Professional Documents
Culture Documents
PDF 83885 Mark IV Operator Manual DL
PDF 83885 Mark IV Operator Manual DL
(SupersedesGEK-83885)
GE DriveSystems
Instructions
Mark IV
SPEEDTRONIC’”
Gas Turbine Control
Operator’s Manual
Mark IV SPEEDTRONICTM
Gas Turbine Control
Operator’s Manual
GEK43885A
(Supersedes GEK-83885)
These instructions do not purport to cover all details or variations in equipment, nor to provide for every
possible contingency to be met dwing installation, operation, and maintenance. Should further
information be desired or should particular problems arise that are not covered sufficiently for the
purchaser’s purpose, the matter should be rej2rred to GE Drive Systems, Salem, Virginia, USA.
0 1987, 1989 by General Electric Company, U.S.A.
All rights reserved.
NOTICE
This document contains proprietary information of General Electric Company, U.S.A. and is
furnished to its customer solely to assist that customer in the installation, testing, and/or
maintenance of the equipment described. This document shall not be reproduced in whole
or in part nor shall its contents be disclosed to any third party without the written approval
of GE Drive Systems, 1501 Roanoke Boulevard, Salem, Virginia 24153, U.S.A.
TABLE OF CONTENTS
LIST OF ILLUSTRATIONS
l-l Typical Mark IV SPEEDTRONIC” Oper- 3-6 Manual Control Display: Auxiliary
ator Interface Module with CRT . . ... . . ... . . 1-O Control .................................................... 3-7
2-1 Operation/Control and Emergency Stop 3-7 Display Menu ............................................. 3-8
Switches of Operator Interface Module -2-l 3-8 Exhaust Thermocouples.. .......................... .3-9
2-2 Display, Alarm, and Printer Switches of q-9 Wheelspace Thermocouples.. .................... -3-9
Operator Interface Module . .. .. . . .. ... . .. .. . ..2-3 3-10 Lube Oil Thermocouples ....................... ..3 - 10
2-3 CRT Display and Display Function 3-11 Timers and Event Counters ................... ..3 - 10
Switches of Operator Interface Module .2-4 3-12 Wet Low Nox Display ............................... 3-11
2-4 Historical Log: Parts 1, 2, and 3 . . . ... .. . .. . ... .2-6 3-13 Demand Display (Normal) ..................... ..3 - 13
2-5 Historical Log: Parts 4, 5, and 3-14 Demand Display (Set Time Mode) ........ ..3 - 13
Alarms (FL) . . ...*....................................... 2-7 3-15 Rung Display (Typical). ........................... .3-l 5
3-1 Normal Display Fields (Relative 3-16 Rung Display (Timer) ............................... 3-15
Positions) . . ... . . .. ... .... .. .. .. . .. ... . . .. . .. .. . .... . .. . . ..3-l 3-17 Administrative Displays (Menu) .............. .3- 16
3-2 Startup Normal Display .. . ... .. . .. . .. .. . .. ... .. . . .. .3-3 3-18 Administrative Display (Normal). ............ .3- 17
3-3 Running Normal Display . .. ... . .. . . ... . .. ... .. .. .. .3-4 3-20 Reset Display Mode .................................. 3-19
3-4 Shutdown Normal Display ... .. . .. . ... . . ... . .. .. . ..3-4 4-1 Auxiliary Display of Operator Interface
3-5 Alarm Display .. . .. ... ... .. .. .. .. . ... .. . . .. .. .. . ... . .. .. . ..3-5 Module .................................................... 4-1
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
- Notes -
.. .
Ill
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
DlsPLAY
XLECT LIST W LllSPLAY MENU - SECTIOW SELECTON -
FUNCYIONS
LIST TITLE LXST TITLE
00 CONTROLREFERENCE 10 TRIP DISPLAY m
EXHAUST THERMOCOUPLES II 1 -2s ANAL00 OUT DISPLAY
:: WEELSPACE THERMGCWPLES I2 DEHANO LOB
RUN0 DISPLAY
- SECT,ONS
RUNN:NO -
:: TIMERS AND EVENT COUNTERS I: I
IS ANALOG CONTROL
t2 LOGIC FDRCING
I?
