Analysis-of-electrical-and-thermal-characteristics-of-PV-array-under - 2021 - en

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Energy 218 (2021) 119480

Contents lists available at ScienceDirect

Energy
journal homepage: www.elsevier.com/locate/energy

Analysis of electrical and thermal characteristics of PV array under


mismatching conditions caused by partial shading and short circuit
failure of bypass diodes
Chung Geun Lee a, b, Woo Gyun Shin b, Jong Rok Lim b, Gi Hwan Kang b, Young Chul Ju b,
Hye Mi Hwang b, Hyo Sik Chang a, Suk Whan Ko b, *
a
Department of Energy Science and Technology, Graduate School of Energy Science and Technology, Chungnam National University, 99, Daeohak-ro,
Yuseon-gu, Daejeon, 305-764, South Korea
b
Photovoltaics Research Department, New and Renewable Energy Institute, Korea Institute of Energy Research, 152, Gajeong-ro, Yuseong-Gu, Daejeon, 305-
343, South Korea

a r t i c l e i n f o a b s t r a c t

Article history: In this paper, the problems of PV arrays under partial shading and a short circuit failure of bypass diode
Received 22 June 2020 were analyzed with modeling the mathematical equation by using simulation, and the electrical and
Received in revised form thermal characteristics were analyzed in an outdoor with a module which fabricated assuming a real PV
19 October 2020
array. The simulation model shows the mismatch current due to a bypass diode failure is proportional to
Accepted 28 November 2020
the number of fault diodes and parallel strings in PV arrays. From the results of a field experiment, a
Available online 5 December 2020
reverse current did not flow into the mismatching string under partial shading regardless of system
operation status, but the temperature of bypass diode in the case of system operation was 15e23  C
Keywords:
Short circuit failure of bypass diodes
higher than that of the other case. However, in case of the fault bypass diode with the system off, the
Voltage mismatch conditions reverse current of 17A flowed into a fault string. Besides, the surface temperature of fault bypass diode
Reverse current reached above 140  C, and some solar cells within a fault string was 18  C higher than normal strings. In
Melting of the junction box this paper, we verified that the short circuit failure of bypass diode creates a mismatch loss in PV system,
PV module Heating and the reverse current causes electric-thermal problems in PV array.
PV system Loss © 2020 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND
license (http://creativecommons.org/licenses/by-nc-nd/4.0/).

1. Introduction connected in parallel to the PV array. Partial shading is mainly


caused by the shadows of obstacles that occur at specific times, and
In the PV (Photovoltaic) systems, the PV array consists of strings temporarily moving clouds [5,6]. Moreover, there is a study
of PV modules connected in parallel, each string is composed of released by using computer simulation to estimate and analyze a
modules connected in series. Recently, the large-scale of PV sys- reverse current due to partial shading and short circuited string in
tems have reduced a capital cost and improved system efficiency as PV system. According to this study, a little reverse current flowed
the system voltage increases up to 1500V [1,2]. However, depend- while the number of shaded PV modules increased, but, a reverse
ing on the system voltage increased 1500V, the number of series current greatly rose as the number of short circuited PV modules
strings increases from to 24 to 32. Therefore, one faulty PV module increased [7]. Bypass diode can fail due to lightning strikes or
could affect more PV module in 1500V, resulting in more mismatch thermal runaway from frequent operation [8]. The recent study
losses [3,4]. The most common factors of mismatch loss in PV showed simulation results that damaged bypass diodes by light-
system is a failure of bypass diode and partial shading. These ning strikes to lead reverse current flowed from normal string to
mismatch factors cause differences in the performance of PV strings the failed string, which generate heat and burn out [9]. Further-
more, bypass diodes can deteriorate due to high temperature of
thermal runaway by rapid transitioning from forward bias state to
* Corresponding author. Tel.: þ82-42-860-3282; Fax: þ82-42-860-3692. reverse bias [10,11]. In this regard, there is a study released which
E-mail addresses: chung4219@gmail.com (C.G. Lee), swghero@kier.re.kr
changes in electrical property at PV module caused by a failure of
(W.G. Shin), jongrok@kier.re.kr (J.R. Lim), ghkang@kier.re.kr (G.H. Kang), ycju@
kier.re.kr (Y.C. Ju), hyemi@kier.re.kr (H.M. Hwang), hschang@cnu.ac.kr
bypass diode. The failure bypass diodes lose their properties of
(H.S. Chang), korea19@kier.re.kr (S.W. Ko). forward and reverse bias to become a micro-resistance, and are in a

https://doi.org/10.1016/j.energy.2020.119480
0360-5442/© 2020 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/
).
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

