Condu

trayectoria Tramo Longitud [m] # de Abonados Dindividual [kVA] Ddiv [kVA] Me [kVA*m] Calibre
Fase Neutro
T-a 30 29 - 16.24 487.2
a-b 25 24 - 13.44 336
1
b-c 15 7 - 4.45 66.75
c-d 10 3 - 2.37 23.7
T-a 30 29 - 16.24 487.2
a-b 25 24 - 13.44 336
0 b-e 15 17 - 9.64 144.6
e-f 20 13 - 7.57 151.4
f-g 30 2 - 1.85 55.5
T-a 30 29 - 16.24 487.2
a-b 25 24 - 13.44 336
b-e 15 17 - 9.64 144.6
2 e-f 20 13 - 7.57 151.4
f-h 15 9 - 5.49 82.35
h-i 30 4 - 2.89 86.7
i-j 20 1 - 1.33 26.6

estrato 2
Conductor Regulacion Perdidas
Kreg I tramo [A]
Inom [A] Kperd [1\kVA*m] Parcial [%] Acum [%] Parcial [%] Parcial [kW]
[1/kVA*m]
0.00159 0.00142 0.774648 0.774648 0.691824 0.1067346067
0.00159 0.00142 0.53424 1.308888 0.47712 0.0609186816
0.00197 0.00163 0.1314975 1.4403855 0.1088025 0.0045996257
0.00197 0.00163 0.046689 1.4870745 0.038631 0.000869777
0.00159 0.00142 0.774648 0.774648 0.691824 0.1067346067
0.00159 0.00142 0.53424 1.308888 0.47712 0.0609186816
0.00159 0.00142 0.229914 1.538802 0.205332 0.0188043046
0.00159 0.00142 0.240726 1.779528 0.214988 0.015460862
0.00197 0.00163 0.109335 1.888863 0.090465 0.0015899224
0.00159 0.00142 0.774648 0.774648 0.691824 0.1067346067
0.00159 0.00142 0.53424 1.308888 0.47712 0.0609186816
0.00159 0.00142 0.229914 1.538802 0.205332 0.0188043046
0.00159 0.00142 0.240726 1.779528 0.214988 0.015460862
0.00159 0.00142 0.1309365 1.9104645 0.116937 0.0060988492
0.00197 0.00163 0.170799 2.0812635 0.141321 0.0038799681
0.00197 0.00163 0.052402 2.1336655 0.043358 0.0005478283

REGULACION ACUMULADA TOTAL 5.509603 PERDIDAS ACUMULADAS TOTAL


Perdidas

Acum [kW]

0.1067346067
0.1676532883
0.172252914
0.173122691
0.1067346067
0.1676532883
0.1864575929
0.2019184549
0.2035083773
0.1067346067
0.1676532883
0.1864575929
0.2019184549
0.2080173041
0.2118972722
0.2124451005

0.5890761688
Condu
# de Dindividual Me
trayectoria Tramo Longitud [m] Ddiv [kVA] Calibre
Abonados [kVA] [kVA*m]
Fase
1 T-a 30 4 2.31 9.24 2x#4

T-b 25 20 1.18 23.6 590 2x#4


b-c 40 15 1.27 19.05 762 2x#4
2 c-d 35 3 2.81 8.43 295.05 2x#4

T-b 25 20 1.18 23.6 590 2x#4


b-c 40 15 1.27 19.05 762 2x#4
c-e 22 6 1.82 10.92 240.24 2x#4
3 e-f 43 2 3.81 7.62 327.66 2x#4
Conductor Regulacion Perdidas
Calibre Kreg Kperd I tramo [A]
Inom [A] Parcial [%] Acum [%] Parcial [%]
Neutro [1/kVA*m] [1\kVA*m]
1x#4 0.0056591 139 0.0060888 0 0 38.5 0

1x#4 0.0056591 139 0.0060888 3.338869 3.338869 101.616555 3.592392


1x#4 0.0056591 139 0.0060888 4.3122342 7.6511032 85.4480632 4.6396656
1x#4 0.0056591 139 0.0060888 1.66971746 9.32082066 38.3989383 1.79650044