:8’ I
INTER-PROCESSON LOGIC DATA
Ii INTER-PNOCESSGR REAL DATA
:: IA CONTACT INPUTS
ID RELAY OUTPUTS I
:: IC ADMINISTRATIVE MENU
ND CATEGGNY 0 COMPOSITE ID CONTROL CONSTANTS
BE COHPOSITE LOGlCS IE MEMORY
NF COHPOS1TE REALS IF DIAGNOSTXC DISPLAYS I
I I
-PANTEN-
-DISPLAY
CUNSDR-
-EXECUTE-
<
El
J,
*OPTIONAL
Figure l-l. Typical Mark IV SPEEDTRONIC N Operator Interface Module with CRT
1-O
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
CHAPTER 1
OVERVIEW
l-l
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
- Notes -
1-2
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
CHAPTER 2
2-1. INTRODUCTION Most operator controls function only when the < C >
Communicator computer is operating. However, the
The Operator Interface Module (refer to Figure l-l) is Emergency Stop pushbutton (see Figure 2-l) is active in
used by an operator to control gas turbine equipment all modes of operation. Additionally, the following
or to obtain data about the equipment. It contains nine switches, identified by a blue triangle printed on them,
functional groups of switches, used as follows: remain functional when the < C > Communicator is
not operating:
l For controlling the equipment
0 stop in the Operation/Control group
- Operation/Control group
- Emergency Stop pushbutton 0 Alarm Silence in the Alarm group
0 Alarm Reset in the Alarm group
- Alarm group
a To manipulate data 2-2. OPERATION/CONTROL SWITCHES
- Display Keypad group The operator uses Operation/Control switches (see
- Display Cursor group Figure 2-l) to send control commands to the gas
“- Display Mode group turbine equipment. These switches are designated by
- Display Functions group their yellow color. Up to 28 Operation/Control
- Printer group switches reside in a group on the right side of the
Operator Interface Module. This group is divided into
0 As an alternative to the CRT the functional subgroups of Operation, Load, Master
- Auxiliary Display group Control, Fuel, IOV Temperature Control, and optional
switches. Another Operation/Control switch, Execute, is
The following paragraphs describe these operator located on the lower left side of the module.
controls and their functions.
OPERATXOW
OPERATION/CONTROL SWITCHES
- DETAILVIEW -
EXECUTE SWITCH OF
~;~~~TlON/CONTROL
Figure 2-l. Operation/Control and Emergency Stop Switches of Operator Interface Module
2-1
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
The operator initiates a control command to the gas down sequence. This pushbutton mechanically latches
turbine equipment by pressing the appropriate Oper- in the STOP position when it is pressed. As noted
ation/Control switch. The control responds with an previously, Emergency Stop is active in all modes of
audible “beep” to acknowledge receipt of the input, operation.
and flashes the light above the switch. It then waits for Operator A&on
Function
the operator to confirm the command. To do this, the
operator must press the yellow Execute switch within 3 Emergency stop Press Emergency Stop
seconds after pressing the control switch.
Reset emergency Turn Emergency Stop clockwise
stop
** NOTE **
This procedure for confirming a com- 2-4. AIARM SWITCHES
mand input prevents false commands
The two Alarm switches are located below the CRT
from being executed. Only switches in the (see Figure 2-2). The Operator uses the Alarm Silence
Operation/Control group require the op switch to silence the alarm horn. The Reset switch
erator to also press the Execute switch. All resets all acknowledged and cleared alarms. As noted
switches in the other functional groups, previously, the Alarm group switches still functions if
plus the Emergency Stop pushbutton, do the < C > communicator is not operating.
not require this protective feature. Section 3-3 discusses the alarm system.
When the Execute command is received, the light above
the control switch changes from flashing to continu- 2-5. DISPLAY KEYPAD SWITCHES
ously on if the gas turbine can accept the control input. An operator uses the Display Keypad switches to select
For example, the gas turbine cannot accept a Crank Data List displays or parameters that appear on the
command if it has detected a fire. Also for example, CRT. These switches are located directly below the
when the Normal Display (see section 3-2) displays the CRT (see Figure 2-2). They include a full set of
message NOT READY TO START, a Stirt command alpha-numeric characters and the following auxiliary
input is accepted but cannot be acted on. When this switches:
occurs, the system displays an alarm message that
specifies the reason the start per-missives are not Space - Creates a blank character
satisfied. Delete - Deletes a single character
Clear - Deletes an entire character string
Not all Operation/Cont.rol switches require pressing
the Execute switch. Ones that involve continuous mon- S&l - Accesses the alternate character printed
itoring (such as the optional Raise and Lower switches at the top of the Display Keypad switch when
that adjust the speed/load setpoint on compressor pressed with the switch
drive applications) do not require the execute action. Enter - Loads the typed characters into the
Additionally, the Stop switch, which normally requires computer to initiate a command
pressing the Execute switch, functions without it if the
The description of the displays (Chapter 3) provides
< C > Communicator stops operating.
examples of how to use the Display Keypad switches.
