Mini-Split Air Conditioners and Heat Pumps: For Residential and Light Commercial Applications
Mini-Split Air Conditioners and Heat Pumps: For Residential and Light Commercial Applications
3
Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
TABLE OF CONTENTS
FEATURES
Mini-Splits Defined.......................................... 4
Individual Zoning ............................................ 6
Comfort Solution ............................................ 8
Energy Efficient ............................................. 9
Comfort & Convenience ............................... 10
Applications .................................................. 11
Feature Descriptions .................................... 12
MODEL LINEUP
Indoor and Outdoor Model Table .................. 14
MULTI-ZONE MINI-SPLITS
Overview ...................................................... 31
Indoor Units
Wall Mount ............................................... 33
Duct .......................................................... 34
Compact Cassette ................................... 35
Multi-Zone (2-4 Zones) Outdoor .................. 36
Flex-Zone (2-8 Zones) Outdoor ................... 37
Branch Boxes ........................................... 38
Wiring ........................................................ 40
Piping ........................................................ 41
Allowable Combinations ............................... 42
ACCESSORIES
Descriptions .................................................. 44
Compatibility Chart ....................................... 45
MISCELLANEOUS
Line Set Length Chart ................................... 46
Model Nomenclature .................................... 46
Fujitsu Mini-Splits:
Year-Round, Whole-Home or Business
Energy Efficient Heating and Cooling
What is a Mini-Split?
Halcyon systems eliminate the need for a
basement or attic-located evaporator unit and
bulky ductwork by using thin copper tubing
that pumps refrigerant directly to discreet wall
mounted or concealed units inside. Even more
remarkable, this same unit works in reverse in
winter, absorbing heat from the outside air and
moving it indoors to heat your home. The
result? Efficient cooling and heating for year-
round, whole-house comfort in most climates.
evaporator/
fancoil (indoor)
air air
Unit Can Be return ...or Hidden supply
Showcased...
grille Compact Duct units are grille
refrigerant lines,
Wall mounted units mounted above a
electric, drain
eliminate the need ceiling or in a framed
for ductwork, mount enclosure below a
high on a wall and ceiling, so only the
deliver all of the grilles show for a clean
compressor/ cooling you pay for. look. They require
condenser minimal ductwork.
(outdoor)
4
Downloaded from www.Manualslib.com manuals search engine
Heat Pumps Provide Heat When it is Chilly
Basic Heat Pump Configuration
Because refrigerant is naturally much colder than outdoor
Heat
temperatures even on a very cold day, it actually absorbs heat Heat In Out
compressor
evaporator
from outdoors, and transfers the heat it absorbs outside to
within your home. The refrigerant's physical properties do this
naturally. What you pay for is the electricity to pump refrigerant
via copper tubing from outdoors to indoors. Because we move
compressor
the heat rather than create it (as electric baseboard or resistant
heat does), we can deliver up to 4 times the heat for the energy expansion
we consume! valve
compressor
from indoors to the outside. For many climates, the advanced
evaporator
technology that goes into these units creates a far more cost
effective alternative to either gas or oil-fired units for heat, or
a central ducted system for air conditioning. Fujitsu’s mini-splits
come in both cooling-only models or heat pumps, which compressor
provide both heating and cooling. expansion
valve
An electric heater converts electricity directly to Heat pumps are more efficient than some other forms
heat, and if we assume that the heat loss is zero, of heating because heat pumps do not actually create
the output from one kilowatt input is one kilowatt heat - they just move it from one place to another.
or 3,400 BTU and the EER is 3.4. For example, the output of an efficient 10 EER heat
pump is triple that of an electric heater.
*EER (Energy Efficiency Rating) = Rated BTU capacity divided by total kW input.
5
Downloaded from www.Manualslib.com manuals search engine
FEATURES
Wall Mounted
Stylish, slim and elegant, wall
mounted units are designed to
complement any interior décor.
Compact size
Wireless remote control
Automatic swinging louvers
6
Downloaded from www.Manualslib.com manuals search engine
Compact Duct
Mounted in a ceiling or in a framed
enclosure below a ceiling. They use
minimal ductwork and remain very
energy efficient.
Concealed and out of sight
Look of central air with the
efficiency of a mini-split
Less ducts = higher efficiency
Wall Mounted
They mount high on a wall, out of sight
and do not require ductwork, increasing
energy efficiency.
Quiet operation
Easy maintenance
High delivered efficiency means
lower utility bills
Compact Cassette
Cassettes are extremely discreet, with
only the grille showing in the ceiling.
They use the latest fan technology to
distribute the conditioned air evenly.
Wired remote controller
(wireless is optional)
Powerful turbo fan operation
Fits into a standard 2’ x 2’
ceiling grid
7
Downloaded from www.Manualslib.com manuals search engine
FEATURES
Stay Comfortable.
8
Downloaded from www.Manualslib.com manuals search engine
Energy Efficient: The Smart Choice in Comfort
As much as half of the energy used in your home goes to heating and cooling.
So, making smart decisions about your home’s heating and air conditioning
system can have a big effect on your utility bills — and your comfort.
Other
Where Does My Money Go? Electronics 8% Heating
7% & Cooling
The high energy efficiencies of Lighting 49%
Halcyon systems slash utility 10%
bills by up to 25%. If your Clothes
average annual utilities are Washer &
Dryer 6%
$4,200, Fujitsu can save you up to
Dishwasher
$1,050 annually or $10,500 in 10 yrs!* 2%
Refrigerator
*Savings may vary based on model selected, hours of operation
5%
Water
Fujitsu
and geographical location. Example given based on 26-SEER Heater saves 25%
system versus 13-SEER system. 13% on your
utility bill
Rebates
To encourage customers to buy energy efficient products, many
local utility companies offer significant rebates for the purchase
of a ductless mini-split system. Go to Fujitsu’s web site to search
for local rebates, consumer loans and utility bill discounts. We
provide a listing of rebates and offerings on qualifying Fujitsu
mini-splits by state. www.fujitsugeneral.com/utility_rebates.htm
9
Downloaded from www.Manualslib.com manuals search engine
FEATURES
Inverter Benefits
More heat at lower outdoor temperatures Temp.
Lower RPMs = quieter operation
Desired temperature in half the time
Up to 30% more efficient Inverter System
Stable temperature
10
Downloaded from www.Manualslib.com manuals search engine
Applications
Where can
mini-splits
be used?
Convenience stores
Fast food chains
Fire houses
Police stations
Oil rigs
Bars
Sunrooms and additions
Warehouses
Nursing homes
Small offices
Older homes
New construction homes
Schools
Places of worship
Hospitals and medical facilities
Restaurants
Computer rooms
Hotels and motels
Car washes
ATM vestibules
11
Downloaded from www.Manualslib.com manuals search engine
FEATURES
temperature to avoid unnecessary cooling and heating. Interface with third party devices such as home automation.
76/2 Warranty
POWERFUL Energy Saver
Keeps room7cool enough for comfort by using a relaxed
Warranty Fujitsu systems come with either a 2 Year Parts / 6 Year
Compressor warranty or a 5 Year Parts / 7 Year Compressor
thermostat setting reducing power consumption. 6 7/5 warranty.
6 Saving Program (ESP)
Warranty
Energy
ESP
If a space is left without turning the unit off, ESP knows that it 6
is *Auto Changeover is not designed to provide rapid changes between heating and
unoccupied and 20 minutes later, temperature is adjusted cooling operation or simultaneous heating and cooling. This feature is not
recommended for systems with more than one indoor unit unless all indoor units
accordingly until users return to the room. have similar heating and cooling requirements and have similar temperature set
points. If all indoor units have similar heating and cooling requirements and have
+Function is bypassed during defrost and at low speed operation. This feature may
similar temperature set points, auto changeover will work.
limit cooling/heating capacity during high/low ambient conditions and increase energy
consumption as system may need to operate longer due to reduced compressor speed.
12
Downloaded from www.Manualslib.com manuals search engine
Feature Single Zone Wall Mount
Heat Pumps
Single Zone Single Single Universal/
Wall Mount
Cooling
Zone Zone Ceiling
Ducted Cassette Susp.
