Reckitt Benckiser - Khi

Installation data _______________________________________________________________________________________________

Installation data

Project: Reckitt Benckiser - Khi


Installer: SUNMARS ENTERPRISES
Phone: 0321 2755707

This report contains 29 pages.

This printout contains the following reports:


Security network data
Panel Configuration
Settings panel
Analogue Loop (Overview)
Analogue Loop (graphical view)
Detector zones
- reports devices for each detector zone
- Detector and output zones for transceiver
Control zones
Masterboxes
Activations
Switch Functions

Page 1 of 29
Reckitt Benckiser - Khi
Overview of all devices in a security network ________________________________________________________________________

Security network data

Number of devices: 2
of which 2 fire alarm panels
Rate of transmission: 500 kBaud

Installed bus devices


Quantity: 116
Automatic Detector
Quantity: 95 of which
93 O-Detector
2 RoR Temperature Detector
Manual Call Point (MCP/TAM)
Quantity: 5
Transponder
Quantity: 1
Sounder/Flasher
Quantity: 15 of which
11 acoustic
4 flash/sound

Panel number 1 ; Reckitt Benckiser -1


Panel Type: FACP IQ8Control-M
Zone ranges Detector zones Control zones Masterbox
1 to 100 11 to 100 1 to 10
Installed Masterboxes: no Master Box
Panel number 2 ; Reckitt Benckiser -2
Panel Type: FACP IQ8Control-M
Zone ranges Detector zones Control zones Masterbox
101 to 200 101 to 200 ---
Installed Masterboxes: no Master Box

Page 2 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Hardware panel no. 1: __________________________________________________________________________________________

Panel Configuration

Panel number 1: FACP IQ8Control-M; Name / Label: Reckitt Benckiser -1


Hardware: Individual Loop Indicator (ILI): not available
Printer: not available
Basic Module:
Serial Interface: not in use
Common fault relay Control Zone 11;
Micro module: Network MM 500k-Module (primary loop 113)
Micro module card 1
Micro module 1: not in use
Micro module 2: not in use
Micro module 3: not in use

Micro module card 2


Micro module 1: Powered Loop-Module with 116 devices (primary loop 131)
Micro module 2: not in use
Micro module 3: not in use

Installed bus devices


Quantity: 116
Automatic Detector
Quantity: 95 of which
93 O-Detector
2 RoR Temperature Detector
Manual Call Point (MCP/TAM)
Quantity: 5
Transponder
Quantity: 1
Sounder/Flasher
Quantity: 15 of which
11 acoustic
4 flash/sound

Page 3 of 29
Reckitt Benckiser - Khi Panel 2; Reckitt Benckiser -2
Hardware panel no. 2: __________________________________________________________________________________________

Panel Configuration

Panel number 2: FACP IQ8Control-M; Name / Label: Reckitt Benckiser -2


Hardware: Individual Loop Indicator (ILI): not available
Printer: not available
Basic Module:
Serial Interface: not in use
Common fault relay Control Zone 111;
Micro module: Network MM 500k-Module (primary loop 213)
Micro module card 1
Micro module 1: not in use
Micro module 2: not in use
Micro module 3: not in use

Installed bus devices


Quantity: 0
Automatic Detector
Quantity: 0
Manual Call Point (MCP/TAM)
Quantity: 0
Transponder
Quantity: 0
Sounder/Flasher
Quantity: 0

Page 4 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Settings panel no. 1: ___________________________________________________________________________________________

Settings panel

Panel number 1: FACP IQ8Control-M; Name / Label: Reckitt Benckiser -1

Configuration:
Person in Charge:
Date and Time: 14.10.2019 23:08:13
Software version for the control panel: 3.12.000
Access Code: not available
Acts in a security network as Network Panel

Zone ranges Detector zones


1 to 100
Number of used detector zones: 14

Zone ranges Control zones


11 to 100
Number of used control zones: 22

Zone ranges Masterbox


1 to 10

Country Version: FM Global class 3010


Test Mode Options: Standard behaviour

Special Functionality: Disablement of single sounder allowed


Allow operation on primary loops
Retrigger sounders with every new fire

Language: English
Display text: Reckitt Benckiser -1

Display and Buzzer: Display level for " Fire Zone"


Do not print...
Sector Activation

Delay time on common trouble 0 minutes


Delay time on power supply trouble 3 minutes
Verification time for output sectors 0 seconds
Delay time for output sectors 0 seconds
Maximum time for test mode 0 minutes

Signal templates
Signal in acc. with DIN 33404.3 (in use)
repeated: until sounder silence
1st signal component: DIN Ton (until sounder silence)

Page 5 of 29
Reckitt Benckiser - Khi Panel 2; Reckitt Benckiser -2
Settings panel no. 2: ___________________________________________________________________________________________

Settings panel

Panel number 2: FACP IQ8Control-M; Name / Label: Reckitt Benckiser -2

Configuration:
Person in Charge:
Date and Time: 14.10.2019 21:50:58
Software version for the control panel: 3.12.000
Access Code: not available
Acts in a security network as Network Panel

Zone ranges Detector zones


101 to 200
Number of used detector zones: 0

Zone ranges Control zones


101 to 200
Number of used control zones: 1

Zone ranges Masterbox


not in use

Country Version: FM Global class 3010


Test Mode Options: Standard behaviour

Special Functionality: Disablement of single sounder allowed


Allow operation on primary loops
Retrigger sounders with every new fire

Language: English
Display text: Reckitt Benckiser -2

Display and Buzzer: Display level for " Fire Zone"


Do not print...
Sector Activation

Delay time on common trouble 0 minutes


Delay time on power supply trouble 3 minutes
Verification time for output sectors 0 seconds
Delay time for output sectors 0 seconds
Maximum time for test mode 0 minutes

Signal templates
Signal in acc. with DIN 33404.3 (in use)
repeated: until sounder silence
1st signal component: DIN Ton (until sounder silence)

Page 6 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

Analogue Loop (Overview)

Loop devices for analogue loop 131; F-14 Ware House Loop
In Degraded Mode Activations are reported as Fire

