Rectifier

DPR 2000

Description
The DPR 2000 Series is a single phase rectifier with
outstanding power density. This rectifier is optimal for
1U shelf solutions. Its short depth and extended
operating temperature range make it most suitable for
space-critical and pole-mount applications
Installation is simplified as all Delta rectifiers have
their connectors at rear and are hot-pluggable. Fan
cooling with speed control ensures near silent
operation.
Delta rectifiers are market leaders in power
density offering solutions for compact space and
Main features
weight requirements. In addition to that, the
• Energy saving – leading edge efficiency
• Advanced energy saving functionality highest efficiency ensures lower total energy
• Space savings – high power density
consumption and leads to smaller environmental
• Wide AC input voltage range
• Optional protection against loss of Neutral and AC footprint.
overvoltage
• Extended operating temperature range
With a focus on continuous improvement of total
cost of ownership, Delta rectifiers combined with
Applications
advanced controlling and monitoring units help
DPR 2000 is used in Delta InD and OutD systems for:
• Network base stations reducing both CAPEX and OPEX.
• Wireless applications
• Fixed line applications, data communications


Rectifier
DPR 2000

Technical specifications
1. Input 3. General
Mains voltage 88 - 310 Vrms Efficiency 91 %
Mains frequency 50 / 60 Hz Power density 25 W / in3
Harmonic distortion (THD) 5% CSU 5
EN 55022, class B *1 Control and monitoring CSU 501
EMI (conducted) CSU 502
EN 55022, class A *2
Protection Internal fuse 16 A User interface Status indication
125.5 x 41.0 x 269.9 mm
AC over voltage protection Incl. loss of neutral *2 Dimensions (W x H x D)
4.9 x 1.6 x 10.6 in
Weight 2.0 kg / 4.4 lb

2. Output Standards
• Safety EN / IEC 60950
Nominal system voltage 54 V
UL 60950
Operating voltage range 40 - 59.5 V CAN / CSA - C22.2
Power limitation 2000 W • EMI (radiated) EN 55022, class B *1
EN 55022, class A *2
Current limitation 41.7 A
• Environment RoHS compliant
Overvoltage protection 59.5 V
Cooling Fan cooled
EMI (conducted) EN 55022, class A
Acoustics 50 dB (A)
Load sharing Yes
-40 to +75 °C
Protection Internal fuse Operating temperature
-40 to +167 °F

Subject to change without notice.


Ordering information
DPR 2000C-48 /
Description *1
ESR-48/40A A
DPR 2000C-48 /
Description *2
ESR-48/40A B

Delta Energy Systems (Switzerland) AG


Freiburgstrasse 251, CH-3018 Bern - Bümpliz
Phone: +41 31 998 5311, Fax: +41 31 998 5353

www.deltapowersolutions.com


FS_DPR2000_en.doc / Rev. 04 / RPä 3791177400