Large
Cassette
HFI Multi-Zone
and Flex-Zone
Summary
12RLFCD
18RLFCD
12RLFCC
18RLFCC
12RLS2H
15RLS2H
12RLFW
9RLFCD
9RLFCC
9RLS2H
18RULX
24RULX
18RCLX
24RCLX
36RCLX
42RCLX
36RSLX
12RLS2
15RLS2
30CLX1
36CLX1
9RLFW
9RLS2
30RLX
12RL2
24CL1
9RL2
18CL
9.8^ 17.0^
9.8^ 17.0^
9.8^ 17.0^
9.8^ 17.0^
9.3^ 14.7^
9.0 16.0
11.0 23.0
12.5 27.2
8.8 27.2
9.0 16.0
11.0 22.0
12.0 25.0
9.3 25.0
12.0 21.5
10.3 21.5
10.0 19.0
10.0 18.0
9.5 17.5
- 19.0
- 17.5
- 16.5
- 15.5
12.2 21.2
11.5 20.0
11.3 19.7
13.0 24.0
12.2 21.9
11.5 20.1
8.5 16.0
8.5 15.0
8.5 14.0
8.5 16.0
8.5 15.0
8.5 14.0
8.5 15.0
SEER
HSPF
ENERGY STAR POWERFUL
Qualified ®
*
Sleep Timer ▲ ▲
Weekly Timer
Dry Mode 7 Dry 7
Power Diffuser
6 7Diffuser
Auto Restart/Reset 7
6
Auto Changeover 6
+ + + + +
7 7 Low
Low Ambient Cooling
Ambient
6
6 0°F
7
0-Degree Ambient Cooling
Ambient
6 ft
165
Long Piping Length (165’+)
Piping
Cold Prevention C old
7
Slender Fit
S6
lender
7
7
Daisy Chain POWERFUL
16
6 Daisy
6
6 Pump Down
7 7
6 6 Duct Capable
Branch Branch
6
7
Condensate Pump
Pump
13
Downloaded from www.Manualslib.com manuals search engine
MODEL LINEUP
Wall Mount
115V Inverter
ASU9RL2 / AOU9RL2 ASU12RL2 / AOU12RL2
Wall Mount
High SEER $ $
ASU9RLS2 / AOU9RLS2 ASU12RLS2 / AOU12RLS2 ASU15RLS2 / AOU15RLS2
Wall Mount
Extra Low Temp Heating $ $
ASU9RLS2 / AOU9RLS2H ASU12RLS2 / AOU12RLS2H ASU15RLS2 / AOU15RLS2H
Wall Mount
Heat Pump $ $
ASU9RLF / AOU9RLFW ASU12RLF / AOU12RLFW
Wall Mount
Cooling Only
Universal Mount
Floor/Ceiling
Ceiling Suspended
Compact Duct
$ $
ARU9RLF / AOU9RLFC ARU12RLF / AOU12RLFC
Compact Cassette
$ $
AUU9RLF / AOU9RLFC AUU12RLF / AOU12RLFC
Large Cassette
Designer Series
Wall Mount
ASU9RLS2 ASU12RLS2 ASU15RLS2
Large
Wall Mount
ASU18RLF ASU24RLF
Compact Duct
ARU9RLF ARU12RLF ARU18RLF ARU24RLF
Compact
Cassette
AUU9RLF AUU12RLF AUU18RLF
Indicates system is ENERGY STAR® Qualified in 2013. $ Indicates system qualifies for Federal Tax Credit in 2013.
14
Downloaded from www.Manualslib.com manuals search engine
18,000 24,000 30,000 36,000 42,000
$ $
ASU18RLF / AOU18RLXFW ASU24RLF / AOU24RLXFW ASU30RLX / AOU30RLX
ABU36RSLX / AOU36RLX
ARU18RLF / AOU18RLFC
AUU18RLF / AOU18RLFC
+
2 Indoor Units
$+
AOU18RLXFZ
+
2 - 3 Indoor Units
$+
AOU24RLXFZ
2* - 4 Indoor Units
AOU36RLXFZ
2 - 8 Indoor Units
AOU48RLXFZ1
* If AOU36RLXFZ is paired with two 18,000 BTU indoor units, you have to purchase optional kit Part #K9FZ1818.
+ The only combinations that qualify are AOU18RLXFZ with (2) ASU9RLF, AOU18RLXFZ with (1) ASU7RLF + (1) ASU12RLF, AOU18RLXFZ with
(1) ASU9RLF + (1) ASU12RLF, AOU24RLXFZ with (2) ASU7RLF + (1) ASU9RLF.
15
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE
MINI-SPLIT SYSTEMS
Making the hottest places
cool and the coolest places
more comfortable
16
Downloaded from www.Manualslib.com manuals search engine
Wall Mounted 115V Inverter 9, and 12,000 BTU Systems
SYSTEMS 9RL2, 12RL2
Outdoor
Outdoor
Indoor
ASU9RL2
Indoor
ASU12RL2
17
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE MINI-SPLITS
AOU15RLS2
AOU9RLS2
Outdoor
Outdoor
Outdoor
Indoor
ASU9RLS2
Indoor
ASU12RLS2
Indoor
ASU15RLS2
18
Downloaded from www.Manualslib.com manuals search engine
Wall Mounted High-Heat 9, 12 and 15,000 BTU Systems
SYSTEMS 9RLS2H, 12RLS2H, 15RLS2H
AOU15RLS2H
Outdoor
Outdoor
Indoor
ASU9RLS2
Indoor
ASU12RLS2
Indoor
ASU15RLS2
Note: Figures are based on 230 Volts. *Height when front panel is open.
19
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE MINI-SPLITS
Outdoor
Outdoor
AOU9RLFW
Indoor
ASU18RLF
Indoor
ASU24RLF
Outdoor
Indoor
ASU9RLF
Indoor
ASU12RLF
20
Downloaded from www.Manualslib.com manuals search engine
Wall Mounted 30,000 BTU Systems
SYSTEM 30RLX
17.5 SEER
Function 30RLX
This wall mounted heat pump provides both heating and Heat Pump
cooling for year-round comfort. Ultra compact yet Nominal Cooling BTU/h 30,000
7
efficient, System 30RLX provides maximum comfort in Min.~Max. Cooling BTU/h 9,900~32,400
6 30% less space while saving you money. Additionally, Nominal Heating BTU/h 32,000
System 30RLX provides low 7
ambient operation rated down Min.~Max. Heating BTU/h 8,000~37,500
to 0°F right out of the box without modification. HSPF BTU/hW 9.5
6 SEER BTU/hW 17.5
Standard Features EER Clg/Htg 10.0
Clg. Operating Range °F(°C) 0~115 (-18~46)
POWERFUL Wireless Wireless Remote Control POWERFUL Economy Mode
Htg. Operating Range °F(°C) 0~75 (-18~24)
POWERFUL Apple Catechin Filter
7 Quiet Mode (Indoor) Moisture Removal Pt./h(l/h) 9.5 (4.5)
7
Ion Deoderizing
6 Filter Diffuser
Power Diffuser Voltage/Frequency/Phase 208-230/60/1
6 Recommended Fuse Size (A) 30
Sleep Timer Auto Restart/Reset 659 (1,120) Clg
7 Air Circ. C.F.M. (m /h): Hi
3
21
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE MINI-SPLITS
7* Available only with optional wired remote controller. Combined Min. Lgth Ft (m) 9 (2.7) 9 (2.7) 16 (5) 16 (5)
+ Feature of 18CL only.
6 ^ Feature of 24CL1, 30CLX1, 36CLX1 only. Operation monitoring 66 (20) 98 (30) 164 (50)
Combined Max. Lgth Ft (m) (pre-charge: 49’) (pre-charge: 49’) (pre-charge: 66’) (pre-charge: 66’) 164 (50)
and On/Off control only.
# Feature of 30CLX1 and 36CLX1 only. Max. Vertical Diff. Ft (m) 49 (15) 66 (20) 98 (30) 98 (30)
POWERFUL
Conn. Pipe Diameter Inch Suc. 1/2 Dis. 1/4 Suc. 5/8 Dis. 1/4 Suc. 5/8 Dis. 3/8 Suc. 5/8 Dis. 3/8
Net Weight lbs. (kg) 20 (9) 88 (40) 31 (14) 88 (40) 31 (14) 135(61) 31 (14) 135(61)
Optional Wired Remote Dimensions: Height Inch 10-13/16 22-3/4 12-5/8 24-7/16 12-5/8 32-3/4 12-5/8 32-3/4
Weekly Timer mm 275 578 320 620 320 830 320 830
Full Function Wired Remote Width Inch 31-1/8 31-1/8 39-1/4 31-1/8 39-1/4 35-3/8 39-1/4 35-3/8
Child Lock Capable mm 790 790 998 790 998 900 998 900
UTY-RNBYU
Depth Inch 8-7/16 11-13/16 9 11-3/4 9 13 9 13
mm 215 300 228 298 228 330 228 330
Refrigerant R410A R410A R410A R410A
Outdoor
AOU36CLX1
Outdoor
AOU30CLX1
Outdoor
AOU18CL
Outdoor
AOU24CL1
Indoor
ASU18CL
Indoor
ASU24CL1
Indoor
ASU30CLX1
Indoor
ASU36CLX1
System Systems
18CL 24CL1,
30/36CLX1 Note: Figures are based on 230 Volts.
