Voltage Drop Analysis: 1250 kVA PP-6

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

VOLTAGE DROP ANALYSIS

1 2 3 4 5 6
28.63 ft 7.21 ft 7.21 ft 18.05 ft 24.8 ft 208.46 ft

4 sets of 3-375 mm2 THHN 8 sets of 3-300 mm2 THW 4 sets of 3-60 mm2 THW 4 sets of 3-50 mm2 THW 3-5.5 mm2 THW
3 -38mm2 THW
10 Feeder Bus 1250 kVA Sub-Feeder Bus
MVA
MDP 1 PP-6 C.O.
Sub Transformer 4
Transformer 2

SUPPLY VOLTAGE = 220 V

VOLTAGE DROP CALCULATION


PHASE WIRE
ITEM NO. DESCRIPTION 1ɸ 3ɸ K L I CM SET
VD %VD
1 Transformer 2 to Feeder Bus 1.732 12.9 28.63 1387.86 750,000 4 0.296 7.114 x 10-3
2 Feeder Bus to Sub Transformer 4 1.732 12.9 7.21 1453.35 76,000 1 3.081 0.07405
3 Sub Transformer 4 to Sub Feeder Bus 1.732 12.9 7.21 2261.53 600,000 8 0.607 0.159

4 Subfeeder to MDP 1 1.732 12.9 18.05 475.48 133,100 4 0.360 0.095

5 MDP1 to PP6 2 12.9 24.80 47.328 105,600 4 0.0717 0.0326


6 PP6 to Convenience Outlet 2 12.9 208.46 10.91 10,380 1 5.653 2.569
TOTAL 10.069 V 2.937 %

T e om te o t e o of W W N
NT t tot 2. 37 e e t e of o t e
o meet t e e e o e of
e e t o e.

CONTRACTOR LOGO NAME OF PROJECT NAME AND ADDRESS OF OWNERS SHEET CONTENT DESIGNED AND DRAWN BY: CHECKED BY: NAME OF PEE PRC REG. NO: SHEET NO.
ENGR. GILBERT B. HOLLMAN PTC NO.:
POWER SYSTEM DESIGN FOR WOODALL INTERNATIONAL VOLTAGE DROP JENIXSON C. TAMONDONG 11
INDUSTRIAL PLANT BAYBAY CITY, LEYTE ANALYSIS JOSHUA L. PALIZA
PROFESSOR ENGR. GILBERT B. HOLLMAN DATE AND PLACE ISSUED: E
15
SCALE = NTS TIN:
From Transformer 2 to Feeder 2 From Feeder 2 to Transformer 4 From Transformer 4 to Subfeeder
K = 12.9 K = 12.9 K = 12.9
L = 28.63 ft. L = 7.21 ft. L = 7.21 ft.
I = 1387.86 A I = 1453.35 A I = 2261.53 A
CM = 750,000 CM = 76,000 CM = 600,000
Runs: 4 Runs: 1 Runs: 8

Substitution Substitution Substitution


VD = 1.732 x K x L x I VD = 1.732 x K x L x I VD = 1.732 x K x L x I
CM CM CM
VD = 1.732 x 12.9 x 28.63 x 1387.86 VD = 1.732 x 12.9 x 7.21 x 1453.35 VD = 1.732 x 12.9 x 7.21 x 2261.53
750,000 x 4 76,000 600,000
VD = 0.296 VD = 3.081 VD = 0.607

%VD = VD x 100 %VD = VD x 100 %VD = VD x 100


4160 4160 380
%VD = 0.296 x 100 %VD = 3.081 x 100 %VD = 0.607 x 100
4160 4160 380
%VD = 7.114 x 10-3% %VD = 0.07405% %VD = 0.159%

CONTRACTOR LOGO NAME OF PROJECT NAME AND ADDRESS OF OWNERS SHEET CONTENT DESIGNED AND DRAWN BY: CHECKED BY: NAME OF PEE PRC REG. NO: SHEET NO.
ENGR. GILBERT B. HOLLMAN PTC NO.:
POWER SYSTEM DESIGN FOR WOODALL INTERNATIONAL VOLTAGE DROP JENIXSON C. TAMONDONG 12
INDUSTRIAL PLANT BAYBAY CITY, LEYTE ANALYSIS JOSHUA L. PALIZA
PROFESSOR ENGR. GILBERT B. HOLLMAN DATE AND PLACE ISSUED: E
15
SCALE = NTS TIN:
From Subfeeder to MDP 1 From MDP to PP6 From PP6 to Convenience Outlet
K = 12.9 K = 12.9 K = 12.9
L = 18.045 ft. L = 24.8 ft. L = 208.46 ft.
I = 475.48 A I = 47.328 A I = 10.91 A
CM = 133,100 CM = 105,600 CM = 10,380
Runs: 4 Runs: 4 Runs: 1