short circuit state with solar cells that connected to a fault bypass reverse current, the temperature of solar cells rose and the bypass
diode [12,13]. Furthermore, a recent research reported, when the diode is irreversible damaged.
bypass diode is shorted failure while the PV system is stopped, the The paper is organized as follows: the next section presents
temperature of a junction box increases [14]. These mismatch fac- electrical characteristics of the PV module by partial shading and
tors change Maximum Power Point (MPP) of PV modules or strings fault bypass diodes. The simulation results and mathematical
bringing about the system output loss on the PV system. models by fault bypass didoes and parallel circuits are provided in
Various studies have been released to improve the output Section 3. The field test results of electrical and thermal charac-
mismatch of PV system using computer simulation or experiments. teristics of PV arrays by partial shading and fault bypass diodes are
According to previous researches, applying DC-DC converters provided in Section 4. Results and discussion are given Section 5.
improved the performance of PV systems and recovered mismatch
losses due to shading [15e17]. There is a recent paper to propose 2. Electrical characteristics of a PV module on partial shading
the current collector optimizer (CCO) topology to increase and short circuit failure of bypass diodes
maximum power from mismatch losses on non-uniform PV array
by aged PV modules [18]. Moreover, there is an experimental study The major causes of mismatch in PV arrays are cases that one is a
released that the new interconnection of PV modules at the string bypass diode operated by shading condition, and the other is short
or array level have increased more the maximum power output in circuit failure of bypass diode. The previous research [30] has
partial shading conditions than traditional module interconnection shown that a reverse current does not flow in a mismatch situation
[19,20]. A comparison of power output characteristics with due to shading, however, it does flow in a bypass diode fault con-
mismatch losses along PV array configurations, such as series- dition. When one bypass diode is conducted by partial shading,
parallel (SP), bridge-linked (BL), total cross tied (TCT), etc, under output voltage (¼Maximum Voltage) of PV module decreases by 1/
partial shading has been analyzed by using a computer simulation 3 (Commercial PV module with 6 solar cell strings, one bypass
and conducting outdoor experiments [21e23]. A study proposed a diode connected 2 solar cell strings). However, open circuit voltage
novel methodology incorporated recent metaheuristic approach of decreases as much as the operating voltage of bypass diode
butterfly optimization algorithm (BOA) to reconfigure the shaded compared to the normal state. This is because solar cell is inde-
PV array optimally and extract the global maximum power (GMP) pendent current source and generate power when there is light. As
[24]. In addition, the performance of PV system according to the shown in Fig. 1, even if the bypass diode operates, the open circuit
impact of partial shading and aerosol has investgated on various PV voltage of module does not decrease significantly, so there will be
array configurations from experimental study [25]. no voltage mismatch between PV strings.
In the other way, many studies have been conducted to detect Bypass diodes are installed inside the junction box of PV module
faults accurately in PV systems due to the external operating con- operating in shading condition, which prevents the output loss of
ditions. The fault detection and diagnosis methods can reduce module and hot spot damage of solar cells. However, if there are
power losses, also improve the reliability and safety of PV plants. short failure of bypass diodes in PV module, the short circuit cur-
There is a review paper published which is sorted fault types of PV rent is the same as the normal state, but the open circuit voltage
system as infrared thermal image pattern and IeV characteristics and maximum power are significantly decreased [31]. The failure of
with expected performance of each fault situations [26,27]. bypass diode loses the characteristics of diode and becomes a
Futehrmore, the other paper reviewd types of fault and diagnosis micro-resistance. Hence, solar cells within PV module that con-
methods for PV system and suggested challenging issues and future nected with a fault bypass diode consist of a short circuit, which can
directions of fault diagnosis techniques [28]. In the stduy of fault express as an equivalent circuit, as shown in Fig. 2. At this moment,
diagnosis in connected PV systems, the indicators of abnormal even if there is no shading, the current flows to the fault bypass
current, voltage and frequency have proposed to detect and esti- diode, as shown in Eq. (1).
mate power losses in fault situations [29]. However, the studies that
analyzed electrical and thermal characteristics of arrays due to ID ¼ Isc  I (1)
mismatch in PV system have been conducted insufficient. In order
to understand actual mismatch situations of real PV systems due to The voltage of solar cells connected to a fault bypass diode is
partial shading and a failure of bypass diode, in-depth studies equal to the product of the current flowing through the diode and
should be conducted. Therefore, at the system level, it is necessary
to analyze mismatch phenomenon caused by shading and bypass
diode failure from the electrical circuit point of view, and to analyze
the changes of thermal characteristics in PV array.
The main contribution of this work is to analyze the electrical
and thermal characteristics of PV arrays under mismatching con-
ditions, caused by partial shading and short circuit failure of bypass
diodes. First, it was conducted to simulated when a short circuit
failure of bypass diode occurred in DC array using Matlab-Simulink.
Based on the simulation results, a mathematical model was derived
for a correlation of the reverse current flowing into the mis-
matching string, the number of parallel circuits in the array, and the
bypass diode failure. Then, a module that imitated a 100 kW scale of
real PV array was fabricated, and experiments were conducted to
analyze the electrical and thermal characteristics of the PV arrays
due to partial shading and bypass diode failure at outdoor. From the
simulation and experiment results, the reverse current did no flow
in partial shading, but the reverse current about 17A flowed in
bypass diode failure when the system was not working (5 parallel Fig. 1. IeV curves of a PV module due to the number of bypass diodes operating by
circuits and 1 bypass diode failure). In addition, due to massive partial shading.

