Introduction
This manual describes the details of Diagnostic Information messages displayed in the Diag-
nostic Information Window of SCS Maintenance Support Tool or System Alarm View of HIS.
The table of the contents of this manual can be used as message number index.
This manual consists of the following chapters:
Chapter 1 : This chapter explains how to refer to the Diagnosis Information in SENG.
Chapter 2 : This chapter explains the details about SCS Messages.
Chapter 3 : This chapter explains the details about common messages of CENTUM VP or
CS 3000 and SENG.
Appendix : A list of the alarm class for the corresponding message number is provided.

Media No. IM 32Q02B10-31E (CD) 4th Edition : Jan. 2015 (YK) IM 32Q02B10-31E 4th Edition : Jan.30,2015-00
All Rights Reserved Copyright © 2011, Yokogawa Electric Corporation
ii

Safety Precautions for Use


n Safety, Protection, and Modification of the Product
• To protect the system controlled by the Product and the Product itself and to ensure safe
operation, please observe the safety precautions described in this Manual. Yokogawa
Electric Corporation ("YOKOGAWA") assumes no liability for safety if users fail to observe
the safety precautions and instructions when operating the Product.
• If the Product is used in a manner not specified in the User's Manuals, the protection pro-
vided by the Product may be impaired.
• If any protection or safety circuit is required for the system controlled by the Product or for
the Product itself, please install it externally.
• Use only spare parts that are approved by YOKOGAWA when replacing parts or consum-
ables of the Product.
• Do not use the Product and its accessories such as power cords on devices that are not
approved by YOKOGAWA. Do not use the Product and its accessories for any purpose
other than those intended by YOKOGAWA.
• Modification of the Product is strictly prohibited.
• The following symbols are used in the Product and User's Manuals to indicate the accom-
panying safety precautions:
Indicates that caution is required for operation. This symbol is labeled on the Prod-
uct to refer the user to the User's Manuals for necessary actions or behaviors in
order to protect the operator and the equipment against dangers such as electric
shock. In the User's Manuals, you will find the precautions necessary to prevent
physical injury or death, which may be caused by accidents, such as electric
shock resulting from operational mistakes.
Identifies a protective conductor terminal. Before using the Product, you must
ground the protective conductor terminal to avoid electric shock.
Identifies a functional grounding terminal. A terminal marked "FG" also has the
same function. This terminal is used for grounding other than protective grounding.
Before using the Product, you must ground this terminal.
Indicates an AC supply.
Indicates a DC supply.
Indicates the ON position of a power on/off switch.

Indicates the OFF position of a power on/off switch.

n Notes on Handling User's Manuals


• Hand over the User's Manuals to your end users so that they can keep the User's Man-
uals on hand for convenient reference.
• Thoroughly read and understand the information in the User's Manuals before using the
Product.
• For the avoidance of doubt, the purpose of the User's Manuals is not to warrant that the
Product is suitable for any particular purpose but to describe the functional details of the
Product.
• Contents of the User's Manuals are subject to change without notice.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


iii
• Every effort has been made to ensure the accuracy of contents in the User's Manuals.
However, should you have any questions or find any errors, contact us or your local dis-
tributor. The User's Manuals with unordered or missing pages will be replaced.

n Warning and Disclaimer


• Except as specified in the warranty terms, YOKOGAWA shall not provide any warranty for
the Product.
• YOKOGAWA shall not be liable for any indirect or consequential loss incurred by either
using or not being able to use the Product.

n Notes on Software
• YOKOGAWA makes no warranties, either expressed or implied, with respect to the Soft-
ware Product's merchantability or suitability for any particular purpose, except as speci-
fied in the warranty terms.
• Purchase the appropriate number of licenses of the Software Product according to the
number of computers to be used.
• No copy of the Software Product may be made for any purpose other than backup; other-
wise, it is deemed as an infringement of YOKOGAWA's Intellectual Property rights.
• Keep the software medium of the Software Product in a safe place.
• No reverse engineering, reverse compiling, reverse assembling, or converting the Soft-
ware Product to human-readable format may be performed for the Software Product.
• No part of the Software Product may be transferred, converted, or sublet for use by any
third-party, without prior written consent from YOKOGAWA.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


iv

Documentation Conventions
n Symbols
The following symbols are used in the User's Manuals.
Identifies instructions that must be observed to avoid physical
injury, electric shock, or death.

Identifies instructions that must be observed to prevent damage


to the software or hardware, or system failures of the Product.

Identifies important information required to understand opera-


tions or functions.

Identifies additional information.

Identifies referenced content.


In online manuals, you can view the referenced content by click-
ing the links that are in green text. However, this action does not
apply to the links that are in black text.

n Typographical Conventions
The following typographical conventions are used throughout the User's Manuals.

l Commonly Used Conventions throughout the User's Manuals


• Δ Mark
Indicates that a space must be entered between character strings.
Example:
.ALΔPIC010Δ-SC
• Character string enclosed by braces { }
Indicates character strings that may be omitted.
Example:
.PRΔTAG{Δ.sheet name}

l Conventions Used to Show Key or Button Operations


• Characters enclosed by brackets [ ]
When characters are enclosed by brackets in the description of a key or button operation,
it indicates a key on the keyboard, a button name in a window, or an item in a list box
displayed in a window.
Example:
To alter the function, press the [ESC] key.

l Conventions of a User-defined Folder


• User-defined folder name enclosed by parenthesis ( )
User definable path is written in a pair of parentheses.
Example:

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


v
(RS Project Folder)\SCS0101

If the RS Project Folder is C:\MYRSPJT, the above path becomes C:


\MYRSPJTSCS0101.

n Drawing Conventions
Drawings used in the User's Manuals may be partially emphasized, simplified, or omitted for
the convenience of description.
Drawings of windows may be slightly different from the actual screenshots with different set-
tings or fonts. The difference does not hamper the understanding of basic functionalities and
operation and monitoring tasks.

n Integration with CENTUM


The Product can be integrated with CENTUM VP or CENTUM CS 3000. In the User's Man-
uals, the integration with CENTUM VP or CENTUM CS 3000 is referred to as "Integration with
CENTUM."
In the User's Manuals, the explanations for integrating the Product with CENTUM VP or
CENTUM CS 3000, the glossary for various features of CENTUM VP is used instead of the
glossary for CENTUM CS 3000. For example, the term "CENTUM VP System Alarm View" is
used instead of "CENTUM CS 3000 System Alarm window." Nevertheless, if the features for
integrating the Product with CENTUM VP and CENTUM CS 3000 are different, both features
will be explained separately.
SEE
ALSO For more information about the functions and usage of CENTUM VP components for integrating the Product
with CENTUM VP, refer to:
User's Manuals (IM), Technical Information (TI), and General Specifications (GS) of CENTUM VP
For more information about the features and usage of CENTUM CS 3000 components for integrating the
Product with CENTUM CS 3000, refer to:
User's Manuals (IM), Technical Information (TI), and General Specifications (GS) of CENTUM CS 3000

n Explanation of Hardware and Software Behaviors in the User's


Manuals
In the User's Manuals, system behaviors are explained assuming that the latest versions of
YOKOGAWA software and hardware at the time of publication of the User's Manuals are in-
stalled.
If additional precise information about the safety of legacy versions of software or hardware is
required, a link to the corresponding explanation is provided. Please refer to the information
according to your system.

n Station Types
A safety control station (hereafter referred to as SCS) is named according to the type of the
safety control unit used in it.

Table Info-1 Names of SCS and Safety Control Unit Used


Name of SCS Model of the safety control unit
SCSV1-S SSC10S/SSC10D
SCSP1-S SSC50S/SSC50D
SCSP2-S SSC60S/SSC60D
SCSU1-S SSC57S/SSC57D

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


vi
In the User's Manuals, the following abbreviations may be used to describe functions of these
SCS as a whole.
• SCSV1: Abbreviation of SCSV1-S
• SCSP1: Abbreviation of SCSP1-S
• SCSP2: Abbreviation of SCSP2-S
• SCSU1: Abbreviation of SCSU1-S

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


vii

Copyright and Trademark Notices


n All Rights Reserved
The copyright of the programs and online manuals contained in the software medium of the
Software Product shall remain with YOKOGAWA.
You are allowed to print the required pages of the online manuals for the purposes of using or
operating the Product; however, reprinting or reproducing the entire document is strictly pro-
hibited by the Copyright Law.
Except as stated above, no part of the online manuals may be reproduced, transferred, sold,
or distributed to a third party in any manner (either in electronic or written form including, with-
out limitation, in the forms of paper documents, electronic media, and transmission via the
network). Nor it may be registered or recorded in the media such as films without permission.

n Trademark Acknowledgments
• CENTUM, ProSafe, Vnet/IP, and STARDOM are registered trademarks of YOKOGAWA.
• Microsoft, Windows, Windows Vista, Windows Server, Visual Basic, Visual C++, and Vis-
ual Studio are either registered trademarks or trademarks of Microsoft Corporation in the
United States and other countries.
• Adobe, Acrobat, and Adobe Reader are registered trademarks of Adobe Systems Incor-
porated.
• Ethernet is a registered trademark of Xerox Corporation.
• HART is a registered trademark of the HART Communication Foundation.
• Modicon and Modbus are registered trademarks of Schneider Electric SA.
• All other company and product names mentioned in the User's Manuals are trademarks
or registered trademarks of their respective companies.
• TM or ® mark are not used to indicate trademarks or registered trademarks in the User's
Manuals.
• Logos and logo marks are not used in the User's Manuals.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


Toc-1

Messages

IM 32Q02B10-31E 4th Edition

CONTENTS
1. Referencing Diagnostic Information Messages on the SENG......... 1-1
1.1 How to Display the Diagnostic Information Window.................................1-2
1.2 Diagnostic Information Window..................................................................1-3
1.3 Printout of Diagnostic Information Message............................................. 1-4
2. Details of Output Messages Specific to the SCS.............................. 2-1
2.1 System Alarms (Message Numbers 4101 through 4199).......................... 2-2
No. 4101 Inter-SCS safety communication error information ....................... 2-2
No. 4102 Inter-SCS safety communication error recovery information .........2-3
No. 4103 Variable lock .................................................................................. 2-3
No. 4104 Cancellation of variable lock ..........................................................2-4
No. 4105 I/O module lock ............................................................................. 2-4
No. 4106 Cancellation of I/O module lock .....................................................2-5
No. 4107 All input module locks ....................................................................2-5
No. 4108 Cancellation of all input module locks ........................................... 2-5
No. 4109 All output module locks ................................................................. 2-5
No. 4110 Cancellation of all output module locks ......................................... 2-5
No. 4111 All module locks ............................................................................ 2-5
No. 4112 Cancellation of all module locks .................................................... 2-6
No. 4113 Number of locks exceeded ............................................................2-6
No. 4114 Recovery from exceeded number of locks .................................... 2-6
No. 4115 Override setting ............................................................................. 2-6
No. 4116 Cancellation of override .................................................................2-6
No. 4117 Information of change to override enabled state ........................... 2-7
No. 4118 Information of change to override disabled state .......................... 2-7
No. 4119 Number of overrides exceeded ..................................................... 2-7
No. 4120 Recovery from exceeded number of overrides ............................. 2-7
No. 4121 Number of enabled overrides exceeded ....................................... 2-8
No. 4122 Recovery from exceeded number of enabled overrides ................2-8
No. 4123 Number of active PASSWD FBs exceeded ................................... 2-8
No. 4124 Recovery from exceeded number of active PASSWD FBs ........... 2-8
No. 4125 I/O module channel error occurred ................................................2-9
No. 4126 Recovery from I/O module channel error ...................................... 2-9
No. 4127 Setting PASSWD FB to ON ........................................................... 2-9

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


Toc-2
No. 4128 Setting PASSWD FB to OFF ......................................................... 2-9
No. 4129 GPS interface unit error ...............................................................2-10
No. 4130 Recovery of GPS interface unit ................................................... 2-10
No. 4131 Communication module lock ....................................................... 2-10
No. 4132 Cancellation of Communication module lock .............................. 2-10
No. 4133 Information of a diagnosis error in the received data of SCS Link
Transmission. .............................................................................. 2-11
No. 4134 Information of a diagnosis error recovery in the received data of
SCS Link Transmission. .............................................................. 2-12
No. 4135 SCS Link Transmission data lock ................................................2-12
No. 4136 Cancellation of SCS Link Transmission data lock ....................... 2-13
No. 4137 Number of Locked Stations in SCS Link Transmission Exceeded .....
..................................................................................................... 2-13
No. 4138 Recovery from exceeded number of locked stations in SCS Link
Transmission ............................................................................... 2-13
No. 4139 Inter-SCS Safety Communication data lock ................................ 2-13
No. 4140 Cancellation of Inter-SCS Safety Communication data lock ....... 2-14
No. 4141 Number of locked stations in Inter-SCS Safety Communication
exceeded .....................................................................................2-14
No. 4142 Recovery from exceeded number of locked stations in Inter-SCS
Safety Communication ................................................................ 2-14
No. 4143 Start of automatic scan period extension .................................... 2-14
No. 4144 Cancellation of automatic scan period extension ........................ 2-15
No. 4145 Abnormal calculation occurred .................................................... 2-15
No. 4146 Recovery from abnormal calculation ........................................... 2-15
No. 4151 Information of retainable data initialization .................................. 2-16
No. 4152 Online change of scan period ......................................................2-16
No. 4153 Information of Inter-SCS Safety Communication data lock time-up ...
..................................................................................................... 2-16
No. 4154 Information of forced cancellation of Inter-SCS Safety
Communication data locks .......................................................... 2-16
No. 4155 Information of SCS Link Transmission status change. ................2-17
No. 4156 Information of SCS Link Transmission definition change ............ 2-17
No. 4157 Information of SCS Link Transmission wiring change ................. 2-17
No. 4158 Information of SCS Link Transmission lock time-up ....................2-17
No. 4159 Information of forced cancellation of SCS Link Transmission locks ...
..................................................................................................... 2-17
No. 4160 Invalid password for Manual Operation FB ................................. 2-18
No. 4161 Information of Output IOM Shutdown ..........................................2-18
No. 4162 Information of communication I/O definition change ................... 2-18
No. 4163 Information of communication I/O wiring change ........................ 2-18
No. 4164 Information of disabling security level change .............................2-18
No. 4165 Information of enabling security level change ............................. 2-19
No. 4166 Information of communication module lock time-up .................... 2-19

