Electrical Network

ETERNAL ENGINEERS GROUP


01007200959-01114911166

١
‫اﻟﺷﺑﻛﺎت اﻟﻛﻬرﺑﯾﺔ‬

‫اﻫم ﻣﯾزة ﻛﻬرﺑﺎﺋﯾﺔ‬


‫ﻧﻘل ﻛﻣﯾﺔ ﻛﺑﯾرة ﻣﻧﻬﺎ ﺑﺳﻬوﻟﺔ ﻟﻣﺳﺎﻓﺎت ﻛﺑﯾرة وﯾﺟب اﻟﻌﻠم ﺑﺄن اﻟﻛﻬرﺑﺎء ﺗﻣر‬
‫ ﻣراﺣل ﻣﻬﻣﺔ وﻫﻰ اﻟﺗوﻟﯾد واﻟﻧﻘل واﻟﺗوزﯾﻊ‬٣ ‫ب‬
→Generation(10-15) KV
→transmission(220-500) KV
→distribution(66-11)KV
(66-22)KV
voltage levels and their classification:
‫↓اﻟﻌزل‬
1. low voltage (0-1000)V (220-380-690)V
2. medium voltage.(1000-33)KV (3.3-6.6-11-
22.4-33)
3. high voltage (33-750)KV (66-132-220-500-750)
4. ultravoltage.>750KV (1000KV) ‫اﻛﺑر ﺟﻬد‬
demand factor
Not of all loads are on all the time all
together.

EαI²t E ‫اﻟطﺎﻗﺔ اﻟﺗﻲ ﺗﺗﺣﻣﻠﻬﺎ اﻟداﺋرة‬


Circuit breaker
1. protection
2. switching

٢
→in housing design C.B for saket of lighting or power loads
is minimum 16A.

Disadvantage of balance (3-Q)


1. increase in losses:
2. high current in one of the phases will cause
protection TRIP
3. unbalance cause high neutral current
design of distribution board for a group of motors
A. individual drive
one motor operate with no relation with other motors.
B. Group drives
Motors that must operates together and stop together.

Ist| group of motors =Ist| largest+DF ‫∑*ﻧﺣﺻل ﻋﻠﯾﻬﺎ ﻣن ﺟدول‬I|others rated

Ir| group =Ir| largest +DF*∑Ir others

p*746
Ir =
* p. f *220

p * 746
Ir =
 * RF * 3 * 380

(kva | st / HP)average *100 * p


Ir =
220

Or Ist=
3 * 380

IIKV Distribution substation


Kiosk ‫ﻛﺷك ﺗوزﯾﻊ‬
Small custmer

٣
- load ‹1.5 mvA
- feed with low voltage (380/220)V from distribution
- feed at low voltage

medium customer
-loads (1.5-5)MVA
-feed from IIKVfeeder (not dedicate) ‫ﯾﻐذي ﻣﺳﺗﻬﻠﻛﯾن اﺧرﯾن‬
-IIKV feeder feeds other custmers.
-custmer has to provide (11-0.4)KVtransformer
-transformer

Big customer
1. load 5 mva
2. fed by dedicated trans (11-0.4)kv
3. customer large motores loads high power may
promise(11-3.3)kvtrans

ex:
1. Hospital
2. Bigh Industrial Facilitier
3. Large Commercion Confer

Tow Types Of Supply


1. radial feeder
2. ring feeder

Distribution Boards
cu ‫وﻓﻰ ﻣﺻر‬cu ‫ ﻣن او‬busbar ‫ﯾﺻﻧﻊ‬
Single Line Diagram

٤
A one line digram engineering drawing showing the
elements of adist ribution system of show the rating of all
these elements and how they are interconnect

Load switch circuit loreaker relay


‫ﻓﻘط‬swiching ‫ﯾﻌﻣل‬ swiching ‫ﯾﻌﻣل‬ ‫ﯾﻌطﻰ اﺷﺎرة ﻓﻘط‬
‫وﯾﻔﺻل اذا ﺣدث ﺗﺳرﯾب‬ ‫وﯾﺣس ﺑﺎﻟﻌطل‬

Main functions of distribution board:


1. switching(on/off)
2. control
3. protection: all parts of an electric system must be
protected against abnormal fault condition
1-sensing
2-
switch off
3-
protection must be

selective.
Abnormal condition (faults) :
1. short circuit 2.over voltage
3.over load 4.earth leakage
5.under voltage 6.earth fault
short circuit

٥
‫‪I=V/Z‬‬
‫‪I=V/zero=α‬‬
‫↑↑‪P=I2R↑↑→heat‬‬

‫‪Over load:‬‬

‫‪ .١‬ﻣن اﻟﻣﻣﻛن ﺗﺧطﻲ ‪ demand factor‬ﻋﻧدﻣﺎ ﯾﻣﻛن ﺗﺷﻐﯾل اﻟﺗﻛﯾﯾﻔﺎت ﻛﻠﻬﺎ ﻓﻲ‬
‫وﻗت واﺣد‪.‬‬
‫‪ .٢‬ﺑﺎﻟﻧﺳﺑﺔ ﻟل ‪ water pump‬ﺗﺳﺣب ﺗﯾﺎر ﻋﺎﻟﻲ ﻋﻧدﻣﺎ ﯾﺗﺳرب ﺑداﺧﻠﻬﺎ‬
‫اﺗرﺑﺔ‪.‬‬

‫‪Under Voltage‬‬

‫·····························‬
‫)‪VR=VS-IZF(∆v‬‬
‫‪∆V=  5%‬‬

‫‪٦‬‬
Over Voltage
‫ اﺳﺑﺎب‬٣ ‫ﻟــ‬
1. Lighting ‫اﻟ ﺻواﻋق‬
2. swiching ‫اﻟﻔﺻل واﻟﺗوﺻﯾل‬
3. Excess Capacitance

*Swiching

DI 
U L =L
DT 
Ecess Capacitance
‫ ( و‬inductive load) ‫ ﻣﻌظم اﻟﺷﺑﻛﺎت‬.١
Lag←P.F
P.F ‫ ﻧﺿﻊ ﻣﻛﺛﻔﺎت ﻟﺗﺣﺳﯾن‬.٢
‫ ﺗﻛون ﻋﺎﻟﯾﺔ‬capacitare ‫ ﻋﻧد ﺣدوث ﻋطل او ﺗﺳرﯾب‬.٣

Earh Leakage
‫( ﯾؤدى اﻟﻰ‬Humidity & Heat) ‫ﺗﯾﺎر ﯾﺗﺳرب ﻣن اﻟﻣوﺻﻼت ﻓﻰ اﻻرض ﻧﺗﯾﺟﺔ‬
‫ وﺑﺎﻟﺗﺎﻟﻰ ﯾﺣدث ﺗﺳرﯾب ﺗﯾﺎر اﻟﻰ اﻻرض‬Deterioration in isulation ←
‫)ﺗدﻫور‬

٧
Small leakage currents due to portial failure of
insulation
Earth fault
Complete failure of insulation leads to live
conductors coming in fall contact with earth.

Switching devices
1. circuit breakers
2. laods switch
3. fuse(protection)
4. contactor
5. fuse switch

Circuit Breaker
1. switching
2. protection
1. moving contact :‫ﻋﺑﺎرة ﻋن ﺟزﺋﯾن‬
2. fixed contact
switching medium ‫ووﺳط ﻣﺣﺑط‬

operating mechanism
1. Low voltage circuit breaker.+
2. medium voltage circuit breaker.

٨
‫ ﺗﺣدث ﺷرارة وﯾﺟب اﻟﺗﻐﻠب ﻋﻠﯾﻬﺎ وﻫذا ﻫو‬2 contacts ‫ﻋﻧد ﻓﺻل‬
.C.B ‫اﻻﺧﺗﻼف ﺑﯾن اﻧواع‬
.(breaking capacity)&(rating)‫اﻟﻣﻔﺗﺎح ﯾﺗﻌرف ﺑﺷﯾﺋﯾن‬
Low voltage CB→
.air ‫وﺳط اﻟﻔﺻل‬

Types of low voltage C.B:


1. miniatureCB:rating (1-125)A
breaking
capcity(6,10,15,20,25)KA
2. molded caseCB:rating(16-1250)A
breaking
capcity(25,30,35,40,45,65,80)KA
3.air CB: rating (400-6300)A
breaking capcity 125KA
(I-t) ‫ﺗﻌﻣل ﻋﻠﻰ ﻣﻧﺣﻧﻰ‬LVC.B ‫وﺟﻣﯾﻊ‬

: ‫ﺗﻌﺗﻣد ﻓﻲ ﻋﻣﻠﻬﺎ ﻋﻠﻰ‬

1.(thermal/magnetic)trip

2.electronic unit trip


‫وﯾﺗم ﻣﻘﺎرﻧﺔ اﻟﺗﯾﺎر ﺑﺎﻟﺗﯾﺎر اﻟﻣﺻﻣم ﻋﻠﯾﻪ اﻟداﺋرة‬analysis ‫ﻣﻌدة اﻟﯾﻛﺗروﻧﯾﺔ ﺗﻌﻣل ﻟﻪ‬
3. micro processor trip
‫ﻋﻣﻠﯾﺔ ﺗﺣﻠﯾل داﺋم‬
→emergency supply system for importants loads

٩
one out of two method

1. each transformer is cabable of suppling all loads.


2. normal operation:
1.main C.B is closed .
2.main transformer fed all
loads
3.auxillary transformer C.B
open (stand by) .

emergency C.B ‫ﻋﻧدﻣﺎ ﯾﺣدث ﻋطل‬

1. main supply fails→main C.B open


2. auxillary C.B→closed
3. auxillary transformer→feeds all loads.

two out of three

١٠
Normal operation:
1. C.B closed feeds load of busbar1
2. C.B2closed feeds load of busbar2
3. C.B3open.
Emergency operation:
1. C.B1 open
2. C.B2 closed
3. C.B3 closed
Feeder 2 feeds emergency loads on busbar(1) and (2).

Stand by generation
(automatic transformer switch) ‫ﯾوﺟد‬

Two types of generator

١١
‫‪1. start and synchronizer‬‬
‫ﯾﺟب ان ﻧﺗرﻛﻪ ﻓﺗرة ﻟﻛﻲ ﯾﻌﻣل ﺗزاﻣن ﻣﻊ اﻻﺣﻣﺎل‬
‫‪2. runs ideal‬‬
‫ﻓﻲ اﻟﻣﻧﺷﺄت اﻟﻣﻬﻣﺔ ﯾﻔﺻل وﯾوﺻل وﯾﻛون ﻣﺗزاﻣن وﻣﺎ ﯾﺧﺳرﻩ اﻟﻣﺳﺗﻬﻠك ﻫو اﻟﻘدرة‬
‫اﻟﺿﺎﺋﻌﺔ‪٠‬‬

‫‪١٢‬‬
ELECTRICAL CABLES

ETERNAL ENGINEERS GROUP


01007200959-01114911166

١٣
‫اﻟﻛﺎﺑﻼت اﻟﻛﻬرﺑﯾﺔ‬

‫ﻧﺑذة ﺗﺎرﯾﺧﯾﺔ‬

‫‪ -١‬ﺗم اﺳﺗﺧدام اﻟﻛﺎﺑﻼت ﻓﻰ ﻧﻘل اﻟﻛﻬرﺑﺎء ﻋﺎم ‪ ١٨٩٠‬ﻋﻧدﻣﺎ اﺳﺗﺧدم ﻓراﻧﺗﻰ اﻟورق‬

‫اﻟﻣﺷرب ﻓﻰ ﻋزل اﻟﻣوﺻﻼت‪.‬‬

‫‪ -٢‬ﻫو ﺧﺷﺗﺎ دﺗر )‪ ( hachstadter‬ﻋﺎم‪١٩١٤‬اﺧﺗرع اﻟﺣﺟﺎب اﻟﻣﺻﻧوع ﻣن اﻟورق‬

‫اﻟﻣﻌدﻧﻰ واﻟﻣوﺿوع ﺣول اﻟﺳطﺢ اﻟﺧﺎرﺟﻰ ﻟﻠﻌزل ﻟﺟﻌل اﻟﻣﺟﺎل اﻟﻛﻬرﺑﻰ داﺧل اﻟﻌزل‬

‫ﻧﺻف ﻗطرى‪.‬‬

‫‪ -٣‬اﺧﺗرع اﻣﺎﻧﯾوﻟﻰ ‪ emmanueli‬اﻟﻛﺎﺑﻼت اﻟﻣﺿﻐوطﺔ ﺑﺎﻟزﯾت ﻟﻠﺗﻐﻠب ﻋﻠﻰ ﻣﺷﻛﻠﺔ‬

‫ﺗﻛون اﻟﻔراﻏﺎت ﻓﻰ اﻟﻌزل واﻟﺗﻰ ﻛﺎﻧت ﺗﺣد ﻣن ﻗﯾﻣﺔ اﻟﺟﻬد اﻟﻣﺳﺗﺧدم ﻓﻲ اﻟﻛﺎﺑﻼت‬

‫ﺑﺎﻟورق اﻟﻣﺷﺑﻊ‪.‬‬

‫‪ -٤‬اﺧﺗراع اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدم ﻓﻰ ﻧﻘل اﻟطﺎﻗﺔ اﻟﻛﻬرﺑﯾﺔ ﺗﺣت اﻟﻣﺎء ﺑﺎﺳﺗﺧدام اﻟﺗﯾﺎر‬

‫اﻟﻣﺳﺗﻣر ‪.‬‬

‫‪ -٥‬اﺧﺗراع اﻟﻣواد اﻟﺑﻠﻣرﯾﺔ اﻻﺻطﻧﺎﻋﯾﺔ وﺗطوﯾرﻫﺎ ﻛﻣواد ﻋزل ﻟﻠﻛﺎﺑﻼت ﺑدﻻ ﻣن اﻟورق‬

‫اﻟﻣﺷرب ﻣﻣﺎ أدى ﻟطﻔرة ﻫﺎﺋﻠﺔ ﻓﻰ ﺻﻧﺎﻋﺔ اﻟﻛﺎﺑﻼت‪.‬‬

‫‪ -٦‬ﺗطوﯾر ﺗﻘﻧﯾﺔ اﺳﺗﺧدام اﻟﻐﺎز اﻟﻣﺿﻐوط ﻛوﺳط ﻋﺎزل ﺑﯾن اﻟﻣوﺻل واﻟﻐﻼف‪.‬‬

‫ﺗﻌرﯾف اﻟﻛﺎﺑل‬

‫‪ -‬وﺳﯾﻠﺔ اﻟﻣواﺻﻼت ﻟﻠطﺎﻗﺔ اﻟﻛﻬرﺑﯾﺔ‪.‬‬

‫‪ -‬ﺗﺳﺗﺧدم ﻓﻰ ﻧﻘل اﻟﻘدرة ﻣن ﻣن أﻣﺎﻛن اﻟﺗوﻟﯾد اﻟﻰ ﻣﻧﺎطق اﻟﺗوزﯾﻊ‪.‬‬

‫‪١٤‬‬
‫اﻟﺧطوط ﻫواﺋﻰ‬ ‫اﻟﻛﺎﺑﻼت‬

‫‪-١‬ﯾﺷوﻩ ﺟﻣﺎل اﻟطﺑﯾﻌﻪ‪٠‬‬ ‫‪-١‬ﻻ ﯾﺷوﻩ ﺟﻣﺎل اﻟطﺑﯾﻌﻪ ‪.‬‬

‫‪-٢‬ﺳﻬوﻟﺔ اﻛﺗﺷﺎف اﻻﻋطﺎل ﺑﺎﻟﻌﯾن اﻟﻣﺟردﻩ‪٠‬‬ ‫‪-٢‬ﺻﻌوﺑﺔ اﻛﺗﺷﺎف اﻻﻋطﺎل‪.‬‬

‫‪-٣‬أﻗل ﺗﻛﻠﻔﻪ‪٠‬‬ ‫‪-٣‬أﻋﻠﻰ ﺗﻛﻠﻔﻪ‪.‬‬

‫‪-٤‬ﯾﺗﺄﺛر ﺑﻌواﻣل اﻟﺗﻌرﯾﻪ‪٠‬‬ ‫‪-٤‬ﻻ ﯾﺗﺄﺛر ﺑﻌواﻣل اﻟﺗﻌرﯾﻪ‪.‬‬

‫‪-٥‬ﺳﻬوﻟﺔ ﺗﺻﻠﯾﺢ اﻻﻋطﺎل‪٠‬‬ ‫‪-٥‬ﺻﻌوﺑﺔ ﺗﺻﻠﯾﺢ اﻻﻋطﺎل‪.‬‬

‫‪-٦‬ﻓﻰ اﻣرﯾﻛﺎ ﯾﺳﺗﺧدﻣوﻧﻬﺎ ﺑﻧﺳﺑﺔ ‪٠%٩٩‬‬ ‫‪-٦‬ﺑﻧﺳﺑﺔ ‪%١‬اﻻ اﻧﻬﺎ ﻓﻰ ﺗزاﯾد‪..‬‬

‫‪-٧‬ﻋﺎم‪1993‬اﻟﺗﻛﻠﻔﻪ =‪1/10‬ﻣن اﻟﻛﺎﺑﻼت‪٠‬‬ ‫‪-٧‬اﻟﺗﻛﻠﻔﻪ=‪10‬اﺿﻌﺎف اﻟﺧطوط اﻟﻬواﺋﯾﻪ‬

‫‪-٨‬ﻋﺎم ‪٠(5/1 ) 2000‬‬ ‫ﻋﺎم‪.1993‬‬

‫‪-٨‬ﻋﺎم‪(1/5)2000‬‬

‫ﻋواﻣل ﺳﺎﻋدت ﻋﻠﻰ اﻧﺗﺷﺎر اﻟﻛﺎﺑﻼت‬

‫‪ -١‬اﻟﺗطور اﻟواﺿﺢ ﻓﻰ ﺗﻛﻧوﻟوﺟﯾﺎ اﻟﻛﺎﺑﻼت ﻧﺗﯾﺟﻪ ﻻﺳﺗﺧدام اﻟﻛﺎﺑﻼت ﺑﺎﻟﻌوازل اﻟﺑﻠﻣرﯾﻪ‪.‬‬

‫‪ -٢‬اﻟﺗﻐﯾر ﻓﻰ ﻫﯾﻛل ﺻﻧﺎﻋﻪ اﻟﻘوى اﻟﻛﻬرﺑﯾﻪ ﺑﺎﻟﺗﺣول ﻣن ان ﺗﻛون ﺻﻧﺎﻋﻪ اﻟﻛﻬرﺑﺎء‬

‫ﺗﺎﺑﻌﻪ ﻟﻠدوﻟﻪ اﻟﻰ ان ﺗﻛون ﻣﻣﻠوﻛﻪ ﻟﻠﻘطﺎع اﻟﺧﺎص‪.‬‬

‫‪ -٣‬ﺗﻧﺎﻣﻰ اﻟوﻋﻰ ﺑﺎﻻﻫﺗﻣﺎم ﺑﺎﻟﺑﯾﺋﻪ وﺣﻣﺎﯾﺗﻬﺎ‪.‬‬

‫ﻣﻣﯾزات اﻟﻛﺎﺑﻼت اﻟﻛﻬرﺑﯾﻪ ﺑﺎﻟﻧﺳﺑﻪ ﻟﻠﺧطوط اﻟﻬواﺋﯾﻪ‬

‫‪١٥‬‬
‫‪ -١‬ﻻ ﺗﺗﻌرض اﻟﻛﺎﺑﻼت اﻟﻣدﻓوﻧﻪ ﺗﺣت اﻻرض ﻟﻠﺗﻐﯾرات اﻟﺟوﯾﻪ واﻟﻌواﻣل اﻟطﺑﯾﻌﯾﻪ‬

‫ﻛﺎﻟرﯾﺎح وﺗراﻛم اﻟﺟﻠﯾد واﻟﺗﻠوث وﺑﺎﻟﺗﺎﻟﻰ ﯾزﯾد ﻋﻣرﻫﺎ اﻻﻓﺗراﺿﻰ‪.‬‬

‫‪ -٢‬ﻗﻠﺔ ﺗﻌرض اﻟﻛﺎﺑﻼت ﻟﻌﻣﻠﯾﺎت اﻟﺗﺧرﯾب‪.‬‬

‫‪ -٣‬ﯾﻣﻛن اﺳﺗﺧدام اﻟﻛﺎﺑﻼت ﻓﻰ رﺑط اﻟﺷﺑﻛﺎت اﻟﻛﻬرﺑﯾﻪ ﻋﺑر اﻻﻧﻬﺎر واﻟﺑﺣﺎر واﻟﻣﻣرات‬

‫اﻟﻣﺎﺋﯾﻪ وﻻ ﯾﻣﻛن اﺳﺗﺧدام اﻟﺧطوط اﻟﻬواﺋﯾﻪ ﻓﻰ ﺗﻠك اﻟﺣﺎﻟﻪ‪.‬‬

‫ﻣﻛوﻧﺎت ﻛﺎﺑﻼت اﻟﻘوى‬

‫‪ -١‬ﻣوﺻل ﻣﻌدﻧﻰ ‪.CONDUCTOR‬‬

‫‪ -٢‬ﻋزل اﻟﻛﺎﺑل ‪.CABLE INSULATION‬‬

‫‪ -٣‬ﺣﺟﺎب اﻟﻣوﺻل ‪.CONDUCTOR SHIELD‬‬

‫‪ -٤‬ﻏﻼف اﻟﻌزل ‪.INSULATION SHIELD‬‬

‫‪ -٥‬اﻟﻐﻼف اﻟﻣﻌدﻧﻲ ‪.METALLIC SHEATH‬‬

‫‪ -٦‬اﻟﻐﻼف اﻟوﻗﺎﺋﻲ ‪.SHEATH COVER‬‬

‫‪ -٧‬اﻟدرع ‪.ARMOUR‬‬

‫‪-١‬اﻟﻣوﺻل اﻟﻣﻌدﻧﻰ ‪:CONDUCTOR‬‬

‫ﯾﺻﻧﻊ ﻣن ﻣﻌدن ذات ﻣﻘﺎوﻣﺔ ﻛﻬرﺑﯾﺔ ﻣﻧﺧﻔﺿﺔ وﯾﻘوم ﻫذا اﻟﻣوﺻل ﺑدور ﺣﻣل وﺗوﺻﯾل اﻟﺗﯾﺎر‬

‫اﻟﻛﻬرﺑﻲ واﻟﻣواد اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﺗﺻﻧﯾﻌﻪ اﻟﻧﺣﺎس واﻻﻟوﻣﻧﯾزم‪.‬‬

‫‪ -٢‬ﻋزل اﻟﻛﺎﺑل‪:CABLE INSULATION‬‬

‫‪١٦‬‬
‫ﯾﺻﻧﻊ ﻣن ﻣﺎدة ﻋﺎزﻟﺔ ﻛﻬرﺑﯾﺎ ‪.DIELECTRIC‬‬

‫ﻣﻬﻣﺗﺔ ‪ :‬ﻋزل اﻟﻣوﺻل اﻟﻣﻌدﻧﻰ اﻟذى ﯾﺣﻣل اﻟطﺎﻗﺔ اﻟﻛﻬرﺑﯾﺔ‪.‬‬

‫ﻣﻧﻊ ﺧطر اﻟﺗوﺻﯾل ﺑﯾن اﻟﻣوﺻل اﻟﻛﻬرﺑﻲ وأي ﻋﻧﺻر ﻣﺣﯾط ﺑﻪ‪.‬‬

‫ﻣواد ﺗﺻﻧﯾﻌﻪ‪ :‬اﻟﻌوازل اﻟورﻗﯾﻪ واﻟﻌوازل اﻟﺑﻠﻣرﯾﺔ‪.‬‬

‫‪ -٣‬ﺣﺟﺎب اﻟوﺻل ‪CONDUCTOR SHIELD‬‬

‫‪ -‬ﯾﺳﻣﻰ أﺣﯾﺎﻧﺎ ﺑﺷﺑﻛﺔ اﻟﻣوﺻل‪. CONDUCTOR SCREEN‬‬

‫‪ -‬طﺑﻘﺔ رﻗﯾﻘﺔ ﺗﺻﻧﻊ ﻣن ﻣﺎدة ﺷﺑﻪ ﻣوﺻﻠﻪ‪.SEMI CONDUCTOR LAYER‬‬

‫‪-‬ﺗوﺿﻊ ﺑﯾن اﻟﻣوﺻل واﻟﻌزل‪.‬‬

‫‪ -‬اﻟﻐرض اﻻﺳﺎﺳﻲ ﻫو اﻟﺗﻘﻠﯾل ﻣن ﻗﯾﻣﺔ اﻟﻣﺟﺎل اﻟﻛﻬرﺑﻲ ﻋﻠﻰ اﻟﺳطﺢ اﻟﻣﺷﺗرك ﺑﯾن اﻟﻣوﺻل‬

‫واﻟﻌزل واﻟذى ﻗد ﯾؤدي اﻟﻲ اﻧﻬﯾﺎر اﻟﻌزل ﻓﻰ ﺑﻌض اﻻﺣﯾﺎن‪.‬‬

‫`‪-‬ﻋﻧد اﺳﺗﺧدام اﻟﻛﺎﺑﻼت ال ‪STRANDED‬واﺳﺗﺧدام اﻟﻌوازل اﻟورﻗﯾﺔ و اﻟزﯾﺗﯾﺔ ﺗﺳﺗﺧدم‬

‫طﺑﻘﺔ ﻣن اﻟورق اﻟﻣﻣﻌدن ‪ METALLIZED PAPER‬أو اﻟورق اﻟﺷﺑﻊ ﺑﺎﻟﻛرﺑون‬

‫‪.CARBON PAPER‬‬

‫وﻓﻰ ﺣﺎﻟﺔ اﺳﺗﺧدام اﻟﻌوازل اﻟﺑﻠﻣرﯾﺔ ﻫﻧﺎك طرﯾﻘﺗﺎن‪:‬‬

‫‪ -١‬ﻟف اﻟﻣوﺻل ﺑﺷرﯾط ﻣن اﻟﻘﻣﺎش أو اﻟﺑﻼﺳﺗﯾك اﻟﻣﺷﺑﻊ ﺑﺎﻟﻛرﺑون وﺗﺳﺗﺧدم ﻫذﻩ اﻟطرﯾﺔ‬

‫ﻓﻰ ﻛﺎﺑﻼت اﻟﺟﻬد اﻟﻣﻧﺧﻔض‪.‬‬

‫‪ -٢‬وﺿﻊ طﺑﻘﺔ ﻣن اﻟﻣﺎدة ﺷﺑﻪ اﻟﻣوﺻﻠﻪ ﻋل اﻟﻣوﺻل اﺛﻧﺎء ﻋﻣﻠﯾﺔ ﺑث اﻟﻌزل‬

‫)‪ (EXTRUSION‬وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﺗﺻﻧﻊ ﻣن ﻣواد ﺑﻠﻣرﯾﺔ ﺧﺎﺻﺔ ﻣﺛل‬

‫‪١٧‬‬
‫‪CARBON FIELD ETHYLVINYL ACETATE-EVA‬ا وﻣﻘﺎوﻣﺗﻬﺎ‬

‫‪ ١٠٠٠٠٠ -١٠٠٠٠‬أوم وﺗﺳﺗﺧدم ﻫذﻩ اﻟطرﯾﻪ ﻓﻰ ﻛﺎﺑﻼت اﻟﺟﻬد اﻟﻣﺗوﺳط واﻟﻌﺎﻟﻰ‪.‬‬

‫‪ -٤‬ﻏﻼف اﻟﻌزل ‪INSULATION SHIELD‬‬

‫ﯾﺳﺗﺧدم ﻫذا اﻟﻐﻼف ﻓﻰ ﺟﻣﯾﻊ اﻧواع اﻟﻛﺎﺑﻼت ﺳواء ذات اﻟﻌوازل اﻟورﻗﯾﺔ أو اﻟﺑﻠﻣرﯾﺔ وان‬

‫اﺧﺗﻠف اﻟﺗﺻﻣﯾم ﻓﻰ ﻛل ﺣﺎﻟﺔ وﻣﻬﻣﺗﻪ‪:‬‬

‫‪ -‬ﺿﻣﺎن اﻻﺣﺗﻔﺎظ ﺑﺎﻟﻌزل داﺧل اﻟﻛﺎﺑل‪.‬‬

‫‪ -‬ﺗوﻓﯾر ﻣﺟﺎل داﺋرى ﻣﺗﺳﺎوي اﻟﺗوزﯾﻊ ‪SYMMETRICAL‬ﻟﻠﻣﺟﺎل اﻟﻛﻬرﺑﻰ داﺧل‬

‫اﻟﻌزل وﺑﺎﻟﺗﺎﻟﻲ ﺗﻘﻠﯾل ﺣدوث ﺗﻔرﯾﻎ ﻛﻬرﺑﻲ ﻋﻠﻲ اﻟﺳطﺢ ‪SURFACE‬‬

‫‪DISCHARGES‬وذﻟك ﺑﺎﻟﺗﺧﻠص ﻣن اﻻﺟﻬﺎدات اﻟﻛﻬرﺑﯾﺔ اﻟﻣﻣﺎﺳﯾﺔ واﻟطوﻟﯾﺔ‪.‬‬

‫‪ -‬اﻟﺗﻘﻠﯾل ﻣن ﺧطر اﻟﺻدﻣﺔ اﻟﻛﻬرﺑﯾﺔ وذﻟك ﺑﺗﺄرﯾض ﻏﻼف اﻟﻌزل ﺟﯾدا‪.‬‬

‫‪ -‬اﻟﺣد ﻣن اﻟﺗداﺧل ﻣﻊ ﻣوﺟﺎت اﻟرادﯾو‪.‬‬

‫‪ -٥‬اﻟﻐﻼف اﻟﻣﻌدﻧﻰ ‪METALLIC SHEATH‬‬

‫ﯾﺳﺗﺧدم ﻟﺣﻣﺎﯾﺔ اﻟﻛﺑل ﻣن ﺗﺳرب اﻟرطوﺑﻪ اﻟﻰ داﺧﻠﻪ وﯾﺳﺗﺧدم ﻓﻰ ﻛﺎﺑﻼت اﻟﻌوازل اﻟورﻗﯾﻪ‬

‫أواﻟﻌوازل اﻟﺑﻠﻣرﯾﻪ ﻋﻠﻰ ﺣد ﺳواء وﯾﻘوم اﻟﻐﻼف ﺑﺣﻣﺎﯾﺔ اﻟﻛﺎﺑﻼت ﺧﺎﺻﺔ ﻛﺎﺑﻼت اﻟﻌوازل‬

‫اﻟورﻗﯾﻪ ﻣن اى ﺻدﻣﺎت ﻣﯾﻛﺎﻧﯾﻛﯾﻪ‬

‫ﻛﺎن اﻟﻐﻼف اﻟﻣﻌدﻧﻰ ﻟﻠﻛﺎﺑﻼت ﯾﺻﻧﻊ ﻣن اﻟرﺻﺎص ﻓﻰ اﻟﻣﺎﺿﻰ اﻻ ان اﻻﻟوﻣﻧﯾوم ﻗد ﺣل‬

‫ﻣﺣل اﻟرﺻﺎص ﻓﻰ اﻟﻛﺎﺑﻼت اﻟﺣدﯾﺛﻪ ﻻن اﻻﻟوﻣﻧﯾوم ﻟﻪ ﻣﻣﯾزات ﻣﻘﺎرﻧﺔ ﺑﺎﻟرﺻﺎص ﻣﻧﻬﺎ ﻗﻠﺔ‬

‫اﻟوزن ورﺧص اﻟﺛﻣن وﺗوﺻﯾﻠﯾﻪ ﻛﻬرﺑﯾﻪ ﺟﯾدﻩ ﺑﺎﻻﺿﺎﻓﻪ ﻟﻣﻣﯾزات ﻣﯾﻛﺎﻧﯾﻛﯾﻪ اﺧرى اﻫﻣﻬﺎ ان‬

‫اﻻﻟوﻣﻧﯾوم ﻻ ﯾﺗﺄﺛر ﺑﺎﻻﻫﺗ اززات اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ ﻣﺛل اﻟﺗﻰ ﻗد ﺗﺗواﺟد ﻋﻠﻰ اﻟﻛﺑﺎرى أو ﺑﺟوار اﻟﺳﻛك‬

‫‪١٨‬‬
‫‪EARTHED METALLIC‬‬ ‫اﻟﺣدﯾدﯾﻪ وﯾﺳﺗﺧدم اﻟﻐﻼف ﻛﺷﺑﻛﻪ ﻣﻌدﻧﯾﻪ ﻣؤرﺿﻪ‬

‫)‪(SCREEN‬ﻻﺑد ﻣن ﺗﺻﻣﯾﻣﻬﺎ ﻟﺗﻛون ﻗﺎدرﻩ ﻋﻠﻰ ﺣﻣل ﺗﯾﺎر اﻟﺧطﺄ أﯾﺿﺎ‪.‬‬

‫‪-٦‬اﻟﻐﻼف اﻟوﻗﺎﺋﻰ ‪SHEATH COVER‬‬

‫ﻣن ﻋﯾوب اﻻﻟوﻣﻧﯾوم ﺳﻬوﻟﻪ ﺗﻌرﺿﻪ ﻟﻼﺗﺣﺎد اﻟﻛﯾﻣﺎﺋﻰ وﻧﺗﯾﺟﻪ ﺗﺳﺗﺧدم طﺑﻘﻪ اﺧرى ﻣن ﻣﺎدﻩ‬

‫ﻛﻠورﯾد اﻟﺑوﻟﯾﻔﯾﻧﺎﯾل ‪PVC‬ﻋﺎﻟﻰ اﻟﺟودة وﻗد ﺗﺳﺗﺧدم اﯾﺿﺎ ﻣﺎدﻩ اﻟﺑوﻟﻰ اﯾﺛﻠﯾن ﻋﺎﻟﻰ اﻟﻛﺛﺎﻓﻪ‬

‫‪HDPE‬ﻓﻰ ﺣﺎﻟﻪ ﻛﺎﺑﻼت اﻟﺟﻬد اﻟزاﺋد‪EHV‬وﻟﺣﻣﺎﯾﻪ اﻟﻐﻼف اﻟﻣﻌدﻧﻰ ﻣن اﻟﺗﺎﻛل ﻓﻰ ﺣﺎﻟﻪ ﺗﻠف‬

‫اﻟﻐﻼف اﻟوﻗﺎﺋﻰ وﺗﺳﺗﺧدم طﺑﻘﻪ اﺿﺎﻓﯾﻪ ﻣن اﻟورق واﻟﺟوت اﻟﻣﺷﺑﻊ ﺑﺎﻟﺑﯾﺗوﻣﯾن اﻟﻣﺿﺎف اﻟﯾﻪ‬

‫ﻣﺎدﻩ ﻟﻣﻧﻊ اﻟﺗﺎﻛل ﺑﯾن اﻟﻐﻼف اﻟﻣﻌدﻧﻰ واﻟﻐﻼف اﻟوﻗﺎﺋﻰ‪.‬‬

‫‪-٧‬اﻟدرع‪ARMOUR‬‬

‫اﻟﻐرض ﻣن اﻟدرع ﻫو ﺗوﻓﯾر اﻟﺣﻣﺎﯾﻪ اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ ﻟﻠﻛﺎﺑل وﻋﻣوﻣﺎ ﻛﺎﺑﻼت اﻻﻏﻠﻔﻪ اﻟﻣﻌدﻧﯾﻪ‬

‫اﻟﻣﺻﻧوﻋﻪ ﻣن اﻻﻟوﻣﻧﯾوم ﻻ ﺗﺣﺗﺎج ﻋﺎدﻩ اﻟﻰ طﺑﻘﻪ ﺗدرﯾﻊ ﻧظ ار ﻟﻠﺧﺻﺎﺋص اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ اﻟﺟﯾدﻩ‬

‫ﻟﻼﻟوﻣﻧﯾوم ‪.‬‬

‫اﻣﺎ ﻛﺎﺑﻼت اﻟﺗﯾﺎر اﻟﻣﺗﻐﯾر ﺑﺎﻟﻣوﺻل اﻟﻣﻧﻔرد واﻟﻐﻼف اﻟﻣﻌدﻧﻰ اﻟﻣﺻﻧوع ﻣن اﻟرﺻﺎص ﻓﺗزود‬

‫ﺑدرع ﻣﺻﻧوع ﻣن ﻣﺎدﻩ ﻏﯾر ﻣﻐﻧﺎطﯾﺳﯾﻪ وﻫﻰ ﻣرﺗﻔﻌﻪ اﻟﺛﻣن ﻧﺳﺑﯾﺎ ‪.‬‬

‫وﻋﺎدﻩ ﻣﺎ ﺗزود اﻟﻛﺎﺑﻼت ﺑطﺑﻘﻪ ﻣﺑطﻧﻪ ﺗﺣت اﻟدرع وﺗﺗﻛون اﻟطﺑﻘﻪ ﻣن ﻣواد ﻟﯾﻔﯾﻪ او ﻣن ﻣﺎدﻩ‬

‫ﻛﻠورﯾد اﻟﺑوﻟﯾﻔﯾﻧﺎﯾل ﻋﻠﻰ ﻫﯾﺋﻪ ﺷراﺋط ﻣﻠﻔوﻓﻪ او طﺑﻘﻪ ﻣﺑﺛوﻗﻪ‪.‬‬

‫وﻣﻌظم ﻛﺎﺑﻼت اﻟﻘوى ﺑﺎﻟﻣوﺻﻼت اﻟﻣﺗﻌددة ‪MULTICORE CABLES‬‬

‫‪١٩‬‬
‫ﯾﺗم ﺗوﻓﯾر اﻟﺣﻣﺎﯾﻪ اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ ﻟﻬﺎ ﻋن طرﯾق دروع ﻟﻬﺎ أﺷﻛﺎل ﻣﺗﻌددﻩ ﻣﻧﻬﺎ ﻣﺎ ﯾﻠﻰ‪:‬‬

‫ﺷراﺋط ﻣن اﻟﺻﻠب ﺗﻠف ﺣول اﻟطﺑﻘﻪ اﻟﻣﺑطﻧﻪ وﯾﺳﺗﺧدم ﻋﺎدﻩ ﺷرﯾطﺎن ﻣﺗداﺧﻼن ﻟﺿﻣﺎن‬

‫اﻟﺗﻐطﯾﻪ اﻟﻛﺎﻣﻠﻪ ﻟﻠﻛﺎﺑل‪.‬‬

‫‪ -١‬أﺳﻼك ﻣن اﻟﺻﻠب اﻟﻣﺟﻠﻔن وﺗﻠف ﺣول اﻟﻛﺎﺑل وﺗﺗﻛون ﻣن طﺑﻘﻪ او طﺑﻘﺗﯾن ‪.‬‬

‫‪ -٢‬اﺳﻼك او ﺷراﺋﺢ ﻣن اﻻﻟوﻣﻧﯾوم ﺗﺳﺗﺧدم ﻋﺎدﻩ ﻓﻰ اﻟﻛﺎﺑﻼت ﺑﺎﻟﻌوازل اﻟﺑﻠﻣرﯾﻪ‬

‫ﺗﺻﻧﯾف اﻟﻛﺎﺑﻼت ﻣن ﺣﯾث ﻣﺎدة اﻟﻌزل اﻟﻣﺳﺗﺧدﻣﺔ‬

‫ﻛﺎﺑﻼت ﻣﻌزوﻟﺔ ﺑﺎﻟورق اﻟﻣﺷﺑﻊ ﺑﺎﻟزﯾت ) ﻛﺎﺑﻼت زﯾﺗﻰ ( ‪.‬‬

‫‪ .١‬ﻛﺎﺑﻼت ﻣﻌزوﻟﺔ ﺑﻣﺎدة ال ‪ ) P . V . C‬اﻟﺑوﻟﻰ ﻓﯾﻧﯾل ﻛﻠوراﯾد ( ‪.‬‬

‫‪ .٢‬ﻛﺎﺑﻼت ﻣﻌزوﻟﺔ ﺑﻣﺎدة اﻟﺑوﻟﻰ إﯾﺛﻠﯾن اﻟﻣﺗﺷﺎﺑك ] ‪ [ X . L . P . E‬ﻛروس ﻟﯾﻧﻛد ﺑوﻟﻲ‬

‫إﯾﺛﻠﯾن‪.‬‬

‫‪ .٣‬ﻛﺎﺑﻼت ﻣﻌزوﻟﺔ ﺑﻣﺎدة اﻟﺑوﻟﻰ إﯾﺛﻠﯾن ] ‪. [ P . E‬‬

‫‪ .٤‬ﻛﺎﺑﻼت ﻣﻌزوﻟﺔ ﺑﻣﺎدة اﻟﺑوﻟﻰ إﯾﺛﻠﯾن اﻟﻣطﺎطﻲ ] ‪. [ E . P . R‬‬

‫و ﻣﻣﺎ ﺳﺑق ﯾﺗﺿﺢ ﻟﻧﺎ أن اﻟﻛﺎﺑﻼت ﺗﺳﻣﻰ ﺑﺎﺳم ﻣﺎدة اﻟﻌزل اﻟﻣﺳﺗﺧدﻣﺔ ﻣﻣﺎ ﯾدل ﻋﻠـﻰ ﻣـدى‬

‫أﻫﻣﯾﺔ اﻟﻌزل ﻓﻰ ﺻﻧﺎﻋﺔ اﻟﻛﺎﺑﻼت وﻫـو أﻫـم ﻣﻛوﻧـﺎت اﻟﻛﺎﺑـل وﻧظـ ار ﻟﻬـذﻩ اﻷﻫﻣﯾـﺔ ﻓﺈﻧـﻪ ﯾﺟـب أن‬

‫ﺗﺗ ـواﻓر ﻓــﻰ ﻣــﺎدة اﻟﻌــزل ﺑﻌــض اﻟﻣواﺻــﻔﺎت ﻣــﻊ اﻷﺧــذ ﻓــﻰ اﻻﻋﺗﺑــﺎر أﻧــﻪ ﻣــن اﻟﺻــﻌب ﺗ ـواﻓر ﻛــل‬

‫ﻣواﺻﻔﺎت وﺧﺻﺎﺋص اﻟﻌزل اﻟﺟﯾد ﻓﻰ ﻣﺎدة واﺣدة ‪.‬‬

‫ﺧﺻﺎﺋص اﻟﻣـﺎدة اﻟﻌـﺎزﻟــﺔ‬

‫‪ (١‬أن ﺗﻛون ﻟﻬﺎ ﻣﻘﺎوﻣﺔ ﻧوﻋﯾﺔ ﻋﺎﻟﯾﺔ ‪.‬‬

‫‪ (٢‬أن ﯾﻛون ﻟﻬﺎ ﺟﻬد اﻧﻛﺳﺎر ﻋﺎﻟﻲ ‪.‬‬

‫‪٢٠‬‬
‫‪ (٣‬أﻻ ﺗﻘﺑل اﻣﺗﺻﺎص اﻟرطوﺑﺔ ﻣن اﻟوﺳط اﻟﻣﺣﯾط ﺑﻬﺎ ‪.‬‬

‫‪ (٤‬ﻻ ﺗﺗﻔﺎﻋل ﻣﻊ اﻷﺣﻣﺎض واﻟﻘﻠوﯾﺎت اﻟﻣوﺟودة ﺑﺎﻟﺗرﺑﺔ ‪.‬‬

‫‪ (٥‬أن ﺗﻛون ﻟﻬﺎ ﺧﺎﺻﯾﺔ اﻟﺻﻼﺑﺔ و اﻟﻣروﻧﺔ ﻣﻌﺎً ‪.‬‬

‫‪ (٦‬ﻻ ﺗﺗﺄﺛر أو ﺗﺗﻐﯾر ﻣﻛوﻧﺎﺗﻬﺎ ﺑﺎرﺗﻔﺎع درﺟﺔ اﻟﺣرارة اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎر اﻟﺣﻣل اﻟﻌﺎدي أو أﻗﺻﻰ‬

‫ﺣﻣل أو اﻟﺣرارة اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎر اﻟﻘﺻر ‪.‬‬

‫‪ (٧‬ﻻ ﺗﻘﺑل ﺳرﯾﺎن اﻟﺣرﯾق ‪.‬‬

‫‪ (٨‬أﻗل ﻓﻘد ﻛﻬرﺑﺎﺋﻰ ﻣﻣﻛن أﺛﻧﺎء اﻟﺗﺷﻐﯾل ‪.‬‬

‫أﺳﻣﻰ ﺑﯾن اﻟﻣوﺻﻼت ‪.‬‬


‫ِ‬ ‫‪ (٩‬ﺿﻣﺎن ﺣﻣل اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻲ ﺑﺄﻣﺎن ﺣﺗﻰ أﻗﺻﻰ ﺟﻬد‬

‫أﻧواع اﻟﻣــــــواد اﻟﻌﺎزﻟــــﺔ‬

‫‪ .١‬اﻟﺑوﻟﻰ ﻓﯾﻧﯾل ﻛﻠوراﯾد ‪.‬‬

‫‪ .٢‬اﻟﺑوﻟﻰ إﯾﺛﻠﯾن ‪.‬‬

‫‪ .٣‬اﻟﺑوﻟﻰ إﯾﺛﻠﯾن اﻟﻣﺗﺷﺎﺑك ‪.‬‬

‫‪ .٤‬اﻟﺑوﻟﻰ إﯾﺛﻠﯾن اﻟﻣطﺎطﻰ ‪.‬‬

‫‪ .٥‬اﻟورق اﻟﻣﺷﺑﻊ ﺑﺎﻟزﯾت ‪.‬‬

‫‪ .٦‬اﻟﻣطﺎط ‪.‬‬

‫‪ .٧‬اﻟﺣرﯾر واﻟﻘطن ‪.‬‬

‫‪ .٨‬اﻟورﻧﯾش ‪.‬‬

‫‪ .٩‬اﻟﺻﻣﻎ اﻟﻬﻧدى ‪.‬‬

‫‪٢١‬‬
‫ﻫذا ﺑﺎﻹﺿﺎﻓﺔ اﻟﻰ ﺑﻌض اﻟﻣواد اﻷﺧرى ‪.‬‬

‫وﻟﻣﺎ ﻛﺎن ﻧﺷﺎط ﺷرﻛﺎت اﻟﺗوزﯾﻊ ﻫو ﺗوﺻﯾل اﻟﺗﯾﺎر اﻟﻰ اﻟﻣﺷﺗرﻛﯾن ﻟﻠﺟﻬود اﻟﻣﺗوﺳطﺔ ‪١١، ٢٢‬‬

‫ك‪.‬ف واﻟﻣﻧﺧﻔض ‪ ٣٨٠/٢٢٠‬ﻓوﻟت اﻟﻰ ﺟﺎﻧب أن اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﻧطﺎق ﻋﻣل اﻟﺷرﻛﺔ‬

‫ﻫﻰ‬

‫‪ .١‬ﻛﺎﺑﻼت ﺟﻬد ﻣﻧﺧﻔض ‪ P . V . C‬ﺑوﻟﻲ ﻓﯾﻧﯾل ﻛﻠوراﯾد ‪.‬‬

‫‪ .٢‬ﻛﺎﺑﻼت ﺟﻬد ﻣﻧﺧﻔض ﻣﻌزوﻟﺔ ﺑﺎﻟورق اﻟﻣﺷﺑﻊ ﺑﺎﻟزﯾت ) زﯾﺗﻲ ( ‪.‬‬

‫‪ .٣‬ﻛﺎﺑﻼت ﺟﻬد ﻣﻧﺧﻔض ﻣﻌزوﻟﺔ ﺑﻣﺎدة ‪X . L . P . E‬‬

‫‪ .٤‬ﻛﺎﺑﻼت ﺟﻬد ﻣﺗوﺳط ﻣﻌزوﻟﺔ ﺑﺎﻟورق اﻟﻣﺷﺑﻊ ﺑﺎﻟزﯾت ) زﯾﺗﻲ ( ‪.‬‬

‫‪ .٥‬ﻛﺎﺑﻼت ﺟﻬد ﻣﺗوﺳط ﻣﻌزوﻟﺔ ﺑﻣﺎدة ‪. X . L . P . E‬‬

‫وﺳﯾﺗم ﻋﻣل ﺷرح واﻓﻰ ﻟﻬذﻩ اﻷﻧواع ﻣﻊ اﻟﺗرﻛﯾز ﻋﻠﻰ اﻟﻧوع اﻷﺧﯾر وﻫو ‪X . L . P‬‬

‫‪ . E‬واﻟذى ﯾﺗم ﺣﺎﻟﯾﺎ إﺣﻼﻟﻪ ﺑدﻻ ﻣن اﻟﻧوع اﻟراﺑﻊ اﻟﻛﺎﺑﻼت اﻟﻣﻌزوﻟﺔ ﺑﺎﻟورق اﻟﻣﺷﺑﻊ ﺑﺎﻟزﯾت‬

‫ﻟظﻬور ﺑﻌض اﻟﻌﯾوب واﻟﺗﻰ ﺳوف ﯾﺗم ﺗوﺿﯾﺣﻬﺎ ﻓﯾﻣﺎ ﺑﻌد أﯾﺿﺎ ‪.‬‬

‫إﻻ أﻧﻪ ﺳـوف ﯾﺗم اﻵن ﺗوﺿﯾﺢ وﺷـرح أﺣـد أﻧواع اﻟﻣواد اﻟﻌﺎزﻟﺔ ﻣن ﺣﯾث ﺧﺻﺎﺋﺻﻬﺎ‬

‫وﻣﻣﯾزاﺗﻬﺎ وﻫﻰ ﻣﺎدة ‪. P . V . C‬‬

‫ﻣواﺻﻔﺎت وﺧﺻﺎﺋص ﻣﺎدة اﻟﺑوﻟﻰ ﻓﯾﻧﯾل ﻛﻠوراﯾد ‪P . V . C‬‬

‫‪ (١‬ﻟﻬﺎ ﻣﻘﺎوﻣﺔ ﻧوﻋﯾﺔ ﻋﺎﻟﯾﺔ ‪.‬‬

‫‪ (٢‬ﻟﻬﺎ ﺟﻬد اﻧﻛﺳﺎر ﺣﺗﻰ ‪ ١٠٠٠‬ﻓوﻟت ‪.‬‬

‫‪ (٣‬ﻟﻬﺎ ﺧﺎﺻﯾﺔ ﻋدم اﻣﺗﺻﺎص اﻟرطوﺑﺔ ﻣن اﻟوﺳط اﻟﻣﺣﯾط ‪.‬‬

‫‪٢٢‬‬
‫‪ (٤‬ﻏﯾر ﻧﺷطﺔ ﻛﯾﻣﯾﺎﺋﯾﺎ أى ﺧﺎﻣﻠﺔ " ﻻ ﺗﺗﻔﺎﻋل ﻣﻊ اﻷﺣﻣﺎض أو اﻟﻘﻠوﯾﺎت " ‪.‬‬

‫‪ (٥‬ﻻ ﺗﺗﺄﺛر وﻻ ﺗﺗﻐﯾر ﻣﻛوﻧﺎﺗﻬﺎ ﺑﺎرﺗﻔﺎع درﺟﺔ اﻟﺣرارة ‪.‬‬

‫‪ (٦‬ﻟﻬﺎ ﺧﺎﺻﯾﺔ اﻟﺻﻼﺑﺔ واﻟﻣروﻧﺔ ‪.‬‬

‫‪ (٧‬ﻻ ﺗﺗﺄﺛر ﺑﺎﻟﻣذﯾﺑﺎت أو اﻟﺷﺣوم ‪.‬‬

‫‪ (٨‬ﻻ ﺗﺗﺄﺛر ﺑﺎﻟﻣﯾﺎﻩ ‪.‬‬

‫ﺗم اﺧﺗﺑـﺎر ﻫذﻩ اﻟﻣﺎدة اﻟﻌﺎزﻟـﺔ وﺗم ذﻛر ﻫذﻩ اﻟﻣواﺻﻔﺎت ﻟﻬﺎ ﺑﺳﺑب ﻛوﻧﻬﺎ ﻣﺎدة ﺗﺳﺗﺧدم‬

‫ﻓﻰ اﻟﻌزل وﺳﯾﺗم ذﻛرﻫﺎ ﻛﻣﺎدة ﻏﻼف ﺧﺎرﺟﻲ ﻟﻠﻛﺎﺑﻼت اﻟﺑﻼﺳﺗﯾﻛﯾﺔ وﺗﺳﺗﺧدم أﯾﺿﺎ ﻓﻰ اﻟﺣﺷو‬

‫ﻟﻠﻛﺎﺑﻼت اﻟﻣﻌزوﻟﺔ ﺑﻣﺎدة ‪ X . L . P . E‬وﯾﻼﺣظ أﻧﻬﺎ ﺣﺎﻟﯾﺎ ﺗﺳﺗﺧدم ﻓﻰ ﻣواﺳﯾر اﻟﻣﯾﺎﻩ‬

‫واﻟﺻرف اﻟﺻﺣﻰ ﻟﻣﺎ ﻟﻬﺎ ﻣن ﺧﻣول ﻛﯾﻣﯾﺎﺋﻲ ‪ ،‬إﻻ أﻧﻬﺎ ﻛﻣﺎدة ﻋﺎزﻟﺔ ﻻ ﺗﺳﺗﺧدم إﻻ ﺣﺗﻰ ﺟﻬد‬

