VTS TF Air System PVT.

LTD
Survey No. 13/1, Kanekallu Village, Near Sevangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
praveen.jha@vtsgroup.com

Technical data for item 2 Offer number 47D/LIVE.EUR/PJ/2021-21


Project name DHARAHARA PROJECT,
NEPAL

Type SingleSupply
Application Indoor
Project Tag BF-1&2 (42 TON)
Size VVS300
Set VVS300-R-MFCV

Insulation thickness 40 mm
Insulation Polyurethane Foam
Weight of the set (+/- 10%)* 1390 Kg

Supply airflow 2 28560.00 m³/h


External pressure 600 Pa

SFP Winter 1.49 kW/m³/s


SFP Summer 1.49 kW/m³/s

Energy efficiency class C 2016

Inspection Panels

Comment 1:

Page: 1/6

ClimaCAD On-Line 4.0.4.0, (Since 4/16/2020) 5/20/2021 9:15:07 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Sevangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
praveen.jha@vtsgroup.com

Technical data for item 2 Offer number 47D/LIVE.EUR/PJ/2021-21

Front View (left) Front View (right)

Top View

Sizes [mm]

Air intake Supply FS 2060x700 Lt 3688 Hid 1496 Wi 2505


Air intake Supply US 700x310 LtA 3813 Hiu 1496 W 2585
Air outlet Supply US 2060x700 Hi 1496
H 1696
Hf 120

Unit design
Casing made of 40mm polyurethane foam ‘sandwich’ type panels formed in ‘C’ shape
Mechanical strength of casing -1000 Pa ÷ 1000 Pa < 2mm (D1 - EN 1886: 2007)

Page: 2/6

ClimaCAD On-Line 4.0.4.0, (Since 4/16/2020) 5/20/2021 9:15:07 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Sevangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
praveen.jha@vtsgroup.com

Technical data for item 2 Offer number 47D/LIVE.EUR/PJ/2021-21


Casing tightness: (MB): (-400) Pa - 0,05 l/sm² (L1 - EN 1886:2007), (+700) Pa - 0,13 l/sm² (L1 - EN 1886:2007); (RU): -400 Pa - 0,09 l/sm²
(L1 - EN 1886:2007), +400 Pa - 0,93 l/sm² (L1 - EN 1886:2007)
Casing heat transfer coefficient K= 0,6 W/m²K (T2 - EN 1886: 2007)
Thermal bridges coefficient Kb = 0,69 (TB2 - EN 1886: 2007)

Temperature Conditions
Reference atmospheric pressure 101325 Pa Winter outdoor reference temperature -5.0 °C
External air Return air
DBT RH DA DBT RH DA

Summer 30.0 °C 25 % 1.2000 kg/m³ 25.0 °C 50 % 1.2000 kg/m³


Winter -5.0 °C 78 % 1.2000 kg/m³ 25.0 °C 50 % 1.2000 kg/m³

Supply

Mixing section

Mixing Box

Winter operation Summer operation


Recirculation 90 % Recirculation 90 %
Supply inlet -5.0 °C/78 % Supply inlet 30.0 °C/25 %
Exhaust inlet DBT/RH 25.0 °C/50 % Exhaust inlet DBT/RH 25.0 °C/50 %
Supply outlet DBT/RH 22.0 °C/55 % Supply outlet DBT/RH 25.5 °C/47 %
Sensible recovery capacity 259.2 kW Sensible recovery capacity 43.6 kW

Panel Filter followed by Short Bag Filter

Type G4/50.Box.Int.Sld
Coarse 75% (ISO 16890) - EFF CLASS Box[21.0]/50
E

Filter Energy Performance Class E


Winter operation Summer operation
50% Dirty Air Pressure Drop 72 Pa 50% Dirty Air Pressure Drop 72 Pa
Initial Air Pressure Drop 45 Pa Initial Air Pressure Drop 45 Pa
100% Dirty Air Pressure Drop 100 Pa 100% Dirty Air Pressure Drop 100 Pa
Air velocity 2.12 m/s Air velocity 2.12 m/s
Filter Sizes
BOX+BAG FLT, VS-300 (1-5-0309-0039) 1 x Pcs

