Professional Documents
Culture Documents
Boiler in Parallel Operation Bari
Boiler in Parallel Operation Bari
For your proper operation of the boilers, we write down the start-up sequences as
follows:
< Boiler Start-up >
1) Select master boiler/PIC C/O SW to “No.1 ”-Stbd boiler
2) Select “PARA” mode
3) Select “16K mode”
4) Set the air controller (port and Stbd boiler) to “cascade mode”
5) Confirm the burners of both boilers are under the firing of B-C oil.
6) Operator increases oil flow of the Stbd boiler manually until the master
pressure rises to 13K around. And then take note the value of oil flow for Stbd
boiler in order to decide the output value of master controller. For example, if
the value of oil flow is 2.5K, master controller output shall be set to 10% ( 4
times is the conversion factor to match range scaling between oil and master
controller, oil : 0 ~ 25K, master: 0 ~ 100%)
7) Steam drum pressure controller(PICP) for Stbd boiler(NO.1) shall be selected
to manual mode and its output shall be set to “4 x oil flow value” for bump-
less transfer at the time of changing the oil controller to Auto mode.
8) Change the oil controller of Stbd boiler to “Auto.”
9) When the above steps are completed, the value of oil flow for port boiler
(No.2) shall be adjusted to match the output value of No.1 master controller.
For example, if the master output value of Stbd boiler (No.1) is 10%, oil flow
value of port boiler (No.2) shall be 2.5K–dividing 10 by 4.
10) Change the oil controller of port boiler (No.2) to “Auto” mode.
11) When the oil flow of both boiler are equal, operator may increase or
decrease the output value of master controller until drum pressure reaches to
the 16K set point.
12) When the drum pressure approaches to +/- 1K of the 16K set value, then
operator is allowed to change the master controller from “manual” to “Auto”
mode.
13) If all the steps are taken successfully, then both boilers will cover the steam
load simultaneously.
1
Note: please keep in mind that boiler should be run slowly for stability at any
time of load increase or decrease. So the governor control of COPT and output
value of the controllers related to boiler ACC including master controller should
be changed slowly during the manual operation. And also note that the number of
boilers to be in service should be selected depending on the steam consumption
of the COPTs in running.
1. Drum level is controlled by two elements: measured value from drum level
transmitter is fed to the controller as Process Value (PV) and percentage value
of steam flow is added to the controller output as feed-forward signal.
2. As drum level variation depends on the load change, increasing or decreasing
boiler load abruptly/quickly should be avoided especially at low load
operation.
3. In certain cases, if drum level fluctuates too much, load change should be
stopped and operator shall switch the controller to manual mode and
manipulate both the drum levels to be kept at nearly same position. Once the
unbalance of both levels is cleared, operator may change the control mode of
controller to “AUTO”
2
operator should be careful that Master boiler/PIC C/O SW must be set to
the boiler in service prior to changing each dedicated FO controller to
Auto mode.
2) Master/Slave mode
-In this mode of operation the boiler selected as Master which fires at
13.5K and stop at 17K will follow the steam load. If FO pressure reaches
12K while drum pressure keeps above 11K, remaining the other boiler
called “Slave” in this case of operation will be started and its FO pressure
will be increased slowly for 15 minutes to cover up the steam
consumption. Then, if FO pressure decreases to reach 4.5K, Slave boiler
will be stopped regardless of steam pressure.
-Meanwhile, Slave boiler will also start and stop when the drum pressure
reaches 13K and 16.5K respectively.
2) 16K mode
3
-In general this mode shall be used at the time of COPT operation..
-At low load of boiler operation when COPT starts and stops, the burner
are to be fired at the drum pressure of 13.5K and stopped at 17K, Master
controller should be set Manual with its output about 10% due to the
reasons as described under 2. 1) above.
3) IGS mode
-This mode of operation can be selected in case that cargo tanks are to be
filled with inert gas (less than 5% O2 content). However, this IGS mode
is not recommended, instead during the filling of inert gas to tanks it is
recommended for operator to observe and make sure that O2 content
should not increase to more than 5% under the 16K mode of one boiler
operation with above 25% MCR load.
-Before change to IGS mode, boiler load must be above 25% MCR under
the 16K mode to avoid any nuisance boiler trip which might be caused by
sharp increase of FO pressure to 6K if select IGS mode at less than 25%
MCR load.
-In this mode boiler will be tripped at 17.5K instead of 17 K of steam
pressure.
-Make sure that boiler load shall be more than 40% MCR in case of IGS
mode of boiler operation and most of steam produced by boiler will flow
through the dump system. (recommend to operate dump valve manually
2) Auto mode
- In this mode, burner will start and stop automatically depending on the
drum pressure variation as stated above.
- All interlock signals will be activated.
- This is the normal mode of boiler operation.
3) Manual mode
- In this mode, burner will start automatically and keep on operation until
4
trip when steam pressure reaches 17.5K. Meanwhile, there will be no
automatic stop of burners depending on the set pressure as described
above.
- This mode can be used in a special case like at the time of safety valve test.
5
consumption, F.D.Fan starting logic will be activated.