ZXDU58 W121

DC Power System
Product Description

Version: V4.0R02M01

ZTE CORPORATION
NO. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://ensupport.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright © 2012 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit ZTE technical support website http://ensupport.zte.com.cn to inquire related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History

Revision No. Revision Date Revision Reason

R1.1 2011-07-18 Add the section ”Documentation Guide”

R1.0 2011-05-05 First edition

Serial Number: SJ-20110308105524-006

Publishing Date: 2011-07-18 (R1.1)

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Contents
About this Manual .......................................................................................... I
Chapter 1 System Overview ...................................................................... 1-1
1.1 System Introduction............................................................................................ 1-1
1.2 System Features ................................................................................................ 1-1
1.3 Implementation Example .................................................................................... 1-2

Chapter 2 System Structure ...................................................................... 2-1


2.1 Overall System Structure .................................................................................... 2-1
2.2 Power Distribution Part ....................................................................................... 2-2
2.3 Temperature-Controlling Components.................................................................. 2-4
2.3.1 Fan Box................................................................................................... 2-4
2.3.2 Heating Unit for Battery Cabinet ................................................................ 2-4
2.4 Board and Signal Interface.................................................................................. 2-5
2.4.1 Layout and Functions of Boards ................................................................ 2-5
2.4.2 Interface of SIB Board .............................................................................. 2-6
2.4.3 Interfaces and DIP Switches of IP Board.................................................... 2-7
2.4.4 Interface and Indicator of SNMP Board ...................................................... 2-9
2.5 Slots Configuration ........................................................................................... 2-10
2.6 Requirements for Equipments to Be Embedded ..................................................2-11
2.7 Dimensions.......................................................................................................2-11

Chapter 3 System Modules........................................................................ 3-1


3.1 ZXD1500 Rectifier .............................................................................................. 3-1
3.1.1 Rectifier Components ............................................................................... 3-1
3.1.2 Rectifier Indicators.................................................................................... 3-1
3.1.3 Rectifier Specifications ............................................................................. 3-2
3.2 Monitoring Unit................................................................................................... 3-2
3.2.1 CSU Parts ............................................................................................... 3-2
3.2.2 CSU Indicators......................................................................................... 3-3
3.2.3 CSU Specifications................................................................................... 3-3
3.2.4 CSU Functions......................................................................................... 3-4
3.2.5 Monitoring Software ................................................................................. 3-4

Chapter 4 System Specifications.............................................................. 4-1


4.1 Technical Specifications...................................................................................... 4-1
4.1.1 Environment Specifications ....................................................................... 4-1
I

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


4.1.2 AC Distribution Specifications ................................................................... 4-1
4.1.3 DC Distribution Specifications ................................................................... 4-2
4.1.4 Other Specifications ................................................................................. 4-2
4.2 Compliance Standards ....................................................................................... 4-3

Appendix A Electrical Connection Diagram ........................................... A-1


Appendix B Documentation Guide .......................................................... B-1
Glossary .......................................................................................................... I

II

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


About this Manual
Purpose
This manual applies to the ZXDU58 W121 (V4.0R02M01) DC Power System. ZXDU58
W121 is an outdoor DC power system and provides power for -48 V communication
equipment. This manual describes the system structure, characteristics and application.

Intended Audience
This manual is intended for:
l Planning engineer
l Maintenance engineer

What Is in This Manual


This manual contains the following chapters/appendixes:

Chapter/Appendix Summary

Chapter 1, System Overview Introduces the system, the implementation example and
describes the system features.

Chapter 2, System Structure Describes the overall structure, power distribution parts,
temperature-controlling components, signal interface board,
slots configuration, requirements for embedded equipments
and dimensions.

Chapter 3, System Modules Describes the ZXD1500 rectifier and the monitoring unit.

Chapter 4, System Specifications Provides the technical specifications and compliant standards
of the system.

Appendix A, Electrical Connection Provides the electrical connection diagram of the system.
Diagram

Appendix B, Documentation Guide Lists the manual suite of the system.

Conventions
This document uses the following typographical conventions.

Typeface Meaning

Italics Refers to other related manuals and documents.

Bold Menus, menu options, function names, input fields, option button names, check
boxes, drop-down lists, dialog box names, window names, parameters and
commands.

CAPS Keys on the keyboard, buttons on screens and company name.

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Typeface Meaning

Danger: Indicates an imminently hazardous situation, which if not avoided,


will result in death or serious injury.

