Professional Documents
Culture Documents
A Three-Phase Multi-Legged Transformer Model ATP Using Directly-Formed Inverse Inductance Matrix Xusheng Chen, Member, Ieee Department of Electrical Engineering Seattle University
A Three-Phase Multi-Legged Transformer Model ATP Using Directly-Formed Inverse Inductance Matrix Xusheng Chen, Member, Ieee Department of Electrical Engineering Seattle University
A Three-Phase Multi-Legged Transformer Model ATP Using Directly-Formed Inverse Inductance Matrix Xusheng Chen, Member, Ieee Department of Electrical Engineering Seattle University
3, July 1996
Abstract - A new transformer model based on core topology is at each time-step. In this paper we shall derive the r-matrix
developed. The model simulates the transformer as a set of for a three-phase, two-winding, multi-legged transformer
coupled inductances. Winding flux linkages are chosen as state under the more general condition of core and leakage
variables and currents are computed from the flux linkages inductance saturation. Since the r-matrix is directly formed
using the directly-formed inverse inductance matrix, the r- at each time-step, the computation of currents from the flux
matrix. Due to the strong magnetic coupling among the
linkages becomes simply a matrix multiplication. Although it
windings, the inductance matrix of a transformer is ill-
might not be the first three-phase transformer model built
conditioned. Directly forming the r-matrix will not only speed
up the computation but also make it more stable. Transformer around the topology-based r-matrix, it distinguishes itself by
core saturation is represented by its anhysteretic magnetization its simplicity and robustness due to the use of flux linkages as
curve. Eddy current and hysteresis losses of the core, and stray state variables. Since the transformer is defined in its natural
losses of the transformer are accounted for by a resistive load on technology, the cause-effect relationship can be closely
the secondary. Winding capacitances are lumped to the investigated, and user effort is minimized.
terminals, the model is thus accurate up to 5 kHz. A supporting
routine is written to generate k-i curve data for each segment of 11. THEORY
the core and the other input data for EM". The model has
been incorporated into the Alternative Transients Program
(ATP), the BPA EMTP, for evaluation, and has passed the The basic layout of the transformer under study is shown in
benchmark test of the GPU line energization test of 1973. Fig. 1. Fig. 2 shows an equivalent circuit of the transformer
along with a simple system used for simulation tests. The
transformer is three-phase, two-winding, five-legged, and wye
I. INTRODUCTION or ye-grounded connected. Modification of the model to
accommodate three-winding and delta connected
In recent years, a number of detailed three-phase transformers is under development. r is the transformer's
transformer models appropriate for the analysis of
electromagnetic transients and unbalanced operations have
been proposed [l-91.
This paper presents a new three-phase, two winding, multi-
legged transformer model. The model is based on magnetic
circuit analysis of the core and represents the transformer as a
set of coupled inductances. An initial effort for developing a
model along these lines is described in [ 11. In that paper, we
derived the inductance matrix for a three-phase, two-winding,
five-legged transformer with constant leakage inductances. Fig. 1 Five-legged transformer.
Since flux linkages were chosen as state variables, it was
necessary to invert the inductance matrix to find the currents
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1555
can be included in ATP data, if the user knows their values. k 7-R7
In modeling linear transformers, either winding flux ‘6- RlO
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1556
length of the kth leg or twice the full length of the kth yoke match the rms excitation current of the transformer at rated
segment. All separately definable segments of the core are voltage. The saturation curves for all the legs and yokes of
thus individually accounted for in the model. the core are assumed identical. Otherwise, seven saturation
The loops are discernible from the self reluctance R, curves should be used. SPR.FOR also generates the h-i
(i=1,8), and are judiciously chosen so that loop k (k=1,6) has curves for the nonlinear segments of the core: Three for a
only one mmf, fk @=1,6), and loops 4 to 8 have no m " s . five-legged transformer and two for a three-legged
Eqs. (1) to ( 5 ) can be either in physical units or in per unit. transformer. The computer algorithm of SPR.FOR is similar
However, our experience shows that it is easier to derive the to the one described in [I] and to subroutine SXF which is
r-matrix in per unit. Therefore, all equations in this paper described in Section 111.