SA 1 IQ8/FSo with Isolator


Serial No.: 156063667138; Allocation: zone 15/detector 1 ; SECURITY RM F 14 SND-1
Activation sounder with control zone 15
Volume: 100%
SA 2 IQ8/FSo with Isolator
Serial No.: 156063667206; Allocation: zone 15/detector 2 ; SECURITY RM OFFICE SND-2
Activation sounder with control zone 17
Volume: 100%
SA 3 IQ8/FSo with Isolator
Serial No.: 156063666445; Allocation: zone 15/detector 3 ; SECURITY RM H-H-BL SND-3
Activation sounder with control zone 19
Volume: 100%
SA 4 IQ8/FSo with Isolator
Serial No.: 156063667305; Allocation: zone 15/detector 4 ; SECURITY RM PHARMA SND-4
Activation sounder with control zone 21
Volume: 100%
SA 5 IQ8/So with Isolator
Serial No.: 156054676002; Allocation: zone 15/detector 5 ; F-14 Ware Huse Secrty SND
Activation sounder with control zone 23
Volume: 100%
SA 6 O with Isolator
Serial No.: 107115340844; Allocation: zone 13/detector 3 ; F-14 Q.LAB Corridor SD-1
SA 7 O with Isolator
Serial No.: 107115337189; Allocation: zone 13/detector 4 ; F-14 Q.LAB Traning Room
SA 8 O with Isolator
Serial No.: 107115340493; Allocation: zone 13/detector 5 ; F-14 Q.LAB DOC Archive
SA 9 O with Isolator
Serial No.: 107115340790; Allocation: zone 13/detector 6 ; F-14 Q.LAB Corridor SD-2
SA 10 O with Isolator
Serial No.: 107115364581; Allocation: zone 13/detector 7 ; F-14 Q.LAB Stability Room
SA 11 O with Isolator
Serial No.: 107115341209; Allocation: zone 13/detector 8 ; F-14 Q.LAB Temp Cont Equi
SA 12 O with Isolator
Serial No.: 107124191154; Allocation: zone 13/detector 9 ; F-14 Q.LAB Packing store
SA 13 O with Isolator
Serial No.: 107115340387; Allocation: zone 13/detector 10 ; F-14 Q.LAB Packing Lab
SA 14 MCP with Isolator
Serial No.: 145113359406; Allocation: zone 11/detector 2 ; F-14 Q.LAB Corridor MCP
SA 15 IQ8/So with Isolator
Serial No.: 156054876075; Allocation: zone 15/detector 6 ; F-14 Q.LAB Corridor SND
Activation sounder with control zone 24
Volume: 100%
SA 16 O with Isolator
Serial No.: 107115340967; Allocation: zone 13/detector 11 ; F-14 Q.LAB Corridor SD-3
SA 17 T RoR with Isolator
Serial No.: 138116397858; Allocation: zone 13/detector 12 ; F-14 Q.LAB Temp Cont Room
SA 18 O with Isolator

Page 7 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

Serial No.: 107110615930; Allocation: zone 12/detector 11 ; F-14 Q.LAB Corridor SD-4
SA 19 O with Isolator
Serial No.: 107115340738; Allocation: zone 12/detector 12 ; F-14 Q.LAB Instrmt Lb SD1
SA 20 O with Isolator
Serial No.: 107115353998; Allocation: zone 12/detector 13 ; F-14 Q.LAB Instrmt Lb SD2
SA 21 T RoR with Isolator
Serial No.: 138116894463; Allocation: zone 12/detector 14 ; F-14 Q.LAB Instrmt Lb SD3
SA 22 O with Isolator
Serial No.: 107115364901; Allocation: zone 12/detector 15 ; F-14 Q.LAB Retention SD1
SA 23 O with Isolator
Serial No.: 107100076475; Allocation: zone 12/detector 16 ; F-14 Q.LAB Retention SD2
SA 24 MCP with Isolator
Serial No.: 145110775018; Allocation: zone 11/detector 3 ; F-14 Q.LAB Corridor MCP
SA 25 IQ8/So with Isolator
Serial No.: 156054876099; Allocation: zone 15/detector 7 ; F-14 Q.LAB Corridor SND
Activation sounder with control zone 25
Volume: 100%
SA 26 O with Isolator
Serial No.: 107115333105; Allocation: zone 12/detector 17 ; F-14 Q.LAB Wet Chem8stry
SA 27 O with Isolator
Serial No.: 107115334034; Allocation: zone 12/detector 18 ; F-14 Q.LAB Wet Chemstry7
SA 28 O with Isolator
Serial No.: 107115333419; Allocation: zone 12/detector 19 ; F-14 Q.LAB Wet Chemstry6
SA 29 O with Isolator
Serial No.: 107115333259; Allocation: zone 12/detector 20 ; F-14 Q.LAB Wet Chemstry5
SA 30 O with Isolator
Serial No.: 139107220445; Allocation: zone 12/detector 1 ; F-14 Q.LAB Wet Chemstry3
SA 31 O with Isolator
Serial No.: 107115332948; Allocation: zone 12/detector 22 ; F-14 Q.LAB Wet Chemstry2
SA 32 O with Isolator
Serial No.: 107100076727; Allocation: zone 12/detector 23 ; F-14 Q.LAB Wet Chemstry1
SA 33 O with Isolator
Serial No.: 107115364932; Allocation: zone 12/detector 24 ; F-14 Q.LAB Wet Chemistry
SA 34 O with Isolator
Serial No.: 107115364680; Allocation: zone 12/detector 25 ; F-14 Q.LAB Wet Chemistry
SA 35 O with Isolator
Serial No.: 107115336953; Allocation: zone 12/detector 26 ; F-14 Q.LAB SSG Pilot Area
SA 36 O with Isolator
Serial No.: 107115340776; Allocation: zone 12/detector 27 ; F-14 Q.LAB Documtion SD1
SA 37 O with Isolator
Serial No.: 107115332122; Allocation: zone 12/detector 28 ; F-14 Q.LAB Documtion SD2
SA 38 O with Isolator
Serial No.: 107115341247; Allocation: zone 12/detector 29 ; F-14 Q.LAB Corridor SD5
SA 39 IQ8/So with Isolator
Serial No.: 156054877188; Allocation: zone 8/detector 1 ; F-14 Q.LAB Corridor SND
Activation sounder with control zone 26
Volume: 100%
SA 40 MCP with Isolator
Serial No.: 145112833686; Allocation: zone 11/detector 4 ; F-14 Q.LAB Corridor MCP
SA 41 O with Isolator