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


Toc-3
No. 4167 Information of forced cancellation of communication module locks ...
..................................................................................................... 2-19
No. 4168 Information of tag name change by online change download ............
..................................................................................................... 2-19
No. 4169 NVRAM diagnosis error ...............................................................2-19
No. 4170 Flash memory diagnosis error .....................................................2-20
No. 4172 Information of resource change by online change download ...... 2-20
No. 4173 Completion of writing to flash memory ........................................ 2-20
No. 4174 Failed to write to flash memory ................................................... 2-21
No. 4175 Failed to update external communication data ............................2-21
No. 4177 Information of SCS security level change ................................... 2-21
No. 4178 Information of security level time-up ............................................2-22
No. 4179 Information of communication I/O module output enabled operation .
..................................................................................................... 2-22
No. 4180 Information of password change ................................................. 2-22
No. 4181 Information of output enabled operation ......................................2-22
No. 4182 Information of output module start operation ...............................2-23
No. 4183 Request to upload SOE to SENG ............................................... 2-23
No. 4184 Notification on saving SOE trip signal file in SCS ....................... 2-23
No. 4185 Information of variable value change .......................................... 2-23
No. 4186 Information of lock time-up .......................................................... 2-24
No. 4187 Information of forced cancellation of locks .................................. 2-24
No. 4188 Start of online change download ................................................. 2-24
No. 4189 Completion of online change download ...................................... 2-24
No. 4190 Online change download error .................................................... 2-24
No. 4191 Completion of I/O definition rewriting .......................................... 2-25
No. 4192 Information of override state time-up ...........................................2-25
No. 4193 Information of forced release of all overrides .............................. 2-25
No. 4194 Information of override enabled state time-up .............................2-25
No. 4195 Information of communication I/O data status change ................ 2-26
No. 4196 Invalid password for PASSWD FB ...............................................2-26
No. 4197 Information on active PASSWD FB time-up ................................ 2-26
No. 4198 Information on forced reset of PASSWD FB ................................2-26
No. 4199 Override communication error .....................................................2-27
3. Details of Output Messages in Common with CENTUM................... 3-1
3.1 Safety Control Station Error Occurrence and Recovery Messages
(Message Numbers 0001 through 0094)..................................................... 3-2
No. 0001 Reset start of safety control station ............................................... 3-2
No. 0003 Safety control station automatic reset start ................................... 3-2
No. 0005 Power ON initial cold start of safety control station ....................... 3-2
No. 0009 Transfer of control right of safety control station ........................... 3-2
No. 0011 Fail information of safety control station ........................................3-3
No. 0013 AC power supply failure of safety control station .......................... 3-4

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


Toc-4
No. 0015 Self-diagnosis error of clock inside CPU module .......................... 3-4
No. 0017 ROM checksum error of CPU module ...........................................3-4
No. 0021 Internal task error of safety control station .................................... 3-5
No. 0023 Mapping block fatal error ...............................................................3-5
No. 0025 Function control word error ........................................................... 3-5
No. 0027 Mapping block record information error .........................................3-5
No. 0033 Online downloading abnormal end ................................................3-5
No. 0041 Safety control station fan alarm .....................................................3-6
No. 0042 Recovery from safety control station fan alarm ............................. 3-6
No. 0043 Safety control station temperature alarm ...................................... 3-6
No. 0044 Recovery from safety control station temperature alarm ...............3-7
No. 0045 Power supply module alarm of safety control station .................... 3-7
No. 0046 Recovery from power supply module alarm of safety control station .
....................................................................................................... 3-7
No. 0047 Battery alarm of CPU module ........................................................3-7
No. 0048 Recovery from battery alarm of CPU module ................................3-8
No. 0055 Information of same frame reception in online change download
communication .............................................................................. 3-8
No. 0057 Information of online change download error ................................ 3-8
No. 0059 Information of recovery from node power failure ...........................3-8
No. 0063 ESB bus error ................................................................................3-8
No. 0064 Normal recovery of ESB bus ......................................................... 3-9
No. 0065 Failure of ESB Bus Interface module (SSB401) of node ...............3-9
No. 0066 Normal recovery of ESB Bus Interface module (SSB401) of node ....
..................................................................................................... 3-10
No. 0067 Failure of power supply module of node ..................................... 3-10
No. 0068 Normal recovery of power supply module of a node ................... 3-10
No. 0069 Error before database download to I/O module .......................... 3-10
No. 0081 Failure of I/O module ................................................................... 3-11
No. 0082 Normal recovery of I/O module ................................................... 3-13
No. 0083 I/O module database error occurred ........................................... 3-13
No. 0085 I/O module communication error occurred .................................. 3-13
No. 0086 Recovery from I/O module communication error .........................3-13
No. 0087 Node error occurred .................................................................... 3-13
No. 0088 Normal recovery of node ............................................................. 3-14
No. 0089 Subsystem communication error .................................................3-14
No. 0090 Subsystem communication recovered ........................................ 3-15
No. 0093 CPU node’s housekeeping unit error ...........................................3-15
No. 0094 Normal recovery of CPU node’s housekeeping unit ....................3-15
3.2 Safety Control Station Status Change Related Messages (Message
Numbers 0450 through 0480).................................................................... 3-16
No. 0450 Copy program and database on control side of safety control station
to standby side ............................................................................ 3-16

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


Toc-5
No. 0451 Information of switching of control side of safety control station ........
..................................................................................................... 3-16
No. 0452 Information of switching of standby side of safety control station .......
..................................................................................................... 3-16
No. 0459 Information on I/O module service side .......................................3-16
No. 0460 Information of I/O module out service ......................................... 3-16
No. 0471 Normal completion of online change download ...........................3-17
No. 0474 Information of tag list duplicate error ........................................... 3-17
No. 0475 Start of database download to I/O module .................................. 3-17
No. 0476 Normal completion of database download to I/O module ............3-17
No. 0477 Database download error to I/O module ..................................... 3-17
No. 0480 Heavy load on periodical processing ...........................................3-18
3.3 Safety Control Station Related Messages (Message Numbers 0727
through 0787).............................................................................................. 3-19
No. 0727 Block mode recovery error information ....................................... 3-19
No. 0743 Self-diagnostic SEN-BUS Failure ................................................3-19
No. 0744 Self-diagnostic SEN-BUS Recovery ............................................3-19
No. 0749 Self-diagnosis detected an I/O Error ........................................... 3-19
No. 0750 I/O Recovery from the error detected by self-diagnosis .............. 3-20
No. 0751 Time self-diagnostic testing error ................................................ 3-20
No. 0753 Communication Overload ............................................................3-20
No. 0767 Faulty one ESB bus in CPU module ........................................... 3-20
No. 0768 Single ESB bus in CPU module Recovery .................................. 3-20
No. 0787 Self-diagnosis detected I/O error in CPU module ....................... 3-21

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


TocApp.-1

Messages

IM 32Q02B10-31E 4th Edition

CONTENTS
Appendix
Appendix 1. Alarm Class..................................................................... App.1-1

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<1. Referencing Diagnostic Information Messages on the SENG> 1-1

1. Referencing Diagnostic Information


Messages on the SENG
You can view diagnostic information messages on the Diagnostic Information window, which
is called up from SCS Status Overview window.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<1.1 How to Display the Diagnostic Information Window> 1-2

1.1 How to Display the Diagnostic Information


Window
You can display the Diagnostic Information window from the SCS Status Overview window.
1. In the SCS Status Overview window, select an SCS.
The following figure shows an example of the SCS Status Overview window.
RS project name
Diagnostic information button
Domain number Status of control bus with SENG

SCS Status Overview


File View Window Tool

MYRSPJT Domain:01 V net 1 V net 2

Station SCS Status CPU Status Comment


Ready Ready
R-Fail

Station name SCS status CPU status Station Comment


Diagnostic information mark

Figure 1.1-1 SCS Status Overview Window and Diagnostic Information button

2. Click the [Diagnostic Information] button on the tool bar.


The Diagnostic Information window is displayed, showing the diagnostic information mes-
sages of the station you have selected.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<1.2 Diagnostic Information Window> 1-3

1.2 Diagnostic Information Window


The Diagnostic Information window is shown in the figure below.
Information Help button Toolbar Alarm class Diagnostic Information
Message

Diagnostic Information-[SCS0101 1.3]


File View Operation Help

Number Date Class Message

4125 5/30/2008 10:26:19.720 AM 1 SCS0101 IOM Channel Error NO.


4125 5/30/2008 10:26:19.720 AM 1 SCS0101 IOM Channel Error NO.
0082 5/30/2008 10:26:17.620 AM 3 SCS0101 IOM Recover F10 NODE
0476 5/30/2008 10:26:09.131 AM 4 SCS0101 IOM Download Complete.
0475 5/30/2008 10:26:04.235 AM 4 SCS0101 IOM Download Start F10.
0082 5/30/2008 10:25:55.320 AM 3 SCS0101 IOM Recover F10 NODE
0459 5/30/2008 10:25:55.320 AM 4 SCS0101 IOM In Service F10 NO.
0476 5/30/2008 10:25:51.931 AM 4 SCS0101 IOM Download Complete.
0475 5/30/2008 10:25:48.388 AM 4 SCS0101 IOM Download Start F10.
0047 5/30/2008 10:25:36.851 AM 2 SCS0101 LEFT Battery Alarm
4129 5/30/2008 10:25:33.328 AM 2 SCS0101 GPS Interface Unit Error
0081 5/30/2008 10:25:33.320 AM 1 SCS0101 IOM Fail FIO NODE 0.

Number Date Class Message

30/95

Alarm marks Status bar Number of currently


Warning generated messages

Figure 1.2-1 Diagnostic Information Window

SEE
ALSO For more information about the diagnostic information window, refer to:
3.2, “Displaying SCS Diagnostic Information” in Utilities and Maintenance Reference (IM
32Q04B20-31E)

n How to Display the Help Dialog Box


The details of Diagnostic Information window is displayed in the Help dialog box.
1. In the Diagnostic Information window, select a diagnostic information message.
2. Click the [Help] button on the tool bar.
The Help dialog box is displayed.
SEE
ALSO For more information about the Help dialog box, refer to:
3.2.3, “Diagnostic Information Message Help Function” in Utilities and Maintenance Reference (IM
32Q04B20-31E)

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<1.3 Printout of Diagnostic Information Message> 1-4

1.3 Printout of Diagnostic Information


Message
The printout of diagnostic information messages is shown in the figure below.

5/30/2008 2:02:44 PM page 1/1

Search condition SCS0101 1.3

Format Alarm mark, Message number, Date, Class, Message

Selection mark New Alarm:No mark, Acknowledged:A, Deleted:D

0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 05 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 05
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 03 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 03
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
0451 5/30/2008 9:00:00.465 AM 2 SCS0101 LEFT Control
0005 5/30/2008 9:00:00.465 AM 2 SCS0101 Power ON (Cold Start)
0013 5/30/2008 9:00:00.465 AM 2 SCS0101 AC Fail (Time 1/1/1970 9:00:00 AM)

Figure 1.3-1 Printout of Diagnostic Information Message

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2. Details of Output Messages Specific to the SCS> 2-1

2. Details of Output Messages Specific


to the SCS
This section describes the details of output messages specific to the SCS. The format for
each message follows the example shown below, Cause, Action, Remark, Note and Error
code may be omitted, depending on the message.

No.xxxx
Message name Name of the message.
Example: Information of security level time-up
Printing example Indicates an example of print or display.
Example: SCS0101 Security Level = 1 Elapsed the Specified Period = 08 :
00 : 00
In this document, space in messages and the leading “00” of various numbers
may be different from actual printing examples to the extent they do not impair
the understanding of messages.
Meaning Meaning of a message.
Example: The security level is set to “1” for the duration exceeding the time
limit (8 hours in the above example) specified in SYS_SECURE Function
Block (hereinafter referred to as “FB”).
Cause Describes the cause of occurrence. The description may be omitted depend-
ing on the message.
Example: The security level has not been reverted.
Action Describes the action to take. The description may be omitted depending on
the message.
Example: Revert the security level to “2.”
Remark Describes an item(s) related to the message. The description may be omitted
depending on the message.
Note Describes cautions. The description may be omitted depending on the mes-
sage.
Error code Describes details of the error code included in the message, if any. The de-
scription may be omitted depending on the message.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-2

2.1 System Alarms (Message Numbers 4101


through 4199)
This section describes system alarm messages issued from the SCS.

No.4101
Message name Inter-SCS safety communication error information
Printing example SCS0101 Inter-SCS Safety Communication Receive Error Variable =
C0102001 Code = 5041-8000
Meaning An error is detected during inter-SCS safety communication. The erroneous
binding variable (C0102001 in the above example) is included in the message.
Cause The following causes may be considered. Check the error codes for more de-
tail.
• Stop/restart on the producing side SCS
• Problem in the communication path
• Change in the application of inter-SCS safety communication
Remark Inter-SCS safety communication
Error code The first four digits are an error code, and the next four digits are a cause
code. The error detail can be found from the descriptions of the both codes.
The error codes and cause codes are listed below.
The error code represents the type of error. The following table explains each
error code and the action you can take to fix the error.

Table 2.1-1 Message No. 4101 - Error Code List


Code (hexadecimal) Description Action
An error that occurs
5040 when an application is Check the application logic.
created incorrectly.
No data received with-
5041 in the reception inter-
val timeout value. Check the producing side SCS and the communication
path.
Time diagnosis found
5042
an error.
Communication proto-
Record the message content and report to Yokogawa’s
5043 col error (internal er-
service department.
ror)

The cause code represents the event that caused the problem and is logical
OR of the following codes.