22
Downloaded from www.Manualslib.com manuals search engine
Ceiling and Universal Floor/Ceiling Mounted Systems
SYSTEMS 18RULX, 24RULX, 36RSLX
Up to 16 SEER
Function
The 18RULX and the 24RULX are universal mount.
7
They can mount low on the wall or transverse 18RULX 24RULX 36RSLX
6 mount them on the ceiling. The 36RSLX can only Heat Pump Heat Pump Heat Pump
7
be mounted on the ceiling, can take in fresh air and Nominal Cooling BTU/h 17,800 22,200 34,100
can throw air farther. 6 Min.~Max. Cooling BTU/h 5,000~21,600 5,000~27,300 8,500~36,000
7 7 Nominal Heating BTU/h 21,500 24,000
Standard Features 7
Low Heating 17°F BTU/h 13,000 15,000
36,500
23,400
6 6 0°F 7
Wireless
Wireless Remote 6 Control 0°F Ambient Cooling
Ambient
Min.~Max. Heating BTU/h 5,000~25,600 5,000~29,000 9,200~42,700
6 ft
165
HSPF BTU/hW 8.5 8.5 8.5
Sleep Timer
P
iping
Long Piping Length
Auto Mode 6 Pump Down Pump Down Operation Recommended Fuse Size (A) 20 20 30
7
Air Circ. C.F.M. (m /h): Hi
3
459 (780) 518 (880) 1089 (1850)
Auto 7Restart/Reset 7
C
eiling
High Ceiling Mode
Medium 383 (650) 436 (740) 977 (1660)
6
Auto6 Changeover
6
Fresh Air Intake^ Low 324 (550) 371 (630) 842 (1430)
POWERFUL POWERFUL
*Available only with optional wired remote controller. Noise Level dB(A): Hi 43/43 (Clg/Htg) 47/47 (Clg/Htg) 48/48 (Clg/Htg)
^Fresh air knockout available. Fresh air fan and ductwork field supplied.
Medium 39/39 (Clg/Htg) 43/43 (Clg/Htg) 45/43 (Clg/Htg)
See Design and Technical Manual for details
Low 35/35 (Clg/Htg) 38/38 (Clg/Htg) 41/39 (Clg/Htg)
Outdoor Fan Speed RPM 780/780 850/900 850/900
Optional Accessories Outdoor Noise Level dB(A) 51/53 53/55 54/55
Current Rated/Max (A): Cooling 7.1/12.5 9.8/12.5 18.3/18.8
POWERFUL Wired Remote Control UTY-RNBYU*
Heating 9.8/12.5 10.2/12.5 15.3/18.8
Weekly Timer
Power Use Rated/Max (kw): Cooling 1.63/2.88 2.25/2.88 4.22/4.35
POWERFUL
Full Function Wired Remote
Heating 2.25/2.88 2.35/2.88 3.50/4.35
Child Lock Capable
Fan Speeds Stage 3 + Auto 3 + Auto 3 + Auto
*Requires dip switch change on indoor unit.
Air Direction: Horizontal Automatic Automatic Automatic
Condensate Pump UTR-DPB24T Vertical Automatic Automatic Automatic
OEM design plug and play Air Filter Washable Washable Washable
Rated for 11.8” of vertical lift. Front Grille Permanent Permanent Permanent
Connection Method Flare Flare Flare
Applications Combined Min. Lgth Ft (m) 16 (5) 16 (5) 16 (5)
165 (50)
Combined Max. Lgth Ft (m) (pre-charge: 49’) 165 (50) 165 (50)
The universal mount 18RULX and 24RULX are ideal (pre-charge: 49’) (pre-charge: 49’)
for a house of worship to mount beneath stained glass Max. Vertical Diff. Ft (m) 66 (20) 66 (20) 98 (30)
windows. Lower in height than the pews, they do not Conn. Pipe Diameter Inch Suc.1/2 Dis. 1/4 Suc.5/8 Dis. 3/8 Suc.5/8 Dis. 3/8
disturb the aesthetics of the space. With long piping Net Weight lbs. (kg) 62 (28) 141 (64) 62 (28) 141 (64) 106 (48) 141 (64)
lengths of 165' the outdoor units can also be placed Dimensions: Height Inch 7-7/8 32-3/4 7-7/8 32-3/4 9-1/2 32-3/4
mm 199 830 199 830 240 830
remotely out of sight. Another popular application for
Width Inch 39-1/8 35-1/2 39-1/8 35-1/2 65-1/2 35-1/2
this model is in hallways where wall space is limited.
mm 990 900 990 900 1660 900
The 36RSLX is popular where fresh air intake and
Depth Inch 25-7/8 13 25-7/8 13 27-5/8 13
high capacity is required like a restaurant or bar. They 655 330 655 330 700 330
mm
are also often suspended from threaded rod and used Refrigerant R410A R410A R410A
in multiple to condition large warehouse spaces.
AOU36RLX
Outdoor
AOU24RLX
Outdoor
Indoor
Indoor
ABU18RULX
ABU36RSLX
AOU18RLX
Outdoor
Indoor
ABU24RULX
23
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE MINI-SPLITS
Function Applications
Compact ducts provide Long maximum combined piping length of 66’
comfort cooling or heating for and 49’ in height allow for versatile installations.
small room applications. Flexible installation, either horizontal or vertical,
Features include high efficiency and low height enables compact soffit or cabinet
up to 21.5 SEER, heating at low temperatures down to installation. These features make compact duct
-5°F, compact design, quiet operation, a standard wired systems ideal for commercial applications such as
remote control, and the ability to bring in fresh air. offices, restaurants, convenience stores, motels,
dorms, in retrofit and new construction.
High Performance Heating
Heating capacity at low 75°F
outdoor temperatures is When
achieved by adopting a used
Single
on
large heat exchanger other Zone
models
and a high capacity
7 +5°F Multi-Tenant Hotels / Motels Dorms
compressor. Systems -5°F Dwellings
7
operate down to -5°F.
6
7
Standard Features Optional Accessories NEW
!
6 7
Wired Remote Control Auto Changeover
Wired
6Low
Backlit Wired Remote Control
7 Weekly Timer Low Ambient Cooling
Ambient
UTY-RVNUM Displays room temp.
7 7
6 Dry
Dry Mode Cold
Cold Prevention Wireless Remote and Receiver
6
Auto Mode 6 16
Daisy
Daisy Chain Unit UTY-LRHUM
POWERFUL UTY-RVNUM
Economy Mode Pump
Built-In Condensate Pump
50 F
I/O
Minimum Heat*Auto 3POWERFUL
rd
Party 3rd Party Device Control^
POWERFUL 7
Auto Restart/Reset
*Available only with optional wireless
6 remote controller.
^Operation
POWERFUL
monitoring and On/Off control only.
24
Downloaded from www.Manualslib.com manuals search engine
Compact Duct 9RLFCD 12RLFCD 18RLFCD
Built-in drain pump allows for Heat Pump Heat Pump Heat Pump
installation of compact duct
unit in smaller spaces than
traditional units.
Nominal Cooling BTU/h 9,000 12,000 18,000
Traditional
Min~Max Cooling BTU/h 3,100~12,000 3,100~13,600 3,100~20,100
Nominal Heating BTU/h 12,000 16,000 21,600
Drain
Pump Min~Max Heating BTU/h 3,100~18,000 3,100~19,400 3,100~25,600
13”
HSPF 12.2 11.5 11.3
SEER 21.5 20.0 19.7
Compact Duct EER Clg/Htg 14.5/14.1 12.8/12.3 12.0/12.9
Cooling Operating Range °F(°C) 14~115 (-10~46) 14~115 (-10~46) 14~115 (-10~46)
Heating Operating Range °F(°C) -5~75 (-21~24) -5~75 (-21~24) -5~75 (-21~24)
9.4”
Moisture Removal Pt./h(l/h) 1.5 (.07) 2.7 (1.3) 4.2 (2.0)
Voltage/Frequency/Phase 208-230/60/1 208-230/60/1 208-230/60/1
Recommended Fuse Size (A) 15 15 20
Return Air-intake Choices Static Pressure In. W. C. 0 ~ 0.36 0 ~ 0.36 0 ~ 0.36
Air Circ. C.F.M. (m /h) Clg/Htg: Hi
3 353 (600) 383 (650) 554 (940)
Medium 324 (550) 353 (600) 518 (880)
Bottom 294 (500) 324 (550) 483 (820)
Low
Quiet 265 (450) 283 (480) 442 (750)
Noise Level dB(A) (Clg/Htg): Hi 28/28 29/29 32/32
Medium 27/26 28/28 30/30
Back Low 26/25 27/27 29/29
Quiet 25/24 26/24 27/27
Outdoor Fan Speed RPM Clg/Htg 590/720 870/780 870/1,000
Flexible Installation Outdoor Noise Level Clg/Htg 48/49 49/50 54/55
Horizontal or vertical. Running Current Rated (A)Clg/Htg 3.0/3.9 4.4/6.0 6.6/7.3
Power Use Rated/Max (kW): Cooling 0.62/1.40 0.94/1.45 1.50/2.15
Heating 0.85/1.80 1.30/2.00 1.67/2.60
Fan Speeds Stage 4 + Auto 4 + Auto 4 + Auto
Air Filter Washable Washable Washable
Connection Method Flare Flare Flare
Combined Min. Length Ft (m) 9 (2.7) 9 (2.7) 9 (2.7)
Combined Max. Length Ft (m) 66 (20) 66 (20) 66 (20)
(pre-charge: 49’) (pre-charge: 49’) (pre-charge: 49’)
Max. Vertical Diff. Ft (m) 49 (15) 49 (15) 49 (15)
Conn. Pipe Diameter Inch suc 3/8 dis 1/4 suc 3/8 dis 1/4 suc 1/2 dis 1/4
Indoor Unit Net Weight lbs. (kg) 41 (19) 41 (19) 50 (23)
Outdoor Unit Net Weight lbs. (kg) 84 (38) 84 (38) 86 (39)
Indoor Unit Dimensions: Height Inch (mm) 7-25/32 (198) 7-25/32 (198) 7-25/32 (198)
Width Inch (mm) 27-9/16 (700) 27-9/16 (700) 35-7/16 (900)
Depth Inch (mm) 24-13/32 (620) 24-13/32 (620) 24-13/32 (620)
*Internal drain pump will not operate Supply Duct Flange
when the unit is mounted in a vertical 5-15/16 (151) 5-15/16 (151) 5-15/16 (151)
Dimensions: Height Inch (mm)
configuration.