Type F7/300.Bag.Int.Sld
ePM2,5 65% (ISO16890) - EFF CLASS Bag[8.0]/300
E

Page: 3/6

ClimaCAD On-Line 4.0.4.0, (Since 4/16/2020) 5/20/2021 9:15:07 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Sevangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
praveen.jha@vtsgroup.com

Technical data for item 2 Offer number 47D/LIVE.EUR/PJ/2021-21


Filter Energy Performance Class E
Winter operation Summer operation
50% Dirty Air Pressure Drop 146 Pa 50% Dirty Air Pressure Drop 146 Pa
Initial Air Pressure Drop 92 Pa Initial Air Pressure Drop 92 Pa
100% Dirty Air Pressure Drop 200 Pa 100% Dirty Air Pressure Drop 200 Pa
Air velocity 2.12 m/s Air velocity 2.12 m/s
Filter Sizes
BOX+BAG FLT, VS-300 (1-5-0309-0039) 1 x Pcs

Dual Temperature Coil

Type WCL VVS300 6R DT SH.St.St.Std Number of rows 6 Connection Supply/Return: 3"/3"


Standard Circuits 77,07 [dm^3] WCL VVS300 SH.St.St.Std

Medium Water Maximum working pressure 16 bar


Glycole concentration 0.00 % Maximum working temperature 160.0 °C
Winter operation Summer operation
Intake air DBT / RH 22.0 °C / 55 % Intake air DBT / RH 25.5 °C / 47 %
Discharge air DBT / RH 22.0 °C / 55 % Discharge air DBT / RH 13.6 °C / 83 %
Air velocity 2.31 m/s Air velocity 2.31 m/s
Pressure drop Wet / Dry Wet 144 Pa Pressure drop Wet / Dry Wet / Dry 144 Pa / 111 Pa
Air Pressure 101325 Pa Air Pressure 101325 Pa
Air Density 1.2000 kg/m³ Air Density 1.2000 kg/m³
Air Volume Flow 28560.00 m³/h Air Volume Flow 28560.00 m³/h
Cooling capacity: Sensible / Total 0.0 kW/0.0 kW Cooling capacity: Sensible / Total 115.8 kW/150.2 kW
Medium temperature: Inlet / Outlet 7.0 °C/12.0 °C Medium temperature: Inlet / Outlet 7.0 °C/12.0 °C
Medium flow rate 0.00 m³/h Medium flow rate 25.75 m³/h
Medium pressure drop 0.00 kPa Medium pressure drop 14.49 kPa

Heating mode
Standard Circuits 77,07 [dm^3] WCL VVS300 SH.St.St.Std

Medium Water Maximum working pressure 16 bar


Glycole concentration 0.00 % Maximum working temperature 160.0 °C
Winter operation Summer operation
Intake air DBT / RH 22.0 °C / 55 % Intake air DBT / RH 25.5 °C / 47 %
Discharge air DBT / RH 26.0 °C / 43 % Discharge air DBT / RH 25.5 °C / 47 %
Air velocity 2.44 m/s Air velocity 2.44 m/s
Pressure drop Wet / Dry Wet 135 Pa Pressure drop Wet / Dry Wet 135 Pa
Air Pressure 101325 Pa Air Pressure 101325 Pa
Air Density 1.2000 kg/m³ Air Density 1.2000 kg/m³
Air Volume Flow 28560.00 m³/h Air Volume Flow 28560.00 m³/h
Total heating capacity 38.9 kW Total heating capacity 0.0 kW
Medium temperature: Inlet / Outlet 50.0 °C/45.0 °C Medium temperature: Inlet / Outlet 50.0 °C/45.0 °C
Medium flow rate 6.71 m³/h Medium flow rate 0.00 m³/h
Medium pressure drop 1.28 kPa Medium pressure drop 0.00 kPa

Page: 4/6

ClimaCAD On-Line 4.0.4.0, (Since 4/16/2020) 5/20/2021 9:15:07 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Sevangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
praveen.jha@vtsgroup.com

Technical data for item 2 Offer number 47D/LIVE.EUR/PJ/2021-21


Plug-Fan Set

Fan Section PLUG_DD_630_5,50_4

Fan System Main Fan Qty in section x2


Fan Set Assembly Type FLX2 (Flanged)
Fan Set Designed for wet operating conditions
The Fan System EffectIs Taken Into Account In The Fan Performances

