Introduction
This manual describes the details of Diagnostic Information messages displayed in the Diag-
nostic Information Window of SCS Maintenance Support Tool or System Alarm View of HIS.
The table of the contents of this manual can be used as message number index.
This manual consists of the following chapters:
Chapter 1 : This chapter explains how to refer to the Diagnosis Information in SENG.
Chapter 2 : This chapter explains the details about SCS Messages.
Chapter 3 : This chapter explains the details about common messages of CENTUM VP or
CS 3000 and SENG.
Appendix : A list of the alarm class for the corresponding message number is provided.
Media No. IM 32Q02B10-31E (CD) 4th Edition : Jan. 2015 (YK) IM 32Q02B10-31E 4th Edition : Jan.30,2015-00
All Rights Reserved Copyright © 2011, Yokogawa Electric Corporation
ii
n Notes on Software
• YOKOGAWA makes no warranties, either expressed or implied, with respect to the Soft-
ware Product's merchantability or suitability for any particular purpose, except as speci-
fied in the warranty terms.
• Purchase the appropriate number of licenses of the Software Product according to the
number of computers to be used.
• No copy of the Software Product may be made for any purpose other than backup; other-
wise, it is deemed as an infringement of YOKOGAWA's Intellectual Property rights.
• Keep the software medium of the Software Product in a safe place.
• No reverse engineering, reverse compiling, reverse assembling, or converting the Soft-
ware Product to human-readable format may be performed for the Software Product.
• No part of the Software Product may be transferred, converted, or sublet for use by any
third-party, without prior written consent from YOKOGAWA.
Documentation Conventions
n Symbols
The following symbols are used in the User's Manuals.
Identifies instructions that must be observed to avoid physical
injury, electric shock, or death.
n Typographical Conventions
The following typographical conventions are used throughout the User's Manuals.
n Drawing Conventions
Drawings used in the User's Manuals may be partially emphasized, simplified, or omitted for
the convenience of description.
Drawings of windows may be slightly different from the actual screenshots with different set-
tings or fonts. The difference does not hamper the understanding of basic functionalities and
operation and monitoring tasks.
n Station Types
A safety control station (hereafter referred to as SCS) is named according to the type of the
safety control unit used in it.
n Trademark Acknowledgments
• CENTUM, ProSafe, Vnet/IP, and STARDOM are registered trademarks of YOKOGAWA.
• Microsoft, Windows, Windows Vista, Windows Server, Visual Basic, Visual C++, and Vis-
ual Studio are either registered trademarks or trademarks of Microsoft Corporation in the
United States and other countries.
• Adobe, Acrobat, and Adobe Reader are registered trademarks of Adobe Systems Incor-
porated.
• Ethernet is a registered trademark of Xerox Corporation.
• HART is a registered trademark of the HART Communication Foundation.
• Modicon and Modbus are registered trademarks of Schneider Electric SA.
• All other company and product names mentioned in the User's Manuals are trademarks
or registered trademarks of their respective companies.
• TM or ® mark are not used to indicate trademarks or registered trademarks in the User's
Manuals.
• Logos and logo marks are not used in the User's Manuals.
Messages
CONTENTS
1. Referencing Diagnostic Information Messages on the SENG......... 1-1
1.1 How to Display the Diagnostic Information Window.................................1-2
1.2 Diagnostic Information Window..................................................................1-3
1.3 Printout of Diagnostic Information Message............................................. 1-4
2. Details of Output Messages Specific to the SCS.............................. 2-1
2.1 System Alarms (Message Numbers 4101 through 4199).......................... 2-2
No. 4101 Inter-SCS safety communication error information ....................... 2-2
No. 4102 Inter-SCS safety communication error recovery information .........2-3
No. 4103 Variable lock .................................................................................. 2-3
No. 4104 Cancellation of variable lock ..........................................................2-4
No. 4105 I/O module lock ............................................................................. 2-4
No. 4106 Cancellation of I/O module lock .....................................................2-5
No. 4107 All input module locks ....................................................................2-5
No. 4108 Cancellation of all input module locks ........................................... 2-5
No. 4109 All output module locks ................................................................. 2-5
No. 4110 Cancellation of all output module locks ......................................... 2-5
No. 4111 All module locks ............................................................................ 2-5
No. 4112 Cancellation of all module locks .................................................... 2-6
No. 4113 Number of locks exceeded ............................................................2-6
No. 4114 Recovery from exceeded number of locks .................................... 2-6
No. 4115 Override setting ............................................................................. 2-6
No. 4116 Cancellation of override .................................................................2-6
No. 4117 Information of change to override enabled state ........................... 2-7
No. 4118 Information of change to override disabled state .......................... 2-7
No. 4119 Number of overrides exceeded ..................................................... 2-7
No. 4120 Recovery from exceeded number of overrides ............................. 2-7
No. 4121 Number of enabled overrides exceeded ....................................... 2-8
No. 4122 Recovery from exceeded number of enabled overrides ................2-8
No. 4123 Number of active PASSWD FBs exceeded ................................... 2-8
No. 4124 Recovery from exceeded number of active PASSWD FBs ........... 2-8
No. 4125 I/O module channel error occurred ................................................2-9
No. 4126 Recovery from I/O module channel error ...................................... 2-9
No. 4127 Setting PASSWD FB to ON ........................................................... 2-9
Messages
CONTENTS
Appendix
Appendix 1. Alarm Class..................................................................... App.1-1
Figure 1.1-1 SCS Status Overview Window and Diagnostic Information button
30/95
SEE
ALSO For more information about the diagnostic information window, refer to:
3.2, “Displaying SCS Diagnostic Information” in Utilities and Maintenance Reference (IM
32Q04B20-31E)
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 05 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 05
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 03 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 03
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
0451 5/30/2008 9:00:00.465 AM 2 SCS0101 LEFT Control
0005 5/30/2008 9:00:00.465 AM 2 SCS0101 Power ON (Cold Start)
0013 5/30/2008 9:00:00.465 AM 2 SCS0101 AC Fail (Time 1/1/1970 9:00:00 AM)
No.xxxx
Message name Name of the message.
Example: Information of security level time-up
Printing example Indicates an example of print or display.
Example: SCS0101 Security Level = 1 Elapsed the Specified Period = 08 :
00 : 00
In this document, space in messages and the leading “00” of various numbers
may be different from actual printing examples to the extent they do not impair
the understanding of messages.
Meaning Meaning of a message.
Example: The security level is set to “1” for the duration exceeding the time
limit (8 hours in the above example) specified in SYS_SECURE Function
Block (hereinafter referred to as “FB”).
Cause Describes the cause of occurrence. The description may be omitted depend-
ing on the message.
Example: The security level has not been reverted.
Action Describes the action to take. The description may be omitted depending on
the message.
Example: Revert the security level to “2.”
Remark Describes an item(s) related to the message. The description may be omitted
depending on the message.
Note Describes cautions. The description may be omitted depending on the mes-
sage.
Error code Describes details of the error code included in the message, if any. The de-
scription may be omitted depending on the message.
No.4101
Message name Inter-SCS safety communication error information
Printing example SCS0101 Inter-SCS Safety Communication Receive Error Variable =
C0102001 Code = 5041-8000
Meaning An error is detected during inter-SCS safety communication. The erroneous
binding variable (C0102001 in the above example) is included in the message.
Cause The following causes may be considered. Check the error codes for more de-
tail.
• Stop/restart on the producing side SCS
• Problem in the communication path
• Change in the application of inter-SCS safety communication
Remark Inter-SCS safety communication
Error code The first four digits are an error code, and the next four digits are a cause
code. The error detail can be found from the descriptions of the both codes.
The error codes and cause codes are listed below.
The error code represents the type of error. The following table explains each
error code and the action you can take to fix the error.
The cause code represents the event that caused the problem and is logical
OR of the following codes.
No.4102
Message name Inter-SCS safety communication error recovery information
Printing example SCS0101 Inter-SCS Safety Communication Receive Recover Variable =
C0102001
Meaning An inter-SCS safety communication error for the variable (C0102001 in the
above example) recovered. (This is a recovery message of No. 4101.)
