Professional Documents
Culture Documents
Modeling of UHV Power Transformer and Analysis of Electromagnetic Transient
Modeling of UHV Power Transformer and Analysis of Electromagnetic Transient
Electromagnetic Transient
Linjun Zeng, Xiangning Lin, IEEE Senior Member, Jingguang Huang, Zhiqian Bo, IEEE Senior Member
Authorized licensed use limited to: ABB - Poland. Downloaded on May 27,2020 at 09:07:03 UTC from IEEE Xplore. Restrictions apply.
gious weight of UHV transformers as the single-phase capabil- Similar to equation derivation of ordinary three winding
ity of UHV transformer is up to 1000 MVA. In view of the transformer, the following equation can be deduced when the
convenience of transportation, adopting single-phase configu- exciting current is ignored, as given by:
ration becomes necessary. The UHV transformer produced in
⎪U C − U Q = I C Z C + I Q Z Q
⎧ & ' & & ' ' &
China is exactly single-phase autotransformer [3]. The
three-phase configuration is implemented with the single-phase
⎨ ' (1)
⎩U C − U B = IC Z C + I B Z B
& &' & ' ' &' '
⎪
transformer bank.
'
Autotransformer has the tertiary winding, namely Where, Z C is the leakage impedance converted from the
low-voltage winding. The tertiary winding is unloaded, instead,
its functionality is to circulate third harmonic. Three phases of series winding; Z Q is the leakage impedance of the common
the tertiary winding are connected by delta-type and earthed '
winding; Z B is the leakage impedance converted from the
through a low-voltage reactor.
To satisfy the demand of isolation, the off-line vol- low-voltage winding.
tage-regulating from the neutral terminal is adopted and the According to (1), its Y-type equivalent circuit can be de-
voltage regulator and compensation transformer separately are duced, as seen in Fig.3:
set by the UHV transformer. The principle can be illustrated by C
Fig.1.
ZC'
ZQ Z B'
Q B
Fig.3 Three ports Y-type equivalent circuit
Authorized licensed use limited to: ABB - Poland. Downloaded on May 27,2020 at 09:07:03 UTC from IEEE Xplore. Restrictions apply.
taken into account in the UMEC model. The piecewise linear citance C0=0.008955μF/km. Nanyang–Jingmen: length=
technique is used to control the model equivalent branch con- 291km. Positive sequence resistance in per km R1
,
=0.00801Ω/km positive sequence reactance in per km X1=
ductance. The non-linearity of the core is input directly into the
0.2631Ω/km
model as a piece-wise linear U-I curve, which makes full use of ,
positive sequence capacitance in per km
C1=0.013830μF/km. Zero sequence resistance R0=0.1563
the interpolation algorithm for the calculation of exact instants
in changing of state range. ,
Ω/km zero sequence reactance X0=0.8306Ω/km zero sequence ,
capacitance C0 = 0.009296μF/km .
Internal faults of transformer include inter-turn short-circuit
fault, inter-turn to ground fault, and phase to phase short-circuit
The UHV autotransformer parameters are as follows: Rated
fault and phase to ground fault. At present, diversified phase to
capabilities of the high-voltage side, the medium-voltage side
phase fault or phase to ground fault are available by means ofand low-voltage side are respectively 1000 MVA, 1000MVA
FAULTS module provided by EMTDC. Therefore, the model and 334MVA. Voltage ratings (RMS)of the high-voltage side,
of internal winding fault is the main concern of this paper. the medium-voltage side and the low-voltage side are respec-
When an inter-turn fault occurs on double-winding transfor-tively 1050 kV, 525kV and 110kV; short-circuit impedances
mer, the fault turns of the faulty winding can be seen as a ter-
(based on rated capabilities of high voltage side): 18% in
tiary winding. It can be regarded as the fault of the tertiaryHigh-medium side, 62% in High-low side, and 40% in me-
winding of a three-winding transformer[5].Based on this con- dium-low side. No-load loss is 0.07%; magnetizing loss is
cept, faulty turns of three winding transformer can be simulated
155kW.
by a fourth winding, see Fig.5. Rated capability of high voltage reactors: 960MVA in Jin-
dongnan side of Jindongnan–Nanyang transmission line, while
720MVA in Nanyang side; 720MVA in Nanyang side of Na-
nyang–Jingmen transmission line, and 600MVA in Jingmen
side.
