ZIMBABWE POWER COMPANY

TECHNICAL SPECIFICATIONS FOR ELECTRONIC HONEYWELL UDI 1700


MICRO-PRO SERIES, UNIVERSAL DIGITAL INDICATOR TA4

BULAWAYO POWER STATION

ELECTRICITY HOUSE

P.O. BOX 1803

BULAWAYO

DATE: 09 MARCH 2021

PREPARED BY: LINCOLYN MOYO (GT CONTROL & INSTRUMENTATION)


Table of Contents

1. BACKGROUND INFORMATION.......................................................................................................1
2. SCOPE OF WORKS..........................................................................................................................1
3. TECHNICAL SPECIFICATIONS..........................................................................................................1
4. DOCUMENTATION.........................................................................................................................1
5. TEST AND ACCEPTANCE CRITERIA..................................................................................................1
6. MAINTENANCE REQUIREMENTS....................................................................................................1
7. GLOSSARY......................................................................................................................................1
1. BACKGROUND INFORMATION

Bulawayo Power Station (BPS) is part of five power plants operated by the Zimbabwe Power
Company, a subsidiary of ZESA. The plant is located in the City of Bulawayo and is
accessible by both rail and road. BPS is a coal-fired power plant with a total installed
capacity of 90MW which is generated from three 30MW CA Parsons Turbo generators. The
plant operates six 15MW Yarrow chain grate boilers.

2. SCOPE OF WORKS

The Contractor shall supply and deliver six Honeywell 1700 universal digital indicator for to
the ZPC Bulawayo Power Station premises. Three Honeywell 1700 universal digital indicator
are to be installed on Turbine Alternator number 4, and the other three shall be installed on
Turbine Alternator number 3. The supply and delivery must include operator’s and
maintenance manuals for the Honeywell 1700 universal digital indicator. The Honeywell
1700 universal digital indicator shall meet or exceed the technical specifications outlined in
Section 3 hereafter.

3. TECHNICAL SPECIFICATIONS

The Honeywell 1700 universal digital indicator shall provide a simple and cost effective
means of meeting the calibration requirements of ISO 9000 and other similar quality
standards. Table 1 below presents the technical requirements of the Honeywell 17 UDI.
Table 1: Technical Requirements

Accuracy Measurement 0.1% of span ± 1 LSD


Linearization for T/C & RTD
Better than ± 0.2 °C for decimal range
Temperature Stability 0.01 % of span per °C
Input Signal Failure For Thermocouple and RTDs: Upscale burnout For linear input:
Downscale burnout (only applicable to 4-20mA)
Input Sampling Rate Four samples per second
Input Filter Digital filter: 0.0 (off), from 0.5 to 100.0 seconds in 0.5s
increment
Input Isolation Universal input isolated at 2500V from all outputs and from
power supply
Approvals UL and CE approved
Environmental EMI immunity: Complies with EN61326 Safety considerations:
comply with EN61010-1 & UL3121
Front Panel Sealing IP66 / NEMA3
Power Consumption 100 to 240Vac, 50/60z: 7.5VA 20 to 48Vac, 50/60Hz: 7.5VA 22
to 65Vdc: 5W
Physical Weight: 210 grams max. Width: 96mm/3.78 inches, Height:
48mm/1.89 inches, Depth: 100mm/3.94 inches Wiring
connection: Screw terminals on the rear of the case (combination
head)
Alarms Up to five soft alarms with 5 SPDT relay outputs Alarm types:
PV high or low with direct or reverse acting Up to five alarm
hysteresis: From 1 LSD to 10% of span Combination alarms:
Logical "OR" or "AND" Alarm 1 can be latched requiring
specific acknowledgment
Output Type Output 1 : - Electromechanical relay output SPDT Output 2 : -
Electromechanical relay output SPDT - Linear DC for PV
retransmission - Dual electromechanical relays (2 SPST) Output
3 : - Electromechanical relay output SPDT - Dual
electromechanical relays (2 SPST) - Transmitter power supply
Linear DC output : Accuracy: ± 0.25% (mA @ 250Ohms, V @
2Kohms) Resolution: 8 bits in 250ms (10 bits in 1 second
typical, >10 bits in >1 second) Electromechanical relay : SPDT
contact with 2 A at 120 V or 240 V (resistive load) Life time: >
500 000 operations at rated voltage/current. Dual
electromechanical relays: Single pole single throw (SPST) with
2 A at 120 V or 240 V (resistive load) Life time: > 200 000
operations at rated voltage/current. Transmitter power supply:
Voltage output: 20-28 Vdc with 24Vdc nominal Minimum load
impedance: 910 ohms (22 mA and 20 Vdc)
Remote Reset Input Voltage free or TTL compatible (External relay contact or TTL
logic signal) To reset the latched alarm output 1
Communication RS485: ASCII or Modbus, selectable. Baud Rate: 1200, 2400,
Interface 4800, 9600,19.2K Baud Link Characteristics: 32 drops
maximum, ASCII protocol, two wires

Warranty
 The float switches shall have a two year warranty.
Lead time
 The preferred lead time is a month from the day the order is issued.

4. DOCUMENTATION

The Contractor shall provide the following documentation:

 The Contractor shall provide the ZPC Engineer with operator’s and maintenance
manuals.
 The test certificates.

All documentation and communication shall be conducted in English.

5. TEST AND ACCEPTANCE CRITERIA

The Honeywell 1700 universal digital indicator are subject to inspection and test by the ZPC
Engineer upon arrival to the ZPC premises to ensure compliance with this Specification and
to provide the necessary operating data.
6. MAINTENANCE REQUIREMENTS

If so required, or to the discretion of the ZPC Engineer, a service contract may be awarded to
the contractor after the supply of the Honeywell 1700 universal digital indicator that will run
for a specified duration, which will be agreed by both parties, or such a time that the ZPC
Engineer sees befitting.

7. GLOSSARY

In interpreting this Specification, the following words have these meaning assigned to them:

Contract – shall mean the agreement between ZPC and the Contractor for the execution of
the works howsoever made.

Contractor – the successful Tenderer appointed in writing to execute the works and shall
include the Contractors legal personal representatives, successors and permitted assigns.

Engineer – the Power Plant Manager, Bulawayo Power Station, or the person notified in
writing by the Power Plant Manager to the Contractor as the Engineer of the Contract.

Specification – shall refer to the whole of this document and any other accompanying
document, including drawings.

ZPC – Zimbabwe Power Company.


MAINTENANCE DEPARTMENT

SPECIFICATION APPROVAL

TECHNICAL SPECIFICATIONS FOR ELECTRONIC FLOAT SWITCHES

PREPARED BY: ……………………………………………….. Date: …………………


(GT CONTROL AND INSTRUMENTATION)

RECOMMENDED BY: ……………………………………….. Date: ….………………


(Snr FOREPERSON E & IMD)

AUTHORISED BY: …………………………………………… Date………………….


(SECTION ENGINEER MAINTENANCE)

APPROVED BY: ………………………………………………. Date: ………………….


(POWER PLANT MANAGER)