Page 8 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

Serial No.: 107115340707; Allocation: zone 12/detector 30 ; F-14 Q.LAB Corridor SD6
SA 42 O with Isolator
Serial No.: 107115337578; Allocation: zone 12/detector 31 ; F-14 Q.LAB Meeting Room
SA 43 O with Isolator
Serial No.: 107115341117; Allocation: zone 12/detector 32 ; F-14 Q.LAB Meeting Room
SA 44 O with Isolator
Serial No.: 107115364260; Allocation: zone 13/detector 1 ; F-14 Q.LAB Ofc Seting SD1
SA 45 O with Isolator
Serial No.: 107115364109; Allocation: zone 13/detector 2 ; F-14 Q.LAB Ofc Seting SD2
SA 46 IQ8/So with Isolator
Serial No.: 156054676606; Allocation: zone 8/detector 2 ; F-14 Ware House SND-1
Activation sounder with control zone 27
Volume: 100%
SA 47 O with Isolator
Serial No.: 139105724389; Allocation: zone 20/detector 1 ; F-14 Ware House SD A
SA 48 O with Isolator
Serial No.: 139105723436; Allocation: zone 20/detector 2 ; F-14 Ware House SD B
SA 49 O with Isolator
Serial No.: 107115365236; Allocation: zone 20/detector 3 ; F-14 Ware House SD-28
SA 50 O with Isolator
Serial No.: 107115364253; Allocation: zone 20/detector 4 ; F-14 Ware House SD-29
SA 51 O with Isolator
Serial No.: 107115364079; Allocation: zone 20/detector 5 ; F-14 Ware House SD-30
SA 52 O with Isolator
Serial No.: 107115364642; Allocation: zone 20/detector 6 ; F-14 Ware House SD-31
SA 53 O with Isolator
Serial No.: 107115365120; Allocation: zone 20/detector 7 ; F-14 Ware House SD-32
SA 54 O with Isolator
Serial No.: 107115364222; Allocation: zone 20/detector 8 ; F-14 Ware House SD-33
SA 55 O with Isolator
Serial No.: 107115364574; Allocation: zone 10/detector 9 ; F-14 Ware House SD-34
SA 56 O with Isolator
Serial No.: 107115365113; Allocation: zone 10/detector 10 ; F-14 Ware House SD-35
SA 57 O with Isolator
Serial No.: 107115365069; Allocation: zone 10/detector 11 ; F-14 Ware House SD-36
SA 58 O with Isolator
Serial No.: 107115365076; Allocation: zone 10/detector 12 ; F-14 Ware House SD-37
SA 59 O with Isolator
Serial No.: 107115364567; Allocation: zone 10/detector 13 ; F-14 Ware House SD-38
SA 60 O with Isolator
Serial No.: 107115364208; Allocation: zone 10/detector 14 ; F-14 Ware House SD-39
SA 61 O with Isolator
Serial No.: 107115364703; Allocation: zone 10/detector 15 ; F-14 Ware House SD-40
SA 62 O with Isolator
Serial No.: 107115365243; Allocation: zone 10/detector 16 ; F-14 Ware House SD-41
SA 63 O with Isolator
Serial No.: 107115365045; Allocation: zone 10/detector 17 ; F-14 Ware House SD-42
SA 64 IQ8/So with Isolator
Serial No.: 156054875245; Allocation: zone 8/detector 3 ; F-14 Ware House SND-5
Activation sounder with control zone 28

Page 9 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

Volume: 100%
SA 65 O with Isolator
Serial No.: 107115364789; Allocation: zone 10/detector 18 ; F-14 Ware House SD-43
SA 66 O with Isolator
Serial No.: 107115365199; Allocation: zone 10/detector 19 ; F-14 Ware House SD-44
SA 67 O with Isolator
Serial No.: 107115364765; Allocation: zone 10/detector 20 ; F-14 Ware House SD-45
SA 68 O with Isolator
Serial No.: 107115364666; Allocation: zone 10/detector 21 ; F-14 Ware House SD-46
SA 69 O with Isolator
Serial No.: 107115364277; Allocation: zone 10/detector 22 ; F-14 Ware House SD-47
SA 70 O with Isolator
Serial No.: 107115364888; Allocation: zone 10/detector 23 ; F-14 Ware House SD-48
SA 71 O with Isolator
Serial No.: 107115364994; Allocation: zone 10/detector 24 ; F-14 Ware House SD-49
SA 72 O with Isolator
Serial No.: 107115354001; Allocation: zone 10/detector 25 ; F-14 Ware House SD-50
SA 73 O with Isolator
Serial No.: 107115365267; Allocation: zone 10/detector 26 ; F-14 Ware House SD-51
SA 74 O with Isolator
Serial No.: 107115364659; Allocation: zone 10/detector 27 ; F-14 Ware House SD-52
SA 75 MCP with Isolator
Serial No.: 145112834324; Allocation: zone 11/detector 1 ; F-14 Ware House MCP-1
SA 76 IQ8/So with Isolator
Serial No.: 156054876716; Allocation: zone 8/detector 4 ; F-14 Ware House SND-6
Activation sounder with control zone 29
Volume: 100%
SA 77 O with Isolator
Serial No.: 107110607805; Allocation: zone 10/detector 28 ; F-14 Ware House SD-1
SA 78 O with Isolator
Serial No.: 107110607935; Allocation: zone 10/detector 29 ; F-14 Ware House SD-2
SA 79 O with Isolator
Serial No.: 107110607843; Allocation: zone 10/detector 30 ; F-14 Ware House SD-3
SA 80 O with Isolator
Serial No.: 107110607737; Allocation: zone 10/detector 31 ; F-14 Ware House SD-4
SA 81 IQ8/So with Isolator
Serial No.: 156054675180; Allocation: zone 8/detector 5 ; F-14 Ware House SND-2
Activation sounder with control zone 30
Volume: 100%
SA 82 O with Isolator
Serial No.: 107110607867; Allocation: zone 10/detector 32 ; F-14 Ware House SD-5
SA 83 O with Isolator
Serial No.: 107110608215; Allocation: zone 9/detector 1 ; F-14 Ware House SD-6
SA 84 O with Isolator
Serial No.: 107106384239; Allocation: zone 9/detector 2 ; F-14 Ware House SD-7
SA 85 O with Isolator
Serial No.: 107110607720; Allocation: zone 9/detector 3 ; F-14 Ware House SD-8
SA 86 O with Isolator
Serial No.: 139105723474; Allocation: zone 14/detector 5 ; F-14 STORE SD
SA 87 O with Isolator