2
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

circuit failure of bypass diode have not been analyzed. Hence, in


this section, it was investigated the correlation between fault
bypass diodes and PV array using Matlab-simulink. In order to
compare results between simulation and real field experiments, the
circuit was designed a lab-scale PV array. The electrical specifica-
tions of solar cell used in the lab-scale module apply equally in the
simulation, and are described in Table 1. The open voltage of solar
cell used in the experiment is similar to the operating voltage of a
bypass diode, so the bypass diode does not turn on. For this reason,
one module in the general PV array is equivalent to three solar cells
in a module of lab-scale PV array, which has one bypass diode
connected per three solar cells, as shown in Fig. 3.
The simulation was performed in the open circuit state of the PV
array due to inverter shutdown and it was assumed that only one of
parallel strings had a short circuit failure bypass diode. The envi-
ronment condition of simulation was assumed in STC conditions, in
which the irradiance is 1000 W/m2, and the temperature of PV
module is 25  C. The variables of the simulation set to increase the
number of parallel circuits from 2 to 5, and the number of fault
bypass diodes to 1 and 2. Under these conditions, a reverse current
flowing into the mismatching string and a current flowing through
the fault bypass diode were simulated.
The simulation results are summarized in Table 2. Both current
values increased as the number of parallel circuits increases from 1
to 5 and fault bypass diode from 1 to 2. A case of one fault bypass
Fig. 2. Schematic diagram of a PV module with a fault bypass diode. diode in one of two parallel circuits, the reverse current which
flowed into the mismatching string was 8.8A, and the current
flowing into the fault bypass diode was 18.24A. The other case of
the resistance. However, the voltage drops almost 0 V due to the
two fault bypass diodes in one of five parallel circuits, the reverse
micro resistance of the fault bypass diode. Thus, a fault bypass
current which flowed into mismatching string was 24.24A, and
diode drops the open voltage of PV module, and the voltage drop
the current flowing into the fault bypass diode was 33.02A. As a
increases as the number of fault bypass diodes. The current equa-
result of the simulation, the reverse current increased as the
tion of PV module including a fault bypass diode is represented as
number of parallel circuits and fault bypass diodes in PV array.
following Eq. (2).
However, it was confirmed that the increase value of the reverse
2 0  1 3 current and the fault diode current reduces due to the increase in
V=2N þ IRs  ID RD=2N the number of parallel circuits, and it affected both of currents, as
6 B C 7
I ¼ Isc  I0 4exp@ A  15 shown in Fig. 4(b). Despite these characteristics, the reverse current
nVth
increased as the number of fault bypass diodes and parallel circuit
  increased.
ðIsc IÞRD
V=2N þ IRs  2N
 (2)
Rsh 3.2. The mathematical model

If the inverter is operating normally, the current flowing into a


Fig. 5 represents an equivalent circuit of PV array with a short
fault bypass diode by the output current will not be large as in Eq.
circuit failure of bypass diode. It described correlation between a
(1). On the other hand, if the inverter is in a fault condition or
voltage drop that caused by a failure of bypass diode, increasing the
stopped, the output current becomes about 0 A, so that the short
number of parallel circuits in PV array and a reverse current. Where
circuit current of solar cell flows into the fault bypass diode, as
V1 and V2 are the voltage of string that has a fault bypass diode and
shown in Eq. (3).
the voltage of normal string, respectively. As the string which
ID ¼ Isc (3) include a fault bypass diode has a lower open voltage than normal
strings in PV array, which causes the potential difference between
In a typical PV module that consists of 60 cells or 72 cells, the PV strings. Therefore, this voltage mismatch between PV strings
open voltage of PV module due to a short circuit failure of bypass allows a reverse current to flow into a fault bypass diode.
diode is reduced by 1/3 per diode. This will lead a large voltage The current flowing into a fault bypass diode is the sum of two
difference between the PV strings. currents by Kirchhoff’s current law, one is the short circuit current
of the solar cell that connected with the fault bypass diode, and the
other is the sum of normal strings’ current (¼ mismatching cur-
3. Analysis of electrical characteristics on short circuit failure
rent). The short circuit current of solar cell Isc is a constant, so the
of bypass diodes in PV array
value of current flowing to the fault bypass diode from Eq. (4) is
determined by the number of normal strings connected in parallel.
3.1. Electrical simulation by using matlab-simulink
ID ¼ Istring þ Isc (4)
The previous results have shown that the reverse current
flowing into the mismatching string increases as the number of The total voltage of the fault PV string V1 can express a sum of
fault bypass diodes increases in a real operating PV system. How- VD , the voltage of fault bypass diode, and V1 VD , the voltage of
ever, there is any electrical properties of PV array caused by a short normal solar cell as expressed in Eq. (5).
3
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Table 1
Specification of mono c-Si solar cell used in simulation and experiment.

Type Isc [A] Imax [A] Voc [V] Vmax [V] Pmax [W] FF [%] Rs [U] Rsh [U] Efficiency [%]

Mono 9.43 8.99 0.64 0.54 4.86 80.29 0.006 7.14 20.11

Fig. 3. (a) Schematic of a general PV array and (b) schematic of a lab-scale designed PV array.

Table 2
The reverse current and fault diode current due to each number of fault bypass diode and string by simulation.