Warning: Indicates a hazard that, if not avoided, could result in serious injuries,
equipment damages or interruptions of major services.

Caution: Indicates a potential hazard that, if not avoided, could result in


moderate injuries, equipment damages or partial service interruption.

Note: Provides additional information about a certain topic.

II

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 1
System Overview
Table of Contents
System Introduction....................................................................................................1-1
System Features ........................................................................................................1-1
Implementation Example ............................................................................................1-2

1.1 System Introduction


ZXDU58 W121 is an outdoor power supply equipment. It can power mobile base stations,
access network equipment, remote switch offices, transmission equipment, ground
satellite transceiver stations, and microwave communication devices.
In full configuration, the ZXDU58 W121 system is equipped with four ZXD1500 rectifiers,
which form a power system with 120 A rated output.

Figure 1-1 ZXDU58 W121

1.2 System Features


The ZXDU58 W121 system has the following features:

l A wide range of input phase voltage (80 VAC - 300 VAC) makes the system suitable
for areas with unstable voltage.

1-1

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

l Integrating the power distribution, rectifiers, monitoring unit and batteries in a single
cabinet, and saving installation space.
l Hot-pluggable rectifiers, and convenient for installation and maintenance.
l Intelligent monitoring unit.
l With fans for heat dissipation.
l High reliability with MTBF ≥ 2.2 × 105 h.
l The ZXDU58 W121 system supports multiple networking modes, such as RS232,
RS485 and IP/SNMP (optional).

1.3 Implementation Example


The ZXDU58 W121 is applied outdoors. The communication equipments and the batteries
can be installed into the cabinet. Figure 1-2 shows a typical application to outdoor BTS
station.

Figure 1-2 Implementation Example

1-2

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 2
System Structure
Table of Contents
Overall System Structure............................................................................................2-1
Power Distribution Part...............................................................................................2-2
Temperature-Controlling Components ........................................................................2-4
Board and Signal Interface .........................................................................................2-5
Slots Configuration ...................................................................................................2-10
Requirements for Equipments to Be Embedded .......................................................2-11
Dimensions ..............................................................................................................2-11

2.1 Overall System Structure


ZXDU58 W121 cabinet is composed of two parts. The upper part is the power cabinet. The
lower part is the battery cabinet. The structure of the ZXDU58 W121 cabinet is illustrated
in Figure 2-1. Figure 2-2 shows the power equipment unit of the system. Refer to Table
2-1 for the descriptions of the parts.

Figure 2-1 Overall System Structure

1. Fan box 2. Communication equipment 3. Communication box


space 4. Power equipment unit

2-1

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

5. Batteries 6. Air vent 1 7. Air vent 2

Figure 2-2 Power Equipment Unit

1. ZXD1500 rectifiers 2. Power distribution part 3. Monitoring unit

Table 2-1 ZXDU58 W121 Part Description

Part Description

Fan box For air ventilation of the equipment cabinet by the fans

Communication l 19–inch in width, 8U in height


equipment space l For the installation of embedded communication equipments

Communication box l 1U in height


l Stores the various communication boards of the system such as SIB

Power equipment unit Integrated with the rectifiers, the monitoring unit and power distribution
unit

ZXD1500 Rectifiers Converts AC to stable DC power

Power distribution part Provides electrical distribution through AC and DC branches and
connection terminals (refer to “Power Distribution Part” section of this
manual)

Monitoring unit Provides management of the power distribution parts (AC and DC),
rectifiers and batteries

Batteries Provides DC power redundancy when AC power is off

Air vent 1 For the air ventilation of the power cabinet

Air vent 2 l For the air ventilation of the battery cabinet


l The fans are optional

2.2 Power Distribution Part


The power distribution part is composed of AC and DC parts of the system and provides
the electrical connection and distribution. Figure 2-3 illustrates the distribution part layout

2-2

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 2 System Structure

and Figure 2-4 shows the terminal connection. Note that the AC input maybe configured
for either three-phase or single-phase system by modifying the AC input breaker. Refer to
Table 2-2 for the descriptions of the parts.

