٢
→in housing design C.B for saket of lighting or power loads
is minimum 16A.
p*746
Ir =
* p. f *220
p * 746
Ir =
* RF * 3 * 380
٣
- load ‹1.5 mvA
- feed with low voltage (380/220)V from distribution
- feed at low voltage
medium customer
-loads (1.5-5)MVA
-feed from IIKVfeeder (not dedicate) ﯾﻐذي ﻣﺳﺗﻬﻠﻛﯾن اﺧرﯾن
-IIKV feeder feeds other custmers.
-custmer has to provide (11-0.4)KVtransformer
-transformer
Big customer
1. load 5 mva
2. fed by dedicated trans (11-0.4)kv
3. customer large motores loads high power may
promise(11-3.3)kvtrans
ex:
1. Hospital
2. Bigh Industrial Facilitier
3. Large Commercion Confer
Distribution Boards
cu وﻓﻰ ﻣﺻرcu ﻣن اوbusbar ﯾﺻﻧﻊ
Single Line Diagram
٤
A one line digram engineering drawing showing the
elements of adist ribution system of show the rating of all
these elements and how they are interconnect
selective.
Abnormal condition (faults) :
1. short circuit 2.over voltage
3.over load 4.earth leakage
5.under voltage 6.earth fault
short circuit
٥
I=V/Z
I=V/zero=α
↑↑P=I2R↑↑→heat
Over load:
.١ﻣن اﻟﻣﻣﻛن ﺗﺧطﻲ demand factorﻋﻧدﻣﺎ ﯾﻣﻛن ﺗﺷﻐﯾل اﻟﺗﻛﯾﯾﻔﺎت ﻛﻠﻬﺎ ﻓﻲ
وﻗت واﺣد.
.٢ﺑﺎﻟﻧﺳﺑﺔ ﻟل water pumpﺗﺳﺣب ﺗﯾﺎر ﻋﺎﻟﻲ ﻋﻧدﻣﺎ ﯾﺗﺳرب ﺑداﺧﻠﻬﺎ
اﺗرﺑﺔ.
Under Voltage
·····························
)VR=VS-IZF(∆v
∆V= 5%
٦
Over Voltage
اﺳﺑﺎب٣ ﻟــ
1. Lighting اﻟ ﺻواﻋق
2. swiching اﻟﻔﺻل واﻟﺗوﺻﯾل
3. Excess Capacitance
*Swiching
DI
U L =L
DT
Ecess Capacitance
( وinductive load) ﻣﻌظم اﻟﺷﺑﻛﺎت.١
Lag←P.F
P.F ﻧﺿﻊ ﻣﻛﺛﻔﺎت ﻟﺗﺣﺳﯾن.٢
ﺗﻛون ﻋﺎﻟﯾﺔcapacitare ﻋﻧد ﺣدوث ﻋطل او ﺗﺳرﯾب.٣
Earh Leakage
( ﯾؤدى اﻟﻰHumidity & Heat) ﺗﯾﺎر ﯾﺗﺳرب ﻣن اﻟﻣوﺻﻼت ﻓﻰ اﻻرض ﻧﺗﯾﺟﺔ
وﺑﺎﻟﺗﺎﻟﻰ ﯾﺣدث ﺗﺳرﯾب ﺗﯾﺎر اﻟﻰ اﻻرضDeterioration in isulation ←
)ﺗدﻫور
٧
Small leakage currents due to portial failure of
insulation
Earth fault
Complete failure of insulation leads to live
conductors coming in fall contact with earth.
Switching devices
1. circuit breakers
2. laods switch
3. fuse(protection)
4. contactor
5. fuse switch
Circuit Breaker
1. switching
2. protection
1. moving contact :ﻋﺑﺎرة ﻋن ﺟزﺋﯾن
2. fixed contact
switching medium ووﺳط ﻣﺣﺑط
operating mechanism
1. Low voltage circuit breaker.+
2. medium voltage circuit breaker.