where units are omitted, per unit should be assumed. Eddy current, hysteresis, and stray losses are dampers to the
Eq. (3) relates the 8 loop fluxes to the 6 externally applied system. Their damping effect is only sigmficant when
mmf's. Our objective is to relate the 6 winding fluxes which currents are small such as in ferroresonance without inrush
are equal to the first 6 loop fluxes, to the 6 applied d s . currents. When currents in the transformer are large such as
This can be done by solving fluxes and from the last two in switching overvoltages and inrush currents, the damping
equations of Eq. (3) and substituting them into the first 6 effect of the winding resistances, IzR, will be much greater.
equations. The resulting 6 by 6 r-matrix is symmetrical with The losses in the transformer excluding I2R are:
elements as follows:
The stray loss is the loss of the tank, end frame, lock plate,
core edge, etc. This loss comprises about 30% of PlOs [12].
According to a recent paper [13], the eddy current loss of
modem grain-oriented silicon steel is about three times its
hysteresis loss, both being very small. Core loss is very
difficult to model. Because the ATP Type-96 pseudo-
nonlinear hysteretic reactor component sometimes produces
results that are at odds with some experimental observations
[14], we choose to place the three losses into one core loss
term accounted for by a resistive load on the transformer
secondary. As we have discussed in [ 11, transformer core loss
is voltage-dependent. For two reasons, though, we don't
The derivation of Eq. (6) is general for both apparent and include t h ~ svoltage dependency in the new transformer
incremental inverse inductance matrices, r and r,. Apparent model even though it is a part of our own computer program.
First, we omit it to improve the speed of computation. The
permeability = Bk / Hk, in Eq. (5) results in r, and
new model represents the transformer as R and coupled-L
incremental permeability, = dBk / dT&, results in r,.
circuits. Any change in the values of elements necessitates
We note that while the L-matrix for a three-phase core-type
then retriangularization of the system conductance matrix.
transformer is always a full matrix, the r-matrix is sparse.
This consumes considerable computer time. Secondly, and
Of the 21 upper triangular elements, 9 are zero, 3 are
more basically, core loss curves above rated transformer
constant, and only 9 need to be updated when core saturation voltage are usually not available.
changes. The directly-formed r-matrix makes the solution of Assuming a sinusoidal steady state in the core, the core loss
the transformer differential equations (which are very stif€ resistances for a three-legged transformer are:
and marginally stable under some system configurations)
more efficient and stable than that of using the numerically-
inverted L-matrix.
It is well-known that core saturation plays a dominant role
in determining the transient behavior of a transformer. In
this research, core saturation is represented by an equilibrium where h i s rms flux in the kth section of the core.
h-i or B-H curve known as the anhysteretic magnetization or The core loss for a five-legged transformer is represented by
saturation curve. The virgin B-H curve should not be used three identical resistances.
[ 1,101. The single-valued saturation curve @referably the h-i One concern with this core loss representation is its ability
curve) is approximated by a five-slope piecewise linear curve. to predict residual fluxes when the transformer is switched
SPR.FOR, a supporting routine based on Eqs. (1) and (2) off. The answer is yes, especially for modern grain-oriented
and the Brent's method [ 111, will scale the saturation curve to steel core transformers. Since the new model computes fluxes
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1557
in all segments of the core at each time-step, the flux IV. VALIDATION OF THE MODEL
distribution at the instant of switching or, more accurately,
after the arcs are extinguished, will be the residual fluxes A series of simulations has been carried out in order to
of the core. Capacitive effects due to load, transmission lines verify the validity of SXF in ATP. The 100 kVA, 50 Hz,
left on the transformer, and winding capacitances of the three-legged, Y N transformer used by Dolinar [3] was used
transformer itself can reduce residual fluxes to near zero [ 151. with the new model. The characteristics of the transformer
It is important to configure a realistic system for the are summarized below:
transformer whose residual fluxes are to be determined.
