Check List For Fire Pump - Nfpa 20 Systems General Submittal Requirements
Check List For Fire Pump - Nfpa 20 Systems General Submittal Requirements
REQUIREMENTS
Nb:
1 This checklist must be completed/answered by consultant(s) by ticking [√] appropriate boxes
2 Submit a separate sheet containing explanatory notes against all negated answers
3 It is axiomatic that the submission has been made by the consultants only upon having read and clearly understood all the relevant provisions of
the current Fire Protection, Fire Prevention and Fire/Emergency Control(FP, FP&FF) Regulations
DRIVER INFORMATION
1 Manufacturer and specification information provided YES NO
2 Model number provided YES NO
3 Rated horsepower provided YES NO
4 RPM's provided YES NO
5 Electric or diesel information provided YES NO
6 Hours of fuel supply given YES NO
ELECTRIC DRIVERS
1 Electrical circuit schematic provided YES NO
2 Schematic for secondary power circuit and transfer equipment YES NO
3 Controller near motors(more than 12" above floor and 3½' clearance YES NO
to the rear)
4 Controller listed for electric motor drivers YES NO
5 Alarm signal provided to an attended location YES NO
6 Transfer switch specification and listing provided YES NO
7 One transfer switch provided for each individual pump YES NO
CHECK LIST FOR FIRE PUMP - NFPA 20 SYSTEMS GENERAL SUBMITTAL
REQUIREMENTS
DIESEL DRIVERS
1 Listed fire pump used YES NO
2 Closed circuit and liquid cooling details provided in the plans YES NO
3 Equipped with over speed shutdown device YES NO
4 Instrument panel with tachometer, oil pressure, and temperature gauges YES NO
5 Two batteries provided for each engine- rack supported YES NO
6 Batteries have two means for recharging shown YES NO
7 Pump room & engine has adequate ventilation provided YES NO
8 Fuel tank is at least 1 gallon per horsepower plus a 5% cushion YES NO
9 The controller is listed for diesel pump use YES NO
10 Controller near motors(more than 12" above floor and 3½' clearance to the YES NO
rear)
11 Alarm signal provided to an attended location YES NO
OTHER DETAILS
1 Dedicated ATS for individual Fire pumps sets provided for electric YES NO
driven pumps
2 Dedicated and direct Power supply for the fire pumps 2 sets provided YES NO
from the main distributin board of the source (DEWA Transformer)
3 Minimum 1m from all sides provided for easy access/maintenance of fire YES NO
protection system maintained inside the room
4 Controllers are placed inside the pump room with easy accessiblity YES NO
5 Control logic/pressure switch setting details provided YES NO
6 Adequate and appropriate ventilations for pump YES NO
7 Factory test curve & related test documents provided YES NO