Ductile Detailing Beam
Ductile Detailing Beam
Ductile Detailing Beam
PRESENTER-
MR. SOLMON SHARMA
FOUNDER
BEAS
DUCTILITY
NOTE:
Importance: Gives us enough time for rehabilitation of the material by
showing yielding in different forms.
DUCTILE DESIGN AND DUCTILE DETAILING is to be considered while
performing any analysis of structure.
Previously IS 456:2000 use to do the designing and IS 13920:1993 was
used for detailing.
IS 13920:2016 gives us provision for both DESINING AND DETAILING.
IMPORTANCE OF IS 13920:2016
Deformation
B/D>0.3
50% Ast
At any section of beam Ast should not be less than Ast/4 ( When we have
different Ast at both the supports, then we need to consider Maximum Ast).
Ast< Ast/4
Anchorage Length has to be beyond the interior face of the column.
90* Bend
SHEAR REINFORCEMENT
Only Vertical Links is to be provided. There should be no inclined links.
Minimum Dia of Link is 8mm.
Following are not calculated for design shear force:
a) Bent up bars b) Inclined Links c) Concrete
From the column face upto 2d distance, close spacing should be provided.
2d 2d
Close spacing : (S1)
a) D/4
b) 8 x (Smallest Longitudinal bar)
c) 100mm
s1 s2 s1
First spacing :
d
50mm max.
Spacing (S2)
2d 2d
>d/2
50mm maximum
6d hoop length is to be provided.
SPLICES ON LONGITUDNAL REINFORCEMENT:
Spacing of stirrups > 150mm
Lap ( in tension zone) < Ld.
Ld should be calculated considering larger dia bar.
Lap splice shall not be provided in: S> 150mm
Xxxxxx Xxxxxx
Xxxx Xxxx
Xxxxx xxxxxxxxxx xxxxxxxxxx Xxxxx
2d xxxxxxxxxx 2d
50mm maximum
Incase if maximum splices is to be provided we should go for welding or by using
mechanical couplers.