Page 10 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

Serial No.: 139105723801; Allocation: zone 14/detector 1 ; F-14 ENGG STORE SD 1


SA 88 O with Isolator
Serial No.: 139105722088; Allocation: zone 14/detector 2 ; F-14 ENGG STORE SD 2
SA 89 O with Isolator
Serial No.: 139105734951; Allocation: zone 14/detector 3 ; F-14 ENGG STORE SD 3
SA 90 MCP with Isolator
Serial No.: 145127044800; Allocation: zone 11/detector 5 ; F-14 ENGG STORE MCP
SA 91 IQ8/So with Isolator
Serial No.: 156056253577; Allocation: zone 8/detector 6 ; F-14 ENGG STORE SND
Activation sounder with control zone 31
Volume: 100%
SA 92 O with Isolator
Serial No.: 139105724495; Allocation: zone 14/detector 4 ; F-14 ENGG STORE OFC SD
SA 93 Alarm. with Isolator
Serial No.: 4313667721; Allocation: zone 21/detector 1 ; F 14 transponder beam
SA 94 O with Isolator
Serial No.: 107106384222; Allocation: zone 9/detector 4 ; F-14 Ware House SD-9
SA 95 O with Isolator
Serial No.: 107110608741; Allocation: zone 14/detector 6 ; F-14 Turpentine SD-1
SA 96 O with Isolator
Serial No.: 107110607713; Allocation: zone 14/detector 7 ; F-14 Turpentine SD-2
SA 97 O with Isolator
Serial No.: 107110607744; Allocation: zone 9/detector 5 ; F-14 Ware House SD-10
SA 98 IQ8/So with Isolator
Serial No.: 156054676651; Allocation: zone 8/detector 7 ; F-14 Ware House SND-3
Activation sounder with control zone 32
Volume: 100%
SA 99 O with Isolator
Serial No.: 107110608765; Allocation: zone 9/detector 6 ; F-14 Ware House SD-11
SA 100 O with Isolator
Serial No.: 107106385908; Allocation: zone 9/detector 7 ; F-14 Ware House SD-12
SA 101 O with Isolator
Serial No.: 107110608710; Allocation: zone 9/detector 8 ; F-14 Ware House SD-13
SA 102 O with Isolator
Serial No.: 107110607928; Allocation: zone 9/detector 9 ; F-14 Ware House SD-14
SA 103 O with Isolator
Serial No.: 107110600974; Allocation: zone 9/detector 10 ; F-14 Ware House SD-15
SA 104 O with Isolator
Serial No.: 107110608048; Allocation: zone 9/detector 11 ; F-14 Ware House SD-16
SA 105 O with Isolator
Serial No.: 107110608345; Allocation: zone 9/detector 12 ; F-14 Ware House SD-17
SA 106 O with Isolator
Serial No.: 107110608789; Allocation: zone 9/detector 13 ; F-14 Ware House SD-18
SA 107 O with Isolator
Serial No.: 107110608673; Allocation: zone 9/detector 14 ; F-14 Ware House SD-19
SA 108 IQ8/So with Isolator
Serial No.: 156054676712; Allocation: zone 8/detector 8 ; F-14 Ware House SND-4
Activation sounder with control zone 33
Volume: 100%
SA 109 O with Isolator

Page 11 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

Serial No.: 107110607751; Allocation: zone 9/detector 15 ; F-14 Ware House SD-20
SA 110 O with Isolator
Serial No.: 107110608758; Allocation: zone 9/detector 16 ; F-14 Ware House SD-21
SA 111 O with Isolator
Serial No.: 107110608468; Allocation: zone 9/detector 17 ; F-14 Ware House SD-22
SA 112 O with Isolator
Serial No.: 107110608031; Allocation: zone 9/detector 18 ; F-14 Ware House SD-23
SA 113 O with Isolator
Serial No.: 107110608871; Allocation: zone 9/detector 19 ; F-14 Ware House SD-24
SA 114 O with Isolator
Serial No.: 107110607997; Allocation: zone 9/detector 20 ; F-14 Ware House SD-25
SA 115 O with Isolator
Serial No.: 107106385014; Allocation: zone 9/detector 21 ; F-14 Ware House SD-26
SA 116 O with Isolator
Serial No.: 107110608772; Allocation: zone 9/detector 22 ; F-14 Ware House SD-27

Page 12 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

IQ8/FSo
Serial No.: 156063667138
zone 15/detector 1
SECURITY RM F 14 SND-1
IQ8/FSo
Serial No.: 156063667206
zone 15/detector 2
SECURITY RM OFFICE SND-2
IQ8/FSo
Serial No.: 156063666445
zone 15/detector 3
SECURITY RM H-H-BL SND-3
IQ8/FSo
Serial No.: 156063667305
zone 15/detector 4
SECURITY RM PHARMA SND-4
IQ8/So
Serial No.: 156054676002
zone 15/detector 5
F-14 Ware Huse Secrty SND
O
Serial No.: 107115340844
zone 13/detector 3
F-14 Q.LAB Corridor SD-1
O
Serial No.: 107115337189
zone 13/detector 4
F-14 Q.LAB Traning Room
O
Serial No.: 107115340493
zone 13/detector 5
F-14 Q.LAB DOC Archive
O
Serial No.: 107115340790
zone 13/detector 6
F-14 Q.LAB Corridor SD-2
O
Serial No.: 107115364581
zone 13/detector 7
F-14 Q.LAB Stability Room
O
Serial No.: 107115341209
zone 13/detector 8
F-14 Q.LAB Temp Cont Equi
O
Serial No.: 107124191154
zone 13/detector 9
F-14 Q.LAB Packing store
O
Serial No.: 107115340387
zone 13/detector 10
F-14 Q.LAB Packing Lab

Page 13 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

MCP
Serial No.: 145113359406
zone 11/detector 2
F-14 Q.LAB Corridor MCP
IQ8/So
Serial No.: 156054876075
zone 15/detector 6
F-14 Q.LAB Corridor SND
O
Serial No.: 107115340967
zone 13/detector 11
F-14 Q.LAB Corridor SD-3
T RoR
Serial No.: 138116397858
zone 13/detector 12
F-14 Q.LAB Temp Cont Room
O
Serial No.: 107110615930
zone 12/detector 11
F-14 Q.LAB Corridor SD-4
O
Serial No.: 107115340738
zone 12/detector 12
F-14 Q.LAB Instrmt Lb SD1
O
Serial No.: 107115353998
zone 12/detector 13
F-14 Q.LAB Instrmt Lb SD2
T RoR
Serial No.: 138116894463
zone 12/detector 14
F-14 Q.LAB Instrmt Lb SD3
O
Serial No.: 107115364901
zone 12/detector 15
F-14 Q.LAB Retention SD1
O
Serial No.: 107100076475
zone 12/detector 16
F-14 Q.LAB Retention SD2
MCP
Serial No.: 145110775018
zone 11/detector 3
F-14 Q.LAB Corridor MCP
IQ8/So
Serial No.: 156054876099
zone 15/detector 7
F-14 Q.LAB Corridor SND
O
Serial No.: 107115333105
zone 12/detector 17
F-14 Q.LAB Wet Chem8stry