Number of Strings 2 3 4 5

Number of Fault diodes 1 2 1 2 1 2 1 2


Reverse Current [A] 8.8 9.3 14.32 18.01 16.73 22.46 17.9 24.24
Fault Diode Current [A] 18.24 18.75 23.76 27.42 26.16 31.62 27.32 33.02

Fig. 4. The current by the number of fault bypass diodes and strings. (a) The reverse current (b) The fault diode current.

because the resistance of a fault bypass diode is minute. From these


conditions, the voltage of the fault string V1 and the voltage of
V1 ¼ VD þ ðV1  VD Þ (5) normal string V2 can be expressed as Eq. (6).
Each circuit connected in a parallel circuit tries to maintain the
same voltage, therefore, VD has a voltage drop equal to the sum of
V1 ¼ V2 (6)
normal voltage of solar cell connected to the fault bypass diode. In
addition, a large current must flow for voltage drop in normal state If the current does not flow into the shunt resistance of the solar
4
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Fig. 5. Equivalent circuit of PV array with a short circuit failure of one bypass diode.

cell, as the PV array is an open state due to the fault status of bypass diodes and parallel circuits in the PV array. Notably, the
inverter, V1 and V2 are represented by Eq. (7) and Eq. (8), number of fault bypass diodes is a major factor to increase a reverse
respectively. current.

V1 ¼ VD þ ðV1  VD Þ ¼ aRD ID þ ðN  MÞVd1 þ ðN  MÞIstring Rs


(7)

4. Analysis of thermal characteristics on partial shading and


Istring
V2 ¼ NVd2  N Rs (8) short circuit failure of bypass diodes
NP
In the previous section, a reverse current of PV array caused by
where Vd1 is the diode voltage of solar cell in the mismatching short circuit failure bypass diode is simulated using Matlab-
string, Vd2 is the diode voltage of solar cell in normal string, Rs is the Simulink following the number of parallel circuits. Thus, the elec-
series resistance of solar cell, ais the number of short circuit failure trical characteristics of PV array was analyzed by a mathematical
bypass diodes, N is the solar cells connected with normal bypass model which is derived from simulation results. In this section,
diodes, M is the solar cells connected with fault bypass diodes, and experiments were conducted to analyze the electrical and thermal
NP is the number of parallel circuits, respectively. The reverse cur- characteristics of voltage mismatch on PV array due to partial
rent of a mismatching string caused by short circuit failure of shading and short circuit failure of bypass diode at real field con-
bypass diodes is represented by solving Eq. (6) e (9). dition. For experiments, a module was fabricated as same as the PV
array circuit used in simulation, as shown in Fig. 3 (b). The electrical
Istring
aRD ID þ ðN  MÞVd1 þ ðN  MÞIstring Rs ¼ NVd2  N Rs (9) parameters for each string of lab-scale PV array are summarized in
NP Table 3. They were measured with a solar simulator under STC
conditions. The open voltage and maximum voltage for each string
MVd1  aRD Isc  NVd1 þ NVd2 are the same, and the maximum power standard deviation is
Istring ¼ (10)
aRD þ NRs  MRs þ NR s 0.16 W. Therefore, there will not be mismatching between strings
NP
under normal condition. The voltage mismatch conditions are
Eq. (10) represents a model of reverse current flowing into the partial shading and a short circuit failure of bypass diode, and DC
mismatching string which is derived from the equivalent circuit. Electronic Load (IT8514Be500V/60A/1200W) was used to imitate
The model shows that the numerator and denominator are related the operation and stop conditions of inverter. Environmental data
to voltage and resistance, respectively. Where NP within denomi- (irradiance, ambient temperature) were measured for the analysis
nator and Istring are proportional relation in large point of view, but of thermal characteristics in each condition, and the surface tem-
Rs and RD are very little, therefore, increasing of Istring by NP does perature of PV module and bypass diode was measured by using a
not increase proportionally. Additionally, where NVd1 and NVd2 thermographic camera (FLIR A300). All thermographic images were
within numerator are offset by an equivalent level of value, and the taken with the camera’s default emissivity of 0.92. Then, an output
value of aRD Isc does not significant effect on Istring because the value current and a diode current were measured by using a power
of RD is very little. On the other hand, M and Istring are proportional, quality analyzer (DEWE-2600). The tilt and orientation of the PV
where M is the number of solar cells connected to fault bypass module were 30 and the south, respectively. The test bed (36.38oN,
diode, Istring increases significantly as M increases. Consequently, it 127.37oE) was established, as shown in Fig. 6. The measuring
was verified from the derived mathematical model that the reverse equipment and sensors used in the experiment are shown in
current is proportional to the number of short circuit failure of Table .4.
5
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Table 3
Characteristics of each string in the test PV array under STC.

1st String 2nd String 3rd String 4th String 5th String

Maximum Power [W] 38.79 38.65 38.94 39.03 38.72


Maximum Power Point Voltage [V] 4.5 4.4 4.4 4.4 4.4
Maximum Power Point Current [A] 8.68 8.84 8.9 8.92 8.87
Open Circuit Voltage [V] 5.3 5.3 5.3 5.3 5.3
Short Circuit Current [A] 9.33 9.33 9.47 9.55 9.53

Fig. 6. Test bed for measuring thermal characteristics of a lab-scale PV array.

