TITLE:
STANDARD: ASHREA STANDARD 62.1, VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
DATE:
PERSON PER OUTDOOR AIR DIVERSITY REQUIRED OUTDOOR FRESH AIR FLOW FOR
Location Unit No. AREA M2 AREA FT2 CFM PER PERSON CFM PER FT2 NO OF PERSON REMARKS
1000FT2 FLOW (CFM) FACTOR AIR (CFM) AHU/FCU (CFM)
Level 5
Office 634 6821 5 0.06 53 5 674 1.0 674 Additional fresh air fan provided to
AHU-L5-GO 1,285 the FCUs with the total flow rate of
Meeting Room (AHU) 210 2259 5 0.06 113 50 700 0.75 525 508 cfm.
Meeting Room (FCU) 86 925 5 0.06 46 50 287 0.75 215
FCU-L5-TR1
Meeting Area Corridor 89 957 0.06 57 N/A NIL 508
Meeting Area Reception FCU-L5-TR2 123 1323 7.5 0.06 20 15 228 1.0 228
Door and window open direct to
Cafeteria FCU-L5-CT 1 & 2 226 2431 7.5 0.18 170 70 1714 N/A No Fresh Air - ourdoor
NOTE
Area CFM per Person CFM per Ft2 Person per 1000 ft2