‫‪ ١٠٠٠‬ﻓوﻟت ﻓﻘط ‪.‬‬

‫اﻟﻣﻘﺎطﻊ اﻟﻣﺧﺗﻠﻔﺔ ﻟﻠﻛﺎﺑﻼت‬

‫ﻓﯾﻣﺎ ﯾﻠﻰ ﺟدول ﯾوﺿﺢ اﻟﻣﻘﺎطﻊ اﻟﻣﺧﺗﻠﻔﺔ ﻟﻠﻛﺎﺑﻼت اﻷرﺿﯾﺔ ﻟﻠﺟﻬدﯾن اﻟﻣﻧﺧﻔض‬

‫واﻟﻣﺗوﺳط وﻛذﻟك ﻋدد اﻟﺷﻌﯾرات ﻟﻛل ﻣﻘطﻊ وﻗطر ﻛل ﻣوﺻل‪:‬‬

‫ﻛﺎﺑﻼت ﺟﻬد ﻣﺗوﺳط‬ ‫ﻗطر اﻟﻣوﺻل‬ ‫ﻋدد اﻟﺷﻌﯾرات‬ ‫ﻛﺎﺑﻼت ﺟﻬد ﻣﻧﺧﻔض‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ١٦× ٣‬ﻣم‬ ‫‪ ٤.٧‬ﻣم‬ ‫‪٧‬‬ ‫‪١٠ + ١٦× ٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٢٥ × ٣‬ﻣم‬ ‫‪ ٥.٩‬ﻣم‬ ‫‪٧‬‬ ‫‪ ١٦ + ٢٥×٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٣٥× ٣‬ﻣم‬ ‫‪ ٧.٠‬ﻣم‬ ‫‪١٩‬‬ ‫‪ ٢٥ + ٣٥× ٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٥٠ × ٣‬ﻣم‬ ‫‪ ٨.٠‬ﻣم‬ ‫‪١٩‬‬ ‫‪ ٢٥ + ٥٠×٣‬ﻣم‬

‫‪٢٣‬‬
‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٧٠× ٣‬ﻣم‬ ‫‪ ٩.٧‬ﻣم‬ ‫‪١٩‬‬ ‫‪ ٣٥ + ٧٠× ٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٩٥ × ٣‬ﻣم‬ ‫‪ ١١.٤‬ﻣم‬ ‫‪١٩‬‬ ‫‪ ٥٠ + ٩٥×٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ١٢٠× ٣‬ﻣم‬ ‫‪ ١٢.٩‬ﻣم‬ ‫‪٣٧‬‬ ‫‪ ٧٠ + ١٢٠× ٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ١٥٠ × ٣‬ﻣم‬ ‫‪ ١٤.٣‬ﻣم‬ ‫‪٣٧‬‬ ‫‪ ٧٠ + ١٥٠×٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ١٨٥× ٣‬ﻣم‬ ‫‪ ١٦.١‬ﻣم‬ ‫‪٣٧‬‬ ‫‪ ٩٥ + ١٨٥× ٣‬ﻣم‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٢٤٠ × ٣‬ﻣم‬ ‫‪ ١٨.٣‬ﻣم‬ ‫‪٦١‬‬ ‫‪ ١٢٠ + ٢٤٠×٣‬ﻣم‬

‫وﯾوﺿﺢ ﻫذا اﻟﺟدول اﻟﻣﻘﺎطﻊ اﻟﻣﺧﺗﻠﻔﺔ واﻟﺛﺎﺑﺗﺔ ﻟﻛﺎﺑﻼت اﻟﺟﻬد اﻟﻣﻧﺧﻔض واﻟﻣﺗوﺳط‬

‫ﻛﻣﺎ اﻧﻪ ﯾوﺿﺢ ﻋدد ﺷﻌﯾرات اﻟﻣوﺻل وﻛذﻟك ﻗطر ﻛل ﻣوﺻل ‪.‬‬

‫وﻣن اﻟﺿروري أن ﯾﻛون اﻟﻘﺎﺋم ﺑﺎﻟﻌﻣل ﻓﻰ ﻗﺳم اﻟﻛﺎﺑﻼت اﻷرﺿﯾﺔ ﻋﻠﻰ ﻋﻠم ﺑﻬذﻩ‬

‫اﻟﻣﻘﺎطﻊ وﻛﻣﺎ اﻧﻪ ﻣن اﻟﺿروري أن ﯾﻛون ﻋﻠﻰ ﻋﻠم ﺑﻛﯾﻔﯾﺔ ﺗﺣدﯾد ﻣﺳﺎﺣﺔ ﻣﻘطﻊ أي ﻛﺎﺑل ﯾراﻩ‬

‫ﺳواء ﻛﺎن ذﻟك ﻣن ﺧﻼل ﺗطﺑﯾق ﻗﺎﻧون ﻋدد اﻟﺷﻌﯾرات أو ﺑطرﯾﻘﺔ ﻗطر اﻟﻣوﺻل أو ﺑﻣﺟرد اﻟﻧظر‬

‫وﻫذا ﯾﺗطﻠب ﺧﺑرﻩ طوﯾﻠﺔ ﻓﻰ اﻟﻌﻣل ‪.‬‬

‫ﯾﻣﻛن ﻣﻌرﻓﺔ ﻋدد ﺷﻌﯾرات اﻟﻣوﺻل ﻣن ﺧﻼل اﻟﻘﺎﻧون اﻷﺗﻰ ‪-:‬‬

‫} ) ‪N = 1 + { 3A ( A + 1‬‬

‫أو ن = ‪ ٣ ] + ١‬أ ) أ ‪[ ( ١ +‬‬

‫ﻫﻰ ﻋدد اﻟﺷﻌﯾرات‬ ‫ن‬ ‫ﺣﯾث أن‬

‫ﻫﻰ ﻋدد اﻟطﺑﻘﺎت‬ ‫أ‬

‫‪٢٤‬‬
‫ﻓﺈذا ﻛﺎن ﻋدد اﻟطﺑﻘﺎت ) ‪( ١‬‬

‫ﻓﺈن ﻋدد اﻟﺷﻌﯾرات ﯾﻛون‬

‫ن = ‪ ( ٧ ) = ٦ + ١ = [ ( ١ + ١ ) ١× ٣ ] + ١‬ﺷﻌﯾرات‬

‫أﻣﺎ إذا ﻛﺎن ﻋدد اﻟطﺑﻘﺎت ) ‪( ٢‬‬

‫ﻓﺈن ﻋدد اﻟﺷﻌﯾرات ﯾﻛون‬

‫ن = ‪ ( ١٩ ) = ١٨ + ١ = [ ( ١ + ٢ ) ٢ × ٣ ]+ ١‬ﺷﻌرﻩ‬

‫أﻣﺎ إذا ﻛﺎن ﻋدد اﻟطﺑﻘﺎت ) ‪( ٣‬‬

‫ﻓﺈن ﻋدد اﻟﺷﻌﯾرات ﯾﻛون‬

‫ن = ‪ ( ٣٧ ) = ٣٦ + ١ = [ ( ١ + ٣ ) ٣ × ٣ ] + ١‬ﺷﻌرﻩ‬

‫أﻣﺎ إذا ﻛﺎن ﻋدد اﻟطﺑﻘﺎت ) ‪( ٤‬‬

‫ﻓﺈن ﻋدد اﻟﺷﻌﯾرات ﯾﻛون‬

‫ن = ‪ ( ٦١ ) = ٦٠ + ١ = [ ( ١ + ٤ ) ٤× ٣ ] + ١‬ﺷﻌرﻩ‬

‫وﯾﻼﺣــظ ﻟﻧﺎ أن اﻟﻛﺎﺑل ﻣﻘطـــﻊ ‪ ٧٠ × ٣‬ﻣم‪ ٢‬ﺗﻛون اﻟﻔﺎزﻩ ﻣن طﺑﻘﺗﯾن إي أن ﻋدد‬

‫اﻟﺷﻌﯾرات ‪ ١٩‬ﺷﻌـــرة ‪.‬‬

‫ﻛﻣﺎ أن اﻟﻛﺎﺑل ﻣﻘطﻊ ‪ ١٥٠× ٣‬ﻣم‪ ٢‬ﺗﻛون اﻟﻔﺎزﻩ اﻟﺧﺎﺻﺔ ﺑﻪ ﻣن ‪ ٣‬طﺑﻘﺎت أى أن ﻋدد‬

‫اﻟﺷﻌﯾرات ‪ ٣٧‬ﺷﻌرة ‪.‬‬

‫‪٢٥‬‬
‫ﻛﻣﺎ أن اﻟﻛﺎﺑل ﻣﻘطﻊ ‪ ٢٤٠ × ٣‬ﻣم‪ ٢‬ﺗﻛون اﻟﻔﺎزﻩ اﻟﺧﺎﺻﺔ ﺑﻪ ﻣﻛوﻧﺔ ﻣن ‪ ٤‬طﺑﻘﺎت أى‬

‫أن ﻋدد اﻟﺷﻌﯾرات ‪ ٦١‬ﺷﻌرة ‪.‬‬

‫وﻟﻣﺎ ﻛﺎﻧت ﻫﻧﺎك ﻣﻘﺎطﻊ ﻟﻠﻛﺎﺑﻼت ﺗﺷﺗرك ﻓﻰ ﻧﻔس ﻋدد اﻟﺷﻌﯾرات ﻣﻣﺎ ﯾﺻﻌب ﻣﻌﻪ‬

‫ﺗﺣدﯾد ﻣﺳﺎﺣﺔ اﻟﻘطﻊ ﻣن ﺧﻼل ﻋدد اﻟﺷﻌﯾرات وﯾﺳﺗﻠزم ذﻟك ﻣﻌرﻓﺔ ﻗطر اﻟﻣوﺻل ﻟﺗﺳﺎﻋد ﻋﻠﻰ‬

‫اﻟﺗﻌرف ﻋﻠﻰ ﻣﺳﺎﺣﺔ اﻟﻣﻘطﻊ اﻟﻣطﻠوب ‪.‬‬

‫وﻣن ﺧﻼل اﻟﺟدول اﻟذى ﯾوﺿﺢ ﻣﺳﺎﺣﺎت اﻟﻣﻘطﻊ وﻋدد اﻟﺷﻌﯾرات وأﻗطﺎر اﻟﻣوﺻﻼت‬

‫ﺳﯾﺗم اﺧﺗﺑﺎر أﺣد اﻟﻣﻘﺎطﻊ ﻟﺣﺳﺎب ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟﻣوﺻل ﻣن ﺧﻼل ﻗطر اﻟﻣوﺻل ‪.‬‬

‫ﻣﺛﺎل ‪:‬‬

‫‪٢‬‬
‫ﻧﺟد أن ﻋدد اﻟﺷﻌﯾرات ‪١٩‬‬ ‫ﻣن اﻟﺟدول اﻟﺳﺎﺑق ﻟﻣوﺻل ﻣﺳﺎﺣﺔ ﻣﻘطﻌﻪ ‪ ٥٠‬ﻣم‬

‫ﺷﻌﯾرة وﻗطر اﻟﻣوﺻل ‪ ٨‬ﻣم وﻣن اﻟﻣﻌﻠوم أن ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟداﺋرة ) ط ﻧق‪ ( ٢‬وﻟﻣﺎ ﻛﺎن‬

‫ﻟﻠﻣوﺻل ﺷﻛل داﺋرى ﻓﺈﻧﻪ ﯾﻣﻛن ﺗطﺑﯾق اﻟﻘﺎﻧون اﻟﺳﺎﺑق ﻋﻠﯾﻬﺎ‬

‫‪٢‬‬
‫‪ ‬ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟﻣوﺻل = ط ﻧق‬

‫‪٢‬‬
‫= ‪( ٤ ) × ٣.١٤‬‬

‫‪٢‬‬
‫= ‪ ٥٠.٢٤ = ١٦ × ٣.١٤‬ﻣم‬

‫‪٢‬‬
‫‪ ‬إذا ﻣﻘطﻊ اﻟﻛﺎﺑل ‪ ٥٠ × ٣‬ﻣم‬

‫وﯾﺗﺿﺢ ﻟﻧﺎ أن اﻟرﻗم اﻟﺧﺎرج ﻣن ﺣﺳﺎب ﻣﺳﺎﺣﺔ اﻟﻣﻘطﻊ ﻟﯾس اﻟرﻗم اﻟﺻﺣﯾﺢ وﻟﻛﻧﻪ‬

‫ﻗرﯾب ﻣن اﻟرﻗم اﻟﻣدون ﺑﺎﻟﺟدول وﯾﻣﻛن ﺗطﺑﯾق اﻟﻘﺎﻧون ﻋﻠﻰ أى ﻗطر ﻷي ﻣوﺻل ‪.‬‬

‫‪٢٦‬‬
‫إﻻ اﻧﻪ ﺑﺎﻟﻧﺳﺑﺔ ﻟذوى اﻟﺧﺑرة اﻟطوﯾﻠﺔ ﻓﻰ ﻣﺟﺎل اﻟﻛﺎﺑﻼت وﻣن ﻛﺛرة اﻟﺗﻌرض ﻟﻠﻣﻘﺎطﻊ‬

‫اﻟﻣﺧﺗﻠﻔﺔ ﻓﻰ اﻟﻌﻣل ﯾﺻﺑﺢ اﻷﻣر ﺑﺎﻟﻧﺳﺑﺔ ﻟﻬم ﻟﺗﺣدﯾد ﻣﺳﺎﺣﺔ اﻟﻣﻘطﻊ ﺳﻬل وﯾﺳﯾر ﺑﻣﺟرد‬

‫اﻟﻧظر‬

‫اﻟﻣوﺻــﻼت‬

‫ﺗﻌرﯾف اﻟﻣوﺻل ‪-:‬‬

‫ﻣﺎدة ﻟﻬﺎ ﻣﻘﺎوﻣﺔ ﻧوﻋﯾﺔ ﺻﻐﯾرة " ﻣوﺻﻠﯾﺔ ﻋﺎﻟﯾﺔ " ﺗﺳﻣﺢ ﺑﻣرور اﻟﺗﯾﺎر اﻟﻛﻬرﺑﻰ ﻣن ﺧﻼﻟﻬﺎ‬

‫ﺑﺳﻬوﻟﺔ ‪.‬‬

‫وﻫﻧﺎك أﻧواع ﻛﺛﯾرة ﻣن اﻟﻣوﺻﻼت وﻣﻧﻬﺎ ‪-:‬‬

‫‪ (١‬اﻟﻔﺿـــــــــﺔ ‪.‬‬

‫‪ (٢‬اﻟﻧﺣـــــــــﺎس ‪.‬‬

‫‪ (٣‬اﻷﻟوﻣﻧﯾـــــوم ‪.‬‬

‫‪ (٤‬اﻟﺻﻠب اﻟﻣﺟﻠﻔن ‪.‬‬

‫‪ (٥‬ﻧﺣﺎس ﻛﺎدﻣﯾوم ‪.‬‬

‫‪ (٦‬أﻟﻣوﻧﯾوم ﻣﻘوى ﺑﻔردﻩ ﺻﻠب ‪.‬‬

‫إﻻ أﻧﻪ ﯾﻼﺣظ أن اﻟﻧﺣﺎس واﻷﻟوﻣﻧﯾوم ﻫﻣﺎ اﻟﻣوﺻﻼن اﻟﻠذان ﯾﺳﺗﺧدﻣﺎن ﻛﻣوﺻﻼت ﻓﻰ‬

‫اﻟﻛﺎﺑﻼت اﻷرﺿﯾﺔ إو ذا أردﻧﺎ ﻋﻣل ﺗرﺗﯾب ﻟﻠﻣوﺻﻼت ﻣن ﺣﯾث اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ اﻷﻗل ﻓﺎﻷﻛﺛر‬

‫‪٢٧‬‬
‫ﻧﺟد أن اﻟﻔﺿﺔ ﻫﻰ أﻗل ﻣوﺻل ﻟﻪ ﻣﻘﺎوﻣﺔ ﻧوﻋﯾﺔ ﺛم اﻟﻧﺣﺎس ﺛم اﻷﻟوﻣﻧﯾوم وﻟذﻟك ﻓﺄن اﻟﻔﺿﺔ‬

‫ﺗﺳﺗﺧدم ﻓﻰ ﻋﻣل ﺗﺷﻌﯾرات اﻟﻣﺻﻬرات وﻻ ﯾﻣﻛن اﺳﺗﺧداﻣﻬﺎ ﻛﻣوﺻل ﻧظ ار ﻻرﺗﻔﺎع ﺛﻣﻧﻬﺎ‪.‬‬

‫وﯾﺳﺗﺧدم اﻟﻧﺣﺎس واﻷﻟوﻣﻧﯾوم ﻓﻘط ﻛﻣوﺻﻼت ﻟﻠﻛﺎﺑﻼت واﻟﺟدول اﻟﺗﺎﻟﻰ ﯾوﺿﺢ اﻟﻔرق ﺑﯾن‬

‫اﻟﻧﺣﺎس واﻷﻟوﻣﻧﯾوم ﻣﻊ ﺑﯾﺎن ﻣﻣﯾزات وﻋﯾوب ﻛل ﻣﻧﻬﻣﺎ ‪.‬‬

‫ﺟدول ﯾوﺿﺢ ﻣﻘﺎرﻧﺔ ﺑﯾن ﻛل ﻣن اﻟﻧﺣﺎس واﻷﻟوﻣﻧﯾوم‬

‫ﻣﻌدن اﻷﻟوﻣﻧﯾوم‬ ‫ﻣﻌدن اﻟﻧﺣﺎس‬ ‫أوﺟﻪ اﻟﻣﻘﺎرﻧﺔ‬ ‫م‬

‫‪% ٩٩.٥‬‬ ‫‪% ٩٩.٩٨‬‬ ‫اﻟﻧﻘﺎوة‬ ‫‪١‬‬

‫‪٥ ٦٦٠‬م‬ ‫‪٥ ١٠٨٣‬م‬ ‫درﺟﺔ اﻻﻧﺻﻬﺎر‬ ‫‪٢‬‬

‫‪٣‬‬ ‫‪٣‬‬
‫‪ ٢.٧‬ﺟم ‪ /‬ﺳم‬ ‫‪ ٨.٩‬ﺟم‪/‬ﺳم‬ ‫اﻟﻛﺛﺎﻓﺔ ﻋﻧد ‪٥ ٢٠‬م‬ ‫‪٣‬‬

‫‪ ٠.٠٢٨٦‬أوم ‪ .‬ﻣم‪ /٢‬م‬ ‫‪ ٠.٠١٧٨‬أوم ‪ .‬ﻣم‪ /٢‬م‬ ‫اﻟﻣﻘﺎوﻣﺔ‬ ‫‪٤‬‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ٦١‬ﻣﺗر‪ /‬أو م ‪ .‬ﻣم‬ ‫‪ ٩٧‬ﻣﺗر ‪ /‬أو م ‪ .‬ﻣم‬ ‫اﻟﻣوﺻﻠﯾﺔ‬ ‫‪٥‬‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ١٠‬ﻛﺟم ‪ /‬ﻣم‬ ‫‪ ١٩‬ﻛﺟم ‪ /‬ﻣم‬ ‫اﻟﺷد اﻟﻣﺳﻣوح ﺑﻪ‬ ‫‪٦‬‬

‫‪٢‬‬ ‫‪٢‬‬
‫‪ ١٨‬ﻛﺟم ‪ /‬ﻣم‬ ‫‪ ٤٠‬ﻛﺟم ‪ /‬ﻣم‬ ‫أﻗﺻﻰ ﺷد‬ ‫‪٧‬‬

‫ﻏﯾر ﻗﺎﺑل ﻟﻠﺗﻣﻐﻧط‬ ‫ﻏﯾر ﻗﺎﺑل ﻟﻠﺗﻣﻐﻧط‬ ‫ﻗﺎﺑﻠﯾﺔ اﻟﺗﻣﻐﻧط‬ ‫‪٨‬‬

‫ﯾﻔﻘد ﻟﻣﻌﺎﻧﺔ ﺑﺳرﻋﺔ وﯾﻐطﻰ ﺑطﺑﻘﺔ ﻣن‬ ‫ﯾﻐطﻰ ﺑطﺑﻘﺔ ﺻدأ ﻟوﻧﻬﺎ أﺧﺿر ﻣن‬ ‫ﻗﺎﺑﻠﯾﺔ اﻟﺻــدأ ﻋﻧد‬ ‫‪٩‬‬

‫أﻛﺳﯾد اﻷﻟوﻣﻧﯾوم وﻫﻰ ﻣﺎدة ﻋﺎزﻟﺔ‬ ‫أﻛﺳﯾد اﻟﻧﺣﺎس وﻫﻰ ﻣﺎدة ﻋﺎزﻟﺔ‬ ‫اﻟﺗﻌرض ﻟﻠﻌواﻣل اﻟﺟوﯾﺔ‬

‫ﺧطوط ﻫواﺋﯾﺔ ‪ -‬ﻛﺎﺑﻼت ‪ -‬ﺳراﻓﯾل‬ ‫ﺧطوط ﻫواﺋﯾﺔ ‪ -‬ﻛﺎﺑﻼت ‪ -‬ﺳراﻓﯾل ‪ -‬ﻛوس‬ ‫اﻻﺳﺗﺧدام‬ ‫‪١٠‬‬

‫‪٢٨‬‬
‫‪ -‬ﻛوس ‪ -‬ﻛﻠﺑﺳﺎت‬ ‫‪ -‬ﻛﻠﺑﺳﺎت ‪ -‬ﻗواﻋد ﻣﺻﻬرات ‪ -‬ﺑﺎرات‬

‫ﻣوﺻل ﺟﯾد‪ -‬طرى‪ -‬ﺧﻔﯾف اﻟوزن‪-‬‬ ‫ﻣوﺻل ﺟﯾد ‪ -‬ﯾﺗﺣﻣل اﺟﺗﻬﺎدات ﻋﺎﻟﯾﺔ‬ ‫اﻟﻣﻣﯾزات‬ ‫‪١١‬‬

‫رﺧﯾص اﻟﺛﻣن‬

‫ﺳرﯾﻊ اﻟﺗﺄﻛﺳد‬ ‫ﺛﻘﯾل اﻟوزن ‪ -‬ﻏﺎﻟﻰ اﻟﺛﻣن‬ ‫اﻟﻌﯾوب‬ ‫‪١٢‬‬

‫ﻣﻘﺎوﻣﺔ =‪ ١.٥‬ﻣن ﻣﻘﺎوﻣﺔ اﻟﻧﺣﺎس‬

‫‪٢٩‬‬
EARTHING

ETERNAL ENGINEERS GROUP


01007200959-01114911166

٣٠
‫اﻟﺗﺄرﯾض ‪earthing‬‬

‫ﺗﻌرﯾف‪ /‬ﯾﻌرف اﻟﺗﺄرﯾض ﺑﺄﻧﻪ ﺗوﺻﯾل ﻣﺗﻌﻣد ﻟﺟزء ﻣن ﻧظﺎم أو ﻣﻌدة ﺗوﺻﯾﻼ ﻣﺑﺎﺷ ار ﺑﺎﻷرض‬
‫ﺑدون وﺟود ﻓﯾوز أو ﻣﻔﺗﺎح أو ﻗﺎطﻊ ﻓﻲ ﻫذا اﻻﺗﺻﺎل اﻷرﺿﻲ‪.‬‬

‫أﻫﻣﯾﺔ اﻟﺗﺄرﯾض ‪:‬‬

‫ﯾﺗم ﺗﺄرﯾض دواﺋر اﻷﺟﻬزة اﻟﻣﺧﺗﻠﻔﺔ ﻟﻠﺣد ﻣـن ارﺗﻔـﺎع اﻟﺟﻬـد اﻟﻧـﺎﺗﺞ ﻣـن ﺗـﺄﺛﯾر اﻟﺻـواﻋق أو‬
‫ﺗﻼﻣس ﻣوﺻﻼت اﻟدواﺋر ﻣﻊ ﻣوﺻﻼت ذات ﺟﻬد أﻋﻠﻰ ‪ .‬ﻛﻣﺎ ﯾﺳﺗﺧدم اﻟﺗﺄرﯾض ﻓـﻲ اﻟﻣﺣﺎﻓظـﺔ‬
‫ﻋﻠﻰ ﺛﺑﺎت اﻟﺟﻬد أﺛﻧﺎء اﻟﺗﺷﻐﯾل اﻟﻌﺎدي وﺗﺳﻬﯾل ﻋﻣل ﻗواطﻊ اﻟوﻗﺎﯾﺔ ﻣن اﻟﺗﺳرب اﻷرﺿﻲ ‪.‬‬

‫أدوات اﻟﺗﺄرﯾض ‪:‬‬

‫‪ -١‬ﻣوﺻل اﻟﺗﺄرﯾض )‪:(GROUNDING CONDUCTOR‬‬

‫ﻣوﺻـل اﻟﺗــﺄرﯾض ﻫــو ﻣوﺻـل ﻣــن اﻟﻧﺣــﺎس أو اﻷﻟﻣﻧﯾــوم ﻣﻌـزول ﺑــﺎﻟﻠون اﻷﺧﺿــر أو اﻟﻠــون‬
‫اﻷﺧﺿر‪ /‬اﻷﺻﻔر وﯾﺗم ﺗﻣدﯾدﻩ ﻣﻊ ﻣوﺻﻼت اﻟدواﺋر اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﯾﻣﺎ ﺑﯾن ﻟوﺣﺔ اﻟﺗوزﯾـﻊ اﻟﻔرﻋﯾـﺔ‬
‫واﻟﻣﺧرج اﻟﻛﻬرﺑﺎﺋﻲ أﻣﺎ ﻣوﺻل ﺗﺄرﯾض اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ واﻟﻌﻣوﻣﯾﺔ ﻓﯾﺗم ﺗﻣدﯾـدﻩ ﻋـن ﻣوﺻـﻼت‬
‫اﻟﻧﺣﺎس أو اﻷﻟﻣﻧﯾوم إو ﻣﺎ أن ﯾﻛون ﻋﺎرﯾﺎً أو ﻣﻌزوﻻً ﻣﺻﻣﺗﺎً أو ﻣﺟدوﻻً ﯾرﺑط اﻟﻠوﺣـﺎت اﻟﻔرﻋﯾـﺔ‬
‫ﻣــﻊ اﻟﻠوﺣــﺎت اﻟﻌﻣوﻣﯾــﺔ ﻣــن ﺟﻬــﺔ وﯾــرﺑط اﻟﻠوﺣــﺎت اﻟﻌﻣوﻣﯾــﺔ ﻣــﻊ ﻗطــب اﻟﺗــﺄرﯾض ﻣــن اﻟﺟﻬــﺔ‬
‫اﻷﺧرى‪ .‬وﯾوﺿﺢ اﻟﺟدول اﻟﺗـﺎﻟﻲ ﻣﻘـﺎطﻊ ﻣوﺻـﻼت اﻟﺗـﺄرﯾض ﺑﺎﻟﻧﺳـﺑﺔ ﻟﻣﻘطـﻊ اﻟﻣوﺻـل اﻟﺣﺎﻣـل‬
‫ﻟﻠﺗﯾﺎر ‪:‬‬

‫ﻣﻘطﻊ أﻛﺑر ﻣوﺻل ﻧﺣﺎس ﺣﺎﻣل‬


‫ﻣﻘطﻊ ﻣوﺻل اﻷرﺿﻲ اﻟرﺋﯾﺳﻲ )ﻣم‪(٢‬‬
‫ﻟﻠﺗﯾﺎر )ﻣم‪(٢‬‬

‫‪١‬‬ ‫‪١‬‬

‫‪١.٥‬‬ ‫‪١.٥‬‬

‫‪٢.٥‬‬ ‫‪٢.٥‬‬

‫‪٤‬‬ ‫‪٤‬‬

‫‪٣١‬‬
‫‪٦‬‬ ‫‪٦‬‬

‫‪١٠‬‬ ‫‪١٠‬‬

‫‪١٦‬‬ ‫‪١٦‬‬

‫‪١٦‬‬ ‫‪٢٥‬‬

‫‪١٦‬‬ ‫‪٣٥‬‬

‫‪٢٥‬‬ ‫‪٥٠‬‬

‫‪٣٥‬‬ ‫‪٧٠‬‬

‫‪٥٠‬‬ ‫‪٩٥‬‬

‫‪٧٠‬‬ ‫‪١٢٠‬‬

‫‪٧٠‬‬ ‫‪١٥٠‬‬

‫‪٩٥‬‬ ‫‪١٨٥‬‬

‫‪١٢٠‬‬ ‫‪٢٤٠‬‬

‫‪١٥٠‬‬ ‫‪٣٠٠‬‬

‫‪١٨٥‬‬ ‫‪٤٠٠‬‬

‫* اﻟﻣﻌدات واﻷﺟﻬزة اﻟواﺟب ﺗﺄرﯾﺿﻬﺎ ﻓﻲ اﻟﻣﺑﺎﻧﻲ ‪:‬‬

‫ﻟﻌﻣل ﺷﺑﻛﺔ ﺗﺄرﯾض ﺟﯾدة ﻟﻠﻣﺑﻧﻰ ﻓﺈﻧﻪ ﻣن اﻟﺿروري أن ﯾﺗم ﺗﺄرﯾض اﻟﻌﻧﺎﺻر اﻟﺗﺎﻟﯾﺔ ‪:‬‬

‫‪ -‬ﻛل اﻷﺟﺳﺎم اﻟﻣﻌدﻧﯾﺔ رأﺳﯾﺎً وﯾزﯾد طوﻟﻬﺎ ﻋن ‪٢٤٠‬ﺳم أو اﻟﻣﻣدة أﻓﻘﯾـﺎً وﯾزﯾـد طوﻟﻬـﺎ ﻋـن‬
‫‪ -‬ﻛل اﻷﺟﻬزة اﻟﻛﻬرﺑﺎﺋﯾﺔ ‪.‬‬ ‫‪١٥٠‬ﺳم واﻟﻣﻌرﺿﺔ ﻟﻠﻣﻼﻣﺳﺔ ‪.‬‬

‫‪ -‬ﺟﻣﯾﻊ ﻣﺧﺎرج اﻟﺑراﯾز ووﺣدات اﻹﻧﺎرﻩ‪.‬‬

‫‪٣٢‬‬
‫‪ -٢‬ﻗطب اﻟﺗﺄرﯾض )‪: (GROUNDING ELECTRODE‬‬

‫ﯾﻣﻛن اﺳﺗﺧدام أﺣد اﻟوﺳﺎﺋل اﻟﺗﺎﻟﯾﺔ ﻛﻘطب ﻟﻠﺗﺄرﯾض وﻫﻰ ‪:‬‬

‫‪ -١‬ﺗﻣدﯾدات اﻟﻣواﺳﯾر اﻟﻣﻌدﻧﯾﺔ ﻟﻠﻣﯾﺎﻩ ‪.‬‬

‫‪ -٢‬أﺳﯾﺎخ اﻟﺗﺳﻠﯾﺢ ﻟﻠﻣﺑﻧﻰ‪.‬‬

‫‪ -٣‬ﻣوﺻل ﻣﻌدﻧﻲ ﯾﺗم ﺗﻣدﯾدﻩ ﺣول اﻟﻣﺑﻧﻰ وﻋﻠﻰ ﻻ ﯾﻘل ﻋن ‪٧٥‬ﺳم ﻣن ﺳطﺢ اﻷرض‪.‬‬

‫ﻛﻣﺎ ﯾﻣﻛن اﺳﺗﺧدام أﻗطﺎب اﻟﺗﺄرﯾض اﻟﺻﻧﺎﻋﯾﺔ اﻟﺗﺎﻟﯾﺔ ‪:‬‬

‫ﻗطب ﺗﺄرﯾض ﺻﻧﺎﻋﻲ )‪: (MADE ELECTRODE‬‬

‫وﻫــو ﻋﺑــﺎرة ﻋــن ﻗﺿــﯾب أو ﻣﺎﺳــورة ﻣﻌدﻧﯾــﺔ ﻻ ﯾﻘــل طوﻟﻬــﺎ ‪٢٤٠‬ﺳــم ﺗــدﻓن رأﺳــﯾﺎً ﻣﻼﻣﺳــﺔ‬
‫ﻟﻠﺗرﺑﺔ إﻻ إذا ﻛﺎﻧت اﻷرض ﺻﺧرﯾﺔ ﻓﯾﻣﻛن وﺿﻌﻬﺎ ﻣﺎﺋﻠﺔ ‪ ٤٥‬درﺟﺔ ﻋﻠـﻰ اﻟﻣﺳـﺗوى اﻟرأﺳـﻲ أو‬
‫ﺗدﻓن ﻓﻲ ﺧﻧدق ﻋﻠﻰ ﻋﻣق ‪٧٥‬ﺳم ﻣن ﺳطﺢ اﻷرض ﻋﻠﻰ اﻷﻗل‪.‬‬

‫ﻟوح اﻟﺗﺄرﯾض )‪:(PLATE ELECTRODE‬‬

‫وﻫو ﻋﺑﺎرة ﻋن ﻟوح ﻣﻌدﻧﻲ ﻗد ﯾﻛون ﻣن اﻟﻧﺣﺎس ﯾﺳﻣك ‪ ١.٥‬ﻣم أو ﻣـن اﻟﺣدﯾـد ﺑﺳـﻣك ﻻ‬
‫ﯾﻘل ﻋن ‪ ٦.٣٥‬ﻣم ‪ .‬وﯾﺟب أﻻ ﺗﻘل اﻟﻣﺳﺎﺣﺔ اﻟﻣﻌرﺿﺔ ﻟﻠﺗرﺑﺔ ﻋن ‪٠.١٨٦‬م‪.٢‬‬

‫وﻋﻣوﻣﺎً ﯾﺟب أن ﯾﻛون ﻗطب اﻟﺗﺄرﯾض اﻟﻣﻼﻣـس ﻟﻠﺗرﺑـﺔ ﺧﺎﻟﯾـﺎً ﻣـن اﻟﺷـﺣوم أواﻟزﯾـوت ﻷﻧﻬـﺎ‬
‫ﺗﺿﻌف ﺧﺻﺎﺋص ﻗﺎﺑﻠﯾﺔ اﻟﺗﺄرﯾض ﻟﻠﺗوﺻﯾل اﻟﻛﻬرﺑﺎﺋﻲ ‪.‬‬

‫* اﻟطرق اﻟﻣﺧﺗﻠﻔﺔ ﻟﺧﻔض ﻣﻘﺎوﻣﺔ اﻟﺗﺄرﯾض ‪:‬‬

‫ﺑﻌد اﻻﻧﺗﻬﺎء ﻣن ﺗﺄرﯾض اﻟﻣﺑﻧﻰ واﻟﻠوﺣﺎت اﻟﻌﻣوﻣﯾـﺔ واﻟﻔرﻋﯾـﺔ ﯾـﺗم ﻗﯾـﺎس ﻣﻘﺎوﻣـﺔ اﻟﺗـﺄرﯾض‬
‫ﺑواﺳطﺔ أﺟﻬزة ﺧﺎﺻـﺔ ﺑـذﻟك ﻓـﺈذا ﻟـوﺣظ أﻧﻬـﺎ ﺗزﯾـد ﻋـن اﻟﺣـد اﻟﻣﺳـﻣوح ﺑـﻪ وﻫـو ‪ ٢٥‬أوم ﻓﺈﻧـﻪ‬
‫ﯾﻠزم ﺧﻔض ﻫذﻩ اﻟﻘﯾﻣﺔ ﺑﺎﺳﺗﺧدام طرﯾﻘﺔ أو أﻛﺛر ﻣن اﻟطرق اﻟﺗﺎﻟﯾﺔ ‪:‬‬

‫* زﯾﺎدة ﻗطر ﻗﺿﯾب اﻟﺗﺄرﯾض ‪:‬‬

‫زﯾــﺎدة ﻗطــر ﻗﺿــﯾب اﻟﺗــﺄرﯾض ﻟﺗزﯾــد اﻟﻣﺳــﺎﺣﺔ اﻟﻣﻌرﺿــﺔ ﻟﻣﻼﻣﺳــﺔ اﻟﺗرﺑــﺔ إﻻ أن زﯾــﺎدة ﻗطــر‬
‫اﻟﻘﺿﯾب ﻻ ﯾﺗﺑﻌﻬﺎ ﺧﻔض ﻣﻠﻣوس ﻓﻲ ﻣﻘﺎوﻣﺔ اﻟﺗـﺄرﯾض ﺑﺎﻹﺿـﺎﻓﺔ إﻟـﻰ أﻧـﻪ ﻻ ﯾﻔﺿـل اﺳـﺗﺧدام‬
‫أﻗطﺎر أﻛﺑر ﻣن ‪١٨‬ﻣم‪.‬‬

‫* زﯾﺎدة طول ﻗﺿﯾب اﻟﺗﺄرﯾض ‪:‬‬

‫‪٣٣‬‬
‫ﯾﻣﻛن أن ﯾﺗم رﺑط أﻛﺛر ﻣن ﻗﺿﯾب ﻋن طرﯾق ﺟﻠﺑﻪ وﺻل ﻣن ﻧﻔس اﻟﻣﻌـدن ﻟﻠﺣﺻـول ﻋﻠـﻰ‬
‫اﻟطــول اﻟﻣﻧﺎﺳــب ورﻏــم أن اﻟطــول اﻟﻣوﺻــﻰ ﺑﺎﺳــﺗﺧداﻣﻪ ﻓــﻲ )‪ (NEC‬ﻫــو ‪٢٤٠‬ﺳــم ﻟﻠﺗرﺑــﺔ‬
‫اﻟﻌﺎدﯾﺔ إﻻ أﻧﻪ ﯾﻣﻛن زﯾﺎدة ﻫذا اﻟطول إﻟﻰ ‪ ١٥‬ﻣﺗر ﻷﻧواع اﻟﺗرﺑﺔ اﻟردﯾﺋﺔ‪.‬‬

‫* زﯾﺎدة ﻋدد ﻗﺿﺑﺎن اﻟﺗﺄرﯾض ‪:‬‬

‫ﯾﻣﻛن اﺳﺗﺧدام أﻛﺛر ﻣن ﻗﺿﯾب ﻣدﻓون ﻓﻲ اﻷرض ﻋﻠﻰ ﻣﺳﺎﻓﺎت ﻻ ﺗﻘل ﻋن ‪٢٤٠‬ﺳـم ﺑـﯾن‬
‫اﻟﻘﺿﯾب واﻵﺧر وذﻟك ﻟﻠﺣﺻول ﻋﻠﻰ أﻓﺿل ﻗﯾﻣﺔ ﻣﻣﻛﻧﺔ ﻟﻣﻘﺎوﻣﺔ اﻟﺗﺄرﯾض‪.‬‬

‫* ﻣﻌﺎﻟﺟﺔ اﻟﺗرﺑﺔ ﻛﯾﻣﯾﺎﺋﯾﺎً ‪:‬‬

‫ﺗﻌــﺎﻟﺞ اﻟﺗرﺑــﺔ اﻟﻣﺣﯾطــﺔ ﺑﻘﺿــﯾب اﻟﺗــﺄرﯾض ﻛﯾﻣﯾﺎﺋﯾ ـﺎً ﻟﻠﺣﺻــول ﻋﻠــﻰ ﻣﻘﺎوﻣــﺔ ﻟﻠﺗــﺄرﯾض ﺑﺄﺣــد‬
‫اﻟطرق اﻟﺗﺎﻟﯾﺔ‪-:‬‬

‫أ( ﺗﻌﻣــل ﺣﻔــرﻩ ﻣﺟــﺎورة ﻟﻘﺿــﯾب اﻟﺗــﺄرﯾض وﺗﺑﻌــد ﻋﻧــﻪ ﺑﻣﺳــﺎﻓﺔ ﻻ ﺗزﯾــد ﻋــن ‪١٠‬ﺳــم وﺗﻣ ـﻼً‬
‫ﺑﺄﻣﻼح ﻛﺑرﯾﺗـﺎت اﻟﻣﻐﻧﯾﺳـﯾوم أو ﻛﺑرﯾﺗـﺎت اﻟﻧﺣـﺎس أو ﻣﻠـﺢ ﺻـﺧري ﺣﺗـﻰ ﻣﻧﺳـوب ‪٣٠‬ﺳـم ﻣـن‬
‫ﺳــطﺢ اﻷرض وﯾﺻــﻌب ﺗﻧﻔﯾــذ ﻫــذﻩ اﻟطرﯾﻘــﺔ ﻓ ـﻲ ﺣﺎﻟــﺔ ﻋــدم ﺗــوﻓر ﻓ ـراغ ﻛــﺎﻓﻲ ﺑﺟ ـوار ﻗﺿــﯾب‬
‫اﻟﺗﺄرﯾض ‪.‬‬

‫ب( أو ﯾﺗم ﻋﻣل ﺧﻧدق داﺋري ﺣول ﻗﺿـﯾب اﻟﺗـﺄرﯾض ﺑﺣﯾـث ﻻ ﯾﻘـل اﻟﻘطـر اﻟـداﺧﻠﻲ ﻟﻠﺧﻧـدق‬
‫ﻋن ‪٤٥‬ﺳم وﻋﻣق ‪٣٠‬ﺳم ‪ .‬وﯾﻣﻸ ﻫذا اﻟﺧﻧـدق ﺑـﺎﻟﻣواد اﻟﻛﯾﻣﯾﺎﺋﯾـﺔ اﻟﺳـﺎﺑق ذﻛرﻫـﺎ ‪ .‬وﯾﺟـب أﻻ‬
‫ﯾﻛون ﻫﻧﺎك اﺗﺻﺎل ﻣﺑﺎﺷر ﺑﯾن اﻟﻣواد اﻟﻛﯾﻣﺎﺋﯾﺔ وﻗﺿـﯾب اﻟﺗـﺄرﯾض ﺣﺗـﻰ ﻻ ﯾﺗﺳـﺑب ﻓـﻲ ﺗﻛـوﯾن‬
‫طﺑﻘﺔ ﻣن اﻟﺻدأ ﻋﻠﻰ ذﻟك اﻟﻘﺿـﯾب ‪ .‬واﻟﻛﻣﯾـﺔ اﻟﺗـﻲ ﯾﻔﺿـل وﺿـﻌﻬﺎ ﺗﻛـون ﻓـﻲ ﺣـدود ‪ ١٨‬إﻟـﻰ‬
‫‪ ٤٠‬ﻛﯾﻠو ﺟرام ﻣن ﻣﺎدة ﻛﺑرﯾﺗﺎت اﻟﻧﺣـﺎس ﻟـرﺧص ﺛﻣﻧﻬـﺎ وﺟـودة ﺗوﺻـﯾﻠﻬﺎ اﻟﻛﻬرﺑـﺎﺋﻲ وﯾﺳـﺗﻣر‬
‫ﻣﻔﻌول ﻫذﻩ اﻟﻛﻣﯾﺔ ﻟﻣدة ﺳﻧﺗﯾن ﺛم ﯾﻛرر وﺿﻌﻬﺎ ﻣرة أﺧرى ‪.‬وﯾﺗم ﻏﻣر ﺑﺋر اﻟﺗﺄرﯾض ﻓﻲ ﺑﺎدئ‬
‫اﻷﻣر ﺑﺎﻟﻣﺎء ﺣﺗﻰ ﯾﺳﺎﻋد ﻋﻠﻰ ﺗﺳرب اﻟﻣواد اﻟﻛﯾﻣﯾﺎﺋﯾﺔ ﻟﻠﺗرﺑﺔ أﻣـﺎ ﺑﻌـد ذﻟـك ﻓـﺈن ﻣﯾـﺎﻩ اﻷﻣطـﺎر‬
‫ﻛﺎﻓﯾﺔ ﻟﻠﻘﯾﺎم ﺑﻬذﻩ اﻟﻌﻣﻠﯾﺔ‪.‬‬

‫اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ ﻟﻠﺗرﺑﺔ ‪:‬‬

‫ﺗﺧﺗﻠف اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ ﻟﻠﺗرﺑﺔ ﺣﺳب ﻧوﻋﻬﺎ ودرﺟـﺔ اﻟرطوﺑـﺔ وﻓـق ﻣـﺎ ﯾﺗﺿـﺢ ﻣـن اﻟﺟـدول‬
‫اﻟﺗﺎﻟﻲ ‪:‬‬

‫‪٣٤‬‬
‫اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ‬

‫اﻟﻘﯾﻣﺔ‬ ‫اﻟﻘﯾﻣﺔ‬ ‫ﻧوع اﻟﺗرﺑﺔ‬


‫اﻟوﺳطﯾﺔأوم ‪.‬‬ ‫اﻟﺗﻘرﯾﺑﯾﺔأوم ‪.‬‬
‫ﻣﺗر‬ ‫ﻣﺗر‬

‫‪٣٠‬‬ ‫‪٥٠ – ١٠‬‬ ‫ﺗرﺑﺔ رطﺑﺔ‬

‫‪١٠٠‬‬ ‫‪٢٠٠ – ٢٠‬‬ ‫ﺗرﺑﺔ طﯾﻧﯾﺔ زراﻋﺔ‬

‫‪٤٥٠‬‬ ‫‪٦٠٠ – ٢٠٠‬‬ ‫ﺗرﺑﺔ رﻣﻠﯾﺔ رطﺑﺔ ﻋﻣق ‪ ٢‬ﻣﺗر‬

‫‪١٠٠٠‬‬ ‫‪١٥٠٠ -٥٠٠‬‬ ‫ﺗرﺑﺔ رﻣﻠﯾﺔ ﺟﺎﻓﺔ‬

‫‪١٥٠٠‬‬ ‫‪٢٠٠٠ -٢٠٠‬‬ ‫ﺻﺧر ﺟﺎﻣد ﻋﻣق ‪ ٢‬ﻣﺗر‬

‫‪٣٠٠٠‬‬ ‫‪٨٠٠ – ٣٠٠‬‬ ‫ﺗرﺑﺔ ﺣﺟرﯾﺔ‬

‫ﻣﻘﺎوﻣﺔ ﻋﺎﻟﯾﺔ‬
‫ﺗرﺑﺔ ﺻﺧرﯾﺔ‬
‫ﺟداً‬

‫اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻲ اﻟﻣﺳﻣوح ﺑﻣرورﻩ ﻓﻲ ﻣوﺻل اﻟﺗﺄرﯾض ‪:‬‬

‫اﻟﺗﯾﺎر اﻟﻠﺣظﻲ اﻟﻣﺳﻣوح‬


‫اﻟﺗﯾﺎر اﻟﻣﺳﻣوح ﺑﻣرورﻩ ﻣدة‬ ‫ﻣﻘطﻊ‬
‫ﺑﻣرورﻩ ﺧﻼل ﺛﺎﻧﯾﺔ واﺣدة‬
‫طوﯾﻠﺔ ﺑﺎﻷﻣﺑﯾر‬ ‫ﻣوﺻل‬
‫ﺑﺎﻷﻣﺑﯾر‬
‫اﻟﺗﺄرﯾض‬
‫)ﻣم‪(٢‬‬
‫أﻟﻣﻧﯾوم‬ ‫ﻧﺣﺎس‬ ‫أﻟﻣﻧﯾوم‬ ‫ﻧﺣﺎس‬

‫‪-‬‬ ‫‪٢٥٠٠‬‬ ‫‪-‬‬ ‫‪١٥٠‬‬ ‫‪١٦‬‬

‫‪٢٧٠٠‬‬ ‫‪٤٠٠٠‬‬ ‫‪١٦٠‬‬ ‫‪٢٠٠‬‬ ‫‪٢٥‬‬

‫‪٣٥‬‬
‫‪٣٧٠٠‬‬ ‫‪٥٥٠٠‬‬ ‫‪٢٠٠‬‬ ‫‪٢٨٠‬‬ ‫‪٣٥‬‬

‫‪٥٣٠٠‬‬ ‫‪٨٠٠٠‬‬ ‫‪٢٥٠‬‬ ‫‪٤٨٠‬‬ ‫‪٥٠‬‬

‫‪٧٤٠٠‬‬ ‫‪١١٥٠٠‬‬ ‫‪٣٢٠‬‬ ‫‪٥٩٠‬‬ ‫‪٧٠‬‬

‫‪١٠٥٠٠‬‬ ‫‪١١٦٠٠‬‬ ‫‪٤٣٠‬‬ ‫‪٧٨٠‬‬ ‫‪٩٥‬‬

‫‪٢١٠٠٠‬‬ ‫‪٣٢٥٠٠‬‬ ‫‪٧٦٠‬‬ ‫‪١٣٨٠‬‬ ‫‪١٨٥‬‬

‫اﻟﺣﻣﺎﯾﺔ ﻣن ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ ‪:‬‬

‫‪ -١‬ﻗواطﻊ اﻟﺣﻣﺎﯾﺔ ﻣن ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ ‪:‬‬

‫ﯾﺗم ﺣﻣﺎﯾﺔ اﻟدواﺋر اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻔرﻋﯾﺔ ﺑﻘواطـﻊ ﻓرﻋﯾـﺔ ﻋﺎدﯾـﺔ ﺳـﻌﺔ ‪ ١٥‬أﻣﺑﯾـر أو ‪ ٢٠‬أﻣﺑﯾـر إﻻ‬
‫أﻧﻬــﺎ ﻗﯾﻣــﺔ ﻣرﺗﻔﻌــﺔ ﺟــداً ﺑﻣﻘﺎرﻧﺗﻬــﺎ ﺑﻣــﺎ ﯾﻧــﺗﺞ ﻋﻧﻬــﺎ ﻣــن أﺧطــﺎر ﺣﯾــث أن ﻣــرور ﺗﯾــﺎر ﻛﻬرﺑــﺎﺋﻲ‬
‫ﺻﻐﯾر ﻓﻲ ﺣدود ‪ ٦٠‬ﻣﻠﻠﻲ أﻣﺑﯾر ﻓﻲ ﺟﺳم اﻹﻧﺳﺎن ﯾﺳﺑب وﻓﺎﺗﻪ‪.‬‬

‫وﻟﻬــذا ﯾﻔﺿــل اﺳــﺗﺧدام ﻗواطــﻊ اﻟﺣﻣﺎﯾــﺔ ﻣــن ﺗﯾــﺎر اﻟﺗﺳــرب اﻷرﺿــﻲ ‪ ،‬وﻫــذﻩ اﻟﻘواطــﻊ ﻣﻣﺎﺛﻠــﺔ‬
‫ﻟﻠﻘواطﻊ اﻟﻌﺎدﯾﺔ ﻣن ﺣﯾث اﻟﺷﻛل إﻻ أﻧﻬﺎ ﺣﺳﺎﺳﺔ ﺟداً ﻟﻣرور اﻟﺗﯾـﺎر اﻟﻛﻬرﺑـﺎﺋﻲ )ﻣﻬﻣـﺎ ﺻـﻐرت‬
‫ﻗﯾﻣﺗﻪ( ﻓﻲ أي ﻣﺳﺎر ﯾﺧﺗﻠف ﻋن اﻟﻣوﺻـل اﻟﻣﺣـدد ﻟﻣـرورﻩ ﻛـﺎن ﯾﻛـون ﻫـذا اﻟﻣﺳـﺎر ﻣـن ﺧـﻼل‬
‫ﺟﺳم اﻹﻧﺳﺎن ﻣﺛﻼً‪ .‬وﻓﻲ ﻫذﻩ اﻟﺣﺎﻟﺔ ‪ ،‬ﻋﻧد ﻣـرور ﺗﯾـﺎر ﺑﺳـﯾط ﻗـد ﯾﺻـل إﻟـﻰ ﺟـزء ﻣـن اﻟﻣﻠﻠـﻲ‬
‫أﻣﺑﯾر ﻓﺈن ﻫذا اﻟﻧوع ﻣن اﻟﻘواطﻊ ﯾﻔﺻل اﻟداﺋرة ‪.‬‬

‫‪ -٢‬أﻧواع ﻗواطﻊ اﻟﺣﻣﺎﯾﺔ ﻣن ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ ‪:‬‬

‫ﻟﻬذﻩ اﻟﻘواطﻊ ﻧوﻋﺎن ‪:‬‬

‫‪٣٦‬‬
‫اﻟﻧوع اﻷول ‪ :‬ﯾﺳﺗطﯾﻊ ﻓﺻل اﻟداﺋرة ﻋﻧدﻣﺎ ﺗﻛون ﻗﯾﻣﺔ اﻟﺗﯾﺎر اﻟﻣﺎر ﻓﯾﻬﺎ ﺑﺣدود ‪ ٦‬ﻣﻠﻠﻲ أﻣﺑﯾر‪.‬‬

‫اﻟﻧوع اﻟﺛﺎﻧﻲ ‪:‬ﯾﺻـﻠﺢ ﻟﻔﺻـل اﻟـدواﺋر اﻟﺗـﻲ ﯾزﯾـد ﺗﯾﺎرﻫـﺎ ﻋـن ‪ ٢٠‬ﻣﻠﻠـﻲ أﻣﺑﯾـر وﯾوﺻـﻲ )‪(NEC‬‬
‫ﺑﺎﺳــﺗﺧدام ﻗواطــﻊ اﻟﺣﻣﺎﯾــﺔ ﻣــن ﺗﯾــﺎر اﻟﺗﺳــرب اﻷرﺿــﻲ ﻓــﻲ ﺑﻌــض اﻟــدواﺋر اﻟﻛﻬرﺑﺎﺋﯾــﺔ ﻟﻠﻣﺑــﺎﻧﻲ‬
‫اﻟﺗﺟﺎرﯾﺔ واﻟﺳﻛﻧﯾﺔ وﺧﺎﺻﺔ اﻟﻣوﺟودة ﻓﻲ اﻷﻣﺎﻛن اﻟﻣﺑﺗﻠﺔ‪.‬‬