Width Inch (mm) 25-19/32 (650) 25-19/32 (650) 33-15/32 (850)
Depth Inch (mm) 3/4 (19) 3/4 (19) 3/4 (19)
Return Duct Flange 6-27/32 (174) 6-27/32 (174) 6-27/32 (174)
Dimensions: Height Inch (mm)
Width Inch (mm) 22-19/32 (574) 22-19/32 (574) 30-15/32 (774)
Depth Inch (mm) 3/4 (19) (Flat) 3/4 (19) (Flat) 3/4 (19) (Flat)
Outdoor Unit Dimensions: Height Inch (mm) 24-1/2 (620) 24-1/2 (620) 24-1/2 (620)
Width Inch (mm) 31-3/32 (790) 31-3/32 (790) 31-3/32 (790)
Depth Inch (mm) 11-11/32 (290) 11-11/32 (290) 11-11/32 (290)
Refrigerant R410A R410A R410A
25
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE MINI-SPLITS
Function Applications
Compact cassettes provide Long maximum combined piping length of 66’
comfort cooling or heating for and 49’ in height allow for versatile installations.
small room applications. 4-way airflow, concealed flush mount design and
Features include high efficiency the ability to operate in limited space above the
up to 24.0 SEER, heating at low temperatures down to drop ceiling, makes these systems ideal for
-5°F, compact design, quiet operation, a standard wired commercial applications such as offices, restaurants,
remote control, and the ability to bring in fresh air through convenience stores, motels, dorms, in retrofit
the optional Fresh Air Kit. and new construction.
Standard Features
Wired
Wired Remote Control
Weekly Timer
7
Dry
Dry Mode
6
7 Auto Louver: Up/ Down
POWERFUL
6
Auto Mode
50 F
7 Minimum Heat*
Economy Mode
7 POWERFUL
Auto Restart/Reset
6 POWERFUL 7
Auto
POWERFUL Changeover
6Low
Ambient
Low Ambient Cooling
Cold Prevention Fresh Air Kit**
Cold
UTZ-VXAA
7 16 Daisy Chain
Daisy Mixes room air then passes
High Ceiling Mode through the heat exchanger.
7 Ceiling
7
POWERFUL
Pump
Condensate Pump
6 Fresh Air Intake**
POWERFUL
I/O * Available only with optional wireless remote control.
3rd Party
3rd Party Device Control^
7
**Requires Fujitsu’s Optional Fresh Air Kit part #UTZ-VXAA. Allows for a
! 4-inch flex duct connection. Requires a field supplied duct booster fan
6 Optional Accessories NEW capable of 60 CFM at .2”W.C. or 90 CFM at .4”W.C. For fan static
pressure requirements, see installation manual. Add hood, filter and duct
Backlit Wired Remote Control losses for fan total static pressure requirements. Will add 4” to the height
UTY-RVNUM Displays room temp. of the indoor unit.
UTY-RVNUM
26
Downloaded from www.Manualslib.com manuals search engine
Easy Installation 9RLFCC 12RLFCC 18RLFCC
Heat Pump Heat Pump Heat Pump
Fits into a standard ceiling tile*.
22.5” 22.5”
Nominal Cooling BTU/h 9,000 12,000 18,000
Min~Max Cooling BTU/h 3,100~12,000 3,100~13,600 3,100~20,100
Nominal Heating BTU/h 12,000 16,000 21,600
Min~Max Heating BTU/h 3,100~18,000 3,100~19,400 3,100~25,600
HSPF 13.0 12.2 11.5
SEER 24.0 21.9 20.1
EER Clg/Htg 14.5/13.5 12.8/11.1 11.2/12.3
Cooling Operating Range °F(°C) 14~115 (-10~46) 14~115 (-10~46) 14~115 (-10~46)
Heating Operating Range °F(°C) -5~75 (-21~24) -5~75 (-21~24) -5~75 (-21~24)
*Dimensions of outer grille are 27-9/16” x 27-9/16” Moisture Removal Pt./h(l/h) 1.3 (.06) 2.5 (1.2) 4.6 (2.2)
and may overlap adjacent tiles.
Voltage/Frequency/Phase 208-230/60/1 208-230/60/1 208-230/60/1
Recommended Fuse Size (A) 15 15 20
318 (540) 359 (610) 400 (680) Clg
2-Stage Turbo Fan Air Circ. C.F.M. (m /h): Hi
3
27
Downloaded from www.Manualslib.com manuals search engine
SINGLE ZONE MINI-SPLITS
Up to 16.0 SEER
Function
Up to 16-SEER, these models provide up to 30% increase in
efficiency over 13-SEER models. These models offer the
ability to send up to 38% of their capacity through two branch
Standard Wired Remote
ducts to adjacent rooms. Slender fit feature now offered on all • Weekly timer
models decreases space required above the ceiling increasing • Set on-off time twice a day
application opportunities.
7 • Set different on-off time by day
7
6 • Set time in 5 minute intervals
Standard Features 6
• Control up to 16 indoor units
7
Weekly Timer Cold Prevention
Cold 7 • Child lock capable
6 7
Dry
Dry Mode
Slender Fit • Remote temperature sensor
6
Slender
6
Auto Louver: Up/ Down
7 Sensor
Remote Temp. Sensor
POWERFUL
Auto Mode
6 7 16
Daisy
Daisy Chain
7
Energy Saver
6
Pump Down
Pump Down Operation
6 7
7
Auto Restart/Reset7
Ceiling
High Ceiling Mode Standard Depth
POWERFUL 6
Auto Changeover6
*Fresh air knockout available. Fresh air fan and ductwork field supplied. See design and technical manual for details. Fujitsu fresh air intake kit available part #KHRS940-25.
28
Downloaded from www.Manualslib.com manuals search engine
18RCLX 24RCLX 36RCLX 42RCLX
Heat Pump Heat Pump Heat Pump Heat Pump
• Install optional field supplied branch Width Inch 32-3/4 35-1/2 32-3/4 35-1/2 32-3/4 35-1/2 32-3/4 35-1/2
ducts on up to two sides to supply up mm 830 900 830 900 830 900 830 900
to 18% capacity per side to adjoining Depth Inch 32-3/4 13 32-3/4 13 32-3/4 13 32-3/4 13
spaces up to 16 feet away. See Design
mm 830 330 830 330 830 330 830 330
and Technical Manual for details.
Refrigerant R410A R410A R410A R410A
• Allows fresh air to be brought into the
AOU42RLX
AOU36RLX
Outdoor
Outdoor
Indoor
Indoor
Indoor
Indoor
AUU42RCLX
AUU18RCLX
AUU24RCLX
AUU36RCLX
AOU18RLX
Outdoor
AOU24RLX
Outdoor
29
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
MULTI ZONE
MINI-SPLIT SYSTEMS
Revolutionary Halcyon
HFI systems are changing
the way we define comfort
Operate as few as one indoor unit
or all indoor units
Choose from 3 indoor unit styles - wall
mount, compact duct or cassette, including
Designer Series RLS2 wall mount units
Four combinations are ENERGY STAR®
Qualified
Create over 9,700 combinations based
on indoor type and BTU
multi
18, 24, 36,000 BTUs
flex
48,000 BTUs
30
Downloaded from www.Manualslib.com manuals search engine
Multi-Zone Outdoor Units 18, 24 and 36,000 BTUs multi
AOU18RLXFZ, AOU24RLXFZ, AOU36RLXFZ 18, 24, 36,000 BTUs
Connectable Capacity
This function allows you to connect indoor units that can exceed outdoor unit capacity (See sizing guide on page 43 for
details). However, if you connect indoor units that exceed 100% of the outdoor unit’s capacity there are limitations.