Figure 2-3 Power Distribution Part

1. AC input breaker 4. DC output breakers 7. AC output socket & breaker


2. AC output breaker 5. Battery breakers 8. Working ground busbar
3. AC SPD 6. DC SPD

Figure 2-4 Terminal Connection

Table 2-2 ZXDU58 W121 Part description

Part Description

AC input breaker l Turns on/off AC input


l Optional configuration: 80 A/2P breaker and 63 A/3P breaker

AC output breaker Turns on/off AC auxiliary output (16 A)

AC SPD Provides AC surge protection

DC output breakers l Provides DC output power to load with overload protection


l Default configuration: LLVD1: 2*63 A + 2*32 A; LLVD2: 2*20 A +
2*16 A
l DC output configuration can be customized by the user

Battery breakers l 2*100 A


l Provides battery connection to the system

DC SPD Provides DC surge protection

2-3

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Part Description

AC output socket & l Optional configuration


breaker l 10 A socket + 16 A breaker
l Located on the left wall of the cabinet
l The breaker is used to turn on/off the socket power supply

Working ground busbar l GND for DC output and battery input


l Located on the right wall of the cabinet

2.3 Temperature-Controlling Components


2.3.1 Fan Box
The fan box is responsible of air circulation and ventilation. Two fans are installed inside it.
Figure 2-5 shows the structure of fan box.

Figure 2-5 Structure of fan box

2.3.2 Heating Unit for Battery Cabinet


The heating unit for battery cabinet includes the heating pads and the heat-insulation
material. It is an optional configuration and is recommended to use in cold areas.
The heating pads are used to raise the temperature inside the cabinet. They are stuck on
the surface of battery trays.
The heat-insulation material is used to reduce the heat loss from inside to outside. It is
stuck on the inner surface of the cabinet.
Figure 2-6 shows the heating unit.

2-4

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 2 System Structure

Figure 2-6 Heating Unit for Battery Cabinet

1. Heating pads 2. Battery tray 3. Heat-insulation material

2.4 Board and Signal Interface


2.4.1 Layout and Functions of Boards
Figure 2-7 shows the boards layout in the communication box, and Table 2-3 describes
their functions.

Figure 2-7 Boards Layout

1. Voltage transmission board 3. Modem power board (MPB) 5. SNMP network interface
(TRB) 4. IP network interface board board (SNMP)
2. Fan control board (FCTL) (IP) 6. Signal interface board (SIB)

Table 2-3 Functions of Boards

Board Function

Voltage transmission board (TRB) Provides AC voltage sampling signals for the monitoring unit.

Fan control board (FCTL) Controls the internal and external heat circulation fans of the
equipment cabinet.

Modem power board (MPB) Optional, used to provide 12 VDC power for the IP or SNMP
board.

IP network interface board (IP) l Optional, used to remote networking.


l IP and SNMP do not exist at the same time.

2-5

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Board Function

SNMP network interface board l Optional, used to remote networking.


(SNMP) l IP and SNMP do not exist at the same time.

Signal interface board (SIB) Provides various signal interfaces, including battery
temperature detection interfaces, environment detection
interfaces and communication interfaces.

2.4.2 Interface of SIB Board


The Signal Interface Board (SIB) provides background communication interfaces and
supervision interfaces.
For the interfaces layout on SIB, see Figure 2-8.

For the interfaces description, Refer to Table 2-4.

Figure 2-8 SIB Board

• NC: Normal Close • NO: Normal Open • COM: Common

Table 2-4 Signal Interface

Interface Description Interface Description

X4 Battery 1 temperature X21 RS485 communication

X5 Battery 2 temperature X22 RS232 communication

X12 Temperature control X23 Flood alarm

X14 Input relays 1, 2, 3, 4 X24 Smoke alarm

X15 Output relays 1: for CSU fault X25 Ambient temperature


Output relays 2: A1, supporting alarm
customization

2-6

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 2 System Structure

Interface Description Interface Description

X16 Output relays 3: A2, supporting alarm X26 Intrusion alarm


customization
Output relays 4: A3, supporting alarm
customization

X17 Output relays 5: A4, supporting alarm - -


customization
Output relays 6: A5, supporting alarm
customization

2.4.3 Interfaces and DIP Switches of IP Board


The IP board interface is used for remote monitoring purpose in IP networks. It is provided
with RS232 interface and a standard network interface.

Note:
The IP board is an optional component that is installed according to the user requirement.

Interfaces
For the IP board interfaces, see Figure 2-9.

Figure 2-9 IP Board Interfaces

For the IP board interfaces description, refer to Table 2-5.

2-7

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Table 2-5 Interfaces Description

Inter- Pin No Signal Definition Interface Description


face

X1 1 GND Power socket with 12 VDC input voltage

2 +12V

X2 _ _ Standard JATG interface, used for downloading


applications.