Cause The following causes may be considered.
• Recovery of the producing side SCS
• Recovery of the communication path
• Recovery of the application of inter-SCS safety communication
Remark Inter-SCS safety communication
No.4103
Message name Variable lock
Printing example In the case of I/O variables:
SCS0101 Variable Locked Variable=VAR001 NODE 01 SLOT 02 CH 03
In the case of internal variables:
No.4104
Message name Cancellation of variable lock
Printing example In the case of I/O variables:
SCS0101 Variable Unlocked Variable=VAR001 NODE 01 SLOT 02 CH 03
In the case of internal variables:
SCS0101 Variable Unlocked Variable=VAR001
Meaning The lock of the variable (VAR001 in the above example) was cancelled by op-
eration from the SENG. In the case of I/O variables, the channel position
(node 1, slot 2 and channel 3 in the above example) corresponding to the vari-
able is also included in the message.
Remark Forcing function
Note If an IO_BOOL type or IO_REAL type variable is unlocked, the member varia-
ble v or status will be indicated in the format of [Variable=VAR001.v] at the po-
sition of the variable name in the system alarms. If the variable is not wired to
the channel, the member variable v will be always displayed. Nevertheless, in
any of the above cases, the whole IO_BOOL type or IO_REAL type variable
will be unlocked.
Moreover, when unlocking an array element, the whole array will be unlocked.
Under this circumstance, the variable name displayed in the system alarm will
be attached with the array element subscript as [Variable=VAR001[1]].
No.4105
Message name I/O module lock
Printing example SCS0101 IOM Locked NODE 01 SLOT 02
Meaning An I/O module was locked by operation from the SENG. The I/O module posi-
tion (node 1 and slot 2 in the above example) is included in the message.
Remark Forcing function
Note Be sure to cancel the lock of the I/O module that was locked.
No.4106
Message name Cancellation of I/O module lock
Printing example SCS0101 IOM Unlocked NODE 01 SLOT 02
Meaning The lock of an I/O module was cancelled by operation from the SENG. The I/O
module position (node 1 and slot 2 in the above example) is included in the
message.
Remark Forcing function
No.4107
Message name All input module locks
Printing example SCS0101 All Input IOM Locked
Meaning All input modules were locked by operation from the SENG.
Remark Forcing function
Note Be sure to cancel the locks of the input modules that were locked.
No.4108
Message name Cancellation of all input module locks
Printing example SCS0101 All Input IOM Unlocked
Meaning The locks of all input modules were cancelled by operation from the SENG.
Remark Forcing function
No.4109
Message name All output module locks
Printing example SCS0101 All Output IOM Locked
Meaning All output modules were locked by operation from the SENG.
Remark Forcing function
Note Be sure to cancel the locks of the output modules that were locked.
No.4110
Message name Cancellation of all output module locks
Printing example SCS0101 All Output IOM Unlocked
Meaning The locks of all output modules were cancelled by operation from the SENG.
Remark Forcing function
No.4111
Message name All module locks
Printing example SCS0101 All IOM Locked
Meaning All I/O modules were locked by operation from the SENG.
No.4112
Message name Cancellation of all module locks
Printing example SCS0101 All IOM Unlocked
Meaning The locks of all I/O modules were cancelled by operation from the SENG.
Remark Forcing function
No.4113
Message name Number of locks exceeded
Printing example SCS0101 Number of Locks Exceeds the Limit = 3
Meaning The total number of locked variables exceeded the limit count (3 in the above
example) specified in SYS_FORCE FB.
Cause This is an operation from the SENG. The number of locks is too many.
Action Cancel the variable locks.
Remark SYS_FORCE FB
Note Lock variables within the limit count.
No.4114
Message name Recovery from exceeded number of locks
Printing example SCS0101 Number of Locks Within the Limit = 3
Meaning The total number of locked variables is reduced to within the limit count (3 in
the above example) specified in SYS_FORCE FB. (This is a recovery mes-
sage of No. 4113.)
Cause This is an operation from the SENG.
Remark SYS_FORCE FB
No.4115
Message name Override setting
Printing example SCS0101 TAG001 Overridden (Instance = OVR0001)
Meaning Override operation was performed for the override FB (OVR0001 in the above
example) that corresponds to the tag name (TAG001 in the above example)
from the HIS.
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
No.4116
Message name Cancellation of override
Printing example SCS0101 TAG001 Override Released (Instance = OVR0001)
No.4117
Message name Information of change to override enabled state
Printing example SCS0101 Override Enabled
Meaning An override was enabled.
Cause The SW input parameter of the override FB was set to “TRUE.”
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
Note If the SW input parameter of any override FB is set to “TRUE,” this message is
generated.
No.4118
Message name Information of change to override disabled state
Printing example SCS0101 Override Disabled
Meaning An override was disabled.
Cause The SW input parameter of all override FBs were set to “FALSE.”
Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB
Note If the SW input parameters of all override FBs are set to “FALSE,” this mes-
sage is generated.
No.4119
Message name Number of overrides exceeded
Printing example SCS0101 Number of Overrides Exceeds the Limit = 3
Meaning The total number of overridden override FBs exceeded the limit count (3 in the
above example) specified in SYS_OVR FB.
Cause This is an operation from the HIS. There are too many overrides.
Action Cancel overrides.
Remark SYS_OVR FB
Note Override within the limit count.
No.4120
Message name Recovery from exceeded number of overrides
Printing example SCS0101 Number of Overrides Within the Limit = 3
Meaning The total number of overridden override FBs is within the limit count (3 in the
above example) specified in SYS_OVR FB. (This is a recovery message of
No. 4119.)
Cause This is an operation from the HIS.
No.4121
Message name Number of enabled overrides exceeded
Printing example SCS0101 Number of Enabled OVR FBs Exceeds the Limit = 3
Meaning The total number of override FBs in the override enabled state exceeded the
limit count (3 in the above example) specified in SYS_OVR FB.
Action Disable override FBs.
Remark SYS_OVR FB
Note Enable overrides within the limit count.
No.4122
Message name Recovery from exceeded number of enabled overrides
Printing example SCS0101 Number of Enabled OVR FBs Within the Limit = 3
Meaning The total number of override FBs in the override enabled state is within the
limit count (3 in the above example) specified in SYS_OVR FB. (This is a re-
covery message of No. 4121.)
Remark SYS_OVR FB
No.4123
Message name Number of active PASSWD FBs exceeded
Printing example SCS0101 Number of Activated PASSWD FBs Exceeds the Limit = 3
Meaning The total number of active PASSWD FBs exceeded the limit count (3 in the
above example) specified in SYS_PSWD FB.
Cause This is an operation from the HIS. There are too many active PASSWD FBs.
Action Inactivate (reset to OFF) the PASSWD FBs that have exceeded the limit
count.
Remark SYS_PSWD FB
Note Make PASSWD FBs active within the limit count.
No.4124
Message name Recovery from exceeded number of active PASSWD FBs
Printing example SCS0101 Number of Activated PASSWD FBs Within the Limit = 3
Meaning The total number of active PASSWD FBs is within the limit count (3 in the
above example) specified in SYS_PSWD FB. (This is a recovery message of
No. 4123.)
Cause Active PASSWD FBs were inactivated (reset to OFF) by operation from the
HIS.
Remark SYS_PSWD FB
No.4125
Message name I/O module channel error occurred
Printing example SCS0101 IOM Channel Error NODE 01 SLOT 02 CH 03 XXXXXXXX (YYYY)
Meaning An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in
the above example). XXXXXXXX indicates an error cause, and YYYY indi-
cates an error code.
Cause Error codes and causes of errors are shown on the following list.
Action Check to see if the connected devices and connecting cables are normal.
No.4126
Message name Recovery from I/O module channel error
Printing example SCS0101 IOM Channel Recover NODE 01 SLOT 02 CH 03
Meaning An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in
the above example) recovered. (This is a recovery message of No. 4125.)
