3.3 Parameterizing using the parameterizing and start–up tool SimoCom U ! 611ue diff !
Integrated help The ”SimoCom U” tool has an integrated Help function, which helps
you to use the tool and the ”SIMODRIVE 611 universal” drive.
This is how you call up the integrated help function:
S Using the menu command Help " Help contents...
or
S By pressing the Help button
or
S By pressing key F1
3
Printing Data for the following dialog boxes can be printed using the print sym-
bol in the symbol bar:
S Traversing blocks
S Teach In
S User parameter list
S Operating conditions
S Status parameters
S Trace function
S Measurement function
S Expert List
Parameter The following parameters are available for the serial interface (X471):
overview
Table 3-4 Overview of the serial interface
Interface Parameter
No. Name Min. Stan- Max. Unit Effec-
dard tive
0801 Toggling between RS232/RS485 –1 0 1 – PO
The serial interface (X471) is either set to RS232 or RS485 using this
parameter.
=1 Interface is set to RS485
3
Switch S1 =0 Interface is set to RS232
= –1 Reserved
The interface can be changed over from both drives. As the interface
can either be set to RS232 or to RS485, when changing the parameter
in a drive, the parameter in the other drive is automatically changed.
Note:
The RS485 interface can only function for control boards from a certain
hardware version onwards.
––> refer under the index entry ”RS485 (from HW ...1)”
0802 Drive number for RS485 0 0 31 – PO
In an RS485 group, using this parameter, each drive must be assigned
a unique drive number that is used for addressing.
Serial
=0 The drive is not available in the RS485 group
interface
X471) = 1 to 31 The drive has this valid drive number
Note:
S The drive number must be unique in the complete group.
S The terminating resistor is switched in/out using switch S1 (on:
Switch 7 and 8 = ON).
Note:
Before changing over the serial interface, it must be checked that the appropriate ”correct” connecting
cable is connected at X471.
Interface For ”SIMODRIVE 611 universal”, the interface parameters for the serial
parameters interface are permanently assigned and cannot be changed.
Communications The serial RS232 interface is used to connect the ”SIMODRIVE 611
via RS232 universal” control board to a PG/PC.
The parameterizing and start–up tool SimoCom U communicates via
this interface in the online mode (refer to Fig. 3-9).
Note
When changing the drive (changing–over the serial connecting cable)
while there is an open connection to SimoCom U, first wait until the
SimoCom U has recognized that the connection has been interrupted
3 (a dialog box opens within a few seconds). You can then insert the
cable into the new drive. In the dialog box, you can then select whether
you wish to re–connect or cancel.
Setup.exe
Notice
The RS485 interface can only function with control boards from the
appropriate hardware version (refer to Order No., MLFB).
Control board (Order No.) RS485? 3
S 6SN1118–VNV00–0AA0 RS485 cannot be used
S from 6SN1118–VNV00–0AA1 RS485 can be used
V: Space retainer for the Order No.
3. Cable
– RS232 connecting cable
Cable between the PG/PC and interface converter
(cable diagram: refer to Chapter 2.5)
– RS485 connecting cable
Cable between the RS232/RS485 interface converter and the
nodes to establish an RS485 link
(cable diagram: refer to Chapter 2.5 or Fig. 3-10)
4. Terminating resistor for the RS485 bus
3 Generally applies:
First and last node ––> terminating resistor switched–in
Other nodes on the bus ––> terminating resistor switched–out
(switch S1, refer to Chapter 1.3.2)
Serial interface
(e.g. COM 1) RS–48
RS232/RS485
5
Ç
ÇÇ
interface converter
PG/PC
ÇÇ
cable plug
ÇÇÇ 3
9–pin
Ç
ÇÇ
9–pin socket
socket Terminating resistor 120 Ω
0V +24 V
9–pin
socket
1 1 9–pin 1
9 9 plug 9
Data +
Data –
Note
Essentially the same as when specifying the possible node addresses
(drive numbers), up to 31 drives can be connected to an
RS232/RS485 interface converter (PC/PPI cable).