In view of the influences which result from the energization
transient of the transmission lines and high voltage reactors, the
energization position is at the high voltage side of UHV trans-
Fig.5 internal faults model of transformer former at Jingmen side.
In Fig.5, 2# winding denotes the fault turns, and the fault The system model is shown in Fig.6.
types can be controlled by the breakers. Leakage reactance X2
of 2# winding and leakage reactance X3 of 3# winding can be
calculated, as given by:
⎪X2 + X3 = Xc
⎧
⎨ (2)
⎩ X 2 / X 3 = ( N 2 / N3 )
2
⎪
In (2), Xc is known as the leakage reactance of series
winding. N2, N3 are respectively the turn quantities of 2#
winding and 3# winding. Practically, N2/N3 nearly is equal to
the ratio of 2# winding's rated voltage to 3# winding's. Fig6. Model system
Authorized licensed use limited to: ABB - Poland. Downloaded on May 27,2020 at 09:07:03 UTC from IEEE Xplore. Restrictions apply.
According to Tab.I, when the initial angle of phase A is
30o, the harmonic ratio of one phase will be under 15%, even if
there is no remnant flux. When the remnant flux is taken into
account, the harmonic ratio of phase C will fall below 1.9%, as
shown in fifths row of Tab.I. This indicates that it is unrealistic
to adjust harmonic restraint ratio only to avoid the
mal-operation of differential protection. Only by virtue of
adopting such a blocking strategy that the protection will be
blocked as the second harmonic ratio of any one phase exceeds
the threshold, and regulating harmonic restraint ratio to the
value lower than 15%, the scenario of above mal-operation can
be avioded. Furthermore, when the remnant flux densities of
three phase are 0.9Bm, 0 and -0.9Bm and the initial angle of
phase A is 30o, the 2nd harmonic ratios of three phase
differential currents are all under 10%. In this case, even the
above strict countermeasure cannot allow the protection to
survive.
It is impossible to simulate all the conditions involving the
Fig.7 Magnetic inrush currents in the condition of typical energization, Initial
angle of phase A is 0o; remnant flux densities of the three phase are all 0 diverse initial angles, remnant flux densities and different op-
eration states of systems. However, the simulation results pre-
The UHV transformer adopts Y-d-11 type. Therefore, our sented in this paper at least suggest that the 2nd harmonic cha-
concern is the differential current with regard to the transformer racteristic of the inrush of UHV transformer is weaker than that
differential protection. Differential current is the summation of in EHV and lower voltage level systems. This scenario should
three-side influx currents, which should be equipped with phase be paid attention to when the differential protection of UHV
and magnitude compensation. Namely, if the influx currents of transformer is put into service.
the high, medium, low voltage sides of phase A are I&ah 、I 、 &
am
Besides, the high order harmonic, especially odd harmonic
of the inrushes are more abundant than ordinary transformer. It
I&al , and the influx currents of the high, medium, low voltage possibly has some impact on the methods identifying inrush by
means of waveform characteristic.
side of phase B are I&bh , I&bm , I&bl , in view of the phase com-
pensation and magnitude compensation, the differential current C. Simulation and analysis of internal faults
of phase A is Inter-turn short-circuit fault, turn-to-ground fault simulations
525 of different faulty turns ratios have been carried out and shown
110 in Fig.6. All the faults occurred in phase A exemplarily.