No.4127
Message name Setting PASSWD FB to ON
Printing example SCS0101 TAG001 PASSWD FB Set to ON (Instance = PASSWD001)
Meaning PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was set to ON (active) by operation
from the HIS.
No.4128
Message name Setting PASSWD FB to OFF
Printing example SCS0101 TAG001 PASSWD FB Set to OFF (Instance = PASSWD001)
Meaning PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was inactivated (reset to OFF) by oper-
ation from the HIS.
No.4129
Message name GPS interface unit error
Printing example SCS0101 GPS Interface Unit Error (RIGHT CPU)
Meaning A CPU module (right side in the above example) detected a GPS unit error or
time synchronization error.
Cause The following causes may be considered.
• Problem in the cable connecting the GPS unit and the GPS interface unit.
• Failure of the GPS interface unit
Action Check to see if a cable connecting the GPS unit and the GPS interface unit is
disconnected or cut. Also, check to see if a terminator is connected to the
ends of the cable. If everything is in place, replace the GPS interface unit.
Note If this message is displayed while the time synchronization method is V net
time synchronization, the CPU module may be faulty.
No.4130
Message name Recovery of GPS interface unit
Printing example SCS0101 GPS Interface Unit Recover (RIGHT CPU)
Meaning Time synchronization of the GPS unit detected by CPU module (right side in
the above example) is recovered. (This is a recovery message of No. 4129.)
No.4131
Message name Communication module lock
Printing example 1 SCS0101 Communication Module All Inputs/Outputs Locked NODE 01 SLOT
02
Printing example 2 SCS0101 Communication Module All Inputs Locked NODE 01 SLOT 02
Printing example 3 SCS0101 Communication Module All Outputs Locked NODE 01 SLOT 02
Meaning The communication module was locked by operation from the SENG. The
message varies depending on the locked range (inputs and outputs, inputs on-
ly or outputs only). The location of the communication module is also included
in the messages (such as node 1, slot 2).
Remark Forcing function, subsystem communication
Note Be sure to cancel the lock of the communication module that was locked.
No.4132
Message name Cancellation of Communication module lock
Printing example 1 SCS0101 Communication Module All Inputs/Outputs Unlocked NODE 01
SLOT 02
Printing example 2 SCS0101 Communication Module All Inputs Unlocked NODE 01 SLOT 02
Printing example 3 SCS0101 Communication Module All Outputs Unlocked NODE 01 SLOT 02
Meaning The lock of the communication module was cancelled by operation from the
SENG. The message varies depending on the locked range (inputs and out-
No.4133
Message name Information of a diagnosis error in the received data of SCS Link Transmis-
sion.
Printing example SCS0101 SCS Link Transmission Receive Error Stn(SCS)=05 Code =
5041-8000
Meaning A diagnosis error has been found in the received data of SCS Link Transmis-
sion. The source station number (such as 05) and the station type (SCS in the
above example) that sent the Link Transmission are indicated in the message
text. The station type indicated in the message is the station type defined on
the SCS Link Transmission builder.
Cause The following causes may be considered. Check the error codes for more de-
tail.
• Stop or restart the sender station
• Problem in the communication path
• The definition of the SCS Link Transmission builder may contain errors.
Remark SCS Link Transmission
Error code The first four digits are an error code, and the next four digits are a cause
code. The error detail can be found from the descriptions of the both codes.
The error codes and cause codes are listed below.
The error code represents the type of error. The following table explains each
error code and the action you can take to fix the error.
The cause code represents the event that caused the problem and is logical
OR of the following codes.
No.4134
Message name Information of a diagnosis error recovery in the received data of SCS Link
Transmission.
Printing example SCS0101 SCS Link Transmission Receive Recover Stn(SCS)=05
Meaning The diagnosed reception error of SCS link transmission has been recovered.
The source station number (such as 05) and the station type (SCS in the
above example) are indicated in the message text. The station type indicated
in the message is the same station type defined on the SCS Link Transmission
builder.
(This is a recovery message of No. 4133.)
Cause The following causes may be considered.
• Recovery of the sender station
• Recovery of the communication path
• The errors in the SCS Link Transmission definition have been removed.
Remark SCS Link Transmission
No.4135
Message name SCS Link Transmission data lock
Printing example SCS0101 SCS Link Transmission Data Locked Stn(SCS)=02
Meaning The reception/transmission data for SCS Link Transmission (in the above ex-
ample, data received from station 2) were locked. The (SCS) in the message
text indicates the station type defined on the SCS Link Transmission builder.
No.4136
Message name Cancellation of SCS Link Transmission data lock
Printing example SCS0101 SCS Link Transmission Data Unlocked Stn(SCS)=02
Meaning The lock of reception/transmission data for SCS Link Transmission (in the
above example, data received from station 2) was cancelled. The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.
Remark Forcing function, SCS Link Transmission
No.4137
Message name Number of Locked Stations in SCS Link Transmission Exceeded
Printing example SCS0101 Number of Locks about SCS Link Transmission Exceeds the Limit =
3
Meaning The number of locked stations exceeded the limit (3 in the above example),
which is defined in SYS_FORCE_ LT FB as the number of stations allowed for
forcing.
Cause Operation from the SENG to lock too many stations.
Action Cancel SCS Link Transmission locks for some SCS.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB
Note You should not lock stations beyond the limit.
No.4138
Message name Recovery from exceeded number of locked stations in SCS Link Transmission
Printing example SCS0101 Number of Locks about SCS Link Transmission Within the Limit = 3
Meaning The number of locked stations fell within the limit (3 in the above example),
which is defined in SYS_FORCE_ LT FB as the number of stations allowed for
forcing. (This is the recovery message of No.4137.)
Cause Operation from the SENG.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB
No.4139
Message name Inter-SCS Safety Communication data lock
Printing example SCS0101 Inter-SCS Safety Communication Data Locked Dom=01 Stn=02
Meaning The Inter-SCS Safety Communication data received from a producer SCS (in
the above example, station 2 in domain 1) were locked.
The message for a lock of the local station (data produced by the station are
locked) is also output in the same format, showing its own domain number and
station number.
No.4140
Message name Cancellation of Inter-SCS Safety Communication data lock
Printing example SCS0101 Inter-SCS Safety Communication Data Unlocked Dom=01 Stn=02
Meaning The lock of Inter-SCS Safety Communication data received from a producer
SCS (in the above example, station 2 in domain 1) was cancelled.
The message of cancellation for the lock of local station (data produced by the
station are locked) is also output in the same format, showing its own domain
number and station number.
Remark Forcing function, Inter-SCS Safety Communication
No.4141
Message name Number of locked stations in Inter-SCS Safety Communication exceeded
Printing example SCS0101 Number of Locks about Inter-SCS Safety Communication Exceeds
the Limit = 3
Meaning The number of locked stations exceeded the limit (3 in the above example),
which is defined in SYS_FORCE_ BD FB as the number of stations allowed
for forcing.
Cause Operation from the SENG to lock too many stations
Action Cancel Inter-SCS Safety Communication locks for some SCS.
Remark Forcing function, Inter-SCS Safety Communication
Note You should not lock stations beyond the limit.
No.4142
Message name Recovery from exceeded number of locked stations in Inter-SCS Safety Com-
munication
Printing example SCS0101 Number of Locks about Inter-SCS Safety Communication Within the
Limit = 3
Meaning The number of locked stations fell within the limit (3 in the above example),
which is defined in SYS_FORCE_ BD FB as the number of stations allowed
for forcing. (This is the recovery message of No.4141.)
Cause Operation from the SENG
Remark SYS_FORCE_BD FB
No.4143
Message name Start of automatic scan period extension
Printing example SCS0101 Scan Period Extended from the Original Scan Period 100ms to
200ms
No.4144
Message name Cancellation of automatic scan period extension
Printing example SCS0101 Scan Period Recovered to the Original Scan Period 100ms
Meaning Automatic extension of the scan period of the application logic execution is
cancelled. (In the above example, the scan period recovered to its original pe-
riod of 100 ms.)
Cause The load on the SCS caused by the application was reduced.