4.1. The operation of a bypass diode by partial shading was confirmed that no reverse current flows due to partial shading
regardless of the on/off condition of electronic load. However, there
The Field experiment was conducted to confirm the thermal was a difference of 15e23  C the surface temperature of a bypass
characteristics of the bypass diode operation by partial shading on diode (Point 1) according to on/off condition of electric load. The
the PV array. The module (a lab-scale real PV array) installed on the reason for this is that when the electronic load is operating, an
test bed, as shown in Fig. 6. For partial shading condition, the third electrical circuit is conducted and mismatch current (¼current
solar cell from the bottom of the leftmost string was fully shaded by difference between normal solar cell and partial shading solar cell)
attached black masking tapes with excellent light blocking rate. flows to a bypass diode. As a result, the temperature of the bypass
However, since the absolute temperature value may vary due to diode connected to partial shaded solar cells increases in the
these characteristics, the solar cell with simulated partial shading operation of system. Meanwhile, it was verified that there was no
was exclude from the temperature analysis. The current and surface reverse current flowing by voltage mismatch between strings
temperature of the module were measured according to the on/off because the open circuit voltage of solar cell did not drop under
condition of electronic load. At the time (March/31/2020) of partial shading condition.
experiment, the irradiance and the ambient temperature
780e1080 W/m2 and 17e20  C when electronic load was operating,
and 910e1010 W/m2 and 17e19  C when electronic load was not 4.2. The short circuit failure of bypass diodes
operating. Fig. 7(a) and (b) show the thermographic image of a lab-
scale PV array under partial shading condition while the electronic Subsequently, an experiment was conducted on the test bed of
load was on and off, respectively. The point 1 is the surface tem- Fig. 6, as same as a section 4.1, to confirm the thermal character-
perature of the bypass diode, and the point 2 is the surface tem- istics on PV array, when a voltage mismatch caused by a short
perature of the normal module in the string with partial shading. circuit failure of bypass diode. For an experiment, a bypass diode
Point 3, 4, 5, and 6 are the surface temperature of the normal solar (one of three) in the module, in which connected with solar cells in
cells in the normal strings. When the electronic load was operating, the leftmost string, was replaced by a faulted bypass diode. The
the output current which is flowing into the electronic load was short circuit failure bypass diode that used for an experiment was
measured 42e43A, and there was no reverse current flowed toward artificially damaged by applying a voltage higher than the reverse
the partial shading string. The surface temperature of solar cells breakdown voltage. The current and surface temperature of the
(Point 2e6) was 32e40  C and that of a bypass diode was 45e60  C, module were measured respectively in considering the on/off
as shown in Fig. 8(a). When the electronic load was not working, condition of electronic load. At the time (April/3/2020) of experi-
the reverse current did not flow to the string with partial shading. ment, the irradiance and the ambient temperature 1045e1075 W/
The surface temperature of solar cells (Point 2e6) was 37e45  C m2 and 17e19  C when electronic load was operating, and
and that of a bypass diode was 30e37  C, as shown in Fig. 8(b). 970e1050 W/m2 and 18e20  C when electronic load was not
Although there is a difference in temperature values of solar cells, it operating. When the electronic load was operating, it was
measured that the output current which is flowing into the
6
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Table 4
Specification of the equipment used in the experiment.

DC Electronic Load (IT8514Be500V/60A/1200W)

Output Rating (0e40  C) Voltage 0e500V


Current 1 mAe60A
Power 1200W
CV Mode Range Accuracy Resolution
Regulation 0.1e18V ±(0.05% þ 0.02%FS) 1 mV
Power Quality analyzer (DEWE-2600)

Channel 16
HSI-HV (Voltage) Range 20Ve1400V
Accuracy 20Ve50V (DC) ±0.05% of reading ± 60 mV
100Ve1400V (DC) ±0.05% of reading ± 0.05 range
HSI-LV (Current) Range 10 mV to 50V
Accuracy 10 mVe100 mV (DC) ±0.02% of reading ± 60uV
2.5V (DC) ±0.02% of reading ± 0.1 of range
200 mV to 50V (DC) ±0.02% of reading ± 0.05 of range
Data throughput 80 MS/s
Resolution 16-bit
Sampling rate Max. 500 kS/s per channel
Thermographic Camera (FLIR A300)

Field of view 25 (H) x 18.8 (V)


Focal Length 18 mm
Spectral range 7.5e13mm
IR resolution 16bit 320  240 pixels
Object temperature range 20  Ce120  C
0  Ce350  C
Accuracy ±2  C or ±2% of reading
Pyranometer (KIPP & ZONEN, CMP 6)

Classification to ISO 9060:2018 Spectrally Flat Class B


Sensitivity 5e20mV /W/m2
Impedance 20e200 U
Expected output range (0e1500 W/m2 ) 0e30 mV
Maximum operational irradiance 2000 W/m2
Temperature transmitter (Delta OHM HD9009TR)

Measuring range 40 ~ þ80  C


Accuracy ±0.15  C ± 0.1% of measurement
Output signal 40  C ¼ 0.00 Vdc
þ80  C ¼ 1.00 Vdc

Fig. 7. Thermographic images of a lab-scale PV array with partial shading while the electronic load was (a) operating and (b) not operating.

electronic load was 45.4A, a current flowing into the fault bypass operating, a reverse current did not flow to the mismatching string.
diode was about 2.3A, and the output current of mismatching string On the other case, when the electronic load was not working, it was
was about 7A, as shown in Fig. 9(a). Even if the voltage drop caused measured the reverse current was about 17A, a current which
by a short failure of bypass diode, when the electronic load was flowed from solar cells connected with a fault bypass diode was

7
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Fig. 8. Surface temperature at each point in a lab-scale PV array while the electronic load was (a) operating and (b) not operating.

