Analog Input/output Modules - SM 331 Analog Input Module
Analog Input/output Modules - SM 331 Analog Input Module
Overview
• Analog inputs
• For connection of voltage and current sensors, thermocouples, resistors and resistance thermometers
Area of application
The analog input modules convert analog signals from the process into digital signals for processing within the PLC.
Voltage and current sensors, thermocouples, resistors and resistance thermometers can be connected as sensors.
Functions
The modules feature the following:
• Resolution from 9 to 15 bits + sign (for different conversion times), configurable
• Choice of measurement ranges;
the basic current/voltage range settings are adjusted mechanically via measurement range modules. Fine adjustments
are made with the STEP® 7 Hardware Configuration tool on a PG
• Interrupt capability;
the modules transmit diagnostic and limit value interrupts to the programmable controller’s CPU
• Diagnostics;
the module sends extensive diagnostic information to the CPU
Technical Specifications
TRANG 1
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Number of inputs 8 8
• For resistance 4 8
measurement
Interrupts
Input resistance/
input ranges
• Voltage +/- 80 mV /10 MΩ, +/- 250 mV/10 MΩ+/- 500 mV/10 +/- 50 mV /10 MΩ
MΩ+/- 1 V/10 MΩ+/- 2.5 V/100 kΩ+/- 5 V/100 kΩ1 to +/- 500 mV /10 MΩ
5 V/100 kΩ+/- 10 V/100 kΩ +/- 1 V /10 MΩ
+/- 5 V /100 kΩ
1 to 5 V /100 kΩ
+/- 10 V /100 kΩ
0 to 10 V /100 kΩ
• Resistance thermometers Pt 100 standard/10 MΩNi 100 standard Pt 100 standard /10 MΩ Pt 100 air-conditioning /10
MΩ
Linearization of characteristic
• Internal Possible -
TRANG 2
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
• Resolution
Cable length (shielded), max. 200 m (50 m at 80 mV) 200 m (50 m at 50 mV)
Current consumption
Number of inputs 2
• For resistance 1
measurement
Interrupts
Diagnostics Red LED for indicating group errors; diagnostic info can
be read out
• Voltage +/- 80 mV /10 MΩ, +/- 250 mV/10 MΩ+/- 500 mV/10
MΩ+/- 1 V/10 MΩ+/- 2.5 V/100 kΩ+/- 5 V/100 kΩ1 to 5
V/100 kΩ+/- 10 V/100 kΩ
- As two-wire Yes
transmitter
TRANG 3
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
- As four-wire Yes
transmitter
- with Yes
2 conductor connections
- With Yes
3 conductor connections
- With Yes
4 conductor connections
Linearization of characteristic
• Internal Possible
• Resolution
- Bipolar 9+sign/12+sign/12+sign/
14+sign bits
Current consumption
Weight 250 g
Number of inputs 8 8
Interrupts
Diagnostics Red LED for indicating group errors; diagnostic info Red LED for indicating group errors; diagnostic info
can be read out can be read out
TRANG 4
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Input ranges
• Voltage - -
• Current - -
• Thermocouples - Type B, E, J, K, L, N, R, S. T, U
- As two-wire - -
transmitter
- As four-wire - -
transmitter
- With Yes -
3 conductor connections
- With Yes -
4 conductor connections
Isolation to backplane bus Yes (4 groups of 2 channels each) Yes (4 groups of 2 channels each)
Linearization of characteristic
• Internal - Possible
- 5 channels or more (> 1 channel per group) 190 ms per module 190 ms per module
Operating error limit (in complete temperature +/- 0.1 % +/- 0.1 %
range, referred to input range), max. +/-1 K +/-1 K
Current consumption
TRANG 5
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
(W x H x D) in mm
Number of inputs 8 8
Interrupts
Diagnostics Red LED for indicating group errors; diagnostic info Red LED for indicating group errors; diagnostic info
can be read out can be read out
Input resistance/
input ranges
• Current ±20 mA/250 Ω0 to 20 mA/ 250 Ω4 to 20 mA/ 250 Ω ±20 mA/250 Ω0 to 20 mA/ 250 Ω4 to 20 mA/ 250 Ω
• Resistance - -
• Thermocouples - -
• Resistance thermometers - -
- As 2-wire transmitter Yes, with external transmitter Yes, with external transducer,
power pack
- With - -
3 conductor connections
- With - -
4 conductor connections
Linearization of characteristic
• For thermocouples - -
Temperature compensation - -
• Internal - -
• Integration time 2.5/16 2/3/20/100 ms 23/72/83/95 ms for all 8 channels of the module. For
more information see manual 3)
• Resolution
TRANG 6
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Operating error limit (in complete temperature ± 0.1 % (voltage) ± 0.1 % (voltage)
range, referred to input range), max. ± 0.3 % (current) ± 0.1 % (current)
Basic error (operational limits at 25 °C, referred to ± 0.05 % (voltage) ± 0.05 % (voltage)
input range), max. ± 0.05 % (current) ± 0.05 % (current)
Current consumption
Number of inputs 8
Interrupts
Diagnostics Red LED for indicating group errors; diagnostic info can
be read out
• Voltage ±1 V / 10 MΩ
±5 V / 100 kΩ
±10 V / 100 kΩ
1 ... 10 V / 100 kΩ
1 ... 5 V / 100 kΩ
• Current ±20 mA / 50 Ω
0 to 20 mA / 50 Ω
4 to 20 mA / 50 Ω
• Resistance -
• Thermocouples -
• Resistance thermometers -
TRANG 7
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Linearization of characteristic
• For thermocouples -
Temperature compensation -
• Internal -
• Integration time -
• Resolution
- Unipolar 14-bit
Current consumption
1) Other details have to be heeded to calculate the cycle time. These can be found in the manual “Configuring an S7-
300®”.
