Room List (Energy evaluation)

1
Project 0

Building 1 · Storey 1
Room List (Energy evaluation)

Room 1

Ptotal ARoom Lighting power density Ēperpendicular (Workplane)


3040.0 W 840.50 m² 3.62 W/m² = 1.07 W/m²/100 lx (Room) 339 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

19 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm

Room 2

Ptotal ARoom Lighting power density Ēperpendicular (Workplane)


960.0 W 45.43 m² 21.13 W/m² = 2.71 W/m²/100 lx (Room) 778 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

6 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm

Room 3

Ptotal ARoom Lighting power density Ēperpendicular (Workplane)


320.0 W 33.63 m² 9.52 W/m² = 3.03 W/m²/100 lx (Room) 314 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm

2
Project 0

Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


674703 lm 4320.0 W 156.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

27 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

3
Project 0

Building 1 · Storey 1
Calculation objects

4
Project 0

Building 1 · Storey 1
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 1) 339 lx 101 lx 485 lx 0.30 0.21 S2


Perpendicular illuminance (adaptive) (≥ 300 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 2) 778 lx 546 lx 968 lx 0.70 0.56 S4


Perpendicular illuminance (adaptive) (≥ 750 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 3) 314 lx 236 lx 372 lx 0.75 0.63 S6


Perpendicular illuminance (adaptive) (≥ 300 lx)
Height: 0.800 m, Wall zone: 0.000 m

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

5
Project 0

Building 1 · Storey 1 · Room 1


Summary

Ground area: 840.50 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: Maintenance factors, see
maintenance data sheet | Clearance height: 7.000 m | Mounting height: 7.000 m 6
Project 0

Building 1 · Storey 1 · Room 1


Summary

Results

Symbol Calculated Target Check Index

Workplane Ēperpendicular 339 lx ≥ 300 lx S2

g1 0.30 - - S2

Consumption values Consumption 6850 kWh/a max. 29450 kWh/a

Lighting power density Room 3.62 W/m² - -

1.07 W/m²/100 lx - -

Utilisation profile: Industrial activities and crafts - Foundries and metal casting, Casthouses

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

19 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

7
Project 0

Building 1 · Storey 1 · Room 1


Luminaire layout plan

8
Project 0

Building 1 · Storey 1 · Room 1


Luminaire layout plan

Manufacturer PHILIPS P 160.0 W

Article name BY481X ACW 1 ΦLuminaire 24989 lm


xLED250S/840 WB

Fitting 1x LED250S/840/-

19 x Philips BY481X ACW 1 xLED250S/840 WB

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 5.340 m / 2.175 m /
7.000 m 5.340 m 2.175 m 7.000 m 1

X-direction 5 pcs., Center - 16.020 m 2.175 m 7.000 m 2


center, 10.680 m
37.380 m 2.175 m 7.000 m 3
Y-direction 4 pcs., Center -
center, 4.350 m 48.060 m 2.175 m 7.000 m 4

Arrangement A1 5.340 m 6.525 m 7.000 m 5

16.020 m 6.525 m 7.000 m 6

26.700 m 6.525 m 7.000 m 7

37.380 m 6.525 m 7.000 m 8

48.060 m 6.525 m 7.000 m 9

5.340 m 10.875 m 7.000 m 10

16.020 m 10.875 m 7.000 m 11

26.700 m 10.875 m 7.000 m 12

37.380 m 10.875 m 7.000 m 13

9
Project 0

Building 1 · Storey 1 · Room 1


Luminaire layout plan

X Y Mounting Luminaire
height

48.060 m 10.875 m 7.000 m 14

5.340 m 15.225 m 7.000 m 15

16.020 m 15.225 m 7.000 m 16

26.700 m 15.225 m 7.000 m 17

37.380 m 15.225 m 7.000 m 18

48.060 m 15.225 m 7.000 m 19

10
Project 0

Site 1 · Building 1 · Storey 1 · Room 1


Maintenance factors

Maintenance factor method Ambient condition Inspection interval


detailed Normal 1.0 Years

pcs. 19 Cleaning interval 1.0 Years

Manufacturer PHILIPS Flux distribution Direct

Article name BY481X ACW 1 Luminaire type Top-closed reflector (no self-cleaning
xLED250S/840 WB effect)

