FOUNDATIONS
STRUCTURES 34.5kV
TYPE 3
TYPE 4
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
INDEX:
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
The electric subestation will be located in the municipality of General Cepeda, Coahuila.
"S.E. LOS
CAÑONES"
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
The characteristics of the site that are considered for the design are:
For the seismic analysis of each structure shall be used the following design parameters:
For wind analysis and design of structures, shall be used the following parameters:
Structure group: Grupo = A
Structure type: Tipo = 2
Class of structure: Clase = A
Terrain category: Cat. = 2.0
Topography factor : FT = 1.0
Regional Wind Speed for 200 years return period: Vr = 151 [km/h]
Altitude: ASNM = 1436 [m]
Maximum extreme temperature: TMAX = 49.0 [°C]
Manimum extreme temperature: TMIN = 15.0 [°C]
Average site temperature: TPROM. = 32.0 [°C]
For the foundation of the Minor Structures, there will be a foundation slab with reinforced concrete dices cast on site.
The heads or dies must protrude at least 0.20 [m] from the existing platform. The free height of the foundation dices will be painted with
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
5.- MATERIALS.
The materials, them features and finishes used in the manufacture of structures and foundations are as follows:
5.1.- Anchors
Anchors ASTM A - 36 Fy = 2530 [kg/cm²] (248.2 MPa)
Hex nuts A563 Grado DH
Flat washer F - 436 Grado 1
Weld electrode strength E - 7018 FEXX = 4922 [kg/cm²] (482.8 MPa)
5.2.- Foundations.
Concret for doundations. f´c = 300 [kg/cm²] (29.4 MPa)
Levelling course concrete f´c = 100 [kg/cm²]
Reinforcing steel ASTM A - 615 Grado 60 Fy = 4200 [kg/cm²] (412.0 MPa)
Anchors ASTM A - 36 Fy = 2530 [kg/cm²] (248.2 MPa)
5.3.- Finished.
Galvanized coating
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
Data
Materials.
Compressive strength of concrete. f´c = 300 [kg/cm²]
Volumetric weight of concrete. γc = 2.4 [ton/m³]
Creep resistance of steel. Fy = 4200 [kg/cm²]
Soil filling ɣ= 1.6 [ton/m³]
Foundation.
Slab Widtn. Bz =B 1.20 [m]
Slab Length. Lz =A 1.20 [m]
Column outcrop. Zo=c = 0.20 [m]
Slab Thickness. Pz=h = 0.20 [m]
Column length. Hd=f= 3.50 [m]
Column Width. Dd= 0.60 [m]
Column Thickness. Ad=C= 0.60 [m]
Depth of the foundation. Df = 3.70 [m]
Total height of foundation Ht = 3.90 [m]
Free distance from the column to slab. (Longitudinal sense)
E= 0.300 [m]
Free distance from the column to slab. (Treansversal sense)
F= 0.300 [m]
Steel coating r= 0.075 [m]
Effective thickness of the slab d= 0.13 [m]
Foundation Weight
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
OVERTURNING REVIEW.
𝐌𝐫
To consider the proper foundation against the effects of overturning, the following must be met: > 𝟏. 𝟎
𝐌𝐯
1 10.16 -0.29 0.23 0.00 0.00 0.95 0.00 0.17 6.10 6.10 0.00 36.62 Ok
2 10.11 0.00 0.18 0.00 0.00 0.00 0.00 0.00 6.07 6.07 0.00 0.00 Ok
3 10.05 -0.07 0.11 0.00 0.00 0.10 0.00 0.18 6.03 6.03 0.00 34.26 Ok
4 10.20 0.00 0.26 0.00 0.00 0.00 0.00 0.00 6.12 6.12 0.00 0.00 Ok
5 10.16 0.00 0.23 -0.16 -0.39 0.00 0.99 0.00 6.10 6.10 6.16 0.00 Ok
6 10.11 0.00 0.18 0.00 0.00 0.00 0.00 0.00 6.07 6.07 0.00 0.00 Ok
7 10.16 0.00 0.23 -0.16 -0.39 0.00 0.99 0.00 6.10 6.10 6.16 0.00 Ok
8 10.11 0.00 0.18 0.00 0.00 0.00 0.00 0.00 6.07 6.07 0.00 0.00 Ok
9 10.11 0.00 0.18 0.00 0.00 0.00 0.00 0.00 6.07 6.07 0.00 0.00 Ok
10 10.16 -0.29 0.23 0.00 0.00 0.95 0.00 0.17 6.10 6.10 0.00 36.62 Ok
11 9.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.96 5.96 0.00 0.00 Ok
REVIEW OF EFFORTS
SOIL BEARING CAPACITY
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