Fig. 9. Measured current of a lab-scale PV array with fault bypass diode while the electronic load was (a) operating and (b) not operating.

about 9A, and a current flowing through the fault bypass diode was affect the temperature increase of a bypass diode and solar cells.
about 26A, as shown in Fig. 9(b). If the electronic load is not Even when the electronic load was not operating, the temperature
operating, a short circuit is formed in the solar cell connected with a at point 3, 4, 5, and 6 was 36e39  C as shown in Fig. 11(b). It was at a
fault bypass diode. Therefore, the sum of short circuit current of similar level to when electronic load was operating. However, it
solar cells and a reverse current, caused by potential difference was confirmed that a large current which is the sum of a short
between strings, flows into a fault bypass diode. As early circuit current of solar cells and a reverse current flowed to a fault
mentioned, outdoor experiments and simulation were conducted bypass diode, then the surface temperature of fault bypass diode
on the same electric circuit of a lab-scale real PV array. From the was measured about 145  C, as expressed in Fig. 12(a). The most
experiment results, the reverse current was measured about 17A, remarkable thing is a significant current (about 26A) flowed
and the simulation result was 17.9A, which this shows a similar continuously into a fault bypass diode, so that a high temperature
trend. Furthermore, the current flowing to the fault bypass diode (about 145  C) occurred 30 min after the start of experiment. It led
also showed the similar result with simulation; a simulation result to that the appearance of fault diode was completely deformed and
was 27.32A and an experimental result was 26A. The simulation the junction box was also melted, as shown in Fig. 12(b). Further-
and experimental results expressed the same trend, and the ther- more, a reverse current flowed to the solar cells connected with
mal characteristics of the PV strings will change due to the reverse normal bypass diodes in the fault string, and the temperature of
current. corresponding solar cells was 18  C higher than other solar cells.
Fig. 10(a) and (b) show the thermographic images of a lab-scale The thermographic image, in Fig. 10(b), exhibits that the current
PV array with a short circuit failure of bypass diode while the due to the voltage mismatch was flowing through the fault bypass
electronic load was on and off, respectively. The point 1 is the diode (Point 1) to the solar cells (Point 2) that connected to the
surface temperature of the bypass diode, and the point 2 is the normal bypass diodes. This result reflected well the simulation
surface temperature of the normal solar cell in the string with a results and the theoretical analysis in Section 3. Consequently, it
fault bypass diode. Point 3, 4, 5, and 6 are the surface temperature was verified that the operating temperature of solar cells elevated
of the normal solar cell in the normal strings. When the electronic as a reverse current flowed in the solar cells during normal oper-
load was operating, the temperature difference at every point was ation, thus, the surface temperature of the solar cell increased. If a
about 5  C, as shown in Fig. 11(a). Although the mismatch current of reverse current flows through the mismatching string continuously
about 2.3A due to a fault bypass diode, this did not significantly due to such a phenomenon in a real PV power plant, the heating

8
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Fig. 10. Thermographic images of a lab-scale PV array with fault bypass diode while the electronic load was (a) operating and (b) not operating.

Fig. 11. Surface temperatures of lab-scale PV array with fault bypass while the electrical load was (a) operating and (b) not operating.

Fig. 12. (a) Surface temperatures of fault bypass diode and (b) burn-out bypass diode by massive reverse current.

occurs in the normal operating PV modules, which causes a 61215:2005, there is an equation to calculate the junction tem-
decrease in the total power generation of the PV system. perature of diode from the measured junction box case tempera-
According to the bypass diode thermal test of KS C IEC ture [32]. The maximum surface temperature of fault bypass diode