If all indoor units are cooling or heating at the same time, the system will limit their capacity so that their total matches
the outdoor unit’s capacity. When a zone meets a desired set temperature it requires less capacity. The unused
capacity is then distributed to the remaining indoor units, increasing their capacity.
For Example
The load on a 3-bedroom home with a living room and kitchen downstairs and 3 bedrooms upstairs is 39,000 BTUs (21,000
BTU downstairs and 18,000 BTU upstairs). However the family isn’t upstairs and downstairs at the same time, therefore not
all units will be running simultaneously allowing 100% heating or cooling to occupied spaces. This can be achieved by our
AOU36RLXFZ outdoor unit.
If all indoor units are cooling or heating at the same time, the system will limit their capacity so that their total matches
the outdoor unit’s capacity. When a zone meets a desired set temperature it requires less capacity. The unused
capacity is then distributed to the remaining indoor units, increasing their capacity.
For Example
The load on a small 2-story office building with a business downstairs and worker apartments upstairs is 62,000 BTUs
(38,000 BTUs downstairs and 24,000 BTUs upstairs) but the workers aren’t upstairs and downstairs at the same time,
therefore not all units will be running simultaneously allowing 100% heating or cooling to occupied spaces.
31
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
Wall Mounts
The ability
to create the
right combinations, ASU7, 9, 12RLF ASU9, 12RLS2 ASU15RLS2
the right quantity
(up to 8-zones),
the right style indoor
units, and the right ASU18RLF ASU24RLF
capacity.
Compact Ducts
It’s the RIGHT choice
for your home or
business.
ARU9, 12RLF ARU18RLF ARU24RLF
32
Downloaded from www.Manualslib.com manuals search engine
multi flex
Wall Mounted 7, 9, 12, 18 and 24,000 BTUs 18, 24, 36,000 BTUs 48,000 BTUs
Nominal Cooling BTU/h* 7,000 9,000 12,000 18,000 24,000 9,000 12,000 14,000
Nominal Heating BTU/h* 8,100 10,200 13,500 20,000 27,000 10,200 13,500 16,300
Voltage/Frequency/Phase 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Clg 330 (560) Clg 353 (600) Clg 388 (660) Clg 542 (920) Clg 659 (1,120) Clg 353 (600) Clg 388 (660) Clg 418 (710)
Air Circ. C.F.M. (m /h): Hi
3
Htg 330 (560) Htg 353 (600) Htg 388 (660) Htg 542 (920) Htg 647 (1,100) Htg 353 (600) Htg 388 (660) Htg 418 (710)
Clg 294 (500) Clg 306 (520) Clg 330 (560) Clg 436 (740) Clg 530 (900) Clg 324 (550) Clg 353 (600) Clg 377 (640)
Medium Htg 294 (500) Htg 306 (520) Htg 330 (560) Htg 436 (740) Htg 530 (900) Htg 324 (550) Htg 353 (600) Htg 377 (640)
Clg 253 (430) Clg 253 (430) Clg 265 (450) Clg 365 (620) Clg 436 (740) Clg 277 (470) Clg 312 (530) Clg 336 (570)
Low Htg 253 (430) Htg 253 (430) Htg 277 (470) Htg 365 (620) Htg 436 (740) Htg 277 (470) Htg 312 (530) Htg 347 (590)
Clg 200 (340) Clg 200 (340) Clg 200 (340) Clg 324 (550) Clg 365 (620) Clg 194 (330) Clg 194 (330) Clg 230 (390)
Quiet
Htg 206 (350) Htg 206 (350) Htg 206 (350) Htg 324 (550) Htg 365 (620) Htg 194 (330) Htg 194 (330) Htg 253 (430)
Noise Level
dB(A) (Clg/Htg): Hi 36/36 37/37 40/40 43/44 49/48 36/36 37/37 41/41
Medium 32/32 33/33 36/36 37/37 42/42 32/32 34/34 36/36
Low 29/29 29/29 30/31 33/33 37/37 28/28 31/31 33/34
Quiet 25/25 25/25 25/25 31/31 33/33 21/21 21/21 25/27
Running Current
0.13 0.15 0.19 0.32 0.53 0.14 0.17 0.20
Rated (A): Cooling
Heating 0.13 0.15 0.19 0.32 0.53 0.14 0.17 0.20
Power Use Rated (w): Clg 15 17 22 41 69 16 19 23
Htg 15 17 22 41 69 16 19 23
Fan Speeds Stage 4+auto 4+auto 4+auto 4+auto 4+auto 4+auto 4+auto 4+auto
Air Direction: Horizontal Manual Manual Manual Auto Auto Manual Manual Manual
Vertical Auto Auto Auto Auto Auto Auto Auto Auto
Primary Air Filter Washable Washable Washable Washable Washable Washable Washable Washable
Ion Deodorizing Filter Disposable Disposable Disposable Disposable Disposable Disposable Disposable Disposable
Apple-Catechin Filter Disposable Disposable Disposable Disposable Disposable Disposable Disposable Disposable
Connection Method Flare Flare Flare Flare Flare Flare Flare Flare
Conn. Pipe Diameter Inch suc 3/8 dis 1/4 suc 3/8 dis 1/4 suc 3/8 dis 1/4 suc 1/2 dis 1/4 suc 5/8 dis 1/4 suc 3/8 dis 1/4 suc 3/8 dis 1/4 suc 1/2 dis 1/4
Net Weight lbs. (kg) 18 (8) 18 (8) 18 (8) 31 (14) 31 (14) 21 (9.5) 21 (9.5) 21 (9.5)
11-1/8 (282) 11-1/8 (282) 11-1/8 (282)
Dims: Height Inch (mm) 11-1/16 (280) 11-1/16 (280) 11-1/16 (280) 12-5/8 (320) 12-5/8 (320) 13-1/4* (337*) 13-1/4* (337*) 13-1/4* (337*)
Width Inch (mm) 31-1/16 (790) 31-1/16 (790) 31-1/16 (790) 39-1/4 (998) 39-1/4 (998) 34-1/4 (870) 34-1/4 (870) 34-1/4 (870)
Depth Inch (mm) 8 (203) 8 (203) 8 (203) 9 (228) 9 (228) 7-1/4 (185) 7-1/4 (185) 7-1/4 (185)
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
^Not compatible with outdoor unit AOU48RLXFZ. *Height when front panel is open.
33
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
multi flex
Compact Duct 9, 12, 18 and 24,000 BTUs 18, 24, 36,000 BTUs 48,000 BTUs
34
Downloaded from www.Manualslib.com manuals search engine
multi flex
Compact Cassettes 9, 12, and 18,000 BTUs 18, 24, 36,000 BTUs 48,000 BTUs
35
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
AOU36RLXFZ
AOU18, 24RLXFZ
AOU AOU AOU AOU
18RLXFZ 24RLXFZ 36RLXFZ 36RLXFZ
Compact Size Heat Pump Heat Pump Heat Pump 18+18 Combo1
The compact size of the outdoor ASU9+ASU9 ASU9+ASU7+ASU7 ASU9 x 4 ASU18+ASU18
Connectable Indoor Unit Number 2 2 to 3 3 to 4 2 1
3/8 x 2 3/8 x 3
is used. Net Weight lbs. (kg) 119 (54) 124 (56) 149 (68) 149 (68)
Dimensions: Height Inch 27-9/16 27-9/16 32-11/16 32-11/16
mm 700 700 830 830
Width Inch 35-7/16 35-7/16 35-7/16 35-7/16
Nominal Capacities, mm 900 900 900 900
Depth Inch 13 13 13 13
SEER and HSPF Ratings mm 330 330 330 330
Data below is based on AHRI Refrigerant R410A R410A R410A R410A
210/240 non-ducted wall 118+18 is the only 2 indoor unit (ASU, ARU or AUU) combination and requires K9FZ1818.
2See table on page 19 for allowed combinations within this connectable capacity range.
mounted models.
