Bureau of Design: Schedule of Loads and Computations: General Notes

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES: SCHEDULE OF LOADS AND COMPUTATIONS:

DISTRIBUTION PANELBOARD " DPC " (FOURTH FLOOR)


DISTRIBUTION PANELBOARD " DPA " (GROUND FLOOR)
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH BRANCH BRANCH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CKT. VA PER CKT. BREAKER SIZE OF HOMERUN CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS ( WIRES IN CONDUIT ) LOAD DESCRIPTION VOLTS ( WIRES IN CONDUIT )
NO. CKT. NO. CKT.
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C AF P AT AF P AT

3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE 1 LIGHTING OUTLETS 1260 230 100 2 20 2 - 3.5mm² THHN IN 15mm Ø C 1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
POWER COMPANY SERVICE POINT.
2 LIGHTING OUTLETS 885 20 2 - 3.5mm² THHN IN 15mm Ø C 2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED.
3 LIGHTING OUTLETS 1070 20 2 - 3.5mm² THHN IN 15mm Ø C 3 LIGHTING OUTLETS 1080 20 2 - 3.5mm² THHN IN 15mm Ø C
5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED WITH NOT LESS THAN 3.5 mm² IN SIZE.
4 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 4 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
5 CONVENIENCE OUTLETS 1440 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 5 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 6 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C

8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 3HP, 1Ø, BOOSTER PUMP 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C
7 SPECIAL PURPOSE OUTLET 3000 30 7 3910 40
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. 8 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 8 SPARE 1500 20

10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN 9 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 9 SPARE 1500 20
THE PLAN.
10 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 10 SPARE 1500 20
a) WALL SWITCHES @ 1300mm
b) WALL CONVENIENCE OUTLETS @ 300 mm
c) SPECIAL PURPOSE OUTLETS @ 300 mm 11 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 11 SPARE 1500 20

11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED 12 FACP 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 12 SPARE 1500 20
ELECTRICAL ENGINEER.

13 CCTV 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C TOTAL 14340 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC
ELECTRICAL SYMBOLS:
14 SPARE 1500 20 TOTAL CONNECTED LOADS: 14340 VA

15 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C 14340
I L @ 85% D.F. = (0.85) + 0.25 (17) = 57.25 AMPERES
CEILING LIGHT OUTLET 230
USE : 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
REFER TO SCHEDULE OF 16 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C (57.25 A / 115 A )
CEILING LIGHT OUTLET LIGHTING FIXTURES AND LAMPS
17 3.0 TR, 1Ø, SPLIT TYPE ACU 4850 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
POWER PANELBOARD "PPH"
CF CEILING FAN, 60 WATTS, 230V, 60Hz BRANCH
18 SPARE 4850 60
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
SCF CEILING FAN CONTROL SWITCH TOTAL 47455 MAIN LUGS ONLY: 225AMPS, 2P, 250V, 22KAIC AF P AT

S SINGLE POLE WALL SWITCH IN ONE SWITCH PLATE TOTAL CONNECTED LOADS: 47455 VA 1 2.0HP, 1Ø, 230V, WATER PUMP MOTOR 2760 230 50 2 30 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
(10 AMP., 230 VOLTS)
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE
(10 AMP., 230 VOLTS) 47455 2 2.0HP, 1Ø, 230V, WATER PUMP MOTOR 2760 230 50 2 30 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
I L @ 90% D.F. = (0.90) + 0.25 (21.09) = 190.97 AMPERES
230 USE : 2 - 100mm² THHN + 1 - 30mm² THHN (G) IN 50mm Ø C
S³ 3 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE
(10 AMP., 230 VOLTS) (190.97 A / 225 A ) TOTAL 5520 MACB : 50AF, 2P, 250V, 50AT, 10KAIC

S3W THREE WAY WALL SWITCH (10 AMP., 230 VOLTS) DISTRIBUTION PANELBOARD " DPB " (SECOND & THIRD FLOOR)
TOTAL CONNECTED LOADS: 4600 VA
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 20A, 250VOLTS BRANCH
CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
"WP" DENOTES WEATHERPROOF OUTLET LOAD DESCRIPTION VOLTS 5520
NO. CKT. ( WIRES IN CONDUIT ) I L @ 100% D.F. = (1.0) + 0.25 (12) = 27 AMPERES
AF P AT 230 USE : 2 -8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
SPECIAL PURPOSE OUTLET, GROUNDING TYPE (20 AMP., 300 VOLTS)
SP
1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
SINGLE CONVENIENCE OUTLET, GROUNDING TYPE MAIN DISTRIBUTION PANELBOARD "MDP "
EF "EF" DENOTES EXHAUST FAN (15 AMP., 230 VOLTS)
2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C BRANCH
CONCEALED OR EMBEDDED CONDUIT RUN CKT. BREAKER
CKT. VA PER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS
3 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C NO. CKT. ( WIRES IN CONDUIT )
UNDERGROUND OR UNDERFLOOR CONDUIT RUN AF P AT

4 LIGHTING OUTLETS 1260 20 2 - 3.5mm² THHN IN 15mm Ø C


CIRCUIT HOMERUN 1 "DPA" 47455 230 225 2 225 2 - 100mm² THHN + 1 - 30mm² THHN (G) IN 50mm Ø C

5 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C


ENCLOSED CIRCUIT BREAKER 2 "DPB" 19580 230 225 2 100 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
RATING AS SHOWN ON THE PLAN
6 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C
3 "DPC" 14340 230 225 2 100 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
PB PULLBOX
7 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
4 "PPH" 5520 230 225 2 50 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C