The following shows a typical operation selection
procedure: 2-6. DISPLAY CURSOR SWITCHES
Operation Press Switch Comments A cursor appears on some CRT Data List displays. It is
Off 1. off Off light on used during maintenance to select a signal value, a
logic level, or a constant to be changed, entered, or
displayed. The operator moves the cursor by pushing
Crank 1. Crank Crank light flashes the Display Cursor switches Up, Down, Lefi, and Right.
As shown in Figure 2-2, these switches are located
2. Execute Crank light goes on
below the CRT.
steady, Off light goes off.
2-7. DISPLAY MODE SWITCHES
2-3. EMERGENCY STOP PUSHBUTTON
The operator uses the five Display Mode switches
The Emergency Stop switch is a large red pushbutton (Norm&, Manual, Alarm, Manual Control, and Reset) to
located on the lower right side of the Ooerator Inter- select display modes. These switches are located on left
face Module (see Figu;e 2-l). The op&ator pushes bottom side of the Operator Interface Module (see
Emergency Stop to stop the gas turbine under emer- Figure 2-2). Chapter 3 describes the CRT displays and
gency conditions, instead of using the normal shut- use of these switches.
2-2
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
cl I
DAYA nu CTL
-PRINTER-
cl cl
PESET
-DISPLAY CURSOR -
Figure 2-2. Display, Alarm., and Printer Switches of Operator Interface Module
2-3
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
Dl9PLAY
T LIST 90 DIS .AY MENU FUNCTIONS
TITLE
CONTROLREFERENCE
EXHAUST THERMOCOUPLES
MELSPACE THERHGCOUPLES
qjGi&f
I2
IIllERSANDEVEllT COUNTERS I:
ANALOG CONTROL
I:
17
I8
ILOGIC FORCING
Figure 2-3. CRT Displuy and Disp,?uy Function Switches of Operator Interface Module
2-4
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
2-5
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
2-6
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
2-7
GEK-83885 Mark IV SPEEDTRONICm Gas Turbine Control Operator’s Manual
- Notes -
2-8
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
CHAPTER 3
CRT DISPLAYS
3-1
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
3-2.2. status. The Status field displays the status 40% oil and 60% gas mixture is selected, the display
of the Operating Mode. Typical messages are: shows 60% gas. This display applies to dual fuel
machines only.
READY TO START
STARTING 3-2.10. Date and Time. The Date and Time field is
FIRING the control panel clock, which appears on all CRT
WARMING UP displays.
FULL SPEED NO LOAD, etc.
3-2.11. FLAME/SPREAD. In the Startup and
3-2.3. SELECT-l and -2. The SELECT-l field Shutdown operating modes, this field provides
displays the master Operation selected (via the Oper- FLAME data. It displays the identification number of
ation/ Control switches; see Figure 2-l). Possible mes- each flame scanner that is detecting a flame.
sages are: In the Run operating mode, this field provides
SPREAD data. It shows the difference between the
. OFF
highest and the lowest exhaust thermocouple temper-
. CRANK ature. The SPREAD is displayed in units of DEG F or
. FIRE DEG C (degrees Fahrenheit or Celsius).
. AUTO
. REMOTE 3-2.12. IGV. The Inlet Guide Vanes field displays
the position of the turbine compressor inlet guide
The SELECT-2 field displays the master Control se- vanes in degrees of mechanical angle. IGV is displayed
lected (via the Operation/Control switches; see Figure only in the RUN operating mode.
2-l). Typical messages are:
3-2.13. MAKVIB. The Maximum Vibration field
. START
displays the maximum signal of all the vibration
l STOP inputs. The display units are IPS (inches per second)
. BASE or MM/S (millimeters per second).
l PEAK, etc.
3-2.14. SPEED LEVEL. The SPEED LEVEL field
3-2.4. CONTRL (Control). The CONTRL field displays the gas turbine current speed level, which is a
identifies the control loop presently governing the fuel predefined speed point. The SPEED LEVEL is dis-
to the gas turbine. Typical messages are: played only in the Startup and Shutdown modes of
operation. Typical messages are:
. STARTUP
0 14HR (Zero Speed)
. ACCEL
0 14HM (Minimum Speed)
. TEMP l 14HA (Accelerating Speed)
0 SPEED, etc. l 14HS (Operating Speed)
3-2.5. TX. The TX field indicates the exhaust 3-2.15. Message 1, 2, and 3. The message fields
thermocouple average temperature. It is displayed in display various messages associated with the gas tur-
DEG F or DEG C (degrees Fahrenheit or Celsius). bine control. The following are typical messages.