Cooling
Heating Capacity
Indoor Unit Capacity COP
Model EER SEER Btu/h HSPF
Btu/h
Type Combination 95◦F 47◦F 17◦F 47◦F
Non-Ducted ASU9+ASU9 18,000 12.50 18.0 22,000 13,900 3.44 9.3
Ducted - 18,000 12.10 16.0 22,000 13,900 3.52 9.0
AOU18RLXFZ Mixed - 18,000 12.30 17.0 22,000 13,900 3.48 9.2
ASU7+ASU12 and
Specific 18,000 12.50 18.0 22,000 13,900 3.67 9.0
ASU9+ASU12
Non-Ducted ASU9+ASU7+ASU7 22,000 12.50 18.0 24,000 14,100 4.04 9.5
AOU24RLXFZ Ducted - 22,000 10.60 15.5 24,000 14,100 3.42 9.0
Mixed - 22,000 11.55 16.8 24,000 14,100 3.74 9.3
Non-Ducted - 35,200 8.80 16.0 36,400 22,000 3.56 9.4
AOU36RLXFZ Ducted - 33,800 8.10 14.5 36,400 21,200 3.08 8.7
Mixed - 34,400 8.45 15.3 36,400 21,600 3.32 9.1
Yellow rows represent models that are ENERGY STAR® Qualified.
36
Downloaded from www.Manualslib.com manuals search engine
Flex Zone Outdoor Unit 48,000 BTUs
AOU48RLXFZ1 flex
48,000 BTUs
37
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
UTP-PU03A, UTP-PU03B
Warning: Branch boxes are not weather tight enclosures and cannot be mounted outdoors or in damp environments exceeding
80% relative humidity, unless using the Branch Box Outdoor Enclosure, Part #UTP-PX-A. See Page 39 for more information.
By reversing the electrical box position you can By reversing the electrical box position you You cannot reverse the electrical
orient the inlet and outlet pipes into a left hand can orient the inlet and outlet pipes into a box position when mounting the
or right hand configuration. left hand or right hand configuration. branch box vertically.
Clearances
Btm. Access Panel, Horiz. Box Mount Top Access Panel, Vertical Box Mount Side Access Panel, Vertical Box Mount
Access Panel Dims Access Panel Dims
Access 12 in. 24 x 34 in. 28 x 34 in.
Panel or as needed. or as needed.
24 in. or more
34 in. or more
Side View
Dims 28 in.
28 x 34 in. Service Space
12 in. or more
or as Bottom View
12 in. or
24 in. or more
needed.
12 in. or
more
28 in. or more
Access
more
28 in. or more
Panel Access
28 in. or more
16 in. or Direction
more 16 in. or
more
Access
Panel
Service Space
34 in. or more Top View
34 in. or more
Unit B
Unit C
Unit A
7-5/8 (195)
5-13/16 (148)
3-11/32
4-3/4 (120)
(85)
1-5/8
3-3/4 3-3/4
(42)
2-15/16 3-3/4 6-1/16 (154) 17-1/16 (433) 9-7/8 (251) (95) (95)
(75) (95)
1-5/8
(66) 13 (304)
2-1/4 (57)
38
Downloaded from www.Manualslib.com manuals search engine
Branch Box Outdoor Enclosure flex
48,000 BTUs
UTP-PX-A
The Branch Box Outdoor Enclosure is used to mount the indoor style Branch Box outdoors. The Branch Box Outdoor
Enclosure is a painted metal cover to match the condensing unit. When Branch Box Outdoor Enclosure is not
required, see Installation Manual for indoor mounting instructions.
FootFoot (Accessory)
(Accessory)
Dimensions In (mm)
(220)
8-11/16 (220)
(248)
9-3/4(248)
8-11/16
9-3/4
20-1/4 (515)
20-1/4 (515)
Knock
Knock out Out
holeHole
For Wiring
for wiring Control Box
Control Box
17-7/8 (454)
(454)
(256)
17-7/8
10-1/16
10-1/16 (256)
1-9/16
1-9/16 (39)
(39)
5/8 (16)
360° rotation on its vertical axis 360° rotation on its vertical axis
39
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
Wiring flex
48,000 BTUs
40
15
Ground
Ground Junction Box
Central Remote
Control
18 - 20 AWG
Power and
Communication = 3PST
3 Wire + Ground = 2PST
Optional Disconnect Switch
(or where code requires)
*Alternate Branch Box Power Configurations (Not Shown):
Each Branch Box may be powered from a separate 15A dedicated HVACR breaker or from a single 15A
dedicated HVACR breaker using a daisy chain to connect to secondary branch boxes.
Out to
Indoor #1
Out to
Indoor #2
Out to
Central Remote Indoor #3
40
Downloaded from www.Manualslib.com manuals search engine
Piping flex
48,000 BTUs
b c
Separation Tube e
Assembly Kit
d Branch Box
Branch Box
Branch Box l m
Outdoor Unit i j k
a
f g h
41
Downloaded from www.Manualslib.com manuals search engine
MULTI ZONE MINI-SPLITS
AOU18RLXFZ AOU36RLXFZ 7 15 15 18 53
15 15 24 52
7 7 14
3 INDOOR UNITS
12 12 15 39
15 18 18 50 7 15 15 24 59
7 9 16 7 7 7 7 28
2 ROOMS
15 18 24 56 7 15 18 18 57
7 12 19 7 7 7 9 30
9 9 18 15 24 24 62 7 18 18 18 61
7 7 7 12 33
9 12 21 18 18 18 54 9 9 9 12 39
7 7 7 15 36
AOU24RLXFZ 18 18 24 60 9 9 9 15 41
7 7 7 18 ** 39
4 ROOMS
7 7 - 14 7 7 7 18 39 9 9 9 18 45
7 7 9 9 32
7 9 - 16 7 7 7 24 45 9 9 9 24 51
7 7 9 12 35
7 12 - 19 7 7 9 18 41 9 9 12 12 42
7 7 9 15 38
7 15 22 7 7 9 24 47 9 9 12 15 44
7 7 12 12 38
7 18 25 7 7 12 15 40 9 9 12 18 48
7 9 9 9 34
9 9 - 18 7 7 12 18 44 9 9 12 24 54
7 9 9 12 37
9 12 21 7 7 12 24 50 9 9 15 15 46
9 9 9 9 36
9 15 24 7 7 15 15 42 9 9 15 18 50
3 ROOMS
AOU48RLXFZ1
9 18 27 18 24 42 7 7 15 18 46 9 9 15 24 56
2
12 12 24 24 24 48 7 7 15 24 52 9 9 18 18 54
12 15 27 7 9 24 40 7 7 18 18 50 9 9 18 24 60
7 7 7 21 7 12 24 43 7 7 18 24 56 9 12 12 12 45
7 7 9 23 7 7 24 24 62
4 INDOOR UNITS
7 15 18 39 9 12 12 15 47
7 7 12 26 7 15 24 45 7 9 9 15 39 9 12 12 18 51
7 9 9 25 7 18 18 43 7 9 9 18 43 9 12 12 24 57
9 9 9 27 7 18 24 49 7 9 9 24 49 9 12 15 15 49
4 INDOOR UNITS
AOU36RLXFZ 7 24 24 55 7 9 12 12 40 9 12 15 18 53
18*18* 36 9 9 24 42 7 9 12 15 42 9 12 15 24 59
7 7 15 - 29 9 12 18 39 7 9 12 18 46 9 12 18 18 57
7 7 18 - 32 9 12 24 45 7 9 12 24 52 9 15 15 15 51
7 7 24 38 9 15 18 41 7 9 15 15 44 9 15 15 18 55
3 INDOOR UNITS
7 9 12 - 28 9 15 24 47 7 9 15 18 48 9 15 15 24 61
7 9 15 - 31 9 18 18 45 7 9 15 24 54 9 15 18 18 59
7 9 18 34 9 18 24 51 7 9 18 18 52 12 12 12 12 48
7 12 12 - 31 9 24 24 57 7 9 18 24 58 12 12 12 15 50
4 ROOMS
7 12 15 34 12 12 18 42 7 12 12 12 43 12 12 12 18 54
7 12 18 37 12 12 24 48 7 12 12 15 45 12 12 12 24 60
9 9 9 - 27 12 15 15 40 7 12 12 18 49 12 12 15 15 52
9 9 12 - 30 12 15 18 44 7 12 12 24 55 12 12 15 18 56
9 9 15 33 12 15 24 50 7 12 15 15 47 12 12 15 24 62
9 9 18 37 12 18 18 48 7 12 15 18 51 12 12 18 18 60
9 12 12 33 12 18 24 54 7 12 15 24 57 12 15 15 15 54
9 12 15 36 12 24 24 60 7 12 18 18 55 12 15 15 18 58
9 12 18 39 15 15 15 42 7 12 18 24 61 12 15 18 18 62
12 12 12 36 15 15 18 46 7 15 15 15 49 15 15 15 15 56
*The optional kit “K9FZ1818 (UTP-MU36A2)” is necessary for dual zone system “18+18”. **Wall mounted type ASU18RLF can not be connected in this combination.
“-” represents available circuit for future expansion when connecting this combination.
