" Power Details ": Project Name
" Power Details ": Project Name
SITE ID : B10
ASSESSMENT:
APPROVED REMARKS:
DISAPPROVED REMARKS:
B10 SL
LEMERY
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
AC POWER DETAILS
Electrical Connectivity: Permanent Temporary Tap to neighbor
Genset
Genset 1 Brand: Powercity Genset 1 capacity: 45 KVA With Pad & Fuel Line (Y/N): N
Genset 1 Brand: Genset 2 capacity: With Pad & Fuel Line (Y/N):
Genset 1 Brand: Genset 3 capacity: With Pad & Fuel Line (Y/N):
KWHR Meter Rating: CL100 ATS Brand: Powercity ATS Capacity: 225A, 3P
Main breaker capacity( inside radio room ): 100 AT Wire size: 2-30mm²THHN
MCB MDP
Rating ON/OFF LOAD Rating ON/OFF LOAD
150 ON 20 ON NO LABEL
20 ON SPARE
20 ON NO LABEL
20 OFF NO LABEL
20 ON SPARE
*put NO LABEL for those
without proper labelling 100 ON TO ACPDB
SPACE
SPACE
SPACE
MCB ACPDB
Rating ON/OFF LOAD Rating ON/OFF LOAD
100 ON SPACE
30 ON UPPER ACU
30 ON LOWER ACU
20 ON NO LABEL
40 OFF NO LABEL
20 ON CO #1
20 ON CO #2
20 ON NO LABEL
20 ON NO LABEL
60 ON ELTEK 1
SPACE
SPACE
20 ON TOWER LIGHTS
SITE SURVEY REPORT
DOCUMENT NO PAGE
SHELTER TYPE (VAN, CONCETE SHELTER, BLDG):VAN AC Loading @ MAIN (AMPERES): L1-44.3 / L2-43.7
SHELTER AREA: LOT SITE SIZE OF WIRE @ ACPDB - MAIN (mm²/AWG): 2-30mm²
TYPE OF VAN (COLLAPSIBLE, RIGID) : LENGTH OF WIRE: 40 m
TRANSFORMER QUANTITY & CAPACITY (KVA): 25 KVA
ACPDB RATING (AT): 100 MAIN BREAKER RATING(AT): 100
Breaker Ratings (AT) Load AMP Load Description
SPACE
30 8.1 UPPER ACU
30 0.3 LOWER ACU
20 0.2 NO LABEL
40 0.2 NO LABEL
20 0.8 CO #1
20 0.1 CO #2
20 0.3 NO LABEL
20 0.3 NO LABEL
60 33 ELTEK 1
SPACE
SPACE
20 0.2 TOWER LIGHTS
AC POWER SUFFICIENCY
Current (I)
AC LOAD Voltage (V) VA Remarks
L1 L2 L3
MAIN BREAKER 224 44.3 43.7 At ACPDB
9923.20
Total 44.3
It = Highest line current reading x 130 % (Safety factor considering Battery charging, WACU starting current & DC loading increase)
It = 44.3 x 130 %
It = 57.59 Amps.
Recommendation/s:
Transformer loading:
Actual AC load (V x It) / Transformer KVA Rating X 100 %
% loading = 51.60 %
Note: Sufficient
NO PICTURE NO PICTURE
ECB MCB
NO PICTURE NA
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
MTS ATS
N/A
MDP ACPDB
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
PHOTOS
N/A
N/A
N/A N/A
SITE SURVEY REPORT
DOCUMENT NO
B5 - SITE LAYOUT
ACPDB
100 AT
RECTIFIER
RECTIFIER
TRANSFORMER
25 KVA
NEW ACPDB 1
125 AT 38 mm2 + 14 mm2 THHN U.G.
40 meters, 1 1/2 in. dia. IMC
NEW ACPDB 2
125 AT
RECTIFIER
RECTIFIER
38 mm2 + 14 mm2 THHN U.G.