٨
ﺗﺣدث ﺷرارة وﯾﺟب اﻟﺗﻐﻠب ﻋﻠﯾﻬﺎ وﻫذا ﻫو2 contacts ﻋﻧد ﻓﺻل
.C.B اﻻﺧﺗﻼف ﺑﯾن اﻧواع
.(breaking capacity)&(rating)اﻟﻣﻔﺗﺎح ﯾﺗﻌرف ﺑﺷﯾﺋﯾن
Low voltage CB→
.air وﺳط اﻟﻔﺻل
1.(thermal/magnetic)trip
٩
one out of two method
١٠
Normal operation:
1. C.B closed feeds load of busbar1
2. C.B2closed feeds load of busbar2
3. C.B3open.
Emergency operation:
1. C.B1 open
2. C.B2 closed
3. C.B3 closed
Feeder 2 feeds emergency loads on busbar(1) and (2).
Stand by generation
(automatic transformer switch) ﯾوﺟد
١١
1. start and synchronizer
ﯾﺟب ان ﻧﺗرﻛﻪ ﻓﺗرة ﻟﻛﻲ ﯾﻌﻣل ﺗزاﻣن ﻣﻊ اﻻﺣﻣﺎل
2. runs ideal
ﻓﻲ اﻟﻣﻧﺷﺄت اﻟﻣﻬﻣﺔ ﯾﻔﺻل وﯾوﺻل وﯾﻛون ﻣﺗزاﻣن وﻣﺎ ﯾﺧﺳرﻩ اﻟﻣﺳﺗﻬﻠك ﻫو اﻟﻘدرة
اﻟﺿﺎﺋﻌﺔ٠
١٢
ELECTRICAL CABLES
١٣
اﻟﻛﺎﺑﻼت اﻟﻛﻬرﺑﯾﺔ
ﻧﺑذة ﺗﺎرﯾﺧﯾﺔ
-١ﺗم اﺳﺗﺧدام اﻟﻛﺎﺑﻼت ﻓﻰ ﻧﻘل اﻟﻛﻬرﺑﺎء ﻋﺎم ١٨٩٠ﻋﻧدﻣﺎ اﺳﺗﺧدم ﻓراﻧﺗﻰ اﻟورق
اﻟﻣﻌدﻧﻰ واﻟﻣوﺿوع ﺣول اﻟﺳطﺢ اﻟﺧﺎرﺟﻰ ﻟﻠﻌزل ﻟﺟﻌل اﻟﻣﺟﺎل اﻟﻛﻬرﺑﻰ داﺧل اﻟﻌزل
ﻧﺻف ﻗطرى.
ﺗﻛون اﻟﻔراﻏﺎت ﻓﻰ اﻟﻌزل واﻟﺗﻰ ﻛﺎﻧت ﺗﺣد ﻣن ﻗﯾﻣﺔ اﻟﺟﻬد اﻟﻣﺳﺗﺧدم ﻓﻲ اﻟﻛﺎﺑﻼت
ﺑﺎﻟورق اﻟﻣﺷﺑﻊ.
-٤اﺧﺗراع اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدم ﻓﻰ ﻧﻘل اﻟطﺎﻗﺔ اﻟﻛﻬرﺑﯾﺔ ﺗﺣت اﻟﻣﺎء ﺑﺎﺳﺗﺧدام اﻟﺗﯾﺎر
اﻟﻣﺳﺗﻣر .
-٥اﺧﺗراع اﻟﻣواد اﻟﺑﻠﻣرﯾﺔ اﻻﺻطﻧﺎﻋﯾﺔ وﺗطوﯾرﻫﺎ ﻛﻣواد ﻋزل ﻟﻠﻛﺎﺑﻼت ﺑدﻻ ﻣن اﻟورق
-٦ﺗطوﯾر ﺗﻘﻧﯾﺔ اﺳﺗﺧدام اﻟﻐﺎز اﻟﻣﺿﻐوط ﻛوﺳط ﻋﺎزل ﺑﯾن اﻟﻣوﺻل واﻟﻐﻼف.