42
Downloaded from www.Manualslib.com manuals search engine
Allowable Combinations for AOU48RLXFZ1 flex
48,000 BTUs
259 Combinations Based on BTU
9,131 Combinations Based on Indoor Type and BTU
15 15 15 18 60 7 9 9 9 12 46 12 12 12 12 12 60 7 7 12 12 12 12 62
4
5
7 7 7 7 12 40 7 9 9 9 15 48 12 12 12 12 15 62 7 9 9 9 9 9 52
7 7 7 7 15 42 7 9 9 9 18 52 7 7 7 7 7 7 42 7 9 9 9 9 12 55
7 7 7 7 18 46 7 9 9 9 24 58 7 7 7 7 7 9 44 7 9 9 9 9 15 57
6 INDOOR UNITS
7 7 7 7 24 52 7 9 9 12 12 49 7 7 7 7 7 12 47 7 9 9 9 9 18 61
7 7 7 9 9 39 7 9 9 12 15 51 7 7 7 7 7 15 49 7 9 9 9 12 12 58
7 7 7 9 12 42 7 9 9 12 18 55 7 7 7 7 7 18 53 7 9 9 9 12 15 60
7 7 7 9 15 44 7 9 9 12 24 61 7 7 7 7 7 24 59 7 9 9 12 12 12 61
7 7 7 9 18 48 7 9 9 15 15 53 7 7 7 7 9 9 46 9 9 9 9 9 9 54
7 7 7 9 24 54 7 9 9 15 18 57 7 7 7 7 9 12 49 9 9 9 9 9 12 57
7 7 7 12 12 45 7 9 9 18 18 61 7 7 7 7 9 15 51 9 9 9 9 9 15 59
7 7 7 12 15 47 7 9 12 12 12 52 7 7 7 7 9 18 55 9 9 9 9 12 12 60
7 7 7 12 18 51 7 9 12 12 15 54 7 7 7 7 9 24 61 9 9 9 9 12 15 62
7 7 7 12 24 57 7 9 12 12 18 58 7 7 7 7 12 12 52 7 7 7 7 7 7 7 49
7 7 7 15 15 49 7 9 12 15 15 56 7 7 7 7 12 15 54 7 7 7 7 7 7 9 51
7 7 7 15 18 53 7 9 12 15 18 60
7 7 7 7 12 18 58 7 7 7 7 7 7 12 54
7 9 15 15 15 58
7 7 7 15 24 59 7 7 7 7 15 15 56 7 7 7 7 7 7 15 56
7 9 15 15 18 62
7 7 7 18 18 57 7 7 7 7 15 18 60 7 7 7 7 7 7 18 60
7 12 12 12 12 55
7 7 9 9 9 41 7 7 7 7 7 9 9 53
5 INDOOR UNITS
7 7 7 9 9 9 48
5 INDOOR UNITS
7 12 12 12 15 57
7 7 9 9 12 44 7 7 7 7 7 9 12 56
6 INDOOR UNITS
7 7 7 9 9 12 51
7 12 12 12 18 61
7 7 9 9 15 46 7 7 7 7 7 9 15 58
7 12 12 15 15 59 7 7 7 9 9 15 53
7 7 9 9 18 50 7 7 7 7 7 9 18 62
7 INDOOR UNITS
7 12 15 15 15 61 7 7 7 9 9 18 57
7 7 9 9 24 56 7 7 7 7 7 12 12 59
9 9 9 9 9 45 7 7 7 9 12 12 54
7 7 9 12 12 47 7 7 7 7 7 12 15 61
9 9 9 9 12 48 7 7 7 9 12 15 56
7 7 9 12 15 49 7 7 7 7 9 9 9 55
9 9 9 9 15 50 7 7 7 9 12 18 60
7 7 9 12 18 53 7 7 7 7 9 9 12 58
9 9 9 9 18 54 7 7 7 9 15 15 58
7 7 9 12 24 59 7 7 7 7 9 9 15 60
9 9 9 9 24 60
7 7 9 15 15 51 7 7 7 9 15 18 62 7 7 7 7 9 12 12 61
9 9 9 12 12 51
7 7 9 15 18 55 7 7 7 12 12 12 57 7 7 7 9 9 9 9 57
9 9 9 12 15 53
7 7 9 15 24 61 7 7 7 12 12 15 59 7 7 7 9 9 9 12 60
9 9 9 12 18 57
7 7 9 18 18 59 7 7 7 12 15 15 61 7 7 7 9 9 9 15 62
9 9 9 15 15 55
7 7 12 12 12 50 7 7 9 9 9 9 50 7 7 9 9 9 9 9 59
9 9 9 15 18 59
7 7 9 9 9 9 12 62
7 7 12 12 15 52 9 9 12 12 12 54 7 7 9 9 9 12 53
7 9 9 9 9 9 9 61
7 7 12 12 18 56 9 9 12 12 15 56 7 7 9 9 9 15 55
7 7 7 7 7 7 7 7 56
7 7 12 12 24 62 9 9 12 12 18 60 7 7 9 9 9 18 59
7 7 7 7 7 7 7 9 58
7 7 12 15 15 54 9 9 12 15 15 58 7 7 9 9 12 12 56
7 7 7 7 7 7 7 12 61
8
7 7 12 15 18 58 9 9 12 15 18 62 7 7 9 9 12 15 58
7 7 7 7 7 7 9 9 60
7 7 12 18 18 62 9 9 15 15 15 60 7 7 9 9 12 18 62
7 7 7 7 7 9 9 9 62
7 7 15 15 15 56 9 12 12 12 12 57 7 7 9 9 15 15 60
7 7 15 15 18 60 9 12 12 12 15 59 7 7 9 12 12 12 59
7 9 9 9 9 43 9 12 12 15 15 61 7 7 9 12 12 15 61
43
Downloaded from www.Manualslib.com manuals search engine
ACCESSORIES
Wall Mounts
Wired Remote Wired Remote Simple Remote
Controller* Controller Controller
UTY-RNBYU^/UTY-RNNUM^ UTY-RVNUM UTY-RSNUM*
The wired remote controller with its unique Features a large backlit LCD display and Suitable when only basic operations
lock function and sleek design provides full displays the room temperature. Provides are required for hotels, offices and
feature access to property managers, full feature access to property managers, other places where there is frequent
building owners, and facility maintenance, building owners, and facility maintenance, arrival and departure of occupants.
as well as providing basic comfort features as well as providing basic comfort features Remote does not allow any timer
to tenants, employees, and teachers. to tenants, employees, and teachers. settings.
Turns system on or off using a normally Required to connect the ASU9RLS2, Required to connect ASU7RLF, 9RLF,
open circuit. For example in home ASU12RLS2 and ASU15RLS2 to Wired 12RLF and ASU15RLS to Wired Remote
automation, BMS integration of only On/Off Remote UTY-RNNUM, Dry Contact Wire UTY-RNNUM, Dry Contact Wire Kit
operation, occupancy sensor, key card Kit UTY-XWZXZ5, and Simple Remote UTY-XWZX, and Simple Remote
switch, or lead-lag control of other Control UTY-RSNUM. Control UTY-RSNUM.
heating/cooling devices.
The wired remote controller with its unique OEM design plugs into factory harness Kit contains current sensor with built-in relay
lock function and sleek design provides full for ease of installation. Rated for 11.8” (Split Core Fixed Threshold Current Status
feature access to property managers, of vertical lift. Only used with System Sensor with Command Relay) and Switching
building owners, and facility maintenance, 36RSLX. Power Supply. Duct and Fan are field supply.
as well as providing basic comfort features A fan capable of generating 15 CFM at a
to tenants, employees, and teachers. static pressure of approximately .26 inches
W.C. required.
Compact Cassettes
High Humidity Fresh Air Dry Contact
Insulation Kit Intake Kit Wire Kit
UTZ-KXGC UTZ-VXAA UTY-XWZX
Additional insulation for compact cassette Mixes room air then passes it through a Turns system on or off using a normally
units, which may be needed when they heat exchanger. Allows for a 4-inch flex open circuit. For example in home
are installed in high humidity areas. duct connection. Requires a field supplied automation, BMS integration of only On/Off
duct booster fan capable of 60 CFM at operation, occupancy sensor, key card
.2”W.C. or 90 CFM at .4”W.C. For fan switch, or lead-lag control of other
static pressure requirements, see heating/cooling devices.
installation manual.
Suitable when only basic operations are In a 3-way air flow configuration an Air
For spaces where there is just no place to required for hotels, offices and other places Outlet Shutter Plate kit is required to block
mount the wired remote or where wireless where there is frequent arrival and departure air flow of 1 louver.
operation is preferred. of occupants. Timer feature is not available.
^ Minimum Heat, Sleep Timer functions will be lost when the wired remote controller is installed.
* Wall mounted ASU7, 9, and 12RLF require accessory interface kit (Part UTY-XCBXZ1) in order to connect this device to them. Wall mounted ASU9, 12,
and 15RLS2 require accessory interface kit (Part UTY-TWBXF) in order to connect this device to them.
