Power Capacitors: Cooper Power Systems Type EX - D Single-Phase Units and Accessories
Power Capacitors: Cooper Power Systems Type EX - D Single-Phase Units and Accessories
Electrical Apparatus
Cooper Power Systems® Type EX®-D
Single-Phase Units and Accessories 230-11
Cooper Power Systems Type EX®-D CAPACITOR APPLICATlON
all-film capacitors feature the latest Capacitor application requires an
Cooper Power Systems design inno- evaluation of the power system to
vations—extended foil/solderless determine:
connections1 and laser-cut foil. They ■ the kVAR needs
are designed, manufactured, and ■ the most effective location
tested to meet the requirements of ■ the necessary protection.
all applicable ANSI/IEEE, NEMA, In general, capacitors are installed:
and IEC standards. In addition ■ at the substation, to supply the
they are designed to exceed the system var needs most effectively
requirements of these standards in ■ at—or near—the load center, to
terms of continuous rms and peak obtain the optimum var supply
overvoltage withstand capabilities, and voltage correction
and in tank rupture characteristics. ■ at the end of the line, to achieve
These capacitors are especially maximum voltage correction.
suited to the rigors of industrial
power systems for: RATINGS
■ power factor improvement Cooper Power Systems Type EX-D
■ harmonic filter applications capacitors are rated in continuous
■ reduction of losses kVAR, voltage and frequency for
■ reducing voltage drop operating within the -40 to +55°C
EX-D capacitors can be installed ambient temperature range.
singly or in factory-assembled Designed to produce not less than
switched or unswitched banks in: rated kVAR at rated voltage and
■ pole mounted racks frequency, they are subjected to all
■ open air substation banks applicable NEMA and ANSI/IEEE
(for outdoor or indoor application) standard dielectric tests. Single-
■ metal enclosures. Figure 1.
phase 50- through 400-kVAR EX®-D single-phase, all-film
The Type EX-D capacitor capacitors are available.
provides these exclusive benefits: capacitor.
Capacitor rated voltage is the
■ 125% continuous rms overvolt voltage that can be applied terminal
age capability to terminal; for example, a 2400-volt The maximum recommended
■ 135% peak overvoltage capability capacitor can be delta-connected on working voltage of an EX-D capacitor
■ greater safety through improved a 2400-volt system or wye-connect- is 125% of rated voltage. Cooper
tank rupture characteristics ed on a 2400/ 4160-volt system. In Power Systems capacitors include a
■ 15,000 Amp fault current handling each case, the voltage applied to the safety factor that permits them to
capability capacitor terminals is 2400 volts. tolerate—without damage— momen-
■ 100 kA transient current Because a capacitor’s kVAR output tary overvoltages caused by
withstand capability varies as the square of the ratio of switching or load changes.
■ ambient operation through +55°C applied voltage to rated voltage, The capacitor units cataloged in
(+131°F) application at the proper voltage is this section are designed for
■ Iow dielectric losses essential for optimum operating operation at a rated frequency of 60
(0.07 watts/kVAR @ 60 Hz) performance and long service life. Hz. kVAR output varies directly as
■ superior electrical performance the ratio of applied frequency to
and reliability rated frequency. Capacitors designed
■ environmentally acceptable to operate at 50 Hz or other frequen-
Edisolt® XT dielectric fluid. cies are also available upon request.
Table 1 lists the
ratings and catalog numbers for
standard Type EX-D single- and
double-bushing capacitors. Other
unit kVAR sizes, voltage ratings and
BIL ratings are available.
TABLE 1
Ratings and Catalog Numbers for Standard Single- and Double-Bushing Capacitors
2
230-11
TABLE 1 (continued)
Ratings and Catalog Numbers for Standard Single- and Double-Bushing Capacitors
Bushings
Bushing characteristics are shown in Table 2.
TABLE 2
Bushing Characteristics and Weights
60-Hz Withstand Approximate Net
Creepage Strike 60-Sec. 10-Sec. Weight/
BIL Distance Distance Drv Wet Bushing
(kV) (in.) (in.) (kV) (kV) (lb)
75** 10.38 6.25 35 30 3
95* 10.38 6.25 35 30 3
150* 18.12 9.50 60 50 5
150 22.00 9.50 60 50 6
200 26.00 14.00 80 75 7
* Bushings furnished on standard capacitors shown in Table 1 and Figure 2.
** Same bushing is used on 75 and 95 kV BIL capacitor units.
3
Single-Phase Capacitors
Figure 2.
Dimensions and weights of 50-, 100-, 150, 200-, 300-, and 400-kvar
capacitors.
Cooper Power Systems® is a registered trademark of Cooper Power Systems, Inc. P.O. Box 1640
Edisol® is a registered trademark of Cooper Power Systems, Inc. Waukesha, WI 53187