Professional Documents
Culture Documents
Fire Protection Hardware and Fire Science - 1st IIEE Socsargen Technical Webinar 2020
Fire Protection Hardware and Fire Science - 1st IIEE Socsargen Technical Webinar 2020
It is accompanied by a release of
energy in the form of heat and light
of varying intensities.
Oxygen Sources
Chemical Chain Reaction
Approx. 16% is required
Normal air contains 21% O2
Fuel Sources
Solid
Liquid
Gas
Heat Sources
Open Flames
Sparks and arcs FIRE TRIANGLE
Friction
Electrical energy
STAGES OF FIRE
DID YOU KNOW??
ELECTRICAL CONNECTIONS
TOP 3 WORST FIRE INCIDENT IN THE PHILIPPINES
DID YOU KNOW??
DIVISION 3. CLASSIFICATION
OF OCCUPANCY:
Assembly, Educational,
Complete/consolidated Health Care, Detention and
assessment: Building Correctional, Residential,
requirements Mercantile, Business,
Industrial, Storage, Mixed
DIVISION 6. FEATURES OF FIRE PROTECTION: Occupancies, Miscellaneous.
CONSTRUCTION AND COMPARTMENTATION,
PROTECTION OF VERTICAL OPENING AND
COMBUSTIBLE CONCEALED SPACES, INTERIOR DIVISION 4. HAZARD OF BUILDINGS
FINISH, FIRE DETECTION, ALARM, AND SECTION 10.2.4.2 CLASSIFICATION OF
COMMUNICATION
SYSTEMS, AUTOMATIC SPRINKLERS AND
HAZARD OF CONTENTS:
OTHER, EXTINGUISHING EQUIPMENT, Low, Moderate/Ordinary, and High
STANDPIPES, PORTABLE AND WHEELED FIRE DIVISION 5. MEANS OF EGRESS
EXTINGUISHERS, SEGREGATION AND -DOORS, STAIRS , OUTSIDE STAIRS , HORIZONTAL EXITS , RAMPS, EXIT
PROTECTION OF HAZARDS SECTION, SMOKE PASSAGEWAYS, ESCALATORS AND MOVING WALKS, FIRE ESCAPE
PARTITIONS , FIRE DOORS. STAIRS,LADDERS AND SLIDE ESCAPES, ILLUMINATION OF MEANS OF
EGRESS, EXIT MARKING ,EMERGENCY EVACUATION PLAN
FIRE COMPLIANCE ISSUE
RESPONSIBILITY OF ISSUANCE ON FIRE SAFETY INSPECTION CERTIFICATE (FSIC)
PEZA- Philippine
Economic Zone BFP- Bureau of Fire
Authority Protection
2. When a required fire alarm system is out of service for more than four (4) hours in a twenty-four hour (24-hr)
period, the C/MFM having jurisdiction shall be notified within twenty-four (24) hours, and a fire watch shall be
assigned until the fire alarm system has been returned to service.
3. To ensure operational integrity, the fire alarm system shall have an approved maintenance and testing program
which shall be developed by the building management in accordance with internationally accepted standards.
Records of conducted maintenance and testing should be maintained and submitted together with the FSMR
when required by the C/MFM having jurisdiction.
Philippine Electronic Code
NFPA 72 Book 2
National Fire Alarm Fire Detection and Alarm
and Signalling Code System
Revised 2019.
WHAT IS REQUIRED
WHEN A FIRE ALARM
IS REQUIRED OTHER REFERENCE
NFPA 90A
Standard for Smoke
Control System
Standards Refers:
Fire Code of the Philippines
RA 9514 Location NFPA 92
Standard for the Installation of Air
Revised Implementing Rules and NFPA 72 Design Details Conditioning and Ventilating Systems
Regulations Revised 2019 National Fire Alarm and
Signalling Code
Installation requirements
Revised 2019. Testing Standards
SYSTEM DESIGN QUALIFICATION
Design Designer
Requirements Requirements
INCLUDES:
Fire Detection and Alarm System
Fire Suppression System
Fire Sprinkler system
INCLUDES:
Fire –resistant walls & glass
Heavy duty fire –door
FIRE PROTECTION
PROTECTION AND PREVENTION HARDWARES
Automatic Fire
Suppression System
AFSS
WHAT IS FIRE DETECTION
AND ALARM SYSTEM
(FDAS)
Fire Detection and Alarm System Activation Sequence
Strobe horn
MIMIC Board
Monitor Switch
Alarm Gong
FIRE DETECTION AND ALARM SYSTEM
FDAS
Why Used Fire Detection and Alarm
System?