Page 14 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

O
Serial No.: 107115334034
zone 12/detector 18
F-14 Q.LAB Wet Chemstry7
O
Serial No.: 107115333419
zone 12/detector 19
F-14 Q.LAB Wet Chemstry6
O
Serial No.: 107115333259
zone 12/detector 20
F-14 Q.LAB Wet Chemstry5
O
Serial No.: 139107220445
zone 12/detector 1
F-14 Q.LAB Wet Chemstry3
O
Serial No.: 107115332948
zone 12/detector 22
F-14 Q.LAB Wet Chemstry2
O
Serial No.: 107100076727
zone 12/detector 23
F-14 Q.LAB Wet Chemstry1
O
Serial No.: 107115364932
zone 12/detector 24
F-14 Q.LAB Wet Chemistry
O
Serial No.: 107115364680
zone 12/detector 25
F-14 Q.LAB Wet Chemistry
O
Serial No.: 107115336953
zone 12/detector 26
F-14 Q.LAB SSG Pilot Area
O
Serial No.: 107115340776
zone 12/detector 27
F-14 Q.LAB Documtion SD1
O
Serial No.: 107115332122
zone 12/detector 28
F-14 Q.LAB Documtion SD2
O
Serial No.: 107115341247
zone 12/detector 29
F-14 Q.LAB Corridor SD5
IQ8/So
Serial No.: 156054877188
zone 8/detector 1
F-14 Q.LAB Corridor SND

Page 15 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

MCP
Serial No.: 145112833686
zone 11/detector 4
F-14 Q.LAB Corridor MCP
O
Serial No.: 107115340707
zone 12/detector 30
F-14 Q.LAB Corridor SD6
O
Serial No.: 107115337578
zone 12/detector 31
F-14 Q.LAB Meeting Room
O
Serial No.: 107115341117
zone 12/detector 32
F-14 Q.LAB Meeting Room
O
Serial No.: 107115364260
zone 13/detector 1
F-14 Q.LAB Ofc Seting SD1
O
Serial No.: 107115364109
zone 13/detector 2
F-14 Q.LAB Ofc Seting SD2
IQ8/So
Serial No.: 156054676606
zone 8/detector 2
F-14 Ware House SND-1
O
Serial No.: 139105724389
zone 20/detector 1
F-14 Ware House SD A
O
Serial No.: 139105723436
zone 20/detector 2
F-14 Ware House SD B
O
Serial No.: 107115365236
zone 20/detector 3
F-14 Ware House SD-28
O
Serial No.: 107115364253
zone 20/detector 4
F-14 Ware House SD-29
O
Serial No.: 107115364079
zone 20/detector 5
F-14 Ware House SD-30
O
Serial No.: 107115364642
zone 20/detector 6
F-14 Ware House SD-31

Page 16 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

O
Serial No.: 107115365120
zone 20/detector 7
F-14 Ware House SD-32
O
Serial No.: 107115364222
zone 20/detector 8
F-14 Ware House SD-33
O
Serial No.: 107115364574
zone 10/detector 9
F-14 Ware House SD-34
O
Serial No.: 107115365113
zone 10/detector 10
F-14 Ware House SD-35
O
Serial No.: 107115365069
zone 10/detector 11
F-14 Ware House SD-36
O
Serial No.: 107115365076
zone 10/detector 12
F-14 Ware House SD-37
O
Serial No.: 107115364567
zone 10/detector 13
F-14 Ware House SD-38
O
Serial No.: 107115364208
zone 10/detector 14
F-14 Ware House SD-39
O
Serial No.: 107115364703
zone 10/detector 15
F-14 Ware House SD-40
O
Serial No.: 107115365243
zone 10/detector 16
F-14 Ware House SD-41
O
Serial No.: 107115365045
zone 10/detector 17
F-14 Ware House SD-42
IQ8/So
Serial No.: 156054875245
zone 8/detector 3
F-14 Ware House SND-5
O
Serial No.: 107115364789
zone 10/detector 18
F-14 Ware House SD-43

Page 17 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

O
Serial No.: 107115365199
zone 10/detector 19
F-14 Ware House SD-44
O
Serial No.: 107115364765
zone 10/detector 20
F-14 Ware House SD-45
O
Serial No.: 107115364666
zone 10/detector 21
F-14 Ware House SD-46
O
Serial No.: 107115364277
zone 10/detector 22
F-14 Ware House SD-47
O
Serial No.: 107115364888
zone 10/detector 23
F-14 Ware House SD-48
O
Serial No.: 107115364994
zone 10/detector 24
F-14 Ware House SD-49
O
Serial No.: 107115354001
zone 10/detector 25
F-14 Ware House SD-50
O
Serial No.: 107115365267
zone 10/detector 26
F-14 Ware House SD-51
O
Serial No.: 107115364659
zone 10/detector 27
F-14 Ware House SD-52
MCP
Serial No.: 145112834324
zone 11/detector 1
F-14 Ware House MCP-1
IQ8/So
Serial No.: 156054876716
zone 8/detector 4
F-14 Ware House SND-6
O
Serial No.: 107110607805
zone 10/detector 28
F-14 Ware House SD-1
O
Serial No.: 107110607935
zone 10/detector 29
F-14 Ware House SD-2

Page 18 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

O
Serial No.: 107110607843
zone 10/detector 30
F-14 Ware House SD-3
O
Serial No.: 107110607737
zone 10/detector 31
F-14 Ware House SD-4
IQ8/So
Serial No.: 156054675180
zone 8/detector 5
F-14 Ware House SND-2
O
Serial No.: 107110607867
zone 10/detector 32
F-14 Ware House SD-5
O
Serial No.: 107110608215
zone 9/detector 1
F-14 Ware House SD-6
O
Serial No.: 107106384239
zone 9/detector 2
F-14 Ware House SD-7
O
Serial No.: 107110607720
zone 9/detector 3
F-14 Ware House SD-8
O
Serial No.: 139105723474
zone 14/detector 5
F-14 STORE SD
O
Serial No.: 139105723801
zone 14/detector 1
F-14 ENGG STORE SD 1
O
Serial No.: 139105722088
zone 14/detector 2
F-14 ENGG STORE SD 2
O
Serial No.: 139105734951
zone 14/detector 3
F-14 ENGG STORE SD 3
MCP
Serial No.: 145127044800
zone 11/detector 5
F-14 ENGG STORE MCP
IQ8/So
Serial No.: 156056253577
zone 8/detector 6
F-14 ENGG STORE SND

Page 19 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

O
Serial No.: 139105724495
zone 14/detector 4
F-14 ENGG STORE OFC SD
Alarm.
Serial No.: 4313667721
zone 21/detector 1
F 14 transponder beam
O
Serial No.: 107106384222
zone 9/detector 4
F-14 Ware House SD-9
O
Serial No.: 107110608741
zone 14/detector 6
F-14 Turpentine SD-1
O
Serial No.: 107110607713
zone 14/detector 7
F-14 Turpentine SD-2
O
Serial No.: 107110607744
zone 9/detector 5
F-14 Ware House SD-10
IQ8/So
Serial No.: 156054676651
zone 8/detector 7
F-14 Ware House SND-3
O
Serial No.: 107110608765
zone 9/detector 6
F-14 Ware House SD-11
O
Serial No.: 107106385908
zone 9/detector 7
F-14 Ware House SD-12
O
Serial No.: 107110608710
zone 9/detector 8
F-14 Ware House SD-13
O
Serial No.: 107110607928
zone 9/detector 9
F-14 Ware House SD-14
O
Serial No.: 107110600974
zone 9/detector 10
F-14 Ware House SD-15
O
Serial No.: 107110608048
zone 9/detector 11
F-14 Ware House SD-16