( )
I&ah − I&bh +
1050
3 I& − I& +
am ( bm )
1050
I&al . Moreover, several phase to ground faults were simulated by
3 3 means of FAULTS module provided by EMTDC, including
Because the transformer is energized at the high-voltage side, phase A to ground, phase A to phase B short-circuit fault and
there are no currents in other two sides, so the differential cur- phase A-phase B short-circuit-to-ground fault.
( )
Several current waveforms of phase A in different fault
rent of phase A is I&ah − I&bh exactly. Tab.I provides the har- conditions are shown in Fig.8.
monic ratios of the three phase differential currents in the con-
dition of various energizations.
Tab.I Harmonic analysis of inrush currents
Remnant flux Initial angle 2nd harmonic ratio (%)
density of phase A Phase Phase Phase
( o) A B C
Phase A:0Bm 0 30.4 40.4 15.1 (a)Inter-turn short-circuit fault
Phase B:0Bm 30 31.8 22.6 14.8
Phase C:0Bm 60 37.0 23.7 34.3
Phase A:0.7Bm 0 16.0 18.9 10.1
Phase B:-0.5Bm 30 17.0 15.4 1.9
Phase C:-0.5Bm (b)turn to ground fault
60 30.3 15.0 3.7
Phase A:0.9Bm 0 12.8 17.7 4.0
Phase B:0Bm 30 9.8 6.9 6.1
Phase C:-0.9Bm
60 17.0 17.0 7.8
(c)phase A to Phase B short-circuit fault
Authorized licensed use limited to: ABB - Poland. Downloaded on May 27,2020 at 09:07:03 UTC from IEEE Xplore. Restrictions apply.
Fig.8 Currents for internal faults [4]T. Yang, C. Shi, X. Tan, Autotransformer and its applications (In Chinese).
According to waveforms, no mater inter-turn short-circuit or Beijing, China: China Electric Power Press, pp.28-30.
[5]W. Wang and B. Hou, Theoretical Basis of the Protection Principle of the
turn to ground fault occurs, the smaller the short-circuited turns, Utility-Type Unit (In Chinese). Beijing, China: China Electric Power Press,
the lower the primary current. When a terminal fault occurs, the pp.63-64.
fault current is big and abnormal. [6]X. Wang and Z. Wang, "Study of simulation of transformer with internal
Due to the distributed capacitive effect of UHV transmission faults", Power System Technology, vol. 28, no. 12, pp.51, 2004. (In Chinese)
[7]Y. Huang and Q. LI, et al, "Simulation for magnetic inrush and fault current
line and the particularity of UHV transformer itself, there is of three-phase transformer based on EMTDC", RELAY, vol. 35, no. 1, pp.
abundant harmonics within the fault currents. However, for 26-29, 2007. (In Chinese)
most inter-turn faults, the ratio of the 2nd harmonic of differen- [8]B. He and X. Xu, "Protection based on wave comparison", Proceedings of
tial currents of diversified faults is under 15%. Therefore, it the CSEE, vol. 18, no.6, pp. 395-398, 1998. (In Chinese)
[9]S. Jiao and W. Liu, "A novel scheme to discriminate inrush current and fault
would not influence the rapidity of the protection operation in a current based on integrating the waveform", Proceedings of the CSEE, vol. 19,
mass of fault conditions. no.8, pp. 35-38, 1999. (In Chinese)
However, the exception still exists. For instance, when a 2% [10]X. Lin, P. Liu, C. Yang, "Studys for identification of the inrush based on
improved correlation algorithm ", Proceedings of the CSEE,vol. 21, no. 5, pp.
inter-turn fault occurs, the 2nd harmonic of the faulty phase is 56-60, 2001. (In Chinese)
nd
up to 22.6%, which exceeds the conventional 2 harmonic re- [11]D. Chen , X. Yin, et al, "Virtual third harmonic restrained transformer
straint ratio setting, leading to the time delay of the protection differential protection principle and practice", Proceedings of the CSEE, vol.
operation. 21, no. 8, pp. 19-23, 2001.(In Chinese)
nd [12]J. He and J. Li, B. Yao, et al, "A new approach of transformer inrush de-
According to the simulation result, 2 harmonic blocking tected based on the sine degree principle of current waveforms", Proceedings
scheme can distinguish between inrush and fault current on the of the CSEE, vol. 24, no. 4, pp. 84-59, 2007.(In Chinese)
whole. The differential protection with 2nd harmonic blocking
can do well when applied in UHV transformer protection if the
restraint ratio is chosen reasonably. However, the settings and BIOGRAPHIES
Linjun Zeng received Bachelor degree from China Three Gorges University
the restraint mode should be chosen carefully. (CTGU) in 2006. He is presently a master candidate at the department of Elec-
Besides, a great deal of beneficial works on the aspect of trical Engineering in CTGU. His research interests are power system protection
identifying inrush current were presented[8-12].we can assess and control.
the adaptability of these methods to UHV transformer based on
the energization and internal fault model of UHV transformer Xiangning Lin received a Master and a Ph.D degree from the Huazhong Uni-
proposed in this paper. Accordingly, the operation performance versity of Science & Technology (HUST) respectively in the Electrical Engi-
neering. He is currently a professor titled of "Chutian Scholar" in Three Gorges
of the differential protection of UHV transformer can be im- University, Yichang, Hubei Province, China. His research interests are modern
proved further. signal processing and its applications in the power systems, power system
protective relaying and control.
IV. CONCLUSION
Jingguang Huang is presently an associate professor at the department of
Based on the elementary transformer model provided by Electrical Engineering in CTGU. His research interest is modern signal
EMTDC, the UHV transformer and its internal fault model processing and its applications in the power systems.
possessing the characteristic of autotransformer are built in this Zhiqian Q. Bo received the B.Sc. degree from Northeastern University, She-
paper. We carry out the corresponding electromagnetic tran- nyang, China, in 1982 and the Ph.D. degree from The Queen’s University of
sient simulations in UHV environment, and offer the reasona- Belfast, Belfast, U.K., in 1988.
From 1989 to 1997, he was with the Power Systems Group, University of Bath,
ble precondition for investigating the protection operation of
Bath, U.K. Currently, he is with AREVA T&D—Automation and Information
the UHV transformer, especially for proving its applicability to Systems, Stafford, U.K., responsible for new technology developments. His
the UHV test and demonstration project in CHINA. The em- main research interests are power system protection and control.
phasis is to evaluate the operation reliability of the differential
protection combined with 2nd harmonic blocking. It is shown
with the simulation results that the 2nd harmonic characteristic
of the inrush in UHV transformer is weaker than EHV and
lower voltage level systems. The 2nd harmonic ratios of three
phase differential currents may be all under 10% in certain
conditions. In the fault conditions, all the 2nd harmonic ratios of
differential currents are under 10% except the light inter-turn
fault. Making a comprehensive view of simulations of inrushes
and fault currents, the differential protection with 2nd harmonic
blocking scheme still has redundancy when applied in UHV
transformer protection.
REFERENCES
[1]Z. Zhao and Z. Feng, "Digital real time simulation model and digital integral
,
of autotransformer" , Journal of TongJi University vol. 29 ,no.4,pp.416- 420,
2001. (In Chinese)
[2]L. Zhao and C. Chen, "Study of model of three phase autotransformer in
electric system transient simulation", Proceedings of the EPSA, vol. 16, no.1,
pp. 83, 2004. (In Chinese)
[3]S. Sun and M. Fang, et al, "Development and design of 1000kV autotrans-
former", Electrical Equipment, vol. 8, no. 4, pp. 6-10, 2007. (In Chinese)
Authorized licensed use limited to: ABB - Poland. Downloaded on May 27,2020 at 09:07:03 UTC from IEEE Xplore. Restrictions apply.