‫‪ -٣‬اﻟﻌﻼﻗﺔ ﺑﯾن ﺷدة ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ وﻣدة ﺳرﯾﺎﻧﻪ ﻓﻲ ﺟﺳم اﻹﻧﺳﺎن ‪.‬‬

‫ﻓﯾﻣﺎ ﯾﻠﻲ ﺟدول ﯾوﺿﺢ ﺗﺄﺛﯾر ﻣرور ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ ﻓﻲ ﺟﺳم اﻹﻧﺳﺎن ‪:‬‬

‫اﻟﺗﺄﺛﯾر اﻟﺑﯾوﻟوﺟﻲ ﻋﻠﻰ ﺟﺳم اﻹﻧﺳﺎن‬ ‫ﻣدة ﺳرﯾﺎن‬ ‫ﺗﯾﺎر اﻟﺗﺳرﺑﻣﻠﻠﻲ‬


‫اﻟﺗﯾﺎر‬ ‫أﻣﺑﯾر‬

‫اﻟﺗﯾﺎر ﻏﯾر ﻣﺣﺳوس وﻟﯾس ﻟﻪ ﺗﺄﺛﯾر‬ ‫ﻣﺳﺗﻣر‬ ‫‪٠.٥ – ٠‬‬

‫ﯾﺑدأ اﻟﺟﺳم ﺑﺎﻹﺣﺳﺎس ﺑﺎﻟﺗﯾﺎر وﯾﻣﻛن‬ ‫ﻣﺳﺗﻣر‬ ‫‪٥ – ٠.٥‬‬


‫ﻟﻺﻧﺳﺎن اﻟﺗﺧﻠص ﻣن اﻟﻣﺻدر إﻻ أﻧﻪ‬
‫ﯾﺗرك آﺛﺎ ارً ﻓﻲ ﻣﻛﺎن اﻟﺗﻼﻣس‬

‫ﯾﺻﻌب اﻻﻧﻔﺻﺎل ﻋن ﻣﺻدر اﻟﻛﻬرﺑﺎء‬ ‫ﻋدة دﻗﺎﺋق‬ ‫‪٣٠ – ٥‬‬


‫وﯾﺳﺑب ارﺗﻔﺎع ﺿﻐط اﻟدم وﺿﯾق‬
‫ﺗﻧﻔس‬

‫ﻋدم اﻧﺗظﺎم ﻧﺑض اﻟﻘﻠب – ﯾرﺗﻔﻊ ﺿﻐط‬ ‫ﺑﺿﻊ ﺛواﻧﻲ‬ ‫‪٥٠ – ٣٠‬‬
‫اﻟدم ﻣﻊ إﻏﻣﺎء‬

‫اﻟﺷﻌور ﺑﺻدﻣﺔ ﻗوﯾﺔ‬ ‫أﻗل ﻣن ﻣدة‬ ‫‪ – ٥٠‬ﻋدة‬


‫اﻟﻧﺑﺿﺔ‬ ‫ﻣﺋﺎت‬

‫إﻏﻣﺎء ﻣﻊ ظﻬور آﺛﺎر ﻋﻧد ﻧﻘط‬ ‫أطول ﻣن ﻣدة‬


‫اﻟﺗﻼﻣس‬ ‫اﻟﻧﺑﺿﺔ‬

‫إﻏﻣﺎء ﻣﻊ ظﻬور آﺛﺎر ﻋﻧد ﻧﻘط‬ ‫أﻗل ﻣن ﻣدة‬ ‫أﻛﺛر ﻣن ﻋدة‬


‫اﻟﺗﻼﻣس‬ ‫اﻟﻧﺑﺿﺔ‬ ‫ﻣﺋﺎت‬

‫إﻏﻣﺎء – ﻣوت أو ﺣرﯾق‬ ‫أطول ﻣن ﻣدة‬

‫‪٣٧‬‬
‫اﻟﻧﺑﺿﺔ‬

‫‪ -٤‬أﻣﺎﻛن ﺗرﻛﯾب ﻗواطﻊ اﻟﺣﻣﺎﯾﺔ ﺿد اﻟﺗﺳرب اﻷرﺿﻲ )‪: (Elcb‬‬

‫أ( ﯾﻣﻛــن أن ﯾوﺿــﻊ ﻗــﺎطﻊ )‪ (Elcb‬ﻋﻠــﻰ اﻟﺧــط اﻟرﺋﯾﺳــﻲ ﻟﻠوﺣــﺔ اﻟﺗوزﯾــﻊ وﻓــﻲ ﻫــذﻩ اﻟﺣﺎﻟــﺔ‬
‫ﺗﻛون ﺣﻣﺎﯾﺗﻪ ﺷﺎﻣﻠﺔ ﻟﺟﻣﯾﻊ اﻟدواﺋر ‪.‬‬

‫وﻣن ﻣﺳﺎويء ﻫذﻩ اﻟطرﯾﻘﺔ أﻧﻪ ﻟو ﻛﺎن ﻫﻧﺎك أي ﺗﺳرب ﻟﻸرض ﻣن وﺣدة إﺿﺎءة ﻣﺛﻼً ﻓـﺈن‬
‫ذﻟك ﯾﺗﺳﺑب ﻓﻲ ﻗطﻊ اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻲ ﻋن ﻛل اﻟﻠوﺣﺔ‪.‬‬

‫ب( أن ﯾﻛــون ﻫﻧــﺎك ﻟوﺣﺗــﺎن ﻣﺗﺟﺎورﺗــﺎن إﺣــداﻫﻣﺎ ﻟﻺﺿــﺎءة واﻷﺧــرى ﻟﻠﻘــوى وﯾوﺿــﺢ ﻗــﺎطﻊ‬
‫)‪ (Elcb‬ﻗﺑــل ﻟوﺣــﺔ اﻟﻘــوى ﺑﺣﯾــث ﯾﺣﻣــﻲ ﻓﻘــط اﻷﺟﻬــزة واﻵﻻت اﻟﻛﻬرﺑﺎﺋﯾــﺔ اﻟﺗــﻲ ﺗﺗﺻــل ﺑــدواﺋر‬
‫اﻟﻘوى‪.‬‬

‫‪٣٨‬‬
‫ج( ﯾﻣﻛــن أن ﯾﺳــﺗﺧدم ﻗــﺎطﻊ )‪ (Elcb‬ﻟﺣﻣﺎﯾــﺔ ﺟﻬــﺎز ﻣﻌــﯾن ﻓﻘــط ﻛﻐﺳــﺎﻟﺔ ﻣــﺛﻼً وﯾــﺗم ذﻟــك‬
‫ﺑﺗوﺻﯾﻠﺔ ﻗﺑل اﻟﻣﺂﺧـذ اﻟﻛﻬرﺑﺎﺋﯾـﺔ )اﻟﺑرﯾـزة( واﻟﻐﺳـﺎﻟﺔ أو أي ﺟﻬـﺎز آﺧـر ﯾـراد ﺣﻣﺎﯾﺗـﻪ ﺑﺷـرط أن‬
‫ﯾﺗم ﺗوﺻﯾل اﻟﺟﻬﺎز ﺑﺎﻷرض ‪.‬‬

‫ﻛﻣﺎ ﯾﻣﻛن أن ﯾﺳﺗﺧدم ﻟﺣﻣﺎﯾﺔ ﺟزء ﻣن ﺳﻛن أو ﻣﺑﻧﻰ أو ﻓراﻏﺎت ﻣﻌﯾﻧﺔ‬

‫‪٣٩‬‬
٤٠
٤١
‫أﻧظﻣﺔ اﻟﺗﺄرﯾض اﻟوﻗﺎﺋﻰ ‪:‬‬

‫اﻟﻐرض ﻣﻧﻪ‪:‬‬
‫‪ -١‬ﺣﻣﺎﯾﺔ اﻷﻓراد )ﻣواطﻧﯾن – ﻋﻣﺎل ( ﻣن اﻟﺻدﻣﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ‪.‬‬
‫‪ -٢‬ﺣﻣﺎﯾﺔ اﻟﻣﻌدات اﻟﻛﻬرﺑﯾﺔ واﻟﻣﻧﺷﺂت ﻣن اﻟﺗﻠف‪.‬‬
‫‪ -٣‬ﻣﻧﻊ ﺟﻬد اﻟﺟﺳم ﻣن اﻹرﺗﻔﺎع إﻟﻰ ﻗﯾﻣﺔ ﻗد ﺗﺷﻛل ﺧطر ﻋﻠﻰ اﻹﻧﺳﺎن‪.‬‬
‫‪ -٤‬اﻟﺳﻣﺎح ﺑﻣرور ﺗﯾﺎر ﻟﻸرض ﻟﻪ ﻗﯾﻣﺔ ﻛﺎﻓﯾﺔ ﻟﺗﺷﻐﯾل اﻷﺟﻬزة اﻟوﻗﺎﺋﯾﺔ )ﻣﺻﻬرات – ﻗواطﻊ(‬
‫أو أﺟﻬزة اﻟوﻗﺎﯾﺔ ﺑﻪ ﻟﻠﺗﺳرب اﻷرﺿﻰ‪.‬‬

‫* ﻣﻛوﻧﺎت اﻟﺗﺄرﯾض اﻟوﻗﺎﺋﻰ‪:‬‬

‫‪ -١‬اﻷرض وﻫﻰ اﻟﺗرﺑﺔ اﻟﺗﻰ ﯾوﺿﻊ ﻓﯾﻬﺎ اﻟﻛﺗرودات اﻟﺗﺄرﯾض‪.‬‬


‫‪ -٢‬اﻟﻛﺗرودات اﻟﺗﺄرﯾض )ﻗد ﯾﻛون ﻗﺿﯾب أو أﺳﻼك ﻣدﻓوﻧﺔ أﻓﻘﯾﺎ أو اﻟواح ﻣﻌدﻧﯾﺔ( ﻓﻰ ﺑﺎطن‬
‫اﻷرض‪.‬‬
‫‪ -٣‬ﻣوﺻﻼت اﻟﺗﺄرﯾض ‪:‬‬
‫أ( اﻷرﺿﻰ اﻟﺛﺎﺑت ‪:‬‬
‫ﻫو اﻷرﺿﻰ اﻟﻣرﻛب ﻋﻠﻰ اﻟﻣﻌدات اﻟﺗﻰ ﯾﺗم ﺗوﺻﯾﻠﻪ ﺑواﺳطﺔ ﺳﻛﺎﻛﯾن ﺑﻧﺎء ﻋﻠﻰ اﻟﺗﻌﻠﯾﻣﺎت‬
‫وﻫو ﯾﻌرف ﺑﺎﻷرﺿﻰ اﻟرﺋﯾﺳﻰ‪.‬‬
‫ب( اﻷرﺿﻰ اﻹﺿﺎﻓﻰ ‪:‬‬
‫) ﻣؤﻗت ‪ -‬اﻟﻣوﺿﻌﻰ( ﻫو أرﺿﻰ ﻣن ﻧوع ﻣﻌﺗﻣد ﯾوﺿﻊ ﻓﻰ اﻷﻣﺎﻛن اﻟﻣﺣددة ﺑﺄﻣر ﺷﻐل )ﻗﺑل‬
‫وﺑﻌد ﻣﻧطﻘﺔ اﻟﻌﻣل(‬

‫أﺳﺑﺎب ﻋﻣل اﻷرﺿﻰ اﻟﻣؤﻗت )اﻟﻣوﺿﻌﻲ( ‪:‬‬

‫ﯾﺗم ﻋﻣل ﻗﺻر ﻋﻠﻰ ﺟﻣﯾﻊ اﻷوﺟﻪ وﺗﺄرﯾﺿﻬﺎ ﺑﺄرﺿﻰ ﻣؤﻗت ﺑﻌد ﻓﺻل اﻟﺗﯾﺎر أﺛﻧﺎء اﺟراء‬
‫اﻟﺻﯾﺎﻧﺔ أو أﺛﻧﺎء ﻋﻣل اﻟﻣﻧﺎورة اﻟـﻼزﻣﺔ ﻟﺗﺣدﯾد اﻟﻌطل وذﻟك ﻗﺑل وﺑﻌد ﻣﻧطﻘﺔ اﻟﻌﻣل ﻟﺣﻣﺎﯾﺔ‬
‫اﻟﻌﺎﻣﻠﯾن ﺿد ﻋودة اﻟﺗﯾﺎر ﺑطرﯾق ﺧﺎطﻰء أو أى ﺳﺑب أﺧر‪.‬‬
‫وﺑﺗﺣﻠﯾل أﺳﺑﺎب اﻟﺣوادث اﻟﺗﻰ ﺗﺗﺳﺑب ﻓﻰ وﻓﺎة اﻟﻌﺎﻣﻠﯾن ﻧﺟد أﻧﻪ ﻟم ﯾﺗم ﻋﻣل ﻫذا اﻟﻧوع ﻣن‬

‫‪٤٢‬‬
‫اﻷرﺿﻰ ﻗﺑل وﺑﻌد ﻣﻧطﻘﺔ اﻟﻌﻣل‪.‬‬

‫‪ ‬اﻟﺗﺄرﯾض اﻟﻣﺣﻠﻰ ‪: Earthing Local‬‬


‫ﯾﺗم اﻟﺗﺄرﯾض اﻟﻣﺣﻠﻰ ﺑﺎﻟﻣوﻗﻊ اﻟﻌﺎم ﻓﻰ اﻷﺑﻧﯾﺔ اﻟﻛﺑﯾرة أو ﻋﻠﻰ ﻣﺳﺎﻓﺎت‬
‫ﻣﺗﺑﺎﯾﻧﺔ ﻓﻰ اﻟﻣدن ﺣﺗﻰ ﺗﻣﻧﻊ ﻣن إرﺗﻔﺎع ﺟﻬد ﻧﻘطﺔ اﻟﺗﻌﺎدل ﻋن اﻟﻘﯾﻣﺔ‬
‫اﻟﻣﺳﻣوح ﺑﻬﺎ و ﯾﺗم ذﻟك ﻣن ﺧﻼل ﺛرى ﻗطﺑﺎ ﻧﺣﺎﺳﯾﺎ أو ﻋددا ﻣﺗوازﯾﺎ‬
‫ﻣﻧﻬﺎ داﺧل اﻷرض ﻋﻠﻰ ﻋﻣق ﻛﺑﯾر ﻣن ﺳطﺢ اﻷرض و طﺑﻘﺎ‬
‫ﻟﻠﻣواﺻﻔﺎت و ﯾﺗم اﺧﺗﯾﺎرﻩ ﻧﺣﺎﺳﯾﺎ اﻟﻣﺎدة ﻷن ﻣﻘﺎوﻣﺗﻪ اﻟﻧوﻋﯾﺔ أﻗل ﻣن‬
‫ﺑﻘﯾﺔ اﻟﻣﻌﺎدن ﺑﺎﻟرﻏم ﻣن أن اﻟذﻫب أﻗل ﻓﻰ اﻟﻘﯾﻣﺔ إﻻ أﻧﻪ ﺑﺎﻫظ اﻟﺗﻛﻠﻔﻪ‬
‫و ﻗد ﯾﺷﻛل ﺧطورة ﻟﺗﻌرﺿﻪ ﻟﻠﺳرﻗﻪ إذا ﻣﺎ ﺗم اﺳﺗﻌﻣﺎﻟﻪ‪.‬‬

‫ﯾﺻﻠﺢ ﻫذا اﻟﻧوع ﻣن اﻟﺗﺄرﯾض ﻟﻠﻣﻧﺎطق اﻟﺻﻧﺎﻋﯾﺔ اﻟﺻﻐﯾرة و ﻟﻠﻣﯾﺎﻧﻰ‬


‫ﺿﺧﻣﺔ اﻻﺳﺗﻬﻼك اﻟﻛﻬرﺑﻰ ﻋﻼوﻩ ﻋﻠﻰ أﻧﻪ ﻫﺎم ﻟﻠﻣﻧﺎزل اﻟﺻﻐﯾرة أﯾﺿﺎ و‬
‫ﻟﻛﻧﻪ ﻻﺑد و أن ﯾﻧﺑﻊ ﻋن ﻣﺗﺧﺻﺻﯾن )ﺷرﻛﺎت اﻟﻛﻬرﺑﺎء( ﺣﺗﻰ ﺗﺻﺑﺢ‬
‫اﻟﻌﻣﻠﯾﺔ دون ﻣﻘﻧﻧﺎت و ﻧﺻل إﻟﻰ اﻟﻔوﺿﻰ اﻟﺗﺄرﯾﺿﯾﺔ و ﻫو ﻣﺎ ﻻ ﯾﺟب‬
‫أن ﯾﺳﻣﺢ ﺑﺣدوﺛﻪ ﺧﺻوﺻﺎ و أن ﻫذا اﻟﺗﺄرﯾض ﻗد ﯾؤﺛر ﺑطرﯾق ﻏﯾر‬
‫ﻣﺑﺎﺷر ﻋﻠﻰ ﻗﯾﻣﺔ اﻟﺗﯾﺎرات اﻟﻘﺻرﯾﺔ اﻟﺗﻰ ﺗﻣر ﺑﺎﻟﻣﻔﺎﺗﯾﺢ اﻟﻛﻬرﺑﯾﺔ و ﺗزﯾد‬
‫ﺑﻘدر ﻏﯾر ﻣﺣﺳوب و ﯾﻔوق ﺣدود ﺗﺷﻐﯾﻠﻬﺎ ﻓﺗؤدى إﻟﻰ ﺗدﻣﯾرﻫﺎ ‪.‬‬

‫ﻗد ﯾﺗﺳﺎءل اﻟﺑﻌض ﻋن اﻟﺳﺑب ﻓﻰ اﺣﺗراق ﻣﻔﺗﺎح ام ﯾﺗم ﺗﻔﺳﯾرﻩ و ﯾﻛون‬


‫ﻧﺗﯾﺟﺔ أﻧﻪ ﻗد ﺗم وﺿﻊ ﺗﺄرﯾض ﻣﺣﻠﻰ ﻓﺄﺛر ﻋﻠﻰ ﻗﯾﻣﺔ اﻟﺗﯾﺎرات ﺻﻔرﯾﺔ‬
‫اﻟطور ﺑﺎﻷرض ﻣزﯾدا ﻗﯾﻣﺗﻬﺎ ﺧﺻوﺻﺎ و اﻧﻪ ﻋﻧد ﺗﺻﻣﯾم اﻟﺷﺑﻛﺎت ﯾﺗم‬
‫ﻗطﻊ ﻣﺳﺎرات ﻫذﻩ اﻟﺗﯾﺎراﺗﺣﺗﻰ ﺗﺻﺑﺢ اﻟداﺋرة ﺻﻔرﯾﺔ اﻟطور ﻏﯾر ﻣﺣﺳوﺑﻪ‬
‫ﻋﻠﻰ اﻹطﻼق ﻓﺗﻘل ﻗﯾم اﻟﺗﯾﺎرات اﻟﺗﻰ ﻧﺣﺗﺎج إﻟﻰ ﻗطﻌﻬﺎ ﻣن ﺧﻼل‬
‫اﻟﻣﻔﺎﺗﯾﺢ اﻟﻛﻬرﺑﯾﺔ ‪،‬و ﻫﻛذا ﻧﺟد أﻧﻛﺛرة ﻫذة اﻟﻧﻘﺎط اﻟﺗﺄرﯾﺿﯾﺔ ﯾﺳﻣﺢ‬
‫ﺑﻣرور اﻟﺗﯾﺎرات ﺻﻔرﯾﺔ اﻟطور ﺑﯾﻧﻬﺎ ﻣزﯾدا ﻣن ﻗدرة اﻟﺗﯾﺎرات اﻟﻘﺻرﯾﺔ و‬
‫ﻫو ﻣﺎ ﯾﻠزم إﻋﺗﺑﺎرﻩ ﻋﻧد اﻟﺗﺻﻣﯾم أﯾﺿﺎ ﻻﺣﺗواء اﻟﺗﺄرﯾض اﻟﻣﺳﺗﻘﺑﻠﻰ ﻓﻰ‬
‫اﻟﻣﻧطﻘﺔ اﻟﺗﻰ ﺗﺗﺄﺛر ﺑذﻟك اﻟﻣوﺿوع ‪.‬‬

‫* ﺷﺑﻛﺔ اﻟﺗﺄرﯾض ‪:‬‬

‫‪٤٣‬‬
‫ﻧﺟد أن اﻟﻣﻧﺎطق ﻛﺑﯾرة اﻻﺳﺗﺧدام و ﻟﯾس اﻻﺳﺗﻬﻼك ﻣﺛل ﻣﺣطﺎت‬
‫اﻟﺗوﻟﯾد أو ﻣﺣطﺎت اﻟﻣﺣوﻻت ﻋﺎﻟﯾﻪ و ﻓﺎﺋﻘﺔ اﻟﺟﻬد أﻛﺛر ﺗﻌرﺿﺎ ﻟﺗﯾﺎرات‬
‫اﻟﻘﺻر و ﺗﺄﺛﯾرﻫﺎ اﻟﺧطر وﻟذﻟك ﻧﺟد أن ﻫذﻩ اﻟﻣﺣطﺎت ﺗﺧﺿﻊ ﻟﻧظﺎم أﺧر‬
‫ﻣن اﻟﺗﺄرﯾض وﻫو اﻟﻣﻌروف ﺑﺎﺳم ﺷﺑﻛﺔ اﻟﺗﺄرﯾض ﺣﯾث ﺗﻛون اﻟﺗﯾﺎرات‬
‫اﻟﻘﺻرﯾﺔ ﻫﺎﺋﻠﺔ اﻟﻘﯾﻣﺔ وﺗﻌطﻰ ﺟﻬدا ﺧط ار ﻣﻊ أﻗل اﻟﻣﻘﺎوﻣﺎت وﯾﻛون‬
‫ﻓوق اﻟﺗﺻور إذا ﻣﺎ أﻫﻣل ﻫذا اﻟﺑﻧد وﯾﻛون اﻟﺿﺣﯾﺔ ﻫم اﻟﻌﺎﻣﻠون ﻓﻰ‬
‫اﻟﻣﺣطﺔ أو اﻟﻣﺗواﺟدﯾن أﺣﯾﺎﻧﺎ‪.‬‬

‫ﻋﻠﻰ اﻟﺟﺎﻧب اﻟﺗﻘﻧﻰ ﻓﺈن ﻫذﻩ اﻟﻣﺷﻛﻠﺔ ﺳﻬﻠﺔ اﻟﺣل ﺣﯾث ﯾﺗم وﺿﻊ‬
‫ﻣﻘﺎوﻣﺔ ﺗﺄرﯾض ﻣﺗﻧﺎﻫﯾﺔ اﻟﺻﻐر وﻫو ﻣﺎ ﯾﻣﻛن ﺗﺣﻘﯾﻘﺔ ﻣن ﺧﻼل اﻟﻘﺎﻋدة‬
‫اﻟﺑﺳﯾطﺔ اﻟﺗﻰ ﺗﻘﻠل ﻗﯾﻣﺔ اﻟﻣﻘﺎوﻣﺔ وذﻟك ﻣن ﺧﻼل اﻟﺗوﺻﯾﻼت ﺗوازى‬
‫ﻟﻠﻣﻘﺎوﻣﺎت ﻓﻌﻧد ﺗوﺻﯾل ﻣﻘﺎوﻣﺗﺎن ﻣﺗﺳﺎوﯾﺗﺎن ﻣﻌﺎ ﻋﻠﻰ اﻟﺗوازى ﺗﻘل‬
‫اﻟﻘﯾﻣﺔ اﻟﻔﻌﻠﯾﺔ ﻟﻬﻣﺎ ﻣﻌﺎ إﻟﻰ اﻟﻧﺻف إﻣﺎ اﻟﺛﻼث ﻓﺗﻛون اﻟﺛﻠث وﻫﻛذا وﻣن‬
‫ﻫﻧﺎ أﻣﻛن اﻟﺧروج ﻣن اﻟﻣﺄزق اﻟﺧطﯾر وﻣﻌﺎﻟﺟﺔ ﻗﯾﻣﺔ ﻣﻘﺎوﻣﺔ اﻷرﺿﻰ‬
‫ﻟﺗﺻﺑﺢ أﻗل ﻣﺎ ﯾﻣﻛن ﻣن ﺧﻼل وﺿﻊ ﺷﺑﻛﺔ أﻓﻘﯾﺔ ﺗﺣت ﺳطﺢ اﻷرض‬
‫ﻧﺣﺎﺳﯾﺔ طﺑﻌﺎ ﯾﺧرج ﻣﻧﻬﺎ أﻗطﺎﺑﺎ رأﺳﯾﺔ ﻟﺗﻛون ﻓﻰ ﺣﻛم اﻟﺗوﺻﯾل ﻋﻠﻰ‬
‫اﻟﺗوازى ﻓﺗﻘل اﻟﻘﯾﻣﺔ اﻟﻣﺣﺻﻠﺔ ﻟﻬم ﺟﻣﯾﻌﺎ‪.‬‬

‫ﻛﻣﺎ أﻧﻪ ﯾﻣﻛن ﺗﻘﻠﯾل ﻫذﻩ اﻟﻘﯾﻣﺔ اﻟﻣﺣﺻﻠﺔ ﻋﻠﻰ اﻟﺗوازي ﻓﻲ اﻟﺷﺑﻛﺔ‬
‫اﻟﺗﺄرﯾﺿﯾﺔ ﺑﺄن ﺗﺳﺗﻐل اﻷﻗطﺎب اﻟرأﺳﯾﺔ ﻟﯾﺧرج ﻣﻧﻬﺎ ﻋﻠﻰ طول ارﺗﻔﺎﻋﻬﺎ‬
‫ﻋددا أﺧر ﻣن اﻷﻗطﺎب اﻷﺻﻐر ﻟﺗﻛون أﻓﻘﯾﺔ اﻟوﺿﻊ ﻓﺗﺻﺑﺢ ﻛﻠﻬﺎ ﺗوازﯾﻪ‬
‫اﻟﺗوﺻﯾل ﻟﺗﻘل اﻟﻣﻘﺎوﻣﺔ ﻟﻛل ﻗطب رأﺳﻲ وﻧﺻل إﻟﻰ اﻟﺣدود اﻟدﻧﯾﺎ ﻣن‬
‫ﻗﯾﻣﺔ اﻟﻣﻘﺎوﻣﺔ اﻷرﺿﯾﺔ وﻧﻛون ﻗد ﺑﻠﻐﻧﺎ اﻟﻬدف دون ﺗﻛﻠﻔﺔ ﺗذﻛر وﻫذا‬
‫ﻫو ﻣﺎ ﯾﺗم ﺑﺎﻟﻔﻌل ﻓﻲ اﻟﻣﺣطﺎت اﻟﻘﺎﺋﻣﺔ وﻫﻛذا ﯾﻛون ﺟﻬد اﻟﺗﻼﻣس ﻏﯾر‬
‫ﺧطﯾر أو ﺿﺎر وﺗﺻﺑﺢ ﻧﻘطﺔ اﻟﺗﻌﺎدل داﺧل اﻟﻣﺣطﺔ أﻣﻧﺔ وﯾﺳﺗطﯾﻊ اﻟﻔرد‬
‫أن ﯾﺗﻌﺎﻣل ﻣﻌﻬﺎ دون ﺧوف وﺑﺄﻣﺎن ﻛﺎﻣل‪.‬‬

‫‪POWER FACTOR CORRECTION‬‬

‫‪٤٤‬‬
ETERNAL ENGINEERS GROUP
01007200959-01114911166

٤٥
‫ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‬
‫ﯾــؤﺛر اﻧﺧﻔــﺎض ﻣﻌﺎﻣــل اﻟﻘــدرة ﺳــﻠﺑﺎ ﻋﻠــﻰ أداء اﻟﻣﻧظوﻣــﺔ اﻟﻛﻬرﺑﯾــﺔ وﯾﻌﺗﻣــد ذﻟــك ﻋﻠــﻰ‬
‫طﺑﯾﻌـﺔ اﻷﺣﻣـﺎل ﻣـن ﺣﯾـث ﻛوﻧﻬـﺎ أﺣﻣـﺎل ﺧطﯾـﺔ )‪ (Resistive loads‬أو أﺣﻣـﺎل ﺣﺛﯾـﻪ ﻏﯾـر‬
‫ﺧـطﯾــﺔ )‪ ( Inductive loads‬ﻣﺛل ) اﻟﻣﺣوﻻت ‪ ،‬اﻟﻣﺣرﻛﺎت اﻟﺣﺛﯾـﺔ‪ ،‬اﻟﻣﺻـﺎﺑﯾﺢ اﻟﻔﻠورﯾـﺔ ‪،‬‬
‫اﻟﻣوﺣدات ‪ ،‬اﻷﻓران اﻟﻛﻬرﺑﺎﺋﯾﺔ ‪ ،‬أﻓران اﻟﺣث ‪ ... ،‬اﻟﺦ‪ (.‬ﺣﯾث ﺗؤدى اﻟطﺑﯾﻌﺔ ﻏﯾر اﻟﺣﺛﯾـﺔ ﻟﻬـذﻩ‬
‫اﻷﺣﻣﺎل إﻟﻰ ﺗﺑدﯾد ﺟزء ﻣن اﻟطﺎﻗﺔ اﻟﻣﻐذﯾﺔ ﻟﻬﺎ ﻓﻲ ﺻورة ﻗدرة ﻏﯾر ﻓﻌﺎﻟـﺔ ﺗﺳـﺗوﺟب اﻟﻌﻣـل ﻋﻠـﻰ‬
‫اﺳﺗﯾﻌﺎﺑﻬﺎ‪ ،‬وذﻟك ﻋن طرﯾـق ﺗﻌـوﯾض ﻫذا اﻟﺟزء ﺑواﺳطﺔ ﻣﺻدر ﺧﺎرﺟﻲ ﯾﻌﻣل ﻛﻣوﻟد ﻟﻠﻘدرة ﻏﯾر‬
‫اﻟﻔﻌﺎﻟﺔ )‪ (KVAR-Generator‬ﻹﺿﺎﻓﺔ ﻗدرة ﻏﯾر ﻓﻌﺎﻟﺔ ﻟﻣﻧظوﻣﺔ اﻟﻘـدرة اﻟﻛﻬرﺑﺎﺋﯾـﺔ وﯾﻛـون‬
‫ﻋﺎدة ﻋن طرﯾق ﻣﻛﺛف ﯾﺗم ﺗوﺻﯾﻠﻪ ﻋﻠﻰ اﻟﺗوازى ﻣﻊ اﻟﺣﻣل اﻟﻣراد ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ﻟﻪ‪.‬‬
‫ﯾؤدى ﺗرﻛﯾب اﻟﻣﻛﺛف ﻣﻊ اﻷﺣﻣﺎل اﻟﺣﺛﯾﺔ ﻓﻰ ﻧﻔس اﻟداﺋرة إﻟﻰ ﺗﺑﺎدل اﻟﺗﯾـﺎر ﺑﯾﻧﻬﻣـﺎ ﻋﻠـﻰ‬
‫ﻧﺣـو ﯾﺟﻌـل اﻟﺗﯾـﺎر اﻟﻣﺗﻘـدم ) ‪ (Leading current‬اﻟﻣﺳـﺣوب ﺑواﺳـطﺔ اﻟﻣﻛﺛـف ﯾﻌـﺎدل ﺟـزء‬
‫‪ (Lagging‬ﻟﻸﺣﻣــﺎل اﻟﺣﺛﯾ ـﺔ اﻟــﻼزم ﻟﻠﻣﻐﻧطــﺔ ﻓﻠــذا ﯾﻌﺗﺑــر‬ ‫ﻣــن اﻟﺗﯾــﺎر اﻟﻣﺗــﺄﺧر ) ‪current‬‬
‫اﻟﻣﻛﺛف ﻫو اﻷداة اﻷﺳﺎﺳﯾﺔ اﻟﺗﻲ ﺗﺳﺗﺧدم ﻟﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‪ ،‬وﯾﻧﻌﻛس ذﻟك اﻧﻌﻛﺎﺳﺎ إﯾﺟﺎﺑﯾــﺎً‬
‫ﻋﻠﻰ أداء اﻟﻣﻧظوﻣﺔ ﻣن ﺣﯾث ﺗﺧﻔﯾض اﻟطﺎﻗﺔ اﻟﻣﻔﻘـودة ﻓـﻲ اﻟﻛـﺎﺑﻼت واﻟﺧطـوط وزﯾـﺎدة ﺳـﻌﺎﺗﻬﺎ‬
‫ﻋﻧـــد ﻧﻔــس اﻟﺣﻣــل‪ ،‬ﺣﯾــث ﯾﻣﻛــن ﻟﻬــذﻩ اﻟﻛــﺎﺑﻼت واﻟﺧطــوط ﺗﺣﻣــل ﻧﻘــل ﻗــــدرات إﺿﺎﻓﯾــــﺔ ﻷﺣﻣـــﺎل‬
‫‪ (Apparent power‬ﻟـذﻟك اﻟﺣﻣـل‪،‬‬ ‫إﺿﺎﻓﯾــﺔ‪ ،‬ﻛﻣــﺎ ﺗـﻧﺧﻔض اﻟﻘـدرة اﻟظﺎﻫرﯾـﺔ )‪kVA‬‬
‫وﻛذﻟك ﺗزداد اﻟﻘدرة اﻟﻣﺗﺎﺣﺔ ﻓﻲ اﻟﻣﺣوﻻت اﻟﻣﺳـﺗﺧدﻣﺔ ﻓـﻲ اﻟﺷـﺑﻛﺔ وﺗﺗﺣﺳـن اﻟﺟﻬـود ﻋﻧـد ﻣراﻛـز‬
‫اﻷﺣﻣﺎل‪.‬‬
‫وﺑذﻟك ﯾﻛـون ﻟﺗﺣﺳـﯾن ﻣﻌﺎﻣـل اﻟﻘـدرة ﻓـﻲ ﻣﻧظوﻣـﺔ ﻧﻘـل وﺗوزﯾـﻊ اﻟﻘـوى اﻟﻛﻬرﺑﺎﺋﯾـﺔ ﻓﺎﺋـدة‬
‫ﻗﺻــوى ﺣﯾــث ﯾﺗــﯾﺢ اﻻﺳــﺗﻔﺎدة ﻣــن ﻓــﺎﺋض اﻟﺳــﻌﺔ ﻟﻣﻬﻣــﺎت اﻟﺷــﺑﻛﺎت اﻟﻘﺎﺋﻣــﺔ ﻓــﻲ ﺗﻐذﯾــﺔ أﺣﻣــﺎل‬
‫إﺿﺎﻓﯾﺔ دون اﻟﺣﺎﺟﺔ إﻟﻰ ﺗوﺳـﻌﺗﻬﺎ أو إﻋـﺎدة ﻫﯾﻛﻠﺗﻬـﺎ‪ ،‬وﻛـذﻟك إﻟـﻰ ﺗـوﻓﯾر ﻧﻔﻘـﺎت إﻧﺷـﺎء ﺷـﺑﻛﺎت‬
‫ﺟدﯾدة وﺗوﺟﯾﻬﻬﺎ ﻻﺳﺗﺛﻣﺎرات أﺧرى ﻋﻠﻰ اﻟﻣﺳﺗوى اﻟﻘوﻣﻲ‪.‬‬

‫ﺗﻌوﯾض اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻓﻰ ﺷﺑﻛﺎت اﻟﺗوزﯾﻊ‬


‫)‪(Reactive power compensation‬‬
‫ﺗﺗﻠﺧص وﺳﺎﺋل ﺗﻌوﯾض اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻓﯾﻣﺎ ﯾﻠﻰ‪:‬‬
‫‪ -‬ﯾﻌﻣـل ﻫــذا اﻟﺗﻌــوﯾض ﻋﻠـﻰ اﻟﺣــد ﻣــن ﻗﯾﻣـﺔ اﻟﺗﯾــﺎر ﻏﯾــر اﻟﻔﻌـﺎل ﻟﺗﺷــﻐﯾل اﻷﺣﻣــﺎل‬
‫اﻟﺣﺛﯾــﺔ اﻟﺗــﻲ ﺗﺳــﺗﻬﻠك ﻗــدرة ﻏﯾــر ﻓﻌﺎﻟــﺔ ﻛﺑﯾــرة وﺟﻌــل ﻫــذا اﻟﺗﯾــﺎر ﻓــﻲ ﺣــدﻩ اﻷدﻧــﻰ‪،‬‬
‫وﯾﺗﺣﻘـــق ذﻟـــك ﻟﻠﻣﻌـــدات اﻟﺣﺛﯾـــﺔ وﻣﻧﻬـــﺎ اﻵﻻت اﻟﺗﺄﺛﯾرﯾـــﺔ ) ﻣﺣـــوﻻت ﻛﻬرﺑﺎﺋﯾـــﺔ ‪،‬‬
‫ﻣﺣرﻛــﺎت ﻛﻬرﺑﺎﺋﯾــﺔ‪ ،‬أﻟــﺦ( ﺑﺣﯾــث ﺗﺻــﺑﺢ ذات ﻣﻌﺎﻣــل ﻗــدرة ﻣرﺗﻔــﻊ ﻧﺳــﺑﯾﺎً‪ .‬وﻛــذﻟك‬

‫‪٤٦‬‬
‫اﺳﺗﺑدال اﻟﻣﻌدات اﻟﻣﺳﺗﺧدﻣﺔ ﺑﺄﺧرى ذات ﻣﻌﺎﻣل ﻗدرة أﻋﻠﻰ‪ ،‬ﻣﺛل اﺳـﺗﺑدال اﻟﻛـﺎﺑﺢ‬
‫اﻟﻣﻐﻧﺎطﯾﺳﻰ ﻟﻠﻣﺻﺎﺑﯾﺢ اﻟﻔﻠورﯾﺔ ﺑﻛﺎﺑﺢ إﻟﻛﺗروﻧﻰ‪.‬‬
‫‪ -‬ﯾـؤدى اﻟﺗﺧطﯾط اﻟﺟﯾد ﻟﻠﺷﺑﻛﺎت اﻟداﺧﻠﯾﺔ ﻟﻠﻣﻧﺷﺂت أﺛﻧﺎء ﻣرﺣﻠﺔ اﻟﺗﺻﻣﯾم ﺑﺗﻘﺳﯾم‬
‫اﻷﺣﻣﺎل إﻟﻰ ﻣﺟﻣوﻋﺎت ﺑﺣﯾث ﺗﺣﺗوى ﻛل ﻣﺟﻣوﻋﺔ ﻋﻠﻰ ﻛل ﻣن اﻷﺣﻣﺎل اﻟﺗﺄﺛﯾرﯾﺔ‬
‫واﻟﺳـــﻌوﯾﺔ ﻣﻌـــﺎ‪ ،‬إﻟـــﻰ ﺧﻔـــض اﻟﻘـــدرة ﻏﯾـــر اﻟﻔﻌﺎﻟـــﺔ اﻟﻣﺳـــﺗﻬﻠﻛﺔ ﺑواﺳـــطﺔ اﻟﺣﻣـــل‬
‫اﻻﺟﻣــﺎﻟﻰ‪ ،‬ﺣﯾــث ﺗﻘــوم اﻷﺣﻣــﺎل اﻟﺳــﻌوﯾﺔ ﺑﺗﻌــوﯾض اﻟﺷــﺑﻛﺔ ﺑﺟــزء ﻣــن اﻟﻘــدرة ﻏﯾــر‬
‫اﻟﻔﻌﺎﻟـــﺔ اﻟﻣطﻠوﺑــــﺔ ﻟﻠﺣﻣــــل إﺟﻣـــﺎﻻً‪ ،‬وﺑﺎﻟﺗــــﺎﻟﻲ ﺗﻧﺧﻔــــض اﻟﻘــــدرة اﻟظﺎﻫرﯾـــﺔ اﻟﻛــــﻠﯾﺔ‬
‫)‪ (Total apparent power‬ﻋﻧــد ﻧﻘطــﺔ اﻟﺗوﺻــﯾل اﻟﻣﺧﺗــﺎرة ﻣــﻊ ﺷــﺑﻛﺔ‬
‫اﻟﺗﻐذﯾﺔ ﻟﻠﻘدرة اﻟﻛﻬرﺑﺎﺋﯾﺔ ‪.‬‬
‫‪ -‬ﯾﻌﺗﺑر ﺗﺣدﯾد ﺳﻌﺔ اﻟﻣﺣرﻛﺎت واﻟﻣﺣوﻻت ﺑﺷﻛل ﻣﻧﺎﺳب وﻛذﻟك ﻋدم ﺗﺷﻐﯾﻠﻬﺎ ﻓـﻲ‬
‫اﻟوﻗــت اﻟــذي ﻻ ﺗﺣﺗﺎﺟــﻪ اﻟﻌﻣﻠﯾــﺎت‪ ،‬ﻣــن أﻫــم ﻋواﻣــل ﺗﺣﺳــﯾن ﻣﻌﺎﻣــل اﻟﻘــدرة ﻓــﻲ‬
‫اﻟﺷﺑﻛﺎت اﻟﻣﻐذﯾﺔ ﻟﻬﺎ‪.‬‬
‫ﻣﻠﺣوظﺔ‪:‬‬
‫ﯾﺟــب ﻓــﻰ ﻛــل اﻷﺣ ـوال دراﺳــﺔ ﺗﺣدﯾــد اﻟﻌﺎﺋـــد اﻻﻗﺗﺻــﺎدى اﻟﻣﺗرﺗــب ﻋﻠــﻰ‬ ‫)‪(١‬‬
‫إﺿﺎﻓـﺔ أﺣﻣـﺎل ﺳﻌوﯾـﺔ ﻟﻣﻧظوﻣﺔ اﻟﻘدرة واﺧﺗﯾﺎر اﻟﺣــﻣل اﻟﺳـﻌوى اﻟﻣﻧﺎﺳـب ﻟﻛــل‬
‫ﺣﺎﻟﺔ‪ ،‬ﺳواء ﻛﺎﻧـت ﻣﺟﻣوﻋﺎت ﻣﻛﺛﻔﺎت اﺳﺗﺎﺗﯾﻛﯾﺔ ‪(Static condenser‬‬
‫‪Synchronous‬‬ ‫)‪ banks‬أو اﺳـــــﺗﺧدام اﻟﻣﻛﺛﻔـــــﺎت اﻟﻣﺗزاﻣــــــﻧﺔ* )‬
‫‪ (condenser‬ﺧﺻوﺻــﺎ ﻓــﻲ ﻣﺣطــﺎت اﻟﻘــوى اﻟﻔرﻋﯾــﺔ اﻟﺗــﻲ ﺗﻐــذى ﺗﺟﻣﻌــﺎت‬
‫رﺋﯾﺳﯾﺔ ‪.‬‬
‫)‪ (٢‬ﯾﺑــــﯾن اﻟﺷــــﻛل وﺣــــدة ذات ﻣﻠــــف وﻣﻛﺛــــف ﻟﻠﺣــــد ﻣــــن ﺗــــﺄﺛﯾر ﻣﺣﺗــــوى‬
‫اﻟﺗواﻓﻘﯾﺎت )‪ (Harmonic contents‬وﻛذﻟك ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‪.‬‬

‫ﻣﻛﺛف‬

‫ﻛوﻧﺗﺎﻛﺗور‬
‫ﻣرﺷﺢ‬
‫)‪(detuned filter‬‬

‫ث‬

‫‪.‬‬

‫‪٤٧‬‬
‫اﻟﻣﻛﺛﻔﺎت اﻟﻣﺗزاﻣﻧﺔ ﻋﺑﺎرة ﻋن ﻣﺣرﻛﺎت ﺗزاﻣﻧﯾﺔ )‪ (Synchronous motors‬ﺗﻌﻣل‬ ‫*‬
‫ﺑدون ﺣﻣل‬

‫وﺣدة ﻣﻠف و ﻣﻛﺛف ﻟﻠﺣد ﻣن ﺗﺄﺛﯾر ﻣﺣﺗوى‬

‫اﻟﺗواﻓﻘﯾﺎت و ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‬

‫اﻟﺧﺻﺎﺋص اﻟواﺟب ﺗواﻓرﻫﺎ ﻓﻰ اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة‬


‫ﯾﺑـﯾن اﻟﺷـﻛل اﻟﻘـﺎدم ﻧﻣوذﺟـﺎً ﻟﻣﻛﺛﻔـﺎت ﺗﺣﺳـﯾن ﻣﻌﺎﻣـل اﻟﻘــدرة ﻣرﻛﺑـﺔ داﺧـل ﻟوﺣـﺔ ﺗﺣﺗــوى‬
‫ﻋﻠﻰ ﻧﻘط ﺗوزﯾﻊ ﺟﻬد ﻣﻧﺧﻔض‪.‬‬

‫ﻧﻣوذج ﻟﻠوﺣﺔ ﺗوزﯾﻊ ) ﺟﻬد ﻣﻧﺧﻔض (‬

‫ﻣرﻛب ﺑﻬﺎ ﻣﻛﺛﻔﺎت ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‬

‫ﯾﺟــب ﺗـواﻓر اﻟﺧﺻــﺎﺋص اﻟﺗﺎﻟﯾــﺔ ﻓــﻰ اﻟﻣﻛﺛﻔــﺎت اﻟﻣﺳــﺗﺧدﻣﺔ ﻓــﻰ ﺗﺻــﺣﯾﺢ ﻣﻌﺎﻣــل‬ ‫‪-‬‬
‫اﻟﻘدرة‪:‬‬

‫‪٤٨‬‬
‫ﯾﻛون اﻟﻔﻘد اﻟﺧـﺎص ﺑـﺎﻟﻣﻛﺛف ﻣﻧﺧﻔﺿـﺎ )ﻓـﻲ ﺣـدود ‪ ٠.٥ -٠.٤‬وات ‪/‬‬ ‫)‪(١‬‬
‫ك‪.‬ﻓﺎر( ﻣﻣﺎ ﯾؤدى إﻟﻰ ﺗﺧﻔـﯾض اﻟﺗﻛﻠﻔـﺔ اﻟﺟﺎرﯾـﺔ )‪ ،(Running cost‬واﻟﺣـد‬
‫ﻣن اﻻرﺗﻔﺎﻋﺎت ﻓـﻲ درﺟـﺎت اﻟﺣـرارة ﻟﺿـﻣﺎن ﺳـﻼﻣﺔ اﻟﻌـزل اﻟﺧـﺎص ﺑـﺎﻟﻣﻛﺛف ‪،‬‬
‫وﻛذا ﺿﻣﺎن ﺷروط ﺗﺷﻐﯾل ﻣﻧﺎﺳﺑﺔ ﻟﻠﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ‪.‬‬
‫إﺿﺎﻓﺔ ﻣﻘﺎوﻣﺔ ﺗﻔرﯾﻎ )أوﻣﯾـﺔ( ﻣﺳـﺗﻘﻠﺔ )‪(Discharge resistor‬‬ ‫)‪(٢‬‬
‫ﻟﻛل وﺣدة ﻣﻛﺛف ﻣن ﻣﺟﻣوﻋﺔ وﺣدات اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳـﺗﺧدﻣﺔ ﺣﯾـث ﯾـؤدى ذﻟـك‬
‫إﻟﻰ أﻧﻪ ﻓﻲ ﺣﺎﻟﺔ ﺣدوث اﻧﻬﯾﺎر ﻹﺣدى ﻣﻘﺎوﻣﺎت اﻟﺗﻔرﯾﻎ أو أﻛﺛـر ﯾﻣﻛـن ﻟﺑـﺎﻗﻲ‬
‫اﻟوﺣدات اﻻﺳﺗﻣرار ﻓﻲ ﺗﻔرﯾـﻎ اﻟﺷـﺣﻧﺎت ﻣـن ﺧـﻼل ﻣﻘﺎوﻣـﺎت اﻟﺗﻔرﯾـﻎ اﻟﺧﺎﺻـﺔ‬
‫ﺑﻬﺎ ‪ ،‬ﺑﻣﺎ ﻓﻲ ذﻟك اﻟﻣﻛﺛﻔﺎت اﻟﺗﻲ اﻧﻬﺎرت ﻣﻘﺎوﻣﺎت اﻟﺗﻔرﯾﻎ ﻟﻬﺎ ‪.‬‬
‫ﯾﺟب أن ﯾﺗﺿﻣن ﺗﺻﻣﯾم ﻛـل ﻣﻛﺛـف ﺧﺎﺻـﯾﺔ اﻻﻟﺗﺋـﺎم اﻟـذاﺗﻲ ) ‪Self‬‬ ‫)‪(٣‬‬
‫‪ ،(healing‬اﻟﺗــﻲ ﺗــؤدى إﻟــﻰ اﻟﺗﺋــﺎم اﻟﻌــزل ﺗﻠﻘﺎﺋﯾــﺎ ﻋﻧــد ﺗﻌــرض أﺟــزاء ﻣﻧــﻪ‬
‫ﻟﻠﺗﺻــدع ﻧﺗﯾﺟــﺔ اﻟﺗﻌــرض ﻟﺟﻬــود زاﺋــدة ﻣؤﻗﺗــﺔ‪ ،‬ﻛﺎرﺗﻔﺎﻋــﺎت اﻟﺟﻬــد اﻟﺗــﻲ ﺗﺣــدث‬
‫أﺛﻧﺎء ﻣراﺣل اﻟﺗﺷﻐﯾل ﻏﯾر اﻟﻌﺎدﯾﺔ ﻟﻣﻧظوﻣـﺔ اﻟﻘـدرة‪ ،‬ﻣﺛﻠﻣـﺎ ﯾﺣـدث ﻓـﻲ اﻟﺣـﺎﻻت‬
‫اﻟﻌـــﺎﺑرة )‪ ،(Transients‬واﻟظـــواﻫر اﻷﺧـــرى اﻟﺗـــﻲ ﺗﺗﻌـــرض ﻟﻬـــﺎ اﻟﻣﻧظوﻣـــﺔ‬
‫وﺗﺣدث ﺑﻬﺎ ارﺗﻔﺎﻋﺎت ﻣﻔﺎﺟﺋﺔ ﻟﻠﺟﻬد ‪.‬‬
‫ﯾﺟب أن ﺗزود ﻛل وﺣـدة ﻣﻛﺛﻔـﺎت ﺑـﺄداة ﻓﺻـل )ﻗـﺎطﻊ ﺗﯾـﺎر أو ﻓﯾـوزات(‬ ‫)‪(٤‬‬
‫)‪ (Breaker or fuses‬ﺑﺷــﻛل ﻣﺳــﺗﻘل‪ ،‬ﺣﺗــﻰ ﯾﻣﻛــن ﻓﺻــل اﻟﺗﯾــﺎر ﻋــن‬
‫وﺣـــدة أو ﻣﺟﻣوﻋـــﺔ اﻟﻣﻛﺛﻔـــﺎت اﻟﺗـــﻲ ﯾﺣـــدث ﺑﻬـــﺎ ﺧﻠـــل‪ ،‬ﻛـــﺄن ﯾﺗﻌـــرض ﻋزﻟﻬـــﺎ‬
‫ﻟﻼﻧﻬﯾﺎر‪ ،‬ﻣﻊ اﺳﺗﻣرار ﺑﺎﻗﻲ اﻟوﺣدات ﻓﻲ اﻟﻌﻣل دون أن ﺗﺗﺄﺛر اﻟﻣﻧظوﻣﺔ ﻟﺣﯾن‬
‫إﺟ ـراء اﻟﺻــﯾﺎﻧﺔ اﻟﻼزﻣــﺔ ﻟﻠوﺣــدة اﻟﺗــﻰ ﺑﻬــﺎ ﻋطــب إن أﻣﻛــن أو ﺗﻐﯾﯾــر اﻟــﻼزم ‪،‬‬
‫وﻫــذا ﯾﺳــﺎﻫم ﺑﺷــﻛل إﯾﺟــﺎﺑﻲ ﻓــﻲ زﯾــﺎدة اﻟﺛﻘــﺔ واﻟﻌــول )‪ ( Reliability‬ﻓــﻰ‬
‫ﻣﻧظوﻣﺔ اﻟﻘدرة وزﯾﺎدة ﻓرص ﺗﻌﺎﻓﯾﻬﺎ ﻓﻲ ﻣواﺟﻬﺔ اﻵﺛـﺎر اﻟﺳـﻠﺑﯾﺔ اﻟﻧﺎﺟﻣـﺔ ﻋـن‬
‫ظروف اﻟﺗﺷﻐﯾل ﻏﯾر اﻟﻌﺎدﯾﺔ ﻟﺿﻣﺎن ﺗﻐذﯾﺔ ﻛﻬرﺑﺎﺋﯾﺔ ﺟﯾدة ﻟﻸﺣﻣﺎل ﻋﻠﻰ وﺟـﻪ‬
‫اﻟﻌﻣوم ‪.‬‬
‫ﯾﺟـب أن ﯾﺣﺗـوى ﻛـل ﻣﻛﺛــف ﺑﺷـﻛل ﻣﺳـﺗﻘل ﻋﻠــﻰ أداة ﻓﺻـل ﻋﻧـد زﯾــﺎدة‬ ‫)‪(٥‬‬
‫اﻟﺿﻐط )‪ (Over pressure device‬داﺧل اﻟوﻋﺎء ﻟﺿﻣﺎن ﻋـدم ﺗﻌـرض‬
‫اﻟﻣﻛﺛف ﻻﻧﻬﯾﺎر ﯾﺗﻌذر ﺗدارﻛﻪ ﻋن طرﯾق ﺧﺎﺻﯾﺔ اﻻﻟﺗﺋﺎم اﻟذاﺗﻲ ﻟﻠﻣﻛﺛف ‪.‬‬
‫ﯾﺟــب اﻟﺗﺄﻛﯾــد ﻋﻠــﻰ ﺿــﻣﺎن ﻗــوة اﻟﻌــزل اﻟﻛﻬرﺑــﺎﺋﻲ ﻟﻠﻣﻛﺛــف ‪،‬واﺳــﺗﻘرارﻩ ‪،‬‬ ‫)‪(٦‬‬
‫وزﯾﺎدة ﻋﻣرﻩ اﻻﻓﺗراﺿﻲ ‪ ،‬ﻣـن ﺧـﻼل اﺧﺗﺑـﺎرات اﻟﺟﻬـود اﻟﻌﺎﻟﯾـﺔ اﻟﺗـﻲ ﺗﺟـرى ﻟـﻪ‬
‫طﺑﻘﺎ ﻟﺣدود اﻟﻘﯾﺎﺳﺎت اﻟﻣﻧﺻوص ﻋﻠﯾﻬﺎ ﻓﻲ اﻟﻣواﺻـﻔﺎت اﻟﻣطﻠـوب ﺗواﻓرﻫـﺎ ﻓـﻲ‬

