GENERAL NOTES AND AIR-CONDITIONING LAY-OUT

SPECIFICATIONS
1. UNIT INSTALLATION MUST CONFORM TO THE
MANUFACTURERS RECOMMENDATIONS AND
ALL ENGINEERING/ARCHITECTURAL DESIGN
REQUIRED BY THE OWNER.
2. CONDENSATE DRAINS MUST BE DIRECTED TO
RM 101 RM 102 RM 103 RM 104 RM 105
UP UP
NEAREST DRAIN VIA PVC OR FLEXIBLE HOSE.
3. THE ACU MUST BE INSTALLED WITH 1.5 METERS
MINIMUM DISTANCE TO FLOOR LINE. GROUND FLOOR
4. INSTALLATION MUST CONFORM TO PME CODE
AND THE NATIONAL BUILDING CODE. A
MECHANICAL PERMIT SHOULD BE SECURED
PRIOR TO INSTALLATION.
5. AIRCON INSTALLERS MUST BE DEALER
ACCREDITED TECHNICIANS TO INCLUDE
ONE (1) YEAR MAINTENANCE. RM 201 RM 202 RM 203 RM 204 RM 205
UP DN DN UP

SCHEDULE OF EQUIPMENTS &


COMPUTATION OF LOADS SECOND FLOOR
CONSIDERATION:
MONTH: MAY
TIME: 5 PM
LOCATION: PH @ 18°NL
ROOM CONDITION: 77°F, 50%RH
OUTDOOR CONDITION: 93°F
RM 301 RM 302 RM 303 RM 304 RM 305
UP DN UP
EQUIPMENT SCHEDULE DN

COOLING
ELECTRICAL CHARACTERISTIC
QTY. CAPACITY
DESCRIPTION DESIGNATION
(Unit)
Btu/hr Watt Amp Volt pH Hz THIRD FLOOR
3.0 TR FLOOR
ACU MOUNTED SPLIT 20 RM 101 - 405 36168.701 3300 15 220 1 60
TYPE AIRCON

COOLING LOAD DEMAND


COMPUTED COOLING LOAD RATED
LOCATION CAPACITY
Btu/hr TOR (TR)
RM 401 RM 402 RM 403 RM 404 RM 405
ROOM 101 31676.75 2.64 3
UP DN DN UP
ROOM 102 29526.77 2.46 3
GROUND FLOOR 2.44
ROOM 103 29284.40 3
(GF)
ROOM 104 28799.65 2.40 3 FOURTH FLOOR
ROOM 105 29870.87 2.49 3

ROOM 201

ROOM 202
31384.29

29234.31
2.62

2.44
3

3
LEGEND AND SYMBOLS LOCATION MAP
SECOND FLOOR ROOM 203 28991.93 2.42 3
(2F)
ROOM 204 28507.18 2.38 3 ACU AIRCONDITIONING UNIT
ROOM 205 29578.41 2.46 3
TOR TONS OF REFRIGERATION
ROOM 301 31384.29 2.62 3 PETRON

ROOM 302 29234.31 2.44 3


THIRD FLOOR TH
(3F) ROOM 303

ROOM 304
28991.93

28507.18
2.42

2.38
3

3
IS
SI
T E
N
ROOM 305 29578.41 2.46 3

ROOM 401 37553.09 3.13 3

ROOM 402 35403.11 2.95 3


FOURTH FLOOR COCA-COLA BOTTLERS
PHILS INC. SAN NICOLAS
ROOM 403 35160.74 2.93 3
(4F)
ROOM 404 34675.99 2.89 3

ROOM 405 35747.22 2.98 3

DRAWN AND DESIGNED BY: PROJECT TITLE: OWNER: SHEET CONTENTS: SHEET NO.

WINSTON F. BERNARDO GENERAL NOTES


CHECKED BY: SAN NICOLAS NATIONAL HIGH SCHOOL EQUIPMENT SCHEDULE
LOCATION MAP W-1
AIR CONDITIONING LAY-OUT
ENGR. NATHANIEL R. MATEO
LOCATION: SAN NICOLAS, ILOCOS NORTE