Professional Documents
Culture Documents
Firestop Standard - Is.12458.1988 - 0
Firestop Standard - Is.12458.1988 - 0
,-.
: I
‘_/
-.
’ \
I .
.
-e -
@ Copyr@t 1989
Gr 2 June 1989
IS : 12458 - 1988
Indian Standard
METHOD OF
FIRE RESISTANCE TEST OF FIRESTOPS
0. FOREWORD
0.1 The Indian Standard was adopted by the horizontal and/or vertical stops for fire resistance
Bureau of Indian Standards on 14 October 1988, requires different procedure in view of its
after the draft finalized by the Fire Safety importance and hence the same has been
Sectional Committee had been approved by the covered in this standard.
Civil Engineering Division Council.
0.3 In reporting the results of a test or analysis
0.2 The method of fire resistance test of various made in accordance with this standard, if the
structures of buildings is covered in IS : 3809- final value, observed or calculated, is to be
1979*. The method of fire resistance test of rounded off, it shall be done in accordance
firestops intended for use in openings in fire with IS : Z-1960*.
resistance wall and/or floor-ceiling assemblies as
*Fire resistance test of structures (Jirst reuision ). *Rules for rounding off numerical values ( re&d ).
1
F------q
1%':12439-1999
rise -The mean deviation of furnace tempe-
8
- 1200 rature rise is given as a percentage by the
(-0 following expression:
L. 1100
ki!
is 1000
A-B
B
x 100
B
L 900 where
3 A = integral value of the average
I- 800
furnace temperature as a func-
:: tion of time, and
g 700
B = integral value of Z-- T, from the
5 600 equation defined in 5.1.1.
2
the penetrating items and are to be fitted closely area 0’25 m2 ) and dimensions of components o.f
above the thermocouples. The temperature lesser sizes should not be less than those provided
shall be measured: in 450 x 560 mm. Similarly, size 800 x 1 250
mm covers all sizes up to and including
a) at a minimum of one point on the throuah- 800 X 1250 mm ( 1 m’ area ) provided dimen-
penetration firestop-material surface-at sions of components are not less than those
the periphery of the test sample. provided in 800 X 1250 mm.
b) at least three points on the through-
4.2 Conditioning - The test specimen shall be
penetration firestop material surface
conditioned for a week.
approximately equidistant from a pene-
trating item or group of penetrating 4.2.1 The drying of the test specimen may be
items in the field of the firestop and the by natural or artificial means and a temperature
periphery. of 60°C should not be exceeded.
c) at a point on any frame installed around
the perimeter of the opening. 5. PROCEDURE AND RATING
4 at a point on the unexposed surface of 5.1 The firestop shall comply with the following
the wall or floor assembly at least 30 mm criteria for the specified rating period.
from any opening.
5.1.1 The sample shall be tested for the rating
4 at one point on each type of through- period and shall withstand fire test without per-
penetrating item. mitting the passage of flame on sustained
flaming for a duration of not more than 10
3.1.5 The temperatures are to be measured at seconds on the unexposed side of the test
intervals of 5 minutes or less until a reading sample; the transmission of heat to raise tempe-
exceeding 100°C has been obtained at any one rature measured by any thermocouple on the
point. Thererafter, the readings would be taken unexposed surfaces of firestop by not more than
at intervals not less than 5 minutes. 163°C above its inital temperature. At the end
of this test, the same sample shall be subjected
3.2 Pressure Conditions * to hose stream test within 10 minutes according
to the procedure given in 5.1.2 and shall not
3.2.1 An overall pressure difference of develop any opening that would permit a pro-
25 f 5 Pa ( 2’5 f 0’5 mm H,O ) shall exist in jection of water from the stream beyond unex-
the furnace during the evaluation period from posed side.
15 min onwards.