X3 _ _ Standard network interface.

X4 1 RS485_B l In RS485 communication mode, X4 and the RS485


interface of the SIB board are interconnected
2 RS485_A
l Uses 2 standard RS485 interface signals
(RS485_A and RS485_B).

X6 2 RS232_RXD l Standard DB9 signal of the RS232 interface.


l In RS232 communication mode, X6 and the RS232
3 RS232_TXD
interface of the SIB board are interconnected.
5 RS232_GND
The RS232 interface and S2[4] DIP switch are
interconnected.

DIP Switches
For a description of the IP board Dual In-line Package (DIP) switches, refer to Table 2-6.

Table 2-6 IP Board-DIP Switches Description

DIP Description
Switch

S1 Jumper for reset (RST) signal.


use the S1[1] switch when downloading programs, as described below:
l OFF: When burning programs onto the MCU chip.
l ON: After finishing burning in programs.
The S1[1] should be turned off before downloading programs. Turn it on after the burning
process is successful.

S2 1. S2[1,2,3] is used to set the baud rate for communication between the IP board and
the CSU, as shown in Table 2-7.
2. The S2[4] switch is used to set the communication mode between the IP board and the
CSU: RS485 or RS232.
l ON: RS485 communication mode.
l OFF: RS232 communication mode.

S3 Used to set working mode of the RS232 port, as shown in Table 2-8.

2-8

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 2 System Structure

Table 2-7 IP Board-DIP Switch Baud Rate

S2[1] S2[2] S2[3] Baud rate

OFF ON OFF 9600 bps

ON ON OFF 4800 bps

OFF OFF ON 2400 bps

ON OFF ON 1200 bps

l The baud rate of two communication terminals should be consistent, otherwise the
communication will fail.
l The maximum baud rate supported by the CSU is 9600 bps.

Table 2-8 RS232 Port-DIP Switch Configuration

S3[1] S3[2] S3[3] S3[4] Description

ON ON OFF OFF When the RS232 interface and the SIB board are
interconnected, used in IP board in normal communication
working mode, making the communication between the IP
board and the SIB board more reliable.

OFF OFF ON ON Used in IP board parameters setting when the RS232


interface and a PC are interconnected.

2.4.4 Interface and Indicator of SNMP Board


For the SNMP board appearance, see Figure 2-10.

Figure 2-10 SNMP Board Appearance

• RESET: To recover to the


default IP address, press
RESET for three seconds.

2-9

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Interface Description
For a description of the interfaces on the SNMP board, refer to Table 2-9.

Table 2-9 SNMP Board Interface Description

Designation Description

+12V +12 VDC power input

RS232/RS485 RS232 and RS485 interface, to receive data from equipment at user end (It is a
Semi-duplex interface)

ETHERNET Adaptive 10/100M Ethernet interface

Indicator Description
For a description of the indicators on SNMP board, refer to Table 2-10.

Table 2-10 SNMP Board Indicator Description

Designation Description

PWR Lit Internal power is normal

Not lit Internal power is faulty

RXD Not lit RS232 interface is not connected


(It is not used to indicate RS485 interface connection)

Lit RS232 interface is connected


(It is not used to indicate RS485 interface connection)

Flashes RS232 or RS485 interface is receiving data

TXD Not lit The ZXDU58 W121 system does not transmit data

Flashes The ZXDU58 W121 system is transmitting data

2.5 Slots Configuration


The number of rectifiers for each of the phases should be identical in order to maintain
phase balance and favor good radiation. The distribution of the slots and phases of the
rectifiers are shown in Figure 2-11 and Figure 2-12.

Figure 2-11 Slots Configuration (Three-phase)

2-10

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 2 System Structure

Figure 2-12 Slots Configuration (Single-phase)

2.6 Requirements for Equipments to Be Embedded


Communication equipments can be embedded in the ZXDU58 W121 cabinet. The
equipments to be embedded must meet the following requirements:
l Total power consumption is not higher than 200 W.
l Adopts 19–inch standard equipment frame, with depth not exceeding 350 mm and
total height not exceeding 8 U.
l Total weight does not exceed 50 kg.

2.7 Dimensions
The dimensions of the ZXDU58 W121 cabinet are shown in Figure 2-13.

Figure 2-13 Cabinet Dimensions

• Unit: mm

The available battery installation space of each rack is shown in Table 2-11.

