Professional Documents
Culture Documents
Windrive - 2001 Assembly Instruction
Windrive - 2001 Assembly Instruction
08
Firmware Version V03.00
Assembly Instructions
for Automatic Sliding Doors SLIDEDOOR
3 Basic Functions 7
4 Components Assembly 10
4.1 Preparing the Profiles 10
4.2 Recommended Tools 11
4.3 Installation Hints 11
4.4 Preassembly / Dimensions Double-leaf Sliding Doors EB 12
4.5 Preassembly / Dimensions Single-leaf Sliding Doors ER 14
4.6 Preassembly / Dimensions Single-leaf Sliding Doors EL 16
4.7 Options 18
4.7.1 Battery Module u 18
4.7.2 Emergency Opening with Spring Packet u 18
4.7.3 Emergency Opening with Rubber String u 20
4.7.4 Manual Disengagement with Bowden Wire ◆ 22
5 Installation On Site 23
5.1 Installation Types, Dimensional Drawings 23
5.2 Installation of Profiles 23
5.3 Installation of the Sliding Leaves 25
6 Mechanical Tuning 26
6.1 Aligning Sliding Leaves 26
6.2 Check Grounding 26
6.3 Adjusting Lock Clearance 27
6.4 Adjusting Manual Disengagement ◆ 28
6.5 Holding Strip for Cladding 28
6.6 External Lock Monitoring Device ◆ 29
7 Electrical Connections 30
7.1 Mains Connection 30
7.2 Plug-in Connections 30
7.3 Terminal Connections 30
7.4 User Interface Connection ◆ 31
7.5 Connection Operating Mode Switch ◆ 31
7.6 Connection of Monitored Sensor
for Secondary Closing Edge ◆ 31
7.7 Threshold Circuit ◆ (Airlock) 31
7.8 7-Segment Display / LED’s 32
9 Trouble Shooting 40
9.1 Fault Diagnosis 40
9.2 Behaviour on Faults 40
9.3 Fault Table 41
9.4 Symbols of the 7-segment digital display 42
9.5 Protective Devices of the Drive 42
10 Check List 43
11 Handing-over to the System Operator 43
Fold-Out Page
The enterprises Landert Motoren AG and Landert GmbH are certified according to
ISO 9001.
Explanation of Symbols Non-observance endangers the safety of the installation personnel, the system opera-
tor or the user.
Text passages in grey background must be absolutely observed for sound operation
of the system! Disregard may cause material damage.
This symbol marks optional components that are not installed in all systems.
Components At the back of these instructions you find a fold-out page. The positions used in the il-
lustrations – for example (2) = header profile – always designate the same structural
member in the detail drawings. For orientation purposes you should always keep the
fold-out page visible during the installation.
Installation Sequence For installation sequences, letters – e.g. A, B – are used in the detail drawings.
Languages These instructions are available in different languages. Please ask your TORMAX
dealer.
SLIDEDOOR For the installation and commissioning of this system, the following instructions and
Win Drive 2201 data sheets are useful; get hold of these documents before beginning the installation
works!
The leaves must be manufactured from materials that pose no potential danger of in-
jury when breaking (e.g. when using glass, use toughened safety glass, compound
safety glass etc.).
Fundamental Protective • Use the system only when it is in a technically sound condition. Faults that might af-
Measures – Professional fect safety must be eliminated at once.
Conduct
3 Basic Functions
Motion Sequence in General Motion sequence is carried out by a controlled DC motor. Parameters for the door move-
ment such as velocity, acceleration and deceleration can individually be programmed
in either direction. The open position is actively controlled by the DC motor. A permanent
and reduced closing force safeguards the closed door position. With the mechanical
emergency opening system installed, the required higher motor torque is adjusted with
the programmable function 5. With the parameters b, C, d and E the motor forces in
opening and closing direction can be adapted with due consideration to the safety
regulations.
Configuration The basic setting of the installation occurs automatically after the manual initialisation
of the auto configuration menu (Section 8.2). Simultaneously, connected components
(user interface, lock, safety devices 1 and 2) are self detected and automatically pro-
grammed. Correct installation of the drivers must be observed (section 4.4 – 4.6). Track
distance is automatically recorded and saved as a reference. In the subsequent calibra-
tion run, the control unit detects the door position and compares the newly recorded
track with the stored reference distance. Out of tolerance deviations, encoder- or motor
defects bring the installation to a stand still. The corresponding error is indicated.