Message 1:
3-2.6. SPEED. The SPEED field displays the gas
turbine high pressure shaft speed in units of percent- . TRIP
age of rated speed. . FAST LOAD START
Message 2:
3-2.7. TNHSET. The TNHSET field provides the
reference for the gas turbine speed or load. It is . SEQ IN PROGRESS
displayed in units of percentage of speed. Message 3:
3-2.8. FSR. The Fuel Stroke Reference is the . IGV FULL OPEN
reference for the gas turbine fuel system that regulates . IGV TEMP CONTROL
the meI flow rate. It is displayed in units of percentage
of FSR. 3-2.16. Alarm Messages. The Alarm Messages
field displays the three oldest unacknowledged alarm
3-2.9. FUEL. The FUEL field displays the per- messages, with the oldest at the top of the list. This
centage of the primary fuel selected. For example, if a display field is provided to avoid the need to switch to
3-2
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
the more comprehensive Alarm Display. In addition, Normal Display Function Operator Action
the number of previously acknowledged alarms is
shown. To display signal in SELECT 1. Type signal name
field 2. Press Enter
An operator can silence, acknowledge, and reset an To clear all SELECT fieids l.TypeO
alarm without changing the display. This is done by 2. Press Enter
pressing either the Alarm A& switch (F5) in the Display This displays the logic or analog parameter in engi-
Functions group, or the Silence or Reset switches in the neering units. When more than three signals are
Alarm group. entered, the bottom signal is deleted from the display
and the new signal is added to the top of the list.
3-2.17. SELECT (Additional Parameters). The 3-2.18. ALARM ACK. This display field assigns
SELECT field enables an operator to select three the Alarm Acknowledge function to the Display Func-
parameters to be displayed simultaneously, without tions switch F,. Press this switch to acknowledge a
needing to call up another display. These can be flashing alarm message.
control or logic type signals, and can be called by their
3-2.19. IDENTITY. This field is provided for
functional name used on the Gas Turbine Control
elementary diagram. reference on multiple unit installations, and may be
disabled on single unit installations. This field displays
an optional two-character ASCII string for identifying
The operator selects signals by typing the required the control panel or turbine being monitored. Main-
signal name(s) on the Display Keypad switches, as tenance personnel enter the ASCII string using the
follows: Administrative Display.
WARMING UP
SELECT AUTO;START FLAME #1#2#7#8
CONTRL STARTUP
TX.... 407 DEG F MAXVIB 0.03IPS
SELECT
TNH PR 1020 RPM ALARM
LlZ 0 LOGIC ACK
ACKNOWLEDGED ALARM.5 1 ID: Ul L2W 0 LOGIC
3-3
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
SPEED. lOO.OO%S PD
ON COOLDOWN
CONTRL STARTUP
3-4
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
Silence alarm horn Silence Alarm 3-3.2. Alarm Logging. For automatic alarm log-
ging, the panel mounted printer prints the appropri-
Acknowledge alarm Alarm Ack Display Functions ate alarm message each time the corresponding alarm
(Flashing light changes to steady on) logic signal changes status. It notes the status (alarm or
normal) of the alarm logic signal.
Reset alarm Reset Ah-m
The alarm log format is: date, time, drop number,
(Delete acknowledged& cleared alarms)
alarm message, and status (Alarm or Normal).
Lockout an alarm 1. Alum Lmout Display Functions
2. Type drop no. Display Keypad 3-3.3. Diagnostic Alarms. Another group of alarm
3. Entm Display Keypad messages are the diagnostic alarms. Maintenance per-
(Drop no. appears in inverse video) sonnel use these to determine the nature of a fault
condition within the control panel. This condition is
Unlock an alarm 1. Alarm Unloc Display Functions identified by the alarm message DIAGNOSTIC
$. gny; drop no. Display Keypad ALARh4 - SEE DISPLAY. The Diagnostic Alarm dis-
Display Keypad
play can be accessed by pressing the Diagn Alarm
(Drop no. returns to normal video) switch in the Display Functions group.
UNLOC
ACK
3-5
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
Table 3-l. Typical Sequence for Silencing, Acknowledging, and Resetting Alarms
Press Alarm Ack switch In Normal Display mode: the three dis layed alarms are
acknowled ed and the messages are de Peted from the Normal Displa
The next tKree oldest unacknowledged alarm messages are displaye 8..
In Alarm Display mode: all alarms are acknowledged to steady on.
Input returns to In Alarm Display mode: Alarm status changes from “1” (alarm) to “0”
normal (clears) (normal).
Printer prints the data for each cleared (normal) alarm.
Manual Control display Man Ctl Display Mode Cooldown On cooldow?l on Display Functions
Next Manual Control Next Page Display Functions (SEQ IN PROGRESS message displayed
function display during cooldown sequence.)
(If aII permissives for Shutdown Status,
Figure 3-6 shows a typical display of manual control of including Operation Off, are satisfied, the
the auxiliaries using Cooldown Mode selection. ON COOLDOWN message is displayed.)
