Max 6inch Non Metallic Pipe With LCI Sealant & Wrap Strips
Max 6inch Non Metallic Pipe With LCI Sealant & Wrap Strips
A
4B 4B 1
3
4D
4C
4D
3
A
Section A-A
1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/ m3 ) concrete. Except as footnoted in the
table under Item 4C, min thickness of concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any
min 6 in. (152 mm) thick hollow-core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete
Blocks*. Diam of opening to be min 1/8 in. (3.2 mm) to max 1-1/2 in. (38 mm) larger than outside diam of pipe or conduit.
See Concrete Blocks (CAZT) or Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of
manufacturers.
2. Steel Sleeve - (Optional, Not Shown) - Nom 5 in. (127 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe or nom 5 in.
(127 mm) diam (or smaller) No. 26 ga (0.022 in. or 0.56 mm thick) sheet steel sleeve with nom 2 in. wide square or circular
anchor flange spot welded to the sleeve at it\'s approx mid-height. Sleeve cast or grouted into min 4-1/2 in. (114 mm) thick floor
or wall assembly, flush with floor or wall surfaces.
3. Through Penetrant - One nonmetallic pipe or conduit to be installed eccentrically or concentrically within the firestop system.
Pipe or conduit to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of nonmetallic
pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) solid or cellular core Schedule 40 polyvinyl chloride
(PVC) pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 6 in. (152 mm) diam (or smaller) SDR 13.5 chlorinated polyvinyl
chloride (CPVC) pipe for use in closed (process or supply) piping systems.
C. Rigid Nonmetallic Conduit+ - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with
Article 347 of the National Electrical Code (NFPA 70).
D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 6 in. (152 mm) diam (or smaller) solid or cellular core Schedule 40
acrylonitrile butadiene styrene (ABS) pipe for use in closed (process or supply) or vented (drain, waste or vent) piping
systems.
E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 6 in. (152 mm) diam (or smaller) solid or cellular core Schedule 40 fire
retardant polypropylene (FRPP) pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
F. High Density Polyethylene (HDPE) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 HDPE pipe for use in closed
(process or supply) piping systems.
4. Firestop System - The firestop system shall consist of the following:
A. Packing Material - (Not Shown) - When required, min 4 pcf (64 kg/m3) mineral wool batt insulation compressed and
installed to the thickness specified in the table under Item 4C. Packing material to be recessed from top surface of floor or
both surfaces of wall as required to accommodate sealant (Item 4B).
ABS, ccABS 2 (51) 4-1/2 (114) BLU or BLU2 1 3 2 NA 1/4 (6) 1/2 (13)
ABS, ccABS 3 (76) 4-1/2 (114) RED, RED2 2 2 0 NA 1/4 (6) 1/2 (13)
ABS, ccABS 3 (76) 4-1/2 (114) BLU or BLU2 2 3 2 NA 1/4 (6) 1/2 (13)
ABS, ccABS 4 (102) 4-1/2 (114) RED, RED2 3 2 0 NA 1/4 (6) 1/2 (13)
ABS, ccABS 4 (102) 4-1/2 (114) BLU or BLU2 3 3 2 NA 1/4 (6) 1/2 (13)
RED, RED2,
ABS, ccABS 6 (152) 4-1/2 (114) 4* 2 2 4 (102) 1/2 (13) 1/4 (6)
BLU or BLU2
ABS, ccABS 6 (152) 4-1/2 (114) RED, RED2 3(a) 3 0 NA 1/2 (13) 3/8 (10)
ABS, ccABS, FRPP 6 (152) 4-1/2 (114) BLU or BLU2 3(a) 3 3 NA 1/2 (13) 3/8 (10)