Further functions and parameters can be programmed according to the programming
table (section 8.4) via the configuration interface directly on the control unit.
Activator inside / outside The door opens in operating mode AUTO, AUTORED and EXIT *. The motion sequence
results according to parameters no. 0 through 4. The hold-open time is determined by
parameter no. 3.
* only with sensor inside
Key Switch Opens the door in operating mode OFF, AUTO, AUTORED and EXIT. The motion se-
quence results according to parameters no. 0, 1, 2, 4. The hold-open time is 5 s, how-
ever, it can be adapted with parameter A.
Safety Facility Closing The photocell or safety activator prevents the door from closing or reverses it during the
closing cycle. The hold open time of the safety devices is 1 s.
Monitored Safety Facility for See programming table section 8.4 and for the connection section 7.3.
the Secondary Closing Edge
Electronic Reversing Electronic reversing monitors the door motion during the opening and closing cycles. If
the door hits an obstacle during the closing motion, the control system detects that
situation and indicates error no. 30. The door reverses its direction withIN1.5 s, stops
during the hold-open time and closes thereafter with a speed of max. 17 cm/s.
After 5 consecutive closing attempts, the door stops at the obstacle and switches to
Fault Repair To faults that make the door switch to manual operation it reacts with a reset of
the control unit. If the fault is eliminated, the door performs a calibration run and func-
tions normally afterwards. If the fault is still present, after 3 retries the door switches
definitively to manual operation.
Operating Modes The 6 operating modes can be selected either via the user interface or limited via hard-
ware inputs. Operating modes can be activated via the inputs IN1 and IN2 have prior-
ity over the user interface. Consequently, operating modes can no longer be changed
trough the user interface.
Even in case of power interruption, the selected operating mode on the user interface
remains active.
Operating Mode OFF In operating mode OFF, the door is closed and locked (). The door can only be opened
through the key switch (), the input function emergency opening (6/4, 7/4) or via battery
(5/2, 5/6). After switching to operating mode OFF, the door closes as soon as no person
is in the range of the activators or the safety facilities. After 10 s, the door closes with
reduced speed, even if sensors or an external safety facility are activated.
If using the user interface the activator inside is still observed during another 10 sec.,
so that the area can be left after switching to operating mode OFF. LED 1 (operating
mode OFF) at the user interface flashes in 3 sets of three consecutive pulses until
10 s have elapsed and then closes and locks correctly.
Operating Mode AUTO In operating mode AUTO, the door opens through the activators inside and outside to
the whole opening width and closes after the set hold-open time. The door is always
unlocked in operating mode AUTO (Exceptions see functions 6/6 and 7/6).
Operating Mode AUTORED Operating mode AUTORED corresponds to operating mode AUTO, but with reduced
opening width. If AUTORED is active longer than 3 s and if afterwards the operating
mode EXIT, OFF or OPEN is selected, the new operating mode adopts the reduced
opening width.
Operating Mode EXIT In operating mode EXIT, the door opens only through the activator at the inside. The
key switch u is also enabled. The activator outside is not observed even when the door
is open. If AUTORED was active longer than 3 s before the selection of OPEN, the
reduced opening width is adopted.
Operating Mode OPEN The door opens and remains open. If AUTORED was active longer than 3 s before the
selection of OPEN, the reduced opening width is adopted.
Panel Lock The panel lock protects the user interface against unauthorized access. On closed
contact, all actions at the user interface are inhibited. Operating modes and faults are
still displayed.
Lock The lock is locked in operating mode OFF. It is unlocks when the key switch is acti-
vated.
The door unlocks also when the optional emergency opening function 6/4 and 7/4 is
used or in case of power failure with the program setting 5/2 or 5/6. Unlocking and
locking in operation mode AUTO/EXIT and AUTORED is achieved with an optional
switch and function (6/6 and 7/6). Lock position is monitored. A wrong position is cor-
rected automatically.
Power Supply 24 V DC The Win Drive 2201 control system provides a power supply of 24 V DC for sensors,
and signalling. The power supply may be continuously loaded to a maximum of 1.0 A.
With load > 1.0 A, the LED goes out on the display. On overload, the unit switches off
automatically.