2-11

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Table 2-11 Available Battery Installation Space of Each Rack

Item Dimension

With heat-insulation material 330 mm × 540 mm × 540 mm (H × W × D)

Without heat-insulation material 330 mm × 540 mm × 560 mm (H × W × D)

2-12

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 3
System Modules
Table of Contents
ZXD1500 Rectifier ......................................................................................................3-1
Monitoring Unit ...........................................................................................................3-2

3.1 ZXD1500 Rectifier


3.1.1 Rectifier Components
The ZXD1500 rectifier converts AC to DC.

For the appearance and structure of the ZXD1500 rectifier, see Figure 3-1.

Figure 3-1 ZXD1500 Rectifier

1. Indicators 3. Handle 5. Input/Output Integrated


2. Grill 4. Stop Pin Socket

3.1.2 Rectifier Indicators


The indicators of the rectifier indicate the current operational status of the rectifier. For the
layout of the rectifier indicators, see Figure 3-2. For a description of the rectifier indicators,
refer to Table 3-1.

Figure 3-2 Layout of Rectifier Indicators

3-1

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Table 3-1 Rectifier Indicators

Indicator Label Status and Color Meaning

IN Lit (green) AC input power is normal.


(Input )

OUT Lit (green) DC output power is normal.


(Output)

CL Lit (yellow) Output current of the rectifier has reached its limit.
(Current limit)

ALM Lit (red) An alarm has occurred.


(Alarm)

Note:
When the rectifier is in sleep mode, only the IN indicator is lit.

3.1.3 Rectifier Specifications


For a description of the ZXD1500 specifications, refer to Table 3-2.

Table 3-2 ZXD1500 Rectifier Specifications

Item Specifications

AC input mode Single-phase, three-wire (L/N/PE)

AC input voltage Rated: 100 V AC - 240 V AC


Range: 80 V AC - 300 V AC
Input voltage variation affects the output power of the rectifier.

DC output voltage Rated output voltage: 53.5 V DC, range: 42 V DC to 58 V DC

3.2 Monitoring Unit


3.2.1 CSU Parts
The Centralized Supervision Unit (CSU) manages the power distribution unit, rectifiers and
batteries of the ZXDU58 W121 system.

For the CSU parts, see Figure 3-3.

3-2

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 3 System Modules

Figure 3-3 Centralized Supervision Unit

1. LCD 4. Buttons 7. Fastening screw


2. Indicators 5. Handle 8. (Rear) Interface
3. Reset button 6. Power switch

3.2.2 CSU Indicators


The indicators of the Centralized Supervision Unit (CSU) indicate the current operational
status of the CSU. For the layout of the CSU indicators, see Figure 3-4. For a description
of the CSU indicators, refer to Table 3-3.

Figure 3-4 CSU Indicators

Table 3-3 CSU Indicators

Indicator Label Status and Color Meaning

PWR Lit (green) Power is applied to the CSU.


Power

RUN Flashing (green) CSU is operating normally.


Run

EQU Lit (green) Battery equalized charge is in-process.


Charge equalization

COMM Flashing (yellow) CSU is communicating with the connected PC.


Communication

ALM Flashing (red) An alarm or fault has occurred.


Alarm

3.2.3 CSU Specifications


For a description of the CSU specifications, refer to Table 3-4.

3-3

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Table 3-4 CSU Specifications

Item Specifications

Power mode DC power

Operation interface LCD and buttons

Precision of AC voltage ±1%

Precision of the battery current and the output current of the system ±1%

Precision of the battery voltage and the output voltage of the system ±0.5%

Temperature precision ±5.4 ℉ (±3 ℃)

Humidity precision ±5%

Boolean value precision 100%

3.2.4 CSU Functions


CSU is the supervision center of the entire system, and responsible of managing AC
distribution, DC distribution, rectifiers and batteries.

l Collects the operational data and monitors the operation of the system.
l Provides alarm and necessary protection if the system is operating abnormally.
l Sends data to the background Supervision Center (SC) and receives the commands
from the SC. In this way, the system can be monitored remotely.

3.2.5 Monitoring Software


Software version: ZXDU B121-CSU (V2.20).
Users can perform the following operations through the CSU:
l Setting parameters
l Querying information, alarms and history records
l Managing operational modes, alarms, rectifiers and batteries
l Starting manual detection for maintenance

For details about using the CSU, refer to the ZXDU B121-CSU (SV2.20) Centralized
Supervision Unit Operation Guide.

3-4

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 4
System Specifications
Table of Contents
Technical Specifications .............................................................................................4-1
Compliance Standards ...............................................................................................4-3

4.1 Technical Specifications


4.1.1 Environment Specifications
The specifications for the environment of the equipment are described in Table 4-1.

Table 4-1 Environment Specifications

Item Specification

Operating temperature -20℃ to +50 ℃

Storage temperature -40℃ to +70℃

Relative humidity 10% to 90% (non-condensing); 40% to 60% recommended

Air pressure 70 kPa to 106 kPa

Other requirements l No conductive dusts or corrosive gases


l No explosion hazard, no shake or jolt
l Ground slope is no more than 5°

4.1.2 AC Distribution Specifications


The specifications for the AC power distribution of the system are described in Table 4-2.

Table 4-2 AC Power Distribution Specifications

Item Specification

AC input The AC input configuration can either be:


l Three-phase five-wire (L1/L2/L3/N/PE)
l Single-phase three-wire (L/N/PE)

AC input voltage Rated: 100 to 240 VAC


Range: 80 to 300 VAC
(Input voltage variation affects the output power of the rectifier)

AC input frequency 50/60 Hz

4-1

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Item Specification

AC input power factor ≥ 0.99 (with full load)

AC SPD l Class B, with discharging current≤120 kA


l Class C, with discharging current≤40 kA

4.1.3 DC Distribution Specifications


The specifications for the DC power distribution of the system are described in Table 4-3.

Table 4-3 DC Power Distribution Specifications

Item Specification

DC output voltage l Rated output voltage: -53.5 VDC


l Range: -42 VDC to -58 VDC

Rated DC output current 120 A (full configuration)

Rated DC output power 6000 W (full configuration)

Maximum DC output power 7660 W (full configuration)

Battery input breakers 2*100 A MCBs

Source effect ≤ 0.1%

Load effect ≤ 0.5%

Regulated voltage precision ≤ 0.6%

Weighted noise voltage < 1 mV

Peak-peak noise voltage ≤ 100 mV

Broad frequency noise voltage ≤ 30 mV (3.4 kHz~150 kHz)


≤ 20 mV (0.15 MHz~30 MHz)

Discrete frequency noise voltage ≤ 5 mV (3.4 kHz~150 kHz)


≤ 3 mV (150 kHz~200 kHz)
≤ 2 mV (200 kHz~500 kHz)
≤ 1 mV (0.5 MHz~30 MHz)

DC voltage drop < 500 mV

4.1.4 Other Specifications


Other specifications are described in Table 4-4.

Table 4-4 Other Specifications

Item Specification

Chassis dimensions 1850 mm × 650 mm × 600 mm (H × W × D)

4-2

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Chapter 4 System Specifications

Item Specification

Chassis weight Approximately 140 kg (excluding rectifiers, monitoring unit and


batteries)

ZXD1500 Rectifier weight 3.6 kg/set

Monitoring unit weight 1.6 kg

Cable connection l Power equipment unit and communication box: front


connection
l Cabinet: bottom connection

Installation mode Floor mounted

Noise ≤ 55 dB(A)

IP level l Power cabinet: IP55


l Battery cabinet: IP34

MTBF ≥ 2.2 × 105 h

• IP: International Protection


• MTBF: Mean Time Between Failures

4.2 Compliance Standards


EMC Standards
The ZXDU58 W121 system is in compliance with the following Electromagnetic
Compatibility (EMC) standards:
l EN55022
l IEC61000-3-3; IEC61000-3-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4;
IEC61000-4-6; IEC61000-4-8; and IEC61000-4-11

Safety Standards
The ZXDU58 W121 system is in compliance with the UL/IEC/EN 60950 safety standards.

Other Standards
The ZXDU58 W121 system is also in compliance with the following standards:
l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of the
European Union.
l This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may
cause undesired operations.

4-3

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

This page intentionally left blank.

4-4

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Appendix A
Electrical Connection
Diagram
ZXDU58 W121 (V4.0R02M01) electrical connection diagrams are shown below:
l Figure A-1 shows the electrical connection diagram for the system with single-phase
AC input and AC SPD of class B.
l Figure A-2 shows the electrical connection diagram for the system with single-phase
AC input and AC SPD of class C.
l Figure A-3 shows the electrical connection diagram for the system with three-phase
AC input and AC SPD of class B.
l Figure A-4 shows the electrical connection diagram for the system with three-phase
AC input and AC SPD of class C.