‫‪٤٩‬‬
‫اﻟﻣﻛﺛــف ‪ ،‬وذﻟــك ﺣﺗــﻰ ﻻ ﺗﺗــﺄﺛر ﺳــﻼﻣﺗﻪ أﺛﻧــﺎء ﻋﻣﻠﯾــﺎت اﻟﻔﺻــل ﻋﻧــد اﻟﺟﻬــود‬
‫اﻟزاﺋدة ﺑواﺳطﺔ وﺳﯾﻠﺔ اﻟﻔﺻل اﻟﻣﺳﺗﺧدﻣﺔ وﻣﺎ ﻗد ﯾﻧﺟم ﻋﻧﻬـﺎ ﻣـن ﺷـرر ﯾﻣﻛـن‬
‫أن ﯾﺗﺳﺑب ﻓﻲ اﻧﻬﯾﺎرات ﺟزﺋﯾﺔ )ﺗﺻدﻋﺎت( ﻟﻠﻌزل‪ ،‬أو ﺗﻌرﺿﻪ ﻟﻼﻧﻬﯾﺎر اﻟﺷﺎﻣل‬
‫ﻓﻲ ﺣﺎﻟﺔ ﺿـﻌﻔﻪ وﻋـدم ﻗدرﺗـﻪ ﻋﻠـﻰ ﺗﺣﻣـل درﺟـﺎت اﻟﺣـرارة اﻟﻌﺎﻟﯾـﺔ اﻟﻧﺎﺗﺟـﺔ ﻋـن‬
‫اﻟﺷرارة ﻗﺑل إطﻔﺎءﻫﺎ ‪.‬‬

‫اﻟﺣﺳﺎﺑﺎت اﻟﺧﺎﺻﺔ ﺑﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة‬


‫ﯾﻣﻛـــن ﺗﻠﺧـــﯾص ﺑﻌـــض اﻟﺗﻌرﯾﻔـــﺎت واﻟﻌﻼﻗـــﺎت اﻟﻬﺎﻣـــﺔ اﻟﻣطوﺑـــﺔ ﻋﻧـــد إﺟـــراء اﻟﻌﻣﻠﯾـــﺎت‬
‫اﻟﺣﺳﺎﺑﯾﺔ اﻟﺧﺎﺻﺔ ﺑﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻲ ‪-:‬‬
‫ﻣﻌﺎﻣل اﻟﻘدرة‬
‫ﻫــو ﺟﯾــب ﺗﻣــﺎم زاوﯾــﺔ اﻟطــور اﻟﺗــﻲ ﯾﺗﺧﻠــف ) ‪ (lagging‬أو ﯾﺗﻘــدم )‪ (leading‬ﺑﻬــﺎ‬
‫اﻟﺗﯾﺎر ﻋن اﻟﺟﻬد )‪ (  1 cos‬ﻋﻧد ﻧﻘطﺔ اﻟﻘﯾﺎس اﻟﻣﺧﺗﺎرة‪ ،‬ﻧﺗﯾﺟﺔ ﻟﻣرورﻩ ﺧـﻼل اﻟﻣﻣﺎﻧﻌـﺔ اﻟﺣﺛﯾـﺔ‬
‫ﻟﻣﻠﻔﺎت اﻟﻣﻌدات اﻟﺗﺄﺛﯾرﯾﺔ اﻟﻣوﺟودة ﺑﺎﻟﺣﻣل‪ ،‬أو اﻟﻣﻣﺎﻧﻌﺔ اﻟﺳﻌوﯾﺔ ﻟﻠﻣﻛﺛﻔﺎت ﺑﻪ‪ ،‬ﻋﻠﻰ اﻟﺗرﺗﯾب ‪.‬‬
‫اﻟﺣﺎﻟﺔ اﻷوﻟﻰ‪ ،‬ﺣﯾث ﺗﻌﺗﺑر اﻟﻣﻠﻔﺎت ﻓـﻲ ﻫـذﻩ اﻟﺣﺎﻟـﺔ ﻋﻧﺻـر اﺳـﺗﻬﻼك ﻟﻘـدرة ﻏﯾـر ﻓﻌﺎﻟـﺔ‬
‫)‪ ،(Reactive power‬وﯾﻧﺑﻐﻲ اﻟﺳـﯾطرة ﻋﻠـﻰ ﻣﻌـدﻻت اﺳـﺗﻬﻼك ﻫـذا اﻟﻧـوع ﻣـن اﻟﻘـدرة ﻏﯾـر‬
‫اﻟﻔﻌﺎﻟــﺔ ﻟﺿــﻣﺎن ﻣﻌﺎﻣــل ﻗــدرة ﻣﻧﺎﺳــب ‪ ،‬ﺣﯾــث اﻟزﯾــﺎدة ﻓــﻲ ﻫــذا اﻻﺳــﺗﻬﻼك ﯾــؤدى إﻟــﻰ ﻣــﺎ ﯾﻣﻛــن‬
‫اﻋﺗﺑـﺎرﻩ ﺗﺑدﯾــدا ﻟﻠﻘــدرة اﻟظﺎﻫرﯾــﺔ )‪ (kVA‬اﻟﻣﺳــﺗﻣدة ﻣـن ﻣﺻــدر اﻟﺗﻐذﯾــﺔ ﺑواﺳــطﺔ اﻟﺣﻣــل وﯾﻣﻛــن‬
‫ﺣﺳﺎب ﻗﯾﻣﺔ ﻣﻌﺎﻣل اﻟﻘدرة ) ‪ ( p. f1‬ﻣن اﻟﻣﻌﺎدﻟﺔ‪.‬‬
‫‪Active Power‬‬ ‫) ‪P (kW‬‬
‫‪p. f1  cos 1 ‬‬ ‫‪ 1‬‬
‫)‪Apparent Power S 1 (kVA‬‬

‫‪P1‬‬
‫)‪(KW‬‬ ‫‪Vref‬‬ ‫‪‬‬
‫‪‬‬
‫‪Q1‬‬
‫‪S1‬‬ ‫)‪(KVAR‬‬

‫)‪(KVA‬‬

‫و اﻟﺣﺎﻟــﺔ اﻟﺛﺎﻧﯾــﺔ اﻟﺗــﻲ ﯾﺗﻘــدم ﻓﯾﻬــﺎ اﻟﺗﯾــﺎر ﻋــن اﻟﺟﻬــد ﻓــﻲ زاوﯾــﺔ اﻟطــور ﻧﺗﯾﺟــﺔ ﻟﻣــرورﻩ ﺧــﻼل‬
‫اﻟﻣﻣﺎﻧﻌﺔ اﻟﺳﻌوﯾﺔ ﻟﻠﻣﻛﺛﻔﺎت ‪ ،‬وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﯾﻣﻛن اﻋﺗﺑﺎر اﻟﻣﻛﺛف ﻋﻧﺻر إﺿـﺎﻓﺔ ﻟﻠﻘـدرة ﻏﯾـر‬
‫اﻟﻔﻌﺎﻟﺔ ‪ ،‬وﯾﻣﻛن ﺣﺳﺎب ﻣﻌﺎﻣل اﻟﻘدرة )‪ (p.f2‬ﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﻣن اﻟﻣﻌﺎدﻟﺔ‪:‬‬
‫‪Active Power‬‬ ‫) ‪P (kW‬‬
‫‪p .f 2  cos  2 ‬‬ ‫‪ 2‬‬
‫)‪Apparent Power S 2 (kVA‬‬

‫‪٥٠‬‬
‫‪‬‬
‫‪S2‬‬
‫)‪(kVA‬‬ ‫‪Q2‬‬
‫)‪(kVAR‬‬

‫‪‬‬ ‫‪Vref‬‬
‫‪P2‬‬
‫)‪(kW‬‬

‫وﺣﯾث أن اﻟﻘدرة اﻟﻔﻌﺎﻟﺔ )‪ (Active Power‬ﺛﺎﺑﺗﺔ ﻓﻲ اﻟﺣﺎﻟﺗﯾن‪ ،‬ﺑﯾﻧﻣﺎ ﺗﺗﻐﯾـر ﻛـل ﻣـن‬
‫اﻟﻘــدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ واﻟﻘــدرة اﻟظﺎﻫرﯾــﺔ ﺑﺗﻐﯾــر ﻣﻌﺎﻣــل اﻟﻘــدرة‪ ،‬ﻟــذا ﻓــﯾﻣﻛن اﻟﺗﻌﺑﯾــر ﻋــن اﻟﻌﻼﻗــﺔ‬
‫اﻟرﯾﺎﺿﯾﺔ اﻟﺗﻲ ﯾﺣﺳب ﻣﻧﻬﺎ ﻣﻌﺎﻣل اﻟﻘدرة ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻲ ﻣن اﻟﻣﻌﺎدﻟﺔ‬
‫‪Reactive Power (kVAR)  Active Power (kW)  tan ‬‬

‫وﻋﻠﯾﻪ ﯾﻣﻛن اﺳﺗﻧﺗﺎج ﻗﯾﻣﺔ اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻗﺑل وﺑﻌد ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣـل اﻟﻘـدرة ﻛﻣـﺎ ﻫـو‬
‫ﻣوﺿﺢ ﺑﺎﻟﺷﻛل )‪:(٥ -٩‬‬
‫)‪P (kW‬‬ ‫‪Vref‬‬ ‫‪‬‬
‫‪  ‬‬
‫‪Q2‬‬
‫)‪(kVAR‬‬
‫‪S2‬‬
‫)‪(kVA‬‬ ‫)‪Q1 (kVAR‬‬
‫‪S1‬‬ ‫‪Qc‬‬
‫)‪(kVA‬‬ ‫)‪(kVAR‬‬

‫ﺣﯾث أن ‪:‬‬
‫ﻣﻌﺎﻣل اﻟﻘدرة ﻗﺑل اﻟﺗﺻﺣﯾﺢ ) ‪=  1 cos( p. f 1‬‬
‫ﻣﻌﺎﻣل اﻟﻘدرة ﺑﻌد اﻟﺗﺻﺣﯾﺢ ) ‪=  2 cos ( p. f 2‬‬
‫‪ 1 tan‬‬ ‫اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻋﻧد ﻣﻌﺎﻣل اﻟﻘدرة ) ‪ = ( p. f 1‬اﻟﻘدرة اﻟﻔﻌﺎﻟﺔ ×‬
‫اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻋﻧد ﻣﻌﺎﻣل اﻟﻘدرة ) ‪ = ( p. f 2‬اﻟﻘدرة اﻟﻔﻌﺎﻟﺔ × ‪ 2 tan‬‬
‫وﺑذﻟك ﺗﺻﺑﺢ ﻗﯾﻣﺔ اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ اﻟﻼزﻣﺔ ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ﻫﻲ )‪ (Qc‬واﻟﺗﻲ‬
‫ﯾﻣﻛن ﺣﺳﺎﺑﻬﺎ ﻣن اﻟﻣﻌﺎدﻟﺔ‬
‫‪Qc(kVAR) = P(kW) × 1 tan [ ]  2 -tan‬‬

‫‪٥١‬‬
‫وﯾﺗﺿﺢ ﻣن اﻟﺷﻛل أﯾﺿﺎً اﻧﺧﻔﺎض اﻟﻘـدرة اﻟظﺎﻫرﯾـﺔ )‪ S1 (kVA‬ﻟﺗﺻـﺑﺢ ﻋﻧـد اﻟﻘﯾﻣـﺔ‬
‫)‪ ، S2 (kVA‬وذﻟــك ﻧﺗﯾﺟــﺔ ﺗﺻــﺣﯾﺢ ﻣﻌﺎﻣــل اﻟﻘــدرة وﻫــو ﻣــﺎ ﯾﻌـود ﺑﺎﻹﯾﺟــﺎب ﻋﻠــﻰ زﯾــﺎدة ﺳــﻌﺔ‬
‫ﻣﻬﻣﺎت ﺷﺑﻛﺔ اﻟﺗﻐذﯾﺔ )اﻟﻣﺻدر( ﻣـن ﻣﺣـوﻻت وﻛـﺎﺑﻼت‪ ،‬ﻛﻣـﺎ ﯾﻔﯾـد اﻟﻣﺷـﺗرك )اﻟﺣﻣـل( ﻓـﻲ زﯾـﺎدة‬
‫اﻟﻘــدرة اﻟﻣﺗﺎﺣــﺔ ﻟﻠﺷــﺑﻛﺔ اﻟداﺧﻠﯾــﺔ ﻟﻠﻣﻧﺷــﺄة‪ ،‬إو ﺗﺎﺣــﺔ إﺿــﺎﻓﺔ أﺣﻣــﺎل أﺧــرى ﻟﻬــﺎ دون اﻟﺣﺎﺟــﺔ إﻟــﻰ‬
‫إﻧﺷﺎء ﺷﺑﻛﺎت إﺿﺎﻓﯾﺔ ‪.‬‬
‫ﯾﻣﻛن ﺗﺣدﯾد ﺳﻌﺔ اﻟﻣﻛﺛﻔﺎت اﻟﻣطﻠوب ﺗوﺻﯾﻠﻬﺎ ﻋﻠﻰ اﻟﺗوازي ﻣﻊ اﻟﺣﻣل ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣـل‬
‫اﻟﻘدرة ﻣن اﻟﺟدول اﻟﺗﺎﻟﻲ ‪ ،‬واﻟذي ﯾﺣﺗوى ﻋﻠﻰ ﻗـﯾم ﺳـﻌﺎت اﻟﻣﻛﺛﻔـﺎت ﻧظﯾـر ﻛـل ﺣﻣـل ﺣﺛـﻲ ﻋﻠـﻰ‬
‫ﺿوء ﻣﻌﺎﻣل اﻟﻘدرة اﻟﺧﺎص ﺑذﻟك اﻟﺣﻣل واﻟﻣطﻠوب ﺗﺻﺣﯾﺣﻪ‪ ،‬وﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف ‪.‬‬
‫ﻋﻠﻰ ﺳﺑﯾل اﻟﻣﺛﺎل إذا ﻛﺎن ﻣﻌﺎﻣل اﻟﻘدرة )‪ (cos Φ‬اﻷﺻـﻠﻰ ﻣﺳـﺎوﯾﺎً )‪ (٠.٧‬واﻟﻣطﻠـوب‬
‫ﺗﺣﺳﯾﻧﻪ إﻟﻰ )‪ (٠.٩٣‬ﺗﻛون ﺳﻌﺔ اﻟﻣﻛﺛﻔﺎت اﻟﻣطﻠوﺑﺔ )‪ (٠.٦٢٥‬ك‪.‬ﻓﺎر ﻟﻛل ﻛﯾﻠـووات‪ ،‬ﺑﯾﻧﻣـﺎ إذا‬
‫ﻛــﺎن ﻣطﻠــوب ﺗﺣﺳــﯾن ﻣﻌﺎﻣــل اﻟﻘــدرة إﻟــﻰ )‪ (٠.٩٥‬ﺗﻛــون ﺳــﻌﺔ اﻟﻣﻛﺛﻔــﺎت اﻟﻣطﻠوﺑــﺔ )‪(٠.٦٩١‬‬
‫ك‪.‬ﻓﺎر ﻟﻛل ﻛﯾﻠووات وﻫﻛذا ‪.‬‬

‫ﯾوﺿﺢ ﻗﯾﻣﺔ اﻟﺛﺎﺑت )‪ (K = kVAR / kW‬اﻟﻣﺳﺗﺧدم ﻓﻰ‬


‫ﺣﺳﺎب ﻛﻣﯾﺔ اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ وﻛذﻟك ﻣﻌﺎﻣل اﻟﻘدرة ﻗﺑل وﺑﻌد اﻟﺗﺻﺣﯾﺢ‬

‫‪٥٢‬‬
before kVAR rating of capacitor bank to Install per kW, to Improve Cos Φ (the power factor) or tan
compensation Φ, to a given value
tan Φ 0,75 0.59 0.48 0.46 0.43 0.40 0.36 0.33 0.29 0.25 0.20 0.14 0.0
tan Φ cos Φ
cos Φ 0.80 0.86 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1
2.29 0.40 1.557 1.691 1.805 1.832 1.861 1.895 1.924 1.959 1.998 2.037 2.085 2.146 2.28
222 0.41 1474 1.625 1.742 1.769 1.798 1.831 1.840 1.896 1.935 1.973 2.021 2082 8
2.22
2-16 0.42 1.413 1.561 1.681 1.709 1.738 1.771 1.800 1.836 1.874 1.913 1.961 2.022 5
2.16
2-10 0.43 1.356 1.499 1.624 1.651 1.680 1.713 1.742 1.778 1.816 1.855 1.903 1.964 4
2.10
204 0.44 1.290 1.441 1.558 1-585 1.614 1.647 1.677 1.712 1.751 1.790 1.837 1.899 7
2.041
198 0.45 1.230 1.384 1.501 1.532 1.561 1.592 1.628 1.659 1.695 1.737 1.784 1.846 1.98
1.93 0.46 1.179 1.330 1.446 1.473 1.502 1.533 1-567 1.600 1.636 1.677 1.725 1.786 8
1.92
1.88 0.47 1.130 1.278 1.397 1.425 1.454 1.485 1.519 1.532 1.588 1.629 1.677 1.758 9
1.881
1.83 0.48 1.076 1.228 1.343 1.370 1.400 1.430 1.464 1.497 1.534 1.575 1.623 1.684 1.826
1.78 0.49 1.030 1.179 1.297 1.326 1.355 1.386 1.420 1.453 1.489 1.530 1.578 1.639 1.782
1.73 0.50 0.982 1 232 1.248 1.276 1.303 1.337 1.369 1.403 1.441 1.481 1.529 1390 1.732
1-69 0.51 0.936 1.087 1.202 1.230 1.257 1.281 1.323 .357 1.395 1.435 1.483 1.544 1.686
164 0,52 0.894 1.043 1.160 1.188 1.215 1.249 1.281 .315 1.353 1.393 1.441 1.502 1.644
1.60 0.53 0.850 1.000 1.116 1.144 1.171 1.205 1.237 .271 1.309 1.349 1.397 1.458 1.600
1.56 0.54 0.809 0.959 1.075 1.103 1.130 1.164 1.196 .230 1.268 1.308 1.356 1.417 1.559
1.52 0.55 0.769 0.918 1.035 1.063 1.090 1.124 1.156 .190 1.228 1.266 1.316 1.377 1.519
1.48 0.56 0.730 0879 0.996 1.024 1.051 1.085 1.117 .151 1.189 1.229 1.277 1.338 1.480
1.44 0.57 0.692 0.841 0.958 0.986 1.013 1.047 1.079 .113 1.151 1-191 1.239 1.300 1.442
1.40 0.58 0.665 O.805 0.921 0-949 0.976 1.010 1-042 .076 1.114 1.154 1.202 1263 1.405
1.37 0.59 0.618 0.768 0.884 0.912 0.939 0.973 1.005 .039 1.077 1.117 1.165 1.226 1.368
1.33 0.60 0.584 0.733 0.849 0-878 0.905 0.939 0.971 .00S 1-043 1.083 1.131 1.192 1.334
1.30 0.61 0.549 0.699 0.815 0.843 0.870 0.904 0.936 0.970 1.008 1.048 1.096 1.157 1.29
1.27 0.62 0.515 0.665 0.781 0.809 0.836 0.870 0.902 0.936 0.974 1.014 1.062 1.123 9
1.26
1.23 0.63 0.483 0.633 0.749 0.777 0.804 0.838 0.870 0.904 0-942 0.962 1.030 1.091 5
1.23
1.20 0.64 0.450 0.601 0.716 0.744 0.771 0.805 0.837 0.871 0.909 0.949 0.997 1.058 3
1.20
1.17 0.65 0.419 0.569 0.685 0.713 0.740 0.774 0.806 0.840 0.878 0-918 0.966 1.007 0
1.16
1.14 0.66 0.388 0.538 0.654 0.662 0.709 0.743 0.775 0.609 0.847 0.887 0.935 0.996 9
1.13
1.11 0.67 0.358 0.508 0.624 0.652 0.679 0.713 0.745 0.779 0.817 0.857 0.905 0.966 8
1.10
1.08 0.68 0.329 0.478 0.595 0.623 0.650 0.684 0-716 0.750 0.788 0.828 0.876 0.937 8
1.07
1.05 0.69 0.299 0.449 0.565 0.593 0.620 0.654 0.666 0.720 0.758 0.798 0.840 0.907 9
1.04
1.02 0,70 0.270 0.420 0.536 0.564 0.591 0.625 0.657 0.691 0.729 0.769 0.811 0-878 9
1.02
0.99 0.71 0.242 0.392 0.508 0.536 0.563 0.597 0.629 0.663 0.701 0.741 0.783 0.850 0
0.99
0.96 0.72 0.213 0.364 0.479 0.507 0.534 0.566 0.600 0.634 0.672 0.712 0.754 0.821 2
0.96
0.94 0.73 0.186 0.336 0.452 0.480 0.507 0.541 0.573 0.607 0.645 0.685 0.727 0-794 3
0.93
0.91 0.74 0.159 0.309 0.425 0.453 0.480 0.514 0.546 0.580 0.618 0.658 0.700 0.767 6
0.90
0.88 0.7S 0.132 0.82 0.396 0.426 0.453 0.487 0.519 0.553 0.591 0.631 0.673 0.740 9
0.88
0.86 0.76 0.105 0.255 0.371 0.399 0.426 0.460 0.492 0.526 0.564 0.6O4 0.652 0.713 2
0-
0.83 0.77 0.079 0.229 0.345 0.373 0.400 0.434 0.466 0.500 0.538 0.578 0.620 0.687 855
0.82
0.80 0.78 0053 0.202 0.319 0.347 0.374 0.408 0.440 0.474 0.512 0.552 0.594 0.661 9
0.80
0.78 0.79 0.026 0.176 0.292 0.320 0.347 0.381 0.413 0.447 0.485 0.525 0.567 0.634 3
0-
0.75 0.80 0.150 0.266 0.294 0.321 0.355 0.387 0.421 0.459 0.499 0.541 0.608 776
0.750
0.72 0.81 0.124 0.240 0.268 0.295 0.329 0.361 0.395 0.433 0.473 0.515 0-582 0.72
0.70 0.82 0.098 0.214 0.242 0.269 0.303 0.335 0.369 0.407 0.447 0-489 0.556 4
0.698
0.67 0.83 0.072 0.188 0.216 0.243 0.277 0.309 0.343 0.381 0.421 0.463 0.530 0.67
0.65 0.84 0.046 0.162 0.190 0.217 0.251 0.263 0.317 0.355 0.395 0.437 0.504 2
0.645
0.62 085 0.020 0.136 0.164 0-191 0.225 0.257 0.291 0.329 0.369 0-417 0.478 0.620
0.59 0.66 0.109 0.140 0.167 0.198 0.230 0.264 0.301 0.343 0-390 0.450 0.593
0.57 0.87 0.083 0.114 0.141 0.172 0.204 0.238 0.275 0317 0.364 0.424 0.56
0.54 0.88 0.054 0.O85 0.112 0.143 0.175 0.209 0.246 0.288 0.335 0.395 7
0.53
0.51 0.89 0.028 0.059 0.086 0.117 0149 0.183 0.230 0.262 0.309 0.369 8
0.51
0.48 0.90 0.031 0.058 0.089 0.121 0.155 0.192 0.234 0.281 0.341 2
0.48
4

٥٣
‫ﺗﺣدﯾد ﻣواﻗﻊ اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة‬

‫ﯾﺗم ﺗرﻛﯾب ﻣﺟﻣوﻋﺎت اﻟﻣﻛﺛﻔﺎت ﻋﺎدة ﺑﻌد اﻟﻌدادات اﻟﻣرﻛﺑﺔ ﻟـدى اﻟﻣﺷـﺗرك‪ ،‬وﻋﻠـﻰ ﺛﻼﺛـﺔ‬
‫ﻣﺳﺗوﯾﺎت ﻣﺗﺑﺎﯾﻧﺔ ﻟﻠﺗرﻛﯾﺑﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟداﺧﻠﯾﺔ ﻟﻠﻣﻧﺷﺄة ﻛﻣﺎ ﯾﻠﻲ‪-:‬‬
‫ﻋﻧــد ﻟوﺣـﺔ اﻟﻣﻔﺎﺗﯾـﺢ اﻟرﺋﯾﺳﯾﺔ ﻟﻠوﺣﺔ اﻟﺟﻬد اﻟﻣﻧﺧﻔض ﻛﻣﺎ ﻫو ﻣوﺿـﺢ‬ ‫)‪(١‬‬

‫‪Tr‬‬

‫‪S‬‬

‫‪C‬‬

‫‪L‬‬ ‫‪L‬‬ ‫‪L‬‬ ‫‪L‬‬

‫ﺗرﻛﯾب اﻟﻣﻛﺛﻔﺎت ﻋﻧد ﻟوﺣﺔ اﻟﺟﻬد اﻟﻣﻧﺧﻔض اﻟرﺋﯾﺳﯾﺔ ﻟﻠﻣﻧﺷﺄة‬

‫ﯾﺣﻘق اﻟﺗرﻛﯾب ﻓﻲ ﻫذا اﻟﻣوﺿﻊ اﺳﺗﯾﻌﺎﺑﺎ ﺷﺎﻣﻼ ﻟﻣﺣﺗوﯾﺎت أﺣﻣﺎل اﻟﻣﻧﺷﺄة وﺧﻔض ﺣﻣل‬
‫اﻟﻣﺣول ﻛﻣﺎ ﺗﻘل اﻟﺳﻌﺎت اﻟﻣطﻠوب ﺗواﻓرﻫـﺎ ﻓـﻲ ﻗواطـﻊ اﻟـداﺋرة اﻟﻣﺳـﺗﺧدﻣﺔ وﯾﺳـﻬل ﻣﻌـﻪ إﻣﻛﺎﻧﯾـﺔ‬
‫ﻓﺣص وﺣدات ﻣﺟﻣوﻋﺔ اﻟﻣﻛﺛﻔﺎت أو ﻣﻠﺣﻘﺎﺗﻬﺎ ﻟوﺟودﻫﺎ ﻣﺟﺗﻣﻌﺔ ﻓﻲ ﻣﻛﺎن واﺣـد ﻛﻣـﺎ ﯾﻣﻛــن ﻓـﻲ‬
‫ﻫـذﻩ اﻟﺣﺎﻟـﺔ أﯾﺿـﺎً إﺿﺎﻓﺔ أﯾـﺔ ﺗرﻛﯾﺑﺎت أو ﺗوﺳﻌﺎت ﺟدﯾدة ﻟﻠﺷﺑﻛﺔ اﻟداﺧﻠﯾــــﺔ ﻟﻠﻣﻧﺷـﺄة ﺑﺳﻬوﻟــــﺔ‪،‬‬
‫وﯾﻌﯾـــب ﻣوﻗـــﻊ اﻟﻣﻛﺛﻔـــﺎت ﻓـﻲ ﻫـــذﻩ اﻟﺣﺎﻟـﺔ ﻋـدم اﻟـﺗﺧﻠص ﻣــن اﻟﻔﻘـد ) ‪(Losses = I2R‬‬
‫‪Reactive current‬‬ ‫اﻟﻧﺎﺗــــﺞ ﻋــــــن ﻣــــرور ﻣرﻛﺑــــﺔ اﻟﺗﯾـــــﺎر ﻏﯾـــــر اﻟﻔﻌـــــــﺎل )‪Ir‬‬
‫‪ (component‬ﻓﻰ اﻟﺗرﻛﯾﺑﺎت اﻟﻣﺣﺻورة ﺑﯾن ﻫذا اﻟﻣوﻗﻊ ﻟﻠﻣﻛﺛﻔﺎت وﻣواﻗﻊ اﻷﺣﻣﺎل‪.‬‬
‫ﺗرﻛﯾـــب ﻣﺟﻣوﻋـــﺎت اﻟﻣﻛﺛﻔـــﺎت ﻓـــﻲ ﺣـــدود ﻣﻧـــﺎطق ﺗوزﯾـــﻊ ﻣﺟﻣوﻋـــﺎت‬ ‫)‪(٢‬‬
‫اﻷﺣﻣﺎل‪ ،‬ﻛﻣﺎ ﻫو ﻣوﺿﺢ‬

‫‪Tr‬‬

‫‪S‬‬

‫‪C1‬‬ ‫‪C2‬‬

‫‪L‬‬ ‫‪L‬‬ ‫‪L‬‬ ‫‪L‬‬

‫‪٥٤‬‬
‫ﺗرﻛﯾب اﻟﻣﻛﺛﻔﺎت ﺑﺟوار ﻧﻘﺎط اﻟﺗوزﯾﻊ إﻟﻰ اﻷﺣﻣﺎل‬

‫وﯾﺣـﻘــق اﻟﺗرﻛـﯾــب ﻓــﻲ ﻫـــذﻩ اﻟﻣواﻗــــﻊ اﻻﺳﺗﻔـــﺎدة ﻣـــن ﻣﻌــﺎﻣــل‬


‫ﺗﺑـﺎﯾن اﻟﺣـﻣـل )‪ (Load diversity factor‬ﻟﻣﺟﻣوﻋﺔ ﻣن اﻷﺣﻣـﺎل ﻣﻣـﺎ‬
‫ﯾزﯾد ﻣن ﻓﺎﻋﻠﯾﺔ ﺗﺻـﺣﯾﺢ ﻣﻌﺎﻣـل اﻟﻘـدرة ‪ ،‬ﻛﻣـﺎ ﯾـؤدى إﻟـﻰ ﺗﺣﺳـﯾن اﻟﺟﻬـد ﻋﻧـد‬
‫ﻧﻘــﺎط ﺗوﺻـــﯾل ﻛـــل ﻣﺟﻣوﻋـــﺔ ﻣـــن ﻣﺟﻣوﻋــﺎت اﻷﺣﻣـــﺎل‪ ،‬وﯾـــؤدى أﯾﺿـــﺎ ﺗرﻛﯾـــب‬
‫اﻟﻣﻛﺛﻔــﺎت ﻓــﻲ ﻫــذﻩ اﻟﻣواﻗــﻊ إﻟــﻰ إﺗﺎﺣــﺔ ﺗﺣﻣﯾــل أﻋﻠــﻰ ﻟﻠﻣﺣــول )ﺗــوﻓﯾر ﺳــﻌﺎت‬
‫اﻟﻣﺣـــول اﻟﺗـــﻰ ﻛﺎﻧـــت ﻣﺳـــﺗﺧدﻣﺔ ﻗﺑـــل اﻟﺗﺻـــﺣﯾﺢ ( إﻻ أن اﻟﻔﻘـــد اﻟﻧـــﺎﺗﺞ ﻋـــن‬
‫اﻟﺗرﻛﯾﺑﺎت اﻟﺗﻲ ﺗﻠﻲ ﻣواﻗﻊ اﻟﻣﻛﺛﻔﺎت ﻓﻲ ﻫذﻩ اﻟﺣﺎﻟﺔ وﺣﺗﻰ ﻣواﻗﻊ اﻷﺣﻣﺎل ﺗظـل‬
‫ﻣوﺟودة ﻧﺗﯾﺟﺔ ﻟﻣرور ﻣرﻛﺑﺔ اﻟﺗﯾﺎر ﻏﯾـر اﻟﻔﻌـﺎل ﻓـﻲ ﻫـذﻩ اﻟﺗرﻛﯾﺑـﺎت ‪ ،‬وﯾﻼﺣـظ‬
‫أن اﻟﻔﻘد ﻓﻲ ﻫذﻩ اﻟﺣﺎﻟﺔ ﯾﻘل ﻧﺳﺑﯾﺎ ﻋﻧﻪ ﻓﻲ اﻟﺣﺎﻟﺔ اﻟﺳﺎﺑﻘﺔ ‪.‬‬
‫ﺗرﻛﯾب ﻣﺟﻣوﻋﺎت اﻟﻣﻛﺛﻔﺎت ﻋﻧد ﻧﻘﺎط ﺗوﺻﯾل اﻷﺣﻣﺎل ﻣﺑﺎﺷـرة ﻛﻣـﺎ ﻫـو‬ ‫)‪(٣‬‬
‫ﻣوﺿﺢ‬

‫‪Tr‬‬

‫‪S‬‬

‫‪C1‬‬ ‫‪C2‬‬ ‫‪C3‬‬ ‫‪C4‬‬


‫‪L‬‬ ‫‪L‬‬ ‫‪L‬‬ ‫‪L‬‬

‫ﺗﻧﺎﺳــب طرﯾﻘــﺔ اﻟﺗرﻛﯾــب ﻫــذﻩ ﺣﺎﻟــﺔ اﻷﺣﻣــﺎل ﻓــﻰ اﻟﻣﻧــﺎطق اﻟﺻــﻧﺎﻋﯾﺔ اﻟﻣطﻠــوب ﺗﺻــﺣﯾﺢ‬
‫ﻣﻌﺎﻣـــل اﻟﻘـــدرة ﻋﻧـــدﻫﺎ ﻋﻠـــﻰ وﺟـــﻪ اﻟﺧﺻـــوص‪ ،‬ﺣﯾـــث ﯾـــﺗم ﺗرﻛﯾـــب اﻟﻣﻛﺛﻔـــﺎت ﻋﻧـــد ﻧﻘطـــﺔ ﺗﻐذﯾـــﺔ‬
‫اﻟﻣﺣرﻛﺎت ذات اﻟﻘدرات اﻟﻛﺑﯾـرة ﻧﺳـﺑﯾﺎ‪ ،‬وﻫـﻰ اﻟطرﯾﻘـﺔ اﻷﻛﺛـر ﻓﺎﻋﻠﯾـﺔ ﻣـن ﻧﺎﺣﯾـﺔ ﻣوﻗـﻊ اﻟﻣﻛﺛﻔـﺎت‬
‫وذﻟك ﻷن اﻟﻘدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﻣوﻟـدة ﺑواﺳـطﺔ اﻟﻣﻛﺛـف ﯾـﺗم اﺳـﺗﻬﻼﻛﻬﺎ ﻣﺑﺎﺷـرة ﺑواﺳـطﺔ اﻟﺣﻣـل‬
‫اﻟﺣﺛﻰ )اﻟﻣﺣرك( وﺑذﻟك ﯾﻘل اﻟﻔﻘد ﻓﻲ اﻟﺧطوط وﻛذﻟك ﯾﻘل‬
‫ﻫﺑــوط اﻟﺟﻬــد إﻟــﻰ اﻟﺣــد اﻷدﻧــﻰ‪ ،‬ﻛﻣــﺎ ﯾــﻧﺧﻔض اﻟﺗﯾــﺎر ﻓــﻲ ﺷــﺑﻛﺔ اﻟﺗوزﯾــﻊ ﻣﻣــﺎ ﯾــؤدى إﻟــﻰ ﺧﻔــض‬
‫ﺗﻛﺎﻟﯾف ﺗوزﯾﻊ اﻟﻘدرة‪.‬‬

‫‪٥٥‬‬
‫وﺗﺗﻣﯾز ﻫذﻩ اﻟطرﯾﻘﺔ ﺑﺎﻧﻌدام ﻣرور اﻟﺗﯾﺎر ﻏﯾر اﻟﻔﻌﺎل )‪ (Ir‬ﻓﻲ ﻛﺎﺑﻼت اﻟﺗرﻛﯾﺑﺎت وﺑـذﻟك‬
‫ﯾﻘل اﻟﻔﻘد ﻓﻰ اﻟﺧطوط )‪ (I2R‬ﺑﺷﻛل ﻣﻠﺣوظ ‪.‬‬
‫ﻣﻠﺣوظﺔ‪:‬‬
‫ﯾﺟب ﻓﻰ ﺟﻣﯾﻊ اﻷﺣـوال دراﺳـﺔ ﻣزاﯾـﺎ ﺗرﻛﯾـب ﻣﺟﻣوﻋـﺎت اﻟﻣﻛﺛﻔـﺎت ﻓـﻲ اﻟﻣواﻗـﻊ اﻟﻣﺧﺗـﺎرة‬
‫دراﺳﺔ اﻗﺗﺻﺎدﯾﺔ ﻣﺗﺄﻧﯾﺔ‪ ،‬ﻣن ﺣﯾث اﻟﺗﻛﺎﻟﯾف اﻟﻼزﻣﺔ ﻋﻧد ﻛل ﺣﺎﻟﺔ واﻟﻣردود اﻻﻗﺗﺻﺎدي ﻟﺗﺣﺳـﯾن‬
‫ﻣﻌﺎﻣل اﻟﻘدرة ﺣﺳب ﻛل ﻣوﻗﻊ أﺧذا ﻓﻲ اﻻﻋﺗﺑﺎر طﺑﯾﻌﺔ اﻷﺣﻣﺎل اﻟﻣراد ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ﻟﻬـﺎ‬
‫وظروف ﺗﺷﻐﯾﻠﻬﺎ ﺑﻣﺎ ﯾﺣﻘق أﻛﺑر ﻓﺎﺋدة ﻟﻛل ﻣن ﻣرﻓق اﻟﻛﻬرﺑﺎء واﻟﻣﻧﺗﻔﻌﯾن ﺑﻬﺎ ﻣﻌﺎ ﻟﻣﺎ ﻓـﻲ ذﻟـك‬
‫ﻣن ﻣدﻟول اﻗﺗﺻﺎدي إﯾﺟﺎﺑﻲ ﻋﻠﻰ ﻣﺳﺗوى اﻟﻧﺎﺗﺞ اﻟﻘوﻣﻲ ﺑﺻﻔﺔ ﻋﺎﻣﺔ ‪.‬‬

‫اﻟﻣﻌﻠوﻣﺎت واﻟﻘﯾﺎﺳﺎت اﻟواﺟب ﺗواﻓرﻫﺎ ﻹﺟراء ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة‬


‫ﯾﺟب ﺗواﻓر اﻟﻣﻌﻠوﻣﺎت اﻟﺗﺎﻟﯾﺔ ﻋﻧد اﻟﺑدء ﻓﻲ اﻟﺣﺳﺎﺑﺎت اﻟﺧﺎﺻﺔ ﺑﺗﺻـﺣﯾﺢ ﻣﻌﺎﻣـل اﻟﻘـدرة‬
‫ﻟﺗﺣدﯾــد ﻗﯾﻣــﺔ اﻟﻘــدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ اﻟﻣطﻠوﺑــﺔ ﺑواﺳــطﺔ اﻟﻣﻛﺛﻔــﺎت ﻟﺗﻌــوﯾض ﻣــﺎ ﺗﺳــﺗﻬﻠﻛﻪ اﻷﺣﻣــﺎل‬
‫اﻟﺣﺛﯾﺔ ﻣن ﻫذﻩ اﻟﻘدرة‪ ،‬وﯾﺗم اﻟﺣﺻول ﻋﻠﻰ ﻫذﻩ اﻟﻣﻌﻠوﻣﺎت ﺑواﺳـطﺔ أﺟﻬـزة اﻟﻘﯾـﺎس اﻟﻣﺳـﺗﺧدﻣﺔ‬
‫ﻓﻲ ﻗﯾﺎس اﻟﻣﺗﻐﯾرات اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻋﻠﻰ اﻟﻘﺿﺑﺎن اﻟرﺋﯾﺳﯾﺔ أو اﻟﻔرﻋﯾـﺔ ﻟﺷﺑﻛـــﺔ اﻟﺗﻐذﯾـــﺔ ﻣﺛـل ﻗﯾـﺎس‬
‫ﺟﻬد اﻟﺧط )‪ ،(Line voltage‬وﺟﻬد اﻟـطــور )‪ ،(Phase voltage‬وﻛذا ﺷدة اﻟﺗﯾﺎر اﻟﻣﺎر‬
‫ﻓـﻲ اﻟﺧـط )‪ ،(Line current‬وﺗﯾـﺎر ﻛـل طـور )‪ (Phase current‬وﻛـذﻟك ﻗﯾـﺎس ﻣﻌﺎﻣـل‬
‫اﻟﻘدرة ‪ cos Φ‬إﻟﻰ ﺟﺎﻧب اﻟﻘﯾﺎﺳﺎت اﻟﺳﺎﺑﻘﺔ ‪.‬‬
‫وﯾﺗم ﺗوﺻﯾل أﺟﻬزة اﻟﻘﯾﺎس اﻟﻣﺳﺗﺧدﻣﺔ ﻟﻠﺣﺻول ﻋﻠﻰ ﻫذﻩ اﻟﻘﯾﺎﺳﺎت ﻋﻧـد ﻧﻘـط اﻟﻘﯾـﺎس‬
‫اﻟﻣﺧﺗﺎرة ﺑﻣراﻛز اﻷﺣﻣﺎل ﻟﺗﺳـﺟﯾل ﻗـﯾم ﻫـذﻩ اﻟﻘﯾﺎﺳـﺎت ﻋﻠـﻰ ﻣـدار ‪ ٢٤‬ﺳـﺎﻋﺔ‪ ،‬وﯾـﺗم ﻧﻘـل اﻟﻧﺗـﺎﺋﺞ‬
‫إﻟﻰ ﺟﻬﺎز اﻟﺣﺎﺳب اﻵﻟﻲ وﻣن ﺛم رﺻد اﻟﻣﻌﺎﯾﯾر اﻟﻣطﻠوﺑـﺔ و اﻟﻼزﻣـﺔ ﻟﺗﺣدﯾـد ﻗﯾﻣـﺔ اﻟﻘـدرة ﻏﯾـر‬
‫اﻟﻔﻌﺎﻟﺔ اﻟﺗﻲ ﯾﺳﺗﻬﻠﻛﻬﺎ اﻟﺣﻣل وﺑﺎﻟﺗـﺎﻟﻲ ﺗﺣدﯾـد اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﺗﻌوﯾﺿـﯾﺔ اﻟﻣطﻠـوب ﺗوﻟﯾـدﻫﺎ‬
‫ﺑواﺳطﺔ اﻟﻣﻛﺛف أو ﻣﺟﻣوﻋـﺔ اﻟﻣﻛﺛﻔـﺎت اﻟﺗـﻲ ﯾـﺗم ﺗﺣدﯾـد ﺳـﻌﺗﻬﺎ ﻋﻠـﻰ ﺿـوء ﻫـذﻩ اﻟﻘﯾﺎﺳـﺎت ‪ ،‬و‬
‫ﻣن ﻫذﻩ اﻟﻣﻌﺎﯾﯾر ‪-:‬‬
‫ﻣﻌﺎﻣل اﻟﻘدرة اﻟﺣﺎﻟﻲ‬ ‫*‬
‫ﯾــﺗم اﺣﺗﺳــﺎب ﻣﻌﺎﻣــل اﻟﻘــدرة اﻟﺣــﺎﻟﻲ ﻟﻠﻣﻧﺷــﺄة أو اﻟﺣﻣــل ﻣوﺿــوع اﻟدراﺳــﺔ ﻋﻠــﻰ‬
‫ﻣـــدار ﻓﺗـــرة اﻟﻘﯾـــﺎس وﺗﺣـــت ظـــروف ﺗﺣﻣﯾـــل ﻣﺧﺗﻠﻔـــﺔ‪ ،‬وﯾراﻋـــﻰ ﻓـــﻲ ﺗﺣدﯾـــد ﺳـــﻌﺔ‬
‫اﻟﻣﻛﺛﻔﺎت اﻋﺗﺑﺎر أﺳﺎس اﻟﺣﺳﺎب ﻋﻠﻰ أﻗل ﻣﻌﺎﻣل ﻗدرة ﺧﻼل ﻓﺗرة اﻟﻘﯾﺎس ‪.‬‬
‫ﻣﻧﺣﻧﻰ اﻟﺣﻣل‬ ‫*‬

‫‪٥٦‬‬
‫ﯾﺟب اﺳﺗﻧﺗﺎج ﻣﻧﺣﻧﯾﺎت اﻟﺣﻣل ) ‪ ( Load Curves‬ﻟﻛل ﻣن اﻟﻘدرة اﻟﻔﻌـــــﺎﻟﺔ‬
‫)‪ (kW‬واﻟﻘــدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ )‪ (kVAR‬ﻟﻠﺷــﺑﻛﺔ أو ﻟﻸﺣﻣــﺎل اﻟﻣطﻠــوب ﺗﺻــﺣﯾﺢ‬
‫ﻣﻌﺎﻣــل اﻟﻘــدرة ﻟﻬــﺎ ﻣــن ﺧــﻼل اﻟﻘﯾﺎﺳــﺎت اﻟﺗــﻲ أﻣﻛــن اﻟﺣﺻــول ﻋﻠﯾﻬــﺎ ﺧــﻼل ﻓﺗــرة‬
‫اﻟﻘﯾﺎس ﻻﺳﺗﻧﺗﺎج ﻣدى ﺗﺑﺎﯾن اﻟﺣﻣل ﺗﺣت ظروف اﻟﺗﺣﻣﯾل اﻟﻣﺧﺗﻠﻔﺔ‪.‬‬
‫ﻣﻌﺎﻣﻼت ﺗﺑﺎﯾن اﻟﺣﻣل) ‪: ( Load diversity factors‬‬ ‫*‬
‫ﯾــﺗم اﺳــﺗﺧﻼص ﻣﻌــﺎﻣﻼت ﺗﺑــﺎﯾن اﻟﺣﻣــل ﻣــن ﺧــﻼل اﻟﻘ ـراءة اﻟدﻗﯾﻘــﺔ ﻟﻣﻧﺣﻧﯾــﺎت‬
‫اﻟﺣﻣل‪ ،‬وﻫذﻩ اﻟﻣﻌﺎﻣﻼت ﺗﻛﺗﺳب أﻫﻣﯾﺔ ﺧﺎﺻﺔ ﻟﻛوﻧﻬﺎ ﻛﺎﺷﻔﺔ ﻟﻠﻣﺗﻐﯾرات اﻟﻛﻬرﺑﺎﺋﯾﺔ‬
‫ﺑﺎﻟﺷﺑﻛﺔ ﻧﺗﯾﺟﺔ ﻟﺗﺑﺎﯾن ظروف اﻟﺗﺣﻣﯾل اﻟﻣﺗﻌﻠﻘﺔ ﺑطﺑﯾﻌﺔ اﻟﺣﻣـل‪ ،‬وﻋﻠـﻰ ﺿـوء ﻫـذﻩ‬
‫اﻟﻣﻌﺎﻣﻼت ﯾﻣﻛن ﺗﺣدﯾد ﻣواﻗﻊ اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ‪.‬‬
‫ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف ‪:‬‬ ‫*‬
‫ﺑﻌد ﻗﯾـﺎس ﻣﻌﺎﻣل اﻟﻘدرة ﻟﻠﺣﻣل ﻗﺑل اﻟﺗﺻﺣﯾﺢ ﯾﺗم ﺗﺣدﯾد ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣطﻠوب‬
‫اﻟﻣﺳﺗﻬدف )‪ (Target P.f.‬وﺑﺎﺳﺗﺧدام اﻟﺟدول اﻟﺳﺎﺑق ﯾﻣﻛن اﻟﺣﺻول ﻋﻠـﻰ‬
‫اﻟﻣﻌﺎﻣــل ‪ K‬اﻟــذي ﯾﺟــب ﺿــرﺑﻪ ﻓــﻲ ﻗﯾﻣــﺔ اﻟﻘــدرة اﻟﻔﻌﺎﻟــﺔ ﻟﺗﺣدﯾــد ﻗﯾﻣــﺔ اﻟﻘــدرة ﻏﯾــر‬
‫اﻟﻔﻌﺎﻟﺔ )‪ (kVAR‬اﻟﻣطﻠوب إﻧﺗﺎﺟﻬﺎ ﺑواﺳطﺔ اﻟﻣﻛﺛف أو ﻣﺟﻣوﻋﺔ اﻟﻣﻛﺛﻔﺎت‪ ،‬وﻣن‬
‫ﺛم ﺳﻌﺔ ﻛل ﻣﻛﺛف واﻟﺗﻲ ﯾﻣﻛن ﺣﺳﺎﺑﻬﺎ ﻣن اﻟﻣﻌﺎدﻟﺔ‬
‫‪2 -‬‬ ‫[ × )‪tan 1 tan Q (kVAR) = P(kW‬‬
‫)‪Q (kVAR) = K P(kW‬‬
‫ﺣﯾث أن ‪:‬‬
‫‪] 2-‬‬ ‫[ =‪tan 1 tan K‬‬
‫وﯾوﺻﻰ ﺑﺎن ﯾﺗراوح ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف ﻣـﺎ ﺑـﯾن ‪ ٠.٩‬إﻟـﻰ ‪ ٠.٩٥‬ﻟﺿـﻣﺎن‬
‫اﻟﺣﺻول ﻋﻠﻰ أﻛﺑر ﻋﺎﺋد ﻣﻣﻛن ﻧﺗﯾﺟﺔ ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ‪.‬‬
‫ﻣواﺻﻔﺎت اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة‬
‫ﺑﻌد اﻻﻧﺗﻬﺎء ﻣن ﺗﺣدﯾد اﻷﺳـﻠوب اﻷﻣﺛـل ﻟﺗﻌـوﯾض اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ ﻛﻣرﺣﻠـﺔ اﺑﺗداﺋﯾـﺔ‬
‫ﻣن ﻣراﺣل ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ﻓﻲ ﺷﺑﻛﺎت اﻟﺗوزﯾﻊ‪ ،‬ﺗﺑدأ ﻣرﺣﻠـﺔ ﺗوﺻـﯾف اﻟﻣﻛﺛﻔـﺎت وﻣﻠﺣﻘﺎﺗﻬـﺎ‬
‫ﻟﺗﺻـﺑﺢ ﻣطﺎﺑﻘـﺔ ﻟﻠﻣﻧﺻـوص ﻋﻠﯾـﻪ ﺑﺎﻟﻣواﺻـﻔﺎت اﻟﻘﯾﺎﺳـﯾﺔ ﻟﺗﻛـون ﻫـذﻩ اﻟﻣواﺻـﻔﺎت ﻫـﻲ اﻷﺳـﺎس‬
‫اﻟذي ﯾﺗم اﻟﻣﻔﺎﺿﻠﺔ ﻋﻠﯾﻪ ﻋﻧـد ﺗﺣﻠﯾـل ﻋـروض اﻷﺳـﻌﺎر اﻟﺧﺎﺻـﺔ ﺑﺎﻟﺗورﯾـد و اﻟﺗرﻛﯾـب اﻟﺗـﻲ ﺗﻘـدم‬
‫ﻣن اﻟﺷرﻛﺎت اﻟﻣﺧﺗﺻﺔ ﻓﻲ ﻫذا اﻟﻣﺟﺎل‪ ،‬ﻋﻠﻰ أن ﺗﻛون اﻟﻣﻛﺛﻔﺎت اﻟﻣطﻠوﺑـﺔ ﻗـﺎدرة ﻋﻠـﻰ اﻟﺗﺷـﻐﯾل‬
‫اﻟﻣﺳﺗﻣر دون اﻹﺧﻼل ﺑﺎﻟﺷروط اﻵﺗﯾﺔ‪-:‬‬
‫* ﯾﺟــب أن ﯾﻛــون اﻟﺗﺻــﻧﯾﻊ و اﻻﺧﺗﺑــﺎرات ﻟوﺣــدات اﻟﻣﻛﺛﻔــﺎت طﺑﻘــﺎ ﻟﻠﻣواﺻــﻔﺎت‬
‫اﻟدوﻟﯾﺔ اﻟﻛﻬروﺗﻘﻧﯾﺔ ‪. IEC 60831‬‬