Rated apparent power 100 kVA
111. COMPUTER PROGRAM Rated voltages 1510.4 kV
Rated currents 3.851144.3 A
Computer simulation models suitable for studjing steady- Rated excitation current 0.0060 p.u.
state and transient behaviors of multi-phase, multi-legged Rated core loss 0.0015 p.u.
transformers have been under development for several years. Winding resistances 25.910.016 n
In its present form (named SEATI’LE XFORMEH. or SXF) it Short circuit reactance 0.0388 p.u.
models three-phase, two-winding, multi-legged, wye or wye- Capacitances to ground 0.0009 10.5 cl.F
grounded transformers. SXF has been incorporated into the
Altemative Transients Program (ATP), the BPA Eh4TP [ 161, Core dimensions
and is presently being assessed by both academic and Length: Wdg L e H . 4 0 Yoke=0.48 Outer Leg-1000 m
industrial users. Area: Wdg Leg-1.14 Yoke=1.14 Outer Leg-5 lo-’ m2
Because ATP uses individual discretization, in interface
had to be written between subroutine SXF and the host Saturation curve data
program. SXF receives winding voltages from ATP, computes B 1.0879 1.2552 1.3389 1.4143 2.9260 p.u.
winding flux linkages using Eq.(lO), updates thc: r and r, H 1.6365 2.6062 4.2427 8.4853 7204.0 1O”p.u.
matrices, if necessary, computes the winding currents using
Eq.(2), and determines the winding current hiistory terms A transformer data file was prepared for both ATP and
using Eq. (11) SPR.FOR from the above information. SPR.FOR generates a
fitting parameter FIEXP (=312.47) which scales the
A, (t) = X (t - At) + [V(t) + V(t - At)] 1 2 (10) saturation curve of the transformer to match the specified rms
excitation current of the transformer. Transformer winding
I = i (t - At) + (At/2) -
v (t At) (11) and core-loss resistances are treated as ATP data, and the
unsaturated apparent inductance matrix computed by
In return SXF passes back an updated r,-matriu, modified SPR.FOR represents the transformer in ATP phasor solution
winding currents, io,and its history term, I. The reason for which generates the initial conditions for the transient
modifjmg the winding currents and their history tmns is that simulation of the system.
the incremental approach computationally loses ,.Information Fig. 4 shows the simulated primary winding excitation
of the dc component of the winding currents. currents iA(=il+iC1,see Fig. 2), iB,and ic ,when rated voltage
The steps for updating the r and r, matrices in the is applied. The rms current is 0.023A(three-phase average)
program code of SXF are outlined below: The fluxes in the and the core loss is 150 W. These should be accurate,
three winding legs are computed by Eq.(lO). Eq.(12) is used because the supporting routine SPR.FOR matches the
to find the node “f‘s, fb,Eq.(13) is then used to determine excitation current and the core loss. It should be pointed out
the fluxes in the two yokes and the two outer legs. Flux that only the three-phase power is an accurate measure and
densities are then found and apparent and incremental not the individual phase power for unloaded transformers.
permeabilities determined from the saturation cwve. The r Fig. 5 shows the measured excitation current ipl (ip2and ip3
and r, matrices are updated by Eqs. (4) to (7). are not available). It is seen that the simulated and measured
current waveforms, iA and i,], are in good agreement. It is
fin= il + i4 + R I AI noted that the higher harmonics in iA (but not in iB) are not
pronounced as compared with that of the measured current
fk=i2+iS+R2h2 (12)
ipl. The lumping of the distributed winding capacitances and
f3, = i3 + I6 + R3h3
the simple constant resistance representation of the core loss
might be the cause of the discrepancy.
Figs. 6 and 7 show the simulated and measured inrush
currents of the transformer. The energizing instant is when
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1558
Os* :
-0.1
0.04
-200; I
P 0.02 0.06 0.08 0.01 0.02 0.03 0.04 0.05
t, seconds t seconds
Fig. 4 Simulated phase A excitation current. Fig. 8a Simulated primary winding short-circuit currents.
01
‘PIA1
0.05
-001
f seconds
Fig. 5 Measured phase A excitation current. Fig. 8b Simulated primary winding fluxlinkages
!
879.80 -584.68 -292.14
-584.68 1172.06 -584.68 H (15)
-292.14 -584.68 879.80
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1559
input data of the autotransformer is summarized below: Fig. 10 Simulated HV voltages (three-phasetransfomer model).
