Contact

AAAC Aerial Conductors (Bare) General Sales


Neon 19_3.75 Phone: 0508 NEXANS
sales.nz@nexans.com

Nexans ref.: Neon 19_3.75


Country ref.: 5632

1120 Aluminium Alloy conductor. Made to AS 1531.

DESCRIPTION
Application

AAAC - All Aluminium Alloy Conductor

AAACaerial conductor has a high tensile strength, good corrosion resistance, light
weight and comparable current carrying capacity.

It is designed for medium and long spans, can be used for LV and MV distribution
networks.
STANDARDS
National AS 1531

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 6/06/21 www.nexans.co.nz Page 1 / 2
Contact
AAAC Aerial Conductors (Bare) General Sales
Neon 19_3.75 Phone: 0508 NEXANS
sales.nz@nexans.com

CHARACTERISTICS
Construction characteristics
Conductor material aluminum alloy
Dimensional characteristics
Conductor cross-section 210 mm²
Stranding (No./mm) 19/3.75
Nominal overall diameter 18.8 mm
Approximate weight 0.58 kg/m
Mechanical characteristics
Minimum breaking load 47.8 kN

ELECTRICAL PERFORMANCE DATA


Calculated DC Reactance at 50Hz with Current Rating Current Rating
Nexans ref. Resistance at 20°C 300mm Spacing Still Air 1 m/s
(0hm/km) (0hm/km) (Amps) (Amps)
Chlorine 0.864 0.310 104 200
Fluorine 0.599 0.299 131 250
Helium 0.383 0.285 173 328
Hydrogen 0.266 0.273 217 410
Iodine 0.239 0.270 231 438
Krypton 0.189 0.259 271 507
Neon 0.142 0.250 328 603
Nitrogen 0.114 0.242 381 690

NOTE
1. GC = Greased Core
2. Coefficient of linear expansion 23.0 x 10-6/°C.
3. Modulus of elasticity:
a. 65 GPa for seven (7) and nineteen (19) wire conductors.
b. 64 GPa for thirtyseven (37) and sixtyone (61) wire conductors.

Current ratings are based on ambient temperature of 30°C, a maximum conductor temperature of 75°C, rural
weathered, summer noon and intensity of solar radiation 1000 W/m².

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 6/06/21 www.nexans.co.nz Page 2 / 2