ﺗﻌرﯾف اﻟﻛﺎﺑل
١٤
اﻟﺧطوط ﻫواﺋﻰ اﻟﻛﺎﺑﻼت
-٨ﻋﺎم(1/5)2000
١٥
-١ﻻ ﺗﺗﻌرض اﻟﻛﺎﺑﻼت اﻟﻣدﻓوﻧﻪ ﺗﺣت اﻻرض ﻟﻠﺗﻐﯾرات اﻟﺟوﯾﻪ واﻟﻌواﻣل اﻟطﺑﯾﻌﯾﻪ
-٣ﯾﻣﻛن اﺳﺗﺧدام اﻟﻛﺎﺑﻼت ﻓﻰ رﺑط اﻟﺷﺑﻛﺎت اﻟﻛﻬرﺑﯾﻪ ﻋﺑر اﻻﻧﻬﺎر واﻟﺑﺣﺎر واﻟﻣﻣرات
-٧اﻟدرع .ARMOUR
ﯾﺻﻧﻊ ﻣن ﻣﻌدن ذات ﻣﻘﺎوﻣﺔ ﻛﻬرﺑﯾﺔ ﻣﻧﺧﻔﺿﺔ وﯾﻘوم ﻫذا اﻟﻣوﺻل ﺑدور ﺣﻣل وﺗوﺻﯾل اﻟﺗﯾﺎر
١٦
ﯾﺻﻧﻊ ﻣن ﻣﺎدة ﻋﺎزﻟﺔ ﻛﻬرﺑﯾﺎ .DIELECTRIC
ﻣﻧﻊ ﺧطر اﻟﺗوﺻﯾل ﺑﯾن اﻟﻣوﺻل اﻟﻛﻬرﺑﻲ وأي ﻋﻧﺻر ﻣﺣﯾط ﺑﻪ.
-اﻟﻐرض اﻻﺳﺎﺳﻲ ﻫو اﻟﺗﻘﻠﯾل ﻣن ﻗﯾﻣﺔ اﻟﻣﺟﺎل اﻟﻛﻬرﺑﻲ ﻋﻠﻰ اﻟﺳطﺢ اﻟﻣﺷﺗرك ﺑﯾن اﻟﻣوﺻل
.CARBON PAPER
-١ﻟف اﻟﻣوﺻل ﺑﺷرﯾط ﻣن اﻟﻘﻣﺎش أو اﻟﺑﻼﺳﺗﯾك اﻟﻣﺷﺑﻊ ﺑﺎﻟﻛرﺑون وﺗﺳﺗﺧدم ﻫذﻩ اﻟطرﯾﺔ
١٧
CARBON FIELD ETHYLVINYL ACETATE-EVAا وﻣﻘﺎوﻣﺗﻬﺎ
ﯾﺳﺗﺧدم ﻫذا اﻟﻐﻼف ﻓﻰ ﺟﻣﯾﻊ اﻧواع اﻟﻛﺎﺑﻼت ﺳواء ذات اﻟﻌوازل اﻟورﻗﯾﺔ أو اﻟﺑﻠﻣرﯾﺔ وان
ﯾﺳﺗﺧدم ﻟﺣﻣﺎﯾﺔ اﻟﻛﺑل ﻣن ﺗﺳرب اﻟرطوﺑﻪ اﻟﻰ داﺧﻠﻪ وﯾﺳﺗﺧدم ﻓﻰ ﻛﺎﺑﻼت اﻟﻌوازل اﻟورﻗﯾﻪ
أواﻟﻌوازل اﻟﺑﻠﻣرﯾﻪ ﻋﻠﻰ ﺣد ﺳواء وﯾﻘوم اﻟﻐﻼف ﺑﺣﻣﺎﯾﺔ اﻟﻛﺎﺑﻼت ﺧﺎﺻﺔ ﻛﺎﺑﻼت اﻟﻌوازل
ﻣﺣل اﻟرﺻﺎص ﻓﻰ اﻟﻛﺎﺑﻼت اﻟﺣدﯾﺛﻪ ﻻن اﻻﻟوﻣﻧﯾوم ﻟﻪ ﻣﻣﯾزات ﻣﻘﺎرﻧﺔ ﺑﺎﻟرﺻﺎص ﻣﻧﻬﺎ ﻗﻠﺔ
اﻟوزن ورﺧص اﻟﺛﻣن وﺗوﺻﯾﻠﯾﻪ ﻛﻬرﺑﯾﻪ ﺟﯾدﻩ ﺑﺎﻻﺿﺎﻓﻪ ﻟﻣﻣﯾزات ﻣﯾﻛﺎﻧﯾﻛﯾﻪ اﺧرى اﻫﻣﻬﺎ ان