Rated apparent power 500 MVA forms of VA and vA’ are very similar though not identical.
Rated voltages 1151345 kV We have also modeled the transformer as a three-phase
Rated currents 25101836.7 A five-legged autotransformer. The only input data changed is
Rated excitation current 0.006 p.u. the core dimensions. This shows the flexibility of the model.
Rated core loss 0.003 p.u. The result is shown in Fig. 10. It is not surprising that the
Short circuit reactance 0.1232 p.u. voltage waveforms are similar to that of the single-phase
Capacitances to ground 0.004 10.064 pF model, for it is a three-phase energization.
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1560
the manufacturer or from standard tests. If the specific Oregon. The author is also grateful to Professor Dolinar of
dimensions of the core are not known,generic values can be University of Maribor, Maribor, Slovenia, for his permission
used without signijicantly affecting the results. The model is to use the figures from his paper, and helpful discussions.
thus useful to the practicing engineers. The author thanks Dr. Paul Neudorfer and Liman Zhuang of
3. Because of the physical asymmetry of a three-phase Electrical Engineering Department for their assistance in the
core-type transformer, the L-matrix calculated by ATP preparation of the final report for the DOE contract.
supporting routine BCTRAN is not suited for transformer no
load analyses and should be replaced by SPR.FOR and its VII. REFERENCES
extensions.
4. All topology-based transformer models need the 1.-i X.S. Chen and P. Neudorfkr, " Digital Model for Transient Studies of a
Three-phase Five-Legged Transformer, " IEE ProceediigsC, Vol. 139, No.
curves for each segment of the core. Unfortunately, the data 4, July, 1992, pp. 351-358.
is not available and there exists no reliable methodology of X. S . Chen, P. Neudorfer, and Liman Zhuang, The Development o f a
obtaining them. SPR.FOR works around the difficulty in Three-phase Mulh-Legged TransformerModel for Use with EMTP, Final
Report and Amendment to the Bonneville Power Administration on DOE
obtaining core h-i curves through measurement by using contract No. DE-AC79-92BP26702,1993.
instead h-i or B-H curve and transformer relative core D. Dolinar, J. Pihler, B. Grcar, " Dynamic Model of A Three-phase Power
dimensions. Although a better approach needs to be devised Transformer, " IEEE Trans. on Power Delivery, Vo1.8, No.4, October
1993, pp. 1811-1819.
for the future, this seems at present to be a suitable and Mehdi Vakilian, R. C. Degeneff, " Computing the Internal transient Voltage
practical method. In fact, a method (computer program) of Response of a Transformer with a Nonlinear Core Using Gear's Method,
using three-phase energization to obtain transformer model Part I Theory," IEEE, 95 WM 099-2-PWRD, 1995.
H. M O M , "Multi-Winding Multi-Phase Transformer Model with
parameters is under development. The theory has been Saturable Core, " IEEE Trans. on Power Delivery, V016, No.1, January
worked out; it remains to be implemented. The sparse r- 1 9 9 1 , ~166-173,
. 1991.
matrix plays an important role in this endeavor. C.M. Arturi, "Transient Simulation and Analysis of a Three-phase Step Up
Transformer Following an Out-of-Phase Synchronization," IEEE Trans.
5 . Winding-to-ground capacitances are substantial for on Power Delivery, Vo1.6, No 1, January 1991, pp. 196-207.
morden low-loss transformers. They must be included in the A Narang and R.H. Brierley, "Topology b d Magnetic Model for Steady-
transformer model. State and Transient Studies for Three-phase Core-type Transformers," IEEE
Trans. on Power Systems, Vol. 9, No. 3, August 1994, pp. 1337-1349.
6. The described methodology of deriving the r-matrix has M. D. Hatziargyiou, J. M. Prousalidis, and B. C. Papadias, " A Generalized
been used to derive the nodal inverse inductance matrix of a Transformer Model Based on the Analysis of Its Magnetic Core Circuit, "
three-phase/six-phase conversion transformer. It is our IEE Pro~eeding~S-C, Vol. 140, NO.4, July 1993, pp. 269-277.