Page 20 of 29
Reckitt Benckiser - Khi
Loop devices for analogue loop 131; F-14 Ware House Loop ___________________________________________________________

O
Serial No.: 107110608345
zone 9/detector 12
F-14 Ware House SD-17
O
Serial No.: 107110608789
zone 9/detector 13
F-14 Ware House SD-18
O
Serial No.: 107110608673
zone 9/detector 14
F-14 Ware House SD-19
IQ8/So
Serial No.: 156054676712
zone 8/detector 8
F-14 Ware House SND-4
O
Serial No.: 107110607751
zone 9/detector 15
F-14 Ware House SD-20
O
Serial No.: 107110608758
zone 9/detector 16
F-14 Ware House SD-21
O
Serial No.: 107110608468
zone 9/detector 17
F-14 Ware House SD-22
O
Serial No.: 107110608031
zone 9/detector 18
F-14 Ware House SD-23
O
Serial No.: 107110608871
zone 9/detector 19
F-14 Ware House SD-24
O
Serial No.: 107110607997
zone 9/detector 20
F-14 Ware House SD-25
O
Serial No.: 107106385014
zone 9/detector 21
F-14 Ware House SD-26
O
Serial No.: 107110608772
zone 9/detector 22
F-14 Ware House SD-27

Page 21 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of detector zones belonging to a panel _____________________________________________________________________

Detector zones

8; F14 WAREHOUSE SD1 Place of install.: esserbus-Module 131


Configuration: Fault latched; Standard; no Master Box
Device Category: Sounder/Flasher (Quantity 8)
Detector 1; F-14 Q.LAB Corridor SND; IQ8/So with IsolatorVolume: 100%; SN:156054877188
Control Zone for Activation: 26no Label Text
Detector 2; F-14 Ware House SND-1; IQ8/So with IsolatorVolume: 100%; SN:156054676606
Control Zone for Activation: 27no Label Text
Detector 3; F-14 Ware House SND-5; IQ8/So with IsolatorVolume: 100%; SN:156054875245
Control Zone for Activation: 28no Label Text
Detector 4; F-14 Ware House SND-6; IQ8/So with IsolatorVolume: 100%; SN:156054876716
Control Zone for Activation: 29no Label Text
Detector 5; F-14 Ware House SND-2; IQ8/So with IsolatorVolume: 100%; SN:156054675180
Control Zone for Activation: 30no Label Text
Detector 6; F-14 ENGG STORE SND; IQ8/So with IsolatorVolume: 100%; SN:156056253577
Control Zone for Activation: 31no Label Text
Detector 7; F-14 Ware House SND-3; IQ8/So with IsolatorVolume: 100%; SN:156054676651
Control Zone for Activation: 32no Label Text
Detector 8; F-14 Ware House SND-4; IQ8/So with IsolatorVolume: 100%; SN:156054676712
Control Zone for Activation: 33no Label Text

9; F14 WAREHOUSE SD2 Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (22 Automatic Detector)
Detector 1; F-14 Ware House SD-6; O with Isolator SN:107110608215
Detector 2; F-14 Ware House SD-7; O with Isolator SN:107106384239
Detector 3; F-14 Ware House SD-8; O with Isolator SN:107110607720
Detector 4; F-14 Ware House SD-9; O with Isolator SN:107106384222
Detector 5; F-14 Ware House SD-10; O with Isolator SN:107110607744
Detector 6; F-14 Ware House SD-11; O with Isolator SN:107110608765
Detector 7; F-14 Ware House SD-12; O with Isolator SN:107106385908
Detector 8; F-14 Ware House SD-13; O with Isolator SN:107110608710
Detector 9; F-14 Ware House SD-14; O with Isolator SN:107110607928
Detector 10; F-14 Ware House SD-15; O with Isolator SN:107110600974
Detector 11; F-14 Ware House SD-16; O with Isolator SN:107110608048
Detector 12; F-14 Ware House SD-17; O with Isolator SN:107110608345
Detector 13; F-14 Ware House SD-18; O with Isolator SN:107110608789
Detector 14; F-14 Ware House SD-19; O with Isolator SN:107110608673
Detector 15; F-14 Ware House SD-20; O with Isolator SN:107110607751
Detector 16; F-14 Ware House SD-21; O with Isolator SN:107110608758
Detector 17; F-14 Ware House SD-22; O with Isolator SN:107110608468
Detector 18; F-14 Ware House SD-23; O with Isolator SN:107110608031
Detector 19; F-14 Ware House SD-24; O with Isolator SN:107110608871
Detector 20; F-14 Ware House SD-25; O with Isolator SN:107110607997
Detector 21; F-14 Ware House SD-26; O with Isolator SN:107106385014
Detector 22; F-14 Ware House SD-27; O with Isolator SN:107110608772

10; F14 WAREHOUSE SD3 Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (24 Automatic Detector)
Detector 9; F-14 Ware House SD-34; O with Isolator SN:107115364574
Detector 10; F-14 Ware House SD-35; O with Isolator SN:107115365113
Detector 11; F-14 Ware House SD-36; O with Isolator SN:107115365069
Detector 12; F-14 Ware House SD-37; O with Isolator SN:107115365076
Detector 13; F-14 Ware House SD-38; O with Isolator SN:107115364567
Detector 14; F-14 Ware House SD-39; O with Isolator SN:107115364208
Detector 15; F-14 Ware House SD-40; O with Isolator SN:107115364703

Page 22 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of detector zones belonging to a panel _____________________________________________________________________

Detector 16; F-14 Ware House SD-41; O with Isolator SN:107115365243


Detector 17; F-14 Ware House SD-42; O with Isolator SN:107115365045
Detector 18; F-14 Ware House SD-43; O with Isolator SN:107115364789
Detector 19; F-14 Ware House SD-44; O with Isolator SN:107115365199
Detector 20; F-14 Ware House SD-45; O with Isolator SN:107115364765
Detector 21; F-14 Ware House SD-46; O with Isolator SN:107115364666
Detector 22; F-14 Ware House SD-47; O with Isolator SN:107115364277
Detector 23; F-14 Ware House SD-48; O with Isolator SN:107115364888
Detector 24; F-14 Ware House SD-49; O with Isolator SN:107115364994
Detector 25; F-14 Ware House SD-50; O with Isolator SN:107115354001
Detector 26; F-14 Ware House SD-51; O with Isolator SN:107115365267
Detector 27; F-14 Ware House SD-52; O with Isolator SN:107115364659
Detector 28; F-14 Ware House SD-1; O with Isolator SN:107110607805
Detector 29; F-14 Ware House SD-2; O with Isolator SN:107110607935
Detector 30; F-14 Ware House SD-3; O with Isolator SN:107110607843
Detector 31; F-14 Ware House SD-4; O with Isolator SN:107110607737
Detector 32; F-14 Ware House SD-5; O with Isolator SN:107110607867

