Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

NOTES:

1. NUMBER OF PIPES AND PERMANENT Mg ANODES SHALL BE AS PER


AC INPUT "DETAILED DESIGN CALCULATION REPORT" DOCUMENT NO.
400V, 3PH, 50Hz TRU 1 4058-VW-CX-00OO000013.
Cable Size: DC OUTPUT: 50V, 75A
3.5C25sq.mm TAG No: 600-ET-89-01
+1G16sq.mm N 2179.30, E 2037.60 2. FOR THE DETAILS OF LINEAR SOCK ANODES AND PIPE CONNECTED IN EACH
BOX, REFER TO THE CABLE SCHEDULE (SEE SHEET 3).

3. BONDING CABLES SHALL BE INSTALLED TO MAINTAIN ELECTRICAL


CONTINUITY BETWEEN PIPING LOCATION SUCH AS NON WELDED JOINTS,
MECHANICAL JOINTS, FLANGES, COUPLINGS, CONCRETE PITS AND
LOCATIONS WHERE THERE IS NO ELECTRICAL CONTINUITY WITHIN THE
1C 50mm² XLPE/PVC
PIPING SYSTEM TO BE PROTECTED.
CABLES

4. FOR THE LOCATION OF THE NEGATIVE CONNECTIONS, PLEASE REFER TO


PDB 1 NDB 1 THE "GENERAL LAYOUT DRAWINGS" DOCUMENT NO.
TAG No: 600-EJ-89-01 TAG No: 600-EJ-89-02 4058-VW-DN-00OO000020.

1C 35mm² XLPE/PVC 1C 50mm² XLPE/PVC


CABLES CABLES

AJB 1-1 AJB 1-2 AJB 1-3 AJB 1-4


TAG No: 600-EJ-89-03 TAG No: 600-EJ-89-04 TAG No: 600-EJ-89-05 TAG No: 600-EJ-89-06

1C 35mm² XLPE/PVC Anode 1: Anode 1: Anode 1: Anode 1:


CABLES A210-DO-12"-A01BU-001 A210-DOV-4"-A01BU-001 A720-DO-4"-A01BU-016 2"-FD-62-0806-A01BU-N

Anode 2: Anode 2: Anode 2: Anode 2:


A210-DO-4"-A01BU-007 A210-DO-4"-A01BU-021 A720-DOV-4"-A01BU-002 A630-DO-10"-A01BU-009

Anode 3: Anode 3: Anode 3: Anode 3:


4"-DC-57-0812-A01BUCD-N 3"-DC-57-5832-A01BUCD-N A720-DO-10"-A01BU-005 A630-DO-10"-A01BU-001

Anode 4: Anode 4: Anode 4:


A210-DOV-4"-A01BU-002 3"-DC-57-5822-A01BUCD-N A720-DO-6"-A01BU-017

Anode 5:
2"-FD-62-0804-A01BU-N

NJB 1-1 NJB 1-2 NJB 1-3


TAG No: 600-EJ-89-09 TAG No: 600-EJ-89-10 TAG No: 600-EJ-89-11

1C 35mm² XLPE/PVC
CABLES
Pipe 1:
Pipe 1: Pipe 1:
3"-DC-57-5812-A01BUCD-N
A720-DO-10"-A01BU-005 A220-DO-10"-A01BU-003

Pipe 2: Acceptance status Eng. Dept. Date


Pipe 2: Pipe 2:
2"-FD-62-0804-A01BU-N 2"-FD-62-0804-A01BU-N
A210-DO-4"-A01BU-008 code

A B.LENKA PROCS 29-12-20


Pipe 3: Comment status code: 20
A720-DO-4"-A01BU-015
A - Accepted CR - Commented. Resubmit for Acceptance
AC - Accepted with Comment, Resubmit NA - Not accepted, Resubmit

IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the


VENDOR from full compliance with contractual obligation

2 02DEC20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

BOND BOX 1-1 BOND BOX 1-2 LEGEND


1 05OCT20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
TAG No: 600-EJ-89-07 TAG No: 600-EJ-89-08 TRANSFORMER RECTIFIER (TRU)