‫‪٥٧‬‬
‫ﻣــن اﻟﺗﯾــﺎر اﻟﻣﻘــﻧن ﻟﻠﺗﺷــﻐﯾل ﻧﺗﯾﺟــﺔ ﻟوﺟــود‬ ‫* ﯾﺟــب أن ﯾﺗﺣﻣــل اﻟﻣﻛﺛــف ‪٪١٣٠‬‬
‫ﺗﯾﺎرات ﺗواﻓﻘﯾﺎت ‪.‬‬
‫* ﯾﺟـب أن ﯾراﻋــﻰ ﻓــﻲ ﻣرﺣﻠــﺔ اﻟﺗﺻـﻣﯾم أن ﯾﻛــون اﻟﻣﻛﺛــف أو ﻣﺟﻣوﻋــﺔ اﻟﻣﻛﺛﻔــﺎت‬
‫ﻣـــن اﻟﻘﯾﻣـــﺔ‬ ‫ﻗـــﺎدرة ﻋﻠـــﻰ إﻧﺗـــﺎج ﻗـــدرة ﻏﯾـــر ﻓﻌﺎﻟـــﺔ )‪ (KVAR‬ﺑﻧﺳـــﺑﺔ ‪٪١٣٥‬‬
‫اﻟﻣﺣﺳــوﺑﺔ‪ ،‬ﻟﺗﺷــﻣل اﻟﻘ ـدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ اﻹﺿــﺎﻓﯾﺔ اﻟﺗــﻲ ﺗﺻــﺎﺣب اﻟﺟﻬــود اﻟزاﺋــدة‬
‫ﻧﺗﯾﺟﺔ ﻟظروف اﻟﺗﺷﻐﯾل ﻏﯾر اﻟﻌﺎدﯾﺔ اﻟﺗـﻲ ﺗﻣـر ﺑﻬـﺎ اﻟﻣﻧظوﻣـﺔ‪ ،‬ﺑﺷـرط أﻻ ﺗﺗﺟـﺎوز‬
‫اﻟزﯾﺎدة اﻟﺟﻬد اﻟﻣﻌدل اﻟﻣﻧﺻوص ﻋﻠﯾﻪ أﯾﺿﺎ ﻋﻠﻰ ﻟوﺣﺔ اﻟﺗوﺻﯾف‪.‬‬
‫ﻣــــن اﻟﻘﯾـﻣـــﺔ اﻟﻣـﺗوﺳطـــﺔ ﻟﻠـﺟـــﻬد اﻟﻣﻌﺗـــﺎد ﻋﻠــــﻰ أﺳــﺎس‬ ‫* ﺗﻘـــدر ﻧﺳــﺑﺔ ‪٪١١٥‬‬
‫)‪ ،(Rated voltage r.m.s‬ﻋﻠﻣـﺎ ﺑـﺎن ﻗﯾﻣـﺔ اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﻣطﻠوﺑـﺔ‬
‫ﻟﻠﺗﺣﺳــﯾن ﺗﺣﺳــب ﻋﻧــد ﺟﻬــد اﻟﺗﺷــﻐﯾل وﻫــو ‪ ٤٠٠‬ﻓوﻟــت ‪ ،‬ﻛﻣــﺎ ﯾﻣﻛــن زﯾــﺎدة ﻫــذﻩ‬
‫اﻟﻘﯾﻣﺔ ﻟﻠﺟﻬد إﻟﻰ ‪ ٤٤٠‬ﻓوﻟت ﻓﻲ ﺣﺎﻟﺔ ﺗﺑﯾن وﺟـود ﻣﺣﺗـوى ﺗواﻓﻘﯾـﺎت ﺟﻬـد أﺛﻧـﺎء‬
‫اﻟﻘﯾﺎس‪.‬‬
‫* ﯾﺗم ﺗﺣدﯾد درﺟﺎت اﻟﺣرارة اﻟﺗﻲ ﯾﺗﺣﻣﻠﻬﺎ اﻟﻣﻛﺛـف طﺑﻘـﺎ ﻟظـروف اﻟﻣﻛـﺎن اﻟﻣوﺟـود‬
‫ﺑﻪ ﻟوﺣﺔ اﻟﺟﻬد اﻟﻣﻧﺧﻔض‪ ،‬وﻣن ﺛـم اﻟﻣوﻗـﻊ اﻟﻣﺧﺗـﺎر ﻟﺗرﻛﯾـب اﻟﻣﻛﺛﻔـﺎت ﻣـن ﺣﯾـث‬
‫ﺟودة اﻟﺗﻬوﯾﺔ ‪ ،‬ﻋﻠﻰ أن ﺗﺗراوح ﻣﺎ ﺑﯾن ‪ ْ٥ -‬إﻟﻰ ‪◌ْ ◌ْ ٥٥ +‬‬

‫اﻟﻣﻬﻣﺎت اﻟﻣﻠﺣﻘﺔ ﺑﺎﻟﻣﻛﺛﻔﺎت‬


‫اﻟﻣﻼﻣﺳﺎت وﻗواطﻊ اﻟﻔﺻل واﻟﺗوﺻﯾل ‪:‬‬ ‫)أ(‬
‫ﻧﻣــــوذج ﻟﻠﻣﻼﻣﺳــــﺎت )‪ (Contactors‬واﻟﻣﺻــــﺎﻫر اﻟﻣﺳــــﺗﺧدﻣﺔ ﻣــــﻊ‬
‫ﻣﺟﻣوﻋﺔ ﻣﻛﺛﻔﺎت ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‪.‬‬
‫ﯾﺗم اﺧﺗﯾﺎر ﻫذﻩ اﻟﻣﻌدات ﻋﻠﻰ أﺳـــﺎس اﻟﺗﯾــــﺎر اﻟﻣﻘﻧـــن‬ ‫‪-‬‬
‫اﻟﻌـﺎدي )‪ (Rated normal current‬ﺑﺣﯾـث ﺗﻛـون ﻣﺻـﻣﻣﺔ ﻋﻠـﻰ‬
‫أﺳﺎس ‪ ١.٥‬ﻣرة ﻣن ﻗﯾﻣﺔ اﻟﺗﯾﺎر اﻟﻣﻘﻧن ﻟﻣﺟﻣوﻋﺔ اﻟﻣﻛﺛﻔﺎت ‪.‬‬

‫اﻟﻣﻼﻣﺳﺎت )اﻟﻛوﻧﺗﺎﻛﺗورات(‬ ‫اﻟﻣﺻﺎھر‬

‫‪٥٨‬‬
‫اﻟﻣﻼﻣﺳﺎت واﻟﻣﺻﺎﻫر اﻟﻣﺳﺗﺧدﻣﺔ‬
‫ﻣﻊ ﻣﺟﻣوﻋﺔ ﻣﻛﺛﻔﺎت ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‬

‫اﻟﻣﺻﺎﻫر اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﺣﻣﺎﯾﺔ وﺣدات اﻟﻣﻛﺛﻔﺎت ‪:‬‬ ‫)ب(‬


‫ﻫﻲ ﻣﺻﺎﻫر ذات ﺳﻌﺔ ﻗطﻊ ﻋﺎﻟﯾﺔ وﻣﺣددة ﻟﻠﺗﯾﺎر) ‪Current‬‬
‫‪ (limiting‬وﻣــن اﻟﺧﺻــﺎﺋص اﻟرﺋﯾﺳــﯾﺔ ﻟﻬــﺎ أﻧﻬــﺎ ﺗﺗﺣﻣــل اﻟﻣوﺟــﺎت‬ ‫‪HRC‬‬
‫اﻟﻌﺎﺑرة اﻟﻌﺎﻟﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻣن ﺗﺷﻐﯾل اﻟﻣﻛﺛﻔﺎت ‪.‬‬
‫ﻋﻧـد ﺣـدوث ﻗﺻـر و اﻧﺻـﻬﺎر اﺣـد اﻟﻣﺻـﺎﻫر اﻟداﺧﻠﯾـﺔ اﻟﻣرﻛﺑــﺔ‬
‫ﻋﻠــﻰ وﺣــدة اﻟﻣﻛﺛــف أو ﻣﺻــﻔوﻓﺔ اﻟﻣﻛﺛﻔــﺎت ‪ ،‬ﯾﺣــدث ارﺗﻔــﺎع ﻓــﻲ اﻟﺟﻬــد ﻋﻠــﻰ‬
‫ﻣﺟﻣوﻋﺔ اﻟﻣﻛﺛﻔﺎت اﻟﻣﺗﺻﻠﺔ ﻋﻠﻰ اﻟﺗوازي ﻣﻊ ﻫذا اﻟﻣﺻـﻬر و ﯾرﺟـﻊ ذﻟـك اﻟـﻰ‬
‫زﯾﺎدة ﻣﻣﺎﻧﻌﺔ اﻟﻣﺟﻣوﻋﺔ ﻧﺗﯾﺟﺔ اﻧﺧﻔﺎض اﻟﺳﻌﺔ اﻟﻣﻛﺎﻓﺋـﺔ ﻟﻠﻣﺟﻣوﻋـﺔ اﻟﻣﺗوازﯾـﺔ‬
‫‪.‬‬
‫وﻟﻠﺣﻔــﺎظ ﻋﻠــﻰ اﻟﻣﻛﺛﻔــﺎت ﯾﺟــب أن ﯾﻛــون زﻣــن ﻋﻣــل اﻟﻣﺻــﻬر‬
‫ﺻــﻐﯾ ارً ﺟــداً ﺑﺣﯾــث ﯾﻛــون اﻟﻘطــﻊ ﺳــرﯾﻌﺎً ﺟــدا و ذﻟــك ﻗﺑــل ﺣــدوث أى اﻧﺻــﻬﺎر‬
‫ﻟﻣﺻﻬر آﺧر ﺑﻧﻔس اﻟﻣﺟﻣوﻋﺔ و ﺑﺎﻟﺗﺎﻟﻲ ارﺗﻔﺎع ﻣﺗﺗﺎﻟﻲ ﻓﻰ اﻟﺟﻬد‪.‬‬
‫اﺳﺗﺧدام ﻣﻧظم اﻟﻣراﺣل ﻟﻠﺗﺣﻛم ﻓﻲ اﻟﻣﻛﺛﻔﺎت آﻟﯾﺎ ‪:‬‬ ‫)ت(‬
‫)‪(Automatic capacitor regulator‬‬
‫ﯾﻣﻛــن ﺗوﺻــﯾف اﻟﻣﻛﺛﻔــﺎت ﻣــن ﺣﯾــث اﻟﺗﺷــﻐﯾل إﻣــﺎ ﻣــن‬ ‫*‬
‫‪ "Fixed‬أو اﻟﻧــــوع اﻟﻘﺎﺑــــل ﻟﻠﻔﺻــــل واﻟﺗوﺻـــــﯾل "‬ ‫اﻟﻧـــوع اﻟﺛﺎﺑـــت"‪type‬‬
‫‪."Switched bank‬‬
‫ﺗﺳـــﺗﺧدم اﻟﻣﻛﺛﻔـــﺎت اﻟﺛﺎﺑﺗـــﺔ إذا ﻛﺎﻧـــت أﺣﻣـــﺎل اﻟﻣﻧﺷـــﺄة‬ ‫*‬
‫اﻟﻣراد ﺗرﻛﯾب ﻣﻛﺛف ﻟﻬﺎ ﺛﺎﺑﺗﺔ ﺗﻘرﯾﺑﺎ ﺧﻼل ﻓﺗرات اﻟﺗﺷﻐﯾل واﻟوردﯾﺎت ‪.‬‬
‫ﻣــن ﻋﯾــوب اﻟﻧــوع اﻟﺛﺎﺑــت أﻧــﻪ ﯾﻌﻣــل ﻋﻠــﻰ رﻓــﻊ ﺟﻬــد‬ ‫*‬
‫اﻟﺷﺑﻛﺔ اﻟﻛﻬرﺑﯾﺔ إﻟﻰ ﻗﯾم أﻋﻠﻰ ﻣن اﻟﺟﻬد اﻟﻣﻘﻧن ﻓﻲ ﺧﻼل ﻓﺗـرات اﻟﻼﺣﻣـل‬
‫و اﻷﺣﻣـﺎل اﻟﺧﻔﯾﻔــﺔ ‪ ،‬ﻛــذﻟك ﺗﻘـل اﻻﺳــﺗﻔﺎدة ﻣــن ﺗﺧﻔـﯾض اﻟﻔﻘــد ﻷن اﺧﺗﯾــﺎر‬
‫ﻗدرة اﻟﻣﻛﺛﻔﺎت ﻣـن ﻫـذا اﻟﻧـوع ﯾﻌﺗﻣـد ﻋﻠـﻰ ﻗﯾﻣـﺔ ﺛﺎﺑﺗـﺔ ﻟﻠﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ‬
‫ﺧﻼل ﺳﺎﻋﺎت اﻟﯾوم اﻟﻛﺎﻣل ‪.‬‬

‫‪٥٩‬‬
‫ﯾﻔﺿـــل اﺳـــﺗﺧدام اﻟﻣﻛﺛﻔـــﺎت ﻣـــن اﻟﻧـــوع اﻟﻘﺎﺑـــل ﻟﻠﻔﺻـــل‬ ‫*‬
‫واﻟﺗوﺻﯾل ﺣﯾث ﯾﻣﻛن اﻟﺗﺣﻛم ﻓﻲ إﺿـﺎﻓﺔ ﻗﯾﻣـﺔ اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﻼزﻣـﺔ‬
‫ﻟﻠﺷﺑﻛﺎت اﻟﻛﻬرﺑﯾﺔ ﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ‪ ،‬وﺑذﻟك ﯾﺗﺣﺳن اﻟﺟﻬد وﯾﻘل اﻟﻔﻘد ‪.‬‬
‫إذا ﻛﺎﻧــت اﻷﺣﻣــﺎل ﺗﺗﻐﯾــر ﺑﺻــﻔﺔ ﻣﺳــﺗﻣرة ﺧــﻼل ﻓﺗ ـرات‬ ‫*‬
‫اﻟﺗﺷﻐﯾل‪ ،‬ﻓﺈﻧﻪ ﯾﺗم ﺗرﻛﯾب ﻣﻛﺛﻔﺎت ﻣن اﻟﻧوع اﻟﻘﺎﺑل ﻟﻠﻔﺻل واﻟﺗوﺻﯾل‪ .‬وﻓـﻲ‬
‫ﺣﺎﻟﺔ اﻷﺣﻣﺎل اﻟﺗﻲ ﺗﺟﻣﻊ ﺑﯾن اﻟﺣﺎﻟﺗﯾن اﻟﺳﺎﺑﻘﺗﯾن ) أﺣﻣـﺎل ﺛﺎﺑﺗـﺔ ‪ +‬أﺣﻣـﺎل‬
‫ﻣﺗﻐﯾرة ( ﻓﺈﻧﻪ ﯾﻣﻛن ﺗرﻛﯾب ﻣﻛﺛﻔﺎت ﺗﺣﺗوي ﻋﻠﻰ ﺟزء ﺛﺎﺑت وﺟزء ﻣـن اﻟﻧـوع‬
‫اﻟﻘﺎﺑل ﻟﻠﻔﺻل واﻟﺗوﺻﯾل‪.‬‬
‫ﺗﻘﺳم اﻟﻣﻛﺛﻔﺎت ﻣن اﻟﻧوع اﻟﻘﺎﺑل ﻟﻠﻔﺻل واﻟﺗوﺻﯾل إﻟـﻰ‬ ‫*‬
‫أﺟزاء ﺗﺳﻣﻰ ﻣراﺣل ) ‪ (Steps‬ﻟﻬﺎ ﻗدرات ) ك‪ .‬ﻓﺎر ( ﻣﺣددة ﺣﯾـث ﯾـﺗم‬
‫اﻟـــﺗﺣﻛم ﻓـــﻲ دﺧـــول ﻣرﺣﻠـــﺔ أو أﻛﺛـــر ﻋـــن طرﯾـــق أﺟﻬـــزة اﻟـــﺗﺣﻛم اﻵﻟـــﻲ )‬
‫‪ ( Automatic Regulator‬ﻣـن ﺧـﻼل ﻣﻼﻣـس ) ‪( Contactor‬‬
‫ﻟﻛل ﻣرﺣﻠﺔ ‪.‬‬

‫‪Automatic‬‬ ‫)‬ ‫اﻟﺷــــروط اﻟواﺟــــب ﺗواﻓرﻫــــﺎ ﻓــــﻲ أﺟﻬــــزة اﻟــــﺗﺣﻛم اﻵﻟــــﻲ‬


‫‪:(Regulator‬‬
‫أن ﯾﻛون ﺗﺻﻣﯾم اﻟﺟﻬﺎز ﺑﺳﯾطﺎ ﺑﻘدر اﻹﻣﻛﺎن وأن ﯾﻛون ﻣوﺛوﻗﺎ ﺑﻪ‪.‬‬ ‫*‬
‫أن ﯾﺗﺣﻣل ظروف اﻟﺑﯾﺋﺔ اﻟﺻﻧﺎﻋﯾﺔ‪.‬‬ ‫*‬
‫ﻟﻪ اﻟﻣﻘدرة ﻋﻠﻰ ﺗوﺻﯾل أو ﻓﺻل ﻣرﺣﻠﺔ أو أﻛﺛر ﻣن اﻟﻣﻛﺛﻔﺎت‪.‬‬ ‫*‬
‫أن ﯾﻛون ﺳﻬل اﻟﺿﺑط‪.‬‬ ‫*‬
‫* ﻓــﻲ ﺣﺎﻟــﺔ اﻷﺟﻬــزة ذات اﻟﻣراﺣــل اﻟﻣﺗﻌــددة ﯾﺟــب أن ﯾﺟﻬــز ﻷي اﺣﺗﻣــﺎل ﺑﺈﺿــﺎﻓﺔ‬
‫ﻣراﺣل ﺗﺎﻟﯾﺔ‪.‬‬

‫اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺗوﺻﯾل اﻟﻣﻛﺛﻔﺎت ‪:‬‬ ‫)ث(‬


‫ﯾﺗم اﺧﺗﯾﺎر ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟﻛﺎﺑل طﺑﻘﺎ ﻟﻠﻣواﺻـﻔﺎت اﻟﻛﻬروﺗﻘﻧﯾـﺔ‬
‫)‪ (IEC – 46‬ﻋﻠــﻰ أﺳــﺎس أن ﯾﻛــون اﻟﺗﯾــﺎر اﻟﻣــﺎر ﯾﺳــﺎوى‬ ‫اﻟدوﻟﯾـﺔ‬
‫‪ ٪١٣٥‬ﻣن اﻟﺗﯾﺎر اﻟﻣﻘﻧن ﻟﻠﻣﻛﺛف‪.‬‬

‫‪٦٠‬‬
‫وﯾﺑــﯾن اﻟﺟــدول اﻟﺗــﺎﻟﻲ ﻣﻘﻧﻧــﺎت اﻟﻣﺻــﺎﻫر وﻣﻘــﺎطﻊ ﻣوﺻــﻼت‬
‫اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدﻣﺔ‪.‬‬

‫ﻣﻘﻧﻧﺎت اﻟﻣﺻﺎﻫر وﻣﻘﺎطﻊ اﻟﻣوﺻﻼت‬


‫اﻟﻣﺳﺗﺧدﻣﺔ ﻣﻊ ﻣﻛﺛﻔﺎت ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‬
‫طﺑﻘﺎً ﻟﻣﻘﻧن أﺟﻬزة اﻟﻣﻼﻣﺳﺎت )‪(Contactors‬‬

‫‪RATED‬‬ ‫‪RATED VOLTAGE VOLTAGE 415 V,‬‬


‫‪VOLTAGE 230‬‬ ‫‪400 V,‬‬ ‫‪50 HZ‬‬
‫‪V,‬‬ ‫‪50 HZ‬‬
‫‪OUT‬‬
‫‪50 HZ‬‬
‫‪PUT‬‬
‫‪RATE FU CAB RATE FU CAB RATE FU CAB‬‬
‫‪(kVA‬‬
‫‪D‬‬ ‫‪SE LE/‬‬ ‫‪D‬‬ ‫‪SE LE/‬‬ ‫‪D‬‬ ‫‪SE LE/‬‬
‫)‪R‬‬ ‫‪2‬‬
‫‪CURR (A) (mm CURR (A) (mm CURR (A) (mm‬‬
‫‪2‬‬ ‫‪2‬‬
‫‪ENT‬‬ ‫)‬ ‫‪ENT‬‬ ‫)‬ ‫‪ENT‬‬ ‫)‬
‫)‪(A‬‬ ‫)‪(A‬‬ ‫)‪(A‬‬
‫‪2.5‬‬ ‫‪6.3‬‬ ‫‪16‬‬ ‫‪2.5‬‬ ‫‪3.6‬‬ ‫‪10‬‬ ‫‪1.5‬‬ ‫‪3.5‬‬ ‫‪10‬‬ ‫‪1.5‬‬
‫‪5‬‬ ‫‪12.6‬‬ ‫‪25‬‬ ‫‪4‬‬ ‫‪7.2‬‬ ‫‪20‬‬ ‫‪2.5‬‬ ‫‪7.0‬‬ ‫‪20‬‬ ‫‪2.5‬‬
‫‪6.67‬‬ ‫‪16.7‬‬ ‫‪35‬‬ ‫‪6‬‬ ‫‪9.6‬‬ ‫‪20‬‬ ‫‪2.5‬‬ ‫‪9.3‬‬ ‫‪20‬‬ ‫‪2.5‬‬
‫‪7.5‬‬ ‫‪19‬‬ ‫‪35‬‬ ‫‪6‬‬ ‫‪10.8‬‬ ‫‪20‬‬ ‫‪2.5‬‬ ‫‪10.4‬‬ ‫‪20‬‬ ‫‪2.5‬‬
‫‪0‬‬
‫‪8.33‬‬ ‫‪21‬‬ ‫‪35‬‬ ‫‪6‬‬ ‫‪12‬‬ ‫‪20‬‬ ‫‪2.5‬‬ ‫‪11.6‬‬ ‫‪20‬‬ ‫‪2.5‬‬
‫‪10‬‬ ‫‪25‬‬ ‫‪50‬‬ ‫‪10‬‬ ‫‪14.4‬‬ ‫‪25‬‬ ‫‪4‬‬ ‫‪13.9‬‬ ‫‪25‬‬ ‫‪4‬‬
‫‪12.5‬‬ ‫‪31‬‬ ‫‪63‬‬ ‫‪16‬‬ ‫‪18‬‬ ‫‪35‬‬ ‫‪6‬‬ ‫‪17.4‬‬ ‫‪35‬‬ ‫‪6‬‬
‫‪15‬‬ ‫‪38‬‬ ‫‪63‬‬ ‫‪16‬‬ ‫‪21.7‬‬ ‫‪35‬‬ ‫‪6‬‬ ‫‪20.9‬‬ ‫‪35‬‬ ‫‪6‬‬
‫‪16.7‬‬ ‫‪42‬‬ ‫‪80‬‬ ‫‪25‬‬ ‫‪24.1‬‬ ‫‪50‬‬ ‫‪10‬‬ ‫‪23.2‬‬ ‫‪50‬‬ ‫‪10‬‬
‫‪20‬‬ ‫‪50‬‬ ‫‪100‬‬ ‫‪35‬‬ ‫‪28.9‬‬ ‫‪50‬‬ ‫‪10‬‬ ‫‪27.8‬‬ ‫‪50‬‬ ‫‪10‬‬
‫‪25‬‬ ‫‪63‬‬ ‫‪125‬‬ ‫‪50‬‬ ‫‪36.1‬‬ ‫‪63‬‬ ‫‪16‬‬ ‫‪34.8‬‬ ‫‪63‬‬ ‫‪16‬‬
‫‪30‬‬ ‫‪75‬‬ ‫‪125‬‬ ‫‪50‬‬ ‫‪43.3‬‬ ‫‪80‬‬ ‫‪25‬‬ ‫‪41.7‬‬ ‫‪80‬‬ ‫‪25‬‬
‫‪33.3‬‬ ‫‪84‬‬ ‫‪160‬‬ ‫‪70‬‬ ‫‪48.1‬‬ ‫‪80‬‬ ‫‪25‬‬ ‫‪46.3‬‬ ‫‪80‬‬ ‫‪25‬‬
‫‪40‬‬ ‫‪100‬‬ ‫‪160‬‬ ‫‪95‬‬ ‫‪57.7‬‬ ‫‪10‬‬ ‫‪35‬‬ ‫‪55.6‬‬ ‫‪100‬‬ ‫‪35‬‬
‫‪0‬‬
‫‪50‬‬ ‫‪125‬‬ ‫‪250‬‬ ‫‪120‬‬ ‫‪72.2‬‬ ‫‪12‬‬ ‫‪50‬‬ ‫‪69.6‬‬ ‫‪125‬‬ ‫‪50‬‬

‫‪٦١‬‬
‫‪5‬‬
‫‪60‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪86.6‬‬ ‫‪16‬‬ ‫‪70‬‬ ‫‪83.5‬‬ ‫‪160‬‬ ‫‪70‬‬
‫‪0‬‬
‫‪66.7‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪96.3‬‬ ‫‪16‬‬ ‫‪70‬‬ ‫‪92.8‬‬ ‫‪160‬‬ ‫‪70‬‬
‫‪0‬‬
‫‪70‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪101‬‬ ‫‪16‬‬ ‫‪70‬‬ ‫‪97‬‬ ‫‪160‬‬ ‫‪70‬‬
‫‪0‬‬
‫‪75‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪108‬‬ ‫‪16‬‬ ‫‪70‬‬ ‫‪104‬‬ ‫‪160‬‬ ‫‪70‬‬
‫‪0‬‬
‫‪83.3‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪120‬‬ ‫‪20‬‬ ‫‪95‬‬ ‫‪116‬‬ ‫‪200‬‬ ‫‪95‬‬
‫‪0‬‬
‫‪100‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪144‬‬ ‫‪25‬‬ ‫‪120‬‬ ‫‪139‬‬ ‫‪250‬‬ ‫‪120‬‬
‫‪0‬‬

‫أﻗل ﻣﻌﺎﻣل ﻗدرة ﻣﺳﻣوح ﺑﻪ‬


‫‪ -‬ﺗﺷــﺗرط ﻫﯾﺋــﺎت إﻣــداد اﻟﻛﻬرﺑــﺎءﻋﻠﻰ ﻋﻣﻼﺋﻬــﺎ أﻻ ﯾﻘــل ﻣﻌﺎﻣــل اﻟﻘــدرة ﻟﻸﺣﻣــﺎل اﻟﻛﺑﯾــرة‬
‫اﻟﺻﻧﺎﻋﯾﺔ واﻟﺗﺟﺎرﯾﺔ ﻋن ﻗﯾﻣﺔ ﻣﺣددة وﻋﻠﻰ أن ﯾﻛون ﻣﻌﺎﻣل اﻟﻘدرة ‪ ٠.٩‬ﻋﻠﻰ اﻷﻗل‪.‬‬
‫ﻋﻧدﻣﺎ ﯾﻛون ﻣﻌﺎﻣل اﻟﻘدرة أﻗل ﻣن ‪) ٠.٩‬ﻣﺛﻼ ﻣﺎ ﺑﯾن ‪ ٠.٧‬و ‪ (٠.٩‬ﻓﺈن ﺗﻌرﯾﻔـﺔ ﺗﻐذﯾـﺔ‬
‫اﻟطﺎﻗﺔ ﺗزاد ﺑﻣﻘدار‪ ٪٠.٥‬ﻟﻛل ‪ ٠.٠١‬إﻧﺧﻔـﺎض ﻓـﻰ ﻣﻌﺎﻣـل اﻟﻘـدرة ﻋـن أﻗـل ﻗﯾﻣـﺔ ﻣﺳـﻣوح ﺑﻬـﺎ‪٠‬‬
‫وﯾﻣﻛن ﺣﺳﺎب ﺗﻛﻠﻔﺔ ﻏراﻣﺔ ﻣﻌﺎﻣل اﻟﻘدرة ﻣن اﻟﻣﻌﺎدﻟﺔ‬
‫‪0.9 - P.f‬‬
‫( ‪Annual cos t of penalty  0.005 ‬‬ ‫)‪)  (Annual consumption)  tariff(L.E/kWhr‬‬
‫‪0.01‬‬

‫وﻓﻰ ﺣﺎﻟﺔ زﯾﺎدة ﻣﻌﺎﻣل اﻟﻘدرة ﻋن ‪) ٠.٩٢‬ﻣﺎ ﺑـﯾن ‪ ٠.٩٢‬و ‪ (٠.٩٥‬ﻓﺳـوف ﺗـﻧﺧﻔض‬
‫اﻟﺗﻌرﯾﻔــﺔ ﺑﻣﻘــدار ‪ ٪٠.٥‬ﻟﻛــل ‪ ٠.٠١‬زﯾــﺎدة ﻓــﻰ ﻣﻌﺎﻣــل اﻟﻘــدرة أﻛﺛــر ﻣــن ‪ ٠.٩٢‬وﯾﻣﻛــن ﺣﺳــﺎب‬
‫ﺗﻛﻠﻔﺔ ﺣﺎﻓز )‪ (Bonus‬زﯾﺎدة ﻣﻌﺎﻣل اﻟﻘدرة ﻣن اﻟﻣﻌﺎدﻟﺔ ﻛﺎﻵﺗﻰ‪:‬‬
‫‪P.f - 0.92‬‬
‫( ‪Annual cos t of bonous  0.005 x‬‬ ‫‪) x Annual consumptio n(kwhr) x tariff‬‬
‫‪0.01‬‬

‫ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻟﺗﺟﺎرﯾﺔ‬


‫ﺗوﺻﯾل ﻣﻛﺛف ﻋﻠﻰ اﻟﺗوازى ﻣﻊ اﻟﺣﻣل‬ ‫)أ(‬

‫‪٦٢‬‬
‫ﻟﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ﯾﺗم ﺗوﺻﯾل ﻣﻛﺛف ﻋﻠـﻰ اﻟﺗـوازى‬ ‫‪-‬‬
‫ﻣﻊ اﻟﺣﻣل )ﻣﺣرﻛﺎت ﻛﻬرﺑﺎﺋﯾﺔ أو ﻣﺻﺎﺑﯾﺢ ﺗﻔرﯾﻎ ﻛﻬرﺑﻰ(‪.‬‬
‫ﯾﻣﻛــن ﺣﺳــﺎب زﯾــﺎدة اﻟﻧﺳــﺑﺔ اﻟﻣﺋوﯾــﺔ ﻟﺗﻘﻠﯾــل اﻟﻔﻘــد ﻓــﻰ‬ ‫‪-‬‬
‫اﻟﻘدرة اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻋﻧدﻣﺎ ﯾﺗﺣﺳن ﻣﻌﺎﻣل اﻟﻘدرة ﻣن ‪ cos 1‬إﻟـﻰ ‪ cos 2‬ﻣـن‬
‫اﻟﻣﻌﺎدﻟﺔ )‪ (٨-٩‬ﻛﺎﻵﺗﻲ‪:‬‬

‫‪ cos 1 2 ‬‬


‫‪% Re duction of losses  1 -‬‬ ‫‪2 ‬‬
‫‪x 100‬‬
‫‪‬‬ ‫‪‬‬‫‪cos‬‬ ‫‪‬‬ ‫‪2‬‬ ‫‪‬‬ ‫‪‬‬

‫ﺑﻔرض أن ‪cos 1 = 0.6 :‬‬


‫ﻓـــﺈن اﻟﻧﺳـــﺑﺔ اﻟﻣﺋوﯾـــﺔ ﻟﺗﻘﻠﯾـــل اﻟﻔﻘـــد ﻓـــﻰ اﻟﻘـــدرة ﻋﻧـــد‬
‫ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة إﻟﻰ اﻟﻘﯾم اﻟواردة ﻓﻰ اﻟﺟدول اﻟﺗﺎﻟﻲ وﺗﻛون ﻛﻣـﺎ ﯾﻠـﻰ‬
‫‪:‬‬

‫ﺗﻘﻠﯾل اﻟﻔﻘد ﻓﻰ اﻟﻘدرة اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻧﺗﯾﺟﺔ ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة‬


‫) ‪( P . f 1  0 .6‬‬

‫‪١‬‬ ‫‪٠.٩‬‬ ‫‪٠.٨‬‬ ‫‪٠.٧‬‬ ‫ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف‬


‫) ‪(P.f 2‬‬
‫‪٦٤‬‬ ‫‪٥٥.٥‬‬ ‫‪٤٣.٧‬‬ ‫‪٢٦.٥‬‬ ‫ﺗﻘﻠﯾل اﻟﻔﻘد ‪٪‬‬

‫ﺗوﺻﯾل ﻣﻛﺛف ﻋﻠﻰ اﻟﺗوازى ﻣﻊ اﻟﺣﻣل )اﻟﻣﺻﺎﺑﯾﺢ اﻟﻔﻠورﯾﺔ(‬


‫ﯾﻛون ﻣﻌﺎﻣل اﻟﻘـدرة ﻟﻠﻣﺻـﺎﺑﯾﺢ اﻟﻔﻠورﯾـﺔ ﻋـﺎدة‬ ‫‪-‬‬
‫ﻣﻧﺧﻔﺿــﺎ‪ ،‬وﻟــذﻟك ﯾﻣﻛــن اﺳــﺗﺧدام ﻣﻛﺛــف ﻋﻠــﻰ اﻟﺗ ـوازى ﻟﺗﺣﺳــﯾن ﻣﻌﺎﻣــل‬
‫اﻟﻘدرة‪.‬‬
‫ﻋﻧــــدﻣﺎ ﯾﺳــــﺗﺧدم ﻣﻛﺛــــف ‪ ٥‬ﻣﯾﻛروﻓــــﺎراد ﻣــــﻊ‬ ‫‪-‬‬
‫ﻣﺻﺑﺎح ﻓﻠورى ﺑطول ‪٦٠‬ﺳم ﻗدرة ‪ ٢٠‬وات‪ ،‬ﻓﺈن ﻣﻌﺎﻣـل اﻟﻘـدرة ﯾﺗﺣﺳـن‬
‫ﻣــن ‪ ٠.٣٦‬إﻟــﻰ ‪ ٠.٩٤‬وﺗﺗﻐﯾــر ﻗﯾﻣــﺔ اﻟﺗﯾـــﺎر ﻣـــن ‪ ٠.٣٧٩‬أﻣﺑﯾــر إﻟــﻰ‬

‫‪٦٣‬‬
‫‪ ٠.١٥‬أﻣﺑﯾــر‪ ٠‬أﻣــﺎ إذا اﺳــﺗﺧدم ﻣﻛﺛــف ﺳــﻌﺔ ‪٥‬ﻣﯾﻛروﻓــﺎراد ﻣــﻊ ﻣﺻــﺑﺎح‬
‫ﻓﻠورى ﺑطول ‪١٢٠‬ﺳم ﻗدرة ‪٤٠‬وات‪ ،‬ﻓﯾﺗﺣﺳن ﻣﻌﺎﻣل اﻟﻘـدرة ﻣـن ‪٠.٤٨‬‬
‫إﻟﻰ ‪ ٠.٩٣‬وﺗﺗﻐﯾر ﻗﯾﻣﺔ اﻟﺗﯾﺎر ﻣن ‪ ٠.٤٠٤‬أﻣﺑﯾر إﻟﻰ ‪ ٠.٢٠١‬أﻣﺑﯾر‪.‬‬
‫ﺑﻧك ﻣﻛﺛﻔﺎت ﻣﻊ اﻟﻠوﺣﺔ اﻟرﺋﯾﺳﯾﺔ‬ ‫)ب(‬
‫ﻟﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻛﻠﻰ ﻓﺈﻧـﻪ ﯾﻣﻛـن اﺳـﺗﺧدام ﺑﻧـك‬ ‫‪-‬‬
‫ﻣﻛﺛﻔﺎت )ﺛﺎﺑت أو ﻣﺗﻐﯾر( ﻣﻊ اﻟﻠوﺣﺔ اﻟرﺋﯾﺳﯾﺔ ﺑدﻻ ﻣن وﺿﻊ ﻣﻛﺛـف ﻣﻧﻔـرد‬
‫ﻋﻠﻰ اﻟﺗوازى ﻣﻊ ﻛل ﺣﻣل‪.‬‬
‫ﯾﻣﻛــــن ﺗﺣدﯾــــد ﻗﯾﻣــــﺔ اﻟﻘــــدرة ﻏﯾــــر اﻟﻔﻌﺎﻟــــﺔ ﻟﻠﻣﻛﺛﻔــــﺎت‬ ‫‪-‬‬
‫اﻟﻣطﻠوﺑـﺔ ‪ (kVAR)c‬ﻟﺗﺣﺳـﯾن ﻣﻌﺎﻣـل اﻟﻘـدرة ﻣـن ‪ P.f 1‬إﻟـﻰ ‪P.f 2‬‬
‫ﻣن اﻟﻣﻌﺎدﻟﺔ ﻛﺎﻵﺗﻲ ‪:‬‬
‫‪kVAR c  kVA  P.f1  tan cos -1 P. f1  - kVA  P.F2  tan cos -1 P. f 2 ‬‬

‫ﯾﻣﻛن ﺣﺳﺎب ﻓﺗرة اﻻﺳﺗرداد اﻟﺗﻰ ﯾﺗﺳﺎوى ﻋﻧدﻫﺎ ﺗﻛﻠﻔﺔ‬ ‫‪-‬‬


‫ﺑﻧــك اﻟﻣﻛﺛﻔــﺎت ﻣــﻊ اﻟﺗﻛﻠﻔ ـﺔ اﻟﻛﻠﯾــﺔ ﻟﻐراﻣــﺔ وﺣــﺎﻓز ﻣﻌﺎﻣــل اﻟﻘــدرة اﻟﻣــﻧﺧﻔض‬
‫اﻟﻣﻘررة ﻣن ﻫﯾﺋﺎت اﻟﻛﻬرﺑﺎء‪.‬‬

‫‪٦٤‬‬
GENERATORS

ETERNAL ENGINEERS GROUP


01007200959-01114911166

٦٥
‫ﻧظﺎم اﻟﺑطﺎرﯾﺎت اﻟﻣرﻛزى‬
‫‪ -‬ﯾﺳﺗﺧدم ﻫذا اﻟﻧظﺎم ﻛﻣﺻدر ﺑدﯾل ﻹﻧﺎرة اﻟطوارئ وﯾﻌﺗﻣد ﻋﻠﻰ ﺗوﻓﯾر ﻣﺻدرﻟﺗﻐذﯾﺔ وﺣدات‬
‫إﻧﺎرة طوارئ ﺗﻌﻣل ﻋﻠﻰ اﻟﺗﯾﺎر اﻟﻣﺳﺗﻣر )‪. (DC‬‬
‫‪ -‬ﯾﻛون اﺳﺗﺧدام ﺑطﺎرﯾﺎت ﺗظل ﻣﺷﺣوﻧﺔ إﻟﻰ اﻟدرﺟﺔ اﻟﺗﻰ ﺗﻛﻔﻰ ﻟﺗﻐذﯾﺔ ﻣﻌظم اﻷﺣﻣﺎل‬
‫اﻟﻣطﻠوﺑﺔ ﻟﻠﺧدﻣﺔ ﺑﻛﺎﻣل اﻟﻣﺑﻧﻰ ﺻﻌﺑًﺎ ﻣن اﻟﻧﺎﺣﯾﺔ اﻟﻌﻣﻠﯾﺔ وﻟﻛﻧﻬﺎ ﺗﺻﻠﺢ ﻓﻘط ﻟﺗﻐذﯾﺔ ﻧظم‬
‫إﻧﺎر ة اﻟطوارئ اﻟﺗﻰ ﺗﻌﺗﻣد ﺑدرﺟﺔ ﻛﺑﯾرة ﻋﻠﻰ ﻣدى ﺷﺣن ﻫذﻩ اﻟﺑطﺎرﯾﺎت واﻟﺗﻰ ﻋﻧد اﻧﺗﻬﺎء‬
‫ﺷﺣﻧﺗﻬﺎ ﯾﺗوﻗف ﻣﻌﻬﺎ اﻟﻧظﺎم وﺗﻛون إﻋﺎدة اﺳﺗﺧداﻣﻬﺎ ﺑﻌد ذﻟك ﻣرﺗﺑطﺎً ﺑطول ﻣدة ﻋطل‬
‫ﻣﺻدر ﺗﯾﺎر اﻟﻣدﯾﻧﺔ ﺛم إﻋﺎدة ﺷﺣن اﻟﺑطﺎرﯾﺎ ت ‪.‬وﺑﺎﻟﺗﺎﻟﻰ ﻓﺈن ﻫذا اﻟﻧظﺎﻣﻬذا اﻟﻧظﺎم ﻏﯾر‬
‫آﻣن وﻻ ﯾﺣﻘق اﻟﻐرﺿﻣﻧﻪ ﻓﻰ ﺣﺎﻟﺔ ﻋطل اﻟﻣﺻدر ﻟﻣدد طوﯾﻠﺔ‪.‬‬

‫اﻟﻣوﻟدات اﻻﺣﺗﯾﺎطﯾﺔ )‪(Standby Generators‬‬

‫‪-‬ﻫﻰ ﻣوﻟدات اﻟﻘوى اﻻﺣﺗﯾﺎطﯾﺔ اﻟﺗﻰ ﺗﻌﻣل ﺑﺎﻟدﯾزل وﯾﻣﻛن ﺗرﻛﯾﺑﻬﺎ ﻓﻰ اﻟﻣﺑﺎﻧﻰ ﻹﻣدادﻫﺎ‬
‫ﺑﺎﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ ﻓﻰ ﺣﺎﻟﺔ اﻧﻔﺻﺎل أو ﺗﻌطل ﻣﺻﺎدر اﻟﻣدﯾﻧﺔ وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﺗﺣﻘق ﺿﻣﺎن‬
‫ﻛﺎﻣل ﻟﻠﺣﻣﺎﯾﺔ ﻣن ﻓﺻل أو ﻋطل ﻣﺻﺎدر اﻟﺗﻐذﯾﺔﻣن اﻟﻣدﯾﻧﺔ‪.‬‬
‫‪ -‬ﯾﻣﻛن أن ﯾﻛون اﻟﻣوﻟد اﻻﺣﺗﯾﺎطﻰ ﺑﺳﻌﺔ ﺗﻛﻔﻰ ﻣﺟﻣوع اﻷﺣﻣﺎل ﺑﺎﻟﻣﺑﻧﻰ وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ‬
‫ﯾﻣﻛن أن ﯾﺗﺻل ﻣﺑﺎﺷرة ﺑﺎﻟﻠوﺣﺔ اﻟﻌﻣوﻣﯾﺔ ﻟﻠﻣﺑﻧﻰ ﺑﻌد ﻋداد اﺗﺣﺳﺎب اﻟطﺎﻗﺔ اﻟﺧﺎﺻﺔ ﺑﺷرﻛﺔ‬
‫اﻟﺗوزﯾﻊ ﻟﺗﻐذﯾﺔ ﻛﺎﻣل اﻟﻣﺑﻧﻰ ﺑﻛل أﺣﻣﺎﻟﻪ‪ ،‬وﯾﺗم ذﻟك ﻋن طرﯾق ﺳﻛﯾﻧﺔ ﻗﻼب ﯾدوﯾﺔ أو‬
‫ﺑﺎﺳﺗﺧدام ﻣﻔﺗﺎح ﺗﺣوﯾل ﺗﻠﻘﺎﺋﻰ‬
‫‪ -‬ﯾﻣﻛن اﺳﺗﺧدام ﻣوﻟد طوارئ ﻟﺗﻐذﯾﺔ اﻷﺣﻣﺎل اﻟﻬﺎﻣﺔ ﺑﺎﻟﻣﺑﻧﻰ ﻓﻘط وﻗت اﻧﻘطﺎع ﻣﺻدر‬
‫اﻟﻣدﯾﻧﺔ‪ ،‬وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﯾﺗﺑﻊ أﺳﻠوب اﻟﺗوزﯾﻊ ﻟﺗﻐذﯾﺔ اﻷﺣﻣﺎل ﺑﺣﯾث ﯾﺗم ﻧﻘل اﻟﺗﻐذﯾﺔ ﻣن‬
‫ﻣﺻدر اﻟﻣدﯾﻧﺔ إﻟﻰ اﻟﻣوﻟد اﻻﺣﺗﯾﺎطﻲ ﻣن ﻣرﻛز ﺗوزﯾﻊ واﺣد ﻟﺗﻐذﯾﺔ ﺟﻣﯾﻊ أﺣﻣﺎل وﺧدﻣﺎت‬
‫اﻟطوارئ وذﻟك ﺑﺄن ﺗﻘﺳم اﻷﺣﻣﺎل ﻋﻧد ﻣﺻدر اﻟﺗﻐذﯾﺔ إﻟﻰ ﻗﺳﻣﯾن أﺣدﻫﻣﺎ ﻟﻸﺣﻣﺎل وﯾﺗﺻل‬
‫ﻓﻘط اﻟﻬﺎﻣﺔ واﻷﺧرى ﻟﻸﺣﻣﺎل ﻏﯾر اﻟﻬﺎﻣﺔ ﻗﺳم اﻷﺣﻣﺎل اﻟﻬﺎﻣﺔ ﺑﻣﺻدرى اﻟﺗﻐذﯾﺔ ﻣﺻدر‬
‫اﻟﻣدﯾﻧﺔ وﻣﺻدر اﻟﻣوﻟد اﻻﺣﺗﯾﺎطﻰ ﺑﯾﻧﻣﺎ ﯾﺗﺻل ﻗﺳم اﻷﺣﻣﺎل ﻏﯾر اﻟﻬﺎﻣﺔ ﺑﻣﺻدر اﻟﻣدﯾﻧﺔ‬
‫ﻓﻘط ﻋﻠﻰ اﻟﻧﺣو اﻟﻣوﺿﺢ ﺑﺎﻷﺷﻛﺎل اﻟﺗﺎﻟﻰ‬

‫‪٦٦‬‬
٦٧
٦٨
‫‪ -‬ﯾﻣﻛن ﺑدء ﺗﺷﻐﯾل ﻣﺎﻛﯾﻧﺎت اﻟدﯾزل ﻹدارة ﻣوﻟدات اﻟطوارئ ﯾدوﯾًﺎ أو ﺗﻠﻘﺎﺋﯾًﺎ‪،‬وﺑﺎﻟرﻏم‬
‫ﻣن ﺑﺳﺎطﺔ اﻟﺑدء ﯾدوﯾًﺎ وﻗﻠﺔ ﺗﻛﻠﻔﺗﻪ إﻻ أﻧﻪ ﺑطﺊ ﻧﺳﺑﯾًﺎ ﻣﻣﺎ ﯾﺳﺑب إﺑﻘﺎء اﻟﻣﺑﻧﻰ‬
‫دون ﻣﺻدر ﻛﻬرﺑﺎﺋﻰ ﻟﻔﺗرة زﻣﻧﯾﺔ إﻟﻰ أن ﯾﺗم إدارة اﻟوﺣدة ﺑﯾﻧﻣﺎ ﯾﻘﻠل اﻟﺑدء ﺗﻠﻘﺎﺋﯾًﺎ‬
‫ﻣن ﻫذﻩ اﻟﻣدة وﯾطﻠق ﻋﻠﻰ ﻣﺎﻛﯾﻧﺔ إدارة ﻣوﻟد اﻟطوارئ اﻟﻣزودة ﺑﺑدء ﺗﻠﻘﺎﺋﻰ ﺑﺄﻧﻬﺎ‬
‫ﻣزودة ﺑﻧظﺎم ﺗﺣﻛم ﺗﻠﻘﺎﺋﻰ ﻋﻧد ﺳﻘوط اﻟﻣﺻدر ‪.(Automatic mains‬‬
‫)‪failure-AMF-‬‬

‫‪٦٩‬‬
‫‪ -‬وﯾوﺿﺢ اﻟﺷﻛل اﻟﻘﺎدم داﺋرة ﺗﺣﻛم ﺑدء ﺣرﻛﺔ ﻣﺎﻛﯾﻧﺔ اﻟدﯾزل ﻟﻣوﻟد اﻟطوارئ ﻋﻧد‬
‫ﺳﻘوط ﺗﯾﺎر اﻟﻣﺻدر ) ‪ (Mains failure control circuit‬ﻛﯾﻔﯾﺔ ﻋﻣل‬
‫اﻟداﺋرة‬

‫‪ -‬ﺗﻛون ﻓﺗﺣﺎت اﻟﺗﻬوﯾﺔ ﻓﻰ ﻋﻛس اﺗﺟﺎﻩ ﻫﺑوب اﻟرﯾﺎح ﺑﺣﯾث ﺗﺳﻣﺢ ﺑﺎﻧدﻓﺎع اﻟﻬواء‬
‫اﻟﺳﺎﺧن إﻟﻰ اﻟﺧﺎرج وﺗﺳﺎﻋد ﺣرﻛﺔ اﻟﻬواء ﻋﻠﻰ ﺳﺣﺑﺔ‪،‬ﻛﻣﺎ ﺗﻛون ﻓﺗﺣﺔ ﺧروج‬
‫اﻟﻌﺎدم ﻓﻰ ﻋﻛس ﻫﺑوب اﻟرﯾﺎح‪.‬‬

‫‪٧٠‬‬
Uninterruptible Power Supply ( ‫ﻣﺻدر ﺗﻐذﯾﺔ ﻗوى ﻋدﯾم اﻻﻧﻘطﺎع‬
UPS)

٧١
‫‪ -‬ﻫو ﻋﺑﺎرة ﻋن وﺣدة ﺗﺗﻛون ﻣن ﻣﻘوم ﺗﯾﺎر ‪ Rectifie‬و ﻣﺟﻣوﻋﺔ ﺑطﺎرﯾﺎت وﻣﻐﯾر‬
‫)‪ (MS‬ﻟﻠﻧﻘل ﻣن‬ ‫ﺗﯾﺎر ﻣن ﻣﺳﺗﻣر إﻟﻰ ﻣﺗردد ﻣن )‪ (Inverter‬وﻣﯾﻛروﺳوﯾﺗس‬
‫اﻟﺑطﺎرﯾﺎت إﻟﻰ اﻟﻣﺻدر أو اﻟﻌﻛس)‪. (MS‬‬

‫‪ -‬ﺗﻐذى اﻷﺣﻣﺎل ﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﻣن اﻟﻣﺻدر ﻣﺑﺎﺷرة ﺑﻌد اﻟﺗﺣوﯾل ﻣن ﻣﺗرددإﻟﻰ‬


‫ﻣﺳﺗﻣر وﻣن ﻣﺳﺗﻣر إﻟﻰ ﻣﺗردد ﺣﯾث ﯾﺗم ﻓﻰ ﻧﻔس اﻟوﻗت ﺷﺣن اﻟﺑطﺎرﯾﺎت ﻣن‬
‫ﺧﻼل اﻟﺗﯾﺎر اﻟﻣﺳﺗﻣر اﻟﻧﺎﺗﺞ ﻣن اﻟﻣوﺣد‪.‬‬
‫‪ -‬ﻋﻧد اﻧﻘطﺎع ﺗﯾﺎر اﻟﻣﺻدر ﺗﻘوم اﻟﺑطﺎرﯾﺎت اﻟﻣﺷﺣوﻧﺔ وﻣن ﺧﻼل )‪(Ms‬‬
‫اﻟﻣﯾﻛروﺳوﯾﺗش‬
‫ﻟﺣظﯾًﺎ ﺑﺈﻣداد ﻣﻐﯾر اﻟﺗﯾﺎر ﻣن اﻟﺑطﺎرﯾﺎت واﻟذى ﯾﻘوم ﺑﺗﺣوﯾل اﻟﺗﯾﺎر اﻟﻣﺳﺗﻣر إﻟﻰ ﺗﯾﺎر‬
‫ﻣﺗردد ﻟﺗﻐذﯾﺔ اﻟﺣﻣل دون اﻧﻘطﺎع ‪.‬وﻋﻧد ﻋودة ﺗﯾﺎر اﻟﻣﺻدر ﺗﺳﺗﻣر اﻟﺗﻐذﯾﺔ وﯾﺗم ﺷﺣن‬
‫اﻟﺑطﺎرﯾﺎت ﻟﺗﻛون ﺟﺎﻫزة ﻋﻧد أى اﻧﻘطﺎع آﺧر ﻟﻠﻣﺻدر‪.‬‬
‫‪ -‬ﯾﻌﺗﺑر اﺳﺗﺧدام أﺟﻬزة )‪ (UPS‬ﻣﺣددًا ﺑوﻗت ﻣﻌﯾن ﯾﻌﺗﻣد ﻋﻠﻰ ﺳﻌﺔ اﻟﺑطﺎرﯾﺎت اﻟﻣرﻛﺑﺔ‬
‫وﺳرﻋﺔ ﺗﻔرﯾﻐﻬﺎ ﻛﻣﺎ ﯾﻌﺗﻣد ﻋﻠﻰ اﻟﺗﻐذﯾﺔ ﻣن ﺗﯾﺎر اﻟﻣدﯾﻧﺔ وﺗﯾﺎر ﻣﺻدر ﻣوﻟد اﻟطوارئ ﻣﻣﺎ‬
‫ﯾﺣﻘق اﺳﺗﻣرارﯾﺔ اﻟﺗﻐذﯾﺔ ﻟﻸﺣﻣﺎل‪.‬‬

‫وﺣدات إﻧﺎرة اﻟطوارئ‬

‫‪٧٢‬‬
‫ﺗﺣﺗوى ﻫذﻩ اﻟوﺣدات ﻋﻠﻰ ﺷﺎﺣن وﺑطﺎرﯾﺎت ﺗﻌﻣل ﻟﻣدد ﻣﺣددة ﺑﻛﺎﻓﺔ أﻧواﻋﻬﺎ وﯾﻣﻛن‬
‫اﺳﺗﺧداﻣﻬﺎ ﻟﻺﻧﺎرة وﺗﺳﻬﯾل ﺣرﻛﺔ اﻷﺷﺧﺎص ﻓﻰ ﺑﻌض اﻷﻣﺎﻛن ﻓﻰ ﻓﺗرات اﻻﻧﺗﻘﺎل ﻣﺎ ﺑﯾن‬
‫ﻣﺻدر اﻟﻣدﯾﻧﺔ وﻣﺻدر ﻣوﻟدات اﻟطوارئ‪.‬‬

‫وﺣدة ﻋدم اﻧﻘطﺎع اﻟﺗﯾﺎر اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ‬


‫))‪(No Break Generator (NB- NBG‬‬
‫وﯾطﻠق ﻋﻠﻰ ﻫذا اﻟﻧظﺎم أﯾﺿًﺎ ﻣوﻟد ﻋدم اﻧﻘطﺎع ﻣﺻدر اﻟﻘوى اﻟدﯾﻧﺎﻣﯾﻛﻰ‪.‬‬
‫)‪(Dynamic diesel UPS System‬‬