Remark SYS_SCANEXT FB, automatic scan period extension
No.4145
Message name Abnormal calculation occurred
Printing example 1 SCS0101 Calculation Error (XXXXXX) Program=PG01
Printing example 2 SCS0101 Calculation Error (XXXXXX) Program=PG01 FU/FB=UFB01
Meaning Abnormal calculation occurred in the application logic.
XXXXXX indicates the type of abnormal calculation. The types are as follows:
Div by Zero : Division by zero
Access to the Outside of Array : Access to the outside of an array
FPU Overflow : Overflow in the floating-point calculation
Cast Overflow : Overflow in casting
At “Program=”, the name of the program (POU name) where the abnormal cal-
culation occurred is indicated. If the abnormal calculation occurred in a user-
defined FU/FB, the POU name of that FU/FB is indicated at “FU/FB=.”
Cause Error in the application
Remark SYS_CERR FB
No.4146
Message name Recovery from abnormal calculation
Printing example 1 SCS0101 Calculation Recover (XXXXXX) Program=PG01
Printing example 2 SCS0101 Calculation Recover (XXXXXX) Program=PG01 FU/FB=UFB01
Meaning Indicates a recovery from the abnormal calculation occurred in the application
logic.
XXXXXX indicates the type of abnormal calculation. The types are as follows:
Div by Zero : Division by zero
Access to the Outside of Array : Access to the outside of an array
FPU Overflow : Overflow in the floating-point calculation
No.4151
Message name Information of retainable data initialization
Printing example SCS0101 Retain Data Initialized
Meaning Retainable data have been initialized.
Cause • Database with different CRC codes or generation time was offline-down-
loaded to the SCS.
• Data saved in the memory with backup battery volatilized.
Action Set the setting values of the external communication function blocks with data
retaining function again.
Remark Data retaining function, external communication function blocks with data re-
taining function (ECWR_B, ECWR_I, ECWR_R), ACCUM FB, AGA_R FB
No.4152
Message name Online change of scan period
Printing example SCS0101 Scan Period Changed to 200ms
Meaning The scan period of the application logic was changed by online change down-
load.
Cause Operation from the SENG
Remark Online change download
No.4153
Message name Information of Inter-SCS Safety Communication data lock time-up
Printing example SCS0101 Inter-SCS Safety Communication Data Lock Elapsed the Specified
Period = 08:00:00
Meaning Inter-SCS Safety Communication lock exceeded the time limit (8 hours in the
above example) specified in SYS_FORCE_BD FB.
Action Check whether all Inter-SCS Safety Communication locks have been cancel-
led and cancel unnecessary locks.
Remark Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB
No.4154
Message name Information of forced cancellation of Inter-SCS Safety Communication data
locks
Printing example SCS0101 All Inter-SCS Safety Communication Data Unlocked.
No.4155
Message name Information of SCS Link Transmission status change.
Printing example SCS0101 SCS Link Transmission Data Status Set to TRUE Old=FALSE
Stn(SCS)=03
Meaning The data status of SCS Link Transmission (such as from station 03) has been
changed (For an example, changed from FALSE to TRUE). The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.
Remark Forcing function
No.4156
Message name Information of SCS Link Transmission definition change
Printing example SCS0101 SCS Link Transmission Definition Changed
Meaning SCS Link Transmission definitions were changed by online change download.
Cause Online change download was executed from the SENG.
No.4157
Message name Information of SCS Link Transmission wiring change
Printing example SCS0101 SCS Link Transmission Wiring Changed
Meaning SCS Link Transmission wirings were changed by online change download.
Cause Online change download was executed from the SENG.
No.4158
Message name Information of SCS Link Transmission lock time-up
Printing example SCS0101 SCS Link Transmission Data Lock Elapsed the Specified Period =
08:00:00
Meaning SCS Link Transmission lock continued exceeding the time limit (8 hours in the
above example) specified in SYS_FORCE_LT FB.
Action Check whether all SCS Link Transmission locks have been cancelled, and
cancel unnecessary locks.
Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB
No.4159
Message name Information of forced cancellation of SCS Link Transmission locks
Printing example SCS0101 All SCS Link Transmission Data Unlocked
No.4160
Message name Invalid password for Manual Operation FB
Printing example SCS0101 TAG001 Specified Invalid Password
Meaning The password string specified for Manual Operation FB (MOB_21, MOB_11,
MOA) from the HIS is invalid.
Cause The password entered from the HIS and the password set in Manual Opera-
tion FB did not match.
Action Enter the correct password for Manual Operation FB again.
Remark Manual Operation FB (MOB_21, MOB_11, MOA)
No.4161
Message name Information of Output IOM Shutdown
Printing example 1 SCS0101 All Output IOM Shutdown
Printing example 2 SCS0101 Output IOM Shutdown NODE 01 SLOT 02
Meaning An output IOM shutdown task is performed by a Shutdown FB (SYS_ALLSD
or SYS_IOSD). If the shutdown task is performed by SYS_IOSD, the output
module location for shutting down (node 1 and slot 2 in the above example) is
also included in the message.
Remark SYS_ALLSD, SYS_IOSD
No.4162
Message name Information of communication I/O definition change
Printing example SCS0101 Communication Definition Changed
Meaning The communication I/O definitions of the communication module were
changed by online change download.
Cause Online change download was executed from the SENG.
No.4163
Message name Information of communication I/O wiring change
Printing example SCS0101 Communication I/O Wiring Changed
Meaning The communication I/O wirings were changed by online change download.
Cause Online change download was executed from the SENG.
No.4164
Message name Information of disabling security level change
No.4165
Message name Information of enabling security level change
Printing example SCS0101 Security Levels Change Enabled
Meaning The security level change of the SCS by a password-authenticated operation
performed from SENG is enabled.
Remark SYS_SEC_CTL FB
No.4166
Message name Information of communication module lock time-up
Printing example SCS0101 Communication Module Lock Elapsed the Specified Period =
08:00:00
Meaning The communication module lock continued exceeding the time limit (8 hours in
the above example) specified in SYS_FORCE_SC FB.
Action Check whether all communication module locks have been cancelled, and
cancel unnecessary locks.
Remark Forcing function, subsystem communication, SYS_FORCE_SC FB
No.4167
Message name Information of forced cancellation of communication module locks
Printing example SCS0101 All Communication Modules Unlocked
Meaning Locks of all communication modules were forcibly cancelled.
Cause Locks of all communication modules were cancelled by operation using
SYS_FORCE_SC FB.
Remark Forcing function, subsystem communication, SYS_FORCE_SC FB
No.4168
Message name Information of tag name change by online change download
Printing example SCS0101 Online Change Download Tag Name = TAG001 Changed
Meaning The tag name (TAG001 in the above example) of PASSWD FB or override FB
was changed by online change download.
Cause Online change download was executed from the SENG.
No.4169
Message name NVRAM diagnosis error
Printing example SCS0101 RIGHT NVRAM Diagnosis Error
No.4170
Message name Flash memory diagnosis error
Printing example SCS0101 RIGHT Flash Memory Diagnosis Error
Meaning An error was detected during self-diagnosis of flash memory in a CPU module
(right side in the above example).
Cause Part of data stored in flash memory was destroyed, or flash memory may be
faulty.
Action If the SCS is in a single CPU module configuration, the SCS will not be able to
start when this CPU restarts next time. It is necessary to change the CPU
module right away.
If the SCS is configured with redundant CPU modules, the control will switch
to the other module after detecting this error, and the module where the error
occurs is restarted as a standby module.
If the error is caused by damage to the data in the flash memory, data in the
control side will be copied to the standby module where the error occurs, and
that module will then recover from abnormal to normal status.
If the error is caused by the physical damage of the flash memory, this system
alarm will occur even after the damaged CPU is switched to standby. Under
this circumstance, it is necessary to change the damaged CPU module.
No.4172
Message name Information of resource change by online change download
Printing example SCS0101 Online Change Download Resource Changed (Total POU=10)
Meaning The resource was changed by online change download. The resource defines
total number of POU (10 in the above example).
Cause Online change download was executed from the SENG.
Action Check and confirm that the total number of POU indicated in this message is
equal to the total number of POU indicated by Database Validity Check Tool.