Fan PLUG_VS_630_AF_Px 2
40

Total Static Pressure 962 Pa Impeller efficiency: Static / Total 71 %/76 %


Dynamic pressure 75 Pa Shaft power 5.41 kW x 2
External pressure 600 Pa Working revolutions 1589 1/min
Total Pressure 1037 Pa Fans Connection Standard FLX2 (Flanged)

Motor AC_IE2_F_132S_IMB3_4p_5.5_50x 2

Motor enclousure IMB3 Rated Currect 11.5 A x 2


IEC Size 132S Rated revolutions 1455 1/min
Operational Voltage 400 V/3 ph Rated Power 5.50 kW x 2
Fan Motor Rated Voltage 400 V/3 ph/50 Hz Motor Version S-Series

VFD
_AC _AC

VFD Yes Connecting Point CP Excluded


VFD Qty in section 2 VFD Voltage Supply 400/3/50 V/ph/Hz
VFD Settings 55 Hz VFD Rated Power 5.50 kW x 2
VFD in selection Included VFD HMI No
VFD Optional Nema KIT No VFD 1PH ModBus Comm Board No
Winter operation Summer operation
EPC for mean contaminated filters 12.82 kW EPC for mean contaminated filters 12.82 kW
EPC for clean filters 11.81 kW EPC for clean filters 11.81 kW
SFP for clean filters 1.49 kW/m³/s SFP for clean filters 1.49 kW/m³/s
Air Pressure 101325 Pa Air Pressure 101325 Pa
Air Density 1.2000 kg/m³ Air Density 1.2000 kg/m³
Air Volume Flow 28560.00 m³/h Air Volume Flow 28560.00 m³/h

Acoustic data

Acoustic power level


Frequency 125 [Hz] 250 [Hz] 500 [Hz] 1000 [Hz] 2000 [Hz] 4000 [Hz] 8000 [Hz] Lw [dB(A)]
[dB(A)]
Inlet [dB(A)] 51.9 65.3 71.2 70.6 67.2 55.4 49.8 75.3
Outlet [dB(A)] 58.2 71.6 77.5 77.8 76.2 71.6 66.0 82.8
Environment [dB(A)] 46.2 65.6 66.5 65.8 62.2 39.6 25.0 71.3

Page: 5/6

ClimaCAD On-Line 4.0.4.0, (Since 4/16/2020) 5/20/2021 9:15:07 AM


VTS TF Air System PVT. LTD
Survey No. 13/1, Kanekallu Village, Near Sevangonthi
railway station; Makanahalli Road, Hosakote, Bangalore –
560 067. Karnataka.; India
DivisionTel_710
praveen.jha@vtsgroup.com

Technical data for item 2 Offer number 47D/LIVE.EUR/PJ/2021-21

Acoustic pressure Frequency 125 [Hz] 250 [Hz] 500 [Hz] 1000 [Hz] 2000 [Hz] 4000 [Hz] 8000 [Hz] Lp [dB(A)]
level at 1 meter
distance [dB(A)] [dB(A)] 39.2 58.6 59.5 58.8 55.2 32.6 18.0 64.3

Air Inlet Outlet ACCESSORIES Supply Exhaust

Controls Selection Mode: No controls

Inlet Outlet Holes Supply Exhaust


Air Inlet Front (Small) 2060x700
Air Inlet (2nd) Top 700x310
Air Outlet Top 2060x700
AirDamper Supply Exhaust
Air Inlet Yes No
Air Inlet (2nd) Yes No

Other Accessories
ViewFinder PRTHL_1 1 Accessories
Quantity
Inside Lighting INT.LHT_1 1 Accessories
Quantity
Control application

Functional Code AS|0|0|1|0|0|1|0|6|3|0|0|0|0|0|1


Section splits

Transport Sections Mass [Kg] LENGTH [mm] WIDTH [mm] HEIGHT [mm]
1 1385 3688 2585 1696

Transport Sections Dims

Page: 6/6

ClimaCAD On-Line 4.0.4.0, (Since 4/16/2020) 5/20/2021 9:15:07 AM