1x#4 0.0056591 139 0.0060888 3.338869 3.338869 101.616555 3.592392


1x#4 0.0056591 139 0.0060888 4.3122342 7.6511032 85.4480632 4.6396656
1x#4 0.0056591 139 0.0060888 1.35954218 9.01064538 49.5998436 1.46277331
1x#4 0.0056591 139 0.0060888 1.85426071 10.8649061 35.1996077 1.99505621
Perdidas Fase Neutro Kregulacion Kperdidas
2x#4 1x#4 0.0056591 0.0060888
Parcial [kW] Acum [kW]
2x#2 1x#2 0.0036195 0.0038315
0 0 2x#1 1x#1 0.00290679 0.00303654
2x#1/0 1x#1/0 0.00233726 0.00240752
0.8054142864 0.80541429 2x#2/0 1x#2/0 0.00188748 0.00191008
0.83966348196 1.64507777 2x#3/0 1x#3/0 0.00153067 0.00151388
0.1438727377374 1.78895051 2x#4/0 1x#4/0 0.00124317 0.00120138

0.1517481033869 1.94069861
0.1444221188971 2.08512073
VT [Vfase] n FP
120 2 0.95
Cond
# de Dindividual Me
trayectoria Tramo Longitud [m] Ddiv [kVA] Calibre
Abonados [kVA] [kVA*m]
Fase
a-b 20 11 - 18.692024 373.84048 -
|
b-c 24 0 - 0 0 -
a-b 20 11 - 18.692024 373.84048 -
II b-d 16 9 - 15.8198159 253.117055 -
d-e 16 1 - 2.03836806 32.613889 -
a-b 20 11 - 18.692024 373.84048 -
III b-d 16 9 - 15.8198159 253.117055 -
d-f 12 2 - 3.9969758 47.9637096 -
a-g 20 50 - 51.5311143 1030.62229 -
IV
g-h 10 3 - 5.88041486 58.8041486 -
a-g 20 50 - 51.5311143 1030.62229 -
g-i 30 42 - 47.0868189 1412.60457 -
V
i-o 12 39 - 45.2121474 542.545769 -
o-q 16 1 - 2.03836806 32.613889 -
a-g 20 50 - 51.5311143 1030.62229 -
g-i 30 42 - 47.0868189 1412.60457 -
VI
i-o 12 39 - 45.2121474 542.545769 -
o-p 16 2 - 3.9969758 63.9516129 -
a-g 20 50 - 51.5311143 1030.62229 -
g-i 30 42 - 47.0868189 1412.60457 -
i-o 12 39 - 45.2121474 542.545769 -
VII o-n 20 39 - 45.2121474 904.242948 -
n-j 16 37 - 43.8897995 702.236792 -
j-r 16 13 - 21.3792634 342.068215 -
r-t 12 3 - 5.88041486 70.5649783 -
a-g 20 50 - 51.5311143 1030.62229 -
g-i 30 42 - 47.0868189 1412.60457 -
i-o 12 39 - 45.2121474 542.545769 -
VIII o-n 20 39 - 45.2121474 904.242948 -
n-j 16 37 - 43.8897995 702.236792 -
j-r 16 13 - 21.3792634 342.068215 -
r-s 20 5 9.4384564 188.769128 -
a-g 20 50 - 51.5311143 1030.62229 -
g-i 30 42 - 47.0868189 1412.60457 -
i-o 12 39 - 45.2121474 542.545769 -
IX o-n 20 39 - 45.2121474 904.242948 -
n-j 16 37 - 43.8897995 702.236792 -
j-k 20 17 - 26.2659835 525.319669 -
k-m 16 6 - 11.1206375 177.930199 -
a-g 20 50 - 51.5311143 1030.62229 -
g-i 30 42 - 47.0868189 1412.60457 -
i-o 12 39 - 45.2121474 542.545769 -
X
X o-n 20 39 - 45.2121474 904.242948 -
n-j 16 37 - 43.8897995 702.236792 -
j-k 20 17 - 26.2659835 525.319669 -
k-l 12 6 - 11.1206375 133.44765 -
Conductor Regulacion Perdidas
Calibre Kreg Kperd I tramo [A]