Internal Protection Motor, transformer and control system contain thermal relays that interrupt the power
supply on overheating.
In case of a system error the installation will routinely revert into a save mode. The doors
immediately slow down and the installation switches to operating mode MANUAL.
Output OUT1 The function of OUT1 is according to the programming table freely selectable (see
section 8.4 - 8.5). On mains failure, the 24 V output is inactive. It is suited to connect a
relay or a signal lamp. A direct connection of Out1 on IN is possible for special applica-
tions.
Input IN1 and IN2 The functions of IN1 and IN2 are freely selectable (see section 8.4 - 8.5). A function
activated through a switching contact is executed as long as the contact remains ac-
tive.
Behaviour on Mains Failure Systems without Battery Module or Mechanical Emergency Opening:
On mains failure the door stops immediately. Afterwards it is freely moveable. To protect
people speed is controlled by the motor even in currentless condition.
Systems with Battery Module:
Comportement is programmable (see section 8.4 - 8.5, adjustment 5)
Systems with Mechanical Emergency Opening:
On mains failure the door opens immediately. The speed is controlled by the motor.
Emergency Opening and Battery Module can be used togehter only in a limited way
(see section 8. 4, function 5)
20 20
25 21 25
21
T1166_5
T1166_79
27
26 17 27
26 29
C
20
65
B
T1166_39 max. 300 A
max. 300 T1166_45
max. 300
max. 300
50
Z-Profile
500
A B B
A
32 32 … 46 57
T1166_38
10 mm 13 mm 3 mm T 25 10 mm
T1166_54
T 25 T 25 T 25 3 mm
T1166_55
T1166_58
4 Nm
T1166_4
L+16
L/2 L/2
m u
70
c 98±1 98±1 c
T1166_10
Opening travel distance W= 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 Header profile length L = 2W + 150
Header profile length min. L= 1750 1950 2150 2350 2550 2750 2950 3150 3350 3550 3750 3950 4150 4350 4550 4750 4950 5150 5350 5550 5750 5950 Motor dimension, min. 790 m = W/2 + 240
Header profile length with emerg. Deflection unit u = W/2 + 240
opening L* = 2020 2120 2220 2350 2550 2750 2950 3150 3350 3550 3750 3950 4150 4350 4550 4750 4950 5150 5350 5550 5750 5950 Belt length at W <1100 f = W + 2160
Motor dimension, min. 790 m= 790 790 790 790 840 890 940 990 1040 1090 1140 1190 1240 1290 1340 1390 1440 1490 1540 1590 1640 1690 Belt length at W≥1100 f =2W + 1060
Deflection unit u= 640 690 740 790 840 890 940 990 1040 1090 1140 1190 1240 1290 1340 1390 1440 1490 1540 1590 1640 1690 Trolley distance c = W/2 – 180
Belt length f= 2960 3060 3160 3260 3460 3660 3860 4060 4260 4460 4660 4860 5060 5260 5460 5660 5860 6060 6260 6460 6660 6860
Trolley distance c= 220 270 320 370 420 470 520 570 620 670 720 770 820 870 920 970 1020 1070 1120 1170 1220 1270 (*with emergency opening spring and at
W<1070 mm true for: L = W+1220)
Double-leaf Sliding Doors EB
B
A
50
T1166_28
T1166_46e
T1166_52
4 Nm
Xmin. = S
W/2–25
B T1166_14
A
A B C
16
D 4 Nm
C
T1166_18
5
T1166_73
B 4 Nm A SW 10
T1166_8 T1166_13
5x
C 4 Nm
B
A
13
T1166_17 A
B
14
4.5 Preassembly / Dimensions Single-leaf Sliding Doors ER
Opening to the right
L+16
u
160 70
56
28
127±1 c
W T1166_11
5x
B
A B
A
T1166_47
T1166_51
16
T1166_46e
T1166_18
D
A
A B C
4 Nm
C
B 4 Nm A SW 10
T1166_14
T1166_8
4 Nm
D T1166_13
C
C 4 Nm
A
T1166_8 T1166_16 B
B
A C B
L + 16
160
70
56
28
c 127±1
T1166_12