3-4.1. COOLDOWN OFF/ON Manual Selection. Cooldown Off cooldoWl off Display Functions
The permissives that govern the cooldown operation (If aII permissives are met, such as if man-
vary, depending on the operating mode and status. datory cooldown time has expired, the
They also may vary with the application requirements. OFF COOLDOWN message is displayed;
The permissives must be met for the control to accept SEQ IN PROGRESS and ON COOL
the Cooldown Mode selection commands. Typically, DOWN messages are deleted.)
3-6
Mark IV SPEEDTRONICm Gas Turbine Control Operator’s Manual GEK-83885
STATUS ON COOLDOWN
CONTROL STARTUP
430 DEG F
TNH 0.97 % SPD
TN-R 95.00 % SPD COOLDOWN
FSR 0.0 % FSR ON
CSGV 34.00 DGA
SELECT:
3-7
GEK-83885 Mark IV SPEEDTRONICN Gas Turbine Control Operator’s Manual
3-5. DATA (DISPLAY MENU) DISPLAYS not marked are used for maintenance. Figures 3-8
thru 3-12 and the following paragraphs discuss the
The Display Menu (see Figure 3-7) contains the list of operator displays.
available displays. It also includes the SELECT LIST
## field in the upper left comer, in which the “##” 3-5.1. Data List 01: Exhaust -Thermocouples.
number identifies the previously selected data list. The This data list displays the exhaust thermocouple tem-
operator can return to this list by pressing the Enter peratures (see Figure 3-8). Press the Next Page or
switch, without having to retype the list number. Previous Page switch in the Display Functions group to
display another data list page, if one exists.
The operator can access a variety of displays by first
selecting the Display Menu, then selecting the desired 3-5.2. Data List 02: Wheelspace Thermocouples.
List number from the Display Menu, as follows: This data list displays the wheelspace thermocouple
temperatures (see Figure 3-9). Press the Next Page or
Function Press Switch Switch Group Previous Page switch in the Display Functions group to
Display Menu 1. Da.!u Display Mode
display another page, if one exists.
Data List 1. Type list no. fi-om Display Keypad
Display Menu 3-5.3. Data List 03: Lube Oil (Bearing Drain Ther-
2. Enter Display Keypad mocouples. This data list displays the lube oil
(bearing drain) thermocouple temperatures (see Fig-
Another 1. Data Display Mode ure 3- 10). Press the Next Page or Previous Page switch in
Data List 2. Type list No. Display Keypad
the Display Functions group to display another page,
3. Enter Display Keypad
if one exists.
Return to 1. Data Display Mode
last selected 2. Enter Display Keypad 3-5.4. Data List 04: Timers and Event Counters.
Data List (Enters Select List no. from upper left of This data list displays the current values of timers and
Display Menu) counters such as FIRED TIME and TOTAL STARTS
(see Figure 3-11). Press the Next Page or Previous Page
On Figure 3-7 (not on the actual display), an asterisk switch in the Display Functions group to display an-
(*) marks displays typically used by an operator. Those other data list page, if one exists.
3-8
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
3-9
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
DATA LIST 04 TIMERS AND EVENT COUNTERS 14 MAR 84 13:54:17 Ul PAGE 000
PREVIOUS
PAGE
NAME TITLE VALUE UNITS
3-10
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
3-5.5. Data List 07: Wet Low Nox Data Average Fuel Flow: for example, LIQ(uid)
FUEL
3-5.5.1. WET LOW NOX DISPLAY. Data List 07 Average Injection Flow: for example, WATER
displays the data required to verify the compliance Average Actual Injection to Fuel Ratio: labeled
with low nitrous oxide emission regulations (see Figure ACTUALRATIO -
3- 12). This data list consists of the Hourly Average and Average Required Injection to Fuel Ratio: la-
the Minute Averages. beled REQUIRED RATIO
The Minute Average is the average of the inputs
3-6.5.2. WET LOW NOX PRINTER LOG. The
during each minute. It is calculated when the Wet Low
panel-mounted printer automatically prints out both
Nox control is enabled. Data List 07 displays the last
the Hourly Average log and the Minute Averages log.
10 sets of Minute Averages with the latest data at the
top of the list. The Hourly Average log prints out once each hour
when: (1) the Wet Low Nox control is enabled
The Hourly Average is the average of the last 60 and (2) 60 of the minute averages have been accumu-
minute averages. It is calculated each minute when the lated.
Wet Low Nox control is enabled and 60 of the minute Each printout consists of one set of data.
averages have been accumulated. Data List 07 displays
The Minute Averages log prints out each hour
the last calculated Hourly Average, which consists of
when: (1) the Wet Low Nox control is enabled, (2) a
one set of data.
quantity of 60 of the minute averages have been
Each set of data, which is displayed on one line, accumulated, and (3) the REQUIRED RATIO is
consists of the following: greater than the ACTUAL RATIO for the hourly
average.