Inom [A] Parcial [%] Acum [%] Parcial [%]
Neutro [1/kVA*m] [1\kVA*m]
- 8.50E-04 - 2.36E-03 0.31776441 51.9222889 0.88226353
- 8.50E-04 - 2.36E-03 0 0 0
- 8.50E-04 - 2.36E-03 0.31776441 51.9222889 0.88226353
- 8.50E-04 - 2.36E-03 0.2151495 43.9439332 0.59735625
- 8.50E-04 - 2.36E-03 0.02772181 5.66213351 0.07696878
- 8.50E-04 - 2.36E-03 0.31776441 51.9222889 0.88226353
- 8.50E-04 - 2.36E-03 0.2151495 43.9439332 0.59735625
- 8.50E-04 - 2.36E-03 0.04076915 11.1027106 0.11319435
- 8.50E-04 - 2.36E-03 0.87602894 143.141984 2.43226859
- 8.50E-04 - 2.36E-03 0.04998353 16.3344857 0.13877779
- 8.50E-04 - 2.36E-03 0.87602894 143.141984 2.43226859
- 8.50E-04 - 2.36E-03 1.20071388 130.796719 3.33374678
- 8.50E-04 - 2.36E-03 0.4611639 125.589298 1.28040801
- 8.50E-04 - 2.36E-03 0.02772181 5.66213351 0.07696878
- 8.50E-04 - 2.36E-03 0.87602894 143.141984 2.43226859
- 8.50E-04 - 2.36E-03 1.20071388 130.796719 3.33374678
- 8.50E-04 - 2.36E-03 0.4611639 125.589298 1.28040801
- 8.50E-04 - 2.36E-03 0.05435887 11.1027106 0.15092581
- 8.50E-04 - 2.36E-03 0.87602894 143.141984 2.43226859
- 8.50E-04 - 2.36E-03 1.20071388 130.796719 3.33374678
- 8.50E-04 - 2.36E-03 0.4611639 125.589298 1.28040801
- 8.50E-04 - 2.36E-03 0.76860651 125.589298 2.13401336
- 8.50E-04 - 2.36E-03 0.59690127 121.91611 1.65727883
- 8.50E-04 - 2.36E-03 0.29075798 59.3868428 0.80728099
- 8.50E-04 - 2.36E-03 0.05998023 16.3344857 0.16653335
- 8.50E-04 - 2.36E-03 0.87602894 143.141984 2.43226859
- 8.50E-04 - 2.36E-03 1.20071388 130.796719 3.33374678
- 8.50E-04 - 2.36E-03 0.4611639 125.589298 1.28040801
- 8.50E-04 - 2.36E-03 0.76860651 125.589298 2.13401336
- 8.50E-04 - 2.36E-03 0.59690127 121.91611 1.65727883
- 8.50E-04 - 2.36E-03 0.29075798 59.3868428 0.80728099
- 1.00E+00 - 1.00E+00 188.929582 26.2179344 189.214623
- 8.50E-04 - 2.36E-03 0.87602894 143.141984 2.43226859
- 8.50E-04 - 2.36E-03 1.20071388 130.796719 3.33374678
- 8.50E-04 - 2.36E-03 0.4611639 125.589298 1.28040801
- 8.50E-04 - 2.36E-03 0.76860651 125.589298 2.13401336
- 8.50E-04 - 2.36E-03 0.59690127 121.91611 1.65727883
- 1.00E+00 - 1.00E+00 525.766191 72.9610652 526.559424
- 2.00E+00 - 2.00E+00 356.011639 30.8906596 356.280314
- 3.00E+00 - 3.00E+00 3092.74289 143.141984 3094.29913
- 4.00E+00 - 4.00E+00 5651.61899 130.796719 5653.75202
- 5.00E+00 - 5.00E+00 2713.19001 125.589298 2714.00925
- 6.00E+00 - 6.00E+00 5426.2263 125.589298 5427.5917
- 7.00E+00 - 7.00E+00 4916.25445 121.91611 4917.31482
- 8.00E+00 - 8.00E+00 4203.00388 72.9610652 4203.79711
- 9.00E+00 - 9.00E+00 1201.14228 30.8906596 1201.34378
Perdidas