Opening travel distance W= 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 Header profile length L = 2W + 90
Header profile length min. L= 1690 1890 2090 2290 2490 2690 2890 3090 3290 3490 3690 3890 4090 4290 4490 Motor dimension m = W + 300
Header profile length with emerg. Belt length f = 2W + 380
opening and battery module L*= 1780 1890 2090 2290 2490 2690 2890 3090 3290 3490 3690 3890 4090 4290 4490 Trolley distance c = W – 220
Motor dimension m= 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
*simultaneously installing battery module and
Belt length f= 1980 2180 2380 2580 2780 2980 3180 3380 3580 3780 3980 4180 4380 4580 4780 emergency opening spring and at W <890 mm
use: L = W+980)
Trolley distanced c= 580 680 780 880 980 1080 1180 1280 1380 1480 1580 1680 1780 1880 1980
** Emergency spring only up to W= 2000 mm applicable
Single-leaf Sliding Doors EL
5x
T1166_44
C
T1166_47 A B
4 Nm A
16
Trolley locking device
T1166_18
D
A
T1166_50
T1166_35
B
B
A
T1166_52
C
B 4 Nm A SW 10
B 4 Nm
4 Nm
T1166_8
T1166_46e
D
C
A B C
C B A T1166_49
T1166_8
B
A T1166_13
17
B
4.7 Options
4.7.1 Battery Module u
Battery Module
T1166_20
Emergency Opening EB or
ER, opening to both sides or
to the right 20
T166_60
20
T1166_59
+24 V
4
EB/ER
GND
5
Progr. 6/9 IN
6
IN
7
+24 V
8
EL
T1166_76
50
Xmin. = S
W/2–25
T1166_73
T1166_63
+24 V
4
GND
5
Progr. 6/9 IN
6
IN
7
T1166_77
+24 V
8
Xmin. = W
/2–25
T1166_73
+24 V
4
GND
5
S Progr. 6/9 IN
6
IN
7
+24 V
8
S
T1166_78
T1166_64
Opening width W 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
X min. 375 425 475 525 575 625 675 725 775 825 875 925 975
Rubber string length S 2175 2465 2755 3045 3335 3625 3915 4205 4495 4785 5075 5365 5655
EL 1 EB/ER
min. 1 30
30 min. 1
C C
B B
A
A
D D
T1166_69
EL 2 EB/ER
B
B
C C
T1166_70
3
min. 1 mm min. 1 mm
T1166_71
max. 10 mm
T1166_72
1.
D C
47
D
100
50
LH + 50
LH
2.
T1166_40
3. C
D
C
D C
4.
D
A
min 5
T1166_40a
5.
A
T1166_57
Depending upon leaf weight an auxiliary person must be available for the installa-
tion.
T1166_27
• Observe safety clearance between walls and door leaves according to national regu-
lations (for example ZH 1/494, CEN: S = 200 mm).
S T1050_7 S
+/–X
+/–y
T1166_23
A SW10 6 Nm T1166_41
B SW13 8 Nm
T1166_53
1
17±
1
98±
1
98±
T1166_36
1
1
17±
±1
127
T1166_37
22
92 … 95
Ø 12
ER
Ø 12
EL
37
Ø 12
T1166_56
T1166_26
EL 1 EB ER
T1166_66
EL 2 EB ER
T1166_68
3 EL EB/ER
mm
1.5
T1166_67
Voltage
Selector
230/115V AC
50/60 Hz
CAUTION !
Netzspannung beachten!
! Check supply voltage!
Observer raccordem. réseau!
T1166_24
GND
1
outside inside
activator IN
2
IN
3
+24 V
4
GND
5
programmable 1
IN1
6
2
inputs
IN2
7
+24 V
8
key-switch GND
9
10 11 12
IN
programmable OUT1
outputs
+24 V
T1166_7e
User interface
6
Panellock
5
4 yellow
3 green yellow 4
green 3
red 2
2 red black 1
1 black T1166_31e
OPEN IN
7
T1166_32e
1
yellow
Air 30 SpotScan white
2 IN
white
GND
5
grey
grey
green IN progr. 6/8
6
GND
5
green* pink
IN progr. 7/8* progr. 6/8
7
IN
6
brown
+24 V pink* progr. 7/8*
8
IN
7
brown
GND +
9
+24 V
8
10 11 12
IN GND
9
yellow
progr. 8/8
10 11 12
SA OUT IN
blue
+24 V – OUT
Test Test
*) 2nd sensor red
T1166_80e + +24 V
Please consult the TORMAX price list for an actual choice of sensors
11
OUT 1 OUT 1
T1166_81
8
T1032/7
The 24 V power supply may be loaded with max. 0.75 A. The point-LED goes out on
overload.