0 Date and Time of the average calculation Each printout consists of 60 sets of minute averages
0 Average Fuel Flow: for example, GAS FUEL that were used in the last hourly average calculation.
HOUR AVERAGE
TIME GAS FUEL LIQ FUEL WATER... ACTUAL.. REQUIRED
LBSISEC LBS/SEC LBS/SEC RATIO RATIO
MINUTE AVERAGES
TIME GAS FUEL LIQ FUEL WATER... ACTUAL.. REQUIRED
LBSISEC LBS/SEC LBSJSEC RATIO RATIO
3.11
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
3-5.6. Data List 12: Demand Display. This data 3-5.6.2. AUTOMATIC DEMAND DISPLAY LOG
list enables the user to display up to 64 selected data PRINTOUT. The following steps show how an op-
points or signal names on two pages of the CRT
erator initiates automatic printout of the Demand
display. Figure 3-13 shows the normal Demand Dis-
Display log.
play. (“Normal” is when the Demand Display is not in
a Set Mode.) Each item in the list consists of the Name, Selection Press Switch Switch Group
Value, and Units (for example, TTXM, 821, DEG F). 1. Data List 12 1. Data Display Mode
This data list can be printed on the panel printer 2. Type 12 Display Keypad
either by manual initiation or automatically. A manual 3. Enter Display Keypad
copy prints only the page currently displayed on the (Displays Data List 12)
CRT.
An automatic log periodically prints all the pages of
the data list with the header message “Demand Display 2. Set Lo 1. Set Time On/ Display Functions
Log.” While the automatic log mode is selected, the Perio rI Off once
data list is printed after each expiration of the speci- (a. Enters Set Time mode)
fied time interval. The time interval may be set from (b. Display Function switches redefined)
continuous operation up to 24 hours.
Figure 3-14 shows the reassignment of the Display 2. Increcxe Period or Display Functions
Functions switches during the Set Time mode. Decrease Period
3. Manual printout 1. Next or Display Functions 4. Turn off 1. Set Log On/Off Display Functions
of another page Previous Page Auto Log once
3-12
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
DELETE
ENTRY
SET LOG
ON/OFF
SET TIME
LINK STATUS R S T 0 FAILED ON/OFF
LOG PERIOD = 240 MINUTES:
DECREASE
PERIOD
SET LOG
ON/OFF
SET TIME
LINK STATUS R S T 0 FAILED ON/OFF
LOG PERIOD = 240 MINUTES
3-13
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
3-4.7. Data List 13: Rung Display. The Rung Selection Press Switch SwitchGroup
Display presents the control Sequencing data in a 4. End rung 1. End (&) Display Functions
ladder diagram format. This display provides a conve-
nient method of reviewing the sequencing data, and (Displays the last rung of sequencing)
the current status of each component. Maintenance
personnel use this display for troubleshooting, but 5. previous 1. Last (Fs) Display Functions
operators can use it to review the condition of specific displayed rung
(Displays the previously displayed rung)
functions.
(Can be used to toggle between two
The Display Functions switches are used to change rungs)
displays, find a rung by signal name, find rungs that
use a particular signal name, and to switch between R, 6. previous 1. PreLJ (FJ Display Functions
S, T, and C sequencing. Each screen displays one rung. sequential rung
(Displays the rung sequentially located
Figure 3-15 shows a typical rung display. before the current rung)
The system provides two methods to indicate the
current value of each contact and coil in the ladder 7. Next 1. Next (F5) Display Functions
sequential rung
diagram. The CRT uses inverse video to indicate (Displays the next sequential rung)
continuity thru a contact and to indicate that a coil is
energized. However, since printed copy cannot use 8. zg Used 1. Right Arrow Display Cursor
this method, it places a “-” under each closed contact 2. Type signal Display Keypad
and energized coil. 3. Enter Display Keypad
For reference, the display also includes the current (Find a rung where a particular signal
value of variables used in special functions, such as is used as an input)
timers. These special functions are shown enclosed in (Dis lay Functions switches now search
a box. Refer to Figure 3- 16 for an example of a timer for 91 e Begin (first se uentjal), End
function. (last sequential), Last 4.prevlous
display), Frey sequentral, and NeXT se-
The following procedures show how to use the Rung quenual run usmg the speafied stgnal
Display. within the seHected sequencing pro-
gram.)