0 13JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI


PIPE

NEGATIVE DISTRIBUTION BOX (NDB)


OR
BOND BOX (BB)
POSITIVE DISTRIBUTION BOX (PDB)
OR
NOTE: CABLE SIZES ANODE JUNCTION BOX (AJB)

AS PER LEGEND Pipe 1: Pipe 1: MMO ANODE SOCK

6"-DC-57-0811-A01BUCD-N 6"-WF-71-0834-A01BU-N
TEST BOX (TB) - TYPE 1

Pipe 2: Pipe 2:
Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud
TEST BOX (TB) - TYPE 2
14"-WF-71-0872-A01BU-N A220-DO-10"-A01BU-010
TEST BOX (TB) - TYPE 3

Pipe 3: CT-EPC/001/SH/EPM-G/EP/18
A210-DOV-4"-A01BU-002 TEST BOX (TB) - TYPE 4

TEST BOX (TB) - TYPE 5

REFERENCE ELECTRODE (RE)

TEST BOX
A 7.7 kg MAGNESIUM ANODE (TEMPORARY CP)
TEST BOX TEST BOX
TYPE 1 (PSP AND TCP) TYPE 2 (PSP AND TCP) TYPE 3 (PCP) - NOTE 1 TEST BOX
TYPE 4 (INTERFERENCE MITIGATION)
TEST BOX
TYPE 5 (PVC CASINGS) SCHEMATIC WIRING DIAGRAM
A 14.5 kg MAGNESIUM ANODE (PERMANENT CP)

A 2x ZN RIBBON ANODES (PERMANENT CP)

4058-VW-DN-00OO000021 1/3
1C 10mm² XLPE/PVC
CABLES
1C 10mm² XLPE/PVC
CABLES
C POLARISATION COUPON

1C 50mm² XLPE/PVC RED CABLE


EPC001-00-DD-EU-CPC-00021-M NTS 2
1C 50mm² XLPE/PVC BLACK CABLE

1C 35mm² XLPE/PVC RED CABLE


A
1C 35mm² XLPE/PVC BLACK CABLE
Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
C A A A 1C 25mm² XLPE/PVC BLACK CABLE
E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
1C 10mm² XLPE/PVC CABLE

A
VENDOR DOCUMENT NO.
42119-CSL-028
NOTES:
AC INPUT 1. NUMBER OF PIPES AND PERMANENT Mg ANODES SHALL BE AS PER
400V, 3PH, 50Hz TRU 2
"DETAILED DESIGN CALCULATION REPORT" DOCUMENT NO.
Cable Size: DC OUTPUT: 50V, 75A 4058-VW-CX-00OO000013.
3.5C25sq.mm TAG No: 300-ET-89-01
+1G16sq.mm N 2391.80, E 1959.00 2. FOR THE DETAILS OF LINEAR SOCK ANODES AND PIPE CONNECTED IN EACH
BOX, REFER TO THE CABLE SCHEDULE (SEE SHEET 3).

3. BONDING CABLES SHALL BE INSTALLED TO MAINTAIN ELECTRICAL


CONTINUITY BETWEEN PIPING LOCATION SUCH AS NON WELDED JOINTS,
MECHANICAL JOINTS, FLANGES, COUPLINGS, CONCRETE PITS AND
1C 50mm² XLPE/PVC LOCATIONS WHERE THERE IS NO ELECTRICAL CONTINUITY WITHIN THE
CABLES PIPING SYSTEM TO BE PROTECTED.

PDB 2 NDB 2 4. FOR THE LOCATION OF THE NEGATIVE CONNECTIONS, PLEASE REFER TO
TAG No: 300-EJ-89-01 TAG No: 300-EJ-89-02 THE "GENERAL LAYOUT DRAWINGS" DOCUMENT NO.
4058-VW-DN-00OO000020.