T1166_62
• Activator LED is active when the activators
inside or outside or the key switch is ac-
tive.
• If both photocells are interrupted the Safe-
ty LED extinguishes.
The procedure is now complete and the 1st number (function) is displayed again.
Start Autoconfiguration • Simultaneously press and release the yellow and the blue key programming mode
is now active. Letter “P” appears on the display.
• Press the yellow key several times until the number 9 appears on the display
Number 9 is active (function no. 9)
• Press the blue key once to confirm your choice.
Number 0 flashes (parameter no. 0)
P 0 I 2 3 4 5 6 7 8 9 A b c b E f
Opening force
Damping
Programmable input
Programmable input
Programmable output
5/5 or 5/6
Open
% holding-closed force
Door-type
% normal
Close
force impulse in opening direction
without spring
Unlock and Op. mode Op. mode Config.
open w. battery
Pos. display reference
90 70 70 2 med soft MANUAL MANUAL 2 40 40 60 0,8 77
8.4 Programming Table
35
8.5 Programmable Functions
0 Reduced opening
width
0…9 Reduced opening width in % of the whole opening travel distance. From 5 % to 100 %, 5 %
and 10 % suitable for pharmacy opening
3 Hold-open Time 0 ... 9 The door remains open during the adjusted hold-open time (0.5 – 120 s). The hold-open time
starts when the door reaches the open position and the activators are no longer active.
When opened through the key switch, it remains open for 5 s, or according to parameter A.
The external safety facility has a hold-open time of 1 s.
The door can only close when the final hold-open time has elapsed.
4 Damping 0…9 There are 3 kinds of damping: (standard: opening = medium, closing = soft)
soft = long braking distance
medium = medium braking distance
hard = short braking distance
5 Program at mains
failure
0 ... 7 The behaviour of the system at mains failure is defined here. Functions see section 8.6.
6 Programmable input
IN1 / IN2
0 IN1 Operating mode OFF,
IN2 Operating mode OPEN.
+ *contact type NC If no operating mode is active on IN1 or IN2, operating mode AUTO applies. (Function see
chapter 3)
7 1 IN1 operating mode OPEN,
IN1 operating mode EXIT.
If no operating mode is active on IN1 or IN2, operating mode AUTO applies. (Function see
chapter 3)
2 Manual operation: The door is brought to standstill and remains thereafter in manual op-
eration as long as the input is active. After deactivation of the input the operating mode se-
lected last becomes active and a firmware reset occurs. (Operating mode jumps back to
AUTO without user interface.)
3* Emergency closing: Suitable applications are e.g. fire alarm or hold-up closing. The door
is closed immediately, with 25 cm/s, regardless of the operating mode, the activator and the
safety facility. The door remains closed as long as the command is applied. The door does
not lock except in operating mode OFF.
After cancellation of the emergency closing command the door functions immediately again in
accordance with the operating mode set last. The key switch has a higher priority
4* Emergency opening: The door opens immediately in all operating modes as long as the
command is active. In operating mode OFF, the door unlocks. After cancellation of the emer-
gency opening command the door functions immediately again in accordance with the operat-
ing mode set last. Emergency opening has higher priority than emergency closing.
5 Switch 100 % opening in operating modes AUTO, AUTORED, EXIT, hold-open time in ac-
cordance with key switch.
6 Locking in CLOSED position: locked in any operating mode, as soon as the door is in
CLOSED position.
7 Operating mode AUTORED: If on IN1 or IN2 no operating mode is active, operating mode
AUTO applies.
8* Creeping function opening
As long as this input is interrupted, the door drives each opening motion with the speed of
5 cm/s. The force is limited to max. 80 N. The tension of the rubber string is nevertheless
compensated with 5/5, 5/6. If the test signal 8/8 is programmed, the function is monitored au-
tomatically.
9* Emergency opening monitoring facility:
As long as this input is interrupted, the door drives into the open position and fault 3 is dis-
played. As long as the emergency opening monitoring facility is active, the door can only be
closed through the operating mode OFF after the transition to OFF is complete. If this disrup-
tion occurs in the operating mode OFF, the door remains closed.