Fitting 1x LED250S/840/- Lamp type LED


160.0 W
Annual operating hours 2250 h

Replacement interval of the lamps 1.0 Years

Immediately replace defective lamps No

RMF 0.95

LMF 0.81

LLMF 1.00

LSF 1.00

MF = RMF x LMF x LLMF x LSF 0.77

11
Project 0

Building 1 · Storey 1 · Room 1


Luminaire list

Φtotal Ptotal Luminous efficacy


474791 lm 3040.0 W 156.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

19 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

12
Project 0

Building 1 · Storey 1 · Room 1


Calculation objects

13
Project 0

Building 1 · Storey 1 · Room 1


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 1) 339 lx 101 lx 485 lx 0.30 0.21 S2


Perpendicular illuminance (adaptive) (≥ 300 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Foundries and metal casting, Casthouses

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

14
Project 0

Building 1 · Storey 1 · Room 1


Workplane (Room 1)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 1) 339 lx 101 lx 485 lx 0.30 0.21 S2


Perpendicular illuminance (adaptive) (≥ 300 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Industrial activities and crafts - Foundries and metal casting, Casthouses

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

15
Project 0

Building 1 · Storey 1 · Room 2


Summary

Ground area: 45.43 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: Maintenance factors, see
maintenance data sheet | Clearance height: 7.000 m | Mounting height: 7.000 m 16
Project 0

Building 1 · Storey 1 · Room 2


Summary

Results

Symbol Calculated Target Check Index

Workplane Ēperpendicular 778 lx ≥ 750 lx S4

g1 0.70 - - S4

Consumption values Consumption 160 kWh/a max. 1600 kWh/a

Lighting power density Room 21.13 W/m² - -

2.71 W/m²/100 lx - -

Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

6 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

17
Project 0

Building 1 · Storey 1 · Room 2


Luminaire layout plan

18
Project 0

Building 1 · Storey 1 · Room 2


Luminaire layout plan

Manufacturer PHILIPS P 160.0 W

Article name BY481X ACW 1 ΦLuminaire 24989 lm


xLED250S/840 WB

Fitting 1x LED250S/840/-

6 x Philips BY481X ACW 1 xLED250S/840 WB

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.925 m / 0.983 m /
7.000 m 1.925 m 0.983 m 7.000 m 1

X-direction 2 pcs., Center - 5.775 m 0.983 m 7.000 m 2


center, 3.850 m
1.925 m 2.950 m 7.000 m 3
Y-direction 3 pcs., Center -
center, 1.967 m 5.775 m 2.950 m 7.000 m 4

Arrangement A1 1.925 m 4.917 m 7.000 m 5

5.775 m 4.917 m 7.000 m 6

19
Project 0

Site 1 · Building 1 · Storey 1 · Room 2


Maintenance factors

Maintenance factor method Ambient condition Inspection interval


detailed Normal 1.0 Years

pcs. 6 Cleaning interval 2.0 Years

Manufacturer PHILIPS Flux distribution Direct

Article name BY481X ACW 1 Luminaire type Top-closed reflector (no self-cleaning
xLED250S/840 WB effect)

Fitting 1x LED250S/840/- Lamp type LED


160.0 W
Annual operating hours 2750 h

Replacement interval of the lamps 1.0 Years

Immediately replace defective lamps No

RMF 0.95

LMF 0.69

LLMF 1.00

LSF 1.00

MF = RMF x LMF x LLMF x LSF 0.65

20
Project 0

Building 1 · Storey 1 · Room 2


Luminaire list

Φtotal Ptotal Luminous efficacy


149934 lm 960.0 W 156.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

6 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

21
Project 0

Building 1 · Storey 1 · Room 2


Calculation objects

22
Project 0

Building 1 · Storey 1 · Room 2


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 2) 778 lx 546 lx 968 lx 0.70 0.56 S4