Parcial [kW] Acum [kW]


D diseño n [Años] r [%]
0.15831639 2.42 15 3.2
0
0.15831639
0.09072063
0.00150615
0.15831639
0.09072063
0.00434338
1.20324011
0.00783428
1.20324011
1.5069651
0.55574396
0.00150615
1.20324011
1.5069651
0.55574396
0.00579117
1.20324011
1.5069651
0.55574396
0.92623993
0.6982813
0.1656871
0.00940114
1.20324011
1.5069651
0.55574396
0.92623993
0.6982813
0.1656871
17.1445821
1.20324011
1.5069651
0.55574396
0.92623993
0.6982813
132.773771
38.0358164
1530.74575
2555.6851
1177.97939
2355.77353
2071.87163
1060.00191
128.253203
VT [Vfase] n FP
120 3 0.96
Cond
# de Dindividual Me
trayectoria Tramo Longitud [m] Ddiv [kVA] Calibre
Abonados [kVA] [kVA*m]
Fase
T-a 10 70 … 115.916084 1159.16084 …
a-b 15 … … 54.0807397 811.211096 …
A
b-f 10 … … 23.205064 232.05064 …
f-g 10 … … 13.8959731 138.959731 …

T-a 10 70 … 115.916084 1159.16084 …


B a-i 25 … … 30.8914882 772.287204 …
i-g 25 … … 16.3973705 409.934263 …
Conductor Regulacion Perdidas
Calibre Kreg Kperd I tramo [A]
Inom [A] Parcial [%] Acum [%] Parcial [%]
Neutro [1/kVA*m] [1\kVA*m]
… 2.43E-03 … 2.98E-03 2.82E+00 2.82E+00 331.058785 3.45E+00
… 2.43E-03 … 2.98E-03 1.97E+00 4.79E+00 157.417021 2.42E+00
… 2.43E-03 … 2.98E-03 5.64E-01 5.35E+00 67.9082578 6.92E-01
… 2.43E-03 … 2.98E-03 3.38E-01 5.69E+00 40.7960909 4.14E-01

… 2.43E-03 … 2.98E-03 2.82E+00 2.82E+00 331.058785 3.45E+00


… 2.43E-03 … 2.98E-03 1.88E+00 4.69E+00 89.8370974 2.30E+00
… 2.43E-03 … 2.98E-03 9.96E-01 5.69E+00 48.1397461 1.22E+00
Perdidas Calcular el porcentaje de perdidas de la red que debe suplir el
trafo que alimenta el circuito de la figura, Tambien dimensione el
Parcial [kW] Acum [kW] trafo y determine la minima tension esperada y en que barra.

3.92400671 3.92400671
1.28120565 5.20521236 Nodo Usuarios Ddiv [kVA] Ddiseño
0.15725624 5.3624686 b 17 30.8756757 3.2
0.05639236 5.41886096 f 4 9.30909091
g 11 21.12
5.41886096 p 2 5.48571429
0.69672278 6.11558373 n 10 19.4782609
0.19630473 6.31188847 j 14 26.0129032
i 7 14.4941176

Matriz sistema (a)


RHS (b)
A B C Me
1 1 1 0 126.775763 (1)
35 0 0 -1 710.604423 (2)
0 50 0 -1 362.352941 (3)
0 0 80 -1 2162.06131 (4)

Matriz inversa
0.467836257 0.01520468 -0.00935673 -0.00584795 A= 54.0807397
0.32748538 -0.00935673 0.01345029 -0.00409357 B= 30.8914882
0.204678363 -0.00584795 -0.00409357 0.00994152 C= 41.8035347
16.37426901 -0.46783626 -0.32748538 -0.20467836 Me= 1182.22147
VT [Vfase] n FP
120 3 0.98