8 Programmable
Output OUT1
0 Bell: The bell is triggered in operating modes AUTO, AUTORED and OPEN. People are de-
tected through the external safety facilities (e.g. photocells). If there are no external safety fa-
cilities, the outside activator acts automatically as trigger. The bell sustain duration is 1 s, the
minimum interval is 10 s.
1 Lock status locked: As soon as the lock slider is in position locked, the message is initiated
on OUT1. The message corresponds to the position of the switch on the lock.
2 Position display Door Open: The encoder detects that the door is completely open door and
initiates the message on OUT1.
3 Position display door closed: The encoder detects that the door is in closed position (+8
mm) and initiates the message on OUT1. Tolerance before closed position 8 mm.
4 Display Manual Door Opening: If the door is forced open more than 8 mm or the lock forced
open manually then a message is initiated. The message is reset when the door is closed.
5 Fault: message on OUT1 with any fault (E10 ... E99) detected by the control system. The
message is applied as long as the fault is active.
6 Light: OUT1 is activated in the operating mode OFF when the door is opened (Time = 60 s
from end of key switch impulse.)
7 Air curtain: OUT1 is activated in any operating mode as from the start of the opening and be-
comes inactive 15 s after reaching the closed position.
8 Test signal: For the connection of monitored sensors for safeguarding the door edge (section
7.6).
9 Operating mode EXIT: activ as long as the operating mode EXIT is functional (triggered by
user interface or IN operating mode
9 Configuration
Query Status
0 Auto configuration:
On auto configuration, all connected components are discovered automatically and included
in the corresponding program sequence, as there are:
• external safety facility 1 (with/without)
• external safety facility 2 (with/without)
• Lock (with/without)
• user interface (with/without)
The reference driving distance is registered and stored over a complete opening- and closing
cycle.
Following the auto configuration a firmware reset is triggered. The position of the door is de-
termined and the driving distance is compared to the reference driving distance.
1 On factory reset, all settings are set back to the factory settings and the fault displays are
deleted. The reference distance is set to Zero and “n” is displayed. The system can only be re-
startet through an auto configuration.
2 Configure reference run: An automatic reference run is started and the whole driving dis-
tance is registered.
3 Configure light beams: The light beams are automatically detected, they may not be inter-
rupted at the moment of automatic detection.
ATTENTION: The function of the light beams must be checked after configuration.
4 Number of opening cycles is displayed (e.g. 00001500 = 1500). The counter reading re-
mains after reset or factory reset (rounded down to 100th). It cannot be reset.
5 Number of operating hours are displayed directly. (e.g. 00000682 = 682)
6 Firmware version: The firmware version of the control unit is displayed as a four-digit number
(e.g. 0300 = V03.00).
7 Configure user interface: Automatic detection of the user interface is triggered.
ATTENTION: The function of the user interface must be verified after configuration.
8 Configure lock: Automatic detection of the lock is triggered.
ATTENTION: The function of the lock must be verified after configuration.
9 Configure direction of rotation: Activation of tthis parameter inverses the direction of rota-
tion of the motor. A reactivation resets the direction of rotation to the initial value.
Main application for Win Drive 2201.Retro.
A Hold-open time for 0…8 Hold-open time for key switch adjustable 1– 60 s (normally 5 s)
key switch 9 Reduced opening width for key switch (hold-open time is always 5 s). Independent of the op-
erating mode (apart from OPEN), an opening with reduced opening width takes place on acti-
vation of the key switch.
B Force in opening 0…8 The force in opening direction can be changed proportionally to the standard value. Range of
adjustment 20 –171%. With force calibration over 100 %, the permissible limit of the
direction
static force at the door edge according to DIN18650 is exceeded! With force calibration
under 100 %, a sufficient force reserve of at least 1 step (approx. 3 N) must be considered.
C Force in closing 0…8 The force in closing direction can be changed proportionally to the standard value. For normal
operation the force is 100% and for operation with spring 150 % (Program 5/5 and 5/6).
direction
Range of adjustment 20 –170%. The closing force in the closed position is not affected by this
adjustment. With force calibration over 100%, the permissible static force at the door
edge in accordance with DIN18650 is exceeded! With force calibration under 100 %, a suf-
ficient force reserve of at least 1 step (approx. 3 N) must be considered.