2) Clock alarms are also supported in the modules
3) In the 4-channel mode the basic execution time for all channels is 10 ms
TRANG 8
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Overview
• Analog outputs
• For the connection of analog actuators
Area of application
The analog output modules convert digital signals from the PLC into analog signals for the process.
Functions
The modules feature the following:
• Resolution from 12 to 15 bits.
• Various voltage and current ranges; the ranges are set independently for each channel by means of parameter
assignment software .
• Interrupt capability; the modules transmit diagnostic interrupts to the programmable controller’s CPU on the occurrence
of errors
• Diagnostics; the module sends extensive diagnostic information to the CPU
Technical Specifications
SM 332 6ES7 332- 5HB01-0AB0 5HD01-0AB0 5HF00-0AB0
Number of outputs 2 4 8
TRANG 9
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Interrupts
Diagnostics Red LED for indicating group errors; Red LED for indicating group errors; Red LED for indicating group errors;
diagnostic info can be read out diagnostic info can be read out diagnostic info can be read out
Output ranges
• Current outputs 4 to 20 mA; +/- 20 mA; 0 to 20 mA 4 to 20 mA; +/- 20 mA; 0 to 20 mA 4 to 20 mA; +/- 20 mA; 0 to 20 mA
Load impedance
Voltage output
Current output
Current consumption
TRANG 10
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Number of outputs 4
Interrupts
Diagnostics Red LED for indicating group errors; diagnostic info can be read out
Output ranges
Load impedance
Voltage output
Current output
• Voltage ± 0.01%
• Current ± 0.01%
Current consumption
TRANG 11
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Overview
• Analog inputs and outputs
• For the connection of analog sensors and actuators
Area of application
The analog input/output modules convert
• analog signals from the process into digital values for the PLC and
• digital signals from the PLC into analog signals for the process.
Functions
The analog input/output module features the following:
• 4 inputs, 2 outputs
• Input resolution: 8 Bit (6ES7 334-0CE01-0AA0) 12 Bit (6ES7 334-0KE00-0AB0)
• Output resolution: 8 bit
• Measuring range 0 to 10 V, 0 to 20 mA, the range is selected using the corresponding connections on the module
Technical Specifications
SM 334 6ES7 334- 0CE01-0AA0 0KE00-0AB0
TRANG 12
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
Inputs 4 4
• For 4 2
voltage measurement
Interrupts
• Diagnostics interrupt - -
Diagnostics - -
- As two-wire - -
transmitter
- As four-wire Yes -
transmitter
Conversion time/
resolution per channel
• Current +/-0.8% -
• 10 kΩ - ± 3.5%
• Pt 100 - ± 1.0%
• Current ± 0.6% -
• 10 kΩ - ± 2.8%
• Pt 100 - +/-0.8%
Outputs 2 2
Interrupts
• Diagnostics interrupt - -
Diagnostics - -
Output ranges
• Voltage 0 to 10 V 0 to 10 V
TRANG 13
COÂNG TY COÂNG NGHEÄ TÖÏ ÑOÄNG TAÂN TIEÁN TEL : (84-8)9973944 MB : 0918730423
outputs
• Current outputs 0 to 20 mA -
Load resistor
Voltage output
Current output
• Current ± 1.0% -
General
Current consumption
• From L+ 110 mA 80 mA
Isolation 500 V DC
TRANG 14