No.4173
Message name Completion of writing to flash memory
Printing example SCS0101 Writing XXXXXX to Flash Memory Succeeded
Meaning Writing to flash memory in a CPU module was normally completed.
XXXXXX: Indicates the data written. The items of the data are as follows.
Security Password : Security password
System Database : System database
Integration Database : Integration database
Variable Database : Variable database
Cause When online change download from SENG to SCS was executed or the pass-
word was changed, data was normally written to flash memory.
No.4174
Message name Failed to write to flash memory
Printing example SCS0101 Writing XXXXX to Flash Memory Error
Meaning Write data error was detected during check at flash memory write in a CPU
module.
XXXXXX: Indicates the data attempted to be written. The items of the data are
as follows.
Security Password : Security password
System Database : System database
Integration Database : Integration database
Variable Database : Variable database
Difference Data : Difference data
No.4175
Message name Failed to update external communication data
Printing example SCS0101 External Data Refresh Failed
Meaning The SCS has failed to update external communication data. This data is refer-
enced in communications with CENTUM stations and Modbus, so when this
error occurs, data will not be updated in those stations.
Cause The CPU processing time allocated for the external communication function
processing was not sufficient. As a result, processing to update the external
communication data is not performed.
Action Reduce the communication load on the SCS. If this error occurs regularly, re-
view the balance between the application logic amount and the scan period.
No.4177
Message name Information of SCS security level change
No.4178
Message name Information of security level time-up
Printing example SCS0101 Security Level = 1 Elapsed the Specified Period = 08:00:00
Meaning The security level is set to “1” for the duration exceeding the time limit (8 hours
in the above example) specified in SYS_SECURE FB.
Cause The security level has not been reverted.
Action Revert the security level to “2.”
Remark SYS_SECURE FB
Note When the security level is “0,” the message is not generated.
No.4179
Message name Information of communication I/O module output enabled operation
Printing example SCS0101 Communication Modules Output Enabled
Meaning The communication modules are enabled for output.
Remark I/O Channel Status dialog box, SYS_STAT_SC FB
Note This is irrelevant for enabling the output of the safety I/O modules. If you have
done the Output enabled operation for the safety output modules, confirm the
message 4181.
No.4180
Message name Information of password change
Printing example SCS0101 Security Level = 1 Password was Changed
Meaning The password for the SCS security level (1 in the above example) was
changed.
Cause The password was changed from the SENG.
Note The message of No. 4173 is also generated after this alarm.
No.4181
Message name Information of output enabled operation
Printing example SCS0101 Output Enabled
Meaning The output enabled operation for the SCS was performed from the SENG.
When all the safety module’s output channels go into “output-enabled” state,
the SCS’s operating mode changes to “Running.”
Remark I/O Channels Status dialog box, SYS_STAT_FB
No.4182
Message name Information of output module start operation
Printing example SCS0101 IOM Started NODE 01 SLOT 02
Meaning An output module (node 1 and slot 2 in the above example) was started from
the SENG.
Remark SCS State Management window
No.4183
Message name Request to upload SOE to SENG
Printing example SCS0101 SOE Save Request
Meaning This notification prompts to upload the event information collected on the SCS
to SENG.
Cause This message is generated every time 12,000 events have occurred on the
SCS.
Action Start SOE Viewer on SENG and upload events from SCS.
Remark SOER function
Note This system alarm is generated even if SOE Viewer is started periodically.
Events can be uploaded from the SCS by starting SOE Viewer and displaying
the latest event.
No.4184
Message name Notification on saving SOE trip signal file in SCS
Printing example SCS0101 SOE Trip Signal File No.= 01 Saved
Meaning The SOE trip signal file (No. 01 in the above example) was saved in SCS.
Action Start SOE Viewer on SENG and upload the events in the file.
Remark SOER function
Note When uploading the events is complete, the trip signal files need to be reset.
Up to two trip signal files can be held in the SCS. The trip signal files can be
reset by starting the Message Cache Tool and initializing the trip information.
No.4185
Message name Information of variable value change
Printing example 1 SCS0101 Variable Set to 10.0 Old = 5.0 Variable = VAR001
Printing example 2 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01
SLOT 02
Printing example 3 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01
SLOT 02 CH 03
Printing example 4 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 Stn=02
No=025
Meaning The value of the variable (VAR001 in the above example) was changed from
the SENG. For a communication I/O, a variable corresponds to the communi-
cation module location (as shown in example 2, node 1, slot 2) is also included
No.4186
Message name Information of lock time-up
Printing example SCS0101 Lock Elapsed the Specified Period = 08:00:00
Meaning Lock continued exceeding the time limit (8 hours in the above example) speci-
fied in SYS_FORCE FB.
Action Check whether all locks have been cancelled, and cancel unnecessary locks.
Remark Forcing function, SYS_FORCE FB
No.4187
Message name Information of forced cancellation of locks
Printing example SCS0101 All Variables Unlocked
Meaning Locks of all variables were forcibly cancelled.
Cause Locks of all variables were cancelled by operation using SYS_FORCE FB.
Remark Forcing function, SYS_FORCE FB
No.4188
Message name Start of online change download
Printing example SCS0101 Online Change Download (System Database) Start
Meaning Online change download to the system database was started.
Remark Download function
No.4189
Message name Completion of online change download
Printing example SCS0101 Online Change Download (System Database) Complete
Meaning Online change download to the system database was normally completed.
Remark Download function
No.4190
Message name Online change download error
Printing example SCS0101 Online Change Download (System Database) Error = 5340-0001
Meaning Online change download to the system database ended with an error.
No.4191
Message name Completion of I/O definition rewriting
Printing example SCS0101 IOM Definition Changed NODE 01 SLOT 02
Meaning I/O definition was changed by online change download to the system data-
base. The I/O module position is included in the message (node 1, slot 2 in the
above example).
If the number following “SLOT” is 00, it means that the node definition informa-
tion has been changed. The node definition information is changed when you
do the following:
• Change comments of the node
• Add or delete I/O modules of the node
• Change slots of the I/O modules of the node
• Change the model of the I/O modules of the node
No.4192
Message name Information of override state time-up
Printing example SCS0101 Override Elapsed the Specified Period = 08:00:00
Meaning Override continued exceeding the time limit (8 hours in the above example)
specified in SYS_OVR FB.
Action Check whether overrides were released, and release unnecessary overrides.
Remark SYS_OVR FB
No.4193
Message name Information of forced release of all overrides
Printing example SCS0101 All Overrides Released
Meaning The overrides for all variables were forcibly released.
Cause The overrides for all variables were forcibly released by operation using
SYS_OVR FB.
Remark SYS_OVR FB
No.4194
Message name Information of override enabled state time-up
Printing example SCS0101 Enabled OVR FB Elapsed the Specified Period = 08:00:00
No.4195
Message name Information of communication I/O data status change
Printing example SCS0101 Communication Data Status Set to TRUE Old = FALSE NODE 01
SLOT 02 Definition 001
Meaning The data status of the communication I/O (such as node 1, slot 2, definition 1
in the above example) was changed (such as from FALSE to TRUE) from the
SENG.
Remark Forcing function
No.4196
Message name Invalid password for PASSWD FB
Printing example SCS0101 TAG001 PASSWD FB Specified Invalid Password
Meaning The password string specified for PASSWD FB from the HIS is invalid.
Cause The password entered from the HIS and the password set in PASSWD FB did
not match.
Action Specify the correct password for PASSWD FB and enter it again.
Remark PASSWD FB
No.4197
Message name Information on active PASSWD FB time-up
Printing example SCS0101 Activated PASSWD FB Elapsed the Specified Period = 10:00:00
Meaning PASSWD FB has been active exceeding the time limit (10 hours in the above
example) specified in SYS_PSWD.
Action Deactivate PASSWD FB that is not required to be active.
Remark SYS_PSWD FB
No.4198
Message name Information on forced reset of PASSWD FB
Printing example SCS0101 All PASSWD FB Reset to OFF
Meaning The outputs of all active PASSWD FBs were forcibly set to OFF.