Table 2.1-2 Message No. 4101 - Cause Code List


Code (hexa-
Errors Description Presumed cause
decimal)
Communication was cut off,
Communication stopped and
8000 No response or the producing side stop-
data no longer arrived.
ped.
The restart on the producing
4000 Reset detection Restart on the producing side
side was detected.
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-3
Table 2.1-2 Message No. 4101 - Cause Code List (Table continued)
Code (hexa-
Errors Description Presumed cause
decimal)
The CRC code of delay-rela-
CRC error in delay-related di- Temporary communication
2000 ted diagnosis information is
agnosis information error
not correct.
The communication content Temporary communication
1000 CRC mismatch
and CRC do not match. error
Communication for acquiring Communication was interrup-
Equalization error of delay-re-
0400 delay-related diagnosis infor- ted or the producer SCS is
lated diagnosis information
mation stopped. stopped.
The variable name is not An application was created
0200 Variable name error
“Cddssxxx.” incorrectly.
The domain and station num-
An application was created
0100 Address error bers are different from the
incorrectly.
binding variable.
Communication was updated
0040 Transmission delay occurred later than the transmission Communication delay
delay timeout time.
An error occurred in time
Date/time error on the pro- management on the produc- Date/time management error
0020
ducing side ing side, so the date/time is on the producing side
not reliable.
An error occurred in time
Date/time error on the con- management on the consum- Date/time management error
0010
suming side ing side, so the date/time is on the producing side
not reliable.
The FB ID information is dif-
0004 Different FB ID information Internal error
ferent from the initial value.
The data type does not
0001 Data type error Internal error
match.

No.4102
Message name Inter-SCS safety communication error recovery information
Printing example SCS0101 Inter-SCS Safety Communication Receive Recover Variable =
C0102001
Meaning An inter-SCS safety communication error for the variable (C0102001 in the
above example) recovered. (This is a recovery message of No. 4101.)
Cause The following causes may be considered.
• Recovery of the producing side SCS
• Recovery of the communication path
• Recovery of the application of inter-SCS safety communication
Remark Inter-SCS safety communication

No.4103
Message name Variable lock
Printing example In the case of I/O variables:
SCS0101 Variable Locked Variable=VAR001 NODE 01 SLOT 02 CH 03
In the case of internal variables:

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-4
SCS0101 Variable Locked Variable=VAR001
Meaning The variable (VAR001 in the above example) was locked by operation from
the SENG. In the case of I/O variables, the channel position (node 1, slot 2
and channel 3 in the above example) corresponding to the variable is also in-
cluded in the message.
Remark Forcing function
Note Be sure to unlock the variables that were locked.
If an IO_BOOL type or IO_REAL type variable is locked, the member variable
v or status will be indicated in the format of [Variable=VAR001.v] at the posi-
tion of the variable name in the system alarms. If the variable is not wired to
the channel, the member variable v will be always displayed. Nevertheless, in
any of the above cases, the whole IO_BOOL type or IO_REAL type variable
will be locked.
When locking an array element, the whole array will be locked. Under this cir-
cumstance, the variable name displayed in the system alarm will be attached
with the array element subscript as [Variable=VAR001[1]].

No.4104
Message name Cancellation of variable lock
Printing example In the case of I/O variables:
SCS0101 Variable Unlocked Variable=VAR001 NODE 01 SLOT 02 CH 03
In the case of internal variables:
SCS0101 Variable Unlocked Variable=VAR001
Meaning The lock of the variable (VAR001 in the above example) was cancelled by op-
eration from the SENG. In the case of I/O variables, the channel position
(node 1, slot 2 and channel 3 in the above example) corresponding to the vari-
able is also included in the message.
Remark Forcing function
Note If an IO_BOOL type or IO_REAL type variable is unlocked, the member varia-
ble v or status will be indicated in the format of [Variable=VAR001.v] at the po-
sition of the variable name in the system alarms. If the variable is not wired to
the channel, the member variable v will be always displayed. Nevertheless, in
any of the above cases, the whole IO_BOOL type or IO_REAL type variable
will be unlocked.
Moreover, when unlocking an array element, the whole array will be unlocked.
Under this circumstance, the variable name displayed in the system alarm will
be attached with the array element subscript as [Variable=VAR001[1]].

No.4105
Message name I/O module lock
Printing example SCS0101 IOM Locked NODE 01 SLOT 02
Meaning An I/O module was locked by operation from the SENG. The I/O module posi-
tion (node 1 and slot 2 in the above example) is included in the message.
Remark Forcing function
Note Be sure to cancel the lock of the I/O module that was locked.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-5

No.4106
Message name Cancellation of I/O module lock
Printing example SCS0101 IOM Unlocked NODE 01 SLOT 02
Meaning The lock of an I/O module was cancelled by operation from the SENG. The I/O
module position (node 1 and slot 2 in the above example) is included in the
message.
Remark Forcing function

No.4107
Message name All input module locks
Printing example SCS0101 All Input IOM Locked
Meaning All input modules were locked by operation from the SENG.
Remark Forcing function
Note Be sure to cancel the locks of the input modules that were locked.

No.4108
Message name Cancellation of all input module locks
Printing example SCS0101 All Input IOM Unlocked
Meaning The locks of all input modules were cancelled by operation from the SENG.
Remark Forcing function

No.4109
Message name All output module locks
Printing example SCS0101 All Output IOM Locked
Meaning All output modules were locked by operation from the SENG.
Remark Forcing function
Note Be sure to cancel the locks of the output modules that were locked.

No.4110
Message name Cancellation of all output module locks
Printing example SCS0101 All Output IOM Unlocked
Meaning The locks of all output modules were cancelled by operation from the SENG.
Remark Forcing function

No.4111
Message name All module locks
Printing example SCS0101 All IOM Locked
Meaning All I/O modules were locked by operation from the SENG.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-6
Remark Forcing function
Note Be sure to cancel the locks of the I/O modules that were locked.

No.4112
Message name Cancellation of all module locks
Printing example SCS0101 All IOM Unlocked
Meaning The locks of all I/O modules were cancelled by operation from the SENG.
Remark Forcing function

No.4113
Message name Number of locks exceeded
Printing example SCS0101 Number of Locks Exceeds the Limit = 3
Meaning The total number of locked variables exceeded the limit count (3 in the above
example) specified in SYS_FORCE FB.
Cause This is an operation from the SENG. The number of locks is too many.
Action Cancel the variable locks.
Remark SYS_FORCE FB
Note Lock variables within the limit count.

No.4114
Message name Recovery from exceeded number of locks
Printing example SCS0101 Number of Locks Within the Limit = 3
Meaning The total number of locked variables is reduced to within the limit count (3 in
the above example) specified in SYS_FORCE FB. (This is a recovery mes-
sage of No. 4113.)
Cause This is an operation from the SENG.
Remark SYS_FORCE FB

No.4115
Message name Override setting
Printing example SCS0101 TAG001 Overridden (Instance = OVR0001)
Meaning Override operation was performed for the override FB (OVR0001 in the above
example) that corresponds to the tag name (TAG001 in the above example)
from the HIS.
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

No.4116
Message name Cancellation of override
Printing example SCS0101 TAG001 Override Released (Instance = OVR0001)

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-7
Meaning An override was cancelled for the override FB (OVR0001 in the above exam-
ple) that corresponds to the tag name (TAG001 in the above example) from
the HIS.
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

No.4117
Message name Information of change to override enabled state
Printing example SCS0101 Override Enabled
Meaning An override was enabled.
Cause The SW input parameter of the override FB was set to “TRUE.”
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
Note If the SW input parameter of any override FB is set to “TRUE,” this message is
generated.

No.4118
Message name Information of change to override disabled state
Printing example SCS0101 Override Disabled
Meaning An override was disabled.
Cause The SW input parameter of all override FBs were set to “FALSE.”
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
Note If the SW input parameters of all override FBs are set to “FALSE,” this mes-
sage is generated.

No.4119
Message name Number of overrides exceeded
Printing example SCS0101 Number of Overrides Exceeds the Limit = 3
Meaning The total number of overridden override FBs exceeded the limit count (3 in the
above example) specified in SYS_OVR FB.
Cause This is an operation from the HIS. There are too many overrides.
Action Cancel overrides.
Remark SYS_OVR FB
Note Override within the limit count.

No.4120
Message name Recovery from exceeded number of overrides
Printing example SCS0101 Number of Overrides Within the Limit = 3
Meaning The total number of overridden override FBs is within the limit count (3 in the
above example) specified in SYS_OVR FB. (This is a recovery message of
No. 4119.)
Cause This is an operation from the HIS.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-8
Remark SYS_OVR FB

No.4121
Message name Number of enabled overrides exceeded
Printing example SCS0101 Number of Enabled OVR FBs Exceeds the Limit = 3
Meaning The total number of override FBs in the override enabled state exceeded the
limit count (3 in the above example) specified in SYS_OVR FB.
Action Disable override FBs.
Remark SYS_OVR FB
Note Enable overrides within the limit count.

No.4122
Message name Recovery from exceeded number of enabled overrides
Printing example SCS0101 Number of Enabled OVR FBs Within the Limit = 3
Meaning The total number of override FBs in the override enabled state is within the
limit count (3 in the above example) specified in SYS_OVR FB. (This is a re-
covery message of No. 4121.)
Remark SYS_OVR FB

No.4123
Message name Number of active PASSWD FBs exceeded
Printing example SCS0101 Number of Activated PASSWD FBs Exceeds the Limit = 3
Meaning The total number of active PASSWD FBs exceeded the limit count (3 in the
above example) specified in SYS_PSWD FB.
Cause This is an operation from the HIS. There are too many active PASSWD FBs.
Action Inactivate (reset to OFF) the PASSWD FBs that have exceeded the limit
count.
Remark SYS_PSWD FB
Note Make PASSWD FBs active within the limit count.

No.4124
Message name Recovery from exceeded number of active PASSWD FBs
Printing example SCS0101 Number of Activated PASSWD FBs Within the Limit = 3
Meaning The total number of active PASSWD FBs is within the limit count (3 in the
above example) specified in SYS_PSWD FB. (This is a recovery message of
No. 4123.)
Cause Active PASSWD FBs were inactivated (reset to OFF) by operation from the
HIS.
Remark SYS_PSWD FB

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-9

No.4125
Message name I/O module channel error occurred
Printing example SCS0101 IOM Channel Error NODE 01 SLOT 02 CH 03 XXXXXXXX (YYYY)
Meaning An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in
the above example). XXXXXXXX indicates an error cause, and YYYY indi-
cates an error code.
Cause Error codes and causes of errors are shown on the following list.

Table 2.1-3 Message No. 4125 - Error Causes


Error cause Code Description Remark
Upper limit error of the transmitter oc-
TRNS+ 5121
curred.
Lower limit error of the transmitter oc-
TRNS- 5122
curred.
IOP+ 5123 Upper limit error of the IOP occurred.
IOP- 5124 Lower limit error of the IOP occurred.
Input value is outside of the range of
5125
Ovr Range input values (-25 % to 125 %). This in-
5126
dicates a failure of the I/O module.
Open circuit of DI/DO is included
Ch Fail 5127 A channel error was detected.
in this error code.

Action Check to see if the connected devices and connecting cables are normal.

No.4126
Message name Recovery from I/O module channel error
Printing example SCS0101 IOM Channel Recover NODE 01 SLOT 02 CH 03
Meaning An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in
the above example) recovered. (This is a recovery message of No. 4125.)

No.4127
Message name Setting PASSWD FB to ON
Printing example SCS0101 TAG001 PASSWD FB Set to ON (Instance = PASSWD001)
Meaning PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was set to ON (active) by operation
from the HIS.

No.4128
Message name Setting PASSWD FB to OFF
Printing example SCS0101 TAG001 PASSWD FB Set to OFF (Instance = PASSWD001)
Meaning PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was inactivated (reset to OFF) by oper-
ation from the HIS.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-10

No.4129
Message name GPS interface unit error
Printing example SCS0101 GPS Interface Unit Error (RIGHT CPU)
Meaning A CPU module (right side in the above example) detected a GPS unit error or
time synchronization error.
Cause The following causes may be considered.
• Problem in the cable connecting the GPS unit and the GPS interface unit.
• Failure of the GPS interface unit
Action Check to see if a cable connecting the GPS unit and the GPS interface unit is
disconnected or cut. Also, check to see if a terminator is connected to the
ends of the cable. If everything is in place, replace the GPS interface unit.
Note If this message is displayed while the time synchronization method is V net
time synchronization, the CPU module may be faulty.

No.4130
Message name Recovery of GPS interface unit
Printing example SCS0101 GPS Interface Unit Recover (RIGHT CPU)
Meaning Time synchronization of the GPS unit detected by CPU module (right side in
the above example) is recovered. (This is a recovery message of No. 4129.)

No.4131
Message name Communication module lock
Printing example 1 SCS0101 Communication Module All Inputs/Outputs Locked NODE 01 SLOT
02
Printing example 2 SCS0101 Communication Module All Inputs Locked NODE 01 SLOT 02
Printing example 3 SCS0101 Communication Module All Outputs Locked NODE 01 SLOT 02
Meaning The communication module was locked by operation from the SENG. The
message varies depending on the locked range (inputs and outputs, inputs on-
ly or outputs only). The location of the communication module is also included
in the messages (such as node 1, slot 2).
Remark Forcing function, subsystem communication
Note Be sure to cancel the lock of the communication module that was locked.

No.4132
Message name Cancellation of Communication module lock
Printing example 1 SCS0101 Communication Module All Inputs/Outputs Unlocked NODE 01
SLOT 02
Printing example 2 SCS0101 Communication Module All Inputs Unlocked NODE 01 SLOT 02
Printing example 3 SCS0101 Communication Module All Outputs Unlocked NODE 01 SLOT 02
Meaning The lock of the communication module was cancelled by operation from the
SENG. The message varies depending on the locked range (inputs and out-

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-11
puts, inputs only or outputs only). The location of the communication module is
also included in the messages (such as node 1, slot 2).
Remark Forcing function, subsystem communication

No.4133
Message name Information of a diagnosis error in the received data of SCS Link Transmis-
sion.
Printing example SCS0101 SCS Link Transmission Receive Error Stn(SCS)=05 Code =
5041-8000
Meaning A diagnosis error has been found in the received data of SCS Link Transmis-
sion. The source station number (such as 05) and the station type (SCS in the
above example) that sent the Link Transmission are indicated in the message
text. The station type indicated in the message is the station type defined on
the SCS Link Transmission builder.
Cause The following causes may be considered. Check the error codes for more de-
tail.
• Stop or restart the sender station
• Problem in the communication path
• The definition of the SCS Link Transmission builder may contain errors.
Remark SCS Link Transmission
Error code The first four digits are an error code, and the next four digits are a cause
code. The error detail can be found from the descriptions of the both codes.
The error codes and cause codes are listed below.
The error code represents the type of error. The following table explains each
error code and the action you can take to fix the error.