q cN c S c ic d c D f N q S q iq d q 0.5BN y S y i y d y
Where:
Soil properties: Cohesión c= 0.51 t/m²
Volumetric weight= 2.05 t/m³
Ø= 32.00 °
Depth of the foundation Df= 1.30 m
Angle of inclination of the foundation θ= 0.00 °
B= 1.20 m
L= 1.20 m
q= 2.665 t/m²
Sc 1 0.2 K P
B
Kp tan 2 45
Shape L 1.65 2 3.25
B
S q S y 1 0.1K P 1.33
L
D
Depth d c 1 0.2 Kp 1.39
B
D
d q d y 1 0.1 Kp
B 1.20
Inclination
2
iC iq 1 1.00
2 90
2
1
iy
iY 1 1.00
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
Section Module
Area= 1.44 [m²] 𝑃𝑡 𝑀𝑢𝑥 𝑀𝑢𝑧 sz 0.29 m³
𝑓= ± ± = 𝐿𝑧 𝐵𝑧 2 𝐿𝑧 2 𝐵𝑧
B= 1.20 [m] 𝐴 𝑆𝑥 𝑆𝑧 sx 0.29 m³ 𝑆𝑧 = = 𝑆𝑥 = =
L= 1.20 [m] 6 6
Review of soil bearing capacity Design of foundations
f1 f2 f3 f4 f1 f2 f3 f4
L/C Review
t/m² t/m² t/m² t/m² t/m² t/m² t/m² t/m²
1 4.36 7.06 0.00 0.58 7.64 7.64 6.48 6.48 Ok 4.94 4.94 3.78 3.78
2 4.32 7.02 0.00 0.00 7.02 7.02 7.02 7.02 Ok 4.32 4.32 4.32 4.32
3 4.28 6.98 0.00 0.61 7.59 7.59 6.37 6.37 Ok 4.89 4.89 3.67 3.67
4 4.38 7.08 0.00 0.00 7.08 7.08 7.08 7.08 Ok 4.38 4.38 4.38 4.38
5 4.36 7.06 3.44 0.00 10.50 3.62 10.50 3.62 Ok 7.80 0.92 7.80 0.92
6 4.32 7.02 0.00 0.00 7.02 7.02 7.02 7.02 Ok 4.32 4.32 4.32 4.32
7 4.36 7.06 3.44 0.00 10.50 3.62 10.50 3.62 Ok 7.80 0.92 7.80 0.92
8 4.32 7.02 0.00 0.00 7.02 7.02 7.02 7.02 Ok 4.32 4.32 4.32 4.32
9 4.32 7.02 0.00 0.00 7.02 7.02 7.02 7.02 Ok 4.32 4.32 4.32 4.32
10 4.36 7.06 0.00 0.58 7.64 7.64 6.48 6.48 Ok 4.94 4.94 3.78 3.78
11 4.20 6.90 0.00 0.00 6.90 6.90 6.90 6.90 Ok 4.20 4.20 4.20 4.20
4.32 0.92 3.67 0.92
Q
FS U R
q´
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
q´
SLIDE CHECK
For the sliding review, the provisions of the AASHTO LRFD Seismic Bridge Desing standard must be taken into account. Within section 6.3.5 we have the following
equation:
SETTLEMENT REVIEW
For the calculation of settlements in footings it is considered that elastic settlements of the rock type will appear. The evaluation of these effects is carried out using
the following equation, shown in the AASHTO LRFD regulation:
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
DISEÑO DE LA CIMENTACION
s max= 7.80 [ton/m²] F´= 0.30 [m] d= 0.125 [m] bW = 1.00 [m]
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
3
d ∗ Dd + d (Dd + d)d3 d(Ad + d) Dd + d 2
J= + +
6 6 2
C γv My X1
VUAB = 5.07 [kg/cm²] Vu = + ∗ 1.1
Maximum shear stress. b0 d J
2
ØVN = 20.65 [kg/cm²] Vc = 0.53 1 + λ f ′c
β
αs d
ØVN = 13.06 [kg/cm²] Resistent shear stress. Vc = 0.27 + 2 λ f ′c
b0
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
Pnu= 7.80 [ton/m²] E´= 0.30 [m] d= 0.125 [m] bW = 1.00 [m]
2
𝑃𝑛𝑢 ∗ 𝐸
Mu= 35086 [kg-cm] Ultimate moment. 𝑀𝑢 =
2
𝑀𝑢
Asc= 0.87 [cm²] Calculated steel área 𝐴𝑠 = = Fr= 0.9
𝐹𝑟 𝑓𝑦 .85 𝑑
0.8 𝑓´𝑐
Asm= 4.12 [cm²] Minimum steel area 𝐴𝑠 = 𝑏𝑤 𝑑 =
𝑓𝑦
1.33Asc= 1.16 [cm²] 1.33 calculated steel area 1.33𝐴𝑠𝑐 10.5.3 ACI
Pnu= 7.80 [ton/m²] F´= 0.30 [m] d= 0.125 [m] bW = 1.00 [m]
2
𝑃𝑛𝑢 ∗ 𝐸
Mu= 35086 [kg-cm] Ultimate moment. 𝑀𝑢 =
2
𝑀𝑢
Asc= 0.87 [cm²] Calculated steel área 𝐴𝑠 = = Fr= 0.9
𝐹𝑟 𝑓𝑦 .85 𝑑
0.8 𝑓´𝑐
Asm= 4.12 [cm²] Minimum steel area 𝐴𝑠 = 𝑏𝑤 𝑑 =
𝑓𝑦
1.33Asc= 1.16 [cm²] 1.33 calculated steel area 1.33𝐴𝑠𝑐 10.5.3 ACI
Technical Direction-Technology-Operations-Engineering
Document Type: CALCULATION REPORT
COLUMN DESIGN
Dimension of the
Hd= 60.00 [cm] Ad´= 60.0 [cm]
Dimension of the column long side colum short side.
Minimum steel percentage by
ρMIN = 0.010
temperature.
ASMIN = 36 [cm²] Minimum steel area by temperature. 𝐴𝑠𝑚𝑖𝑛 > 0.01 𝐴𝑔
No.
Varilla # 5 AV = 1.99 20 39.80 [cm²]
de
These 20 vars will be placed. # 5
Using 20 Var # 5 Ok.
distributed on the column.
Technical Direction-Technology-Operations-Engineering