Selection Press Switch Switch Group
1. Data List 1. Data Display Mode 9. Rung mode 1. La@Arrow Display Cursor
13 2. Type 13 Display Keypad 2. Type signal Display Keypad
3. Enter Display Keypad 3. Enter Display Keypad
2. Current 1. Select (F,) Display Functions (Find a rung with the specified signal
as the output coil)
program (Toggles between < RST> and <C > (Normal Display mode, Display Func-
sequencing) tions keys now select for the Begin
(first rung), End (last rung), Last ( re-
3. First rung 1. Begin (FI) Display Functions vious display)! Prey sequential, an f!
Next sequenual rung withm the
(Displays the first rung of sequencing) selected sequencing program.)
3-14
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
END
PREV
PREV
3-15
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
3-5.8. Data List 1C: Administrative Displays Menu Selection Press Switch Switch Group
Data List 1C is the list of available Administrative 5. Return to 1. Exit (F,) Display Functions
last selected 2. Enter Display Keypad
Displays. This menu contains a SELECT ## field in
Administrative
the upper left comer. The “##” is the identifying Display (Enters Select No. from upper left comer
number of the previously selected menu list. The of Administrative Displays screen.)
operator can return to this list by pressing the Enter
switch, without having to retype the list number.
The operator can select different Administrative dis-
plays by first selecting Data List lC, Administrative
Displays, and then selecting the desired List number
from the menu. Figure 3-17 shows a typical Adminis- 3-5.9. Administrative Displays List No. 00: Admin-
trative Displays menu. istrative Display. This display enables the operator
to set the date and time, and to select the type of
The following procedures show how to access the scaling units to be used in displaying data. Figures
Administrative displays. 3-18 and 3-19 show these displays.
Selection Press Switch Switch Group The Security Code selection, Identify Code selection,
1. Data List 1. Data Display Mode and PROM Identification Numbers are for mainte-
nance use. The Identify Code is an optional
2. Administrative 1. Type List No. 1C Display Keypad
Displaysmenu 2. Enter P-character ASCII string that can be used to identify
Display Keypad
most data list displays and logs on multi-unit installa-
3. Administrative 1. Type Display No. Display Keypad tions. When enabled, it appears between the Date/
Display from list of dis- Time field and the Page Number field on most dis-
plays plays. It is printed in the space between logs in the
2. Enter Display Keypad format “ID: ##“, where ## is the ASCII string
entered using this display. Refer to Figures 3-18 and
4. Another 1. Exit (F,,) Display Functions 3- 19 for typical examples of displays with identity code
$$?:$trative (Returns to list) enabled. The identity code also appears on the Nor-
2. Type Display No. Display Keypad mal Display (see paragraph 3-2 and Figure 3-4).
3. Enter Display Keypad
SELECT 00
00 ADMINISTRATIVE DISPLAY
(SET TIME: SCALING CODE: SECURITY CODE)
01 RENAMEABLE LDATA POINT SUMMARY
02 RENAMEABLE IDATA POINT SUMMARY
03 SCALING DATA SUMMARY
04 LDATA/IDATA MODIFICATION DISPLAY
(PLUS CONTROLCONSTANTS DISPLAY ADDITION)
05 ALARM MESSAGE LIST
06 ALARM TEXT MODIFICATION DISPLAY
07 EEPROM MAINTENANCE DISPLAY
08 OPTIONS DISPLAY
3-16
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
3-17
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
3-5.9.1. TIME AND DATE SETTING. The follow- Selection Press Switch Switch Group
ing steps show how to set the time and date, using “27 10. Cancel Set 1. Exit LXspkzyFunctions
Mar 84 15:13:00” as the example. Time and Date
mode. (before
Selection Press Switch Switch Group Enter), and re-
turn to Menu.
1. Data List 1C 1. Data Display Mode (Time and date are not changed.)
;* in?; 1C
3-18
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
13 MAR84 21:15:30
MASTER
RESET
LOCKOUT FUNCl-‘ION MASTER RESET SWITCH
3-19
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
- Notes -
3-20
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
CHAPTER 4
AUXILIARY DISPLAY
nhicTmD*- -VALUE-
AUXILIARY DISPLAY
- DETAIL VIEW - L,W uY)n
IB”lll”lm13D]
- SECTION SELECTOR -
fJ”fJoiptio ~rnm-l
- SECTlOWS RUNNINO -
6 b b b
41
GEK-83885 Mark Iv SPEEDTRONIC” Gas Turbine Control Operator’s Manual
2. Value (4 digits) Select this mode to exit the current display mode or to
- When the List Mode is selected, the value of enable the selection of another display mode:
the point number is displayed in engineer-
ing units along with the decimal, when Selection Press Switch Switch Group
applicable. 1. Mode Shif Function Selector
- When the Alarm mode is selected, the Value
field is blank. 2. State Exit Function Selector
The Function/Value display may show a numeral “1” (“1” rotates through the display)
continuously rotating fi-om right to left. This is normal
and indicates that the List Mode or Alarm Mode can This mode displays a prede-
4-3.2. List Mode.
be selected (see paragraph 4-3).
fmed list of data points that are displayed one at a time
for 2 seconds each as they are rotated through the
4-2.2. SECTIONS RUNNING Lights: C, R, S, and display. The rotation can be stopped and the points
T. These four lights continuously monitor the run- stepped one at a time.
ning status of the panel computers: <C > communi-
These data points are the primary control parameters
cator and < R > < S > CT> controllers. A light on
and are shown in the same order and with the same
indicates that the computer is operating.
units as shown in the Normal Display.