Cause The outputs of all active PASSWD FBs were forcibly inactivated (reset to OFF)
by operation using SYS_PSWD FB.
Remark SYS_PSWD FB
No.4199
Message name Override communication error
Printing example SCS0101 TAG001 Override Communication Error (Instance = OVR001)
Meaning Despite an attempt to operate override on the FB OVR001 (in the above ex-
ample) with the tag name TAG001 (in the above example) from HIS, communi-
cation error has occurred.
Cause A temporary communication error occurred, and the SCS detected the prob-
lem of the communication data.
Action Execute override operation again.
Remark SYS_OVR FB
No.0001
Message name Reset start of safety control station
Printing example SCS0101 RIGHT Manual Reset Start
Meaning A CPU module (right side in the above example) of the safety control station
(station name = SCS0101) was reset and started.
Cause Start operation from the SENG or from the front switch of the CPU module
No.0003
Message name Safety control station automatic reset start
Printing example SCS0101 RIGHT Automatic Reset Start
Meaning An error occurred in the displayed CPU module (right side in the above exam-
ple) of the safety control station (station name=SCS0101), which caused the
safety control station to be automatically reset started.
Cause CPU module is faulty.
No.0005
Message name Power ON initial cold start of safety control station
Printing example SCS0101 Power ON (Cold Start)
Meaning The safety control station (station name = SCS0101) performed the initial cold
start processing after it was powered ON.
Cause Recovery from power failure
Note The safety control station always performs the initial cold start processing after
recovery from power failure.
No.0009
Message name Transfer of control right of safety control station
Printing example SCS0101 Control Transfer
Meaning A transfer of control right occurred in the redundant safety control station (sta-
tion name = SCS0101).
Cause • The CPU module on one side was stopped.
• An error occurred in the CPU module on one side.
Action The CPU module on the standby side takes over control. Replace the CPU
module that was stopped.
No.0011
Message name Fail information of safety control station
Printing example SCS0101 RIGHT Fail (xxxxxxxx Code= yyyy yyyy yyyy yyyy)
Meaning A CPU module (right side in the above example) of the safety control station
(station name = SCS0101) failed.
Cause The causes are indicated by “causes (xxxxxxxx)” and a code. For more infor-
mation, see the following table.
*1: If this error message is displayed, report the display contents of causes (xxxxxxxx) and code to Yokogawa’s service depart-
ment.
*2: Refer to the following “Table 2.1-4 Error Codes and Solutions.”
Action If the safety control station operates normally after restarting automatically,
continue operation. If the safety control station stops after restarting automati-
cally, replace the CPU module.
No.0013
Message name AC power supply failure of safety control station
Printing example SCS0101 AC Fail (Time 05.02.01 18:45)
Meaning AC power of the safety control station (station name = SCS0101) failed and
was then recovered. The date and time indicated are when the power failed.
This message is output after the power is recovered.
Cause The voltage of AC power supply dropped, or a power failure occurred.
Note The SCS has been initialized and then started.
No.0015
Message name Self-diagnosis error of clock inside CPU module
Printing example SCS0101 RTC Diagnose Error Code=0001
Meaning An error was detected during self-diagnosis of the clock inside the safety con-
trol station (station name = SCS0101).
Code=0001: Check pattern mismatch
Code=0002: Inappropriate date/time value
Code=0003: Date/time not updated
No.0017
Message name ROM checksum error of CPU module
Printing example SCS0101 RIGHT ROM Sum Check Error
Meaning A ROM checksum error was detected in the indicated CPU module (right side
in the above example) of the safety control station (station name = SCS0101).
Action Replace the CPU module.
No.0021
Message name Internal task error of safety control station
Printing example SCS0101 Internal Error TASK=TSK1 Code=100 Error=1000 - E0F0
Meaning An error state was detected during the execution of a task (TSK1 in the above
example) in the safety control station (station name = SCS0101). “TASK”,
“Code” and “Error” indicate detailed error information.
Cause This is a software problem.
Action Report the message content to Yokogawa’s service department.
No.0023
Message name Mapping block fatal error
Printing example SCS0101 Block TAG001 Return Error 8E04 and stop
Meaning An execution disabled error was detected during the execution of a mapping
block (TAG001 in the above example) in the safety control station (station
name = SCS0101).
Cause There is a problem in the integration DB. “Error” indicates detailed error infor-
mation.
Action Report the message content to Yokogawa’s service department.
No.0025
Message name Function control word error
Printing example SCS0101 No Block Control Word for Block Type=1804
Meaning The internal program that corresponds to the block type code of the safety
control station (station name = SCS0101) does not exist. “Type” indicates de-
tailed internal information.
Cause This is an internal error at task initialization.
Action Report the message content to Yokogawa’s service department.
No.0027
Message name Mapping block record information error
Printing example SCS0101 TAG001 Block Bad Record No = 3
Meaning There is a bad record in the mapping block (TAG001 in the above example) of
the safety control station. “No” indicates the bad record number in the data-
base.
Cause The mapping block and the record block number do not match.
Action Report the block type and record number where an error occurred to Yokoga-
wa’s service department.
Note Do not perform online change download after this alarm occurred.
No.0033
Message name Online downloading abnormal end
No.0041
Message name Safety control station fan alarm
Printing example SCS0101 Fan (SCU N1) Alarm
Meaning A cooling fan of the safety control station (station name = SCS0101) is abnor-
mal. One of the following items is displayed in the parentheses in the above
example.
SCU N1: Left side fan
SCU N2: Right side fan
No.0042
Message name Recovery from safety control station fan alarm
Printing example SCS0101 Fan(SCU N1) Recover
Meaning The cooling fan of the safety control station (station name = SCS0101) recov-
ered. The content in the parentheses in the above example is the same as
message No. 0041. (This is a recovery message of No. 0041.)
Remark HKU function
No.0043
Message name Safety control station temperature alarm
Printing example SCS0101 Temperature(RIGHT BATTERY) Alarm
Meaning This is a temperature rise alarm of the safety control station (station name =
SCS0101). One of the following items is displayed in the parentheses in the
above example.
RIGHT BATTERY: Battery of the right side CPU module
LEFT BATTERY: Battery of the left side CPU module
No.0044
Message name Recovery from safety control station temperature alarm
Printing example SCS0101 Temperature(RIGHT BATTERY) Recover
Meaning The temperature of the safety control station (station name = SCS0101) recov-
ered normally. The content in the parentheses in the above example is the
same as message No. 0043. (This is a recovery message of No. 0043.)
Remark HKU function
No.0045
Message name Power supply module alarm of safety control station
Printing example SCS0101 RIGHT PSU Alarm
Meaning The power supply module of a CPU node (right side in the above example) of
the safety control station (station name = SCS0101) is abnormal.
Cause Power supply module failure
Action Replace the applicable power supply module.
No.0046
Message name Recovery from power supply module alarm of safety control station
Printing example SCS0101 RIGHT PSU Recover
Meaning The power supply module of a CPU node (right side in the above example) of
the safety control station (station name = SCS0101) recovered normally. (This
is a recovery message of No. 0045.)
No.0047
Message name Battery alarm of CPU module
Printing example SCS0101 RIGHT Battery Alarm
Meaning A battery of the CPU module (right side in the above example) of the safety
control station (station name = SCS0101) is abnormal.
Cause The battery switch is OFF, or the battery is faulty.
Action Make sure that the switch of the applicable battery is ON. If the above mes-
sage occurs even if the battery switch is ON, replace the battery.
Remark HKU function
No.0048
Message name Recovery from battery alarm of CPU module
Printing example SCS0101 RIGHT Battery Recover
Meaning A battery of the CPU module (right side in the above example) of the safety
control station (station name = SCS0101) recovered normally. (This is a recov-
ery message of No. 0047.)
Remark HKU function
No.0055
Message name Information of same frame reception in online change download communica-
tion
Printing example SCS0101 Received Same Online Download Frame Code=1 Frame=3
Meaning The same communication frame was received twice during the execution of
online change download. “Code” and “Frame” indicate detailed internal infor-
mation.