** Internal thermosensor function in Wired Remote UTY-RNNUM is disabled when using this interface kit.
44
Downloaded from www.Manualslib.com manuals search engine
Compact Ducts
Receiver Unit Remote Sensor Simple Remote Compact Duct
UTY-LRHUM UTY-XSZX Controller Connector Kit
UTY-RSNUM UTD-ECS5A
Includes a wireless remote Wall mounted temperature Suitable when only basic Comes with 5 sets of wires. Can
control. sensor for compact duct operations are required for be used to turn unit on/off, wire
models. hotels, offices and other places in float switch, AUX heater, turn
where there is frequent arrival on an external device (Fan), or
and departure of occupants. show if the unit is running.
AOU36RLXFZ AOU48RLXFZ1
18+18 Combo Central Outdoor Unit Outdoor Unit
Fittings Kit Remote Input/Output Base Heater
K9FZ1818 Controller Connector Connector
UTY-DMMUM UTY-XWZXZ3 UTY-XWZXZ4
Allows two 18,000 BTU indoor This remote controls up to 8 Gives the ability to limit the noise Used to hook up an AUX base pan
units to be used on an outdoor individual indoor units. Set of the unit*, stop the outdoor heater to the outdoor unit. Heater
AOU36RLXFZ. Requires special temperatures on timers to unit, limit power consumption*, will stop ice from forming in the out-
piping; limited to only 18,000 BTU best meet individuals’ control the operating mode door unit. Base heater will operate
models. Total BTU capacity needs. Includes a large (Htg/Clg), or use output status to when outdoor temperature is below
is limited to 31,600 BTU in backlit LCD and 4-way see if the compressor is running. 36°F. Heater is field supply. Heaters
cooling. The kit upsizes linesets navigation pad. Remote You will need to order a greater than 25W can’t be fed
to 3/8” and 1/2”. connects in daisy chain to kit for each option. directly from the board, but have to
branch boxes. *Will reduce capacity. be powered from another source.
All Models
3-Pole Single Throw Safety Switch R410A Swivel Adapter
K3PST K9R410A55
For use where code requires a disconnect at the In order to minimize incorrect charging of systems with
indoor unit. R22 Fujitsu uses a different access port. Contractors will
need this 55-degree swivel access fitting.
Single Single Universal/ Large HFI Multi-Zone
Single Zone Wall Mounted Zone Zone Ceiling
Cassette and Flex-Zone
Compatibility Ducted Cassette Suspended
AOU48RLXFZ1
Compact Duct
Designer Wall
(9, 12, 15k BTU)
(7, 9, 12k BTU)
24RLXFW
12RLFCD
18RLFCD
12RLFCC
18RLFCC
12RLS2H
15RLS2H
12RLFW
Cassette
9RLFCD
9RLFCC
9RLS2H
18RULX
24RULX
18RCLX
24RCLX
36RCLX
42RCLX
36RSLX
12RLS2
15RLS2
30CLX1
36CLX1
9RLFW
9RLS2
30RLX
12RL2
24CL1
9RL2
18CL
45
Downloaded from www.Manualslib.com manuals search engine
MISCELLANEOUS
18RLXFW
24RLXFW
12RLFCD
18RLFCD
12RLFCC
18RLFCC
12RLS2H
15RLS2H
12RLFW
9RLFCD
9RLFCC
9RLS2H
18RULX
24RULX
18RCLX
24RCLX
36RCLX
42RCLX
36RSLX
12RLS2
15RLS2
30CLX1
36CLX1
9RLFW
9RLS2
30RLX
12RL2
24CL1
9RL2
18CL
1/4” x 3/8”
1/4” x 1/2”
1/4” x 5/8”
3/8” x 1/2”
3/8” x 5/8”
Total System
Max. Combined 66 66 66 66 66 66 66 66 66 66 66 165 165 66 165 165 165 66 66 66 66 66 66 165 165 165 165 165 165 230
Pipe Length ft (m) (20) (20) (20) (20) (20) (20) (20) (20) (20) (20) (20) (50) (50) (20) (50) (50) (50) (20) (20) (20) (20) (20) (20) (50) (50) (50) (50) (50) (50) (70)
Min. Combined 9 9 9 9 9 9 9 9 9 9 9 16 16 9 16 16 16 9 9 9 9 9 9 16 16 16 16 16 16 16
Pipe Length ft (m) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (5) (5) (2.7) (5) (5) (5) (2.7) (2.7) (2.7) (2.7) (2.7) (2.7) (5) (5) (5) (5) (5) (5) (5)
While these systems share indoor units, different line sizes are required.
UTP-PU03A /3B^
ARU18RLF x 2*
AUU18RLF x 2*
ASU18RLF x 2*
AOU48RLXFZ1
AOU18RLXFZ
AOU24RLXFZ
AOU36RLXFZ
AOU36RLXFZ
ASU12RLS2
ASU15RLS2
ASU9RLS2
ARU12RLF
ARU18RLF
ARU24RLF
AUU12RLF
AUU18RLF
ASU12RLF
ASU18RLF
ASU24RLF
AUU9RLF
ASU7RLF
ASU9RLF
ARU9RL
(18+18)
1/4” x 3/8”
1/4” x 1/2”
1/4” x 5/8”
3/8” x 1/2”
3/8” x 5/8”
Total System
Max. Combined 165 165 230 131 377
Pipe Length ft (m) (50) (50) (70) (40) (115)
Min. Combined 49 49 66 49 161 102
Pipe Length ft (m) (15) (15) (20) (15) (5)1(3)2
Each Indoor Unit Minimum and maximum pipe lengths for multi-zone units are found on pages 36, 37 and 41.
*18+18 is the only 2 indoor unit combination allowed for AOU36RLXFZ and requires kit K9FZ1818.
While these systems share indoor units, different line sizes are required.
^ Line set size from outdoor unit AOU48RLXFZ1 to the branch boxes.
1
Minimum combined pipe length from outdoor unit to branch box.
2
Minimum combined pipe length from branch box to indoor unit each.
46
Downloaded from www.Manualslib.com manuals search engine
Things To Know Before You Buy a Fujitsu System
Complete System Warranty Trademarks
Warranties vary depending on model: The Fujitsu logo is a registered trademark of Fujitsu Limited. The Halcyon and
2 Year Parts, 6 Year Compressor Warranty OR Halcyon HFI logos and names are trademarks of Fujitsu General America, Inc.
5 Year Parts, 7 Year Compressor Warranty. ENERGY STAR® is a registered trademark of the EPA and DOE. Copyright ©
Note: Condensing units come pre-charged from factory. Additional refrigerant 2013 Fujitsu General America, Inc.
may be required, be sure to check installation manual for more details.
• Cooling capacity is based on the following conditions: Non-Internet Retail Policy
Indoor temperature: 80°F DB/67°F WB (26.7°C DB/19.4°C WB) Internet sales are strictly prohibited and unauthorized. Any HVAC systems
Outdoor temperature: 95°F DB/75°F WB (35°C DB/23.9°C WB) purchased on the Internet, from an online retailer or any similar e-tailing web-
• Heating capacity is based on the following conditions: site, OR where the original factory serial numbers of the display have been
Indoor temperature: 70°F DB (21.1°C DB) removed, defaced, or replaced in any way WILL NOT BE COVERED BY
Outdoor temperature: 47°F DB/43°F WB (8.3°C DB/6.1°C WB) WARRANTY.
Certifications
ISO
ASTM
ISO14001 is the standard defined by the International Organization
Our outdoor units shall withstand 1,000 hours of salt spray tested per procedure
for Standardization (ISO) related to environmental management systems.
ASTM B117.
Fujitsu General America, Inc. has been acknowledged by an internationally
accredited compliance organization as having an appropriate program of
environmental protection procedures and activities to meet the requirements RoHS Compliant
of ISO14001. The air conditioners manufactured by Fujitsu have received Fujitsu participates in the RoHS Directive, which is the Restriction of Hazardous
ISO9001 series certification for quality assurance. Substances in electrical and electronic equipment. It is
an EU directive intended protect the environment by
forcing manufacturers to eliminate or severely curtail
• ISO9001 the use of cadmium, hexavalent chromium, and lead in
• ISO14001 all products from automobiles to consumer electronics.
47
Downloaded from www.Manualslib.com manuals search engine
For over 35 years,
making the hottest places cool
and the coolest places...
more comfortable.
Halcyon Mini-Splits Are For You If:
Central air quotes give you
sticker shock
You don’t want to lose closet
space to ductwork
You have warm or cold spots in
your home or business
Your window air conditioner’s
noise prevents you from hearing
the television
Distributed by:
A subsidiary of
Fujitsu General Limited
Printed in the USA Rev. 3/13
Part #6-26-FG2028