Determine the safe span that 100 mm x 150 mm purlins would have if it has a spacing of 800 mm
on centers to carry a roofing load of 60 Pa and wind load of 1.4 kPa of vertical surface. Allowable bending
stress is 10 MPa. Weight of purlins is 5000 N/m³. Use nominal dimensions only. The roof truss has a pitch
of ¼.
Solution:
1
Tan Ѳ =
2
Ѳ = 26.6°
Wind load:
2 P sin 26.6 °
Pn =
1+ sin ² 26.6 °
Pn
Pn = 1044 Pa
W2 = 835.2 L
W1 = 75 L + 43 L
W1 = 118 L
W1 = W2 + W1 Cos 26.6°
Wn = 835.2 L + 118 L Cos 26.6°
Wn = 940.7 L
Wt = 52.8 L
W L
Mn = n
8
940.7 L( L)(1000)
Mn =
8
Mn = 117587.5L²
Wt L
Mt =
8
52.8 L ²(1000)
Mt =
8
Mt = 6600 L²
6 Mn
fn =
db ²
6 ( 117587.5 ) L²
fn =
100(150)²
fn = 0.314 L²
6 Mt
ft =
db ²
6 ( 6600 ) L ²
ft =
150(100)²
ft = 0.026 L²
ft = f n+ f t
10 = 0.314 L² + 0.026 L²
10 = 0.340 L²
L = 5.42 m
PROBLEM:
Determine the maximum safe rather spacing whose dimension are 75 mm x 300 mm x 5m. as
shown, with allowance flexural stress of 15.9 MPa. Consider live load = 770 N/m² , roof and purlin loads =
280 N/m² and weight of rafter is 8 x 10³ N/m³.
Solution:
W1 = 5843.7 S + 900
W2 = W1 Cos 25°
W 2L
M =
8
W 2 ( 5 ) ( 1000 ) N . mm
M =
8
6M
M =
bd ²
6M
15.9 =
75(300)²
M = 17.9 x 106
(5000)
17.9 x 106 = W2
8
W2 =28640
27824
S =
5296
S = 5.25 m. (spacing)
Fa Fb
+ =1
fa fb
T
Fa = (actual tensile stress)
An
3
An = A (net area, to allow for notching, bolt holes)
5
6M
Fb = (actual bending stress)
bd ²
T
6M
Trial area = 3 f + = bd
fd
5