11; F14 WAREHOUSE MCP Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (5 Manual Call Point
(MCP/TAM))
Detector 1; F-14 Ware House MCP-1; MCP with Isolator SN:145112834324
Detector 2; F-14 Q.LAB Corridor MCP; MCP with Isolator SN:145113359406
Detector 3; F-14 Q.LAB Corridor MCP; MCP with Isolator SN:145110775018
Detector 4; F-14 Q.LAB Corridor MCP; MCP with Isolator SN:145112833686
Detector 5; F-14 ENGG STORE MCP; MCP with Isolator SN:145127044800

12; F14 LAB AREA Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (22 Automatic Detector)
Detector 1; F-14 Q.LAB Wet Chemstry3; O with Isolator SN:139107220445
Detector 11; F-14 Q.LAB Corridor SD-4; O with Isolator SN:107110615930
Detector 12; F-14 Q.LAB Instrmt Lb SD1; O with Isolator SN:107115340738
Detector 13; F-14 Q.LAB Instrmt Lb SD2; O with Isolator SN:107115353998
Detector 14; F-14 Q.LAB Instrmt Lb SD3; T RoR with Isolator SN:138116894463
Detector 15; F-14 Q.LAB Retention SD1; O with Isolator SN:107115364901
Detector 16; F-14 Q.LAB Retention SD2; O with Isolator SN:107100076475
Detector 17; F-14 Q.LAB Wet Chem8stry ; O with Isolator SN:107115333105
Detector 18; F-14 Q.LAB Wet Chemstry7 ; O with Isolator SN:107115334034
Detector 19; F-14 Q.LAB Wet Chemstry6 ; O with Isolator SN:107115333419
Detector 20; F-14 Q.LAB Wet Chemstry5 ; O with Isolator SN:107115333259
Detector 22; F-14 Q.LAB Wet Chemstry2 ; O with Isolator SN:107115332948
Detector 23; F-14 Q.LAB Wet Chemstry1 ; O with Isolator SN:107100076727
Detector 24; F-14 Q.LAB Wet Chemistry ; O with Isolator SN:107115364932
Detector 25; F-14 Q.LAB Wet Chemistry ; O with Isolator SN:107115364680
Detector 26; F-14 Q.LAB SSG Pilot Area; O with Isolator SN:107115336953
Detector 27; F-14 Q.LAB Documtion SD1; O with Isolator SN:107115340776
Detector 28; F-14 Q.LAB Documtion SD2; O with Isolator SN:107115332122
Detector 29; F-14 Q.LAB Corridor SD5; O with Isolator SN:107115341247
Detector 30; F-14 Q.LAB Corridor SD6; O with Isolator SN:107115340707
Detector 31; F-14 Q.LAB Meeting Room ; O with Isolator SN:107115337578
Detector 32; F-14 Q.LAB Meeting Room; O with Isolator SN:107115341117

13; F14 LAB AREA Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (12 Automatic Detector)
Detector 1; F-14 Q.LAB Ofc Seting SD1; O with Isolator SN:107115364260

Page 23 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of detector zones belonging to a panel _____________________________________________________________________

Detector 2; F-14 Q.LAB Ofc Seting SD2; O with Isolator SN:107115364109


Detector 3; F-14 Q.LAB Corridor SD-1; O with Isolator SN:107115340844
Detector 4; F-14 Q.LAB Traning Room; O with Isolator SN:107115337189
Detector 5; F-14 Q.LAB DOC Archive; O with Isolator SN:107115340493
Detector 6; F-14 Q.LAB Corridor SD-2; O with Isolator SN:107115340790
Detector 7; F-14 Q.LAB Stability Room; O with Isolator SN:107115364581
Detector 8; F-14 Q.LAB Temp Cont Equi; O with Isolator SN:107115341209
Detector 9; F-14 Q.LAB Packing store; O with Isolator SN:107124191154
Detector 10; F-14 Q.LAB Packing Lab; O with Isolator SN:107115340387
Detector 11; F-14 Q.LAB Corridor SD-3; O with Isolator SN:107115340967
Detector 12; F-14 Q.LAB Temp Cont Room; T RoR with Isolator SN:138116397858

14; F14 ENGINEER STORE Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (7 Automatic Detector)
Detector 1; F-14 ENGG STORE SD 1; O with Isolator SN:139105723801
Detector 2; F-14 ENGG STORE SD 2; O with Isolator SN:139105722088
Detector 3; F-14 ENGG STORE SD 3; O with Isolator SN:139105734951
Detector 4; F-14 ENGG STORE OFC SD; O with Isolator SN:139105724495
Detector 5; F-14 STORE SD; O with Isolator SN:139105723474
Detector 6; F-14 Turpentine SD-1; O with Isolator SN:107110608741
Detector 7; F-14 Turpentine SD-2; O with Isolator SN:107110607713

15; F14 SECURITY DEPT Place of install.: esserbus-Module 131


Configuration: Fault latched; Standard; no Master Box
Device Category: Sounder/Flasher (Quantity 7)
Detector 1; SECURITY RM F 14 SND-1; IQ8/FSo with IsolatorVolume: 100%; SN:156063667138
Control Zone for Activation: 15no Label Text
Detector 2; SECURITY RM OFFICE SND-2; IQ8/FSo with IsolatorVolume: 100%;
SN:156063667206
Control Zone for Activation: 17no Label Text
Detector 3; SECURITY RM H-H-BL SND-3; IQ8/FSo with IsolatorVolume: 100%;
SN:156063666445
Control Zone for Activation: 19no Label Text
Detector 4; SECURITY RM PHARMA SND-4; IQ8/FSo with IsolatorVolume: 100%;
SN:156063667305
Control Zone for Activation: 21no Label Text
Detector 5; F-14 Ware Huse Secrty SND; IQ8/So with IsolatorVolume: 100%; SN:156054676002
Control Zone for Activation: 23no Label Text
Detector 6; F-14 Q.LAB Corridor SND; IQ8/So with IsolatorVolume: 100%; SN:156054876075
Control Zone for Activation: 24no Label Text
Detector 7; F-14 Q.LAB Corridor SND; IQ8/So with IsolatorVolume: 100%; SN:156054876099
Control Zone for Activation: 25no Label Text

20; F14 WAREHOUSE SD4 Place of install.: esserbus-Module 131


Configuration: Fire; Standard; no Master Box
Device Category: Analogue Detector (8 Automatic Detector)
Detector 1; F-14 Ware House SD A; O with Isolator SN:139105724389
Detector 2; F-14 Ware House SD B; O with Isolator SN:139105723436
Detector 3; F-14 Ware House SD-28; O with Isolator SN:107115365236
Detector 4; F-14 Ware House SD-29; O with Isolator SN:107115364253
Detector 5; F-14 Ware House SD-30; O with Isolator SN:107115364079
Detector 6; F-14 Ware House SD-31; O with Isolator SN:107115364642
Detector 7; F-14 Ware House SD-32; O with Isolator SN:107115365120
Detector 8; F-14 Ware House SD-33; O with Isolator SN:107115364222

21; transponder Place of install.: esserbus-Module 131


Configuration: Fault latched; Standard; no Master Box

Page 24 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of detector zones belonging to a panel _____________________________________________________________________

Device Category: Transponder (Quantity 1)


Detector 1; F 14 transponder beam ; Alarm. with Isolator SN:4313667721
G1: Detector Zone 22 F 14 beam detectoer 1
G2: Detector Zone 23 F 14 beam detector 2
G3: Detector Zone 24 F 14 beam detector 2
G4: Detector Zone 25 no Label Text
K1: Control Zone 12; no Label Text
K2: Control Zone 13; no Label Text

22; F 14 beam detectoer 1 Place of install.: esserbus-Module 131 - Alarm. 21/1


Configuration: Fire; Standard; no Master Box
Device Category: Standard Detector(Automatic Detector)
Monitoring: 10k Ohm Quiescent
23; F 14 beam detector 2 Place of install.: esserbus-Module 131 - Alarm. 21/1
Configuration: Fire; Standard; no Master Box
Device Category: Standard Detector(Automatic Detector)
Monitoring: 10k Ohm Quiescent
24; F 14 beam detector 2 Place of install.: esserbus-Module 131 - Alarm. 21/1
Configuration: Fire; Standard; no Master Box
Device Category: Standard Detector(Automatic Detector)
Monitoring: 10k Ohm Quiescent
25; no Label Text Place of install.: esserbus-Module 131 - Alarm. 21/1
Configuration: Fire; Standard; no Master Box
Device Category: Standard Detector(Automatic Detector)
Monitoring: 10k Ohm Quiescent

Page 25 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of control zones belonging to a panel ______________________________________________________________________

Control zones

11; no Label Text


Place of install.: Basic Module
Disabled when: - Inspection active
Configuration: Standard inverse
Type of Contact: NO contact
12; no Label Text
Place of install.: esserbus-Module 131 - Alarm. 21/1
Disabled when: - Inspection active
Configuration: Standard
Type of Contact: NO contact
13; no Label Text
Place of install.: esserbus-Module 131 - Alarm. 21/1
Disabled when: - Inspection active
Configuration: Standard
Type of Contact: NO contact
15; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/1
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
16; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/1
Disabled when: - Inspection active
Configuration: Standard
17; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/2
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
18; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/2
Disabled when: - Inspection active
Configuration: Standard
19; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/3
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
20; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/3
Disabled when: - Inspection active
Configuration: Standard
21; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/4
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
22; no Label Text
Place of install.: esserbus-Module 131 - IQ8/FSo 15/4
Disabled when: - Inspection active
Configuration: Standard
23; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 15/5

Page 26 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of control zones belonging to a panel ______________________________________________________________________

Disabled when: - Inspection active


- Function "Sounder off" activated
Configuration: Alarm Installation
24; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 15/6
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
25; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 15/7
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
26; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/1
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
27; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/2
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
28; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/3
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
29; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/4
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
30; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/5
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
31; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/6
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
32; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/7
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation
33; no Label Text
Place of install.: esserbus-Module 131 - IQ8/So 8/8
Disabled when: - Inspection active
- Function "Sounder off" activated
Configuration: Alarm Installation

Page 27 of 29
Reckitt Benckiser - Khi Panel 2; Reckitt Benckiser -2
Summary of control zones belonging to a panel ______________________________________________________________________

Control zones

111; no Label Text


Place of install.: Basic Module
Disabled when: - Inspection active
Configuration: Standard inverse
Type of Contact: NO contact

Page 28 of 29
Reckitt Benckiser - Khi Panel 1; Reckitt Benckiser -1
Summary of Activations in a Panel ________________________________________________________________________________

Activations

Activation by detector zone (range activation)

Alarm (Fire/TAL)
Zone 1 to Zone 6 Activation: 17; no Label Text
Zone 1 to Zone 6 Activation: 18; no Label Text
Zone 9 to Zone 10 Activation: 15; no Label Text
Zone 9 to Zone 10 Activation: 16; no Label Text
Zone 10/12 to Zone 10/12 Activation: 23; no Label Text
Zone 10/12 to Zone 10/12 Activation: 24; no Label Text
Zone 10/12 to Zone 10/12 Activation: 25; no Label Text
Zone 10/12 to Zone 10/12 Activation: 26; no Label Text
Zone 10/12 to Zone 10/12 Activation: 27; no Label Text
Zone 10/12 to Zone 10/12 Activation: 28; no Label Text
Zone 10/12 to Zone 10/12 Activation: 29; no Label Text
Zone 10/12 to Zone 10/12 Activation: 30; no Label Text
Zone 10/12 to Zone 10/12 Activation: 31; no Label Text
Zone 10/12 to Zone 10/12 Activation: 32; no Label Text
Zone 10/12 to Zone 10/12 Activation: 33; no Label Text
Zone 11 to Zone 14 Activation: 15; no Label Text
Zone 11 to Zone 14 Activation: 16; no Label Text
Zone 16 to Zone 17 Activation: 22; no Label Text
Zone 18 to Zone 19 Activation: 19; no Label Text
Zone 18 to Zone 19 Activation: 20; no Label Text
Zone 20 to Zone 20 Activation: 15; no Label Text
Zone 20 to Zone 20 Activation: 16; no Label Text
Zone 21 to Zone 23 Activation: 15; no Label Text
Zone 21 to Zone 23 Activation: 16; no Label Text
Zone 21 to Zone 23 Activation: 19; no Label Text
Zone 21 to Zone 23 Activation: 20; no Label Text
Zone 24 to Zone 24 Activation: 19; no Label Text
Zone 24 to Zone 24 Activation: 20; no Label Text
Zone 101 to Zone 104 Activation: 21; no Label Text
Zone 106 to Zone 109 Activation: 21; no Label Text

Page 29 of 29