اﻻﻟوﻣﻧﯾوم ﻻ ﯾﺗﺄﺛر ﺑﺎﻻﻫﺗ اززات اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ ﻣﺛل اﻟﺗﻰ ﻗد ﺗﺗواﺟد ﻋﻠﻰ اﻟﻛﺑﺎرى أو ﺑﺟوار اﻟﺳﻛك
١٨
EARTHED METALLIC اﻟﺣدﯾدﯾﻪ وﯾﺳﺗﺧدم اﻟﻐﻼف ﻛﺷﺑﻛﻪ ﻣﻌدﻧﯾﻪ ﻣؤرﺿﻪ
ﻣن ﻋﯾوب اﻻﻟوﻣﻧﯾوم ﺳﻬوﻟﻪ ﺗﻌرﺿﻪ ﻟﻼﺗﺣﺎد اﻟﻛﯾﻣﺎﺋﻰ وﻧﺗﯾﺟﻪ ﺗﺳﺗﺧدم طﺑﻘﻪ اﺧرى ﻣن ﻣﺎدﻩ
ﻛﻠورﯾد اﻟﺑوﻟﯾﻔﯾﻧﺎﯾل PVCﻋﺎﻟﻰ اﻟﺟودة وﻗد ﺗﺳﺗﺧدم اﯾﺿﺎ ﻣﺎدﻩ اﻟﺑوﻟﻰ اﯾﺛﻠﯾن ﻋﺎﻟﻰ اﻟﻛﺛﺎﻓﻪ
HDPEﻓﻰ ﺣﺎﻟﻪ ﻛﺎﺑﻼت اﻟﺟﻬد اﻟزاﺋدEHVوﻟﺣﻣﺎﯾﻪ اﻟﻐﻼف اﻟﻣﻌدﻧﻰ ﻣن اﻟﺗﺎﻛل ﻓﻰ ﺣﺎﻟﻪ ﺗﻠف
اﻟﻐﻼف اﻟوﻗﺎﺋﻰ وﺗﺳﺗﺧدم طﺑﻘﻪ اﺿﺎﻓﯾﻪ ﻣن اﻟورق واﻟﺟوت اﻟﻣﺷﺑﻊ ﺑﺎﻟﺑﯾﺗوﻣﯾن اﻟﻣﺿﺎف اﻟﯾﻪ
-٧اﻟدرعARMOUR
اﻟﻐرض ﻣن اﻟدرع ﻫو ﺗوﻓﯾر اﻟﺣﻣﺎﯾﻪ اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ ﻟﻠﻛﺎﺑل وﻋﻣوﻣﺎ ﻛﺎﺑﻼت اﻻﻏﻠﻔﻪ اﻟﻣﻌدﻧﯾﻪ
اﻟﻣﺻﻧوﻋﻪ ﻣن اﻻﻟوﻣﻧﯾوم ﻻ ﺗﺣﺗﺎج ﻋﺎدﻩ اﻟﻰ طﺑﻘﻪ ﺗدرﯾﻊ ﻧظ ار ﻟﻠﺧﺻﺎﺋص اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ اﻟﺟﯾدﻩ
ﻟﻼﻟوﻣﻧﯾوم .
اﻣﺎ ﻛﺎﺑﻼت اﻟﺗﯾﺎر اﻟﻣﺗﻐﯾر ﺑﺎﻟﻣوﺻل اﻟﻣﻧﻔرد واﻟﻐﻼف اﻟﻣﻌدﻧﻰ اﻟﻣﺻﻧوع ﻣن اﻟرﺻﺎص ﻓﺗزود
ﺑدرع ﻣﺻﻧوع ﻣن ﻣﺎدﻩ ﻏﯾر ﻣﻐﻧﺎطﯾﺳﯾﻪ وﻫﻰ ﻣرﺗﻔﻌﻪ اﻟﺛﻣن ﻧﺳﺑﯾﺎ .