4-2.3. SECTION SELECTOR Switches: C, R, S, The following is a typical list of points displayed in the
and T. List Mode.
4-3.1. Mode Select State. This is the normal mode 5. Exit List 1. Shift Function Selector
for the display and is indicated by the numeral “ 1” Mode 2. Exzt Function Selector
continuously rotating from right to left through the (“1” rotates through the display)
Value and Function digital display fields.
4-2
Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual GEK-83885
4-3.3. Alarm Mode. This mode displays all of the Selection Press Switch Switch Group
existing alarm drop numbers, one at a time, with the Function Selector
5. Decrement 1. Shz$t
unacknowledged alarm drop numbers flashing and the display 2. Prev Function Selector
with the acknowledged alarm drop numbers steady on. (The previous (older) drop No. is
The alarms are listed in the order of their occurrence displayed)-
with the latest alarm appearing first in the alarm list.
6. Increment I. Shift Function Selector
The alarms are acknowledged with the Function Se- the display 2. Next Function Selector
lector Next switch and the display is incremented or (The next (newer) drop No. is displayed)
decremented with the Next or Prev switch. The alarms
7. Exit Alarm 1. Shifii Function Selector
are silenced and reset with the Alarm group switches.
Mode 2. Emt Function Selector
Whenever there is valid communications between the (“1” rotates through the display)
<R>, <S>, and CT> controllers and the CC>
communicator (all four Section Running lights are on),
the alarms in the < R> , < S > , and CT> controllers
are automatically acknowledged and reset, thus the The following is a typical sequence for silencing,
< R > , < S > , and <T > controller alarms are dis- acknowledging and resetting the alarms using the
played steady on and the CC> communicator new Auxiliary Display group and the Alarm group switches.
alarms are displayed flashing. The <: C > communica- It is assumed that the <C > communicator is not
tor alarms (both the CRT and Auxiliary Display) can f?unctioning during this typical sequence.
be acknowledged either with the Auxiliary Display
Alarm Input Press Switch Switch Group
group’s Function Selector switches or with the CRT
1. Fault occurs 1. Silence AIa77il.
Display Function’s Acknowledge switch.
(alarm horn
sounds)
If the < C > communicator should fail ( c C > Section
Running light ofE), the < R > , c S > , and <T> con- (The alarm horn silences)
troller new alarms are displayed flashing to indicate to 2. R,S, or T Section Selector
the operator which alarms have occurred since the (Selects controller to be displayed)
<C> communicator failed. The <R>, <S>, and 3. Shift Function Selector
<T> controller alarms must be separately acknowl- 4. Exit Function Selector
edged by repeating the following Alarm Mode display (Selects the Mode Select state)
and acknowledge procedure for each controller. (“1” rotates through the display)
$TYP$ I Function Selector
Selection Press Switch Switch Group
1. Computer to 1. C,R,S, or T Section Selector (Selects the Alarm Mode: first unacknowl-
be displayed edged alarm drop no. is displayed flash-
(Corresponding light comes on)
ing)
2. Mode Select 1. Shift Function Selector 6. Shift Function Selector
State 2. Exat Function Selector 7. Next Function Selector
(“1” rotates through the display) (Acknowledges the alarm: the drop no.
changes to steady on)
3. Select 1. Type 1 (Alarm) Function Selector
Alarm mode
(If unacknowledged, the first new alarm 2. ~~otrea~ms 8. Reset Alarm
drop no. is displayed flashing)
(clears)
(If acknowledged, the latest alarm drop
no. is displayed steady on) (All acknowledged and cleared alarms are
deleted)
4. Acknowledge 1. Shift Function Selector
the alarm 2. Next Function Selector (Re eat steps 2 through 8 for each CR > , <S >, and
c ?p> controller)
(The alarm drop goes steady on)
4-3
GEK-83885 Mark IV SPEEDTRONIC” Gas Turbine Control Operator’s Manual
- Notes -
4-4
GE Drive Systems
Genefalflectric
Company
1501RoanokeBoulevard
Salem,Virginia
24153
(703)387-7000