Perpendicular illuminance (adaptive) (≥ 750 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

23
Project 0

Building 1 · Storey 1 · Room 2


Workplane (Room 2)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 2) 778 lx 546 lx 968 lx 0.70 0.56 S4


Perpendicular illuminance (adaptive) (≥ 750 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms, Plant rooms, switchgear rooms

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

24
Project 0

Building 1 · Storey 1 · Room 3


Summary

Ground area: 33.63 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: Maintenance factors, see
maintenance data sheet | Clearance height: 7.000 m | Mounting height: 7.000 m 25
Project 0

Building 1 · Storey 1 · Room 3


Summary

Results

Symbol Calculated Target Check Index

Workplane Ēperpendicular 314 lx ≥ 300 lx S6

g1 0.75 - - S6

Consumption values Consumption 53 kWh/a max. 1200 kWh/a

Lighting power density Room 9.52 W/m² - -

3.03 W/m²/100 lx - -

Utilisation profile: General areas inside buildings - Store rooms and cold stores, Dispatch and packing handling areas

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

26
Project 0

Building 1 · Storey 1 · Room 3


Luminaire layout plan

27
Project 0

Building 1 · Storey 1 · Room 3


Luminaire layout plan

Manufacturer PHILIPS P 160.0 W

Article name BY481X ACW 1 ΦLuminaire 24989 lm


xLED250S/840 WB

Fitting 1x LED250S/840/-

2 x Philips BY481X ACW 1 xLED250S/840 WB

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.850 m / 1.525 m /
7.000 m 2.850 m 1.525 m 7.000 m 1

X-direction 2 pcs., Center - 2.850 m 4.375 m 7.000 m 2


center, 2.850 m

Y-direction 1 pcs., Center -


center, 5.900 m

Arrangement A1

28
Project 0

Site 1 · Building 1 · Storey 1 · Room 3


Maintenance factors

Maintenance factor method Ambient condition Inspection interval


detailed Normal 1.0 Years

pcs. 2 Cleaning interval 2.0 Years

Manufacturer PHILIPS Flux distribution Direct

Article name BY481X ACW 1 Luminaire type Top-closed reflector (no self-cleaning
xLED250S/840 WB effect)

Fitting 1x LED250S/840/- Lamp type LED


160.0 W
Annual operating hours 2750 h

Replacement interval of the lamps 1.0 Years

Immediately replace defective lamps Yes

RMF 0.95

LMF 0.69

LLMF 1.00

LSF 1.00

MF = RMF x LMF x LLMF x LSF 0.65

29
Project 0

Building 1 · Storey 1 · Room 3


Luminaire list

Φtotal Ptotal Luminous efficacy


49978 lm 320.0 W 156.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 PHILIPS BY481X ACW 1 xLED250S/840 WB 160.0 W 24989 lm 156.2 lm/W

30
Project 0

Building 1 · Storey 1 · Room 3


Calculation objects

31
Project 0

Building 1 · Storey 1 · Room 3


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 3) 314 lx 236 lx 372 lx 0.75 0.63 S6


Perpendicular illuminance (adaptive) (≥ 300 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms and cold stores, Dispatch and packing handling areas

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.

32
Project 0

Building 1 · Storey 1 · Room 3


Workplane (Room 3)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 3) 314 lx 236 lx 372 lx 0.75 0.63 S6


Perpendicular illuminance (adaptive) (≥ 300 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms and cold stores, Dispatch and packing handling areas

Notes on planning:
The calculation of the results is based purely on the direct light component. The effect of reflected light has not been considered.