1C 35mm² XLPE/PVC 1C 50mm² XLPE/PVC 1C 35mm² XLPE/PVC


CABLES CABLES CABLE

AJB 2-1 AJB 2-2 AJB 2-3 AJB 2-4


TAG No: 300-EJ-89-03 TAG No: 300-EJ-89-04 TAG No: 300-EJ-89-05 TAG No: 300-EJ-89-06

1C 35mm² XLPE/PVC Anode 1: Anode 1: Anode 1: Anode 1: Pipe 1:


CABLES A310-DOV-4"-A01BU-002 3"-HM-57-4403-A03-N A330-DO-16"-A01BU-004 8"-DP-57-4301-M01-N A360-DO-16"-A01BU-001

Anode 2: Anode 2: Anode 2: Anode 2:


A310-DO-16"-A01BU-004 A320-DO-16"-A01BU-001 4"-DP-57-4391-M01-N 3"-DC-57-4376-A01BUCD-N

Anode 3: Anode 3: Anode 3: Anode 3:


A330-DOV-4"-A01BU-003 A320-DO-16"-A01BU-003 A380-DO-6"-A01BU-008 A340-DO-6"-A01BU-037

Anode 4: Anode 4: Anode 4: Anode 4:


A310-DO-6"-A01BU-006 8"-DC-57-4343-A01BUCD-N 2"-DP-57-4301-M01-N A340-DO-6"-A01BU-041

Anode 5: Anode 5:
8"-DP-57-4349-M01-N 3"-DP-57-4387-M01-N

Anode 6: Anode 6:
3"-DC-57-4368-A01BUCD-N A380-DOV-4"-A01BU-001

NJB 2-1 NJB 2-2 NJB 2-3


TAG No: 300-EJ-89-10 TAG No: 300-EJ-89-11 TAG No: 300-EJ-89-12

1C 35mm² XLPE/PVC
CABLES
Pipe 1: Pipe 1:
Pipe 1: Acceptance status Eng. Dept. Date
4"-DC-57-4371-A01BUCD-N 3"-HM-57-4403-A03-N
A380-DO-16"-A01BU-004 code

Pipe 2: Pipe 2:
Pipe 2:
2"-DP-41-4403-M01-N A320-DO-16"-A01BU-003 Comment status code:
8"-DP-57-4301-M01-N
A - Accepted CR - Commented. Resubmit for Acceptance

Pipe 3: Pipe 3: AC - Accepted with Comment, Resubmit NA - Not accepted, Resubmit


Pipe 3:
A340-DO-10"-A01BU-008 8"-DC-57-4343-A01BUCD-N
3"-DC-57-4376-A01BUCD-N
IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the
VENDOR from full compliance with contractual obligation
Pipe 4:
Pipe 4:
8"-DP-57-4301-M01-N
3"-HM-41-4399-A03-N

Pipe 5:
A340-DO-6"-A01BU-041

BOND BOX 2-1 BOND BOX 2-2 BOND BOX 2-3 2 02DEC20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
TAG No: 300-EJ-89-07 TAG No: 300-EJ-89-08 TAG No: 300-EJ-89-09 LEGEND
1 05OCT20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI
TRANSFORMER RECTIFIER (TRU)

0 13JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI


PIPE

NEGATIVE DISTRIBUTION BOX (NDB)


OR
BOND BOX (BB)

NOTE: CABLE SIZES POSITIVE DISTRIBUTION BOX (PDB)


OR
AS PER LEGEND Pipe 1: Pipe 1: Pipe 1: ANODE JUNCTION BOX (AJB)

14" EXISTING WF LINE 2"-HM-41-4396-A03-N 14"-WF-71-0847-A01BU-N


MMO ANODE SOCK

Pipe 2: Pipe 2: Pipe 2: TEST BOX (TB) - TYPE 1


A320-DO-16"-A01BU-002 8"-DC-57-4300-A01BUCD-N A800-DO-12"-A01BU-002

Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud


TEST BOX (TB) - TYPE 2

Pipe 3:
8"-DP-57-4301-M01-N TEST BOX (TB) - TYPE 3

CT-EPC/001/SH/EPM-G/EP/18
TEST BOX (TB) - TYPE 4
Pipe 4:
A370-DO-6"-A01BU-003
TEST BOX (TB) - TYPE 5

REFERENCE ELECTRODE (RE)