Table 2.1-4 Message No. 4133 - Error Code List


Code (hexadecimal) Description Action
No data received with-
5041 in the reception inter-
val timeout value. Check the sender SCS and its communication path.
Time diagnosis found
5042
an error.
Communication proto-
Record the message content and report to Yokogawa’s
5043 col error (internal er-
service department.
ror)

The cause code represents the event that caused the problem and is logical
OR of the following codes.

Table 2.1-5 Message No. 4133 - Cause Code List


Code (hexa-
Errors Description Presumed Cause
decimal)
Communication error, or the
Communication stopped and
8000 No response sender station stopped or un-
data no longer arrived.
able to send outputs.
The CRC code of delay-rela-
CRC error in delay-related di- Temporary communication
2000 ted diagnosis information is
agnosis information error
not correct.
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-12
Table 2.1-5 Message No. 4133 - Cause Code List (Table continued)
Code (hexa-
Errors Description Presumed Cause
decimal)
Temporary communication
The CRC code of SCS Link
CRC error in communication error, or SCS Link Transmis-
1000 Transmission data is not cor-
data sion builder definition may
rect.
contain [Type] error.
Communication for acquiring Communication was interrup-
Equalization error of delay-re-
0400 delay-related diagnosis infor- ted or the sender station is
lated diagnosis information
mation stopped. stopped.
The application may contain
errors, or the setting in the
0100 Address error Illegal station number
database is inconsistent with
the setting of dipswitches.
Communication was updated
0040 Transmission delay occurred later than the transmission Communication delay
delay timeout time.
Time diagnosis error occur-
Time diagnosis error of the Time diagnosis error of the
0020 red in the sender, so that this
sender sender
date/time may not be correct.
Time diagnosis error occur-
Time diagnosis error of the red in the receiver, so that Time diagnosis error of the
0010
receiver this date/time may not be cor- receiver
rect.
The detected scan cycle is
0008 Illegal scan cycle Internal error
an illegal value 0.

No.4134
Message name Information of a diagnosis error recovery in the received data of SCS Link
Transmission.
Printing example SCS0101 SCS Link Transmission Receive Recover Stn(SCS)=05
Meaning The diagnosed reception error of SCS link transmission has been recovered.
The source station number (such as 05) and the station type (SCS in the
above example) are indicated in the message text. The station type indicated
in the message is the same station type defined on the SCS Link Transmission
builder.
(This is a recovery message of No. 4133.)
Cause The following causes may be considered.
• Recovery of the sender station
• Recovery of the communication path
• The errors in the SCS Link Transmission definition have been removed.
Remark SCS Link Transmission

No.4135
Message name SCS Link Transmission data lock
Printing example SCS0101 SCS Link Transmission Data Locked Stn(SCS)=02
Meaning The reception/transmission data for SCS Link Transmission (in the above ex-
ample, data received from station 2) were locked. The (SCS) in the message
text indicates the station type defined on the SCS Link Transmission builder.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-13
Remark Forcing function, SCS Link Transmission
Note Be sure to cancel the lock of the station that was locked.

No.4136
Message name Cancellation of SCS Link Transmission data lock
Printing example SCS0101 SCS Link Transmission Data Unlocked Stn(SCS)=02
Meaning The lock of reception/transmission data for SCS Link Transmission (in the
above example, data received from station 2) was cancelled. The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.
Remark Forcing function, SCS Link Transmission

No.4137
Message name Number of Locked Stations in SCS Link Transmission Exceeded
Printing example SCS0101 Number of Locks about SCS Link Transmission Exceeds the Limit =
3
Meaning The number of locked stations exceeded the limit (3 in the above example),
which is defined in SYS_FORCE_ LT FB as the number of stations allowed for
forcing.
Cause Operation from the SENG to lock too many stations.
Action Cancel SCS Link Transmission locks for some SCS.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB
Note You should not lock stations beyond the limit.

No.4138
Message name Recovery from exceeded number of locked stations in SCS Link Transmission
Printing example SCS0101 Number of Locks about SCS Link Transmission Within the Limit = 3
Meaning The number of locked stations fell within the limit (3 in the above example),
which is defined in SYS_FORCE_ LT FB as the number of stations allowed for
forcing. (This is the recovery message of No.4137.)
Cause Operation from the SENG.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No.4139
Message name Inter-SCS Safety Communication data lock
Printing example SCS0101 Inter-SCS Safety Communication Data Locked Dom=01 Stn=02
Meaning The Inter-SCS Safety Communication data received from a producer SCS (in
the above example, station 2 in domain 1) were locked.
The message for a lock of the local station (data produced by the station are
locked) is also output in the same format, showing its own domain number and
station number.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-14
Remark Forcing function, Inter-SCS Safety Communication
Note Be sure to cancel the lock of the station that was locked.

No.4140
Message name Cancellation of Inter-SCS Safety Communication data lock
Printing example SCS0101 Inter-SCS Safety Communication Data Unlocked Dom=01 Stn=02
Meaning The lock of Inter-SCS Safety Communication data received from a producer
SCS (in the above example, station 2 in domain 1) was cancelled.
The message of cancellation for the lock of local station (data produced by the
station are locked) is also output in the same format, showing its own domain
number and station number.
Remark Forcing function, Inter-SCS Safety Communication

No.4141
Message name Number of locked stations in Inter-SCS Safety Communication exceeded
Printing example SCS0101 Number of Locks about Inter-SCS Safety Communication Exceeds
the Limit = 3
Meaning The number of locked stations exceeded the limit (3 in the above example),
which is defined in SYS_FORCE_ BD FB as the number of stations allowed
for forcing.
Cause Operation from the SENG to lock too many stations
Action Cancel Inter-SCS Safety Communication locks for some SCS.
Remark Forcing function, Inter-SCS Safety Communication
Note You should not lock stations beyond the limit.

No.4142
Message name Recovery from exceeded number of locked stations in Inter-SCS Safety Com-
munication
Printing example SCS0101 Number of Locks about Inter-SCS Safety Communication Within the
Limit = 3
Meaning The number of locked stations fell within the limit (3 in the above example),
which is defined in SYS_FORCE_ BD FB as the number of stations allowed
for forcing. (This is the recovery message of No.4141.)
Cause Operation from the SENG
Remark SYS_FORCE_BD FB

No.4143
Message name Start of automatic scan period extension
Printing example SCS0101 Scan Period Extended from the Original Scan Period 100ms to
200ms

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-15
Meaning Automatic extension of the scan period of the application logic execution star-
ted. (In the above example, the original scan period of 100 ms was extended
to 200 ms.)
Cause The application caused heavy load on the SCS.
Remark SYS_SCANEXT FB, automatic scan period extension

No.4144
Message name Cancellation of automatic scan period extension
Printing example SCS0101 Scan Period Recovered to the Original Scan Period 100ms
Meaning Automatic extension of the scan period of the application logic execution is
cancelled. (In the above example, the scan period recovered to its original pe-
riod of 100 ms.)
Cause The load on the SCS caused by the application was reduced.
Remark SYS_SCANEXT FB, automatic scan period extension

No.4145
Message name Abnormal calculation occurred
Printing example 1 SCS0101 Calculation Error (XXXXXX) Program=PG01
Printing example 2 SCS0101 Calculation Error (XXXXXX) Program=PG01 FU/FB=UFB01
Meaning Abnormal calculation occurred in the application logic.
XXXXXX indicates the type of abnormal calculation. The types are as follows:
Div by Zero : Division by zero
Access to the Outside of Array : Access to the outside of an array
FPU Overflow : Overflow in the floating-point calculation
Cast Overflow : Overflow in casting
At “Program=”, the name of the program (POU name) where the abnormal cal-
culation occurred is indicated. If the abnormal calculation occurred in a user-
defined FU/FB, the POU name of that FU/FB is indicated at “FU/FB=.”
Cause Error in the application
Remark SYS_CERR FB

No.4146
Message name Recovery from abnormal calculation
Printing example 1 SCS0101 Calculation Recover (XXXXXX) Program=PG01
Printing example 2 SCS0101 Calculation Recover (XXXXXX) Program=PG01 FU/FB=UFB01
Meaning Indicates a recovery from the abnormal calculation occurred in the application
logic.
XXXXXX indicates the type of abnormal calculation. The types are as follows:
Div by Zero : Division by zero
Access to the Outside of Array : Access to the outside of an array
FPU Overflow : Overflow in the floating-point calculation

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-16
Cast Overflow : Overflow in casting
At “Program=”, the name of the program (POU name) where the abnormal cal-
culation occurred is indicated. If the abnormal calculation occurred in a user-
defined FU/FB, the POU name of that FU/FB is indicated at “FU/FB=.”
Cause The error in the application was corrected.
Remark SYS_CERR FB

No.4151
Message name Information of retainable data initialization
Printing example SCS0101 Retain Data Initialized
Meaning Retainable data have been initialized.
Cause • Database with different CRC codes or generation time was offline-down-
loaded to the SCS.
• Data saved in the memory with backup battery volatilized.
Action Set the setting values of the external communication function blocks with data
retaining function again.
Remark Data retaining function, external communication function blocks with data re-
taining function (ECWR_B, ECWR_I, ECWR_R), ACCUM FB, AGA_R FB

No.4152
Message name Online change of scan period
Printing example SCS0101 Scan Period Changed to 200ms
Meaning The scan period of the application logic was changed by online change down-
load.
Cause Operation from the SENG
Remark Online change download

No.4153
Message name Information of Inter-SCS Safety Communication data lock time-up
Printing example SCS0101 Inter-SCS Safety Communication Data Lock Elapsed the Specified
Period = 08:00:00
Meaning Inter-SCS Safety Communication lock exceeded the time limit (8 hours in the
above example) specified in SYS_FORCE_BD FB.
Action Check whether all Inter-SCS Safety Communication locks have been cancel-
led and cancel unnecessary locks.
Remark Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB

No.4154
Message name Information of forced cancellation of Inter-SCS Safety Communication data
locks
Printing example SCS0101 All Inter-SCS Safety Communication Data Unlocked.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-17
Meaning Locks of all the Inter-SCS Safety Communication data (reception/transmis-
sion) in the station were forcibly cancelled.
Cause Locks of all the Inter-SCS Safety Communication data were cancelled by us-
ing the SYS_FORCE_BD FB.
Remark Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB

No.4155
Message name Information of SCS Link Transmission status change.
Printing example SCS0101 SCS Link Transmission Data Status Set to TRUE Old=FALSE
Stn(SCS)=03
Meaning The data status of SCS Link Transmission (such as from station 03) has been
changed (For an example, changed from FALSE to TRUE). The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.
Remark Forcing function

No.4156
Message name Information of SCS Link Transmission definition change
Printing example SCS0101 SCS Link Transmission Definition Changed
Meaning SCS Link Transmission definitions were changed by online change download.
Cause Online change download was executed from the SENG.

No.4157
Message name Information of SCS Link Transmission wiring change
Printing example SCS0101 SCS Link Transmission Wiring Changed
Meaning SCS Link Transmission wirings were changed by online change download.
Cause Online change download was executed from the SENG.

No.4158
Message name Information of SCS Link Transmission lock time-up
Printing example SCS0101 SCS Link Transmission Data Lock Elapsed the Specified Period =
08:00:00
Meaning SCS Link Transmission lock continued exceeding the time limit (8 hours in the
above example) specified in SYS_FORCE_LT FB.
Action Check whether all SCS Link Transmission locks have been cancelled, and
cancel unnecessary locks.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No.4159
Message name Information of forced cancellation of SCS Link Transmission locks
Printing example SCS0101 All SCS Link Transmission Data Unlocked

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-18
Meaning Locks of all the locked SCS Link Transmission were forcibly cancelled.
Cause Locks of all SCS Link Transmission were cancelled by operation using
SYS_FORCE_LT FB.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No.4160
Message name Invalid password for Manual Operation FB
Printing example SCS0101 TAG001 Specified Invalid Password
Meaning The password string specified for Manual Operation FB (MOB_21, MOB_11,
MOA) from the HIS is invalid.
Cause The password entered from the HIS and the password set in Manual Opera-
tion FB did not match.
Action Enter the correct password for Manual Operation FB again.
Remark Manual Operation FB (MOB_21, MOB_11, MOA)

No.4161
Message name Information of Output IOM Shutdown
Printing example 1 SCS0101 All Output IOM Shutdown
Printing example 2 SCS0101 Output IOM Shutdown NODE 01 SLOT 02
Meaning An output IOM shutdown task is performed by a Shutdown FB (SYS_ALLSD
or SYS_IOSD). If the shutdown task is performed by SYS_IOSD, the output
module location for shutting down (node 1 and slot 2 in the above example) is
also included in the message.
Remark SYS_ALLSD, SYS_IOSD

No.4162
Message name Information of communication I/O definition change
Printing example SCS0101 Communication Definition Changed
Meaning The communication I/O definitions of the communication module were
changed by online change download.
Cause Online change download was executed from the SENG.

No.4163
Message name Information of communication I/O wiring change
Printing example SCS0101 Communication I/O Wiring Changed
Meaning The communication I/O wirings were changed by online change download.
Cause Online change download was executed from the SENG.

No.4164
Message name Information of disabling security level change

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-19
Printing example SCS0101 Security Levels Change Disabled
Meaning The security level change of the SCS by a password-authenticated operation
performed from SENG is disabled.
Remark SYS_SEC_CTL FB

No.4165
Message name Information of enabling security level change
Printing example SCS0101 Security Levels Change Enabled
Meaning The security level change of the SCS by a password-authenticated operation
performed from SENG is enabled.
Remark SYS_SEC_CTL FB

No.4166
Message name Information of communication module lock time-up
Printing example SCS0101 Communication Module Lock Elapsed the Specified Period =
08:00:00
Meaning The communication module lock continued exceeding the time limit (8 hours in
the above example) specified in SYS_FORCE_SC FB.
Action Check whether all communication module locks have been cancelled, and
cancel unnecessary locks.
Remark Forcing function, subsystem communication, SYS_FORCE_SC FB

No.4167
Message name Information of forced cancellation of communication module locks
Printing example SCS0101 All Communication Modules Unlocked
Meaning Locks of all communication modules were forcibly cancelled.
Cause Locks of all communication modules were cancelled by operation using
SYS_FORCE_SC FB.
Remark Forcing function, subsystem communication, SYS_FORCE_SC FB

No.4168
Message name Information of tag name change by online change download
Printing example SCS0101 Online Change Download Tag Name = TAG001 Changed
Meaning The tag name (TAG001 in the above example) of PASSWD FB or override FB
was changed by online change download.
Cause Online change download was executed from the SENG.