9
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

measured with a thermographic camera was 145  C, but the actual the reverse current cannot be blocked because of a failure of
junction temperature may be higher. fuse, a fault bypass diode may cause fire accidents.
4) This study simulated a 100 kW scale of PV array, but, the pos-
Tj ¼ Tcase þ RTHjc $UD $ID (11) sibility of reverse current accidents caused by a short circuit
failure of bypass diode has increased according to the trend of
where Tj is the junction temperature of diode, Tcase is the measured high efficiency of PV module and large capacity of PV power
temperature of junction box case, RTHjc is typical thermal resistance plants. In order to secure stable performance of the PV power
junction to lead (at the case), UD is diode voltage, ID is diode cur- plants, it is necessary to monitor a failure of the bypass diodes
rent, respectively. The values of each variable are Tcase : 145 C, and fuses, and system diagnosis is required periodically to
RTHjc : 4  C=W, UD : 1:564V, ID : 26:71A, so the actual junction prevent system output loss and accidents. Further study aims at
temperature calculated through Eq. (11) is estimated to be 312  C. data process technology using Big data or AI for detecting fault
Consequently, a massive mismatching current flowed that caused bypass diodes.
by a short circuit failure of bypass diode, which occurred a serious
heat on the diode. Thus, it was verified that a possibility of irrep-
arable damage to PV module may occur due to serious deformation Credit author statement
of the diode and the junction box.
Chung Geun Lee: Investigation, Data curation, Writing e original
draft Woo Gyun Shin: Conceptualization, Software, Validation,
5. Conclusions Visualization Jong Rok Lim: Methodology, Resources Gi Hwan
Kang: Methodology, Supervision Young Chul Ju: Data curation,
In this paper, a study was conducted to confirm the electrical Resources Hye Mi Hwang: Software, Data curation Hyo Sik Chang:
and thermal characteristics of PV array caused by voltage mismatch Methodology, Visualization, Suk Whan Ko: Conceptualization,
between strings due to a short circuit failure of bypass diode on PV Validation, Supervision, Writing e review & editing
module. Simulation was performed to analyze the electrical char-
acteristics of the correlation between the fault bypass diode and PV Declaration of competing interest
array. It was found out that a mismatching current due to a fault
bypass diode, when the PV system was stopped, is proportional to The authors declare that they have no known competing
the number of parallel circuits in the PV array, and is considerably financial interests or personal relationships that could have
increased by the number of fault bypass diodes. Experiments at appeared to influence the work reported in this paper.
outdoor conditions were performed to analyze the electrical and
thermal characteristics of each voltage mismatch conditions in a Acknowledgements
lab-scale PV array module that mimics a real PV array of 100 kW. In
a case of bypass diode operation due to partial shading, the mis- This work was supported by a grant from the Renewable Energy
matching current (¼reverse current) did not flowed, and only the of Korea Institute of Energy Technology Evaluation and Planning
surface temperature of the bypass diode connected with a fully (KETEP) funded by the Korean Ministry of Trade, Industry, and
shaded solar cell was increased in an inverter is working. When the Energy (Project No: 20183020010990, 20183010013960).
inverter was operating in case of a short circuit failure of bypass
diode, a reverse current that caused by voltage drop did not flow References
into a fault string, also the surface temperature did not change
significantly. However, when the inverter stopped, a significant [1] Serban E, Ordonez M, Pondiche C. DC-bus voltage range extension in 1500 v
photovoltaic inverters. IEEE J Emerg Sel Top Power Electron 2015;3:901e17.
mismatching current (about 26A) flowed into the fault bypass
https://doi.org/10.1109/JESTPE.2015.2445735.
diode that generates a high surface temperature of 145  C to deform [2] Yan C, Xu D. Design study of MW photovoltaic inverter. In: 2018 IEEE Int
the diode and junction box. The results are summarized as follows. power electron appl Conf expo (PEAC); 2018. p. 1e6. https://doi.org/10.1109/
PEAC.2018.8590642. Shenzhen.
[3] M€ aki A, Valkealahti S. Power losses in long string and parallel-connected short
1) When the voltage mismatch caused by a fully shaded solar cell, strings of series-connected silicon-based photovoltaic modules due to partial
regardless of whether the inverter is operating or not, a reverse shading conditions. IEEE Trans Energy Convers 2012;27:173e83. https://
current between the PV strings did not flow and only the tem- doi.org/10.1109/TEC.2011.2175928.
[4] Wurster TS, Schubert MB. Mismatch loss in photovoltaic systems. Sol Energy
perature of the bypass diode connected with fully shaded solar 2014;105:505e11. https://doi.org/10.1016/j.solener.2014.04.014.
cell rose slightly. [5] Lappalainen K, Valkealahti S. Photovoltaic mismatch losses caused by moving
2) On the other hand, a short circuit failure of bypass diode created clouds. Sol Energy 2017;158:455e61. https://doi.org/10.1016/
j.solener.2017.10.001.
electrical and thermal problems in a PV array. When the inverter [6] Lobera DT, Valkealahti S. Mismatch losses in PV power generators caused by
was operating, a reverse current did not flow. However, when partial shading due to clouds. In: 2013 4th IEEE Int symp power electron
the inverter was off, a significant reverse current generated a distrib gener syst PEDG 2013 - Conf Proc; 2013. https://doi.org/10.1109/
PEDG.2013.6785587.
high heat and deformed a fault bypass diode. Moreover, the [7] Vargas JP, Goss B, Gottschalg R. Large scale PV systems under non-uniform and
operating temperature of solar cells that connected to the fault conditions. Sol Energy 2015;116:303e13. https://doi.org/10.1016/
normal bypass diodes among a fault string elevated about 18  C j.solener.2015.03.041.
[8] Fahrenbruch SA. Solar bypass diodes: Then and now. A PV Management
than other solar cells. Magazine 2010.
3) In a real PV system, there are fuses for blocking overcurrent [9] Ishikura N, Okamoto T, Nanno I, Hamada T, Oke S, Fujii M. Simulation analysis
installed at the (þ) and () terminals of each string. However, of really occurred accident caused by short circuit failure of blocking diode
and bypass circuit in the photovoltaics system. In: 7th Int. IEEE Conf. Renew.
when a certain fuse is operated by overcurrent, the corre-
Energy Res. Appl. ICRERA 2018, vol. 5. IEEE; 2018. p. 533e6. https://doi.org/
sponding PV string becomes an open circuit to result in overall 10.1109/ICRERA.2018.8566896.
system output losses. On the contrary, if a reverse current below [10] Posbic J, Rhee E, Amin D. High temperature reverse by-pass diodes bias and
the fuse current rating flows so the fuse does not operate, it may failures. 2013. 2013, https://www.energy.gov/sites/prod/files/2014/01/f7/
pvmrw13_ps3_memc_posbic.pdf.
create heat losses in normal PV modules of the fault string [11] Shiradkar NS, Schneller E, Dhere NG, Gade V. Predicting thermal runaway in
which may lead degradation of PV modules. In the worst case, if bypass diodes in photovoltaic modules. In: 2014 IEEE 40th Photovolt. Spec.