40 meters, 1 1/2 in. dia. IMC
12 meters
TAAL DIVERSION ROAD 50 mm2 THHN AERIAL TO TAAL - SAN NICOLAS ROAD
TRANSFORMER
25 KVA
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR
B10 S.L
LEMERY
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
38 mm2 THHN
7 meters, 2 in. dia. IMC
TRANSFORMER
25 KVA 12 meters
38 mm2 THHN AERIAL CL100 M
38 mm2 THHN,
20 meters, 1 1/2 in. dia. IMC
(DETERIORATED CONDUIT)
ECB L1: 44.3
150 AT L2: 43.7
NEMA 1 V: 212 2 meters - 38 mm2 THHN, 1 1/2 in. dia IMC
2 meters - 50 mm2 THHN, 1 1/2 in. dia IMC
(ALREADY DETERIORATED) (IMPROPER WIRING INSTALLATION)
20AT,2P 20AT,2P
30 mm2 THHN,
2 meters, 1 1/2 in. dia. IMC NO LABEL 1 2 SPARE
20AT,2P 100AT,2P
TO ACPDB
NO LABEL 3 4
20AT,2P
SPARE 5 6 SPACE
20AT,2P
NO LABEL 7 8 SPACE
20AT,2P
NO LABEL 9 10 SPACE
ACPDB
30 mm2 THHN + 30 mm2 BCU GND U.G., (G.E.)
40 meters, 1 1/2 in. dia. IMC
100AT,2P
MAIN 1 2 SPACE
30AT,2P 30AT,2P
UPPER ACU 3 4 LOWER ACU
20AT,2P 40AT,2P
NO LABEL 5 6 NO LABEL
20AT,2P 20AT,2P
CO #1 7 8 CO #2
20AT,2P 20AT,2P
NO LABEL 9 10 NO LABEL
60AT,2P
ELTEK 1 11 12 SPACE
20AT,2P
SPACE 13 14 TOWER LIGHTS
DOCUMENT NO PAGE
SITE SURVEY REPORT
TECHNICAL SERVICES DIVISION
SITE ID AREA SITE NAME: VENDOR
B10 S.L
LEMERY
ROLLOUT REMARKS
LTE AC UPGRADE AC POWER DETAILS
Proposed SLD
TRANSFORMER
25 KVA 12 meters
50 mm2 THHN AERIAL CL200 M
ECB
150 AT 50 mm2 + 14 mm2 THHN,
NEMA 1 4 meters, 1 1/2 in. dia. IMC
125AT,2P 125AT,2P
50 mm2 + 14 mm2 THHN,
2 meters, 1 1/2 in. dia. IMC 1 2 A
70AT,2P 70AT,2P
SPARE 3 4 SPARE
20AT,2P 20AT,2P
L.O. GENSET C.O. GENSET
SHELTER 5 6 SHELTER
20AT,2P 20AT,2P
L.O. 7 8 C.O. GH
GH PERIMETER 20AT,2P 20AT,2P
LIGHTS 9 10 SPARE
NEW ACPDB 1
125AT,2P
70AT,2P 70AT,2P
DC PLANT 1 1 2 DC PLANT 2
30AT,2P 30AT,2P
2 HP ACU 3 4 2 HP ACU
30AT,2P 20AT,2P
2 HP ACU 5 6 LIGHTINGS
20AT,2P 20AT,2P
C.O. 7 8 EMER. LIGHTS
30AT,2P 30AT,2P
SPARE 9 10 SPARE
DOCUMENT NO PAGE
ROLLOUT REMARKS
LTE AC UPGRADE
AC POWER DETAILS
Proposed SLD
NEW ACPDB 2
125AT,2P
70AT,2P 70AT,2P
NEW REC NEW REC
1 2 FED B
FED A 70AT,2P 70AT,2P
SPARE 3 4 SPARE
70AT,2P 70AT,2P
SPARE 5 6 SPARE
20AT,2P 20AT,2P
SPARE 7 8 SPARE
20AT,2P 20AT,2P
SPARE 9 10 SPARE
30AT,2P 30AT,2P
SPARE 11 12 SPARE