No.4169
Message name NVRAM diagnosis error
Printing example SCS0101 RIGHT NVRAM Diagnosis Error

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-20
Meaning An error was detected during diagnosis of NVRAM (nonvolatile memory) in a
CPU module (right side in the above example).
Cause NVRAM may be faulty.
Action Replace the applicable CPU module.

No.4170
Message name Flash memory diagnosis error
Printing example SCS0101 RIGHT Flash Memory Diagnosis Error
Meaning An error was detected during self-diagnosis of flash memory in a CPU module
(right side in the above example).
Cause Part of data stored in flash memory was destroyed, or flash memory may be
faulty.
Action If the SCS is in a single CPU module configuration, the SCS will not be able to
start when this CPU restarts next time. It is necessary to change the CPU
module right away.
If the SCS is configured with redundant CPU modules, the control will switch
to the other module after detecting this error, and the module where the error
occurs is restarted as a standby module.
If the error is caused by damage to the data in the flash memory, data in the
control side will be copied to the standby module where the error occurs, and
that module will then recover from abnormal to normal status.
If the error is caused by the physical damage of the flash memory, this system
alarm will occur even after the damaged CPU is switched to standby. Under
this circumstance, it is necessary to change the damaged CPU module.

No.4172
Message name Information of resource change by online change download
Printing example SCS0101 Online Change Download Resource Changed (Total POU=10)
Meaning The resource was changed by online change download. The resource defines
total number of POU (10 in the above example).
Cause Online change download was executed from the SENG.
Action Check and confirm that the total number of POU indicated in this message is
equal to the total number of POU indicated by Database Validity Check Tool.

No.4173
Message name Completion of writing to flash memory
Printing example SCS0101 Writing XXXXXX to Flash Memory Succeeded
Meaning Writing to flash memory in a CPU module was normally completed.
XXXXXX: Indicates the data written. The items of the data are as follows.
Security Password : Security password
System Database : System database
Integration Database : Integration database
Variable Database : Variable database

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-21
Difference Data : Difference data

Cause When online change download from SENG to SCS was executed or the pass-
word was changed, data was normally written to flash memory.

No.4174
Message name Failed to write to flash memory
Printing example SCS0101 Writing XXXXX to Flash Memory Error
Meaning Write data error was detected during check at flash memory write in a CPU
module.
XXXXXX: Indicates the data attempted to be written. The items of the data are
as follows.
Security Password : Security password
System Database : System database
Integration Database : Integration database
Variable Database : Variable database
Difference Data : Difference data

Cause Flash memory may be faulty.


Action If the SCS is in a single CPU module configuration, the CPU module continues
the operation even if this error occurs. However, the SCS will not start properly
when this CPU module restarts next time. It is necessary to change the CPU
module as soon as possible.
On a dual-redundant CPU module configuration SCS, if this writing error to
flush memory occurs on one of the CPU modules, the CPU module will be
failed and operation is continued with the other CPU module. It is necessary to
change the failed CPU module right away. If writing to the flash memories in
both CPU modules fails, the SCS will not be able to start when the CPU re-
starts. Under this circumstance, it is necessary to change both CPU modules
right away.
Remark Flash memory diagnosis

No.4175
Message name Failed to update external communication data
Printing example SCS0101 External Data Refresh Failed
Meaning The SCS has failed to update external communication data. This data is refer-
enced in communications with CENTUM stations and Modbus, so when this
error occurs, data will not be updated in those stations.
Cause The CPU processing time allocated for the external communication function
processing was not sufficient. As a result, processing to update the external
communication data is not performed.
Action Reduce the communication load on the SCS. If this error occurs regularly, re-
view the balance between the application logic amount and the scan period.

No.4177
Message name Information of SCS security level change

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-22
Printing example SCS0101 Security Level Changed to 1
Meaning The security level of the SCS was changed (1 in the above example).
Cause The security level of the SCS was changed. The security level can be changed
from the SENG or SYS_SECURE FB.
Note Be sure to revert the security level to “2.”

No.4178
Message name Information of security level time-up
Printing example SCS0101 Security Level = 1 Elapsed the Specified Period = 08:00:00
Meaning The security level is set to “1” for the duration exceeding the time limit (8 hours
in the above example) specified in SYS_SECURE FB.
Cause The security level has not been reverted.
Action Revert the security level to “2.”
Remark SYS_SECURE FB
Note When the security level is “0,” the message is not generated.

No.4179
Message name Information of communication I/O module output enabled operation
Printing example SCS0101 Communication Modules Output Enabled
Meaning The communication modules are enabled for output.
Remark I/O Channel Status dialog box, SYS_STAT_SC FB
Note This is irrelevant for enabling the output of the safety I/O modules. If you have
done the Output enabled operation for the safety output modules, confirm the
message 4181.

No.4180
Message name Information of password change
Printing example SCS0101 Security Level = 1 Password was Changed
Meaning The password for the SCS security level (1 in the above example) was
changed.
Cause The password was changed from the SENG.
Note The message of No. 4173 is also generated after this alarm.

No.4181
Message name Information of output enabled operation
Printing example SCS0101 Output Enabled
Meaning The output enabled operation for the SCS was performed from the SENG.
When all the safety module’s output channels go into “output-enabled” state,
the SCS’s operating mode changes to “Running.”
Remark I/O Channels Status dialog box, SYS_STAT_FB

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-23

No.4182
Message name Information of output module start operation
Printing example SCS0101 IOM Started NODE 01 SLOT 02
Meaning An output module (node 1 and slot 2 in the above example) was started from
the SENG.
Remark SCS State Management window

No.4183
Message name Request to upload SOE to SENG
Printing example SCS0101 SOE Save Request
Meaning This notification prompts to upload the event information collected on the SCS
to SENG.
Cause This message is generated every time 12,000 events have occurred on the
SCS.
Action Start SOE Viewer on SENG and upload events from SCS.
Remark SOER function
Note This system alarm is generated even if SOE Viewer is started periodically.
Events can be uploaded from the SCS by starting SOE Viewer and displaying
the latest event.

No.4184
Message name Notification on saving SOE trip signal file in SCS
Printing example SCS0101 SOE Trip Signal File No.= 01 Saved
Meaning The SOE trip signal file (No. 01 in the above example) was saved in SCS.
Action Start SOE Viewer on SENG and upload the events in the file.
Remark SOER function
Note When uploading the events is complete, the trip signal files need to be reset.
Up to two trip signal files can be held in the SCS. The trip signal files can be
reset by starting the Message Cache Tool and initializing the trip information.

No.4185
Message name Information of variable value change
Printing example 1 SCS0101 Variable Set to 10.0 Old = 5.0 Variable = VAR001
Printing example 2 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01
SLOT 02
Printing example 3 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01
SLOT 02 CH 03
Printing example 4 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 Stn=02
No=025
Meaning The value of the variable (VAR001 in the above example) was changed from
the SENG. For a communication I/O, a variable corresponds to the communi-
cation module location (as shown in example 2, node 1, slot 2) is also included

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-24
in the message. For an I/O variable, a variable corresponds to the variable lo-
cation (as shown in example 3, node 1, slot 2, channel 3) is also included in
the message.
The VAR001 in the above printing example 4 is the instance name of the func-
tion block that accesses the data of SCS Link Transmission. The related sta-
tion number and bit number are also printed.
Remark Forcing function

No.4186
Message name Information of lock time-up
Printing example SCS0101 Lock Elapsed the Specified Period = 08:00:00
Meaning Lock continued exceeding the time limit (8 hours in the above example) speci-
fied in SYS_FORCE FB.
Action Check whether all locks have been cancelled, and cancel unnecessary locks.
Remark Forcing function, SYS_FORCE FB

No.4187
Message name Information of forced cancellation of locks
Printing example SCS0101 All Variables Unlocked
Meaning Locks of all variables were forcibly cancelled.
Cause Locks of all variables were cancelled by operation using SYS_FORCE FB.
Remark Forcing function, SYS_FORCE FB

No.4188
Message name Start of online change download
Printing example SCS0101 Online Change Download (System Database) Start
Meaning Online change download to the system database was started.
Remark Download function

No.4189
Message name Completion of online change download
Printing example SCS0101 Online Change Download (System Database) Complete
Meaning Online change download to the system database was normally completed.
Remark Download function

No.4190
Message name Online change download error
Printing example SCS0101 Online Change Download (System Database) Error = 5340-0001
Meaning Online change download to the system database ended with an error.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-25
Cause/Action Causes and actions vary depending on the error code.

Table 2.1-6 Message No. 4190 - Error Causes and Actions


Error code Cause Action
Set the security level to “1” and then execute online
5340-**** The security level stays “2.”
change download again.
Record the message content and report to Yokoga-
Others Internal error
wa’s service department.

No.4191
Message name Completion of I/O definition rewriting
Printing example SCS0101 IOM Definition Changed NODE 01 SLOT 02
Meaning I/O definition was changed by online change download to the system data-
base. The I/O module position is included in the message (node 1, slot 2 in the
above example).
If the number following “SLOT” is 00, it means that the node definition informa-
tion has been changed. The node definition information is changed when you
do the following:
• Change comments of the node
• Add or delete I/O modules of the node
• Change slots of the I/O modules of the node
• Change the model of the I/O modules of the node

No.4192
Message name Information of override state time-up
Printing example SCS0101 Override Elapsed the Specified Period = 08:00:00
Meaning Override continued exceeding the time limit (8 hours in the above example)
specified in SYS_OVR FB.
Action Check whether overrides were released, and release unnecessary overrides.
Remark SYS_OVR FB

No.4193
Message name Information of forced release of all overrides
Printing example SCS0101 All Overrides Released
Meaning The overrides for all variables were forcibly released.
Cause The overrides for all variables were forcibly released by operation using
SYS_OVR FB.
Remark SYS_OVR FB

No.4194
Message name Information of override enabled state time-up
Printing example SCS0101 Enabled OVR FB Elapsed the Specified Period = 08:00:00

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-26
Meaning The override enabled state continued exceeding the time limit (8 hours in the
above example) specified in SYS_OVR FB.
Cause Check override FB in the override enabled state, and release unnecessary
override enabled state.
Remark SYS_OVR FB

No.4195
Message name Information of communication I/O data status change
Printing example SCS0101 Communication Data Status Set to TRUE Old = FALSE NODE 01
SLOT 02 Definition 001
Meaning The data status of the communication I/O (such as node 1, slot 2, definition 1
in the above example) was changed (such as from FALSE to TRUE) from the
SENG.
Remark Forcing function

No.4196
Message name Invalid password for PASSWD FB
Printing example SCS0101 TAG001 PASSWD FB Specified Invalid Password
Meaning The password string specified for PASSWD FB from the HIS is invalid.
Cause The password entered from the HIS and the password set in PASSWD FB did
not match.
Action Specify the correct password for PASSWD FB and enter it again.
Remark PASSWD FB

No.4197
Message name Information on active PASSWD FB time-up
Printing example SCS0101 Activated PASSWD FB Elapsed the Specified Period = 10:00:00
Meaning PASSWD FB has been active exceeding the time limit (10 hours in the above
example) specified in SYS_PSWD.
Action Deactivate PASSWD FB that is not required to be active.
Remark SYS_PSWD FB

No.4198
Message name Information on forced reset of PASSWD FB
Printing example SCS0101 All PASSWD FB Reset to OFF
Meaning The outputs of all active PASSWD FBs were forcibly set to OFF.
Cause The outputs of all active PASSWD FBs were forcibly inactivated (reset to OFF)
by operation using SYS_PSWD FB.
Remark SYS_PSWD FB

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<2.1 System Alarms (Message Numbers 4101 through 4199)> 2-27

No.4199
Message name Override communication error
Printing example SCS0101 TAG001 Override Communication Error (Instance = OVR001)
Meaning Despite an attempt to operate override on the FB OVR001 (in the above ex-
ample) with the tag name TAG001 (in the above example) from HIS, communi-
cation error has occurred.
Cause A temporary communication error occurred, and the SCS detected the prob-
lem of the communication data.
Action Execute override operation again.
Remark SYS_OVR FB

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3. Details of Output Messages in Common with CENTUM> 3-1

3. Details of Output Messages in


Common with CENTUM
This section describes the details of output messages used in common with CENTUM.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-2

3.1 Safety Control Station Error Occurrence


and Recovery Messages (Message
Numbers 0001 through 0094)
This section describes messages having the same message numbers as those of the
CENTUM control station.

No.0001
Message name Reset start of safety control station
Printing example SCS0101 RIGHT Manual Reset Start
Meaning A CPU module (right side in the above example) of the safety control station
(station name = SCS0101) was reset and started.
Cause Start operation from the SENG or from the front switch of the CPU module

No.0003
Message name Safety control station automatic reset start
Printing example SCS0101 RIGHT Automatic Reset Start
Meaning An error occurred in the displayed CPU module (right side in the above exam-
ple) of the safety control station (station name=SCS0101), which caused the
safety control station to be automatically reset started.
Cause CPU module is faulty.

No.0005
Message name Power ON initial cold start of safety control station
Printing example SCS0101 Power ON (Cold Start)
Meaning The safety control station (station name = SCS0101) performed the initial cold
start processing after it was powered ON.
Cause Recovery from power failure
Note The safety control station always performs the initial cold start processing after
recovery from power failure.

No.0009
Message name Transfer of control right of safety control station
Printing example SCS0101 Control Transfer
Meaning A transfer of control right occurred in the redundant safety control station (sta-
tion name = SCS0101).
Cause • The CPU module on one side was stopped.
• An error occurred in the CPU module on one side.
Action The CPU module on the standby side takes over control. Replace the CPU
module that was stopped.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-3

No.0011
Message name Fail information of safety control station
Printing example SCS0101 RIGHT Fail (xxxxxxxx Code= yyyy yyyy yyyy yyyy)
Meaning A CPU module (right side in the above example) of the safety control station
(station name = SCS0101) failed.
Cause The causes are indicated by “causes (xxxxxxxx)” and a code. For more infor-
mation, see the following table.