AUTORED
Behaviour on Mains Failure
OPEN
AUTO
EXIT
OFF
5.0 Without, or with battery and Remains closed without Stops without current* Remains open without
wake-up current* current
5.1 Opening with battery Remains closed and be- Opens and becomes Remains open and
comes then current-free* then current-free becomes then current-
free
5.2 Unlocking and opening with Unlocks, opens and Opens and becomes Remains open and
battery becomes then current- then current-free becomes then current-
free* free
5.3 Closing with battery Remains closed, locks Closes and becomes Closes and becomes then
and becomes then then current-free* current-free*
current-free*
5.4 Cycling operation with battery Remains closed* Operation continues til Operation continues
(with 50% Vo / Vc) battery is switched off** according to operating
mode
5.5 Opening with spring without Remains closed Opens with spring force Remains open
battery
5.6 Unlocking and opening with Unlocks, opens and Opens and becomes Remains open and
battery and spring becomes then current- then current-free becomes then current-
free free
5.7 FRW-D Operation continues til Operation continues
For Win Drive 2201.FWR-D Remains closed battery is switched off according to operating
see T-1211 Opens with spring force mode, until battery
switches off
5.8
5.9
*) Wake-Up: The disactivated battery module can be switched on via the key switch
(terminal 9–10). The door opens and closes. Thereafter the battery
module is switched off again.
After switch-off of the battery wait at least for 5 s, before performing
again wake-up.
**) Just before the battery is completely discharged, the door opens and
remains in open position.
Diagnosis through user 5 fault groups can be displayed via the LED’s 1 – 5 of the user interface. 1 or more
interface ◆ flashing LEDs indicate a fault.
The flashing LED indicates the fault group. If several LEDs are flashing (MANUAL
operation), the non-flashing LED indicates the fault group.
Diagnosis through Two-digit fault numbers are displayed through the 7-segment display, e.g. “E21”. The
7-segment display first digit indicates the fault group, the second digit indicates the detailed fault reason.
User / Fitter The fault message can be acknowledged through firmware reset, mains interruption or
operating mode change. The system attempts to resume normal operation – until the
fault reappears.
Display P System in programming mode through pressing yellow and blue key simultaneously.
System carries out auto configuration and detects the connected components (see
Display n
section 8.1).
Display o flashing System performs the opening sequence of the reference run during auto configura-
tion.
Display c flashing System performs the closing sequence of the reference run during auto configuration.
Display o System performs the opening sequence of the calibration run after a firmware reset.
Display c System performs the closing sequence of the calibration run after a firmware reset.
Display E 3 0 Example of a fault indication for error E30 (see section 9.3)
Voltage Display 24 V Decimal point-LED of the 7-segment display goes out on overload (> 1.0 A) or voltage
< 21 VDC. The alimentation is short-circuit proof
Functions ❏ Desired modes of operations are adjustable through the user interface
❏ Speeds have been adjusted
❏ Hold-open time has been adjusted
❏ Emergency opening ◆ has been checked (whole opening width!)
❏ Manual disengagement ◆ inside/outside works properly
❏ Customer requests have been checked in accordance with contract / order sheet
Behaviour of the System • Observe the fault, particularly the flashing LED combination on the user interface.
Operator in Case of Fault • Fault detection and further course of action in accordance with the description in the operating
instructions.
• On contacting the support department, provide a fault description that is as accurate as pos-
sible.