MAIN DISTRIBUTION PANELBOARD 8 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
TOTAL 86895 MACB : 400AF, 2P, 250V, 400AT, 42KAIC

9 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
DISTRIBUTION PANELBOARD
TOTAL CONNECTED LOADS: 82150 VA
10 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
M ELECTRIC SERVICE METER
86895
I L @ 90% D.F. = (0.90) + 0.25 (21.09) = 345.30 AMPERES USE : 2 -250mm² THHN + 1 - 50mm² THHN (G) IN 90mm Ø RSC
11 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 230 (345.30 A / 400 A )
ELECTRIC SERVICE ENTRANCE
12 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C

CAPACITY OF TRANSFORMER:
GROUNDING SYSTEM 13 SPARE 1500 20
KVA = EI @ D.F. = 80%, DIVERSITY FACTOR = 1.10 DECKROOF
14 SPARE 1500 20 1000

FACP = (230) (377.80) (0.80) = 63.20 kVA


FIRE ALARM CONTROL PANEL NOTE:
15 SPARE 1500 20 1000 (1.10)
ALL SIZES OF SERVICE FEEDER (WIRES IN CONDUIT)
USE: ONE (1) SET - 65 kVA, 34.5 kV/230V, 1Ø, 60Hz, AC, OISC, POLE MOUNTED, REFER TO SCHEDULE OF LOADS AND COMPUTATIONS
16 SPARE 1500 20
DISTRIBUTION TRANSFORMER
4TH FLOOR
SCHEDULE OF LIGHTING FIXTURES AND LAMPS TOTAL 19580 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC
"DPC"
INSTALLATION/
SYMBOLS DESCRIPTION TOTAL CONNECTED LOADS: 19580 VA SERVICE LATERAL PROVIDED WITH 90mmØ
MOUNTING
"TYPE F" CONDULETS FOR 230V, 2-WIRE,
SURFACED CEILING 19580 60Hz, A.C. TO CONNECT TO AVAILABLE
1 ONE (1)-28W, 230V,60Hz AC, FLUORESCENT LIGHTING FIXTURE, BOX TYPE. (0.85) = 72.36 AMPERES
MOUNTED I L @ 85% D.F. =
230 USE : 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C POWER LINES.
"MDP"- 3 3RD FLOOR
SURFACED CEILING
(72.36 A / 115 A )
2 TWO (2)-28W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE REINFORCED CONCRETE ELECTRIC
MOUNTED
PEDESTAL 5.00m X 0.30m X 0.30m "DPB"

300mm
ONE (1)-18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE WITH SURFACED CEILING

3100mm (MIN.) - 5500mm (MAX.)


MEDIUM BASE KEYLESS TYPE PORCELAIN RECEPTACLE MOUNTED

ELECTRIC SERVICE
NOTE: ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT METER (CTC METERING) PROPOSED: 2.0HP, 1Ø, 230V,
WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES,
"MDP"- 2 2ND FLOOR 60Hz., AC, WATER PUMP MOTOR
WIRED AND READY FOR USE.
"PPH"
M "DPA" "MDP"
MANHOLE SIZE
AS REQUIRED

1800mm
WP WP

FIN. FLOOR LINE A A


FIN. GRADE LINE
MH
TO "MDP"- 4
1-50mm² THHN IN 25mmØ C. -
2- 250mm² THHN + 1-50mm²THHN(G) CLAMPED TO A 25mmØ X
1-5.5mm² THHN IN 15mmØ C.
IN 90mmØ RSC 3000mm COPPERCLAD AUTOMATIC CIRCUIT BREAKER
A - CLAMPED TO A 16mmØ X
GROUNDING ELECTRODE 50AF, 2P, 240VOLTS, 30AT
2400mm COPPERCLAD
IN NEMA 3R ENCLOSURE
GROUNDING ELECTRODE
ELECTRICAL RISER DIAGRAM B
AUTOMATIC CIRCUIT BREAKER
NOT TO SCALE 50AF, 2P, 240VOLTS, 40AT
IN NEMA 3R ENCLOSURE

AUTOMATIC CIRCUIT BREAKER


C 100AF, 2P, 240VOLTS, 60AT
IN NEMA 3R ENCLOSURE

REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED: SIGNED SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO. SHEET NO.
MARU BRYAN T. ZAPLAN
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS GENERAL NOTES
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
MODIFIED STANDARD DPWH - DEPED ELECTRICAL SYMBOLS CADD: SIGNED
BUREAU OF DESIGN FOUR (4) STOREY, TWENTY (20) SCHEDULE OF LOADS MARU BRYAN T. ZAPLAN
ENGINEER II
APPROVED WITH SIGNATURE BOD
E - 12
BUILDINGS DIVISION SCHEDULE OF LIGHTING FIXTURES AND LAMPS JOSEPHINE P. ISTURIS LEA N. DELFINADO GILBERTO S. REYES LEONOR M. BRIONES
CLASSROOM SCHOOL BUILDING ELECTRICAL RISER DIAGRAM CHECKED: SIGNED
OIC, UNDERSECRETARY FOR B 12 90
BONIFACIO DRIVE PORT AREA, MANILA ERIBERTO B. SIOSON CHIEF, BUILDINGS DIVISION OFFICER-IN-CHARGE, BOD SECRETARY, DEP ED
ENGINEER IV TECHNICAL SERVICES, DPWH

You might also like