1. Used to protect;
LIFE
PROPERTY
2. Mandatory Requirements
ORDER OF RESPONSE;
1. Aspirating Detector
2. Spot Type Smoke Detector
3. Flame Detector
4. Heat Detector
CLASSIFICATION OF SYSTEM & BASIC COMPONENTS
• Manual pull station
• Heat Detector
• Smoke detector
Initiating Devices • Flame Detector
• Water flow Devices
• Tamper Switches
• Combination Detectors
• Bells
• Buzzers & Horns
Notification • Strobe Lights
Appliances • Speakers
• Recorded Voice Messages
• The one who receive and send signal to other devices in the
system.
28
FDAS Devices Functions & Controls
Power Source
• Main supply 220 or 230 VAC (Primary Supply)
29
FDAS Devices Functions & Controls
HD/SD -Detector
• Initiating Device
• Sends signal to FACP. (Automatic Operation)
Normal & Alarm Led • detect the presence of heat and an increase in air
Indicator:
temperature. These detectors have few false alarms but,
• Blinking Light for they take longer to identify a fire than a smoke detector.
Normal & Steady Light
for Alarm
• Blinking green Light for
Normal & Steady red
for Alarm
30
FDAS Devices Functions & Controls
Manual Pull Station
• Initiating Device
• Sends signal to panel if Working Temperature is reach.
(Manual Operation)
32
FDAS Devices Functions & Controls
Horn & Strobe
• Notification Device
• Gives an Alerting Sound & Flashing Light
33
TYPES OF FIRE
ALARM SYSTEM
Non –Addressable System
FACP
INITIATING DEVICES
NOTIFICATION APPLIANCES
Horn Strobe
E
O Sounder Circuit
L
Detectors
FIRE E
ALARM O ZONE 1
CONTROL L
SYSTEM
Manual Call Point
E
O ZONE 2
L
Addressable System
Each fire detector is provided with an
address
Identification of alarm status by zone and
by address
Fire detectors indicates various condition
such as smoke level
Indicates and records system events
NOTIFICATION APPLIANCES
INITIATING DEVICES
ZONE 1
Line Isolator Module
FIRE ALARM
ZONE 2
CONTROL
SYSTEM
ZONE 3
Line Isolator Module
FDAS System Operation Working Principle
Appropriate for small building such as retail store and small Best for large structure with may different
BUILDING SIZE restaurants rooms and even multiple businesses
Each device (smoke detector, heat detector, fore sprinkler, One wire connects all devices to a central
CABLING etc.) is connected to a control panel via a separate wire control panel
Tend to be more expensive and less efficient to install but Require more expertise to install due to
INSTALLATION most installer can handle the task programming and software requirements
Can be more costly since all devices have to be checked or Can alert to problems with one device, saving
MAINTENANCE replaced on overall maintenance and repair
ALARM Alarm activates when there is fire or smoke in any sector, Pinpoints fire location
FUNCTIONALITY without the ability to pinpoint which alarm is active
A severed wire between any device and the control panel Wire loop means that even if one end is
RELIABILITY
can render the device useless in fire protection severed signals can still reach the control panel
FDAS DESIGN FLOW
Project * Fire
Safety Building
Assessment
PROJECT
IMPLEMENTATION
Start with, what type of
protection is required
“LIFE, PROPERTY or BOTH”
Motorized Damper
Deluge System
AFSS
ELECTRICAL ROOM
WHAT IS DEDICATED
ELECTRICAL SPACE?
According to NFPA 70
Dedicated electrical space is defined as the space equal to
the with and the depth of the equipment extending from
the floor to a height of 1.8 m above the equipment or the
structural ceiling, which ever is lower
ELECTRICAL ROOM
Thank
you!
For more inquires;
Contact : 0950-224-1411
Email add: clifforddhonnscaburnay@yahoo.com