‫‪ -‬اﻟظروف اﻟﻌﺎدﯾﺔ‪:‬‬

‫ﯾﻛون اﻟﻘﺎﺑض ﻣﻔﺻو ﻻ واﻟﻣﺣرك ﻣﺗﺻﻼ ﺑﻣﺻدر ﺗﯾﺎر اﻟﻣدﯾﻧﺔ وﯾﻌﻣﻼن ﻫو واﻟﻣوﻟد‬
‫واﻟﺣداﻓﺔ ﻣﻌًﺎ ﻓﯾﻘوم اﻟﻣوﻟد ﺑﺗوﻟﯾد اﻟﺗﯾﺎر اﻟﻼزم ﻟﺗﻐذﯾﺔ أﺣﻣﺎل اﻟطوارئ ﺑﺻﻔﺔ داﺋﻣﺔ‪.‬‬

‫‪ -‬ﻋﻧد اﻧﻘطﺎع اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ‪:‬‬

‫‪٧٣‬‬
‫ﺗظل اﻟﺣداف ة ﻛﻛﺗﻠﺔ ﻋﺎﻟﯾﺔ اﻟوزن )اﻟﻘﺻور اﻟذاﺗﻰ ﻟﻠﺣداﻓﺔ ﻓﻰ ﺣدود‪ 1300‬ﻛﺞ م‪( ٢‬‬
‫ﻓﻰ إدارة اﻟﻣﺣرك واﻟﻣوﻟد وﯾﻘوم اﻟﻣوﻟد ﺑﺗوﻟﯾد اﻟﻘوى اﻟﻼزﻣﺔ ﻷﺣﻣﺎل اﻟطوارئ ﻟﻌدة ﺛوان‬
‫ﯾﺳﻣﺢ ﻓﯾﻬﺎ ﺑﺎﻧﺧﻔﺎض اﻟﺟﻬد واﻟﺗردد) ﺣﺗﻰ‪ (٪ 5‬ﯾﻣﻛن اﺧﺗﯾﺎر اﻟﻣﺎﻛﯾﻧﺔ ﺑﺄن ﯾﻛون ﻫذا‬
‫اﻻﻧﺧﻔﺎض ﻣﺎ ﺑﯾن‪ ٪ 1‬و‪ ( 5‬واﻟذى ﯾﺗﺣدد ﻣﻧﻪ وزن اﻟﺣداﻓﺔ وﻧوﻋﯾﺔ أﻋﻣدة اﻟﻣﺣﺎور‬
‫اﻟﻣﺳﺗﺧدم ة )وﻓﻰ‬
‫ﻧﻔس اﻟوﻗت ﯾﻧﻘﺑض اﻟﻘﺎﺑض اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﻲ وﺗﻘوم اﻟﺣداﻓﺔ ﺑﻣﺎ ﺗﺣﺗوﯾﻪ ﻣن ﻗﺻور ذاﺗﻰ‬
‫ﻋﺎﻟﻰ ﺑﺈدارة ﻣﺎﻛﯾﻧﺔ اﻟدﯾزل ﺗﻣﻬﯾدًا ﻟﺑدء ﺣرﻛﺗﻬﺎ ﻟﺗﻐذﯾﺔ اﻟﻣﺟﻣوﻋﺔ ﻛﻠﻬﺎ ﺑﺎﻟﺣرﻛﺔ)اﻟﺣداﻓﺔ‬
‫واﻟﻣﺣرك واﻟﻣوﻟد( وﻋﻧد ذﻟك ﯾﺳﺗﻣر اﻟﻣوﻟد ﻓﻰ إﻣداد اﻷﺣﻣﺎل ﺑﺎﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ‪.‬‬

‫‪ -‬ﻋﻧد ﻋودة ﻣﺻدر اﻟﻣدﯾﻧﺔ‪:‬‬

‫ﯾﻔﺻل اﻟﻘﺎﺑض اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﻲ وﺑﻌد ﻓﺗرة ﺗﺗوﻗف اﻟﻣﺎﻛﯾﻧﺔ اﻟدﯾزل وﯾﺳﺗﻣر اﻟﻌﻣل ﺑواﺳطﺔ‬
‫ﻣﺻدر اﻟﻣدﯾﻧﺔ ﻋﻠﻰ اﻟﻧﺣو اﻟﺳﺎﺑق‪.‬‬
‫‪ -‬ﯾﻌﻣل ﻣﻊ اﻟﻣﺎﻛﯾﻧﺔ اﻟدﯾزل ﻓﻰ ﻫذا اﻟﻧظﺎم ﺑطﺎرﯾﺎت ﻗوﯾﺔ وﺷﺎﺣن ﺑطﺎرﯾﺎت ﯾﺗم‬
‫ﺗﻐذﯾﺗﻪ ﺳواء ﻣن ﻣﺻدر اﻟﻣدﯾﻧﺔ أو ﻣن ﻣوﻟد اﻟﻣﺎﻛﯾﻧﺔ وﺗﻘوم ﻫذﻩ اﻟﺑطﺎرﯾﺎت ﺑﺗﻐذﯾﺔ‬
‫اﻟﻘﺎﺑض اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﻲ وﻛذا ﺗﻐذﯾﺔ ﺳﺧﺎﻧﺎت اﻟﻣﺎﻛﯾﻧﺔ اﻟدﯾزل اﻟﻣوﺟودة ﻓﻰ دورة‬
‫اﻟزﯾت واﻟﻣﯾﺎﻩ ﻟﺟﻌﻠﻬﺎ داﺋﻣًﺎ ﺑدرﺟﺔ ﻋﺎﻟﯾﺔ ﻟﻼﺳﺗﺟﺎﺑﺔ ﻓﻰ ﺑدء اﻟﺣرﻛﺔ ﻟﻘﺑول اﻷﺣﻣﺎل‬
‫ﺑﻣﺟرد وﺻول ﺳرﻋﺗﻬﺎ إﻟﻰ ﺳرﻋﺔ اﻟﺗزاﻣن‪.‬‬
‫‪ -‬ﺗوﺟد ﻓﻰ اﻷﺳواق وﺣدات ﻟﻣﺻﺎدر اﻟﺗﻐذﯾﺔ ﻋدﯾﻣﺔ اﻻﻧﻘطﺎع اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ )‪(NBDD‬‬
‫ﺑﻘدرات ﺣﺗﻰ ‪2500‬ك‪.‬ف‪.‬أ‪ .‬ﻋﻧد ﺟﻬد ‪ ٣/٥٠/ ٣٨٠‬ﻓوﻟت ‪3/50/11000‬‬
‫ﻓوﻟت )‪ (Synchronous machine‬ﺗﻘوم ﺑﺎﻟﻌﻣل ﺑﻬﺎ آﻟﺔ ﻣﺗزاﻣﻧﺔ واﺣدة ﺗﻌﻣل‬
‫ﻛﻣﺣرك وﻣو ﻟد ﻓﻰ اﻟﻧظﺎم‪ ،‬وﻛﻣﺎ ﻫو ﻣوﺿﺢ ﻓﻰ اﻟﺷﻛل اﻟﻘﺎدم ‪.‬‬

‫‪٧٤‬‬
‫أﺣﻣﺎل اﻟطوارئ ﻓﻰ اﻟﻣﺑﺎﻧﻰ‬

‫‪-‬أﺣﻣﺎل اﻹﻧﺎرة‬
‫ﯾﺟب اﺳﺗﺧدام ﻣﺻﺎدر اﻟﺗﻐذﯾﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﻰ ﺣﺎﻻت اﻟطوارئ ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻰ‪:‬‬

‫‪٧٥‬‬
‫‪ -‬ﺗﺧﺻص أﺟزاء ﻣن أﺣﻣﺎل اﻹﻧﺎرة ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻹدارﯾﺔ واﻟﺗﺟﺎرﯾﺔ واﻟﻔﻧدﻗﯾﺔ‬
‫واﻟﺻﺣﯾﺔ)ﻣﺳﺗﺷﻔﯾﺎت( ﻟﺗﺳﻬﯾل ﺣرﻛﺔ اﻷﺷﺧﺎص ﺑﺎﻟﻣﺑﻧﻰ‪.‬‬
‫‪ -‬ﯾﺟب ﻋﻠﻰ اﻷﻗل إﻧﺎرة اﻟﻣداﺧل واﻟﺳﻼﻟم ﺑﺎﻷدوار وﺳﻼﻟم اﻟﻬروب وﺧﺎﺻﺔ‬
‫ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻟﺳﻛﻧﯾﺔ‪.‬‬
‫‪ -‬ﯾﺟب إﻧﺎرة ﺟزء ﻣن إﻧﺎرة ﻏرف اﻹﻗﺎﻣﺔ ﺑﺎﻟﻔﻧﺎدق واﻟﻣﺳﺗﺷﻔﯾﺎت‪.‬‬
‫‪ -‬ﯾﺟب إﻧﺎرة ﺟزء ﻣن اﻟﻣﻧﺎطق اﻟﻌﺎﻣﺔ ﺑﺎﻟﻣﺑﺎﻧﻰ وأﻣﺎﻛن اﻻﺳﺗﻘﺑﺎل وأﻣﺎﻛن‬
‫اﻻﻧﺗظﺎر وﻛذا دورات اﻟﻣﯾﺎﻩ‪.‬‬
‫‪ -‬إﻧﺎرة أى أﺟزاء ذات أﻫﻣﯾﺔ ﺧﺎﺻﺔ ﻓﻰ اﻟﻣﺑﺎﻧﻰ‪.‬‬
‫‪ -‬ﯾﺧﺻص ﺟزء ﻣن إﻧﺎرة اﻟدور اﻟﺳﻔﻠﻰ )اﻟﺑدروم( وﺧﺻوﺻًﺎ ﻓﻰ اﻟﻣﺑﺎﻧﻰ‬
‫ﻣﺗﻌددة اﻟﺑدروﻣﺎت‪.‬‬
‫‪ -‬ﯾﺟب إﻧﺎرة أﺟزاء ﻣن ﻣﺑﺎﻧﻰ اﻟﺳﺟون وﻣﺎ ﺷﺎﺑﻬﻬﺎ‪.‬‬
‫‪ -‬ﯾﺟب إﻧﺎرة ﻏرف ﻣﺎﻛﯾﻧﺎت اﻟﻣﺻﺎﻋد وﻏرف اﻟﻣﺣوﻻت وﻟوﺣﺎت اﻟﺗوزﯾﻊ‬
‫اﻟرﺋﯾﺳﯾﺔ وﻏرف اﻟﻣوﻟدات اﻻﺣﺗﯾﺎطﯾﺔ‪.‬‬
‫‪ -‬وﻻ ﺑد ﻣن اﺧﺗﯾﺎر أﺟزاء ﻣن طرﻗﺎت ﺣرﻛﺔ اﻷﻓراد ﺑﺎﻷدوار ﻹﻧﺎرﺗﻬﺎ ﻣن‬
‫ﻣﺻدر اﻟطوارئ وﺧﺎﺻﺔ ﻓﻰ اﻟﻔﻧﺎدق و اﻟﻣﺳﺗﺷﻔﯾﺎت‪.‬‬
‫‪ -‬ﯾﺟب اﺧﺗﯾﺎر إﻧﺎرة أﺟزاء ﻣن دور اﻟﻌر ض وﻣداﺧﻠﻬﺎ وﻣﺧﺎرﺟﻬﺎ وﻛذا أﻣﺎﻛن‬
‫ﻟﻌب اﻷطﻔﺎل ﻹﻧﺎرﺗﻬﺎ ﻣن ﻣﺻدر اﻟطوارئ‪.‬‬
‫‪ -‬ﯾﺗم اﺧﺗﯾﺎر أﺟزاء ﻣن اﻹﻧﺎرة اﻟﺧﺎرﺟﯾﺔ ﻟﺗﺄﻣﯾن ﺣرﻛﺔ اﻷﻓراد ﺧﺎرج اﻟﻣﺑﻧﻰ‬
‫إو ﻧﺎرﺗﻬﺎ ﻣن ﻣﺻدر اﻟطوارئ‪.‬‬
‫‪ -‬ﯾﺟب إﻧﺎرة أﻧﻔﺎق اﻟﺳﯾﺎرات واﻟﻣﺷﺎة وﻣﺣطﺎت ﻣﺗرو اﻷﻧﻔﺎق وﻣﺎ ﺷﺎﺑﻬﻬﺎ ﻣن‬
‫ﻣﺻدر اﻟطوارئ‪.‬‬

‫أﺣﻣﺎل اﻟﻣﻌدات‬

‫ﯾﺟب ﺑﺎﻹﺿﺎﻓﺔ إﻟﻰ ﺗﻐذﯾﺔ اﻟﻣﻌدات اﻟﻬﺎﻣﺔ ﻣن ﻣﺻدر اﻟطوارئ أن ﯾﺗم ﺗﻐذﯾﺔ اﻹﻧﺎرة‬
‫اﻟﻣﻧﺎﺳﺑﺔ ﻟﻬﺎ أﯾﺿًﺎ ﻣن ﻣﺻدر اﻟطوارئ ﻛﻰ ﯾﺗﺣﻘق أداء اﻟﻐرض ﻣن ﺗﻐذﯾﺔ اﻟطوارئ وﻣن‬
‫ﺑﯾن ﻫذﻩ اﻟﻣﻌدات‪:‬‬
‫‪ -‬ﻣﺻﺎﻋد اﻟرﻛﺎب ﺑﺎﻟﻣﺑﺎﻧﻰ اﻟﻣﺧﺗﻠﻔﺔ وﻣﺻﺎﻋد اﻟﻣرﺿﻰ ﺑﺎﻟﻣﺳﺗﺷﻔﯾﺎت‪.‬‬
‫‪ -‬اﻟﺛﻼﺟﺎت ﺑﻣطﺎﺑﺦ اﻟﻔﻧﺎدق واﻟﻣﺳﺗﺷﻔﯾﺎت وﻛذا ﺛﻼﺟﺎت ﺣﻔظ اﻟﺟﺛث‪.‬‬

‫‪٧٦‬‬
‫‪ -‬ﻣﺣطﺎت طﻠﻣﺑﺎت رﻓﻊ اﻟﻣﯾﺎﻩ وطﻠﻣﺑﺎت اﻟﺻرف أو اﻟﻧزح وﻛذا طﻠﻣﺑﺎت إطﻔﺎء اﻟﺣرﯾق‪.‬‬
‫‪ -‬ﻣراوح ﺳﺣب اﻟدﺧﺎن ﻣن ﺳﻼﻟم وﻣﻣرات اﻟﻬروب‪.‬‬
‫‪ -‬أﺟزاء ﻣن ﻣﻌدات اﻟﻣطﺎﺑﺦ ﻓﻰ اﻟﻣﺳﺗﺷﻔﯾﺎت واﻟﻔﻧﺎ]دق‪.‬‬
‫‪ -‬ﺑﻌض اﻟﻣﻌد ات ﺑﺎﻟﻣﺻﺎﻧﻊ وﺧﺎﺻﺔ ﻓﻰ ﻣﺻﺎﻧﻊ اﻟﻣﻌﺎﻟﺟﺎت اﻟﻛﯾﻣﺎوﯾﺔ وﻣﺻﺎﻧﻊ‬
‫اﻟﺑﻼﺳﺗﯾك واﻟﺗﻰ ﺗﺗﺄﺛر ﺑﺄﺿرار ﻛﺑﯾرة ﻋﻧد اﻧﻘطﺎع اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ‪.‬‬

‫أﺣﻣﺎل ﻣﺗﺻﻠﺔ ﺑﺣﯾﺎة اﻷﺷﺧﺎص ﺑﺎﻟﻣﺳﺗﺷﻔﯾﺎت‬

‫ﯾﺟب ﺗﻐذﯾﺔ اﻟﻣﻌدات اﻟﻬﺎﻣﺔ اﻟﻣوﺟودة داﺧل اﻷﻣﺎﻛن اﻟﺗﺎﻟﯾﺔ وﻛذﻟك وﺣدات اﻹﻧﺎرة ﺑﻬﺎ وﻛذﻟك‬
‫ﯾﺟب ﺗدﺑﯾر أﺣد ﻣﺻﺎدر ﻋدم اﻧﻘطﺎع اﻟﺗﯾﺎر ﻟﻣﺛل ﻫذﻩ اﻟﻣﻌدات ﻣﺛل )‪.(UPS or NBG‬‬

‫‪-‬ﻏرف اﻟﻌﻣﻠﯾﺎت ﺑﻣﺧﺗﻠف أﻧواﻋﻬﺎ وأﻧظﻣﺔ اﻹﻧﺎرة اﻟﺧﺎﺻﺔ ﺑﻬﺎ‪.‬‬


‫‪-‬ﻏرف اﻟرﻋﺎﯾﺔ اﻟﻣرﻛزة واﻟﻔﺎﺋﻘﺔ واﻟزاﺋدة‪.‬‬
‫‪-‬أﺟﻬزة اﻟﻘﻠب اﻟﺻﻧﺎﻋﻰ وﻗﺳطرة اﻟﻘﻠب واﻟﻐﺳﯾل اﻟﻛﻠوى‪.‬‬
‫‪ -‬اﻷﺟﻬزة اﻟﻣﺗﺻﻠﺔ ﺑﺎﻟﻣرﺿﻰ ﻟﻣراﻗﺑﺔ أداء وظﺎﺋف اﻟﺟﺳم أو أداء اﻟﻌﻼج ﻟﻬﺎ‪.‬‬
‫‪ -‬ﺑﻌض ﻋﯾﺎدات اﻷﺳﻧﺎن واﻟﻌظﺎم وﺑﻌض اﻟﺟراﺟﺎت وﻣﺎ ﺷﺎﺑﻬﻬﺎ‪.‬‬

‫أﻧظﻣﺔ ﺗﻌﻣل ﺑﺎﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ ﻓﻰ ﺟﻣﯾﻊ اﻟظروف وﻻ ﯾﺳﻣﺢ ﺑﺎﻧﻘطﺎﻋﻪ‬


‫ي‬
‫ﺟب ﺗﺄﻣﯾن ﺗﻐذﯾﺔ ﺑﻌض اﻷﻧظﻣﺔ اﻟﻬﺎﻣﺔ ﻟﯾس ﻓﻘط ﺑﺗﻐذﯾﺗﻬﺎ ﻣن ﻣوﻟدات اﻟطوارئ وﻟﻛن ﻣن‬
‫ﻣﺻﺎدر ﻋدم اﻧﻘطﺎع اﻟﺗﯾﺎر ﻣﺛل ال )‪ UPS‬و‪( NBG‬‬

‫‪ -‬أﻧظﻣﺔ وأﺟﻬزة ﺗﺄﻣﯾن اﻟﻣﺑﺎﻧﻰ ﺿد اﻟﺳرﻗﺔ أو اﻻﺧﺗراق وأﺟﻬزة اﻷﻣن ﺑوﺟﻪ ﻋﺎم‬
‫ﻟﻠﻣﺑﻧﻰ‪.‬‬
‫‪ -‬أﻧظﻣﺔ وأﺟﻬزة اﻟﺗﻧﺑﯾﻪ واﻹﻧذار ﺑﺎﻟﻣﺑﺎﻧﻰ‪.‬‬
‫‪ -‬أﻧظﻣﺔ اﻟﺗﻠﯾﻔوﻧﺎت وﺳﻧﺗراﻻﺗﻬﺎ ﺑﺎﻟﻣﺑﺎﻧﻰ‪.‬‬
‫‪ -‬أﻧظﻣﺔ اﻹذاﻋﺔ اﻟداﺧﻠﯾﺔ ﺑﺎﻟﻣﺑﺎﻧﻰ‪.‬‬
‫‪-‬أﻧظﻣﺔ إﻧذار اﻟﺣرﯾق ﺑﺎﻟﻣﺑﺎﻧﻰ‪.‬‬
‫‪ -‬أﻧظﻣﺔ اﻟﻬواﺋﻰ اﻟﻣرﻛزى وﻣﺣطﺎت اﺳﺗﻘﺑﺎل اﻟﻘﻧوات اﻟﻔﺿﺎﺋﯾﺔ ﺑﺎﻟﻣﺑﺎﻧﻰ‪.‬‬

‫‪٧٧‬‬
‫‪ -‬أﻧظﻣﺔ إﻧﺎرة ﻏرف اﻟﻌﻣﻠﯾﺎت واﻻﺳﺗدﻋﺎء اﻟﺻوﺗﻰ واﻟﺿوﺋﻰ ﺑﺎﻟﻣﺳﺗﺷﻔﯾﺎت وﻛذﻟك أﻧظﻣﺔ‬
‫ﺷﺎﺷﺎت اﻟﻣﺗﺎﺑﻌﺔ ﺑﻐرف اﻟﻌﻣﻠﯾﺎت وأﺟﻬزة اﻻﺗﺻﺎل ﺑﻬﺎ واﻷﺟﻬزة اﻟﻣوﺟودة ﺑﻐرف ال ﻋﻧﺎﯾﺔ‬
‫اﻟﻣرﻛزة واﻷﺟﻬزة اﻟﻣﺗﺻﻠﺔ ﺑﺎﻟﻣرﺿﻰ ﻟﻣراﻗﺑﺔ وظﺎﺋف اﻟﺟﺳم‪.‬‬
‫‪ -‬أﻧظﻣﺔ وأﺟﻬزة اﻟﻛوﻣﺑﯾوﺗر وﺧﺻوﺻًﺎ ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻟﻌﺎﻣﺔ )إدارﯾﺔ – ﺗﺟﺎرﯾﺔ‬
‫–ﺑﻧوك – ﻣﺳﺗﺷﻔﯾﺎت – ﻓﻧﺎدق – واﻟﻣﺻﺎﻧﻊ اﻟﺗﻰ ﺗﻌﺗﻣد ﻋﻠﻰ اﻟﻛوﻣﺑﯾوﺗر ﻓﻰ إدارﺗﻬﺎ‬
‫وأﻧظﻣﺔ اﻟﺗﺣﻛم ﻓﻰ إدارة اﻟﻣﺑﻧﻰ )‪Power management system (PMS‬‬
‫‪ -‬ﺗﻐذﯾﺔ إﻧﺎرة اﻟﻣراﻗﺑﺔ وأﺑراج اﻟﻣراﻗﺑﺔ ﺑﺎﻟﻣطﺎرات‪.‬‬
‫‪ -‬ﺗﻐذﯾﺔ إﻧﺎرة ﻣﻣرات وأﺟﻬزة وأﻧظﻣﺔ اﻟﻬﺑوط وأﻧظﻣﺔ ﺷﺎﺷﺎت اﻟﻣراﻗﺑﺔ وأﺑراﺟﻬﺎ ﺑﺎﻟﻣطﺎرات‪.‬‬
‫‪ -‬ﺗﺷﻐﯾل ﻣراﻛز اﻟﻘﯾﺎدة وأﺟﻬزﺗﻬﺎ وﺷﺎﺷﺎﺗﻬﺎ وأﺟﻬزة اﺗﺻﺎﻟﻬﺎ اﻟﻣﺧﺗﻠﻔﺔ‪.‬‬

‫‪٧٨‬‬
‫اﻟﻠوﺣﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ واﻟﻘواطﻊ اﻟﻛﻬرﺑﺎﺋﯾﺔ‬

‫‪ETERNAL ENGINEERS GROUP‬‬


‫‪01007200959-01114911166‬‬

‫‪٧٩‬‬
‫ﻣواﺻﻔﺎت اﻟﻘواطﻊ اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻣطﻠوﺑﺔ‪:‬‬

‫ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﺣرارﯾﺔ وﻣﻐﻧﺎطﯾﺳﯾﺔ ﻋﯾﺎرﯾﺔ ﺣﺳب اﻟﻌﯾﺎرات اﻟﻣطﻠوﺑﺔ ﻓﻲ‬
‫اﻟﻣﺧططﺎت أو اﻟﺟداول‪ .‬وﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ذو ﺟودة ﻋﺎﻟﯾﺔ وﺑﺄﻧواع ﻏرﺑﯾﺔ‬
‫ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن اﻷﻧظﻣﺔ اﻟﻌﺎﻟﻣﯾﺔ‪.IEC 947 , VDE 0660 :‬‬

‫ﻣواﺻﻔﺎت اﻟﻘواطﻊ اﻟﻬواﺋﯾﺔ‪:‬‬

‫‪ .١‬ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﻣن ﻧوع ‪ ACB‬اﻟﻬواﺋﯾﺔ ﻣﺻﻧوﻋﺔ وﻣﺧﺗﺑرة ﻣن اﻷﻧظﻣﺔ‬


‫اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻌﺎﻟﻣﯾﺔ‪:‬‬
‫‪.IEC/EN60 947, VDE0660‬‬
‫‪ .٢‬ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﻋﯾﺎرﯾﺔ ﺑﺎﻟﻣﺟﺎﻟﯾن اﻟﺣراري واﻟﻣﻐﻧﺎطﯾﺳﻲ ﻛل ﻋﻠﻰ ﺣدى‪.‬‬
‫‪ .٣‬اﻟﻘواطﻊ اﻟﻬواﺋﯾﺔ ‪ ACB‬ﯾﺟب أن ﯾﻛون اﻟﻌﯾﺎر اﻟﺣراري ﻣن ‪0,4 – 1 x In‬‬
‫واﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن ‪1.5–12 x In‬‬
‫‪ .٤‬ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﻋﯾﺎرﯾﺔ ﺑﺎﻟﻣﺟﺎﻟﯾن اﻟﺣراري واﻟﻣﻐﻧﺎطﯾﺳﻲ ﻛل ﻋﻠﻰ ﺣدى‪.‬‬
‫‪ .٥‬ﺗﺣﻣل درﺟﺔ اﻟﺣرارة ‪ ٥٥+ ٢٥ - :‬درﺟﺔ ﻣﺋوﯾﺔ ﻓﻲ ﺣﺎﻟﺔ وﺳط ﻣﻐﻠق‪.‬‬
‫‪ .٦‬درﺟﺔ اﻟﺗﻠوث ﻟﻠﻘواطﻊ ﯾﺟـب أن ﺗﻛـون ﻣـن اﻟدرﺟـﺔ اﻟﺛﺎﻟﺛـﺔ )‪ (III/3‬وﺗﺳـﺗﺧدم ﻟﻸﻏـراض‬
‫اﻟﺻﻧﺎﻋﯾﺔ‪.‬‬
‫‪ .٧‬ﯾﺟب أن ﯾﻛون اﻟﻌﻣر اﻟﻣﯾﻛﺎﻧﯾﻛﻲ ﻟﻠﻘواطﻊ طوﯾﻼً ‪ ١٠٠٠٠‬ﻋﻣﻠﯾﺔ‪.‬‬
‫‪ .٨‬ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ ‪ ١٠٠٠‬ﻓوﻟط‪.‬‬
‫‪ .٩‬ﺗوﺗر اﻟﻌﻣل‪ ٦٩٠ – ٤٠٠ :‬ﻓوﻟت‪.‬‬
‫‪ .١٠‬ﺷدة اﻟﻘطﻊ ﻟﻠﻘواطﻊ ﯾﺟب أن ﺗﻛون ﺑﺷدة ﻗطﻊ ‪.......‬ﻛﯾﻠو أﻣﺑﯾر ‪.ICU = ICS‬‬
‫‪ .١١‬ﯾﺟب أن ﺗﻛـون اﻟﻘواطـﻊ ﺧﺎﺿـﻌﺔ ﻟﻼﺧﺗﺑـﺎرات اﻟﻣﻧﺎﺧﯾـﺔ ﺣﺳـب ‪IEC/EN 60068-2-‬‬
‫‪30‬‬
‫‪ .١٢‬ﯾﻣﻛن ﺗﻐذﯾﺔ اﻟﻘواطﻊ‪ :‬ﺑﺎﺗﺟﺎﻫﯾن ﻣن اﻷﻋﻠﻰ أو اﻷﺳﻔل‪.‬‬
‫‪ .١٣‬إﻣﻛﺎﻧﯾﺔ ﺗرﻛﯾب اﻛﺳﺳوارات ﻋﻠﻰ اﻟﻘواطﻊ ﺣﺳب ﺣﺎﺟـﺔ اﻟﻌﻣـل ﻣﺛـل‪ :‬ﻣﺣرﻛـﺎت‪ ،‬ﺗﻣﺎﺳـﺎت‬
‫ﻣﺳﺎﻋدة‪ ،‬وﺷﯾﻌﺔ ﻫﺑوط ﺟﻬد أو وﺷﯾﻌﺔ ﻓﺻل ﻋن ﺑﻌد‪.‬‬

‫‪٨٠‬‬
‫اﻟﻘواطﻊ اﻟﻣﻘوﻟﺑﺔ ‪ MCCB‬ﻓﻲ اﻟﻠوﺣﺎت اﻟرﺋﯾﺳﯾﺔ‬

‫‪ .١‬ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﻣن ﻧوع ‪ MCCB‬ﻣﺻﻧوﻋﺔ وﻣﺧﺗﺑرة ﻣن اﻷﻧظﻣﺔ‬


‫اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻌﺎﻟﻣﯾﺔ‪:‬‬
‫‪.IEC/EN60 947, VDE0660‬‬
‫‪ .٢‬ﯾﺟــــب أن ﺗﻛــــون ﺟﻣﯾــــﻊ اﻟﻘواطــــﻊ ﺣرارﯾــــﺔ وﻣﻐﻧﺎطﯾﺳــــﯾﺔ ﻋﯾﺎرﯾــــﺔ ﺑﺎﻟﻣﺟــــﺎﻟﯾن اﻟﺣــــراري‬
‫واﻟﻣﻐﻧﺎطﯾﺳﻲ ﻛل ﻋﻠﻰ ﺣدى ﺣﺳب ﻣﺎ ﻫو ﻣطﻠوب ﻓﻲ اﻟﻣﺧططﺎت‪.‬‬
‫‪ .٣‬اﻟﻘواطــﻊ اﻟﻣﻘوﻟﺑــﺔ ‪ MCCB‬ﻟﻐﺎﯾــﺔ ‪ ٢٥٠‬أﻣﺑﯾــر ﯾﺟــب أن ﯾﻛــون اﻟﻌﯾــﺎر اﻟﺣـراري ﻣــن‬
‫‪0.8 -1x In‬‬
‫واﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن‬
‫‪6 – 10 x In‬‬
‫اﻟﻘواطﻊ اﻟﻣﻘوﻟﺑﺔ ‪ MCCB‬ﻣن ‪ ٤٠٠‬أﻣﺑﯾر ﻓﻣﺎ ﻓوق ﯾﺟب أن ﯾﻛون اﻟرﯾﻠﯾﻪ اﻟﻛﺗروﻧﻲ‬
‫‪0.5‬‬ ‫واﻟﻌﯾﺎر اﻟﺣراري ﻣن‬
‫‪- 1 x In‬‬
‫واﻟﻌﯾﺎر‬
‫اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن ‪2 – 10 x I n‬‬
‫‪ .٤‬اﺧﺗﺑﺎر اﻟﺗوﺗر اﻟﻧﺑﺿﻲ ﻟﻠﻘواطﻊ ‪ ٨٠٠٠ :MCCB‬ﻓوﻟط )ﻣﺎ ﻋدا اﻟﻘواطﻊ اﻟﺻﻐﯾرة‬
‫ﻟﻐﺎﯾﺔ ‪ ١٦٠‬أﻣﺑﯾر ﯾُﻘﺑل ‪ ٦٠٠٠‬ﻓوﻟت(‪.‬‬
‫‪ .٥‬ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ ﻟﻠﻘواطﻊ ‪ ١٠٠٠‬ﻓوﻟط و ﯾﻣﻛن ﻟﻠﻘواطﻊ ﻣﺎ دون ‪ ٢٥٠‬أﻣﺑﯾر أن ﺗﻛون‬
‫اﻟﻌﺎزﻟﯾﺔ ‪ ٨٠٠‬ﻓوﻟط‬
‫‪ .٦‬ﺗﺣﻣل درﺟﺔ اﻟﺣرارة ‪ ٥٥+ ٢٥- :‬درﺟﺔ ﻣﺋوﯾﺔ ﻓﻲ ﺣﺎﻟﺔ وﺳط ﻣﻐﻠق‪.‬‬
‫‪ .٧‬درﺟﺔ اﻟﺗﻠوث ﻟﻠﻘواطﻊ ﯾﺟب أن ﺗﻛـون ﻣـن اﻟدرﺟـﺔ اﻟﺛﺎﻟﺛـﺔ )‪ (III/3‬وﺗﺳـﺗﺧدم ﻟﻸﻏـراض‬
‫اﻟﺻﻧﺎﻋﯾﺔ‪.‬‬
‫‪ .٨‬ﯾﺟب أن ﯾﻛون اﻟﻌﻣر اﻟﻣﯾﻛﺎﻧﯾﻛﻲ واﻟﻛﻬرﺑﺎﺋﻲ ﻟﻠﻘواطﻊ طوﯾﻼً‪.‬‬
‫‪ .٩‬ﺷدة اﻟﻘطﻊ ﻟﻠﻘواطﻊ‪ :‬ﯾﺟب أن ﺗﻛون ﺑﺷدة ﻗطﻊ ‪........‬ﻛﯾﻠو أﻣﺑﯾر‬
‫‪ ICU = ICS .١٠‬ﻟﻠﻘواطﻊ ‪ ٦٣٠‬أﻣﺑﯾر و ﻣﺎ دون ‪ ICU = 75% /‬ﻟﻠﻘواطﻊ ‪-٨٠٠‬‬
‫‪ ١٦٠٠‬أﻣﺑﯾر‬
‫‪ .١١‬ﺗﻛون اﻟﻘواطﻊ ﺧﺎﺿﻌﺔ ﻟﻼﺧﺗﺑﺎرات اﻟﻣﻧﺎﺧﯾﺔ ﺣﺳب ‪IEC/EN 60068-2-30‬‬
‫‪ .١٢‬ﯾﻣﻛن ﺗﻐذﯾﺔ اﻟﻘواطﻊ‪ :‬ﺑﺎﺗﺟﺎﻫﯾن ﻣن اﻷﻋﻠﻰ أو اﻷﺳﻔل‪.‬‬

‫‪٨١‬‬
‫‪ .١٣‬ﺟﻣﯾﻊ اﻟﻘواطﻊ اﻟﺗﻲ ﻧوع اﻟﺣﻣﺎﯾﺔ ﻓﯾﻬﺎ إﻟﻛﺗروﻧﻲ ﯾﺟب أن ﺗﻛـون ﻣـزودة ﺑﻣﺄﺧـذ ﻹﻣﻛﺎﻧﯾـﺔ‬
‫رﺑطﻬﺎ ﻣﻊ اﻟﺣﺎﺳوب‪.‬‬
‫‪ .١٤‬إﻣﻛﺎﻧﯾﺔ ﺗرﻛﯾب اﻛﺳﺳوارات ﻋﻠﻰ اﻟﻘواطـﻊ ﺣﺳـب ﺣﺎﺟـﺔ اﻟﻌﻣـل ﻣﺛـل‪ :‬ﻣﺣرﻛـﺎت‪ ،‬ﺗﻣﺎﺳـﺎت‬
‫ﻣﺳﺎﻋدة‪ ،‬وﺷﯾﻌﺔ ﻫﺑوط ﺟﻬد أو وﺷﯾﻌﺔ ﻓﺻل ﻋن ﺑﻌد‪.‬‬

‫‪٨٢‬‬
‫ﻣواﺻﻔﺎت اﻟﻘواطﻊ اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﻲ اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ‬

‫‪ .١‬ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﺣرارﯾﺔ وﻣﻐﻧﺎطﯾﺳﯾﺔ ﺣﺳب اﻟﻌﯾﺎرات اﻟﻣدوﻧﺔ ﻋﻠﻰ‬
‫اﻟﻣﺧططﺎت‪.‬‬
‫ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ذو ﺟودة ﻋﺎﻟﯾﺔ وﺑﺄﻧواع ﻏرﺑﯾﺔ ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن‬ ‫‪.٢‬‬
‫اﻷﻧظﻣﺔ اﻟﻌﺎﻟﻣﯾﺔ ‪. IEC 947, VDE 0660‬‬
‫‪ .٣‬ﯾﺟب أن ﺗﻛون اﻟﻘواطﻊ ﺑﻌﯾﺎر ‪ ٨٠‬أﻣﺑﯾر ﻓﻣﺎ ﻓوق ﻗواطﻊ ﺣرارﯾﺔ ﻣﻐﻧﺎطﯾﺳﯾﺔ ﻋﯾﺎرﯾﺔ‬
‫ﻣن ﻧوع ‪) MCCB‬وﻟﻛن ﺗﻘﺑل اﻟﻘواطﻊ اﻟﻐﯾر اﻟﻌﯾﺎرﯾﺔ ‪ MCB‬ﻟﻐﺎﯾﺔ ‪ ١٢٥‬أﻣﺑﯾر ﻓﻲ‬
‫ﺣﺎل ﻛﺎﻧت اﻟﻠوﺣﺎت ﺗﺳﺗﺧدم ﻟﺣﻣﺎﯾﺔ دارات اﻹﻧﺎرة(‪.‬‬
‫ﺗﻛون اﻟﻘواطﻊ اﻟﻣﻐذﯾﺔ ﻟدارات اﻹﻧﺎرة واﻟﻣﺂﺧذ ﻣﺎ ﺑﯾن اﻟﻌﯾﺎرات ‪ ٦٣ – ٦‬أﻣﺑﯾر ﻣن ﻧوع‬ ‫‪.٤‬‬
‫‪MCB‬‬
‫‪ Miniature circuit breaker‬وﺑﺄﻗطﺎب أﺣﺎدي‪ ،‬ﺛﻧﺎﺋﻲ‪ ،‬ﺛﻼﺛﻲ ﺣﺳب ﻣﺎ ﻫو‬
‫ﻣطﻠوب ﻓﻲ اﻟﻣﺧططﺎت‪.‬‬
‫ﺗﻛون اﻟﻘواطﻊ اﻟﻣﻐذﯾﺔ ﻟﻠﻣﺣرﻛﺎت )ﺛﻼﺛﯾﺔ اﻷﻗطﺎب( ﻣﺎ ﺑﯾن )‪ (٢٠٠-١‬أﻣﺑﯾر ﻣن‬ ‫‪.٥‬‬
‫ﻧوع ‪ Motor protective circuit breaker‬ﺗﺳﺗﺧدم ﺑﺷﻛل ﺧﺎص ﻟﺣﻣﺎﯾﺔ‬
‫اﻟﻣﺣرﻛﺎت‪.‬‬

‫ﻣواﺻﻔﺎت اﻟﻘواطﻊ ‪ MCCB‬ﻓﻲ اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ‪:‬‬

‫‪ -‬ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻘواطﻊ ﺣرارﯾﺔ ﻣﻐﻧﺎطﯾﺳﯾﺔ ﻣﺻﻧّﻌﺔ وﻣﻘﺑوﻟﺔ ﻣن ﻗﺑـل اﻷﻧظﻣـﺔ اﻟﻌﺎﻟﻣﯾـﺔ‬
‫‪.IEC947…, VDE 0660‬‬
‫ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﻋﯾﺎرﯾﺔ ﺑﺎﻟﻣﺟﺎﻟﯾن اﻟﺣراري واﻟﻣﻐﻧﺎطﯾﺳﻲ ﻛل ﻋﻠﻰ ﺣدى‪.‬‬ ‫‪-‬‬
‫اﻟﻘواطﻊ ﻟﻐﺎﯾﺔ ‪ ٢٥٠‬أﻣﺑﯾر ﯾﺟب أن ﯾﻛون اﻟﻌﯾﺎر اﻟﺣراري ﻣن ‪0.8 – 1 x In‬‬
‫واﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن ‪6 – 10 x In‬‬
‫‪0.5 – 1 x In‬‬ ‫اﻟﻘواطﻊ ﻣن ‪ ٤٠٠‬أﻣﺑﯾر ﻓﻣﺎ ﻓوق ﯾﺟب أن ﯾﻛون اﻟﻌﯾﺎر اﻟﺣراري ﻣن‬
‫واﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن ‪2 – 10 x In‬‬
‫‪ -‬اﺧﺗﺑﺎر اﻟﺗوﺗر اﻟﻧﺑﺿﻲ ﻟﻠﻘواطﻊ ‪ ٦٠٠٠‬ﻓوﻟط أو ‪ ٨٠٠٠‬ﻓوﻟط‬
‫درﺟﺔ اﻟﺣرارة‪ ٤٠+ ، ٢٥- :‬درﺟﺔ ﻣﺋوﯾﺔ ﻓﻲ ﺣﺎﻟﺔ وﺳط ﻣﻐﻠق‪.‬‬ ‫‪-‬‬

‫‪٨٣‬‬
‫‪ -‬ﺷدة اﻟﻘطﻊ ﻟﻠﻘواطﻊ‪ ........ :‬ﻛﯾﻠو أﻣﺑﯾر ‪.ICU = ICS‬‬
‫‪ -‬اﻣﺎ ﻓﻲ ﺣﺎل ﻛﺎﻧت اﻟﻘواطﻊ اﻟﻣطﻠوﺑـﺔ ﻓـﻲ اﻟﻣﺧططـﺎت ﻣـن ﻧـوع ‪ MCCB‬وﺑﺷـدة ﻗطـﻊ ‪١٨‬‬
‫ﻛﯾﻠـــو أﻣﺑﯾـــر وﺗﺳـــﺗﺧدم ﻟﺣﻣﺎﯾـــﺔ اﻟﻛـــﺑﻼت ﯾﻣﻛـــن أن ﺗﻛـــون اﻟرﯾﻠﯾـــﻪ اﻟﺣـــراري ﻋﯾـــﺎري ﻟﻛـــن‬
‫اﻟﻣﻐﻧﺎطﯾﺳﻲ ﺛﺎﺑت‪.‬‬
‫‪ -‬درﺟﺔ اﻟﺗﻠوث ﻟﻠﻘواطﻊ ﯾﺟب أن ﺗﻛون ﻣن اﻟدرﺟﺔ اﻟﺛﺎﻟﺛﺔ وﺗﺳﺗﺧدم ﻟﻸﻏراض اﻟﺻﻧﺎﻋﯾﺔ‪.‬‬
‫‪ -‬ﺗوﺗر اﻟﻌﻣل‪ ٦٩٠ :‬ﻓوﻟط‪ ٥٠ ،‬ﻫرﺗز‪.‬‬
‫ﯾﺟب أن ﺗﻛون اﻟﻘواطﻊ ﺧﺎﺿﻌﺔ ﻟﻠﺗﺟﺎرب اﻟﻣﻧﺎﺧﯾﺔ ‪IEC60068‬‬ ‫‪-‬‬
‫‪ -‬ﺗﻐذﯾﺔ اﻟﻘواطﻊ‪ :‬ﻣن اﻷﻋﻠﻰ أو اﻷﺳﻔل‪.‬‬
‫ﺗﻛون اﻟﻘواطـﻊ ﻗﺎﺑﻠـﺔ ﻟﻠﺗرﻛﯾـب ﻋﻠﯾﻬـﺎ اﻹﻛﺳﺳـوارات اﻟﺿـرورﯾﺔ ﻣـن ﺗﻣﺎﺳـﺎت ﻣﺳـﺎﻋدة‪ ،‬ﻗﻔـل‬ ‫‪-‬‬
‫ﻣﯾﻛﺎﻧﯾﻛﻲ‪ ،‬وﺷﯾﻌﺔ ﻫﺑوط ﺟﻬد اﻟﺦ …‪..‬‬

‫ﻣواﺻﻔﺎت اﻟﻘواطﻊ ‪:Miniature circuit breaker MCB‬‬


‫‪ -‬ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻘواطﻊ ﺣرارﯾﺔ ﻣﻐﻧﺎطﯾﺳﯾﺔ ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن ﻗﺑل اﻷﻧظﻣﺔ اﻟﻌﺎﻟﻣﯾﺔ‬
‫‪.IEC/EN 60898, VDE 0641‬‬
‫‪ -‬درﺟﺔ اﻟﺣرارة‪ ٤٠ + ،٥- :‬درﺟﺔ ﻣﺋوﯾﺔ‪.‬‬
‫‪ -‬ﺗﻛون ﻫذﻩ اﻟﻘواطﻊ ﺑﺗﺟﺎوب ﻣﻐﻧﺎطﯾﺳﻲ ‪ B‬او ‪ C‬وذﻟك ﺣﺳب ﻣﺎ ﻫو ﻣطﻠوب‪.‬‬
‫‪ -‬اﻟﻌﻣر اﻟﻣﯾﻛﺎﻧﯾﻛﻲ ﻟﻠﻘواطﻊ‪ ٢٠٠٠٠ :‬ﻋﻣﻠﯾﺔ‪.‬‬
‫‪ -‬اﺧﺗﺑﺎر اﻟﺗوﺗر اﻟﻧﺑﺿﻲ‪ ٤٠٠٠ :‬ﻓوﻟط‪.‬‬
‫‪ -‬ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ‪ ٤٠٠ :‬ﻓوﻟط‪.‬‬
‫‪ -‬درﺟﺔ اﻟﺗﻠوث‪ :‬ﻣن اﻟدرﺟﺔ اﻟﺛﺎﻟﺛﺔ وﺗﺳﺗﺧدم ﻷﻏراض ﺻﻧﺎﻋﯾﺔ‪.‬‬
‫‪ -‬ﺗوﺗر اﻟﻌﻣل‪ ٤٠٠/٢٣٠ :‬ﻓوﻟط‪.‬‬
‫‪ -‬ﺗﯾﺎر اﻟﻘﺻر‪ ١٠ :‬ﻛﯾﻠو أﻣﺑﯾر ‪ 10KA‬وﻓق ﻧظﺎم ‪. IEC/EN 60898‬‬
‫‪ -‬ﺗﻐذﯾﺔ اﻟﻘواطﻊ‪ :‬ﻣن اﻷﻋﻠﻰ أو اﻷﺳﻔل‪.‬‬
‫‪ -‬ﺗﺗم ﺗﻐذﯾﺔ اﻟﻘواطﻊ ﺿن اﻟﻠوﺣﺎت ﻋﺑـر ﺑـﺎرات ﺷـك )ﻣﺳـﺑق اﻟﺻـﻧﻊ( ﺧﺎﺻـﺔ ﻟﺗﻐذﯾـﺔ اﻟﻘواطـﻊ‬
‫‪.MCB‬‬

‫ﻣواﺻﻔﺎت ﻗواطﻊ اﻟﻣﺣرك ‪: Motor protective circuit breaker‬‬


‫‪ -‬ﯾﺟــب أن ﺗﻛــون ﻫــذﻩ اﻟﻘواطــﻊ ﺣرارﯾــﺔ وﻣﻐﻧﺎطﯾﺳــﯾﺔ ﺧﺎﺻــﺔ ﻟﺣﻣﺎﯾــﺔ اﻟﻣﺣرﻛــﺎت‪ ،‬ﻣﺻــﻧوﻋﺔ‬
‫وﻣﻘﺑوﻟﺔ ﻣن ﻗﺑل اﻷﻧظﻣﺔ اﻟﻌﺎﻟﻣﯾﺔ ‪IEC/EN 60947, VDE 0660‬‬
‫‪ -‬ﯾﺟب أن ﺗﻛون اﻟﻘواطﻊ ﺧﺎﺿﻌﺔ ﻟﻠﺗﺟﺎرب اﻟﻣﻧﺎﺧﯾﺔ ‪IEC 60068‬‬
‫‪ -‬درﺟﺔ اﻟﺣرارة‪ ٤٠ + ، ٢٥ - :‬درﺟﺔ ﻣﺋوﯾﺔ ﻓﻲ ﺣﺎل وﺳط ﻣﻐﻠق‪.‬‬

‫‪٨٤‬‬
‫اﺧﺗﺑﺎر اﻟﺗوﺗر اﻟﻧﺑﺿﻲ‪ ٦٠٠٠ :‬ﻓوﻟط‪.‬‬ ‫‪-‬‬
‫درﺟﺔ اﻟﺗﻠوث‪ :‬ﻣن اﻟدرﺟﺔ اﻟﺛﺎﻟﺛﺔ وﺗﺳﺗﺧدم ﻷﻏراض ﺻﻧﺎﻋﯾﺔ‪.‬‬ ‫‪-‬‬
‫ﺗوﺗر اﻟﻌﻣل‪ ٦٩٠ :‬ﻓوﻟط‪ ٥٠ ،‬ﻫرﺗز‪.‬‬ ‫‪-‬‬
‫اﻟﻌﯾﺎر اﻟﺣراري‪ :‬ﯾﻣﻛن ﺗﻌﯾﯾرﻫﺎ ﻣﺎ ﺑﯾن ‪0.6 – 1 x Iu‬‬ ‫‪-‬‬
‫اﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ‪ :‬ﺛﺎﺑت ‪ ١٤‬ﻣرة ‪ x Iu 14‬ﺑﺣﯾث ﺗﺗﺣﻣل إﻗﻼﻋﺎت اﻟﻣﺣرﻛﺎت‪.‬‬ ‫‪-‬‬
‫اﻟﻘواطــﻊ ﯾﺟــب أن ﺗﻛــون ﻟــﻪ ﻣﯾــزة ‪) Phase-failure sensitivity‬ﺣﺳﺎﺳــﯾﺔ اﻧﻘطــﺎع‬ ‫‪-‬‬
‫اﻟﻔﺎز( وﻓق ﻧظﺎم ‪IEC/EN 60947-4-1‬‬
‫ﻣواﺻﻔﺎت اﻟﻠوﺣﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ‬

‫اﻟﻐﺎﯾﺔ ﻣن اﻟﻣﺷروع‪:‬‬

‫ﺗﻘدﯾم وﺗﻧﻔﯾذ اﻟﻠوﺣﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟرﺋﯾﺳﯾﺔ واﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ ﺑﺣﯾث ﺗﻛون ﺟﺎﻫزة ﻟﻠﺗرﻛﯾب واﻟﺗﺷﻐﯾل‬
‫ﺣﺳب اﻟﻣواﺻﻔﺎت واﻟﺷروط اﻟﻔﻧﯾﺔ اﻟﻣطﻠوﺑﺔ‪.‬‬

‫ﻟوﺣﺎت اﻟﺗوزﯾﻊ اﻟرﺋﯾﺳﯾﺔ‪:‬‬

‫ﺳــﺗﻛون ﻫــذﻩ اﻟﻠوﺣــﺎت ﻣﺟﻬــزة ﺑﺟﻣﯾــﻊ اﻟﻘواطــﻊ اﻟﻛﻬرﺑﺎﺋﯾــﺔ اﻟﻣطﻠوﺑــﺔ ﻓــﻲ اﻟﻣﺧططــﺎت واﻟﺑــﺎرات‬
‫اﻟﻧﺣﺎﺳﯾﺔ وأﺟﻬزة اﻟﻘﯾﺎس ﺟﺎﻫزة ﻟﻠﺗرﻛﯾب واﻟﺗﺷﻐﯾل‪.‬‬

‫اﻟﻬﯾﻛل اﻟﺻﺎج ﻟﻠوﺣﺎت‪:‬‬

‫اﻟﺧﻼﯾــﺎ ﯾﺟــب أن ﺗﻛــون ﻣــن اﻟﺻــﻧﺎﻋﺔ اﻟﻣﺣﻠﯾــﺔ وﻣــن اﻟﻧــوع اﻟﺗــﻲ ﺗﺳــﺗﺧدم ﻟﺗوزﯾــﻊ اﻟطﺎﻗــﺔ‬
‫اﻟﻛﻬرﺑﺎﺋﯾﺔ‬
‫‪ Power distribution board‬أي ﻣﺻﻧوﻋﺔ وﻓق اﻟﻧظﺎم اﻟﻛﻬرﺑﺎﺋﻲ ‪.IEC439-1‬‬

‫ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻠوﺣﺎت ﻋﻠﻰ ﺷﻛل ﺧﻠﯾـﺔ ﻣﺳـﺗﻘﻠﺔ أو ﺧﻼﯾـﺎ ﻛﻬرﺑﺎﺋﯾـﺔ ﻗﺎﺑﻠـﺔ ﻟﻠﺗﺟﻣﯾـﻊ ﻣـﻊ‬
‫ﺑﻌﺿﻬﺎ اﻟﺑﻌض وﯾﻛون ﻋدد اﻟﺧﻼﯾـﺎ ﺣﺳـب اﻟﻘواطـﻊ اﻟﺗـﻲ ﺳـﺗرﻛب ﺿـﻣﻧﻬﺎ ﻣـﻊ ﻣراﻋـﺎة ﻋﻣﻠﯾـﺔ‬
‫اﻟﺗوﺳﯾﻊ إو ﺿﺎﻓﺔ ﺧﻼﯾﺎ ﺟدﯾدة ﻣﺳﺗﻘﺑﻼً‪.‬‬

