ( Equivalent to Flat section )
R = { ( p/ 4r ) + ( p/L ) } Ohm
Where p = Soil Resistivity in Ohm- Mtr,
r = Radius in mtr of a Circle having same area as that covered by
earth mat
L = Length of buried conductors in mtrs.
8. TRANSFORMER CABLES
1. DATA REQUIRED
3Ph. Fault MVA for O/C Relay setting
Single Line to Ground Fault MVA for E/F relay
CTR used
Relay Characteristics
2. STANDARD DATA TO BE USED
Operating Time$ can be selected as follows
$ The selection and choice of the operating time of the relays depend
upon the type of protection scheme used in the system and type of
radial system and type of relay used in the system.
PSM of O/C relay
It is to be selected according to the load required by the system and
thermal characteristics of the line conductor
Standard allowable OVER LOADING FACTOR is ( 1.25 to 1.5 )
PSM of E/F relay
It is to be selected according to the residual current and allowable
unbalance current in the a system
EXAMPLE 1
Suppose 3 Phase fault MVA = 1000 MVA
Single line to Ground fault MVA = 750 MVA
CTR used = 500/1
STEP 1 ( CALCULATION OF CM )
3 TDS 3 TDS
OT 0.5 TDS = 0.278 ≈ 0.3
log10 CM log10 46.65
SO, FINAL PSM = 0.75, TSM= 0.3
Note ;- For E/F relay setting SLG fault MVA should be considered.
EXAMPLE 2
Note ;- For general practice the temperature of rigid aluminium bus to 1000
C and for emergency rating 2500 C for short circuit duty.
Vibration in Bus
Sl PLACES ILLUMINATION
LEVEL (LUX )
1 Switch Yard 25
2 Control Room, 300-500
3 Carrier Room, LT Panels, Charger Room, 300
Offices, Conference Room, Rest Room,
Work Shop, Repair Bay etc
4 Battery Room, Corridor, PLCC Room, 100
Toilets, Store Room, Cloak Room, stairs
etc..
2. VOLTAGE STANDARD
1 IS 335 : 993 New Insulating Oil 10 IS 6104 / Test method of IFT of oil
1971 against water by Ring
method
2 IS 1448 ( Test Method for petroleum products by 11 IS 6262 Test method for power
PT –10 ) cloud point and pour point . :1971 factor and Dielectric
1970 Constant of insulating
materials
3 IS 1448 ( Density of Crude petroleum liquid 12 IS Method of Determination
PT –16 ) petroleum products by Hydrometer 6792:1992 of Electric Strength
1970 Method
4 IS 1448 ( Flash point by DENSKY – MARTENS 13 IS 6855 Method of sampling for
PT –21 ) apparatus :1973 liquid Dielectric.
1970
5 IS 1448 ( Determination of Kinematics and 14 IS 9434 Guide for sampling and
PT – 25 ) Dynamic Viscosity :1992 analysis of free and
1970 dissolved gasses and oil
from oil filled equipment.
G) SURGE ARRESTERS
IEC: 99-4 Specification for Surge Arresters 3 IEC 270 Partial Discharge
1 without gap for AC System Measurement
2 IEC: 99-1 Non Linear Resistor type gapped 4 IS : 3070 LA for AC Systems
arresters for AC Systems (Pt-3 ) / Specification for Metal
1993 Oxide LA without gap. )
Telecommunication system
Teleprotection system
Sl Data Value
No
1 Comm. Channel width 0-4 KHz
2 Unused ( Vacant ) width 0-300 Hz ( To avoid 6th Harmonics )
3 Speech channel 300-2200 Hz
4 Pilot frequency dialing 3600 ± 30 Hz
purpose
5 Centre frequency for 3600 Hz
healthy ness test
6 For VFT band 2200-3570 Hz
7 Frequency Shift Keying 50, 100, 200 baud as per CCITT
(FSK) recommendation
8 DATA TRANSMISSION a. 1200 baud rate FSK to CCITT Rec.V23
on a basic 4-wire, 4 KHz PLC
b. 2400 baud phase modulated 4- wire
leased telephone type circuit as CCITT
Rec.V29
c. PCM 64 kbps digital data channel to
CCITT Rec.C702
d. For FAX, CCITT Rec.T3 used with
vestigial side band modulation ( BW 800-
2600 Hz
9 LEASED CIRCUITS a. 2- Wire audio cables ( up to 20 Km )