Table 3.1-1 Message No. 0011 - Cause List


Causes Code (hex 16 digits) Auto re-
Item Description
xxxxxxxx yyyy yyyy yyyy yyyy start
Stop by operation of the front switch of
SW STOP No
the CPU module
-
V STOP Stop instruction via control bus No
DC STOP Stop due to power failure No
NSR3(*1)
An error occurred during CPU module er-
CPU CPU INTSTS(*1) ror check.
Yes
module DOWN ERRSTS1(*1) NSR3, INTSTS, ERRSTS1 and
stop ERRSTS2 are detailed error codes.
ERRSTS2(*1)
SELF-
Stop after software detected an error No
STOP
UN- (*2)
Stop due to unknown cause No
KNOWN
RESTART Restart after software detected an error Yes

*1: If this error message is displayed, report the display contents of causes (xxxxxxxx) and code to Yokogawa’s service depart-
ment.
*2: Refer to the following “Table 2.1-4 Error Codes and Solutions.”

Table 3.1-2 Error Codes and Solutions


Code (hex; 16 digits) Error Solution
Check to see if the application logic con-
Zero division occurred when running
0000 5090 yyyy yyyy tains zero division or not, and correct the
the application logic.
application logic if it contains.
The application logic is trying to ac- Check the application and find out which
0000 5091 yyyy yyyy cess an array datum beyond the logic program is accessing the out-of-range
scope of the array. array data and correct the error.
The database inconsistence is de-
tected. It may be caused by restart-
0000 50a9 yyyy yyyy Run offline downloading.
ing the SCS without releasing the
brake point.
The firmware (Revision F4) in the For a system that contains Optical ESB
4000 3BF1 0255 8082 CPU module is too old to support the Bus Repeater modules, the firmware of
(*1) system with Optical ESB Bus Re- CPU with the proper revision number
peater modules. should be used.
An error has been detected in the
I/O unit of the CPU module.
If one of the redundant CPU modules has
SCSV1-S : There may be a failure in
stopped, message No. 0787 is generated
the I/O unit of the CPU module.
4000 3BF1 xxxx xxxx at the same time.
SCSP2-S: There may be a failure in
Refer to the explanation of message No.
the I/O unit of the CPU module or
0787.
the I/O communication is posing
heavy load on the CPU.
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-4
Table 3.1-2 Error Codes and Solutions (Table continued)
Code (hex; 16 digits) Error Solution
The CPU model and station model Match the CPU model and station model
0000 5010 yyyy yyyy
are inconsistent. with each other.
Check the application and find out what
The calculation in a running applica-
FFFF 000B 0000 000F caused the calculation overflow and then
tion overflowed.
modify it.
If this error message is displayed, report
the display contents of causes (xxxxxxxx)
Other Other
and the code to Yokogawa’s service de-
partment.

*1: This code is not generated in SCSP2-S

Action If the safety control station operates normally after restarting automatically,
continue operation. If the safety control station stops after restarting automati-
cally, replace the CPU module.

No.0013
Message name AC power supply failure of safety control station
Printing example SCS0101 AC Fail (Time 05.02.01 18:45)
Meaning AC power of the safety control station (station name = SCS0101) failed and
was then recovered. The date and time indicated are when the power failed.
This message is output after the power is recovered.
Cause The voltage of AC power supply dropped, or a power failure occurred.
Note The SCS has been initialized and then started.

No.0015
Message name Self-diagnosis error of clock inside CPU module
Printing example SCS0101 RTC Diagnose Error Code=0001
Meaning An error was detected during self-diagnosis of the clock inside the safety con-
trol station (station name = SCS0101).
Code=0001: Check pattern mismatch
Code=0002: Inappropriate date/time value
Code=0003: Date/time not updated

Action Replace the CPU module.

No.0017
Message name ROM checksum error of CPU module
Printing example SCS0101 RIGHT ROM Sum Check Error
Meaning A ROM checksum error was detected in the indicated CPU module (right side
in the above example) of the safety control station (station name = SCS0101).
Action Replace the CPU module.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-5

No.0021
Message name Internal task error of safety control station
Printing example SCS0101 Internal Error TASK=TSK1 Code=100 Error=1000 - E0F0
Meaning An error state was detected during the execution of a task (TSK1 in the above
example) in the safety control station (station name = SCS0101). “TASK”,
“Code” and “Error” indicate detailed error information.
Cause This is a software problem.
Action Report the message content to Yokogawa’s service department.

No.0023
Message name Mapping block fatal error
Printing example SCS0101 Block TAG001 Return Error 8E04 and stop
Meaning An execution disabled error was detected during the execution of a mapping
block (TAG001 in the above example) in the safety control station (station
name = SCS0101).
Cause There is a problem in the integration DB. “Error” indicates detailed error infor-
mation.
Action Report the message content to Yokogawa’s service department.

No.0025
Message name Function control word error
Printing example SCS0101 No Block Control Word for Block Type=1804
Meaning The internal program that corresponds to the block type code of the safety
control station (station name = SCS0101) does not exist. “Type” indicates de-
tailed internal information.
Cause This is an internal error at task initialization.
Action Report the message content to Yokogawa’s service department.

No.0027
Message name Mapping block record information error
Printing example SCS0101 TAG001 Block Bad Record No = 3
Meaning There is a bad record in the mapping block (TAG001 in the above example) of
the safety control station. “No” indicates the bad record number in the data-
base.
Cause The mapping block and the record block number do not match.
Action Report the block type and record number where an error occurred to Yokoga-
wa’s service department.
Note Do not perform online change download after this alarm occurred.

No.0033
Message name Online downloading abnormal end

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-6
Printing example SCS0101 Online Download Error Code=9402 - 0000
Meaning Online change download of the safety control station (station name =
SCS0101) ended with an error. “Error Code” indicates detailed internal infor-
mation.
Cause/Action See the following table.

Table 3.1-3 Message No. 0033 - Error Code List


Code Error Contents Cause Action
9402
Online change
9403 The SCS was reset and started
downloading ab- Execute offline download.
9404 during online change download.
normal end
9405
Report the display content of the code
Others Internal error Internal error
to Yokogawa’s service department.

No.0041
Message name Safety control station fan alarm
Printing example SCS0101 Fan (SCU N1) Alarm
Meaning A cooling fan of the safety control station (station name = SCS0101) is abnor-
mal. One of the following items is displayed in the parentheses in the above
example.
SCU N1: Left side fan
SCU N2: Right side fan

Cause The cooling fan stopped or its revolution is abnormal.


Action Replace the failed fan unit.
Remark HKU function

No.0042
Message name Recovery from safety control station fan alarm
Printing example SCS0101 Fan(SCU N1) Recover
Meaning The cooling fan of the safety control station (station name = SCS0101) recov-
ered. The content in the parentheses in the above example is the same as
message No. 0041. (This is a recovery message of No. 0041.)
Remark HKU function

No.0043
Message name Safety control station temperature alarm
Printing example SCS0101 Temperature(RIGHT BATTERY) Alarm
Meaning This is a temperature rise alarm of the safety control station (station name =
SCS0101). One of the following items is displayed in the parentheses in the
above example.
RIGHT BATTERY: Battery of the right side CPU module
LEFT BATTERY: Battery of the left side CPU module

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-7
AIR IN: Air inlet
AIR OUT: Air outlet

Cause The CPU module temperature exceeded the specified value.


Action After checking the operation of the cooling fans, report to Yokogawa’s service
department as necessary.
Remark HKU function

No.0044
Message name Recovery from safety control station temperature alarm
Printing example SCS0101 Temperature(RIGHT BATTERY) Recover
Meaning The temperature of the safety control station (station name = SCS0101) recov-
ered normally. The content in the parentheses in the above example is the
same as message No. 0043. (This is a recovery message of No. 0043.)
Remark HKU function

No.0045
Message name Power supply module alarm of safety control station
Printing example SCS0101 RIGHT PSU Alarm
Meaning The power supply module of a CPU node (right side in the above example) of
the safety control station (station name = SCS0101) is abnormal.
Cause Power supply module failure
Action Replace the applicable power supply module.

No.0046
Message name Recovery from power supply module alarm of safety control station
Printing example SCS0101 RIGHT PSU Recover
Meaning The power supply module of a CPU node (right side in the above example) of
the safety control station (station name = SCS0101) recovered normally. (This
is a recovery message of No. 0045.)

No.0047
Message name Battery alarm of CPU module
Printing example SCS0101 RIGHT Battery Alarm
Meaning A battery of the CPU module (right side in the above example) of the safety
control station (station name = SCS0101) is abnormal.
Cause The battery switch is OFF, or the battery is faulty.
Action Make sure that the switch of the applicable battery is ON. If the above mes-
sage occurs even if the battery switch is ON, replace the battery.
Remark HKU function

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-8

No.0048
Message name Recovery from battery alarm of CPU module
Printing example SCS0101 RIGHT Battery Recover
Meaning A battery of the CPU module (right side in the above example) of the safety
control station (station name = SCS0101) recovered normally. (This is a recov-
ery message of No. 0047.)
Remark HKU function

No.0055
Message name Information of same frame reception in online change download communica-
tion
Printing example SCS0101 Received Same Online Download Frame Code=1 Frame=3
Meaning The same communication frame was received twice during the execution of
online change download. “Code” and “Frame” indicate detailed internal infor-
mation.
Action Execute online change download again.

No.0057
Message name Information of online change download error
Printing example SCS0101 Online Download Error Call Code=9601 - 0000 Data=91,0,0,0
Meaning An error occurred during the execution of online change download of the safe-
ty control station (station name = SCS0101). “Code” and “Data” indicate de-
tailed internal information.
Cause This error occurs if error data cannot be saved on the safety control station
side.
Action It is necessary to determine an action to take based on the “Code” and “Data”
information. Report the display contents of “Code” and “Data” to Yokogawa’s
service department.
Note Do not execute online change download after this alarm occurred.

No.0059
Message name Information of recovery from node power failure
Printing example SCS0101 FIO NODE Power On FIO NODE 02
Meaning An I/O node (2 in the above example) of the safety control station (station
name = SCS0101) recovered from power failure.

No.0063
Message name ESB bus error
Printing example SCS0101 FIO-BUS Fail FIO BUS No.1
Meaning An error occurred on one side (No. 1 in the above example) of the ESB buses
of the safety control station (station name = SCS0101).
Cause This is an ESB bus error on one side.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-9
Action SSB401, SEC402/SEC401 or ESB bus failure may be considered as an error
cause. Take appropriate action in the following:
• Check to see if the ESB bus cables are connected correctly. Check for in-
correct connection or bad connection of the cables, or check the termina-
tors of the bus.
• Check to see if one SSB401 is causing a bus error of the entire buses ac-
cording to the following procedure.
Pull out the ESB bus connector of each SSB401 that connects to the cor-
responding bus, one by one, from the node.
Wait for two to three seconds, and if “Recover” is not printed, insert the
ESB bus connector again, and pull the bus connector of the next node.
If “Recover” is printed, the bus connector of the SSB401 that was pull out
at that time is faulty, so replace the SSB401.
• If no recovery was made even after the bus connectors of all nodes were
pulled out, the SEC402/SEC401 may be faulty. In such a case, replace
the SEC402/SEC401.
• If no recovery was still made, press the [START/STOP] button on the
CPU module’s front panel on the control side twice, and switch the control
right of the CPU module. Replace the CPU module after restarting.
If the bus does not recover even after these operations, the error may be rela-
ted to the ESB bus cable (T-shape connector and so on). Replace the ESB
bus cable.
Note This message is generated if all the I/O nodes, excluding the CPU node, be-
come abnormal.
However, if a system contains Optical ESB Bus Repeater module, when all the
I/O nodes directly connected to/from SEC402/SEC401 (i.e., the I/O nodes not
connected via Optical ESB Bus Repeater module), become abnormal, but the
I/O nodes connected via the Optical ESB Bus Repeater module are normal,
this message is not generated.

No.0064
Message name Normal recovery of ESB bus
Printing example SCS0101 FIO-BUS Recover FIO BUS No.1
Meaning The ESB bus indicated in the message recovered normally. (This is a recovery
message of No. 0063.)

No.0065
Message name Failure of ESB Bus Interface module (SSB401) of node
Printing example SCS0101 SBS Fail FIO NODE 02 SBS RIGHT
Meaning An error occurred in an ESB Bus Interface module (right side in the above ex-
ample) of an I/O node (2 in the above example) of the safety control station
(station name = SCS0101).
Cause One of the following causes may be considered.
• ESB Bus Interface module becomes abnormal.
• Connection route to the ESB Bus Interface module becomes abnormal.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-10
• For the I/O nodes that are connected via Optical ESB Bus Repeater mod-
ule, the Optical ESB Bus Repeater module related hardware such as
module or Fiber-optic cable may have problem.
Action If an I/O node routed through the Optical ESB Bus Repeater related devices
becomes abnormal, the erroneous device can be identified according to the
content of the messages or the LED status so as to replace the damaged de-
vice. If all the I/O nodes routed through the Optical ESB Bus Repeater related
devices become abnormal, the error may have occurred in the Optical ESB
Bus Repeater module related hardware such as module or Fiber-optic cable.
Moreover, if the Optical ESB Bus Repeater modules are mounted in the
SNT10D, the error may be caused by the failure of a power supply module of
SNT10D unit.

No.0066
Message name Normal recovery of ESB Bus Interface module (SSB401) of node
Printing example SCS0101 SBS Recover FIO NODE 02 SBS RIGHT
Meaning An ESB Bus Interface module (right side in the above example) of an I/O node
(2 in the above example) of the safety control station (station name =
SCS0101) recovered normally. (This is a recovery message of No. 0065.)

No.0067
Message name Failure of power supply module of node
Printing example SCS0101 PSU Fail FIO NODE 02 PSU RIGHT
Meaning An error occurred in a power supply module (right side in the above example)
of an I/O node (2 in the above example) of the safety control station (station
name = SCS0101).
Cause Failure of a power supply module of an I/O node
Action Replace the power supply module of the applicable node.
Note When the message shows node 1, it indicates that an error occurred in a PSU
for the CPU node.

No.0068
Message name Normal recovery of power supply module of a node
Printing example SCS0101 PSU Recover FIO NODE 02 PSU RIGHT
Meaning The power supply module of the I/O node indicated in the message (2 in the
above example) recovered normally. (This is a recovery message of No.
0067.)