NOTE- The passage of flame is characterized by
3.2.2 The overall pressure shall be measured ignition of cotton, fibres pad ( 100 mm’ X 20 mm thick
and monitored at 100 mm from the underneath of mass 3-4 g conditioned at 1OO’C for half-an-hour ) at
a distance of 25 mm, Max.
surface for the horizontal specimen and at a
point located approximately at three-quarters 5.1.2 The stream is to be delivered through a
of the height of test specimen. 63 mm hose and discharged through a stand
pipe ( see IS : 903-1984* ) with water pressure
3.3 Testing Conditions - The testing equip- and duration of application as given in Table 2.
ment and test sample assembly are to be prot- The nozzle orifice is to be 6 m from the centre
ected from abnormal condition of wind and of the exposed surface of the test specimen and
weather. The ambient temperature at the stream shall be directed first at the middle and
beginning of the test shall lie within the range then at all other parts of the exposed face with
of 20 to 40%. all changes in directions being made slowly.
4. TEST SPECIMENS -
TABLE 2 PRESSURE AND DURATION-
4.1 Each type (;f firestop as described by the HOSE STREAM TEST
construction drswing types of material used
s&all be tested in a higher rating fire resisting PERIOD OF WATERPRESSURR DURATIONOF
wall or floor. The periphery of firestop shall be FIRETEST AT BA8E OB APPLICATION
NOZZLE SPERm'Ex-
not closer than 300 mm to the furnace edge. kPa
min PO~EDAREA
The penetrating items of the test sample should
be such that they extend 300 f 25 mm from >240<480 310 32
the exposed side and 900 f 25 mm from the > 120 < 240 210 16
unexposed side. The individual ends of these
> 9og 120 210 9’7
items shall be covered. The two sizes ( as
< 90 210 6’5
defined by openings ) given in 4.1.1 will cover
all ranges up to 1 m2.
4.1.1 The size 450 X 560 mm will cover all *Specification for fire hose delivery couplings branch
sizes up to and including 450 x 560 mm ( and pipe, nozzles and nozzle spanner ( third r&&n ).
3
IS:124!38-1988
6.1 The test report shall include the following b) Rating of each firestop,
information:
c) Name of the manufacturer and the trade-
a) A description of the assembly including name, and
fixing arrangement of firestop and draw-
ings showing the exact size of the d) Observation made during the test and
component and the location of firestops after furnace fire is extinguished.
‘3
4
BUREAU OF INDIAN STANDARDS
Headquarters:
Manak Bhavan, 9 Bahadnr Shah Zafar Marg, NEW DELHI 110002
Telephones: 3 3101 31,3 31 13 75 Telegrams: Manaksanstha
( Common to all Offices )
Branch O$cts:
2 63 48
‘Pushpak’, Nurmohamed Shaikh Marg, Khanpur, AHMADABAD 380001
{ 2 63 49
38 49 55
SPeenya Industrial Area, 1st Stage, Bangalore-Tumkur Road, BANGALORE 560058
{ 38 49 56
Gangotri Complex, 5th Floor, Bhadbhada Road, T. T. Nagar, BHOPAL 462003 6 67 16
Plot No. 82/83, Lewis Road, BHUBANESHWAR 751002 5 3.6 27
53/5 Ward No. 29, R.G. Barua Road, 5th By-lane, GUWAHATI 781003 3 31 77
5-8-56C, L.N. Gupta Marg ( Nampally Station Road ), HYDERABAD 500001 23 10 83
6 3471
R14 Yudhister Marg, C Scheme, JAIPUR 302005
{ 6 98 32
21 68 76
117/418 B Sarvodaya Nagar, KANPUR 208005
{ 21 82 92
Patliputra Industrial Estate, PATNA 800013 6 23 05
6 21 04
T.C. No. 14/1421, University P.O., Palayam, TRIVANDRUM 695034
6 21 17
*Sales Office in Calcutta is at 5 Chowringhee Approach, P.O. Princep Street, Calcutta 700072 27 68 00
TSales Office in Bombay is at Novelty Chambers, Grant Road, Bombay 400007 89 65 28
$Sales Office in Bangalore is at Unity Building, Narasimharaja Square, Bangalore 560002 223971