F. de Leon and A Semlyen, "Complete Transformer Model for
opinion that the theoretical value of this paper is at least the Electromagnetic Transients," IEEE Trans. on Power Delivery, Vol. 9, No. 1,
same as its practical value. Jan. 1994, pp 231-239
7. The constant or variable resistance representation of the [10]D.C. Jiles- A d D.L. Atherton, "Theory of Ferromagnetic Hysteresis,"
Journal of Magnetism and Magnetic Materials, Vol. 61, 1986, pp.48-60.
core loss is only a reasonable approximation to the [ l l ] W. H. Pres, B. P. Flannery, S . A Teukolsky, and W. T. Vetterling,
complicated mechanism of the core loss. While it works Numerical Recipes : The Art of Scientijc Computingflecond Edition) ,
excellently for low-frequency transients such as transformer Cambridge University Press, 1992.
inrush currents, short circuits, and unbalanced operations, it [12]D. Pavlik, D. C. Johnson and R. S . e g i s , "Calculation and the Reduction
of Stray and Eddy Losses in Core-Form Transformers Using a Highly
does not work well for high-frequency transients such as Accurate Finite Element Modeling Technique," IEEE Trans. on Power
repetitive breaker re-ignition and lightening overvoltages. Delivery, Vol. 8, No. 1, Jan. 1993, pp 239-245.
The work presented here is really the first step. Research is [13]k J. Moses, "Electrical Steels: Past, Present and Future Developments,"
IEE proCeeding~-A,NO.5, pp 233-245, September 1990.
ongoing to integrate the work of Degeneff and Vakilian, Zhu [14]k Narang,, "Detailed Transformer Model for EMTP, Part 11: Magnetic
et al, and Leon and Semlyen into our mode1[4,9,17]. In the Model ," EMTP Review, Vo1.4, No. 2, EMTP DCGEPFU, April 1990.
high frequency transformer model, windings are modeled by [15]H. W. Dommel, Electromagnetic Transients Program Reference Manual
(EMTP Theory Book), BPA Portland, Oregon, USA, August 1986.
RLC networks, eddy current, hysteresis, and stray losses are [16]W. S . Meyer and T. H. Liu, Alternative Transients Program(2TP) Rule
modeled separately, and the frequency dependence of the Book, BPA Podland, Oregon, USA, 1992.
core loss and the winding resistances are included. The [17] J. G. Zhu, S . Y. R. Hui, and V. S . Ramsden, " Discrete modelling of
methodology presented in this paper can accommodate the magnetic Cora including hysteresis eddy current and anomalous losses, "
IEE Proceeding-A, Vol. 140, NO. 4, July, 1993, pp. 317-322.
above extensions with no difficulty,
Xusheng Chen was born in Shanghai, China. He received his MSEE f?om
VI. ACKNOWLEDGMENTS Shanghai Jiao Tong university and MSEE from Louisiana State University, both
in the area of power systems in 1981 and 1984, respectively. He received a
Ph.D. in electrical and computer engineering fiom Washington State University
This work was performed under United States Department in 1987. Dr.Chen has extensive experience in power system design, construction
of Energy contract # DE-AC79-92BP26702. The author is and operation. He is currently an associate professor at Seattle University,
Seattle, W k His areas of interest are power system transients and relay
grateful for insights offered by Drs. W. Scott Meyer and Tsu- protection, electrical machine modeling, six-phase power transmission, and wind
huei Liu of the Bonneville Power Administration, Portland, generation. Dr.Chen is a member of IEEE and Tau Beta Pi.
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1561
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.
1562
need for an interface between the electric and magnetic yet been found to include the capacitances from high-
circuits of the hybrid model is removed. I would like to voltage to low-voltage windings in SPR.FOR.
note that SABER, a commercially available software, can
solved the equations of the hybrid model directly. 8. My motivation for developing topology-based models
for transformers is an interest in studying ferroresonence
4. The reluctances of the air paths around the legs and phenomenon of five-legged distribution transformers.
yokes are not shown in Fig. 3 for clarity. They are in Since Prof. Stuehm and my contracts for BPA were
parallel with the seven nonlinear reluctances representing performed concurrently, I naturally turned to Prof.