Action Execute online change download again.
No.0057
Message name Information of online change download error
Printing example SCS0101 Online Download Error Call Code=9601 - 0000 Data=91,0,0,0
Meaning An error occurred during the execution of online change download of the safe-
ty control station (station name = SCS0101). “Code” and “Data” indicate de-
tailed internal information.
Cause This error occurs if error data cannot be saved on the safety control station
side.
Action It is necessary to determine an action to take based on the “Code” and “Data”
information. Report the display contents of “Code” and “Data” to Yokogawa’s
service department.
Note Do not execute online change download after this alarm occurred.
No.0059
Message name Information of recovery from node power failure
Printing example SCS0101 FIO NODE Power On FIO NODE 02
Meaning An I/O node (2 in the above example) of the safety control station (station
name = SCS0101) recovered from power failure.
No.0063
Message name ESB bus error
Printing example SCS0101 FIO-BUS Fail FIO BUS No.1
Meaning An error occurred on one side (No. 1 in the above example) of the ESB buses
of the safety control station (station name = SCS0101).
Cause This is an ESB bus error on one side.
No.0064
Message name Normal recovery of ESB bus
Printing example SCS0101 FIO-BUS Recover FIO BUS No.1
Meaning The ESB bus indicated in the message recovered normally. (This is a recovery
message of No. 0063.)
No.0065
Message name Failure of ESB Bus Interface module (SSB401) of node
Printing example SCS0101 SBS Fail FIO NODE 02 SBS RIGHT
Meaning An error occurred in an ESB Bus Interface module (right side in the above ex-
ample) of an I/O node (2 in the above example) of the safety control station
(station name = SCS0101).
Cause One of the following causes may be considered.
• ESB Bus Interface module becomes abnormal.
• Connection route to the ESB Bus Interface module becomes abnormal.
No.0066
Message name Normal recovery of ESB Bus Interface module (SSB401) of node
Printing example SCS0101 SBS Recover FIO NODE 02 SBS RIGHT
Meaning An ESB Bus Interface module (right side in the above example) of an I/O node
(2 in the above example) of the safety control station (station name =
SCS0101) recovered normally. (This is a recovery message of No. 0065.)
No.0067
Message name Failure of power supply module of node
Printing example SCS0101 PSU Fail FIO NODE 02 PSU RIGHT
Meaning An error occurred in a power supply module (right side in the above example)
of an I/O node (2 in the above example) of the safety control station (station
name = SCS0101).
Cause Failure of a power supply module of an I/O node
Action Replace the power supply module of the applicable node.
Note When the message shows node 1, it indicates that an error occurred in a PSU
for the CPU node.
No.0068
Message name Normal recovery of power supply module of a node
Printing example SCS0101 PSU Recover FIO NODE 02 PSU RIGHT
Meaning The power supply module of the I/O node indicated in the message (2 in the
above example) recovered normally. (This is a recovery message of No.
0067.)
No.0069
Message name Error before database download to I/O module
Printing example SCS0101 IOM Download Error=A701
Meaning Database download to the I/O module (IOM) can not be started.
Cause/Action The cause and action vary depending on the content of the error.
• A701
No.0081
Message name Failure of I/O module
Printing example SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code=5101
Meaning An error occurred in the I/O module mounted in slot 1 of node 1 (CPU node) of
the safety control station (station name = SCS0101).
Cause For more information about error codes, see the following table.
Action Replace the applicable I/O module.
Table 3.1-4 Error Details of Message No. 0081 - Errors of Analog Input Modules and Contact I/O Mod-
ules
Error code Description of error
The communication between CPU and I/O modules encounters a no-response error.
5101 This error is caused either by the I/O module abnormality or by the communication
route abnormality.
The type of the I/O module defined on the SENG and the type of the I/O module
5102
mounted does not match. Check type of the I/O module.
The setting information defined on the SENG and the I/O module setting information
5103
do not match. Execute IOM download.
A hardware error of the I/O module was detected. Check detailed error causes in the
5104
IOM report.
A setting error of the I/O module. Check detailed error causes in the IOM report (field
5105
side connector disconnection, field power supply/wiring problem, etc.)
The I/O module recovered from an error state. Check detailed error causes in the IOM
5106
report.
The error that actuated the output shutoff switch occurred. Check detailed error cau-
5107 ses in the IOM report. When this error occurred, start the I/O module after recovering
from the error.
A communication data check error was detected between the CPU and the I/O mod-
5111, 5112, 5113 ule. A failure of the I/O module or a problem of the communication path up to the I/O
module may be the cause.
Continues on the next page
Table 3.1-5 Error Details of Message No.0081 – Errors on ALR111/ALR121/ALE111 Modbus Slave and
ALE111 DNP3 Slave
Error Code Cause/Action
The communication between CPU and I/O modules encounters a no-response error.
C580 This error may be caused by the I/O module abnormality, communication route abnor-
mality or an abnormality other than C581 to C583 depicted.
The communication program is not downloaded to the communication module. Run
C581
IOM download.
The communication program in the communication module is not the program for
C582
Modbus slave communication/DNP3 slave function. Run IOM download.
The physically installed communication module shows a different model name from
C583 the communication module defined in SENG. Check the model of the communication
module.
No.0082
Message name Normal recovery of I/O module
Printing example SCS0101 IOM Recover FIO NODE 01 SLOT 01
Meaning The I/O module mounted in slot 1 of node 1 in the safety control station (sta-
tion name = SCS0101) recovered normally. (This is a recovery message of
No. 0081.)
No.0083
Message name I/O module database error occurred
Printing example SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
Meaning An error occurred in the database on the I/O module mounted in slot 1 of node
1 in the safety control station (station name = SCS0101).
Cause The database on the I/O module and the database on the SCS do not match.
The following causes may be considered.
• IOM download has not been executed.
• IOM failure.
Action If this error occurred after replacing a module or at startup, the database might
not have been downloaded to the I/O module. Execute IOM download.
If this error occurred during I/O module operation, the I/O module may be faul-
ty. Replace the I/O module.
No.0085
Message name I/O module communication error occurred
Printing example SCS0101 IOM Communication Error FIO NODE 01 SLOT 01 RIGHT
Meaning An error occurred in one of the SB buses (right side in the above example). An
error occurred when accessing the I/O module mounted in slot 1 of node 1 in
the safety control station (station name = SCS0101).
Cause If this error occurred on all input modules within the same node, an I/O module
may be faulty, or the backboard bus of the node may be faulty. Or, an ESB bus
(right side in the above example) or an SSB401 (right side in the above exam-
ple) may be faulty, or they may not be connected properly.
Action Report to Yokogawa’s service department.
No.0086
Message name Recovery from I/O module communication error
Printing example SCS0101 IOM Communication Recover FIO NODE 01 SLOT 01 RIGHT
Meaning A communication error with the I/O module mounted in slot 1 of node 1 in the
safety control station (station name = SCS0101) recovered. (This is a recovery
message of No. 0085.)
No.0087
Message name Node error occurred
No.0088
Message name Normal recovery of node
Printing example SCS0101 NODE Recover FIO NODE 02
Meaning The node indicated in the message recovered normally. (This is a recovery
message of No. 0087.)
No.0089
Message name Subsystem communication error
Printing example SCS0101 SS-COM Error FIO NODE 01 SLOT 01 PORT 01 STN001 Code=
A3B0
Meaning A communication error occurred between the indicated communication module
and the subsystem.
Cause/Action The error details can be found in the instruction manuals of the connected
subsystem. See the manuals for error details.
The error codes that irrelevant to the connected subsystems are shown.
Table 3.1-7 Error Details of Message No.0089 - Errors that irrelevant to subsystems
Code Error Cause/Action
A391 Driver Busy Occurs when sending or receiving.
This message occurs when carrier detection fails due to the
A392 Communication Line Busy CD line is energized within the transmission enable monitor-
ing time.(*1)
This message occurs when clear to send fails due to the CS
line is not energized within the transmission enable monitor-
A393 Communication Line Not Ready ing time, or when data ready fails due to the DR line is not
energized within the transmission enable monitoring time.