وﻋﺎدﻩ ﻣﺎ ﺗزود اﻟﻛﺎﺑﻼت ﺑطﺑﻘﻪ ﻣﺑطﻧﻪ ﺗﺣت اﻟدرع وﺗﺗﻛون اﻟطﺑﻘﻪ ﻣن ﻣواد ﻟﯾﻔﯾﻪ او ﻣن ﻣﺎدﻩ
١٩
ﯾﺗم ﺗوﻓﯾر اﻟﺣﻣﺎﯾﻪ اﻟﻣﯾﻛﺎﻧﯾﻛﯾﻪ ﻟﻬﺎ ﻋن طرﯾق دروع ﻟﻬﺎ أﺷﻛﺎل ﻣﺗﻌددﻩ ﻣﻧﻬﺎ ﻣﺎ ﯾﻠﻰ:
ﺷراﺋط ﻣن اﻟﺻﻠب ﺗﻠف ﺣول اﻟطﺑﻘﻪ اﻟﻣﺑطﻧﻪ وﯾﺳﺗﺧدم ﻋﺎدﻩ ﺷرﯾطﺎن ﻣﺗداﺧﻼن ﻟﺿﻣﺎن
-١أﺳﻼك ﻣن اﻟﺻﻠب اﻟﻣﺟﻠﻔن وﺗﻠف ﺣول اﻟﻛﺎﺑل وﺗﺗﻛون ﻣن طﺑﻘﻪ او طﺑﻘﺗﯾن .
إﯾﺛﻠﯾن.
و ﻣﻣﺎ ﺳﺑق ﯾﺗﺿﺢ ﻟﻧﺎ أن اﻟﻛﺎﺑﻼت ﺗﺳﻣﻰ ﺑﺎﺳم ﻣﺎدة اﻟﻌزل اﻟﻣﺳﺗﺧدﻣﺔ ﻣﻣﺎ ﯾدل ﻋﻠـﻰ ﻣـدى
أﻫﻣﯾﺔ اﻟﻌزل ﻓﻰ ﺻﻧﺎﻋﺔ اﻟﻛﺎﺑﻼت وﻫـو أﻫـم ﻣﻛوﻧـﺎت اﻟﻛﺎﺑـل وﻧظـ ار ﻟﻬـذﻩ اﻷﻫﻣﯾـﺔ ﻓﺈﻧـﻪ ﯾﺟـب أن
ﺗﺗ ـواﻓر ﻓــﻰ ﻣــﺎدة اﻟﻌــزل ﺑﻌــض اﻟﻣواﺻــﻔﺎت ﻣــﻊ اﻷﺧــذ ﻓــﻰ اﻻﻋﺗﺑــﺎر أﻧــﻪ ﻣــن اﻟﺻــﻌب ﺗ ـواﻓر ﻛــل
٢٠
(٣أﻻ ﺗﻘﺑل اﻣﺗﺻﺎص اﻟرطوﺑﺔ ﻣن اﻟوﺳط اﻟﻣﺣﯾط ﺑﻬﺎ .
(٦ﻻ ﺗﺗﺄﺛر أو ﺗﺗﻐﯾر ﻣﻛوﻧﺎﺗﻬﺎ ﺑﺎرﺗﻔﺎع درﺟﺔ اﻟﺣرارة اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎر اﻟﺣﻣل اﻟﻌﺎدي أو أﻗﺻﻰ
.٦اﻟﻣطﺎط .
.٨اﻟورﻧﯾش .
٢١
ﻫذا ﺑﺎﻹﺿﺎﻓﺔ اﻟﻰ ﺑﻌض اﻟﻣواد اﻷﺧرى .