the core. Their values are scaled by supporting routine Stuehm’s report. However, the simulation results for both
SPR.FOR to match the air-core inductance of the three- and five-legged transformers, using my model and
transformer. Details are shown in [2] of the paper. Prof. Stuehm’s dualityderived models, and using the data
reported in [l] of the discusser, did not match the
5. Prof. Mork correctly pointed out that core loss measurements. I concluded that h-i curves for each
representation of the new model for a five-legged segment of the core obtained by single-phase tests were not
transformer is not completely topology-based. To use three accurate. I then turned to Prof. Dolinar for help and used
linear or nonlinear resistors to represent the core loss for a his data of a three-legged transformer to verify the model.
five-legged transformer is based on my belief that modeling The GPU Stolle Road transformer had a tertiary. Since
is an extraction of essence rather than the construction of a only the two-winding transformer model had been
detailed replica of a phenomenon. Transformer core loss incorporated into ATP, both SXF, the new model, and the
mcdeling is still 2n art ai this stage of development, and a existing ATP model TRANSFORMER, modeled the
five-:egged transfoner is quite symmetrical, therefore, the autotransformer with no tertiary. SXF also modeled the
:hree-resistor core-loss representation is a good Stolle Road transformer as a five-legged transformer. The
approximation. My experience in modeling transformers dimensions of the transformer are shown in the second row
shows that the distribution of flux flows in the core of the data table under heading: Core dimension (sinde-
segments is dominated by the saturation curves, and not by phase/five-lenned).
the core losses. If further research shows that topology- No ATP rule book section for the model is written, since
based core loss representation for a five-legged transformer I was not asked to do it. However, all information is
is important, one of the following methods can be used to documented in [2], and there is a tutorial in supporting
realize it: (a) Add one fictitious winding (shorted by a routine (C“) SPR.FOR. The demonstration card of the
linear or nonlinear resistor representing the core-loss of the new model in ATP is DC-31, the SEATTLE XFORMER.
segment) to each of the yokes and the outer legs. The The three-winding version of the model has not yet been
inverse inductance matrix will become 10 by 10 for a two- incorporated into ATP. I was stalled for two years by a
winding transformer. By slightly modlfylng Fig. 3, the difficulty in getting the wyedelta transformer model
inverse inductance matrix can be detennined by inspection! working. I am now going to incorporate the three-winding
(b) Replace the subroutine for 1-i curves in SPR.FOR and and possibly ten-winding (for high frequency applications)
SXF.FOR with an improved version of ATP Typed-96 version of the model into ATP.
pseudo-nonlinear hysteretic reactor component which can
account for both saturation and core loss of the segment. 9. “Generic values” for transformer core dimensions can
be obtained from [3,6,8] of this paper and [A] shown below.
6 . Normal B-H curves are first adjusted by hand to make Using three-phase energization to obtain the seven
the slope of the curve non-increasing with increasing B. nonlinear h-i curves for a five-legged transformer is my
SPR.FOR is then used to scale the B-H curve to match the dream. The challenge is in predicting the residual fluxes in
rated average nns excitation current and the aircore the core. I shall report the results as soon as the theory is
inductance of the transformer (2 to 3 times the short-circuit verified by the experiments.
inductance of the transformer). Details are shown in [2].
10. Correction: The residual fluxes for Fig. 8 should be
7. The reported formulation permits capacitive effects to 0.0,0.9798, -0.9798,0.0,0.9798,and-0.9798.
be introduced in the same manner as existing transformer
models in ATP, not offering a better approach. However, in REERENCES
using SPR.FOR to determine the model parameters, only
capacitances to ground are included. While the [A] J. R. Stewart, et all, “Transformer Winding Selection
capacitances between adjacent high-voltage windings can be Associated with Reconfiguration of Existing Double Circuit
easily included by either modlfying the code of SPR.FOR, Line to Six-Phase Operation,” IEEE Trans. on Power
or by lumping them to the winding-to-ground capacitances Delivery, vo1.7, No. 2, April 1992, pp. 979-985.
through a delta-wye transformation, no simple method has Manuscript received October 23, 1995.
Authorized licensed use limited to: ABB - Poland. Downloaded on June 09,2020 at 11:24:03 UTC from IEEE Xplore. Restrictions apply.