b. CCITT M1 020 and M1 040 types of
circuit ( Similar to PLC and Microwave
System )
c. Wide Spectrum Signals on either group (
60 to 108 KHz ) or super group ( 312 to
520 KHz ) as per CCITT Rec. M900 &
M910
d. Satellite leased circuit such as SCPC, FM
modulated, Analogous
10 MIN. CLERANCES a. LT Lines ( 230/400 V ) -- 1.22 m
POWER AND TELECOM b. 11 KV Lines ---- 1.83 m
LINE c. 33/66 KV Lines ---- 2.44 m
d. 132 KV Lines ---- 3.05 m
e. 220 KV Lines ---- 4.58 m
f. 400 KV Lines ---- 5.49 m
800 KV Lines ---- 7.94 m
DISPLAY DISPLAY
AG,BG,CG Phase to Ground
Fault M1PT,M2 Phase Dist. Time Delay
PT,M3PT
AB AB Phase Fault LOP Loss of Potential
BC BC Phase Fault 67Q1, Dirr. Neg. Seq. O/C Inst
67Q2,67Q
CA CA Phase Fault 67N1,67N2 Dir. E/F Time Delay
,67N3
TWO PHASE TO 67Q2T,67 Dirr. Neg. Seq. Time
ABG GROUND Q3T,67Q4 Delay
BCG SAME 3P27 3 Phase U/V
CAG SAME 50H High Set O/C , Inst
ABCT 3 Phase Fault 50Q1 Neg. Seq Non – Dirr
Z1G,Z2G,Z3G Zone Mho or Quadr. 50N1 High Set E/F Non-Dir
M1P,M2P,M3P Zone Phase Dist. Inst 3PT 3 Pole Trip
Z1GT,Z2GT,Z3 Zone Dist. Time 3P59 3 Phase O /V
GT Delay
1. POWER TRANSFORMER
Periodi Checking/Testin Notes on Actions to be
city g Checking taken
Pre- 1. Components 1. All Components 1. Compare with
Commissi checking ( OLTC, PRV, factory value.
oning Bushing others )
2. Electrical Testing 2. Routine Test 2. –do-
Hourly/Co 1. Temp. Monitoring 1. Reading of OTI, 1. Follow up
ntinuous WTI action
2. Electrical 2. Voltage, 2. Follow up
Parameters Current, Loads action
3. Oil Flow ( OFAF ) 3. Ensure about the 3. Follow up
flow action
Daily 1.Oil Levels in 1. Check up to 1. Top up Oil if
Transformer Level required
2. Cooling System 2. check contacts, 2. change or
bearings etc replace the faulty
parts
3. Breather Reagent 3. Check Colour of 3. Change
Reagent Reagents
Quarterly 1.Bushings, OTI, WTI, 1. Clean the Tank, 1. Suitable Action
other Equipments Bushing
and Trial operation
of components
2. Oil condition in 2. Dielectric 2. Filter the Oil if
Transformer Strength of Oil required.
Half 1. DGA of Oil 1. Check Sample of 1. Compare with
Yearly Main Tank Oil and Initial Result and
OLTC Follow up action
Yearly 1. Electrical Testing 1. Routine Test Compare with
2. PI , Tan δ value 2. Record Values Initial Result and
3. DGA 3. DGA Analysis Follow up action
4. Detail Checking of 4. Check
Clamps, joints etc.
5. OLTC 4. 5. OLTC Checking
3. CVTs and PT
SYMPTOMS REMEDIES
1. Corrosion 1. Remove Electrolyte
2. Pour Distill Water
3. Refill with New Electrolyte
2 Sulphation
Under Charging 1. Initial stage, repeat the low rate
Over Discharge Charging and Discharging.
Too strong /Weak Acid 2. Latter stage, Special treatment
Too Rapid Discharge should be provided
Short Circuit
Plate Exposed to Air
6. SURGE ARRESTER
Periodicity Checking/Testing Actions to be taken
Daily 1.Surge Counter Reading 1. Record purpose
2. Leakage Current 2. within the Green zone
Reading 3. Like Crack, damage
3. Other visual check
Monthly 1.Earth Resistance 1. within the Limit
2. Leakage Current 2. Compare Results
Analysis.
Yearly 1. Capacitance Compare with Initial Results
Measurement and Follow up action
2. All Connections
3. Cleaning of insulator
4. Ammeter Calibration
1. Name :-
2. Address / phone No :-
3. Comments if any :-
Presentation of Data
Table-A
Sl. Topics / Sub- Topics Area /Page
No No.
Errors Noticed
2. DATA# Error ( Use Table C )
4. Special Suggestions :-
P.K.PATTANAIK
Deputy GENERAL Manager (Elect. )
E&MR Division,
OPTCL ( Formerly GRIDCO )
BHUBANESWAR, ODISHA-751022