وﻟﻣﺎ ﻛﺎن ﻧﺷﺎط ﺷرﻛﺎت اﻟﺗوزﯾﻊ ﻫو ﺗوﺻﯾل اﻟﺗﯾﺎر اﻟﻰ اﻟﻣﺷﺗرﻛﯾن ﻟﻠﺟﻬود اﻟﻣﺗوﺳطﺔ ١١، ٢٢
ك.ف واﻟﻣﻧﺧﻔض ٣٨٠/٢٢٠ﻓوﻟت اﻟﻰ ﺟﺎﻧب أن اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﻧطﺎق ﻋﻣل اﻟﺷرﻛﺔ
ﻫﻰ
وﺳﯾﺗم ﻋﻣل ﺷرح واﻓﻰ ﻟﻬذﻩ اﻷﻧواع ﻣﻊ اﻟﺗرﻛﯾز ﻋﻠﻰ اﻟﻧوع اﻷﺧﯾر وﻫو X . L . P
. Eواﻟذى ﯾﺗم ﺣﺎﻟﯾﺎ إﺣﻼﻟﻪ ﺑدﻻ ﻣن اﻟﻧوع اﻟراﺑﻊ اﻟﻛﺎﺑﻼت اﻟﻣﻌزوﻟﺔ ﺑﺎﻟورق اﻟﻣﺷﺑﻊ ﺑﺎﻟزﯾت
ﻟظﻬور ﺑﻌض اﻟﻌﯾوب واﻟﺗﻰ ﺳوف ﯾﺗم ﺗوﺿﯾﺣﻬﺎ ﻓﯾﻣﺎ ﺑﻌد أﯾﺿﺎ .
إﻻ أﻧﻪ ﺳـوف ﯾﺗم اﻵن ﺗوﺿﯾﺢ وﺷـرح أﺣـد أﻧواع اﻟﻣواد اﻟﻌﺎزﻟﺔ ﻣن ﺣﯾث ﺧﺻﺎﺋﺻﻬﺎ
٢٢
(٤ﻏﯾر ﻧﺷطﺔ ﻛﯾﻣﯾﺎﺋﯾﺎ أى ﺧﺎﻣﻠﺔ " ﻻ ﺗﺗﻔﺎﻋل ﻣﻊ اﻷﺣﻣﺎض أو اﻟﻘﻠوﯾﺎت " .
ﺗم اﺧﺗﺑـﺎر ﻫذﻩ اﻟﻣﺎدة اﻟﻌﺎزﻟـﺔ وﺗم ذﻛر ﻫذﻩ اﻟﻣواﺻﻔﺎت ﻟﻬﺎ ﺑﺳﺑب ﻛوﻧﻬﺎ ﻣﺎدة ﺗﺳﺗﺧدم
ﻓﻰ اﻟﻌزل وﺳﯾﺗم ذﻛرﻫﺎ ﻛﻣﺎدة ﻏﻼف ﺧﺎرﺟﻲ ﻟﻠﻛﺎﺑﻼت اﻟﺑﻼﺳﺗﯾﻛﯾﺔ وﺗﺳﺗﺧدم أﯾﺿﺎ ﻓﻰ اﻟﺣﺷو
واﻟﺻرف اﻟﺻﺣﻰ ﻟﻣﺎ ﻟﻬﺎ ﻣن ﺧﻣول ﻛﯾﻣﯾﺎﺋﻲ ،إﻻ أﻧﻬﺎ ﻛﻣﺎدة ﻋﺎزﻟﺔ ﻻ ﺗﺳﺗﺧدم إﻻ ﺣﺗﻰ ﺟﻬد
ﻓﯾﻣﺎ ﯾﻠﻰ ﺟدول ﯾوﺿﺢ اﻟﻣﻘﺎطﻊ اﻟﻣﺧﺗﻠﻔﺔ ﻟﻠﻛﺎﺑﻼت اﻷرﺿﯾﺔ ﻟﻠﺟﻬدﯾن اﻟﻣﻧﺧﻔض
ﻛﺎﺑﻼت ﺟﻬد ﻣﺗوﺳط ﻗطر اﻟﻣوﺻل ﻋدد اﻟﺷﻌﯾرات ﻛﺎﺑﻼت ﺟﻬد ﻣﻧﺧﻔض
٢ ٢
١٦× ٣ﻣم ٤.٧ﻣم ٧ ١٠ + ١٦× ٣ﻣم
٢ ٢
٢٥ × ٣ﻣم ٥.٩ﻣم ٧ ١٦ + ٢٥×٣ﻣم
٢ ٢
٣٥× ٣ﻣم ٧.٠ﻣم ١٩ ٢٥ + ٣٥× ٣ﻣم
