Professional Documents
Culture Documents
08 - Kitchen Exhaust Systems - 2.10
08 - Kitchen Exhaust Systems - 2.10
SECTION: 2.10
1.0 Scope
3) Exhaust fans
2.1 All kitchen hoods shall be fabricated from 1.0mm thick S.S 304
supported on galvanised steel frame work.. The type, size and height of
hood and general construction shall conform to the details shown on the
drawings or as approved.
2.2 The entire hood casing shall be welded and rendered air tight. An all-
round grease gutter shall be provided with necessary slope towards
valved drains as shown on drawings.
2.4 Hoods must house one light fitting for every 1.2m length or part
thereof. The fittings shall use 2 x 11 watt compact fluorescent tubes in
vapour tight fitting with Lexon cover. All wiring inside shall be
through 90 deg. C rated wires in galvanised steel conduit brought out in
galvanised steel junction box over the hood with a suitably rated EL
MCB.
2.6 Sprinklers shall be provided inside the hood over the equipment.
Sprinklers shall be water mist type 163°C rated. Sprinkler header shall
be brought out of the hood and terminated in a ball type brass valve.
3.3 Longitudinal joints shall be lapped and revitted or spot welded at 75mm
centre to centre. All joints shall be rendered leak tight by welding or
high temperature tape or any other medium to SMACNA C12 and
validated by testing 10% of duct length.
3.4 Round elbows shall be of five sections upto 200 dia and seven sections
over 200 dia and the centre line radius shall be minimum two pipe
diameters. Transformation shall be concentrically tapered and all
branches shall enter at an angle not exceeding 15 degree. Cleaning
gutters and trapped drains shall be provided as shown on drawings and
as required.
3.5 Upright sprinklers shall be provided inside the duct at every 3.2m till
the vertical riser. All sprinklers shall be water mist 260°C rated.
5.1 The fans shall be tested for the total static pressure and the discharge air
quantity and compared with the design. Hood exhaust quantities shall
be set to conform to design values and the system are balance
accomplished. After balancing, the fan speed shall be regulated by
changing the motor pulleys.
a) Grease filters
c) Sprinklers
6.2 All exhaust ducting shall be measured and paid for per unit area and
this should include:
c) supports
d) joint sealing
6.3 All fire dampers shall be measured and paid per unit cross sectional
area and the rate shall include:
a) cost of damper
b) fusible element/actuator