3
4 22
5 6 7
8 9 10 11
12
13 14
15
16 24
17 18 19 20 21 23 T1166_1
2 28
20 20
25
25 21 21
7.08 27 27
26 17 26 29
D E F I ESP NL
1 Einhängeprofil 1 Hook-on profile 1 Profilé de suspension 1 Profilo di aggancio 1 Perfil de suspensión 1 Aanhaakprofiel
2 Kämpferprofil 2 Header profile 2 Profilé traverse 2 Profilo traversa 2 Perfil autoportante 2 Montageprofiel
3 Getriebe-Motoreinheit 3 Geared motor unit 3 Unité engrenage - moteur 3 Unità 3 Unidad motor de engranaje 3 Aandrijfunit
4 Netzanschluss 4 Mains connection 4 Branchement sur le réseau 4 Allacciamento alla rete 4 Conexión a la red 4 Aansluiting netvoeding
5 Encoderkabel 5 Encoder cable 5 Câble encodeur 5 Cavo encoder 5 Cable del encoder 5 Encoder-kabel
6 Motorkabel 6 Motor cable 6 Câble moteur 6 Cavo motore 6 Cable del motor 6 Motorkabel
7 Sicherung 5 AT 7 Fuse 5 AT 7 Fusible 5 AT 7 Fusibile 5 AT 7 Fusible 5 AT 7 Zekering 5 AT
8 Steuerung 8 Control unit 8 Commande 8 Comando 8 Sistema de control 8 Controller
9 7-Segmentanzeige 9 7-digit display 9 Affichage 7 segments 9 7-Segmentanzeige 9 Indicador de 7 segmentos 9 7-cijferig display
10 gelbe Programmiertaste 10 Yellow programming key 10 Touche de programmation jaune 10 gelbe Programmiertaste 10 Tecla de programación amarilla 10 Gele programmeertoets
11 blaue Programmiertaste 11 blue programming key 11 Touche de programmation bleue 11 blaueProgrammiertaste 11 Tecla de programación azul 11 Blauwe programmeertoets
12 Riegel ◆ 12 Lock ◆ 12 Verrou ◆ 12 Serratura ◆ 12 Bloqueo ◆ 12 Electroslot ◆
13 Mitnehmer 13 Driver 13 Entraîneur 13 Asta di trasmissione 13 Arrastrador 13 Meenemer
14 Zahnriemen 14 Toothed belt 14 Courroie dentée 14 Cinghia 14 Correa dentada 14 Tandriem
15 Laufwagen 15 Trolley 15 Chariot 15 Carrello 15 Carro 15 Loopwagen
16 Umlenkeinheit 16 Deflection unit 16 Poulie de renvoie 16 Unità di rinvio 16 Unidad deflectora 16 Omkeereenheid
17 Kabelführungsprofil 17 Cable guiding profile 17 Profilé passe-câble 17 Canalina porta cavi 17 Perfil guía del cable 17 Kabelprofiel
18 Kabelklip 18 Cable clip 18 Clip câble 18 Clip porta cavi 18 Clip para el cable 18 Kabelklip
19 Endanschlag 19 End stop 19 Butée de fin de course 19 Terminale di arresto 19 Tope final 19 Eindaanslag
20 Laufschiene 20 Guide rail 20 Rail de guidage 20 Binario guida 20 Carril 20 Geleiderail
21 Laufschienengummi 21 Shaped rubber band 21 Caoutchouc du rail de guidage 21 guarnizione sottobinario di gomma 21 Goma del carril 21 Rubberband geleiderail
22 innere Montagenute 22 inside mounting keyway 22 Rainure de montage intérieure 22 Scanalatura montaggio interna 22 Ranuras de montajes interiores 22 Bevestigingsgleuf
23 Seitenplatte 23 Side plate 23 Plaque latérale 23 Lamiera laterale 23 Fijo lateral 23 Zijplaat
24 Blinddeckel 24 Blind cover 24 Couvercle d’obturation 24 Coopertura cieca 24 Tapa ciega 24 Afdekplaatje
25 Verschalung 25 Cladding 25 Habillage 25 Copertura anteriore 25 Cobertor 25 Behuizing
26 Z-Profil 26 Z-profile 26 Profilé Z 26 Profilo Z 26 Perfil en Z 26 Z-profiel
27 Klemmblech zu Z-Profil 27 Clamping strip for Z-profile 27 Tôle de serrage pour profilé Z 27 Placche di fissaggio profilo Z 27 Chapa de sujeción para el perfil en Z 27 Klemstrip Z-profiel
28 Kämpferprofil H100 28 Headerprofil H100 28 Profilé traverse H100 28 Profilo traversa H100 28 Perfil autoportante H100 28 Montageprofiel H100
29 Abdeckprofil 29 Cover profile 29 Profilé de protection 29 Profilo di protezione 29 Perfil cobertor 29 Afdekprofiel
Your first Choice for Door Automation
TORMAX SLIDEDOOR
TORMAX SWINGDOOR
TORMAX FOLDDOOR
TORMAX REVOLVEDOOR