Substitution Substitution Substitution


VD = 1.732 x K x L x I VD = 2 x K x L x I VD = 2 x K x L x I
CM CM CM
VD = 1.732 x 12.9 x 18.045 x 475.48 VD = 2 x 12.9 x 24.80 x 47.328 VD = 2 x 12.9 x 208.46 x 10.91
133,100 x 4 105,600 x 4 10,380
VD = 0.360 VD = 0.0717 VD = 5.653
%VD = VD x 100 %VD = VD x 100
380 220 %VD = VD x 100
%VD = 0.360 x 100 %VD = 0.0717 x 100 220
380 220 %VD = 5.653 x 100
%VD = 0.095% %VD = 0.0326% 220
%VD = 2.569%

CONTRACTOR LOGO NAME OF PROJECT NAME AND ADDRESS OF OWNERS SHEET CONTENT DESIGNED AND DRAWN BY: CHECKED BY: NAME OF PEE PRC REG. NO: SHEET NO.
ENGR. GILBERT B. HOLLMAN PTC NO.:
POWER SYSTEM DESIGN FOR WOODALL INTERNATIONAL VOLTAGE DROP JENIXSON C. TAMONDONG 13
INDUSTRIAL PLANT BAYBAY CITY, LEYTE ANALYSIS JOSHUA L. PALIZA
PROFESSOR ENGR. GILBERT B. HOLLMAN DATE AND PLACE ISSUED: E
15
SCALE = NTS TIN:
SHORT CIRCUIT ANALYSIS

34.5KV,3Ø ,3 WIRE
60HZ SUPPLY

3-34.5KV / 230V
LA 27KV

KW KVAR

3-250 : 5 CT

600AT OCB

ZL1 3-xy

200A, 34.5KV

T-2
10 MVA
34.5KV/4.16KV

ZL2 1
4160V BUS

ZL3 ZL4 ZL5 ZL6 ZL7 ZL8


ZL9
T-4
1200KVA
4.16KV/380V
2 4 6 8 10 12
ZL10
2000HP 1500HP
X''=20% X''=20%

2 380V BUS

SF - 5 SF -4 SF - 3 SF - 2 SF - 1

500AT 500AT 500AT

ZL12
3
ZL11

ZL13

CONTRACTOR LOGO NAME OF PROJECT NAME AND ADDRESS OF OWNERS SHEET CONTENT DESIGNED AND DRAWN BY: CHECKED BY: NAME OF PEE PRC REG. NO: SHEET NO.
ENGR. GILBERT B. HOLLMAN PTC NO.:
POWER SYSTEM DESIGN FOR WOODALL INTERNATIONAL SHORT CIRCUIT JENIXSON C. TAMONDONG 14
INDUSTRIAL PLANT BAYBAY CITY, LEYTE ANALYSIS JOSHUA L. PALIZA
PROFESSOR ENGR. GILBERT B. HOLLMAN DATE AND PLACE ISSUED: E
15
SCALE = NTS TIN:
AT POINT 1 AT POINT 2 AT POINT 3

E E
E 4160V BUS 4160V BUS

4160V BUS
XS XS

ZL3 ZL4 ZL5 ZL6 ZL7 ZL8 ZL3 ZL4 ZL5 ZL6 ZL7 ZL8
ZL1 ZL1
XS
XT2 XT2
XSM1 XSM2 XSM3 XSM4 XSM5 XSM6 XSM1 XSM2 XSM3 XSM4 XSM5 XSM6
ZL1 ZL2 ZLM ZL2 ZLM
ZEQ2
XT2 XGM XGM
ZL9 ZL9

ZL2 XT4 XT4

ZL10 ZL10
1
2 ZL12

CONTRACTOR LOGO NAME OF PROJECT NAME AND ADDRESS OF OWNERS SHEET CONTENT DESIGNED AND DRAWN BY: CHECKED BY: NAME OF PEE PRC REG. NO: SHEET NO.
ENGR. GILBERT B. HOLLMAN PTC NO.:
POWER SYSTEM DESIGN FOR WOODALL INTERNATIONAL SHORT CIRCUIT JENIXSON C. TAMONDONG 15
INDUSTRIAL PLANT BAYBAY CITY, LEYTE ANALYSIS JOSHUA L. PALIZA
PROFESSOR ENGR. GILBERT B. HOLLMAN DATE AND PLACE ISSUED: E
15
SCALE = NTS TIN: