URJA Techniques (India) Pvt. Ltd.

Transformer Manufacturer An ISO 9001:2015, 14001:2015, OHSAS: 18001:2007 Certified Co.


www.urjatransformers.com

UQ / 370 / 20-21 09th June 2021 Quotation


JSPL MOZAMBIQUE MINERAIS LDA.
3605C Chirodzi Coal Mines,
Tete-Songo Highway EN-258, Neutral Earthing Transformer
Tete - Mozambique
Email : saurabh.singh@jindalafrica.com

Kind Attn : Mr. Saurabh Kumar Singh (Asst General Manager) - T- +258 25227138 M- + 258 825631170

Sub : Supply – 33 kV Neutral Earthing Transformer

Dear Sir,

We acknowledged with thanks the receipt of your email enquiry dated 08th June 2021 for the subject transformer.

We deem it to be a distinct pleasure to be the preferred transformer manufacturer for your project and thank you
for considering us.

At the outset, we are pleased to extend our proposal and are detailing below the requirements along with the
rates for your kind consideration.

TRANSFORMERS

CONTENTS

GUARANTEED TECHNICAL
PARTICULARS – I

STANDARD FITTINGS &


ACCESSORIES - II

COMMERCIAL TERMS &


CONDITIONS.- III

URJA – « A Breed Apart »

Office B-17, Shri Ram Ind. Estate, G.D. Ambekar Road, Tel : +91-22-2415 0505
Wadala, Mumbai – 400 031. e-mail : exports@urjatransformers.com,

Works R-653, TTC, M.I.D.C. Thane Belapur Road, Rabale, Tel. : +91-22-20872550/51
Navi Mumbai – 400 701. e-mail : admin@urjatransformers.com,
Urja Techniques (I) Pvt. Ltd., Continued sheet

GUARANTEED TECHNICAL PARTICULARS – SCHEDULE I


Sr. No DESCRIPTION
1) Winding Interstar (zig-zag),copper wound
2) Cooling ONAN
3) Insulation Class A
4) Primary voltage 33000 V
5) Vector group ZNO
6) Phases & frequency 3 phase & 50 Hz
7) Type Conservator
8) Short time current through Neutral 2300 Amp for 10 sec
9) ZPS Impedance 29 Ohms per phase (- 5 % to + 20 %)
10) Ambient Temperature 45C
11) Temp. Rise (above Amb.) Oil / Wdg. 50/55C
12) Installation Outdoor
13) Colour Shade Shade 632 as per IS - 5 / RAL 7024 Synthetic Enamel
14) Service Continues
15) Standards IEC 60076
16) Terminals Air insulated cable end box with disconnecting chamber for
primary & Air insulated cable end box with disconnecting
chamber for Neutral
STANDARD FITTINGS & ACCESSORIES- SCHEDULE - II
Sr. No. DESCRIPTION
1. Inspection openings
2. Filter valve with blanking plate top and bottom
3. Oil Conservator
4. Pressure relief device
5. Tank lifting lugs
6. 4 Uni directional Rollers
7. Earthing Terminal 2 Nos
8. Name & rating plate
9. Drain cum sampling valve
10. Thermometer Pocket
11. First filling of oil as per IEC 60296
12. Dehydrating Breather
13. 4” dial type thermometer without contacts
14. Buchholz relay with alarm and trip contacts and trip contacts
15. Magnetic Oil Level Gauge with Alarm contacts
16. Oil Temperature Indicator with Contacts
17. Marshaling Box

Losses, Weights and Dimensions


No Load Losses (Watts) 1400
Core & Coil (Kg) 1500
Tank & Fittings 550
Oil (Kg / Ltrs) 675 / 800
Total Weight in Kg (Approx.) 2725
Overall Dimensions in mm (Approx.) (L x W x H) 2000 mm x 900 mm x 2000 mm

Urja Techniques (I) Pvt. Ltd. Continuation Sheet

COMMERCIAL TERMS & CONDITIONS FOR SALE SCHEDULE – III


Description Rating Rate / Each ( USD )

Neutral Earthing Transformer 33 KV, 2300 Amp for 10 sec 18,000/-

Term FOB – JNPT, Navi Mumbai


Taxes Nil against export
Seaworthy Packing Inclusive
Storage Should storage of goods be necessary owing to immediate dispatch to destination
being impossible due to lack of instructions from you or transport facilities, the
cost of such storage at ¼ %per week of basic price along with demurrage charges
and incidental charges at actual will be to your account.
Delivery Within 8 weeks from the date of receipt of your technically and commercially
clear order along with advance & drawing approval.
Payment 50% advance of the order value along with order & balance with 100% taxes &
duties against Pro-forma invoice before delivery.
Warrantee We undertake to repair, free of cost, the equipment supplied by us should it
become defective under normal and proper use, due to faulty material or
workmanship within 18 months from the date of dispatch. In the event of
manufacturing defect, “first hand report” is sought from site. Necessary site
visits with requisite material to redress. In case unable to rectify at site, product
is called back to works to redress without transport etc., charges obligations.
Testing & Certificate Routine tests shall be carried out as per IEC Standards and certificate shall be
issued.
Force Majeure Clause Although every effort will be made to meet the delivery we will not bear any
responsibility for delay in delivery due to factors like Strikes, Power Cuts,
Natural calamities and such factors beyond our control.
Validity Our offer is valid up to & including 25.06.2021 from the date and thereafter
subject to our confirmation.
Note 1. Order once placed cannot be cancelled.
2. Purchase Order is placed are subject to our confirmation.

We now look forward to the pleasure of your kind patronage and esteem order and you can be rest assured of our
best services at all times.

For and on behalf of


URJA TECHNIQUES (I) PVT. LTD.,

PRATAP VARAVADEKAR
Vice President – Marketing
(Mob: 98200 81474)

Office B-17, Shri Ram Ind. Estate, G.D. Ambekar Road, Tel : +91-22-2415 0505
Wadala, Mumbai – 400 031. e-mail : exports@urjatransformers.com,

Works R-653, TTC, M.I.D.C. Thane Belapur Road, Rabale, Tel. : +91-22-20872550 / 1
Navi Mumbai – 400 701. e-mail : admin@urjatransformers.com,