10
C.G. Lee, W.G. Shin, J.R. Lim et al. Energy 218 (2021) 119480

Conf. PVSC. Institute of Electrical and Electronics Engineers Inc.; 2014. scenarios. Energy 2017;127:438e53. https://doi.org/10.1016/
p. 3585e8. https://doi.org/10.1109/PVSC.2014.6924881. 2014. j.energy.2017.03.139.
[12] Shin W-G, Jung T-H, Go S-H, Ju Y-C, Chang H-S, Kang G-H. Analysis on thermal [23] Krishna GS, Moger T. Improved Su-Do-Ku reconfiguration techique for total-
& electrical characteristics variation of PV module with damaged bypass di- cross-tied PV array to enhance maximum power under partial shading con-
odes. J Korean Sol Energy Soc 2015;35:67e75. https://doi.org/10.7836/ ditions. Renew Sustain Energy Rev 2019;109:333e48.
kses.2015.35.4.067. [24] Fathy A. Butterfly optimization algorithm based methodology for enhancing
[13] Shin WG, Ko SW, Song HJ, Ju YC, Hwang HM, Kang GH. Origin of bypass diode the shaded photovoltaic array extracted power via reconfiguration process.
fault in c-Si photovoltaic modules: leakage current under high surrounding Energy Convers Manag 2020;220:1e21.
temperature. Energies 2018;11. https://doi.org/10.3390/en11092416. [25] Ghosh S, Yadav VK, Mukherjee V. Evaluation of cumulative impact of partial
[14] Ko S-W, Ju Y-C, So J-H, Hwang H-M, Jung Y-S, Kang G-H. The characteristics of shading and aerosols on different PV array topologies through combined
PV module under the partial shading condition and with a failure of bypass Shannon’s entropy and DEA. Energy 2018;144:765e75. https://doi.org/
diode with short. J Korean Sol Energy Soc 2016;36:41e7. https://doi.org/ 10.1016/j.energy.2017.12.040.
10.7836/kses.2016.36.4.041. [26] Tsanakas JA, Ha L, Buerhop C. Faults and infrared thermographic diagnosis in
[15] Deline C. Partially shaded operation of multi-string photovoltaic systems. Conf operating c-Si photovoltaic modules: a review of research and future chal-
Rec IEEE Photovolt Spec Conf 2010:394e9. https://doi.org/10.1109/ lenges. Renew Sustain Energy Rev 2016;62:695e709. https://doi.org/10.1016/
PVSC.2010.5616821. j.rser.2016.04.079.
[16] Deline C, Marion B, Granata J, Gonzalez S. A performance and economic [27] Haque A, Bharath KVS, Khan MA, Khan I, Jaffery ZA. fault diagnosis of
analysis of distributed power electronics in photovoltaic systems. 2011. photovoltaic modules. Energy Sci Eng 2019;7:622e44. https://doi.org/
https://doi.org/10.2172/1004490. 10.1002/ese3.255.
[17] Chaudhari YD. Compensation of mismatch in PV characteristics using DC-DC [28] Mellit A, Tina GM, Kalogirou SA. Fault detection and diagnosis methods for
converter. In: 2017 Int Conf power embed drive Control. (ICPEDC) IEEE; photovoltaic systems: a review. Renew Sustain Energy Rev 2018;91:1e17.
2017. p. 511e5. 2017:511e5. https://doi.org/10.1016/j.rser.2018.03.062.
[18] Refaat A, Osman MH, Korovkin NV. Current collector optimizer topology to [29] Silvestre S, Kichou S, Chouder A, Nofuentes G, Karatepe E. Analysis of current
extract maximum power from non-uniform aged PV array. Energy 2020;195. and voltage indicators in grid connected PV (photovoltaic) systems working in
https://doi.org/10.1016/j.energy.2020.116995. faulty and partial shading conditions. Energy 2015;86:42e50. https://doi.org/
[19] Satpathy PR, Jena S, Sharma R. Power enhancement from partially shaded 10.1016/j.energy.2015.03.123.
modules of solar PV arrays through various interconnections among modules. [30] Shin WG, Lim JR, Kang GH, Ju YC, Hwang HM, Ko SW. Current flow analysis of
Energy 2018;144:839e50. https://doi.org/10.1016/j.energy.2017.12.090. pv arrays under voltage mismatch conditions and an inverter failure. Appl Sci
[20] Bingo €
€l O, Ozkaya B. Analysis and comparison of different PV array configu- 2019;9. https://doi.org/10.3390/app9235163.
rations under partial shading conditions. Sol Energy 2018;160:336e43. [31] Ko SW, Ju YC, Hwang HM, So JH, Jung YS, Song HJ, et al. Electric and thermal
https://doi.org/10.1016/j.solener.2017.12.004. characteristics of photovoltaic modules under partial shading and with a
[21] Harrag A, Messalti S. Adaptive Ga-based reconifiguration of photovoltaic array damaged bypass diode. Energy 2017;128:232e43. https://doi.org/10.1016/
combating partial shading conditions. Neural Comput Appl 2018;30(4): j.energy.2017.04.030.
1145e70. [32] KS C IEC 61215. Crystalline silicon terrestrial photovoltaic(PV) modules e
[22] Bana S, Saini RP. Experimental investigation on power output of different design qualification and type approval n.d. 2005.
photovoltaic array configurations under uniform and partial shading

11

You might also like