(*1)
Data size is too large for send-
A394
ing.
The port for sending is not de-
A395
clared.
A397 Underrun
Interval of characters became This message occurs when the interval of characters ex-
A398
timeout ceeds the specified time.
Continues on the next page
*1: The transmission-watching timer monitors the waiting time of the transmission line become ready for transmission. When RS
is sent, and the waiting time for transmission exceeds the specified time period, the transmission becomes error. The trans-
mission waiting time is normally set to 1000 ms.
The conditions for transmission are as follows:
• CD line off (When CD check is enabled)
• CS (CTS) line on
• DR line on (When DR check is enabled)
No.0090
Message name Subsystem communication recovered
Printing example SCS0101 SS-COM Recover FIO NODE 01 SLOT 01 PORT 01 STN001
Meaning The communication between the indicated communication module and the
subsystem recovered from the error.
Remark Subsystem communication
No.0093
Message name CPU node’s housekeeping unit error
Printing example SCS0101 RIGHT HKU Error Code=0001
Meaning The CPU node’s housekeeping unit of the safety control station (station name
= SCS0101) is faulty. “Code” indicates detailed internal information.
Action Report to Yokogawa’s service department.
Remark HKU function
No.0094
Message name Normal recovery of CPU node’s housekeeping unit
Printing example SCS0101 RIGHT HKU Recover Code=0001
Meaning The CPU node’s housekeeping unit of the safety control station (station name
= SCS0101) recovered normally. (This is a recovery message of No. 0093.)
Remark HKU function
No.0450
Message name Copy program and database on control side of safety control station to stand-
by side
Printing example SCS0101 Copy
Meaning The copying of the program and database on the control side of the safety
control station to the standby side has been started.
Cause This message is displayed when the CPU module on the standby side of the
safety control station (station name = SCS0101) was started.
No.0451
Message name Information of switching of control side of safety control station
Printing example SCS0101 RIGHT Control
Meaning The CPU module on the right or left side (right side in the above example) of
the safety control station (station name = SCS0101) has been set to the con-
trol side.
No.0452
Message name Information of switching of standby side of safety control station
Printing example SCS0101 LEFT Stand-By
Meaning The CPU module on the right or left side (left side in the above example) of the
safety control station (station name = SCS0101) has been set to the standby
side.
No.0459
Message name Information on I/O module service side
Printing example SCS0101 IOM In Service FIO NODE 01 SLOT 01
Meaning One side (slot 1 of node 1 in the above example) of a redundant I/O module
has gained control right.
No.0460
Message name Information of I/O module out service
Printing example SCS0101 IOM Out Service FIO NODE 01 SLOT 01
Meaning An I/O module (slot 1 of node 1 in the above example) has been set to stand-
by or stopped.
No.0471
Message name Normal completion of online change download
Printing example SCS0101 Online Download (Integration Database) Complete
Meaning Online change download to the safety control station has normally been com-
pleted.
No.0474
Message name Information of tag list duplicate error
Printing example SCS0101 Tag Duplication Error Tag = TAG001
Meaning A duplicate tag list name exists in the same safety control station.
Action Report to Yokogawa’s service department.
No.0475
Message name Start of database download to I/O module
Printing example SCS0101 IOM Download Start FIO NODE 01 SLOT 01
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Start FIO NODE 01 SLOT 02
Meaning Database download to the I/O module indicated in the message has been star-
ted.
No.0476
Message name Normal completion of database download to I/O module
Printing example SCS0101 IOM Download Complete FIO NODE 01 SLOT 01
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Complete FIO NODE 01 SLOT 02
Meaning Database download to the I/O module indicated in the message has normally
been completed.
No.0477
Message name Database download error to I/O module
Printing example SCS0101 IOM Download Error FIO NODE 01 SLOT 01 Error= xxxx
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Error FIO NODE 01 SLOT 02 Error= xxxx
Meaning An error occurred during database download to the I/O module indicated in the
message. “xxxx” indicates an error code.
Cause/Action The following lists error codes. If an error occurs, remove the cause, and exe-
cute IOM download again.
If an error other than the following occurred, replace the I/O module and exe-
cute IOM download again. If other error occurred again, report details to Yoko-
gawa’s service department.
No.0480
Message name Heavy load on periodical processing
Printing example SCS0101 Too Heavy Load
Meaning The processing time of External Communication Function of the safety control
station has exceeded the four times the scan period that is specified for Exter-
nal Communication Function.
Cause The load on the safety control station is too heavy.
Action Correct the application and reduce the load on the safety control station.
No.0727
Message name Block mode recovery error information
Printing example SCS0101 Block Mode Change Error Block=TAG001 Code=9601-0000
TAG001: Tag name
9601-0000: Error code
No.0743
Message name Self-diagnostic SEN-BUS Failure
Printing example SCS0101 SEN-BUS Alarm SEN-BUS No.1
Meaning The SEN-BUS in question has failed.
Cause There is a failure in the SEN-BUS in the CPU node or the CPU module moun-
ted.
Action Replace the CPU node or the CPU module mounted.
No.0744
Message name Self-diagnostic SEN-BUS Recovery
Printing example SCS0101 SEN-BUS Recover SEN-BUS No.1
Meaning The SEN-BUS in question has returned to normal. (This is a recovery mes-
sage of No. 0743.)
No.0749
Message name Self-diagnosis detected an I/O Error
Printing example SCS0101 FIO Self Diag Error FIO CODE = 00005119 DET = 00000000
Meaning I/O error was detected during self-diagnosis.
Cause/Action The action varies depending on the Code and DET. Contact Yokogawa service
department with the contents of CODE and DET.
The following describes the contents of CODE and DET.
CODE = 00005119 : An error was detected in the redundant control
unit. Switching is not performed even if an error oc-
curred on the control side. Replace the I/O module.
CODE = 0000511B : An error was detected in the I/O unit of the CPU
module.
No.0750
Message name I/O Recovery from the error detected by self-diagnosis
Printing example SCS0101 FIO Self Diag Recover FIO CODE = 00000000 DET = 00000000
Meaning Recovery from I/O error detected by self-diagnosis. (This is a recovery mes-
sage of No. 0749.)
No.0751
Message name Time self-diagnostic testing error
Printing example SCS0101 RIGHT Time Self Diag Error Code=00030021
Meaning A clock error is detected by self-diagnosis while the CPU of either redundant
or non-redundant is running.
Cause VEHICLE clock, RTC or GPS clock trouble
Action Replace the CPU module.
No.0753
Message name Communication Overload
Printing example SCS0101 Communication Overload
Meaning Communication load to safety control station exceeded the limit.
Cause There were many communication demands from the operation and monitoring
function window or application programs to the safety control station.
Action If the windows for the indicated safety control station are displayed on the
CENTUM HIS, the windows need to be closed. Modifying the application pro-
grams may also reduce the communication load to the safety control station.
No.0767
Message name Faulty one ESB bus in CPU module
Printing example SCS0101 FIO-BUS Fail FIO RIGHT BUS No.1
Meaning A communication error (bus1 in the above example) occurred in standby side
CPU module (right side in the above example) of the safety control station
(station name = SCS0101). (Communication with all nodes on the bus1 side
became abnormal.)
Cause The CPU module or the backboard of the CPU node may be faulty.
Action Replace the CPU module or the CPU node.
No.0768
Message name Single ESB bus in CPU module Recovery
Printing example SCS0101 FIO-BUS Recover FIO RIGHT BUS No.1
No.0787
Message name Self-diagnosis detected I/O error in CPU module
Printing example SCS0101 I/O Diagnosis Error IO RIGHT CODE=02518000 00000000
Meaning A self-diagnosis error occurred in a CPU module (right side in the above ex-
ample) of the safety control station (station name = SCS0101).
Revision Information
Title : Messages
Manual No. : IM 32Q02B10-31E
Jan. 2015/4th Edition/R3.02.20 or later*
*: Denotes the release number of the Software Product corresponding to the contents of this Man-
ual. The revised contents are valid until the next edition is issued.