Fully Calculated Fire Fighting Systems According EN 12845 Standard
Fully Calculated Fire Fighting Systems According EN 12845 Standard
EN 12845 standard
Design and calculations with 4M FINE FIRE software
𝑸=𝑲 𝑷
Maximum coverage and spacing for sprinkler other than sidewall (table 19)
Q= K x P
6, 05 x105
P xLxQ1,85
C 1,85 xd 4,87
Detailed calculation
Detailed calculation
Total flow required = 260+285+315= 860 lpm> 720 (12 * 60) lpm
Υπόμνημα
1 Υδραυλικά δυσμενέστερη περιοχή
2 Παροχή σχεδιασμού αντλίας
3 Μέγιστη απαιτούμενη παροχή
4 Υδραυλικά ευμενέστερη περιοχή
The rated duty of the pump shall be a function of the most unfavourable area curve.
A pump is chosen which:
• provides 0,5 bar higher pressure than that required for the most unfavourable area
• has a curve which extends to the point of NPSHr = 16 m
The Max Demand Flow & Pressure of the selected pump is calculated based on the most
favourable area
It is checked if the pump can deliver the maximum operating point at all levels of water supply
NPSHa NPSHreq 1
Briefly, according paragraph 4.4.3.3, 4.4.4.4-5 for fully calculated pipework, the following
shall be given, with detailed calculations, either on purpose designed work-sheets or as a
computer printout:
ii. the specified design density in millimetres per viii. velocity in metres per second (m/s)
minute;
ix. static head change in metres
iii. pressures at inlet and outlet in bar
x. friction loss in bar;
iv. the nominal K-factor
xi. numbers, types and equivalent length in metres of
v. Nominal diameter in mm fittings and components
a © 4M s/n:999723
c. Detailed and dimensioned working drawings
i. the node or pipe reference scheme used to v. the maximum area covered per sprinkler in
identify pipes, junctions, sprinkler heads and square metres (m2)
fittings which need hydraulic consideration
ii. the position of the hydraulically most vi. the hazard class
unfavourable and favourable area of operation
vii. the specified design density in millimetres per
ii. the four sprinklers upon which the design minute
density is based
viii. the number of sprinklers in the area of operation
iii. the height above datum (e.g. pump axis) of each
point of identified pressure value. ix. the sprinkler nominal orifice size in
millimetres(mm)
vi
ix
Unfavourable
i group
viii
ii
iii Favourable
group
v vii
iv
d. Detailed calculations for the automatic pump set and storage
tank
For fully calculated networks apart from the supplier’s data it s required the following
diagrams and calculations:
i. Chart with the demand pressure/flow characteristic for the hydraulically most
unfavourable and most favourable area of operation calculated at the control valve 'C'
gauge.η.
ii. the available and the specified NPSH at maximum required flow
FINE FIRE advantages for the user
• Familiar graphical user interface based on AutoCAD® or IntelliCad®
• Enables automatic and reliable hydraulic calculation and pipe sizing for all the
widely known standards like EN 12845, NFPA 13, FM GLOBAL, CEA 4001,
AS 2118, BS 9251 and ASIB 11th edition.
• Automated processes for the definition and calculation of most favorable and
unfavorable sprinkler group directly from the calculation engine
support@4msa.com