Figure A-1 ZXDU58 W121 (V4.0R02M01) Electrical Connection Diagram


(Single-phase,Class B)

A-1

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Figure A-2 ZXDU58 W121 (V4.0R02M01) Electrical Connection Diagram


(Single-phase,Class C)

Figure A-3 ZXDU58 W121 (V4.0R02M01) Electrical Connection Diagram


(Three-phase,Class B)

A-2

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Appendix A Electrical Connection Diagram

Figure A-4 ZXDU58 W121 (V4.0R02M01) Electrical Connection Diagram


(Three-phase,Class C)

A-3

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

This page intentionally left blank.

A-4

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Appendix B
Documentation Guide
Applicable Product
This guide and related documents apply to the ZXDU58 W121 (V4.0R02M01) DC power
system.

Manual Suite
Refer to the table below for the manual suite of the ZXDU58 W121 system.

Document Description and Intended Audience

DC Power System Safety Information This manual describes the personal health & safety
information and the system security information that you
should learn when working with the ZTE system products.
Intended Audience: This manual is intended for device
installation engineers, commissioning engineers and
maintenance engineers.

ZXDU58 W121 (V4.0R02M01) DC In this manual, you will learn about:


Power System Product Description l System structure (detailed description)
l ZXD1500 rectifier
l Monitoring unit
l System specifications
l Electrical connection diagram
Intended Audience: This manual is intended for planning
engineers and maintenance engineers.

ZXDU58 W121 (V4.0R01/R02M01) In this manual, you will learn about:


DC Power System User Guide l System structure (brief description)
l Monitoring software (brief description)
l Indicators
l System startup and shutdown
l Symptoms and troubleshooting
Intended Audience: This manual is intended for device
installation engineers, commissioning engineers and
maintenance engineers.

B-1

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


ZXDU58 W121 Product Description

Document Description and Intended Audience

ZXDU58 W121 (V4.0R01/R02M01) In this manual, you will learn about:


DC Power System Quick Installation & l Equipment installation
Commissioning Guide l Cable connection
l System commissioning
Intended Audience: This manual is intended for device
installation engineers and commissioning engineers.

ZXDU58/ZXDU68 B121-CSU (V2.20) In this document, you will learn about:


Monitoring Unit Operation Manual l Querying data
l Setting parameter
l System management
l System parameters and battery parameters
l Alarm list
Intended Audience: This manual is intended for
commissioning engineers and maintenance engineers.

ZXDU58/ZXDU68 B121-CSU (V2.20) This manual describes:


Monitoring Unit Alarm List l Alarm name
l Default level
l Default output relay
Intended Audience: This manual is intended for
commissioning engineers and maintenance engineers.

ZXDU58/ZXDU68 Series (V4.0) In this document, you will learn about:


DC Power System Maintenance l System startup and shutdown
Manual l Routine maintenance
l Alarm handling
l Troubleshooting
l Components replacement
Intended Audience: This manual is intended for
maintenance engineers.

How to Get in Touch


ZTE welcomes your comments and suggestions on the quality and usefulness of this
document.

The following sections provide information on how to obtain support for the documentation.

If you have problems, questions, comments, or suggestions regarding your product,


contact us by e-mail at 800@zte.com.cn. You can also call our customer support center
at (86) 755 26771900.

For further questions, comments, or suggestions on the documentation, you can fax your
comments and suggestions to (86) 755 26770801. You can also browse our website at htt
p://ensupport.zte.com.cn, which contains various interesting subjects like documentation,
knowledge base, forum and service request.

B-2

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential


Glossary
AC
- Alternating Current
- 交流电,交流
BTS
- Base Transceiver Station
- 基站收发信机
DC
- Direct Current
- 直流电
IP
- Internet Protocol
- 因特网协议
LLVD
- Load Low Voltage Disconnect
- 低压负载下电

MTBF
- Mean Time Between Failures
- 平均故障间隔时间
PC
- Personal Computer
- 个人电脑
RoHS
- Restriction of Hazardous Substances
- 有害物质限制

SIB
- Signal Interface Board
- 信号接口板
SNMP
- Simple Network Management Protocol
- 简单网络管理协议
SPD
- Surge Protection Device
- 电涌保护装置

SJ-20110308105524-006|2011-07-18 (R1.1) ZTE Proprietary and Confidential