Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

6 5 4 3 2 1

WINDOW WINDOW
D D

1000

Oxygen Generator Plant Panel

DOOR W-4000 x H-3400


Compressor
Type: Oil Lubricated Screw
Compressor 2500
Length : 2500mm
C C
WINDOW

Breadth : 1500mm 3500


Air Treatment & Gas seperation
Height : 2000mm
6500 Weight : 2020 kg Control Unit 4000
Air Dryer - CS 650
Coarse, Fine, After Filters
Oxygen Generator - GO960
Air receiver 2000 Litrs
Oxygen receiver 2000 Litrs
Control Panel
1000 Pressure Regulation System
2500 1000 Height : 2900 mm 1000
1000 Weight : 4100 kg

Power Panel
(L x B x H)
300 1300 x 300 x 1800 mm 3500
Weight : 350 Kg
1000

B B

WINDOW WINDOW
9000
FOUNDATION:
Oxygen Generator Plant 3500 X 3500 X 100 mm (LXBXH)
Note: Compressor 2500 X 2500 X 100 mm (LXBXH)
1. All the measurements are in mm & Kg and are approximate only.
2. Recommended Room size 9000 x 6500 x 3900 mm min (L x B x H)
3. Ducting to be carry out from Air compressor Exhaust. Does this drawing contains critical
TITLE CUSTOMER
Interface Dimensions : ----
4. Ventilation is required for air circulation. Critical to Quality Characteristics
PRODUCT OXYGEN GENERATOR
5. 100 mm platform is required for compressors placing Marked thus : ---- PLANT LAYOUT - GO 960 DRG NO ----
6. Incoming cable recommendations for power distribution panel UNLESS OTHERWISESPECIFIED USE THE FOLLOWING
UNLESS SPECIFIED ALL DIMS. ARE IN mm REV LEVEL R0
A 3.5 core x 120 Sq.mm Copper cable. GENERAL TOLERANCE FOR LINEAR DIMENSION 3.2
IS 2102 (PART 1) 1993 ISO 2768 -1: 1989
SCALE SHEET File :\\D:Selva/drawings\go series A
7. Provide Earth 2 places in compressor and 1 place in power distribution panel DIMS. 0.5/6 6/30 30/120 120/400 400/1000
NTS 1 OF 1 MEASUREMENT SHOULD NOT
MATERIAL : VARIES QTY:
(cable size: 25 x 3 flat Copper) --- BE TAKEN AS REF. FROM DRG.
FINE `0.05 `0.1 `0.15 `0.2 `0.3
8. Provide Earth for oxygen generator plant panel (cable size: 1.5 gauge) Separately. APPROVED RSK 22-10-2020
This Drawing which Contains Proprietary information is the
CJP
property of Trident Pneumatics Pvt. Ltd. It shall not be
reproduced in any manner nor disclosed to third parties without
CHECKED
DRAWN
22-10-2020
22-10-2020
TRIDENT
getting written permission of Trident Pneumatics Pvt. Ltd. RVK
6 5 4 3 2 1