No.0069
Message name Error before database download to I/O module
Printing example SCS0101 IOM Download Error=A701
Meaning Database download to the I/O module (IOM) can not be started.
Cause/Action The cause and action vary depending on the content of the error.
• A701

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-11
This message occurs when attempting to download to an IOM while an-
other IOM download is still running. Only one IOM download can be per-
formed at one time, so please wait for the other IOM download to com-
plete before running an IOM download operation again.
• A72C
Automatic IOM download to a standby side I/O module is running. This
error occurs if IOM download to the same I/O module is manually execu-
ted from the SENG or online change download is executed to make
changes in I/O parameter settings while automatic IOM download is run-
ning.
• 5135
This message occurs when attempting to download to an IOM even
though it is running normally.
• Others
Report the error display content to Yokogawa’s service department.

No.0081
Message name Failure of I/O module
Printing example SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code=5101
Meaning An error occurred in the I/O module mounted in slot 1 of node 1 (CPU node) of
the safety control station (station name = SCS0101).
Cause For more information about error codes, see the following table.
Action Replace the applicable I/O module.

Table 3.1-4 Error Details of Message No. 0081 - Errors of Analog Input Modules and Contact I/O Mod-
ules
Error code Description of error
The communication between CPU and I/O modules encounters a no-response error.
5101 This error is caused either by the I/O module abnormality or by the communication
route abnormality.
The type of the I/O module defined on the SENG and the type of the I/O module
5102
mounted does not match. Check type of the I/O module.
The setting information defined on the SENG and the I/O module setting information
5103
do not match. Execute IOM download.
A hardware error of the I/O module was detected. Check detailed error causes in the
5104
IOM report.
A setting error of the I/O module. Check detailed error causes in the IOM report (field
5105
side connector disconnection, field power supply/wiring problem, etc.)
The I/O module recovered from an error state. Check detailed error causes in the IOM
5106
report.
The error that actuated the output shutoff switch occurred. Check detailed error cau-
5107 ses in the IOM report. When this error occurred, start the I/O module after recovering
from the error.
A communication data check error was detected between the CPU and the I/O mod-
5111, 5112, 5113 ule. A failure of the I/O module or a problem of the communication path up to the I/O
module may be the cause.
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-12
Table 3.1-4 Error Details of Message No. 0081 - Errors of Analog Input Modules and Contact I/O Mod-
ules (Table continued)
Error code Description of error
An error was detected in the redundant control part of the I/O module. Replace the I/O
module.
However, when two I/O modules in single configuration are changed to dual-redun-
dant configuration and online change download is performed, this error may be detec-
5114, 5115
ted if a connector cable is plugged to only one of the two modules. In this case, plug
the connector cables to both modules. Recovery from this error is notified with system
alarm message No.0082 “Normal recovery of I/O module”, and there is no need to re-
place the I/O modules.
5116, 5117 An I/O module error was detected. Replace the I/O module.
5118 An SCS internal error (SCS database error) was detected.

Table 3.1-5 Error Details of Message No.0081 – Errors on ALR111/ALR121/ALE111 Modbus Slave and
ALE111 DNP3 Slave
Error Code Cause/Action
The communication between CPU and I/O modules encounters a no-response error.
C580 This error may be caused by the I/O module abnormality, communication route abnor-
mality or an abnormality other than C581 to C583 depicted.
The communication program is not downloaded to the communication module. Run
C581
IOM download.
The communication program in the communication module is not the program for
C582
Modbus slave communication/DNP3 slave function. Run IOM download.
The physically installed communication module shows a different model name from
C583 the communication module defined in SENG. Check the model of the communication
module.

Table 3.1-6 Error Details of Message No.0081 - ALR111/ALR121 Subsystem Communication


Error Code Cause/Action
No response from the communication module due to communication module abnor-
A33D
mality. Change the communication module.
A33E Error occurred in the communication route between CPU and node.
The communication program is not downloaded to the communication module. Run
C581
IOM download.
The communication program in the communication module is not the program for the
C582
communication defined in SENG. Run IOM download.
The physically installed communication module shows a different model name from
C583 the communication module defined in SENG. Check the model of the communication
module.
C585 Error is found by self-diagnosis. Change the communication module.
The communication module is reset due to online change download or the IOM down-
C598
loading.
C599 Downloading to database.
C59A Downloading communication program.
Error found after resetting the communication module. Change the communication
C5C1
module.
Failed to download the communication program. Waiting time for shifting to the down-
C5C6 loading mode of the communication program exceeded the time limit. Start IOM
download again.
Failed to download the communication program. Processing time for downloading the
C5C7
communication program exceeded the time limit. Start IOM download again.
Communication module encountered an error and stopped. Change the communica-
C5E2
tion module.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-13

No.0082
Message name Normal recovery of I/O module
Printing example SCS0101 IOM Recover FIO NODE 01 SLOT 01
Meaning The I/O module mounted in slot 1 of node 1 in the safety control station (sta-
tion name = SCS0101) recovered normally. (This is a recovery message of
No. 0081.)

No.0083
Message name I/O module database error occurred
Printing example SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
Meaning An error occurred in the database on the I/O module mounted in slot 1 of node
1 in the safety control station (station name = SCS0101).
Cause The database on the I/O module and the database on the SCS do not match.
The following causes may be considered.
• IOM download has not been executed.
• IOM failure.
Action If this error occurred after replacing a module or at startup, the database might
not have been downloaded to the I/O module. Execute IOM download.
If this error occurred during I/O module operation, the I/O module may be faul-
ty. Replace the I/O module.

No.0085
Message name I/O module communication error occurred
Printing example SCS0101 IOM Communication Error FIO NODE 01 SLOT 01 RIGHT
Meaning An error occurred in one of the SB buses (right side in the above example). An
error occurred when accessing the I/O module mounted in slot 1 of node 1 in
the safety control station (station name = SCS0101).
Cause If this error occurred on all input modules within the same node, an I/O module
may be faulty, or the backboard bus of the node may be faulty. Or, an ESB bus
(right side in the above example) or an SSB401 (right side in the above exam-
ple) may be faulty, or they may not be connected properly.
Action Report to Yokogawa’s service department.

No.0086
Message name Recovery from I/O module communication error
Printing example SCS0101 IOM Communication Recover FIO NODE 01 SLOT 01 RIGHT
Meaning A communication error with the I/O module mounted in slot 1 of node 1 in the
safety control station (station name = SCS0101) recovered. (This is a recovery
message of No. 0085.)

No.0087
Message name Node error occurred

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-14
Printing example SCS0101 NODE Fail FIO NODE 02
Meaning An error occurred in node 2 of the safety control station (station name =
SCS0101).
Cause One of the following causes may be considered.
• A power failure occurred in the node, or both of the two ESB buses are
abnormal.
• Both SSB401 are abnormal.
• For the I/O nodes that connected via Optical ESB Bus Repeater module,
the Optical ESB Bus Repeater module related hardware such as module
or Fiber-optic cable may have problem.
Action Report to Yokogawa’s service department.

No.0088
Message name Normal recovery of node
Printing example SCS0101 NODE Recover FIO NODE 02
Meaning The node indicated in the message recovered normally. (This is a recovery
message of No. 0087.)

No.0089
Message name Subsystem communication error
Printing example SCS0101 SS-COM Error FIO NODE 01 SLOT 01 PORT 01 STN001 Code=
A3B0
Meaning A communication error occurred between the indicated communication module
and the subsystem.
Cause/Action The error details can be found in the instruction manuals of the connected
subsystem. See the manuals for error details.
The error codes that irrelevant to the connected subsystems are shown.

Table 3.1-7 Error Details of Message No.0089 - Errors that irrelevant to subsystems
Code Error Cause/Action
A391 Driver Busy Occurs when sending or receiving.
This message occurs when carrier detection fails due to the
A392 Communication Line Busy CD line is energized within the transmission enable monitor-
ing time.(*1)
This message occurs when clear to send fails due to the CS
line is not energized within the transmission enable monitor-
A393 Communication Line Not Ready ing time, or when data ready fails due to the DR line is not
energized within the transmission enable monitoring time.
(*1)
Data size is too large for send-
A394
ing.
The port for sending is not de-
A395
clared.
A397 Underrun
Interval of characters became This message occurs when the interval of characters ex-
A398
timeout ceeds the specified time.
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages (Message Numbers 0001 through
0094)> 3-15
Table 3.1-7 Error Details of Message No.0089 - Errors that irrelevant to subsystems (Table continued)
Code Error Cause/Action
A399 Reception buffer overflow
A39A Reception parity error
A39B Reception overrun
A39C Reception frame error
Number of characters beyond
A39D
range
A39F Other errors
A3B0 to For more information, see the instruction manuals of sub-
Reserved for subsystems
A3FF systems.

*1: The transmission-watching timer monitors the waiting time of the transmission line become ready for transmission. When RS
is sent, and the waiting time for transmission exceeds the specified time period, the transmission becomes error. The trans-
mission waiting time is normally set to 1000 ms.
The conditions for transmission are as follows:
• CD line off (When CD check is enabled)
• CS (CTS) line on
• DR line on (When DR check is enabled)

Remark Subsystem communication

No.0090
Message name Subsystem communication recovered
Printing example SCS0101 SS-COM Recover FIO NODE 01 SLOT 01 PORT 01 STN001
Meaning The communication between the indicated communication module and the
subsystem recovered from the error.
Remark Subsystem communication

No.0093
Message name CPU node’s housekeeping unit error
Printing example SCS0101 RIGHT HKU Error Code=0001
Meaning The CPU node’s housekeeping unit of the safety control station (station name
= SCS0101) is faulty. “Code” indicates detailed internal information.
Action Report to Yokogawa’s service department.
Remark HKU function

No.0094
Message name Normal recovery of CPU node’s housekeeping unit
Printing example SCS0101 RIGHT HKU Recover Code=0001
Meaning The CPU node’s housekeeping unit of the safety control station (station name
= SCS0101) recovered normally. (This is a recovery message of No. 0093.)
Remark HKU function

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.2 Safety Control Station Status Change Related Messages (Message Numbers 0450 through 0480)>
3-16

3.2 Safety Control Station Status Change


Related Messages (Message Numbers
0450 through 0480)
This section describes status change-related messages from the safety control station.

No.0450
Message name Copy program and database on control side of safety control station to stand-
by side
Printing example SCS0101 Copy
Meaning The copying of the program and database on the control side of the safety
control station to the standby side has been started.
Cause This message is displayed when the CPU module on the standby side of the
safety control station (station name = SCS0101) was started.

No.0451
Message name Information of switching of control side of safety control station
Printing example SCS0101 RIGHT Control
Meaning The CPU module on the right or left side (right side in the above example) of
the safety control station (station name = SCS0101) has been set to the con-
trol side.

No.0452
Message name Information of switching of standby side of safety control station
Printing example SCS0101 LEFT Stand-By
Meaning The CPU module on the right or left side (left side in the above example) of the
safety control station (station name = SCS0101) has been set to the standby
side.

No.0459
Message name Information on I/O module service side
Printing example SCS0101 IOM In Service FIO NODE 01 SLOT 01
Meaning One side (slot 1 of node 1 in the above example) of a redundant I/O module
has gained control right.

No.0460
Message name Information of I/O module out service
Printing example SCS0101 IOM Out Service FIO NODE 01 SLOT 01
Meaning An I/O module (slot 1 of node 1 in the above example) has been set to stand-
by or stopped.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.2 Safety Control Station Status Change Related Messages (Message Numbers 0450 through 0480)>
3-17

No.0471
Message name Normal completion of online change download
Printing example SCS0101 Online Download (Integration Database) Complete
Meaning Online change download to the safety control station has normally been com-
pleted.

No.0474
Message name Information of tag list duplicate error
Printing example SCS0101 Tag Duplication Error Tag = TAG001
Meaning A duplicate tag list name exists in the same safety control station.
Action Report to Yokogawa’s service department.

No.0475
Message name Start of database download to I/O module
Printing example SCS0101 IOM Download Start FIO NODE 01 SLOT 01
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Start FIO NODE 01 SLOT 02
Meaning Database download to the I/O module indicated in the message has been star-
ted.

No.0476
Message name Normal completion of database download to I/O module
Printing example SCS0101 IOM Download Complete FIO NODE 01 SLOT 01
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Complete FIO NODE 01 SLOT 02
Meaning Database download to the I/O module indicated in the message has normally
been completed.

No.0477
Message name Database download error to I/O module
Printing example SCS0101 IOM Download Error FIO NODE 01 SLOT 01 Error= xxxx
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Error FIO NODE 01 SLOT 02 Error= xxxx
Meaning An error occurred during database download to the I/O module indicated in the
message. “xxxx” indicates an error code.
Cause/Action The following lists error codes. If an error occurs, remove the cause, and exe-
cute IOM download again.
If an error other than the following occurred, replace the I/O module and exe-
cute IOM download again. If other error occurred again, report details to Yoko-
gawa’s service department.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.2 Safety Control Station Status Change Related Messages (Message Numbers 0450 through 0480)>
3-18
• IOM error codes other than ALR111, ALR121, and ALE111.
A701: This I/O module is currently executing download.
3B1B: The I/O module is faulty.
CFxx: An error was replied from the I/O module.
CF10: The type of the I/O module is not correct.

• Error codes of ALR111, ALR121, and ALE111


A33D: Communication cannot be performed with the ALR1x1 and
ALE111.
A33E: The communication path between the CPU module and the
ALR1x1 is abnormal. (Node failure, etc.)
A731: Simultaneous download attempts were made for communication
programs. In one attempt of the online change download,
ALR1x1 for subsystems, ALR1x1 for Modbus Slave, ALE111 for
Modbus/TCP Slave and ALE111 for DNP3 Slave are not allowed
to add simultaneously. If you try to add them simultaneously,
A731 error occurs when downloading is attempted for the sec-
ond and subsequent modules. When an error occurs, perform
IOM download to the failed communication module on SCS State
Management Window after the online change download com-
pletes.

No.0480
Message name Heavy load on periodical processing
Printing example SCS0101 Too Heavy Load
Meaning The processing time of External Communication Function of the safety control
station has exceeded the four times the scan period that is specified for Exter-
nal Communication Function.
Cause The load on the safety control station is too heavy.
Action Correct the application and reduce the load on the safety control station.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.3 Safety Control Station Related Messages (Message Numbers 0727 through 0787)> 3-19

3.3 Safety Control Station Related Messages


(Message Numbers 0727 through 0787)
This section describes messages that have common message numbers with the messages of
the CENTUM control station.

