Test Procedure for Steel


Beam-Column Joints
(AISC Seismic Provision Appendix S)

Typical Test Subassemblages

Exterior Subassemblage Interior Subassemblage

1
3/3/2014

Typical Exterior Subassemblage

 Δ

Lbeam

Δ
Interstory Drift Angle  =
Lbeam

Typical Exterior Subassemblage

2
3/3/2014

Typical Interior Subassemblage

Hcolumn

Δ
Interstory Drift Angle  =
Hcolumn

Typical Interior Subassemblage

3
3/3/2014

Typical Interior Subassemblage (with concrete floor slab)

Appendix S
Testing Requirements - Loading History

Apply the following loading history:


6 cycles at  =  0.00375 rad.
6 cycles at  =  0.005 rad.
6 cycles at  =  0.0075 rad.
4 cycles at  =  0.01 rad.
2 cycles at  =  0.015 rad.
2 cycles at  =  0.02 rad.
2 cycles at  =  0.03 rad.
2 cycles at  =  0.04 rad.
continue at increments of 0.01 rad, with two
cycles of loading at each step

4
3/3/2014

Appendix S
Testing Requirements - Loading History

0.06
0.05
0.04
Interstory Drift Angle 

0.03
0.02
0.01
0
-0.01
-0.02
-0.03
-0.04
-0.05

Acceptance Criteria for SMF Beam-to-Column Connections:


After completing at least one loading cycle at  0.04 radian, the measured flexural
resistance of the connection, measured at the face of the column, must be at least
0.80 Mp of the connected beam

Example of Successful Conformance Demonstration Test


per Appendix S:

40000
M 0.04 0.8 M p
Beam Moment at Face of Column (in-kips)

30000

0.8 Mp
20000

10000

-10000

-20000
- 0.8 Mp

-30000
M 0.04 0.8 M p

-40000
-0.08 -0.06 -0.04 -0.02 0 0.02 0.04 0.06 0.08
Interstory Drift Angle (rad)

5
3/3/2014

Prosedur Tes Lainnya

 NEHRP 2003 (FEMA 450)


 ACI ITG-5.1-07

“Acceptance Criteria for Special


Unbonded Post-Tensioned Precast
Structural Walls Based on Validation
Testing”