‫‪٨٥‬‬
‫‪ ‬اﻟﻘواطﻊ ﺑﺎﺳﺗطﺎﻋﺔ ‪ ٨٠٠‬أﻣﺑﯾر وﻣﺎ ﻓوق ﯾﺟـب أن ﺗُرﻛـب ﺿـﻣن ﺧﻠﯾـﺔ ﻣﺳـﺗﻘﻠﺔ‪ .‬أﻣـﺎ‬
‫إذا ﻛﺎن اﻟﻘﺎطﻊ اﻟرﺋﯾﺳـﻲ ﻟﻠوﺣـﺔ ‪ ٦٣٠‬أﻣﺑﯾـر وﻣـﺎ دون ﯾﻣﻛـن أن ﯾُرﻛـب ﻣـﻊ اﻟﻘواطـﻊ‬
‫اﻟﻔرﻋﯾﺔ ﺿﻣن ﺧﻠﯾﺔ واﺣدة‪.‬‬
‫‪ ‬ﯾﺟب أن ﺗﺻﻧﻊ اﻟﺧﻼﯾﺎ ﻣن أﻟواح اﻟﺻـﺎج اﻟﻔوﻻذﯾـﺔ ﺑﺳـﻣﺎﻛﺔ ‪ ٢‬ﻣﻠـم وﻫـﻲ ﻋﺑـﺎرة ﻋـن‬
‫ﻫﯾﻛـل ﻣــن اﻟﺻــﺎج ﺑﺳــﻣﺎﻛﺔ ‪ ٢‬ﻣﻠــم وﻣﻠﺣوﻣــﺔ ﻣـﻊ ﺑﻌﺿــﻬﺎ ﺑﺷــﻛل ﻣﺗــﯾن ﺑﺣﯾــث ﺗﺷــﻛل‬
‫ﻫﯾﻛــل اﻟﻠوﺣــﺔ‪ ،‬وﯾﻛــون اﻟﻐطــﺎء اﻟﺧﻠﻔــﻲ ﻗطﻌــﺔ واﺣــدة وﻣــزودة ﺑﺄﻏطﯾــﺔ ﺟﺎﻧﺑﯾــﺔ ﻋﻠــﻰ‬
‫طرﻓﻲ ﻧﻬﺎﯾﺔ اﻟﻠوﺣﺔ ﺑﺣﯾث ﯾﻣﻛن ﻓﻛﻬﺎ ﺣﺳب اﻟﺣﺎﺟﺔ‪.‬‬
‫‪ ‬ﺗُرﻛب اﻷﺑواب اﻷﻣﺎﻣﯾـﺔ ﻋﻠـﻰ اﻟﻬﯾﻛـل ﺑﻣﻔﺻّـﻼت ﺧﺎﺻـﺔ وﺗﻔـﺗﺢ اﻷﺑـواب ﺑزاوﯾـﺔ ‪١٢٠‬‬
‫درﺟﺔ ﻟﺳﻬوﻟﺔ اﻟﻌﻣـل ﺿـﻣﻧﻬﺎ‪ .‬وﺗﻛـون ﻫـذﻩ اﻷﺑـواب ﻣـزودة ﺑﺟواﻧـﺎت ﻣطﺎطﯾـﺔ ﻋﻠـﻰ‬
‫إطﺎرات اﻷﺑواب ﻣن أﺟل ﺗﺣﻘﯾق ﻛﺗﺎﻣﺔ ﻋﺎﻟﯾﺔ‪.‬‬
‫‪ ‬ﯾﺟب أن ﯾﻛـون ارﺗﻔـﺎع ﻛـل ﺧﻠﯾـﺔ ﻣـن اﻟﺧﻼﯾـﺎ )ﺳـﺗﺎﻧدر( ‪ ٢‬ﻣﺗـر وﻻ ﯾﻘـل ﻋﻣﻘﻬـﺎ ﻋـن‬
‫‪ ٦٠‬ﺳم‪ .‬أﻣﺎ اﻟﻌرض ﻓﯾﻛون ﺣﺳب اﻟﻘواطﻊ اﻟﺗﻲ ﺳﺗرﻛب ﺿـﻣﻧﻬﺎ ﺑﺣﯾـث ﻻ ﯾﻘـل ﻋـن‬
‫‪ ٥٠‬ﺳم )‪ ٦٠٠×٥٠٠×٢٠٠٠‬ﻣﻠم(‪.‬‬
‫‪ ‬ﺗﻛون اﻟﻠوﺣﺔ ﻣﻐﻠﻘﺔ وﻛﺗﯾﻣﺔ ﻣن ﺟﻣﯾـﻊ اﻟﺟﻬـﺎت ﻣـﺎ ﻋـدا اﻷﺳـﻔل ﺣﯾـث ﺗﻛـون ﻣﻔﺗوﺣـﺔ‬
‫ﻟدﺧول وﺧروج اﻟﻛﺎﺑﻼت‪ .‬ﻛﻣﺎ ﺗزود اﻟﻠوﺣﺔ ﺑﻘﺎﻋدة ﻣﻌدﻧﯾﺔ ﻋﻠﻰ طوﻟﻬﺎ ﺑﺳﻣﺎﻛﺔ ‪ ٢‬ﻣﻠم‬
‫وﺑﺎرﺗﻔﺎع ‪ ١٠‬ﺳم ﻣن أﺟل ﺗﺛﺑﯾﺗﻬﺎ ﻋﻠـﻰ اﻟﻘﺎﻋـدة اﻻﺳـﻣﻧﺗﯾﺔ ﺛـم ﺗوﺿـﻊ وﺗﺛﺑـت اﻟﻠوﺣـﺔ‬
‫ﻋﻠﻰ ﻫذﻩ اﻟﻘﺎﻋدة اﻟﻣﻌدﻧﯾﺔ‪.‬‬
‫‪ ‬ﯾﺟب أن ﺗزود ﻛﺎﻓﺔ اﻟﻠوﺣﺎت ﺑﻘﻔل أﺟﻧﺑﻲ ﻣوﺣد‪.‬‬
‫‪ ‬ﻟون اﻟﻠوﺣﺔ ﻋﺎﺟﻲ وﺗدﻫن ﻋن طرﯾق ﺑﺦ ﺑودرة إﻟﻛﺗروﺳﺗﺎﺗﯾﻛﻲ‪.‬‬

‫اﻟﺗﻘﺳﯾم اﻟداﺧﻠﻲ ﻓﻲ اﻟﻠوﺣﺎت‪:‬‬

‫‪ ‬ﯾﺟــب أن ﯾﻛــون اﻟﺗﻘﺳــﯾم اﻟــداﺧﻠﻲ ﻟﻠوﺣــﺎت اﻟرﺋﯾﺳــﯾﺔ ﻻ ﯾﻘــل ﻋــن )‪ (Form 2‬ﺣﺳــب‬
‫اﻟﻧظﺎم ‪ IEC439‬ﺑﺣﯾث ﯾﻛون ﺣﺳب اﻵﺗﻲ‪:‬‬

‫‪ ‬ﺧﻼﯾﺎ ﺗوزﯾﻊ اﻟطﺎﻗﺔ ‪ ٨٠٠‬أﻣﺑﯾر وﻣﺎ ﻓوق‪:‬‬

‫‪٨٦‬‬
‫ﺗﻛون اﻟﺧﻠﯾﺔ ﻣﻘﺳﻣﺔ داﺧﻠﯾﺎً إﻟﻰ ﺛﻼث ﺣﺟرات وﻛل ﺣﺟرة ﻣﻔﺻوﻟﺔ داﺧﻠﯾﺎً ﻋن اﻷﺧر وﻟﻬﺎ ﺑﺎﺑﻬﺎ‬
‫اﻟﻣﺳﺗﻘل‪:‬‬

‫‪ (١‬ﻓﻲ اﻟﺣﺟرة اﻟﻌﻠوﯾﺔ‪ :‬ﺗُرﻛب ﻋﻧﺎﺻر اﻟﺗﺣﻛم )إن وﺟدت(‪.‬‬


‫‪ (٢‬ﻓﻲ اﻟﻣﻧﺗﺻف‪ :‬ﯾُرﻛب اﻟﻘﺎطﻊ اﻟﻛﻬرﺑﺎﺋﻲ‪.‬‬
‫‪ (٣‬ﻓﻲ اﻟﺣﺟرة اﻟﺳﻔﻠﯾﺔ‪ :‬ﺗُﺳﺗﺧدم ﻟدﺧول اﻟﻛﺑﻼت ﻟﺗﻐذﯾﺔ اﻟﻘﺎطﻊ‪.‬‬

‫‪ ‬ﺧﻼﯾﺎ ﺗوزﯾﻊ اﻟطﺎﻗﺔ ﺑﻘواطﻊ ‪ ٦٣٠‬أﻣﺑﯾر وﻣﺎ دون‪:‬‬

‫ﺗرﻛـــب اﻟﻘواطـــﻊ ﺑﺷـــﻛل أﻓﻘـــﻲ ﻋﻠـــﻰ ﺻـــﻔﺎﺋﺢ ﻣﻌدﻧﯾـــﺔ ﻣزﯾﺑﻘـــﺔ‬


‫ﺑﺳﻣﺎﻛﺔ ‪ ٢‬ﻣﻠم ﻓﻲ اﻟﻘﺳم اﻷﻣﺎﻣﻲ ﻣن اﻟﻠوﺣﺔ ﺑﺣﯾث ﻓـﻲ ﺣـﺎل‬
‫ﻓﺗﺢ ﺑﺎب اﻟﻠوﺣﺔ ﯾﻣﻛن ﻣﺷﺎﻫدة اﻟﻘواطﻊ اﻟﻣرﻛﺑﺔ ﺿـﻣﻧﻬﺎ‪ .‬وﻓـﻲ‬
‫ﺣﺎل رﻏﺑﺔ اﻟﻣﺷرف ﯾﻣﻛـن إظﻬـﺎر ﻗﺑﺿـﺎت اﻟﻘواطـﻊ ﻓـﻲ اﻟﺧـﺎرج‬
‫ﻋﻠﻰ ﺑﺎب اﻟﻠوﺣﺔ ﻟﯾﺗم ﺗﺷﻐﯾﻠﻬﺎ ﺧﺎرﺟﯾﺎً‪.‬‬
‫أﻣﺎ اﻟﻘﺳـم اﻟﺧﻠﻔـﻲ ﻣـن ﻛـل ﻟوﺣـﺔ أي ﺧﻠـف اﻟﺻـﻔﺎﺋﺢ اﻟﻣﻌدﻧﯾـﺔ‬
‫ﻟﻠﻘواطﻊ ﺗرﻛب اﻟﺑﺎرات ‪ L1 – L2 – L3‬ﺑﺷﻛل ﺷﺎﻗوﻟﻲ ﻟﺗﻐذﯾﺔ‬
‫اﻟﻘواطﻊ‪ .‬وﺗﻛون اﻟﺑﺎرات ﻣﺣﺟوﺑﺔ ﺗﻣﺎﻣﺎً ﺑﯾﻧﻬﺎ وﺑـﯾن اﻟﻘواطـﻊ ﻻ‬
‫ﯾﻣﻛــن ﻣﺷــﺎﻫدﺗﻬﺎ وﻻ اﻟوﺻــول إﻟــﻰ اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ ﻓــﻲ ﺣــﺎل‬
‫ﻓــﺗﺢ ﺑــﺎب اﻟﻠوﺣــﺔ ﺑﺣﯾــث ﺗﻛــون اﻟﺗﻘﺳــﯾم اﻟــداﺧﻠﻲ )‪(Form2‬‬
‫وﺗﺣﻘق اﻷﻣﺎن ﻓﻲ اﻟﺗﺷﻐﯾل واﻟﺻﯾﺎﻧﺔ‪.‬‬

‫‪٨٧‬‬
‫اﻟﻣواﺻﻔﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻟﻠّوﺣﺎت‪:‬‬

‫‪ .١‬ﯾﺟب أن ﺗﺻﻧﻊ وﺗﺟﻣﻊ اﻟﻠوﺣﺎت وﻓق اﻟﺷروط اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻌﺎﻟﻣﯾﺔ ‪.IEC 439‬‬
‫‪ .٢‬ﺗرﻛب ﺟﻣﯾﻊ اﻟﺗﺟﻬﯾـزات اﻟﻛﻬرﺑﺎﺋﯾـﺔ )اﻟﻘواطـﻊ …اﻟـﺦ‪ (.‬اﻟﻣـذﻛورة ﻓـﻲ اﻟﻣﺧططـﺎت ﺿـﻣن‬
‫ﻫذﻩ اﻟﻠوﺣﺔ وﻟﻛـن ﯾﺟـب اﻷﺧـذ ﺑﻌـﯾن اﻻﻋﺗﺑـﺎر أن ﺗرﻛﯾـب اﻟﻘواطـﻊ ﺿـﻣن اﻟﺧﻼﯾـﺎ وﺗﺻـﻣﯾم‬
‫اﻟﻠوﺣﺔ وﻋدد اﻟﺧﻼﯾﺎ ﯾﻛون ﺑﺷـﻛل ﻓﻧـﻲ وﻣـدروس ﻣـﻊ ﻣراﻋـﺎة ﺷـروط اﻟﻧﺷـر اﻟﺣـراري و ﻻ‬
‫ﺗرﻛب اﻟﻘواطﻊ ﺿﻣن اﻟﺧﻠﯾﺔ ﺑﻛﻣﯾﺎت ﻋﺷواﺋﯾﺔ دون دراﺳﺔ اﻟﻧﺷر اﻟﺣراري‪.‬‬
‫‪ .٣‬ﯾﺟب أن ﺗﺗﺣﻣل اﻟﻠوﺣﺔ ﺷدة ﻗطﻊ ﻋﺎﻟﯾﺔ‪.‬‬
‫‪ .٤‬درﺟﺔ اﻟﻛﺗﺎﻣﺔ ﻟﻠوﺣﺎت‪.IP 40 :‬‬
‫‪ .٥‬ﺗوﺗر اﻟﻌﻣل‪ (٤٠٠ – ٣٨٠) :‬ﻓوﻟط‪ ٥٠ ،‬ﻫرﺗز‪.‬‬
‫‪ .٦‬ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ ‪ ٦٩٠‬ﻓوﻟط‪.‬‬
‫‪ .٧‬ﺧطوط اﻟﺷﺑﻛﺔ )اﻟﺑﺎرات(‪ :‬ﺧﻣس ﺧطوط ‪. L1, L2, L3, N, PE‬‬
‫‪ .٨‬ﯾﺟب ﺣﻣﺎﯾﺔ ﺟﻣﯾﻊ دارات اﻟﺗﺣﻛم ﺑواﺳطﺔ ﻓﯾوز ‪ /١/‬أﻣﺑﯾر ﺑﺷدة ﻗطﻊ ﻋﺎﻟﯾﺔ‪.‬‬

‫اﻟﺑﺎرات اﻟﻧﺣﺎﺳﯾﺔ واﻟﺣﻣﺎﻻت ﻓﻲ اﻟﻠوﺣﺎت‪:‬‬

‫ﺗ ﺷﻛل ﻧظﺎم اﻟﺑﺎرات ﻓﻲ اﻟﻠوﺣﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ أﻫﻣﯾـﺔ ﻛﺑﯾـرة ﻟﺿـﻣﺎن اﺳـﺗﻣرارﯾﺔ ﻋﻣـل اﻟﻠوﺣـﺔ‪ .‬وﯾﺟـب‬
‫أن ﯾﻛــون ﻫــذا اﻟﻧظــﺎم ﻣطﺎﺑﻘ ـﺎً ﻟﻠﻧظــﺎم اﻟﻛﻬرﺑــﺎﺋﻲ ‪ ،IEC 439-1‬وذات وﺛوﻗﯾــﺔ ﻋﺎﻟﯾــﺔ ﺗﺣﻘــق‬
‫ﻣﺗطﻠﺑﺎت اﻻرﺗﻔﺎع اﻟﺣراري ﻟﻠﺑﺎرات وﺷدة ﺗﯾﺎر اﻟﻘﺻر ﻟﻣدة ﺛﺎﻧﯾﺔ واﺣدة‪.‬‬
‫ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﺑﺎرات ﺿﻣن اﻟﻠوﺣﺎت ﻧﺣﺎﺳﯾﺔ إﻟﻛﺗروﻟﯾﺗﯾﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ وﺑﻛﺛﺎﻓـﺔ ﺗﯾـﺎر ﻻ‬
‫ﺗزﯾد ﻋن ‪ ١.٦‬أﻣﺑﯾر‪/‬ﻣم‪. ٢‬‬
‫إن ﺗﺻﻣﯾم ﻧظﺎم اﻟﺑﺎرات ﺿﻣن اﻟﻠوﺣﺔ ﯾﻌﺗﻣد ﻋﻠﻰ اﻟﺗوﺿﻊ اﻷﻓﻘﻲ واﻟﺷﺎﻗوﻟﻲ ‪.‬‬
‫ﻓـﻲ ﺣـﺎل ﻛـون اﻟﻠوﺣـﺔ ﺗﺗـﺄﻟف أﻛﺛـر ﻣـن ﺧﻠﯾـﺔ ﯾـﺗم ﺗﻣرﯾـر اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ ‪ L1, L2, L3‬ﻋﺑـر‬
‫اﻟﺧﻼﯾﺎ ﺑﺷﻛل أﻓﻘﻲ ﻟﺗﻐذي اﻟﺑﺎرات اﻟﺷﺎﻗوﻟﯾﺔ اﻟﺗﻲ ﺗﺗﻐذى ﻣﻧﻬﺎ اﻟﻘواطﻊ ﻓﻲ اﻟﺧﻼﯾﺎ اﻟﺗـﻲ ﺗﺗﺿـﻣن‬
‫ﻗواطﻊ ﺑﻌﯾﺎرات ‪ ٦٣٠‬أﻣﺑﯾر وﻣﺎ دون‪.‬‬

‫‪٨٨‬‬
‫وﯾرﻛب أﯾﺿﺎً ﻓﻲ اﻷﺳﻔل وﻋﻠﻰ طـول اﻟﻠوﺣـﺔ ﺑـﺎر ﺣﯾـﺎدي ‪ –N-‬ﻣﺛﺑـت ﻋﻠـﻰ ﺣﻣـﺎﻻت ﺑـﺎرات وﺑـﺎر‬
‫أرﺿﻲ ‪.PE-‬‬

‫ﺗﺛّﺑت اﻟﺑﺎرات ﻋﻠﻰ ﺣﻣـﺎﻻت ﺧﺎﺻـﺔ أﺟﻧﺑﯾـﺔ اﻟﺻـﻧﻊ ﺗﺗﺣﻣـل اﺟﻬـﺎدات دﯾﻧﺎﻣﯾﻛﯾـﺔ ﻋﺎﻟﯾـﺔ أﺛﻧـﺎء دارة‬
‫اﻟﻘﺻر‪.‬‬
‫وﯾﺗم ﺗﺻﻧﯾﻊ ﺣﺎﻣﻼت اﻟﺑﺎرات ﻣن ﺑـوﻟﯾﻣﯾرات ﻋﺎﻟﯾـﺔ اﻟﺟـودة واﻟﺗـﻲ ﺗـؤﻣن ﻋﺎزﻟﯾـﺔ ﻛﻬرﺑﺎﺋﯾـﺔ ﻋﺎﻟﯾـﺔ‬
‫ﻟﻠﻘﺿــﺑﺎن اﻟﻧﺣﺎﺳــﯾﺔ‪ ،‬وﺗﺗﺣﻣــل ﺑﺷــﻛل ﺟﯾــد اﻻﺟﻬــﺎدات اﻟﺣرارﯾــﺔ واﻟﻣﯾﻛﺎﻧﯾﻛﯾــﺔ اﻟﻧﺎﺗﺟــﺔ ﻋــن ﺗﯾــﺎرات‬
‫اﻟﻘﺻر ﻛﻣﺎ ﺗﺗﺣﻣل اﻟﺗﻐﯾﯾرات اﻟﺣرارﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻋن اﻟﺗﺷﻐﯾل‪.‬‬

‫اﻟﺗﻣدﯾدات ﺿﻣن اﻟﻠوﺣﺎت‪:‬‬

‫ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﺗﻣدﯾدات ﺿﻣن اﻟﻠوﺣﺎت ﺑطرﯾﻘﺔ ﻓﻧﯾﺔ وﺻﺣﯾﺣﺔ ﺑﺣﯾث ﺗﻛون ﺗﻐذﯾﺔ‬
‫اﻟﻘواطﻊ ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﺣﺳب اﻵﺗﻲ‪:‬‬
‫‪ ‬ﯾــﺗم ﺗﻐذﯾــﺔ اﻟﻘواطــﻊ ‪ ٢٠٠‬أﻣﺑﯾــر وﻣــﺎ دون ﻣــن اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ ﺑواﺳــطﺔ ﻛــﺑﻼت‬
‫ﺷﻌرﯾﺔ ﺑﻌﺎزﻟﯾﺔ ‪ ٦٩٠‬ﻓوﻟط وﺑﻣﻘﺎطﻊ ﻣﻧﺎﺳـﺑﺔ ﺣﺳـب ﺗﯾـﺎرات اﻟﻘواطـﻊ وﻧظـﺎم ‪IEC‬‬
‫‪.439‬‬

‫‪٨٩‬‬
‫‪ ‬وﺗﻐذﯾﺔ اﻟﻘواطﻊ ‪ ٢٥٠‬أﻣﺑﯾر وﻟﻐﺎﯾﺔ ‪ ٦٣٠‬أﻣﺑﯾر ﻣن اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ ﯾـﺗم ﺑواﺳـطﺔ‬
‫ﺑﺎرات ﻣرﻧﺔ ﻣﻌزوﻟﺔ ﺧﺎﺻﺔ ﺗﺳﺗﺧدم ﻟﻠﺗﻣدﯾـدات ﺿـﻣن اﻟﻠوﺣـﺎت ﺑﻌﺎزﻟﯾـﺔ ‪ ٦٩٠‬ﻓـوﻟط‬
‫وﺑﻣﻘﺎطﻊ ﻣﻧﺎﺳﺑﺔ ﺣﺳب ﺗﯾﺎرات اﻟﻘواطﻊ‪.‬‬
‫‪ ‬وﺗﻐذى اﻟﻘواطﻊ ﺑﺗﯾﺎر اﺳﻣﻲ أﻋﻠﻰ ﻣن ‪ ٦٣٠‬أﻣﺑﯾر ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﺑواﺳطﺔ‬
‫ﺑﺎرات ﻧﺣﺎﺳﯾﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ أو ﺑﺎرات ﻣرﻧﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ وﺣﺳب اﻟﻣﻘﺎطﻊ‬
‫اﻟﻣﻧﺎﺳﺑﺔ‪.‬‬
‫إن ﻋﻣﻠﯾﺔ ﺗﻔرﯾﻊ اﻟﻛﺑﻼت اﻟﺷﻌرﯾﺔ واﻟﺑﺎرات اﻟﻣرﻧﺔ ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳـﯾﺔ )‪ (L1-L2-L3‬ﺗـﺗم‬
‫ﻋﺑر ﻣﻘﺎﻣط )ﻛﻠﯾﺑﺳـﺎت( ﺧﺎﺻـﺔ ﺗرﻛـب ﻋﻠـﻰ اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ وﺗﻔـرّع ﻣﻧﻬـﺎ اﻟﻛـﺑﻼت واﻟﺑـﺎرات‬
‫اﻟﻣرﻧﺔ ﻟﺗﻐذﯾﺔ اﻟﻘواطﻊ وﻻ ﯾﺳﻣﺢ ﺑﺗﺛﻘﯾب اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﻟﻠﺗﻔرﯾﻊ ﻣﻧﻬﺎ‪.‬‬

‫اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ‪:‬‬

‫ﯾﺟـــب أن ﺗﻛـــون ﻫـــذﻩ اﻟﻠوﺣـــﺎت ﻣﺟﻬـــزة ﺑﺟﻣﯾـــﻊ اﻟﻘواطـــﻊ واﻟﺗﺟﻬﯾـــزات اﻟﻛﻬرﺑﺎﺋﯾـــﺔ اﻟﻣطﻠوﺑـــﺔ ﻓـــﻲ‬
‫اﻟﻣﺧططــﺎت وﻣﺻ ـﻧّﻌﺔ وﻓــق اﻟﻣواﺻــﻔﺎت اﻟﻣطﻠوﺑــﺔ ﻓــﻲ دﻓﺗــر اﻟﺷــروط‬
‫اﻟﻔﻧﯾﺔ ﻛﺎﻣﻠﺔ ﺟﺎﻫزة ﻟﻠﺗرﻛﯾب واﻻﺳﺗﺛﻣﺎر‪.‬‬

‫‪٩٠‬‬
‫ﻫﯾﻛل اﻟﺻﺎج ﻟﻠّوﺣﺎت‪:‬‬

‫ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻠوﺣﺎت ﺟدارﯾﺔ أو ﻟوﺣﺎت ﺗرﻛﯾب أرﺿﻲ ﺣﺳب ﻣواﻗﻊ ﺗرﻛﯾﺑﻬـﺎ ﻣﺻـﻧّﻌﺔ ﻣـن‬
‫أﻟواح اﻟﺻﺎج اﻟﻔوﻻذﯾﺔ ﺑﺳﻣﺎﻛﺔ ‪ ١.٥‬ﻣﻠم‪.‬‬
‫ﺗﻛون اﻟﻠوﺣﺎت ﻣﻐﻠﻘﺔ وﻛﺗﯾﻣﺔ ﻣن ﺟﻣﯾﻊ اﻟﺟﻬﺎت وﺗزود ﻓﻲ أﻋﻠﻰ وأﺳﻔل اﻟﻠوﺣﺎت ﺑﺄﻏطﯾﺔ ﯾﻣﻛـن‬
‫ﻓﻛﻬﺎ ﻟدﺧول اﻟﻛﺑﻼت‪.‬‬
‫أﻣﺎ ﻋﻠﻰ اﻟ ﻬﯾﻛل اﻟﺧﺎرﺟﻲ ﺗُﺛﺑت اﻷﺑواب ﻋﺑر ﻣﻔﺻﻼت ﺧﺎﺻﺔ‪ ،‬وﺗﻔﺗﺢ اﻷﺑواب ﺑزاوﯾﺔ أﻛﺛر ﻣن‬
‫‪ ١٢٠‬درﺟﺔ ﻟﺗﺳﻬﯾل ﻋﻣﻠﯾﺔ اﻟﺻﯾﺎﻧﺔ ﻓﻲ داﺧل اﻟﻠوﺣﺔ وﺗزود ﻋﻠﻰ إطﺎرات اﻷﺑواب ﺟواﻧﺎت‬
‫ﻣطﺎطﯾﺔ )ﻛﺎوﺗﺷوﻛﯾﺔ( ﻣن أﺟل ﺗﺣﻘﯾق ﻛﺗﺎﻣﺔ ﻋﺎﻟﯾﺔ‪.‬‬
‫ﺗﻛون اﻟﻠوﺣﺎت ﻣﺻﻧّﻌﺔ ﺑﺑﺎب أو ﻏطﺎء داﺧﻠﻲ ﯾﻐطﻲ اﻟﺗﺟﻬﯾزات اﻟﻣرﻛﺑﺔ ﻓﻲ اﻟداﺧل واﻟذي ﺗظﻬر‬
‫ﻣﻧﻪ ﺻواﻋد اﻟﻘواطﻊ اﻟﺻﻐﯾرة وﺑﺎب ﺛﺎﻧﻲ ﺧﺎرﺟﻲ ﺷﻔﺎف ﻋﻠﻰ طول اﻟﻠوﺣﺔ‪.‬‬
‫أﺑﻌﺎد اﻟﻠوﺣﺎت ﯾﺟب أن ﺗﻛون ﺑﺄﺑﻌﺎد ﻧظﺎﻣﯾﺔ وﻓق اﻟﻘواطﻊ واﻟﺗﺟﻬﯾزات اﻟﺗﻲ ﺳﺗرﻛب ﺿﻣﻧﻬﺎ‬
‫وﺑﻘﯾﺎﺳﺎت )ﺳﺗﺎﻧدرد( وﻣن ﻣﺿﺎﻋﻔﺎت ‪ ٢٠‬ﺳم ﺑﺣﯾث ﻻ ﯾﻘل ﻋرض اﻟﻠوﺣﺎت ﻋن ‪ ٦٠‬ﺳم‪.‬‬
‫)اﻟﻣﻘﺻود ﻣن ﻣﺿﺎﻋﻔﺎت ‪ ٢٠‬ﺳم ﻣﺛﺎل‪ ٢٠٠×٦٠٠×١٠٠٠ :‬طول × ﻋرض × ﻋﻣق(‪.‬‬

‫‪ -‬ﯾﺟب أن ﺗزود ﻛﺎﻓﺔ اﻟﻠوﺣﺎت ﺑﻘﻔل أﺟﻧﺑﻲ ﻣوﺣد‪.‬‬


‫ﻟون اﻟﻠوﺣﺔ ﻋﺎﺟﻲ وﺗدﻫن ﻋن طرﯾق ﺑﺦ ﺑودرة إﻟﻛﺗروﺳﺗﺎﺗﯾﻛﻲ‪.‬‬ ‫‪-‬‬

‫ﯾرﻛب داﺧل اﻟﻠوﺣﺔ ﻫﯾﻛل ﻣﻌدﻧﻲ ﻣﺗﺣرك ﻣﺻﻧوع ﻣـن اﻟﺻـﺎج اﻟﻣزﯾﺑـق ﺑﺳـﻣﺎﻛﺔ ‪ ١.٥‬ﻣﻠـم ﺑﺣﯾـث‬
‫ﺗرﻛب ﻋﻠﯾﻬﺎ اﻟﻘواطﻊ واﻟﺗﺟﻬﯾزات اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻣطﻠوﺑﺔ وﯾﻛون ﺗرﺗﯾب اﻟﺗﺟﻬﯾزات ﻓﻲ داﺧـل اﻟﻠوﺣـﺔ‬
‫ﺣﺳب اﻵﺗﻲ‪:‬‬
‫‪ -‬اﻟﻘﺳم اﻟﻌﻠوي ﻣـن اﻟﻠوﺣـﺔ ﺗرﻛـب اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ )إن وﺟـدت( ‪ L1, L2, L3‬ﻣﺛﺑﺗـﺔ ﻋﻠـﻰ‬
‫ﺣﻣﺎﻻت ﺑﺎرات ﺧﺎﺻﺔ ﺗﺗﺣﻣل اﻹﺟﻬﺎدات اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎرات اﻟﻘﺻر‪.‬‬
‫اﻟﻘﺳــم اﻷوﺳــط ﺗرﻛــب اﻟﻘواطــﻊ واﻟﺗﺟﻬﯾ ـزات اﻟﻛﻬرﺑﺎﺋﯾــﺔ اﻟﻣطﻠوﺑــﺔ اﻟﺗــﻲ ﺗﺛﺑــت ﻋﻠــﻰ ﺻــﻔﺎﺋﺢ‬ ‫‪-‬‬
‫ﻓوﻻذﯾﺔ ﻣزﯾﺑﻘﺔ ﺑﺳﻣﺎﻛﺔ ‪ ١.٥‬ﻣﻠم‪.‬‬
‫اﻟﻘﺳم اﻟﺳﻔﻠﻲ ﺗرﻛـب ﻣـراﺑط )ﺟﻧﻛﺳـﯾوﻧﺎت( اﻟـدﺧل واﻟﺧـرج ﻟﻸﺳـﻼك ﺣﯾـث ﯾﻛـون ﻟﻛـل ﻗـﺎطﻊ‬ ‫‪-‬‬
‫ﻣرﺑط ﺧﺎص ﺑﻪ وﯾرﻛب أﯾﺿﺎً ﻓﻲ اﻷﺳﻔل وﻋﻠﻰ طول اﻟﻠوﺣﺔ ﺑﺎر اﻟﺣﯾﺎدي ‪ N‬وﺑﺎر اﻷرﺿﻲ‪.‬‬
‫أﻣــﺎ ﻓــﻲ ﺣــﺎل ﻛﺎﻧــت اﻟﻠوﺣــﺎت اﻟﻣطﻠوﺑــﺔ ﺻــﻐﯾرة ﻟــدارات اﻹﻧــﺎرة ﻓــﯾﻣﻛن اﻻﺳــﺗﻐﻧﺎء ﻋــن اﻟﺑــﺎرات‬
‫اﻟرﺋﯾﺳﯾﺔ ‪. L1, L2, L3‬‬

‫‪٩١‬‬
‫اﻟﻣواﺻﻔﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻟﻠوﺣﺎت‪:‬‬
‫‪ -‬ﺗرﻛب اﻟﺗﺟﻬﯾزات اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﻲ اﻟﻠوﺣﺎت ﺑﺷﻛل ﻓﻧﻲ وﻣدروس وﺑﺣﯾث ﺗوﺻﱠل ﺟﻣﯾﻊ اﻟﻘواطـﻊ‬
‫ﻣن ﻣﺧﺎرﺟﻬﺎ إﻟﻰ ﻣراﺑط )ﺟﻧﻛﺳﯾوﻧﺎت( ﺧﺎﺻﺔ ﻟﻛل ﻗﺎطﻊ‪.‬‬
‫ﯾﺟب أن ﺗﺗﺣﻣل اﻟﻠوﺣﺎت ﺷدة ﻗطﻊ ﻋﺎﻟﯾﺔ‪.‬‬ ‫‪-‬‬
‫ﺗوﺗر اﻟﻌﻣل‪ ٦٩٠ – ٣٨٠ :‬ﻓوﻟط‪ ٥٠ ،‬ﻫرﺗز‪.‬‬ ‫‪-‬‬
‫‪ -‬ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ‪ ٦٩٠ :‬ﻓوﻟط‪.‬‬
‫‪ -‬ﺧطوط اﻟﺷﺑﻛﺔ‪ :‬ﻓﻲ ﺣﺎل وﺟـود ﻗواطـﻊ ﻋدﯾـدة ﻓـﻲ اﻟﻠوﺣـﺎت وﯾﺳـﺗدﻋﻲ وﺟـود ﺑـﺎرات رﺋﯾﺳـﯾﺔ‬
‫ﻓﯾﺟب أن ﺗﻛون ﺧﻣس ﺧطوط ‪L1-L2-L3-N+PE‬‬
‫‪ -‬ﯾﺟـب أن ﺗﻛــون اﻟﺑــﺎرات اﻟرﺋﯾﺳـﯾﺔ ﻧﺣﺎﺳــﯾﺔ إﻟﻛﺗروﻟﯾﺗﯾــﺔ أﺟﻧﺑﯾــﺔ اﻟﺻـﻧﻊ وﺑﻛﺛﺎﻓــﺔ ﺗﯾــﺎر ﻻ ﺗزﯾــد‬
‫ﻋن ‪ ٢‬أﻣﺑﯾر‪/‬ﻣم‪.٢‬‬
‫‪ -‬ﺣﻣــﺎﻻت اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ‪ :‬ﯾﺟــب أن ﺗﻛــون أﺟﻧﺑﯾــﺔ اﻟﺻــﻧﻊ ﻣــن إﺣــدى اﻟﺷــرﻛﺎت اﻟﻌﺎﻟﻣﯾــﺔ‬
‫وﺗﺗﺣﻣل اﻹﺟﻬﺎدات اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ اﻟﻌﺎﻟﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎرات اﻟﻘﺻر‪.‬‬
‫ﺗُﺣﻣﻰ ﺟﻣﯾﻊ دارات اﻟﺗﺣﻛم ﺿﻣن اﻟﻠوﺣﺎت ﺑﻔﯾوزات ‪ ١‬أﻣﺑﯾر‪.‬‬ ‫‪-‬‬
‫اﻟﻣراﺑط‪ :‬ﯾﺟب أن ﺗﺳﺗﺧدم ﻓﻲ اﻟﻠوﺣﺎت ﻣراﺑط ﺧﺎﺻـﺔ ﺗرﻛـب ﻋﻠـﻰ ﺳـﻛﺔ ﻟﻠﻣﻘـﺎطﻊ ﻟﻐﺎﯾـﺔ ‪٧٠‬‬ ‫‪-‬‬
‫ﻣﻠـم وﻣـراﺑط ﺻــﻧﺎﻋﯾﺔ ﺧﺎﺻــﺔ ﻟﻣﻘــﺎطﻊ ‪ ٧٠‬ﻣﻠــم ﻓﻣـﺎ ﻓــوق وﺗﻛــون ﻫــذﻩ اﻟﻣـراﺑط ﻣــن‬
‫أﺟود اﻷﻧواع اﻟﻐرﺑﯾﺔ ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن اﻟﻣواﺻﻔﺎت اﻟﻌﺎﻟﯾﺔ ‪. IEC, VDE‬‬

‫اﻟﺗﻣدﯾدات ﺿﻣن اﻟﻠوﺣﺎت‪:‬‬


‫‪ -‬ﺗﻛــون ﺟﻣﯾــﻊ اﻟﺗﻣدﯾــدات ﺿــﻣن اﻟﻠوﺣــﺎت ﺑطرﯾﻘــﺔ ﻓﻧﯾــﺔ وﺻــﺣﯾﺣﺔ وﺗﺟﻣــﻊ اﻷﺳــﻼك ﻟﻠﻘواطــﻊ‬
‫اﻟﻔرﻋﯾﺔ ﺿﻣن ﻣﺟﺎري ﺑﻼﺳﺗﯾﻛﯾﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ‪.‬‬
‫ﺗﺗم ﺗﻐذﯾﺔ اﻟﻘواطﻊ ﻣﺎ دون ‪ ٢٠٠‬أﻣﺑﯾر ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﻋﺑـر ﻛـﺑﻼت ﺷـﻌرﯾﺔ وﺑﻣﻘـﺎطﻊ‬ ‫‪-‬‬
‫ﻣﻧﺎﺳﺑﺔ ﺣﺳب ﺗﯾﺎرات اﻟﻘواطﻊ ووﻓق اﻟﻧظﺎم ‪ ،IEC439‬أﻣﺎ اﻟﻘواطﻊ ‪ ٢٠٠‬أﻣﺑﯾر ﻓﻣﺎ ﻓـوق‬
‫ﻟﻐﺎﯾــﺔ ‪ ٦٣٠‬أﻣﺑﯾــر ﻓﺗــﺗم ﺗﻐــذﯾﺗﻬﺎ ﺑﺑــﺎرات ﻣرﻧــﺔ ﻣﻌزوﻟــﺔ ﺧﺎﺻــﺔ ﺗﺳــﺗﺧدم ﻟﻠﺗﻣدﯾــدات ﺿــﻣن‬
‫اﻟﻠوﺣﺎت وﺑﻣﻘﺎطﻊ ﻣﻧﺎﺳﺑﺔ وﻓق ﺗﯾﺎرات اﻟﻘواطﻊ‪.‬‬

‫‪٩٢‬‬
‫إن ﻋﻣﻠﯾﺔ ﺗﻔرﯾﻊ اﻟﻛﺑﻼت اﻟﺷﻌرﯾﺔ واﻟﺑﺎرات اﻟﻣرﻧﺔ ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳـﯾﺔ )‪ (L1-L2-L3‬ﺗـﺗم‬
‫ﻋﺑــر ﻣﻘــﺎﻣط )ﻛﻠﯾﺑﺳــﺎت( ﺧﺎﺻــﺔ ﺗرﻛــب ﻋﻠــﻰ اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ وﺗﻔــرّع ﻣﻧﻬــﺎ اﻟﻛــﺑﻼت واﻟﺑــﺎرات‬
‫اﻟﻣرﻧﺔ وﻻ ﯾﺳﻣﺢ ﺑﺗﺛﻘﯾب اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﻟﻠﺗﻔرﯾﻊ ﻣﻧﻬﺎ‪.‬‬
‫ﺗﺳــﺗﺧدم ﺟﻣﯾــﻊ اﻷﺳــﻼك ﺿــﻣن اﻟﻠوﺣــﺎت ﺑــﺎﻟﻠون اﻷﺳــود ﻣــﺎ ﻋــدا أﺳــﻼك اﻟــﺗﺣﻛم ﺑــﺎﻟﻠون‬ ‫‪-‬‬
‫اﻷﺣﻣر وأﺳﻼك اﻟﺣﯾﺎدي ﺑﺎﻟﻠون اﻷزرق‪.‬‬
‫ﺗﻛون ﺟﻣﯾﻊ اﻷﺳﻼك ﻓﻲ ﻧﻬﺎﯾﺗﻬﺎ ﻣرﻗﻣﺔ ﺑﺣﯾث ﯾﺳﻬل ﻋﻣﻠﯾﺔ اﻟﺻﯾﺎﻧﺔ ﻓﻲ اﻟﻣﺳﺗﻘﺑل‪.‬‬ ‫‪-‬‬

‫‪٩٣‬‬
TRANSFORMER

ETERNAL ENGINEERS GROUP


01007200959-01114911166

٩٤
‫اﻟﻣﺣوﻻت اﻟﻛﻬرﺑﯾﺔ‬

‫ﺗﻌرﯾف اﻟﻣﺣول‪:‬‬
‫ﻫو ﻣﻌدة ﺳﺎﻛﻧﺔ ﻻ ﺗﺣﺗوى ﻋﻠﻰ أي أﺟزاء ﻣﺗﺣرﻛﺔ ﺗﺳﺗﺧدم ﻟﻧﻘل اﻟﻘدرة اﻟﻛﻬرﺑﯾﺔ ﻣن ﺟﻬﺔ إﻟﻰ‬
‫ﺟﻬﺔ أﺧري وذﻟك ﺑﺗﻐﯾﯾر ﻗﯾم ﻣﻛوﻧﺎت ﻫذﻩ اﻟﻘدرة )اﻟﺟﻬد واﻟﺗﯾﺎر ( ﻣﻊ اﻟﻣﺣﺎﻓظﺔ ﻋﻠﻰ اﻟﺗردد ‪.‬‬
‫وﻋﺎدة ﯾﺳﻣﻲ اﻟﻣﻠف اﻟﻣﺗﺻل ﺑﻣﺻدر اﻟﺟﻬد ﺑﺎﻟﻣﻠف اﻻﺑﺗداﺋﻲ ﻛﻣﺎ ﯾﺳﻣﻲ اﻟﻣﻠف اﻟﻣﺗﺻل ﺑﺎﻟﺣﻣل‬
‫ﺑﺎﻟﻣﻠف اﻟﺛﺎﻧوي‪.‬‬

‫اﺳﺗﺧداﻣﺎت اﻟﻣﺣوﻻت‪:‬‬
‫‪1.‬ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻟﻧﻘل اﻟﻘدرة اﻟﻛﻬرﺑﯾﺔ ﻟﻣﺳﺎﻓﺎت ﺑﻌﯾدة ﻣن أﻣﺎﻛن ﺗوﻟﯾدﻫﺎ إﻟﻰ أﻣﺎﻛن‬
‫ﺗوزﯾﻌﻬﺎ واﺳﺗﺧداﻣﻬﺎ‪.‬‬
‫‪2.‬ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻣﻊ أﺟﻬزة اﻟﻘﯾﺎس واﻟوﻗﺎﯾﺔ ﻋﻧدﻣﺎ ﺗﻛون اﻟﺗﯾﺎرات واﻟﺟﻬود اﻟﻛﻬرﺑﯾﺔ ﻋﺎﻟﯾﺔ‬
‫وذﻟك ﺑﺧﻔض ﻗﯾم اﻟﺗﯾﺎرات أو اﻟﺟﻬود إﻟﻰ ﻗﯾم ﺻﻐﯾرة ﯾﻣﻛن ﻗﯾﺎﺳﻬﺎ واﻟﺗﻌﺎﻣل ﻣﻌﻬﺎ‪.‬‬
‫‪3.‬ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻓﻲ اﻟﻌزل اﻟﻛﻬرﺑﺎﺋﻲ ﺑﻐرض ﻣﻧﻊ اﻟﺷوﺷرة اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﯾﺔ ﻓﻲ اﻟدواﺋر‬
‫اﻹﻟﻛﺗروﻧﯾﺔ‪.‬‬
‫‪4.‬ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻓﻲ اﻏﻠب اﻷﺟﻬزة اﻟﻛﻬرﺑﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ ﻟﻠﺣﺻول ﻋﻠﻰ ﺟﻬود ﺗﺷﻐﯾل ﻫذﻩ‬
‫اﻷﺟﻬزة واﻟﺗﻲ ﺗﻌﺗﺑر ﺻﻐﯾرة ﺟدا ﺑﺎﻟﻣﻘﺎرﻧﺔ ﺑﺟﻬد اﻟﻣﺻدر‪.‬‬
‫‪5.‬ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت أﯾﺿﺎ ﻟﻠﻣواﺋﻣﺔ ) اﻟﺗوﻓﯾق ( ﺑﯾن اﻟﻣﻣﺎﻧﻌﺎت‪.‬‬

‫ﺗرﻛﯾب اﻟﻣﺣول‪:‬‬
‫ﯾﺗرﻛب اﻟﻣﺣول ﻋﻣوﻣﺎ ﻣن‪:‬‬
‫‪1-‬ﻗﻠب ﺣدﯾدي ﻣﺻﻧوع ﻣن رﻗﺎﺋق ﻣن اﻷﻟواح اﻟﻣﺻﻧوﻋﺔ ﻣن اﻟﺻﻠب اﻟﺳﻠﯾﻛوﻧﻲ‪.‬‬
‫‪2-‬ﻣﻠﻔﯾن ﻣن اﻷﺳﻼك اﻟﻛﻬرﺑﯾﺔ اﻟﻣﻌزوﻟﺔ اﺣدﻫﻣﺎ ﻫو اﻟﻣﻠف اﻻﺑﺗداﺋﻲ واﻵﺧر ﻫو اﻟﻣﻠف‬
‫اﻟﺛﺎﻧوي وﯾﺗم ﻟﻔﻬﻣﺎ ﻋﻠﻰ ﺟﺎﻧﺑﻲ اﻟﻘﻠب اﻟﺣدﯾدي‪.‬‬
‫أي اﻧﻪ ﯾﻣﻛن اﻋﺗﺑﺎر اﻟﻣﺣول ﻣﻛون ﻣن داﺋرﺗﯾن اﺣداﻫﻣﺎ داﺋرة ﻣﻐﻧﺎطﯾﺳﯾﺔ واﻷﺧرى داﺋرة ﻛﻬرﺑﯾﺔ‬
‫ﺣﯾث ﯾﻣﺛل اﻟﻘﻠب اﻟﺣدﯾدي اﻟداﺋرة اﻟﻣﻐﻧﺎطﯾﺳﯾﺔ و ﺗﻣﺛل اﻟﻣﻠﻔﺎت اﻟداﺋرة اﻟﻛﻬرﺑﯾﺔ‪.‬‬

‫اﻧﻧﺎ ﻓﻲ اﻟﻣﻧﺗدى ﻏﺎﻟﺑﺎ ﻣﺎﻧﺗﺎول ﺟواﻧب اﻟﻧﺻب واﻟﺗﺷﻐﯾل واﻟﻔﺣص واﻟﺻﯾﺎﻧﺔ وﻗﻠﯾﻼ ﻣﺎ ﻧﻧظر اﻟﻰ‬
‫اﻟﺟﺎﻧب اﻟﺗﺻﻧﯾﻌﻲ ﻣن اﻟﻣﺣوﻟﺔ وﺳﺎﺣﺎول ﻓﻲ اﻟﻣﺷﺎرﻛﺎت ادﻧﺎﻩ ﺷرح اﻟﻣواد اﻟﻼزﻣﺔ ﻻﻧﺗﺎج‬
‫ﻣﺣوﻻت اﻟﺗوزﯾﻊ واﻟﻘدرة ﻣرﻛ از ﻋﻠﻰ اﻟﻣﺣوﻻت اﻟﺷﺎﺋﻌﺔ اﻻﺳﺗﺧدام واﻟﻣﺑردة ﺑﺎﻟزﯾت‬

‫‪٩٥‬‬
‫اوﻻ ‪ :‬اﻟﻣواد واﻻﺟﻬزة اﻻزﻣﺔ ﻻﻧﺗﺎج اﻟﻣﺣوﻻت ﺑﺻورة ﻋﺎﻣﺔ ﻫﻲ‬
‫‪ -١‬اﻟﺣدﯾد اﻟﻛﻬرﺑﺎﺋﻲ‬
‫‪ -٢‬اﻟﻣوﺻﻼت‬
‫‪-٣‬اﻟﻌوازل‬
‫‪-٤‬زﯾوت اﻟﻌزل‬
‫‪-٥‬ﻣﺂﺧذ اﻟﺗﯾﺎر )اﻟﺑوﺷﻧﺟﺎت(‬
‫‪-٦‬ﻣﻐﯾرات اﻟﺟﻬد‬
‫‪-٧‬اﺟﻬزة وﻣﺗﺣﺳﺳﺎت ﻣﻠﺣﻘﺔ ﻣﺛل ﻣزﯾﻼت اﻟرطوﺑﺔ وﻣﻌدات اﻟﺳﯾطرة ﻋﻠﻰ ﺗدﻓق اﻟزﯾوت وﻏﯾرﻫﺎ‬
‫‪ -٨‬ﺣدﯾد ﺧزان اﻟﺗﺑرﯾد وﻣواد ﻣﺗﻌﻠﻘﺔ ﺑﺎﻟﺧزان واﻟﺗﺟﻣﯾﻊ اﻟﻣﯾﻛﺎﻧﯾﻛﻲ ﻟﻪ‬
‫وﺳﺎﺣﺎول ﻻﺣﻘﺎ ﺗﻔﺻﯾل ﻛل ﻣن اﻟﻔﻘرات اﻋﻼﻩ‬

‫‪ -١‬اﻟﺣدﯾد اﻟﻛﻬرﺑﺎﺋﻲ ‪:‬‬


‫ﯾﻌﺗﺑر اﻟﺣدﯾد اﻟﻛﻬرﺑﺎﺋﻲ ﻣن اﻟﻧوع ‪CGOS (Cold Rolled Grain Oriented Silicon‬‬
‫‪ (Steel‬اﻟﻧوع اﻻﻛﺛر ﺷﯾوﻋﺎ ﻓﻲ اﯾﺎﻣﻧﺎ اﻟﺣﺎﺿرة ﻟﻼﺳﺗﺧدام ﻓﻲ ﺻﻧﺎﻋﺔ اﻟﻣﺣوﻻت ﺑﺎﻟرﻏم ﻣن‬
‫وﺟود اﻧواع اﺧرى وﺑﻣواﺻﻔﺎت اﻋﻠﻰ وﻟﻛن اﺳﺗﺧداﻣﻬﺎ ﻻ زال ﻣﺣدودا ﻣﺛل ) ‪Amorphes , Mu‬‬
‫‪.(****ls , Nicle-Iron‬‬
‫اﻟﺧﺻﺎﺋص اﻟﻣﻣﯾزة ﻟﻠﺣدﯾد اﻟﺳﻠﯾﻛوﻧﻲ اﻟﻣدرﻓل ﻋﻠﻰ اﻟﺑﺎرد ‪ CGOS‬ﺑﺎﻟﻣﻘﺎرﻧﺔ ﻣﻊ اوﻟﻰ اﻧواع‬
‫اﻟﺣدﯾد اﻻﻋﺗﯾﺎدي اﻟﻣﺳﺗﺧدﻣﺔ ﻗدﯾﻣﺎ ﻫﻲ ‪ :‬ﻗﻠﺔ ﺧﺳﺎﺋر اﻟﺗﺧﻠف )‪(hysteresis losses‬‬
‫اﻟﺿﺎﺋﻌﺔ ﺑﺷﻛل ﻗدرة ﺣرارﯾﺔ ﻓﻲ ﺣدﯾد اﻟﻣﺣوﻟﺔ ‪ ،‬ارﺗﻔﺎع اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ ﺑﺎﻟﺣدﯾد ﻣﻣﺎ ﯾﻌﻧﻲ ﻗﻠﺔ‬
‫ﺧﺳﺎﺋر اﻟﺗﯾﺎرات اﻟدواﻣﺔ ‪ ،‬زﯾﺎدة اﻟﻧﻔﺎذﯾﺔ اﻟﻧﺳﺑﯾﺔ )‪ ، (permeability‬اﻟﻔﯾض اﻟﻣﺣﺗث اﻻﻗﺻﻰ‬
‫ﻋﻧد اﻟﺗﺷﺑﻊ ‪ ،‬وﻛذﻟك اﺳﺗﻘرار اﻟﻣواﺻﻔﺎت اﻟﻣﻐﻧﺎطﯾﺳﯾﺔ ﻋﻠﻰ ﻋﻣر ﺣدﯾد اﻟﻣﺣوﻟﺔ ‪.‬‬
‫اﻧواع اﻟﺣدﯾد اﻻﻛﺛر اﺳﺗﺧداﻣﺎ اﻻن ﻫﻲ ﻣن اﻻﺻﻧﺎف )‪ (M3,M4‬ﺣﺳب ﺗﺻﻧﯾف ‪AISI‬‬
‫واﻟﺣرف ‪ M‬ﯾﻌﻧﻲ ان اﻟﺣدﯾد ﻣﻐﻧﺎطﯾﺳﻲ واﻟرﻗم اﻟذي ﯾﻠﯾﻪ ﯾﺗﻌﻠق ﺑﻣﻘدار اﻟﺧﺳﺎرة ﻟﻛل رطل ﻓﻲ‬
‫اﻻﻧواع اﻻوﻟﻰ ﻣن اﻟﺣدﯾد )ﻣﺛﻼ ‪ M4‬ﺣدﯾد ﻣﻐﻧﺎطﯾﺳﻲ ﺑﺧﺳﺎﺋر ‪W/lb at ٠.٤‬‬
‫‪. (1.5T,60Hz‬‬
‫ﯾﺑﺎع ﻫذا اﻟﺣدﯾد ﻋﺎدة ﻋﻠﻰ ﺷﻛل ﺑﻛرات ﺿﺧﻣﺔ ﻋرﺿﻬﺎ ﺣواي اﻟﻣﺗر وﯾﺗم ﺗﻘطﯾﻌﻪ ﺣﺳب‬