No.0727
Message name Block mode recovery error information
Printing example SCS0101 Block Mode Change Error Block=TAG001 Code=9601-0000
TAG001: Tag name
9601-0000: Error code

Meaning Block mode recovery failed at the end of downloading.


Action Report the error code to Yokogawa’s Service department.

No.0743
Message name Self-diagnostic SEN-BUS Failure
Printing example SCS0101 SEN-BUS Alarm SEN-BUS No.1
Meaning The SEN-BUS in question has failed.
Cause There is a failure in the SEN-BUS in the CPU node or the CPU module moun-
ted.
Action Replace the CPU node or the CPU module mounted.

No.0744
Message name Self-diagnostic SEN-BUS Recovery
Printing example SCS0101 SEN-BUS Recover SEN-BUS No.1
Meaning The SEN-BUS in question has returned to normal. (This is a recovery mes-
sage of No. 0743.)

No.0749
Message name Self-diagnosis detected an I/O Error
Printing example SCS0101 FIO Self Diag Error FIO CODE = 00005119 DET = 00000000
Meaning I/O error was detected during self-diagnosis.
Cause/Action The action varies depending on the Code and DET. Contact Yokogawa service
department with the contents of CODE and DET.
The following describes the contents of CODE and DET.
CODE = 00005119 : An error was detected in the redundant control
unit. Switching is not performed even if an error oc-
curred on the control side. Replace the I/O module.
CODE = 0000511B : An error was detected in the I/O unit of the CPU
module.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.3 Safety Control Station Related Messages (Message Numbers 0727 through 0787)> 3-20
DET = 0000 Y48x : A detail code of CODE = 0000511B. Y = 0 indi-
cates an error in the right CPU module, and Y = 8
indicates an error in the left CPU module.

No.0750
Message name I/O Recovery from the error detected by self-diagnosis
Printing example SCS0101 FIO Self Diag Recover FIO CODE = 00000000 DET = 00000000
Meaning Recovery from I/O error detected by self-diagnosis. (This is a recovery mes-
sage of No. 0749.)

No.0751
Message name Time self-diagnostic testing error
Printing example SCS0101 RIGHT Time Self Diag Error Code=00030021
Meaning A clock error is detected by self-diagnosis while the CPU of either redundant
or non-redundant is running.
Cause VEHICLE clock, RTC or GPS clock trouble
Action Replace the CPU module.

No.0753
Message name Communication Overload
Printing example SCS0101 Communication Overload
Meaning Communication load to safety control station exceeded the limit.
Cause There were many communication demands from the operation and monitoring
function window or application programs to the safety control station.
Action If the windows for the indicated safety control station are displayed on the
CENTUM HIS, the windows need to be closed. Modifying the application pro-
grams may also reduce the communication load to the safety control station.

No.0767
Message name Faulty one ESB bus in CPU module
Printing example SCS0101 FIO-BUS Fail FIO RIGHT BUS No.1
Meaning A communication error (bus1 in the above example) occurred in standby side
CPU module (right side in the above example) of the safety control station
(station name = SCS0101). (Communication with all nodes on the bus1 side
became abnormal.)
Cause The CPU module or the backboard of the CPU node may be faulty.
Action Replace the CPU module or the CPU node.

No.0768
Message name Single ESB bus in CPU module Recovery
Printing example SCS0101 FIO-BUS Recover FIO RIGHT BUS No.1

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<3.3 Safety Control Station Related Messages (Message Numbers 0727 through 0787)> 3-21
Meaning A communication error (bus1 in the above example) in standby side CPU
module (right side in the above example) of the safety control station (station
name = SCS0101) recovered. (This is a recovery message of No. 0767.)

No.0787
Message name Self-diagnosis detected I/O error in CPU module
Printing example SCS0101 I/O Diagnosis Error IO RIGHT CODE=02518000 00000000
Meaning A self-diagnosis error occurred in a CPU module (right side in the above ex-
ample) of the safety control station (station name = SCS0101).

Table 3.3-1 Message No. 0787 - Error Code Detail


CODE(hexadecimal, 16
digits)
Error code Error detail Factor
(Upper 8 (Lower 8
digits) digits)
0251 8000 0000 0000 A CPU module error was detected. Replace the CPU module.
This code indicates that the revision of
If a system contains Optical ESB Bus
0000 0270 the firmware (F4) in the CPU module is
0255 8082 Repeater module, the proper revision
(*1) obsolete for the system configured with
of CPU should be used.
Optical ESB Bus Repeater modules.
SCSP2-S: An error was detected during
If many I/O modules are installed on
the diagnosis of I/O operation.
the ESB bus extended with optical ca-
xxxx0471 xxxx xxxx The CPU module have failed or the load
bles, estimate the I/O communication
in the I/O communication band is too
band and check the validity.
heavy.
SCSP2-S: There may be a failure in the
xxxx0313 xxxx xxxx Replace the SCP461 card.
I/O unit of the CPU module.

*1: This code is not generated in SCSP2-S.

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<Appendix 1. Alarm Class> App.1-1

Appendix 1. Alarm Class


The following table shows the alarm class that is added to each Diagnostic Information Mes-
sage.

Table Appendix 1-1 Alarm Class


Message number Message name Alarm class
0001 Reset start of safety control station 2
0003 Safety control station automatic reset start 2
0005 Power ON initial cold start of safety control station 2
0009 Transfer of control right of safety control station 2
0011 Fail information of safety control station 2
0013 AC power supply failure of safety control station 2
0015 Self-diagnosis error of clock inside CPU module 2
0017 ROM checksum error of CPU module 2
0021 Internal task error of safety control station 2
0023 Mapping block fatal error 2
0025 Function control word error 2
0027 Mapping block record information error 2
0033 Online downloading abnormal end 2
0041 Safety control station fan alarm 2
0042 Recovery from safety control station fan alarm 3
0043 Safety control station temperature alarm 2
0044 Recovery from safety control station temperature alarm 3
0045 Power supply module alarm of safety control station 2
0046 Recovery from power supply module alarm of safety control 3
station
0047 Battery alarm of CPU module 2
0048 Recovery from battery alarm of CPU module 3
0055 Information of same frame reception in online change down- 2
load communication
0057 Information of online change download error 2
0059 Information of recovery from node power failure 1
0063 ESB bus error 1, or 2
0064 Normal recovery of ESB bus 3
0065 Failure of ESB Bus Interface module (SSB401) of node 1, or 2
0066 Normal recovery of ESB Bus Interface module (SSB401) of 3
node
0067 Failure of power supply module of node 1, or 2
0068 Normal recovery of power supply module of a node 3
0069 Error before database download to I/O module 1, or 2
0081 Failure of I/O module 1, or 2
0082 Normal recovery of I/O module 3
0083 I/O module database error occurred 1, or 2
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<Appendix 1. Alarm Class> App.1-2
Table Appendix 1-1 Alarm Class (Table continued)
Message number Message name Alarm class
0085 I/O module communication error occurred 1, or 2
0086 Recovery from I/O module communication error 3
0087 Node error occurred 1
0088 Normal recovery of node 3
0089 Subsystem communication error 2
0090 Subsystem communication recovered 3
0093 CPU node’s housekeeping unit error 2
0094 Normal recovery of CPU node’s housekeeping unit 3
0450 Copy program and database on control side of safety control 4
station to standby side
0451 Information of switching of control side of safety control sta- 4
tion
0452 Information of switching of standby side of safety control sta- 4
tion
0459 Information on I/O module service side 4
0460 Information of I/O module out service 4
0471 Normal completion of online change download 4
0474 Information of tag list duplicate error 2
0475 Start of database download to I/O module 4
0476 Normal completion of database download to I/O module 4
0477 Database download error to I/O module 2
0480 Heavy load on periodical processing 4
0727 Block mode recovery error information 2
0743 Self-diagnostic SEN-BUS Failure 2
0744 Self-diagnostic SEN-BUS Recovery 3
0749 Self-diagnosis detected an I/O Error 1, or 2
0750 I/O Recovery from the error detected by self-diagnosis 3
0751 Time self-diagnostic testing error 1
0753 Communication Overload 2
0767 Faulty one ESB bus in CPU module 2
0768 Single ESB bus in CPU module Recovery 3
0787 Self-diagnosis detected I/O error in CPU module 1, or 2
4101 Inter-SCS safety communication error information 1
4102 Inter-SCS safety communication error recovery information 3
4103 Variable lock 4
4104 Cancellation of variable lock 4
4105 I/O module lock 4
4106 Cancellation of I/O module lock 4
4107 All input module locks 4
4108 Cancellation of all input module locks 4
4109 All output module locks 4
4110 Cancellation of all output module locks 4
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<Appendix 1. Alarm Class> App.1-3
Table Appendix 1-1 Alarm Class (Table continued)
Message number Message name Alarm class
4111 All module locks 4
4112 Cancellation of all module locks 4
4113 Number of locks exceeded 2
4114 Recovery from exceeded number of locks 3
4115 Override setting 4
4116 Cancellation of override 4
4117 Information of change to override enabled state 4
4118 Information of change to override disabled state 4
4119 Number of overrides exceeded 2
4120 Recovery from exceeded number of overrides 3
4121 Number of enabled overrides exceeded 2
4122 Recovery from exceeded number of enabled overrides 3
4123 Number of active PASSWD FBs exceeded 2
4124 Recovery from exceeded number of active PASSWD FBs 3
4125 I/O module channel error occurred 1
4126 Recovery from I/O module channel error 3
4127 Setting PASSWD FB to ON 4
4128 Setting PASSWD FB to OFF 4
4129 GPS interface unit error 2
4130 Recovery of GPS interface unit 3
4131 Communication module lock 4
4132 Cancellation of Communication module lock 4
4133 Information of a diagnosis error in the received data of SCS 1, or 2
Link Transmission.
4134 Information of a diagnosis error recovery in the received data 3
of SCS Link Transmission.
4135 SCS Link Transmission data lock 4
4136 Cancellation of SCS Link Transmission data lock 4
4137 Number of Locked Stations in SCS Link Transmission Excee- 2
ded
4138 Recovery from exceeded number of locked stations in SCS 3
Link Transmission
4139 Inter-SCS Safety Communication data lock 4
4140 Cancellation of Inter-SCS Safety Communication data lock 4
4141 Number of locked stations in Inter-SCS Safety Communica- 2
tion exceeded
4142 Recovery from exceeded number of locked stations in Inter- 3
SCS Safety Communication
4143 Start of automatic scan period extension 1
4144 Cancellation of automatic scan period extension 3
4145 Abnormal calculation occurred 1
4146 Recovery from abnormal calculation 3
4151 Information of retainable data initialization 4
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<Appendix 1. Alarm Class> App.1-4
Table Appendix 1-1 Alarm Class (Table continued)
Message number Message name Alarm class
4152 Online change of scan period 4
4153 Information of Inter-SCS Safety Communication data lock 2
time-up
4154 Information of forced cancellation of Inter-SCS Safety Com- 4
munication data locks
4155 Information of SCS Link Transmission status change. 4
4156 Information of SCS Link Transmission definition change 4
4157 Information of SCS Link Transmission wiring change 4
4158 Information of SCS Link Transmission lock time-up 2
4159 Information of forced cancellation of SCS Link Transmission 4
locks
4160 Invalid password for Manual Operation FB 4
4161 Information of Output IOM Shutdown 4
4162 Information of communication I/O definition change 4
4163 Information of communication I/O wiring change 4
4164 Information of disabling security level change 4
4165 Information of enabling security level change 4
4166 Information of communication module lock time-up 2
4167 Information of forced cancellation of communication module 4
locks
4168 Information of tag name change by online change download 4
4169 NVRAM diagnosis error 2
4170 Flash memory diagnosis error 2
4172 Information of resource change by online change download 4
4173 Completion of writing to flash memory 4
4174 Failed to write to flash memory 2
4175 Failed to update external communication data 2
4177 Information of SCS security level change 4
4178 Information of security level time-up 2
4179 Information of communication I/O module output enabled op- 4
eration
4180 Information of password change 4
4181 Information of output enabled operation 4
4182 Information of output module start operation 4
4183 Request to upload SOE to SENG 4
4184 Notification on saving SOE trip signal file in SCS 4
4185 Information of variable value change 4
4186 Information of lock time-up 2
4187 Information of forced cancellation of locks 4
4188 Start of online change download 4
4189 Completion of online change download 4
4190 Online change download error 2
Continues on the next page

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


<Appendix 1. Alarm Class> App.1-5
Table Appendix 1-1 Alarm Class (Table continued)
Message number Message name Alarm class
4191 Completion of I/O definition rewriting 4
4192 Information of override state time-up 2
4193 Information of forced release of all overrides 4
4194 Information of override enabled state time-up 2
4195 Information of communication I/O data status change 4
4196 Invalid password for PASSWD FB 4
4197 Information on active PASSWD FB time-up 2
4198 Information on forced reset of PASSWD FB 4
4199 Override communication error 2

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00


Rev-1

Revision Information
Title : Messages
Manual No. : IM 32Q02B10-31E
Jan. 2015/4th Edition/R3.02.20 or later*
*: Denotes the release number of the Software Product corresponding to the contents of this Man-
ual. The revised contents are valid until the next edition is issued.

Introduction ProSafe-RS document map has been removed,


descriptions of “Safety, Protection, and Modifica-
tion of the Product” have been modified.
No.0081, No.0477 Descriptions of messages changed.
Oct. 2013/3rd Edition/R3.02.10 or later
Introduction Description of station types has been changed.
No.4151 New message added.
Appendix 1 No.4151 added.
Dec. 2012/2nd Edition/R3.02 or later
1.1, 1.2 Descriptions changed.
No.4145, No.4146, No.0081, No.0477, No.0749 Descriptions of messages changed.
Appendix 1 Newly added.
Aug. 2011/1st Edition/R3.01 or later
Newly published.

n For Questions and More Information


Online Query: A query form is available on the following URL for online query.
http://www.yokogawa.com/iss
n Written by Yokogawa Electric Corporation
n Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN

IM 32Q02B10-31E 4th Edition : Jan.30,2015-00

You might also like