TEST BOX
A 7.7 kg MAGNESIUM ANODE (TEMPORARY CP)
TEST BOX TEST BOX
TYPE 1 (PSP AND TCP) TYPE 2 (PSP AND TCP) TYPE 3 (PCP) - NOTE 1 TEST BOX
TYPE 4 (INTERFERENCE MITIGATION)
TEST BOX
TYPE 5 (PVC CASINGS) SCHEMATIC WIRING DIAGRAM
A 14.5 kg MAGNESIUM ANODE (PERMANENT CP)

A 2x ZN RIBBON ANODES (PERMANENT CP)

4058-VW-DN-00OO000021 2/3
1C 10mm² XLPE/PVC
CABLES
1C 10mm² XLPE/PVC
CABLES
C POLARISATION COUPON

1C 50mm² XLPE/PVC RED CABLE


EPC001-00-DD-EU-CPC-00021-M NTS 2
1C 50mm² XLPE/PVC BLACK CABLE

1C 35mm² XLPE/PVC RED CABLE


A
1C 35mm² XLPE/PVC BLACK CABLE
Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666
C A A A 1C 25mm² XLPE/PVC BLACK CABLE
E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk
1C 10mm² XLPE/PVC CABLE

A
VENDOR DOCUMENT NO.
42119-CSL-028
CABLE SCHEDULE LINEAR SOCK ANODE SCHEDULE
NOTES:
1. NUMBER OF PIPES AND PERMANENT Mg ANODES SHALL BE AS PER
"DETAILED DESIGN CALCULATION REPORT" DOCUMENT NO.
4058-VW-CX-00OO000013.

2. FOR THE DETAILS OF LINEAR SOCK ANODES AND PIPE CONNECTED IN EACH
BOX, REFER TO THE CABLE SCHEDULE.

3. BONDING CABLES SHALL BE INSTALLED TO MAINTAIN ELECTRICAL


CONTINUITY BETWEEN PIPING LOCATION SUCH AS NON WELDED JOINTS,
MECHANICAL JOINTS, FLANGES, COUPLINGS, CONCRETE PITS AND
LOCATIONS WHERE THERE IS NO ELECTRICAL CONTINUITY WITHIN THE
PIPING SYSTEM TO BE PROTECTED.

4. FOR THE LOCATION OF THE NEGATIVE CONNECTIONS, PLEASE REFER TO


THE "GENERAL LAYOUT DRAWINGS" DOCUMENT NO.
4058-VW-DN-00OO000020.

Acceptance status Eng. Dept. Date


code

Comment status code:


A - Accepted CR - Commented. Resubmit for Acceptance
AC - Accepted with Comment, Resubmit NA - Not accepted, Resubmit

IMPORTANT: CONTRACTOR acceptance of this Document does not relieve the


VENDOR from full compliance with contractual obligation

2 02DEC20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

1 05OCT20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

0 13JUL20 ISSUED FOR APPROVAL L.HULL N.SIPPEL A.BONETTI

Realisation du 4eme Train GPL a ZCINA, Hassi Messaoud


CT-EPC/001/SH/EPM-G/EP/18

SCHEMATIC WIRING DIAGRAM


NOTE:
Cable for Test post.
2 no. 1C 10 Sq.mm Cu/XLPE/PVC cable shall be connected to pipe. 4058-VW-DN-00OO000021 3/3
Each length shall be 10m

EPC001-00-DD-EU-CPC-00021-M NTS 2

Grantham, Lincs, UK, NG31 7XS Tel. +44(0)1476 590666


E-mail cpc@cathodic.co.uk Web www.cathodic.co.uk

VENDOR DOCUMENT NO.


42119-CSL-028

You might also like