‫‪٩٦‬‬
‫اﻟﺣﺎﺟﺔ ﺑﺎﻟﻣﺻﻧﻊ وﺳﻣﻛﻪ ﺣواﻟﻲ )‪ (mm٠.٣‬واﻟﺣدﯾد ﻫذا ﻣﻌزول ﺑطﺑﻘﺔ طﻼء ﻣؤﻛﺳد ﻟﻠﺷرﯾﺣﺔ‬
‫وﻣﻌﺎﻣل اﻟﺗﺟﻣﯾﻊ ﻟﻪ ﻓﻲ اﻟﻣﺣوﻻت ﺑﻌد اﻟﺗﻘطﯾﻊ )‪.(٠.٩٧ -٠.٩٥‬‬

‫‪ -٢‬اﺳﻼك اﻟﻣﻠﻔﺎت ‪ :‬وﺗﻛون ﻣن اﻟﻧﺣﺎس او اﻻﻟﻣﻧﯾوم وﻟﻛن اﻟﻧﺣﺎس ﻫو اﻟﻐﺎﻟب وﺗﻘﺳم‬


‫اﻻﺳﻼك اﻟﻣﺳﺗﺧدﻣﺔ ﺑﺻﻧﺎﻋﺔ ﻣﻠﻔﺎت اﻟﻣﺣوﻻت اﻟﻰ ‪:‬‬
‫• اﺳﻼك داﺋرﯾﺔ )‪ (round‬ﻣﻌزوﻟﺔ ﺑﺎﻟدﻫن )‪ ( enameled round wires‬وﻫﻲ اﻻﻛﺛر‬
‫ﺷﯾوﻋﺎ وﺗﺻﻧف ﺑﺻورة ﻋﺎﻣﺔ ﺣﺳب ﺗﺣﻣﻠﻬﺎ ﻟﻠﺣرارة وﺑﺣﺳب ﻧوع اﻟﻌﺎزل اﻟذي ﺗﻌزل ﺑﻪ ‪.‬‬
‫اﺻﻧﺎف اﻟﺣرارة ﻟﻼﺳﻼك ﻛﻣﺎ ﯾﻠﻲ ‪°٢٠٠، C°١٨٠، C°١٥٥، C°١٣٠، C°١٠٥ ) :‬‬
‫‪( C°٢٤٠ ،C‬‬
‫• اﺳﻼك ﻣﺳﺗطﯾﻠﺔ )‪ (rectangular wires‬وﺗﻛون اﯾﺿﺎ ﻣﻌزوﻟﺔ ﺑﺎﻟدﻫن )‪(enameled‬‬
‫وﻟﻬﺎ ﺧﺻﺎﺋص اﻻﺳﻼك اﻟداﺋرﯾﺔ ‪.‬‬
‫• اﺳﻼك ﻣﺳﺗطﯾﻠﺔ ﻣﻌزوﻟﺔ ﺑورق اﻟﻌزل وﺑﻌض ﻣواﺻﻔﺎﺗﻬﺎ ﻛﻣﺎ ﯾﻠﻲ‬
‫‪Conductor Dimensions‬‬
‫• ‪Thickness : 1.0mm - 0.8mm‬‬
‫• ‪mm٣٠.٠ - Width : 2.5mm‬‬
‫• رﻗﺎﺋق )‪ (foils‬او ﺑﻛرات )‪(Rolls‬‬
‫وﻫﻲ ﻋﺑﺎرة ﻋن ﺷراﺋﺢ ﺑﻛرات ﻣن اﻟﺷراﺋﺢ ﺗﺗراوح اﺳﻣﺎﻛﻬﺎ ﺑﯾن )‪ (mm ٠.٣-٠.٠٥‬اﻣﺎ‬
‫اطواﻟﻬﺎ ﻓﻔﻣﻛن ان ﺗﺻل اﻟﻰ اﻟﻣﺗر اﻣﺎ اﻟﺑﻛرات ﻓﺎﺳﻣﺎﻛﻬﺎ ﺗﺗراوح ﻣﺎﺑﯾن )‪ (mm ٣-٠.١‬وطوﻟﻬﺎ‬
‫)‪ (mm ١٢٠٠-٢٠٠‬وﯾﺗم ﻋﻧد ﻟﻔﻬﺎ ﺑﺎﻟﻣﺣوﻻت ادراج ورق اﻟﻌزل ‪.‬‬

‫‪ -٣‬اﻟﻌوازل ‪:‬‬
‫ﻣن اﻟﻣواد اﻻوﻟﯾﺔ اﻟداﺧﻠﺔ ﺑﺻﻧﺎﻋﺔ اﻟﻣﺣوﻻت ﻫﻲ اﻟﻌوازل اﻟﻣﺧﺗﻠﻔﺔ اﻟﻣﺳﺗﺧدﻣﺔ ﻻﻏراض اﻟﻌزل‬
‫اﻟﻣﺧﺗﻠﻔﺔ داﺧل اﻟﻣﺣوﻟﺔ ‪ ،‬ﺑﻌض ﻫذﻩ اﻟﻌوازل ورﻗﯾﺔ او ﻗد ﺗﻛون طﺑﻘﺎت ﻣن اﻟورق اﻟﻣﻘوى وﻗد‬
‫ﺗﺎﺧذ اﺷﻛﺎﻻ ﻣﺧﺗﻠﻔﺔ ﻣﺛل اﺷﻛﺎل ﻣﺟﺎري اﻟزﯾت واﻻﺷﻛﺎل اﻻﺳطواﻧﯾﺔ وﻏﯾرﻫﺎاﻟﻛﺛﯾر ‪.‬‬
‫ﯾﻣﻛن ﺗﻘﺳﯾم اﻧواع اﻟﻌوازل اﻟﻰ ‪:‬‬
‫‪ -١‬ﻋوازل ﻣن اﻟﺧﺷب اﻟﻣﺿﻐوط )‪(Densified Wood‬‬
‫‪ -٢‬ﻋوازل ورق ﻣﺿﻐوط واﻟواح ﻣﺿﻐوطﺔ )‪(Presspaper & Pressboard‬‬
‫‪ -٣‬اﻟورق واﻻﻟواح اﻟﻣﺿﻐوطﺔ اﻻرﻣﯾدﯾﺔ )‪(Pressboard & Aramid Presspaper‬‬
‫‪ -٤‬ﻋوازل ﻣرﻧﺔ‬
‫وﻟﻠﻌوازل اﺻﻧﺎف ﻣﻘﺳﻣﺔ ﺑﺎﻻﻋﺗﻣﺎد ﻋﻠﻰ اﻟﺣرارة اﻟﺗﻲ ﺗﺗﺣﻣﻠﻬﺎ ﻣﻧﻬﺎ‬

‫‪٩٧‬‬
‫‪(C°١٠٥) Class A ‬‬
‫‪(Class B (130°C ‬‬
‫‪(Class F (155°C ‬‬
‫‪(C°١٨٠) Class H ‬‬
‫ﻫﻧﺎك اﻧواع ﻟﻣﺎرﻛﺎت ﻣﺳﺟﻠﺔ ﻟورق اﻟﻌزل اﻟﻣﺳﺗﺧدم ﻟﻌزل اﻟﺷراﺋﺢ واﻟﻣﻘﺎطﻊ اﻟﻣوﺻﻠﺔ‬
‫اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺻﻧﻊ اﻟﻣﻠﻔﺎت ﺑﻌﺿﻬﺎ ﻟﻪ ﺧﺻﺎﺋص ﻣﺳﺎﻣﯾﺔ ﺗؤﻫﻠﻪ ﻻﻣﺗﺻﺎص اﻟزﯾت واﻋطﺎء‬
‫ﺧﺻﺎﺋص ﻋزل ﻣﻣﺗﺎزة ﻟﻣﺣوﻻت اﻟزﯾت ‪ ،‬واﻟﺑﻌض اﻻﺧر ﯾﺳﺗﻌﻣل ﻣﻊ اﻟﻣﺣوﻻت اﻟﺟﺎﻓﺔ وﻫذﻩ‬
‫ﺑﻌض ﻣﻧﻬﺎ ‪:‬‬
‫• ‪Kraft Paper‬‬
‫• ‪Thermally upgraded paper‬‬
‫• ‪Crepe paper‬‬
‫• ‪Lumirror‬‬
‫• ‪Nomex‬‬

‫‪ -٤‬زﯾت اﻟﻌزل ‪:‬‬


‫ﯾﺳﺗﺧدم زﯾت اﻟﺗﺑرﯾد ﻓﻲ اﻟﻣﺣوﻟﺔ ﻟﻐﺎﯾﺗﯾن اﺳﺎﺳﯾﺗﯾن وﻫﻣﺎ زﯾﺎدة اﻟﻌزل اﻟﻛﻬرﺑﺎﺋﻲ ‪ ،‬وﻟﺗﺑرﯾد‬
‫اﻟﻣﺣوﻟﺔ ‪ .‬وﯾﺟب ﻋﻠﻰ اﻟزﯾت ذو اﻟﻧوﻋﯾﺔ اﻟﺟﯾدة ان ﯾﻣﺗﻠك ﺧﺻﺎﺋص ﻓﯾزﯾﺎﺋﯾﺔ وﻛﯾﻣﯾﺎﺋﯾﺔ ﻣﺳﺗﻘرة‬
‫‪ ،‬ﺣﯾث ان اﻟﺗﻐﯾ ارت اﻟﻛﯾﻣﯾﺎﺋﯾﺔ ﻏﯾر اﻟﻣﺳﺗﻘرة ﺗﺳﺑب ﺗﻛوﯾن اﻟﺣﺎﻣﺿﯾﺔ اﻟﻌﺿوﯾﺔ واﻟﺗرﺳﺑﺎت ﻓﻲ‬
‫اﻟزﯾت ‪ .‬ﻓﻲ ﺣﯾن ان اﻟرطوﺑﺔ واﻟﻣﺎء اﻟوﺟود ﺑﺎﻟزﯾت و اﻟﻣواد اﻟﻛﺎرﺑوﻧﯾﺔ ﺗﺳﺑب اﻧﺧﻔﺎض‬
‫ﻣواﺻﻔﺎت اﻟﻌزل اﻟﻛﻬرﺑﺎﺋﻲ ﻟﻠزﯾت ‪.‬‬
‫ﻣن اﻟﺧﺻﺎﺋص اﻟﺗﻲ ﯾﺟب اﻻﻧﺗﺑﺎﻩ ﻋﻠﯾﻬﺎ ﻋﻧد اﺧﺗﯾﺎر اﻟزﯾت ﻫﻲ درﺟﺔ اﻟﻠزوﺟﺔ ) ‪kinematic‬‬
‫‪ ، (viscosity‬درﺟﺔ اﻟﺗوﻫﺞ )‪ ،(flash point‬درﺟﺔ اﻻﻧﺳﻛﺎب )‪ ، (pour point‬ﺗﺣﻣﻠﯾﺔ‬
‫اﻟﻌزل )‪ ، (dielectric strength‬ﻣﻘدار ‪ tan delta‬ﻟﻠزﯾت وﻣﻘدار رﻗم اﻟﺗﻌﺎدل ) ‪mg‬‬
‫‪. (KOH‬‬
‫ﻫﻧﺎك اﻧواع ﻋدﯾدة اﻻن ﻣن زﯾوت اﻟﻌزل اﻟﺗﻲ ﺗﺳﺗﺧدم ﻟﺗﺑرﯾد وﻋزل اﻟﻣﺣوﻻت ﻫذﻩ ﺑﻌض‬
‫اﻧواﻋﻬﺎ ‪:‬‬
‫‪ : Mineral Oil‬وﻫﻲ اﻟزﯾوت اﻻﻛﺛر اﺳﺗﺧداﻣﺎ اﻻن وﺗﺳﺗﺧرج ﻣن اﻟﺗﻛرﯾر ﻟﻠﻧﻔط اﻟﺧﺎم وﻟﻪ‬
‫ﺧﺻﺎﺋص ﻋزل ﻛﻬرﺑﺎﺋﻲ ﻣﻣﺗﺎزة وﻣﺳﺗﻘر ﻟﻣدى ﺟﯾد ﻣن درﺟﺎت اﻟﺣرارة درﺟﺔ ﺗوﻫﺟﻪ ﺣواي‬
‫‪ ١٤٠‬درﺟﺔ ﻣﺋوﯾﺔ‬

‫‪٩٨‬‬
‫‪ : Silicon Oil‬وﻫﻲ زﯾوت ﻏﯾر ﺳﺎﻣﺔ اﻣﯾﻧﺔ وﻣﺳﺗﻘرة ﻟدرﺟﺎت ﺣرارة واﺳﻌﺔ وﻣﻘﺎوﻣﺔ ﻟﻠﺗﺎﻛﺳد‬
‫وﻟﻬﺎ ﺧﺻﺎﺋص ﺟﯾدة ‪.‬‬
‫‪ : Natural Ester‬وﻫﻲ زﯾوت ﻧﺑﺎﺗﯾﺔ ﻻﺗﺣﺗوي اي ﻣواد ﻫﺎﻟوﺟﯾﻧﯾﺔ او ﺑﺗروﻟﯾﺔ او ﺳﻠﯾﻛوﻧﯾﺔ‬
‫وﻫﻲ ﻏﯾر ﺳﺎﻣﺔ ﻟﻬﺎ درﺟﺎت ﺗوﻫﺞ ﻋﺎﻟﯾﺔ )ﺣواي ‪ ٣٣٠‬درﺟﺔ( وﺑﺳﺑب طﺑﯾﻌﺗﻬﺎ ﻟﻬﺎ ﺧﺻﺎﺋص‬
‫ﺻدﯾﻘﺔ ﻟﻠﺑﯾﺋﺔ وﺗﻌﺗﺑر اﻛﺛر اﻣﺎﻧﺎ ﻣن ﻧﺎﺣﯾﺔ اﻻﺣﺗراق وﻣن اﻟﻧﺎﺣﯾﺔ اﻟﻛﯾﻣﯾﺎﺋﯾﺔ‪.‬‬

‫‪ -٥‬ﻣﺂﺧذ اﻟﺗﯾﺎر )‪: (Terminals‬‬


‫ﺗﺗم ﺗوﺻﯾﻼت اﻟﺗﻐذﯾﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻟﻣﻠﻔﺎت اﻟﻣﺣوﻟﺔ ﻋﺑر ﺗﺷﻛﯾﻼت ﻣﻌﯾﻧﺔ ﺗﺳﻣﻰ اﻟﺑوﺷﻧﺞ‬
‫)‪ ، (bushing‬وﺣﺳب ﺗﺻﻣﯾم اﻟﻣﺣوﻟﺔ ‪ .‬ﯾﺗم ﺗوﺻﯾل اﻟﻣﺣوﻟﺔ ﻋﺑر ﻧوﻋﯾن رﺋﯾﺳﯾﯾن واﺣد‬
‫ﻟﻠﻣﺂﺧذ اﻟﻣﻛﺷوﻓﺔ واﻻﺧر ﻟﻠﻣﺂﺧذ اﻟﻣﻐطﺎة ﺑﺻﻧدوق ﺗوﺻﯾل اﻟﻧﻬﺎﯾﺎت ‪.‬‬

‫اﻧواع اﻟﺑوﺷﻧﺟﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ اﻟﺗوﺻﯾﻼت اﻟﻣﻛﺷوﻓﺔ واﻟﻣﻐطﺎة ﻫﻲ ‪:‬‬

‫• اﻟﻧوع اﻻول ﻓﯾﻪ ﻗﺿﯾب اﻟﺗوﺻﯾل ﻣﻠﺣوم ﻟﻧﻬﺎﯾﺔ اﻟﻣﻠف ‪ ،‬وﯾﺧﺗرق اﻟﺗوﺻﯾل اﻟﺑورﺳﻠﯾن‬
‫اﻟﻣﺛﻘوب ﻣن اﻟوﺳط ﻟﯾوﻓر ﻣﻧﻔذا ﻟﻠﺗﯾﺎر ﻓﻲ ﻧﻬﺎﯾﺗﻪ ﻣﻌزوﻻ ﻋن اﻟﺟﺳم اﻟﻣﺣﯾط ﺑﻪ ‪ .‬ﺗﺛﺑت ﻧﻬﺎﯾﺔ‬
‫اﻟﻘﺿﯾب ﺑﺎﻟﺑورﺳﻠﯾن ﻋﺑر ﻏﺷﺎء ﻛﺎزﻛﯾت ﻟﻣﻧﻊ اﻟزﯾت ﻣن اﻟﺗﺳرب وﯾﺗم ﺷد اﻟﻧﻬﺎﯾﺎت ﺑﺑراﻏﻲ‬
‫ﺗوﺻﯾل‬
‫• اﻟﻧوع اﻟﺛﺎﻧﻲ ﯾﻛون ﻓﯾﻪ اﻟﺑوﺷﻧﺞ اﻟﺑورﺳﻠﯾﻧﻲ واﻟﻣوﺻﻼت ﻣﺻﺑوﺑﺔ وﯾﺗم اﺟراء اﻟﺗوﺻﯾل‬
‫ﻟﻠﻣﻠﻔﺎت واﻟﻘﺎﺑﻠوات ﻋﺑر ﺑراﻏﻲ وﺻﺎﻣوﻻت ﻣرﺑوطﺔ ﻓﻲ طرﻓﻲ اﻟﺗوﺻﯾل ﻟﻠﺑوﺷﻧﺞ‬
‫• اﻟﻧوع اﻻﺧﯾر ﻋﺑﺎرة ﻋن ﻧﺎﻗل ﺗﯾﺎر )‪ (bus bar‬ﻣﺻﺑوب ﺑﺎﻻﯾﺑوﻛﺳﻲ وﯾﺳﺗﻌﻣل ﻣﻊ ﻧوع‬
‫اﻟﻣﺣوﻻت اﻟﻣوﺻﻠﺔ ﻋﺑر ﺻﻧدوق ﺗﻐطﯾﺔ ‪.‬‬

‫‪ -٦‬ﻣﻐﯾرات اﻟﺟﻬد )‪: (tap changer‬‬


‫وﻫﻲ ﻧوﻋﯾن‬
‫• ‪Circuit Tap Changer Off‬‬
‫وﻣن ﺗﺳﻣﯾﺗﻬﺎ ﻫﻲ اﻟﻧوع اﻟذي ﯾﻣﻛن اﺟراء ﻋﻣﻠﯾﺔ ﺗﻐﯾﯾر ﻣﺂﺧذ اﻟﻣﻠﻔﺎت ﻟﻠﻣﺣوﻟﺔ ﻋﻧد اطﻔﺎء‬
‫اﻟﻣﺣوﻟﺔ وﻋﻣﻠﯾﺔ اﻟﺗﻐﯾﯾر ﺗﺗم ﯾدوﯾﺎ ‪ ،‬ﻫذا وﯾﻛون ﻣﻐﯾر اﻟﺟﻬد داﺧل اﻟزﯾت ﻋﻧد اﻟﺗرﻛﯾب ‪ .‬وﻫذا‬
‫اﻟﻧوع ﯾﺳﺗﺧدم ﻋﺎدة ﻣﻊ ﻣﺣوﻻت اﻟﺗوزﯾﻊ وﯾوﺟد ﻣﻧﻪ ﻣن ﯾﻌﻣل ﻋﻠﻰ )‪ ٢٠‬او ‪ ٣٠‬ﻛﯾﻠوﻓوﻟت(‬
‫وﯾﺗﺣﻣل ﺗﯾﺎرات )‪ ١٠،٣٠،٦٠‬اﻣﺑﯾر( وﯾوﺟد ﻣﻧﻪ ﻣﺎﯾﺗﻐﯾر ﺑﯾن)‪ ٧-٣‬ﺧطوات( وﻟﻬذا اﻟﻧوع‬

‫‪٩٩‬‬
‫اﺷﻛﺎل ﻣﺗﻧوﻋﺔ ‪.‬‬
‫• ‪Changer On Circuit Tap‬‬
‫وﻫذا اﻟﻧوع اﻻﺧر ﻣن ﻣﻐﯾرات اﻟﺟﻬد ﯾﻣﻛن ﻓﯾﻪ ﺗﻐﯾﯾر اﻟﺟﻬد واﻟﻣﺣوﻟﺔ ﺑﺣﺎﻟﺔ اﻻﺷﺗﻐﺎل وﻟﻣﻧﻊ‬
‫ﺣﺻول اﻟﺷرارة ﯾﺟب وﺟود زﯾت ﻓﻲ ﺻﻧدوق ﻣﻐﯾر اﻟﺟﻬد ‪ .‬وﯾﻛون ﻫذا اﻟﻧوع ﻣن ﻣﻐﯾرات اﻟﺟﻬد‬
‫اﻣﺎ ﻣﺳﺗﻘﻼ ﻣﻌزوﻻ ﻋن ﺧزان اﻟﻣﺣوﻟﺔ او ﯾﻧﺻب ﺑﺧزان اﻟﻣﺣوﻟﺔ وﻫﻧﺎك ﻣﺣرك ﯾﻘوم ﺑﻌﻣﻠﯾﺔ‬
‫ﺗﻐﯾﯾر اﻟﺟﻬد ‪.‬‬

‫‪ -٧‬اﻻﺟﻬزة اﻟﻣﻠﺣﻘﺔ ‪:‬‬


‫وﻫﻲ ﻣﺟﻣوﻋﺔ ﻣن اﻻﻻت واﻟﻣﻌدات اﻟﻣﺗﺧﺻﺻﺔ اﻟﺗﻲ ﺗﺻﻧﻊ ﻓﻲ ﻣﻌﺎﻣل ﺧﺎﺻﺔ وﻗﺳم ﻣﻧﻬﺎ ﯾرﺑط‬
‫ﺣﺳب اﻟطﻠب وﺗﺳﺗﺧدم ﻟﻣراﻗﺑﺔ ﺣﺎﻟﺔ اﻟﻣﺣوﻟﺔ وﺣﻣﺎﯾﺗﻬﺎ واﻧواﻋﻬﺎ ‪:‬‬
‫• ‪Air Dehumidifier‬‬
‫• ‪Relay Bochholz‬‬
‫• ‪Flaw Gauges‬‬
‫• ‪Gas Density Monitor‬‬
‫• ‪Detector Integrated Safety‬‬
‫• ‪Oil Level Indicator‬‬
‫• ‪Pressure Monitor‬‬
‫• ‪Valves Pressure Relief‬‬
‫• ‪Rapid Pressure Rise Relay‬‬
‫• ‪Temperature Control Unit‬‬

‫‪ -٨‬اﻟﻣواد اﻟﻣﺗﻌﻠﻘﺔ ﺑﺧزان اﻟﺗﺑرﯾد ﻓﻲ اﻟﻣﺣوﻻت اﻟزﯾﺗﯾﺔ واﻟﻘطﻊ اﻟﻣرﺑوطﺔ ﻣﻌﻪ ‪:‬‬
‫وﻫﻲ ﻣواد ﻛﺛﯾرة ﺗﺷﻣل اوﻻ اﻟﺣدﯾد اﻟﻼزم ﻟﺻﻧﻊ ﺧزان اﻟﺗﺑرﯾد واﻟﺧزان اﻻﺣﺗﯾﺎطﻲ وﺻﻧدوق‬
‫ﺗوﺻﯾﻼت اﻟﻣﺣوﻟﺔ واﻟذي ﯾﺻﻧﻊ ﻣن اﻟواح اﻟﺣدﯾد اﻟﺻﻠب )‪ (plate steel‬وﺑﺎﺳﻣﺎك ﻣﺧﺗﻠﻔﺔ‬
‫ﺣﺳب اﻟﺗﺻﻣﯾم ‪ ،‬وﻫﻧﺎك اﯾﺿﺎ ﻣﻘﺎطﻊ ﺣدﯾدﯾﺔ ﺑﺎﺷﻛﺎل ﻣﺗﻧوﻋﺔ ﻣﺛل ‪ chanels U‬وﺑراﻏﻲ ﺷد‬
‫وﺻﺎﻣوﻻت ﻻﺣﻛﺎم رﺑط اﻟﺣدﯾد اﻟﻛﻬرﺑﺎﺋﻲ وﻟﻌﻣل ﻗﺎﻋدة اﻟﺟزء اﻟﻔﻌﺎل ﻣن اﻟﻣﺣوﻟﺔ وﻟﺻﻧﺎﻋﺔ‬
‫ﺣﻠﻘﺎت اﻟرﻓﻊ ﻟﻠﻣﺣوﻟﺔ )‪ (lifting lugs‬وﺑﻛرات ارﺟل اﻟﻣﺣوﻟﺔ اﻟﺣدﯾدﯾﺔ‪.‬‬
‫وﻟﻌﻣﻠﯾﺔ ﻟﺣﺎم اﻟﺧزان وﺗﻘطﯾﻊ ﻗطﻊ اﻟﺣدﯾد اﻟﻣﺧﺗﻠﻔﺔ ﻧﺣﺗﺎج ﻏﺎزات ﺻﻧﺎﻋﯾﺔ ﻣﺛل اﻻرﻛون‬
‫واﻻوﻛﺳﺟﯾن واﻟﻣﺳﺗﺧدﻣﺔ ﻟﻌﻣﻠﯾﺔ اﻟﻠﺣﺎم واﻟﻘطﻊ وﻛذﻟك اﺳﻼك ﻟﺣﺎم ‪.‬‬

‫‪١٠٠‬‬
‫وﻫﻧﺎك اﯾﺿﺎ ﻣرﺗﺑط ﺑﺎﻟﺧزان اﻧﺎﺑﯾب ﻣﻌدﻧﯾﺔ ﺑﺎﻗطﺎر ﻣﺧﺗﻠﻔﺔ وﻓﻠﻧﺟﺎت وﺻﻣﺎﻣﺎت اﻟﻘﻔل اﻟﻣﯾﻛﺎﻧﯾﻛﯾﺔ‬
‫ﻟﻼﻧﺎﺑﯾب واﻟﺗﻲ ﻋن طرﯾﻘﻬﺎ ﯾﺗم اﻣﻼء وﺗﻔرﯾﻎ اﻟﻣﺣوﻻت ﻣن اﻟزﯾت ‪.‬‬
‫وﻟﻠﻣﺳﺎﻋدة ﻋﻠﻰ اﺣﻛﺎم ﻗﻔل اﻟﺧزان ﻧﺣﺗﺎج اﻟﻰ اﺷﻛﺎل ﻣﺧﺗﻠﻔﺔ ﻣن اﻟﻣطﺎط اﻟﺻﻧﺎﻋﻲ اﻟﻣﺳﻣﻰ‬
‫)‪ (neoprene casket‬ﻓﻲ ﻣﻧﺎطق اﻻﻗﻔﺎل ﻟﻠﺑوﺷﻧﺟﺎت واﻟﻐطﺎء اﻟﻌﻠوي ﻟﻠﺧزان واي ﻣﻧﻔذ ﻣﺎﺑﯾن‬
‫ﺟﺳم اﻟﻣﺣوﻟﺔ اﻟﺧﺎرﺟﻲ واﻟﺟزء اﻟﻔﻌﺎل ‪.‬‬
‫وﻓﻲ اﻟﻣﺣوﻻت اﻟﺿﺧﻣﺔ ﻗد ﺗﺣﺗﺎج اﻟﻰ ﻣراوح ﻫواء ﻟﺗﺑرﯾد اﻟﺧزان او ﻣﺿﺧﺎت ﻟﺗدوﯾر اﻟزﯾت‬
‫ﻗﺳرﯾﺎ ‪.‬‬
‫واﺧﯾ ار ﻻﻧﻧﺳﻰ اﻻﺻﺑﺎغ اﻟﺗﻲ ﺗطﻠﻰ ﺑﻬﺎ اﻟﻣﺣوﻟﺔ ﺑﻌد اﻛﻣﺎل ﺗﺻﻧﯾﻊ اﻟﺧزان ‪ ،‬وﻟوﺣﺔ ﺗﻌﻠﯾم‬
‫اﻟﻣﺣوﻟﺔ )‪ (plate name‬اﻟﻣطﺑوﻋﺔ ﻋﻠﻰ اﻟﺣدﯾد وﻓﯾﻬﺎ ﻣواﺻﻔﺎت اﻟﻣﺣوﻟﺔ‪.‬‬

‫ﺗﺻﻣﯾم اﻟﻣﺣوﻻت‬
‫ﯾﺗم ﺗﺣدﯾد ﺳﻌﺔ ﻣﺣول اﻟﺗوزﯾﻊ اﻟﻼزم ﻟﺗﻐذﯾـﺔ اﻟﻣﻧﺷـﺄة ﺑﻧـﺎ ًء ﻋﻠـﻰ أﻗﺻـﻰ طﻠـب‬ ‫)أ(‬
‫ﻛﻬرﺑﻲ ﻣﺗوﻗﻊ ﻟﻬذﻩ اﻟﻣﻧﺷﺄة وذﻟك طﺑﻘﺎً ﻟﻣﺎ ﯾﻠﻲ‪:‬‬
‫ﺳــﻌﺔ اﻟﻣﺣــول=‪ ×١.٢٥‬أﻗﺻــﻰ طﻠــب ﻛﻬرﺑــﻲ )ك‪.‬ف‪.‬أ( )ﺑﻣﻌﻧــﻰ أن اﻟﻣﺣــول‬
‫ﯾﺣﻣل ﻓﻘط ﺑـ ‪ ٪٨٠‬ﻣن ﺳﻌﺗﻪ(‬
‫)ب( ﺗﻛــون اﻟﺣــدود اﻟﻣﺳــﻣوح ﺑﻬــﺎ ﻟﻼرﺗﻔــﺎع ﻓــﻲ درﺟــﺔ ﺣـرارة ﻣﺣــوﻻت اﻟﺗوزﯾــﻊ ﻋﻧــد‬
‫ﺗﺣﻣﯾﻠﻬــﺎ ﺑﺎﻟﺳــﻌﺔ اﻹﺳــﻣﯾﺔ ﻟﻬــﺎ ﺑﺻــﻔﺔ ﻣﺳــﺗﻣرة )ﻟﻣــدة ﻻ ﺗﻘــل ﻋــن ‪ ٦‬ﺳــﺎﻋﺎت(‬
‫ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻰ‪:‬‬
‫)‪ (١‬ﯾﺟــب أﻻ ﯾﺗﺟــﺎوز اﻻرﺗﻔــﺎع ﻓــﻲ درﺟــﺔ ﺣ ـرارة اﻟزﯾــت أﻋﻠــﻰ ﺧ ـزان اﻟﺗﻣــدد‬
‫‪ ْ٤٥‬م‪.‬‬
‫ﯾﻛون ﻣﺗوﺳط اﻻرﺗﻔﺎع ﻓﻲ درﺟﺔ ﺣرارة اﻟﻣﻠﻔﺎت )واﻟﺗﻲ ﺗﻘﺎس ﻋن طرﯾق‬
‫ﻗﯾﺎس ﻣﻘﺎوﻣﺔ اﻟﻣﻠﻔﺎت( ‪°٦٠‬م‪.‬‬
‫)‪ (٢‬ﻻ ﯾﺟب أن ﺗرﺗﻔﻊ درﺟﺔ ﺣرارة اﻟزﯾت ﻓﻰ ﺧزان اﻟﺗﻣدد وﻛذﻟك اﻟﺗوﺻﯾﻼت‬
‫اﻟﻛﻬرﺑﯾﺔ ﺑﺣﯾث ﻻ ﺗﺳﺑب ﺿر ارً ﻋﻠﻰ اﻟﻣﺣﯾط اﻟﺧﺎرﺟﻲ‪.‬‬
‫وﯾــﺗم ﻋﻣوﻣ ـﺎً إﺗﺑــﺎع اﻹرﺷــﺎدات اﻟﺧﺎﺻــﺔ ﺑﺎﻟﻣﺻــﻧﻊ ﻓــﻲ ﺗرﻛﯾــب وﺗﺷــﻐﯾل‬
‫اﻟﻣﺣول‪.‬‬

‫ﺗﺣدﯾد ﺳﻌﺔ ﻣﺣول اﻟﺗوزﯾﻊ‬


‫ﺗﺑرﯾد اﻟﻣﺣوﻻت‬ ‫)أ(‬

‫‪١٠١‬‬
‫ﯾﺣـدد اﻟﻣﺻــﻧﻊ طرﯾﻘـﺔ ﺗﺑرﯾــد اﻟﻣﺣـول‪ ،‬ﺑﺎﺳــﺗﺧدام أرﺑـﻊ ﺣــروف‪ ،‬ﯾرﻣـز اﻟﺣرﻓــﺎن‬
‫اﻷوﻻن إﻟﻲ اﻟﻣواﺋﻊ اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺗﺑرﯾد اﻟﻣﻠﻔﺎت داﺧل اﻟﻣﺣول‪ ،‬ووﺳﯾﻠﺔ دﻓﻊ‬
‫ﻫذﻩ اﻟﻣواﺋـﻊ‪ ،‬و ﯾرﻣـز اﻟﺣرﻓـﺎن اﻵﺧـران إﻟـﻲ اﻟﻣواﺋـﻊ اﻟﻣﺳـﺗﺧدﻣﺔ ﻟﺗﺑرﯾـد ﺟﺳـم‬
‫اﻟﻣﺣــول ﻣــن اﻟﺧــﺎرج‪ ،‬ووﺳــﯾﻠﺔ دﻓــﻊ اﻟﻣواﺋــﻊ‪ ،‬و ﯾﺣﺗــوي اﻟﺟــدول ﻋﻠــﻲ اﻟرﻣــوز‬
‫اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﻫذا اﻟﻧظﺎم‬

‫ﺟدول ﺗوﺿﯾﺣﻲ ﻟﻠﺣروف اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﻫذا اﻟﻧظﺎم‬

‫اﻟرﻣز‬ ‫ﺳرﯾﺎن اﻟﻣﺎﺋﻊ‬ ‫اﻟرﻣز‬ ‫اﻟﻣﺎﺋﻊ اﻟﻣﺑرد‬


‫زﯾـــت ﻣﻌـــدﻧﻲ أو زﯾـــت اﺻـــطﻧﺎﻋﻲ درﺟـــﺔ‬
‫‪N‬‬ ‫طﺑﯾﻌﻲ‬ ‫‪O‬‬
‫ﺣرارة اﺷﺗﻌﺎﻟﻪ ≥‪ °٣٠٠‬م‬
‫‪L‬‬ ‫زﯾوت اﺻطﻧﺎﻋﯾﺔ أﺧري‬
‫‪G‬‬ ‫ﻏﺎز و درﺟﺔ ﺣرارة إﺷﺗﻌﺎﻟﻪ ≥‪ °٣٠٠‬م‬
‫‪F‬‬ ‫اﺻطﻧﺎﻋﻲ‬
‫‪A‬‬ ‫ﻫواء‬
‫‪W‬‬ ‫ﻣﺎء‬

‫ﻣﺛﺎل‪:‬‬
‫ﻣﺣــول زﯾﺗــﻲ )ﯾﺑــرد داﺧﻠﯾ ـﺎً ﺑﺳــرﯾﺎن اﻟزﯾــت ﺳــرﯾﺎﻧﺎً طﺑﯾﻌﯾ ـﺎً وﯾﺑــرد‬ ‫‪: ONAN‬‬
‫اﻟﺟﺳم ﻣن اﻟﺧﺎرج ﺑﺳرﯾﺎن اﻟﻬواء ﺣوﻟﻪ ﺳرﯾﺎﻧﺎً طﺑﯾﻌﯾﺎً أﯾﺿﺎً(‬
‫أﻗﺻﻰ ﺗﺣﻣﯾل ﯾوﻣﻰ ﻟﻠﺣﻔﺎظ ﻋﻠﻰ ﺳﻼﻣﺔ اﻟﻣﺣوﻻت‬
‫‪Daily Peak Load of Transformer Nameplate Rating to Give Normal‬‬
‫‪Life Expectancy‬‬
‫)‪ (١‬ﯾﻣﻛــن ﺗﺷــﻐﯾل اﻟﻣﺣــوﻻت ﻋﻧــد درﺟــﺎت ﺣــرارة اﻟزﯾــت أﻋﻠــﻰ ﻣــن ‪ ْ٩٥‬م‪،‬‬
‫ﻟﻔﺗرات ﻗﺻﯾرة ﻣﺣددة ﺑدون أن ﺗﺳﺑب ﻣﺧﺎطر ﺗذﻛر ﻋﻠﻰ اﻟﻣﺣول‪ ،‬ﻛذﻟك‬
‫ﯾﻣﻛن ﺗﺷﻐﯾﻠﻬﺎ ﻟﻔﺗرات أطول ﻋﻧد درﺟﺎت ﺣرارة أﻗل ﻣن ‪ ْ٩٥‬م‪.‬‬
‫ﻋﺎدة ﺗﺗﻛـون دورة اﻟﺗﺣﻣﯾـل اﻟﯾـوﻣﻰ )‪ (Daily load‬ﻣـن أﺣﻣـﺎل ﻣﺗﻐﯾـرة‬
‫ﺧــﻼل اﻟﯾــوم‪ ،‬وﯾﻣﻛــن أن ﻧﻘﺳــم اﻟــدورة إﻟــﻰ ﻣراﺣــل ﺑﺣﯾــث ﯾﻛــون اﻟﺣﻣــل‬

‫‪١٠٢‬‬
‫ﺛﺎﺑﺗ ـﺎً ﺗﻘرﯾﺑ ـﺎً ﻓــﻰ ﻛــل ﻣرﺣﻠــﺔ‪ ،‬ﻛﻣــﺎ ﯾﻣﻛــن ﺣﺳــﺎب اﻟﺣﻣــل اﻟﻣﻛــﺎﻓﺊ ﻟــدورة‬
‫اﻟﺗﺣﻣﯾل اﻟﯾوﻣﻰ ﻣن اﻟﻣﻌﺎدﻟﺔ ‪:‬‬

‫‪L12 t1  L22 t2  ....  L2n t n‬‬


‫‪Equivalent load ‬‬
‫‪t1  t2 .............  t n‬‬

‫ﺣﯾث‪:‬‬
‫أﺣﻣﺎل اﻟﻣراﺣل اﻟﻣﺧﺗﻠﻔﺔ‬ ‫‪L1 , L2 , Ln‬‬
‫ﻓﺗرة ﻛل ﻣرﺣﻠﺔ‬ ‫‪t1 , t 2 , t n‬‬
‫)‪ (٢‬ﯾﺟب ﻋﻧد ﺗﺣﻣﯾل اﻟﻣﺣوﻻت ﻋﻧد درﺟﺎت ﺣرارة أﻛﺑر ﻣن ‪ ْ٥٠‬م أﻻ ﺗﺗﻌدى‬
‫ﺣــــدود اﻟﺗﺣﻣﯾــــل ﻓﺗــــرة زﻣﻧﯾــــﺔ ﻣﻌﯾﻧــــﺔ‪ ،‬ﻣﺣــــددة ﺑﺎﻟﻣواﺻــــﻔﺎت اﻟﻘﯾﺎﺳــــﯾﺔ‬
‫اﻟﻌﺎﻟﻣﯾــﺔ‪ ،‬ﺣﺗــﻰ ﻻ ﯾﺗــﺄﺛر اﻟﻣﺣــول وﯾﻘــل ﻋﻣــرﻩ اﻻﻓﺗراﺿ ـﻰ‪ ،‬وﯾﺟــب ﻋﻣــل‬
‫ﺗـوازن ﻟــدورة اﻟﺣﻣــل اﻟﯾــوﻣﻰ‪ ،‬ﺑﺣﯾــث ﯾــﺗم ﺗﺣﻣﯾــل اﻟﻣﺣــول ﺑﺣﻣــل ﺻــﻐﯾر‬
‫ﻟﻔﺗرات أﺧرى‪ ،‬ﺛم ﺗﺣﻣﯾﻠﻪ ﻟﻔﺗرة زﻣﻧﯾﺔ ﺻﻐﯾرة ﺑﺎﻟﺣﻣل اﻟزاﺋد‪ ،‬وﯾﺗم اﻟﻛﺷف‬
‫ﻋﻠــﻰ ﺟﻣﯾــﻊ أﺟــزاء اﻟﻣﺣـــول‪ ،‬ﺑﻌــد ﺗﺷــﻐﯾﻠﻪ ﺑزﯾـــﺎدة ﺣﻣــل )ﻣﺛــل‪ :‬ﻧﻬﺎﯾـــﺔ‬
‫اﻟﻛﺎﺑﻼت – ﻧﻘط اﻟﺗﻘﺳﯾم ‪ ،‬إن أﻣﻛن‪ ،‬ﻋوازل اﻻﺧﺗراق ‪.(....‬‬
‫ﯾوﺿــﺢ اﻟﺟــدول اﻟﺗــﺎﻟﻲ أﻗﺻــﻰ ﺗﺣﻣﯾــل ﯾــوﻣﻰ ﻟﻠﻣﺣــوﻻت ﺑدﻻﻟــﺔ درﺟــﺔ اﻟﺣ ـرارة‬
‫اﻟﻣﺣﯾط ﻟﻠﺣﻔﺎظ ﻋﻠﻰ ﻋﻣرﻫﺎ اﻻﻓﺗراﺿﻰ‪٠‬‬
‫‪Daily peak load of Transformer nameplate rating to give normal life‬‬
‫‪expectancy‬‬

‫‪١٠٣‬‬
‫ﺟدول أﻗﺻﻰ ﺣﻣل ﯾوﻣﻰ ﻛﻧﺳﺑﺔ ﻣن اﻟﺣﻣل اﻟﻣﻘﻧن اﻟﻣذﻛور ﺑﻠوﺣﺔ ﺑﯾﺎن‬
‫اﻟﻣﺣول‪ ،‬ﻟﺣﻔﺎظ ﻋﻠﻰ ﻋﻣر اﻟﻣﺣول‬
‫زﻣﻦ‬
‫أﻗﺼﻰ‬
‫ﺣﻤﻞ‬
‫)ﺳﺎﻋﺔ(‬
‫درﺟﺔ اﻟﺣرارة اﻟﻣﺣﯾطﺔ ) ◌ْ م(‬ ‫درﺟﺔ اﻟﺣرارة اﻟﻣﺣﯾطﺔ ) ◌ْ م(‬ ‫درﺟﺔ اﻟﺣرارة اﻟﻣﺣﯾطﺔ ) ◌ْ م(‬

‫‪١٠٤‬‬
‫اﻟﺗﺣﻣﯾل اﻟزاﺋد ﻟﻠﻣﺣوﻻت‬
‫اﻟﻣﺣوﻻت اﻟﻣﻐﻣورة ﻓﻰ اﻟزﯾت‬ ‫)أ(‬
‫اﻟﺟــدول اﻟﺗــﺎﻟﻲ ﯾﺣﺗــوى ﻋﻠــﻰ ﻗــدرة اﻟﺗﺣﻣﯾــل اﻟزاﺋــد )ﻛﻧﺳــﺑﺔ ﻣــن اﻟﻘــدرة اﻟﻣﻘﻧﻧــﺔ‬
‫ﻟﻠﻣﺣوﻻت اﻟﻣﻐﻣـورة ﻓـﻰ اﻟزﯾـت‪ ،‬طﺑﻘـﺎً ﻟﻠﻣواﺻـﻔﺎت اﻟﻘﯾﺎﺳـﯾﺔ اﻷﻟﻣﺎﻧﯾـﺔ )‪(DIN‬‬
‫ﯾﺟب أﻻ ﺗﺗﻌدى ﻣﺗوﺳط درﺟـﺔ ﺣـرارة اﻟﻣﻠﻔـﺎت ‪ ْ١٠٥‬م‪ ،‬إذا ﻛـﺎن ﻣﺗوﺳـط درﺟـﺔ‬
‫وﺳــط اﻟﺗﺑرﯾــد ﺧــﻼل اﻟــدورة ‪ ْ٢٥‬م‪ ،‬إو ذا ﻛﺎﻧــت اﻟﻣﺣــوﻻت ﻣﺟﻬــزة ﺑﻣـراوح ﺗﺑرﯾــد‬
‫وﻟﻛـــن اﻟﻣـــراوح ﻣﻌزوﻟـــﺔ ﻓﯾﺟـــب أن ﯾﻛـــون اﻟﺗﺣﻣﯾـــل ‪ ٪٦٠‬ﻣـــن اﻟﻘـــدرة اﻟﻣﻘﻧﻧـــﺔ‬
‫ﻟﻠﻣﺣول‪.‬‬

‫ﻓﺗرة زﯾﺎدة اﻟﺣﻣل ﻟﻠﻣﺣوﻻت اﻟﻣﻐﻣورة ﻓﻰ اﻟزﯾت‬

‫ﻣدة اﻟﺗﺣﻣﯾل اﻟزاﺋد ﺑﺎﻋﺗﺑﺎر اﻟﺣﻣل اﻟزاﺋد ﻧﺳﺑﺔ‬ ‫درﺟﺔ ﺣرارة اﻟزﯾتْ م ﻋﻧد‬
‫ﻣن اﻟﻣﻘﻧن‬ ‫ﺑداﯾﺔ زﯾﺎدة اﻟﺣﻣل ﺗﺑﻌﺎً‬ ‫ﻧﺳﺑﺔ اﻟﺗﺣﻣﯾل‬
‫ﻟﺣﺎﻟﺔ اﻟﺗﺑرﯾد‬ ‫اﻟﺳﺎﺑﻘﺔ ‪ ٪‬ﻣن‬
‫‪٪٥٠‬‬ ‫‪٪٤٠‬‬ ‫‪٪٣٠‬‬ ‫‪٪٢٠‬‬ ‫‪٪١٠‬‬ ‫ﺗﺑرﯾد ﻣﯾﺎﻩ –‬ ‫ﺗﺑرﯾد ﻫواء‬ ‫ﻗﯾﻣﺔ ﻗدرة‬
‫ﺗﺑرﯾد زﯾت‬ ‫طﺑﯾﻌﻰ أو‬ ‫اﻟﻣﺣول‬
‫دﻗﯾﻘﺔ‬ ‫دﻗﯾﻘﺔ‬ ‫دﻗﯾﻘﺔ‬ ‫ﺳﺎﻋﺔ‬ ‫ﺳﺎﻋﺔ‬
‫وﻫواء ﻣدﻓوع‬ ‫ﻣراوح‬
‫‪١٥‬‬ ‫‪٣٠‬‬ ‫‪٦٠‬‬ ‫‪١.٥‬‬ ‫‪٣‬‬ ‫‪٤٩‬‬ ‫‪٥٥‬‬ ‫‪٥٠‬‬
‫‪٨‬‬ ‫‪١٥‬‬ ‫‪٣٠‬‬ ‫‪١‬‬ ‫‪٢‬‬ ‫‪٦٠‬‬ ‫‪٦٨‬‬ ‫‪٧٥‬‬
‫‪٤‬‬ ‫‪٨‬‬ ‫‪١٥‬‬ ‫‪٠.٥‬‬ ‫‪١‬‬ ‫‪٦٨‬‬ ‫‪٧٨‬‬ ‫‪٩٠‬‬

‫)ب( اﻟﻣﺣوﻻت اﻟﺟﺎﻓﺔ‬


‫ﯾوﺿﺢ اﻟﺟدول اﻟﺗـﺎﻟﻲ ﻓﺗـرات زﯾـﺎدة اﻟﺣﻣـل ﻟﻠﻣﺣـوﻻت اﻟﺟﺎﻓـﺔ ذات ﻣـﺎدة ﻋـزل‬
‫ﻣن اﻟدرﺟﺔ )‪ (A‬ﺑﻔرض أن اﻟﻣﻠﻔﺎت اﻻﺑﺗداﺋﯾﺔ ﻣﺑردة ﺑـﺎﻟﻬواء اﻟﻣﺣـﯾط ﻣﺑﺎﺷـرة‪،‬‬
‫ﻟﻠﻣﺣـــوﻻت اﻟﺟﺎﻓـــﺔ ذات ﻣـــﺎدة ﻋـــزل ﻣـــن اﻟدرﺟـــﺔ )‪ (B‬واﻟدرﺟـــﺔ )‪ (E‬ﯾﺳـــﺗﺧدم‬
‫اﻟﺟدول ﻣﻊ ﻣراﻋﺎة أن ﺗﻘل ﻧﺳﺑﺔ اﻟﺗﺣﻣﯾل ﺑﻧﺳﺑﺔ ‪ ٪٩٠ ، ٪٨٥‬ﻋﻠﻰ اﻟﺗواﻟﻰ‪.‬‬

‫‪١٠٥‬‬
‫ﻓﺗرة زﯾﺎدة اﻟﺣﻣل ﻟﻠﻣﺣوﻻت اﻟﺟﺎﻓﺔ ذات ﻋزل درﺟﺔ )‪(A‬‬

‫ﻓﺗرة زﯾﺎدة اﻟﺣﻣل ﻟﻠﻣﺣوﻻت ﻛﻧﺳﺑﺔ ﻣن اﻟﻣﻘدرة‬ ‫ﻧﺳﺑﺔ اﻟﺗﺣﻣﯾل‬


‫اﻟﻣﻘﻧﻧﺔ‬ ‫اﻟﺳﺎﺑﻘﺔ ‪ ٪‬ﻣن‬
‫‪٪٥٠‬‬ ‫‪٪٤٠‬‬ ‫‪٪٣٠‬‬ ‫‪٪٢٠‬‬ ‫‪٪١٠‬‬ ‫ﻗﯾﻣﺔ ﻗدرة‬
‫دﻗﯾﻘﺔ‬ ‫دﻗﯾﻘﺔ‬ ‫دﻗﯾﻘﺔ‬ ‫دﻗﯾﻘﺔ‬ ‫دﻗﯾﻘﺔ‬ ‫اﻟﻣﺣول‬
‫‪١٢‬‬ ‫‪١٥‬‬ ‫‪٢٠‬‬ ‫‪٣٠‬‬ ‫‪٦٠‬‬ ‫‪٥٠‬‬
‫‪٩‬‬ ‫‪١١‬‬ ‫‪١٥‬‬ ‫‪٢٣‬‬ ‫‪٥٥‬‬ ‫‪٧٥‬‬
‫‪٥‬‬ ‫‪٧‬‬ ‫‪١٠‬‬ ‫‪١٦‬‬ ‫‪٤٥‬‬ ‫‪٩٠‬‬

‫إذا ﻛﺎﻧت درﺟﺔ ﺣرارة اﻟﻬواء ﻣﺧﺗﻠﻔﺔ ﻋن اﻟﻘﯾم اﻟﻘﯾﺎﺳﯾﺔ اﻟﻣﺳـﺗﺧدﻣﺔ ﻟﻠﻣﺣـوﻻت‬
‫ﻓﯾﺗم اﻟرﺟوع إﻟﻰ اﻟﺟدول اﻟﺗﺎﻟﻲ ﻟﻠﻣﺣوﻻت اﻟﻣﻐﻣورة ﻓﻰ اﻟزﯾت – ﺗﺑرﯾد اﻟﻬواء‪.‬‬

‫اﻟﺣﻣل اﻟﻣﺳﺗﻣر اﻟﻣﺳﻣوح ﻟﻠﻣﺣوﻻت اﻟزﯾﺗﯾﺔ )ﺗﺑرﯾد ﻫواء(‬


‫ﻋﻧد درﺟﺔ ﺣرارة ﺗﺧﺗﻠف ﻋن اﻟﻘﯾم اﻟﻘﯾﺎﺳﯾﺔ‬

‫‪+‬‬ ‫‪+‬‬ ‫‪-‬‬ ‫‪-‬‬ ‫اﺧﺗﻼف درﺟﺔ ﺣرارة اﻟﻬواء ﻋن‬


‫ﺻﻔر‬
‫‪ ْ٢٠‬م‬ ‫‪ ْ١٠‬م‬ ‫‪ ْ١٠‬م‬ ‫‪ ْ٢٠‬م‬ ‫اﻟﻘﯾﻣﺔ اﻟﻘﯾﺎﺳﯾﺔ‬
‫‪٨١‬‬ ‫‪٩١‬‬ ‫‪١٠٠‬‬ ‫‪١١١‬‬ ‫‪١٢١‬‬ ‫ﺗﺑرﯾد ﻫواء ﻋﺎدى‬ ‫اﻟﻘدرة‬
‫‪٨٣‬‬ ‫‪٩٢‬‬ ‫‪١٠٠‬‬ ‫‪١٠٩‬‬ ‫‪١١٥‬‬ ‫اﻟﻣﺳﺗﺧدﻣﺔ ‪ ٪‬ﺗﺑرﯾد ﻫواء ﺑﺎﻟﻣراوح‬
‫اﺳﺗﺧدام ﻣﺿﺧﺎت‬ ‫ﻣن ﻗﯾﻣﺔ‬
‫‪٨٤‬‬ ‫‪٩٢‬‬ ‫‪١٠٠‬‬ ‫‪١٠٧‬‬ ‫‪١١٥‬‬ ‫اﻟﻘدرة اﻟﻣﻘﻧﻧﺔ‬
‫ﻫواء‬

‫ﻣﻼﺣظﺎت‬
‫‪PILLAR‬‬ ‫‪-١‬‬
‫ﺻﻧدوق اﻟﺗوزﯾﻊ اﻟﻣﻐذى ﻣﺑﺎﺷرة ﻣن اﻟﻣﺣول‬
‫‪COFFREE‬‬ ‫‪-٢‬‬

‫‪١٠٦‬‬
‫اﻟﻠوﺣﺔ اﻟﻣﻐذﯾﺔ ﻟﻠﻣﻧﺷﺄة‬
‫اﻟﻘرار اﻟوزاري‬ ‫‪-٣‬‬
‫ﻫو اﻟﻣﺣور اﻷﺳﺎﺳﻲ ﻟﺗﺻﻣﯾم اﻟﺷﺑﻛﺎت‬

‫‪١٠٧‬‬