٢ ٢
٥٠ × ٣ﻣم ٨.٠ﻣم ١٩ ٢٥ + ٥٠×٣ﻣم
٢٣
٢ ٢
٧٠× ٣ﻣم ٩.٧ﻣم ١٩ ٣٥ + ٧٠× ٣ﻣم
٢ ٢
٩٥ × ٣ﻣم ١١.٤ﻣم ١٩ ٥٠ + ٩٥×٣ﻣم
٢ ٢
١٢٠× ٣ﻣم ١٢.٩ﻣم ٣٧ ٧٠ + ١٢٠× ٣ﻣم
٢ ٢
١٥٠ × ٣ﻣم ١٤.٣ﻣم ٣٧ ٧٠ + ١٥٠×٣ﻣم
٢ ٢
١٨٥× ٣ﻣم ١٦.١ﻣم ٣٧ ٩٥ + ١٨٥× ٣ﻣم
٢ ٢
٢٤٠ × ٣ﻣم ١٨.٣ﻣم ٦١ ١٢٠ + ٢٤٠×٣ﻣم
وﯾوﺿﺢ ﻫذا اﻟﺟدول اﻟﻣﻘﺎطﻊ اﻟﻣﺧﺗﻠﻔﺔ واﻟﺛﺎﺑﺗﺔ ﻟﻛﺎﺑﻼت اﻟﺟﻬد اﻟﻣﻧﺧﻔض واﻟﻣﺗوﺳط
ﻛﻣﺎ اﻧﻪ ﯾوﺿﺢ ﻋدد ﺷﻌﯾرات اﻟﻣوﺻل وﻛذﻟك ﻗطر ﻛل ﻣوﺻل .
وﻣن اﻟﺿروري أن ﯾﻛون اﻟﻘﺎﺋم ﺑﺎﻟﻌﻣل ﻓﻰ ﻗﺳم اﻟﻛﺎﺑﻼت اﻷرﺿﯾﺔ ﻋﻠﻰ ﻋﻠم ﺑﻬذﻩ
اﻟﻣﻘﺎطﻊ وﻛﻣﺎ اﻧﻪ ﻣن اﻟﺿروري أن ﯾﻛون ﻋﻠﻰ ﻋﻠم ﺑﻛﯾﻔﯾﺔ ﺗﺣدﯾد ﻣﺳﺎﺣﺔ ﻣﻘطﻊ أي ﻛﺎﺑل ﯾراﻩ
ﺳواء ﻛﺎن ذﻟك ﻣن ﺧﻼل ﺗطﺑﯾق ﻗﺎﻧون ﻋدد اﻟﺷﻌﯾرات أو ﺑطرﯾﻘﺔ ﻗطر اﻟﻣوﺻل أو ﺑﻣﺟرد اﻟﻧظر
} ) N = 1 + { 3A ( A + 1
٢٤
ﻓﺈذا ﻛﺎن ﻋدد اﻟطﺑﻘﺎت ) ( ١
ن = ( ٧ ) = ٦ + ١ = [ ( ١ + ١ ) ١× ٣ ] + ١ﺷﻌﯾرات
ن = ( ١٩ ) = ١٨ + ١ = [ ( ١ + ٢ ) ٢ × ٣ ]+ ١ﺷﻌرﻩ
ن = ( ٣٧ ) = ٣٦ + ١ = [ ( ١ + ٣ ) ٣ × ٣ ] + ١ﺷﻌرﻩ
ن = ( ٦١ ) = ٦٠ + ١ = [ ( ١ + ٤ ) ٤× ٣ ] + ١ﺷﻌرﻩ
ﻛﻣﺎ أن اﻟﻛﺎﺑل ﻣﻘطﻊ ١٥٠× ٣ﻣم ٢ﺗﻛون اﻟﻔﺎزﻩ اﻟﺧﺎﺻﺔ ﺑﻪ ﻣن ٣طﺑﻘﺎت أى أن ﻋدد
٢٥
ﻛﻣﺎ أن اﻟﻛﺎﺑل ﻣﻘطﻊ ٢٤٠ × ٣ﻣم ٢ﺗﻛون اﻟﻔﺎزﻩ اﻟﺧﺎﺻﺔ ﺑﻪ ﻣﻛوﻧﺔ ﻣن ٤طﺑﻘﺎت أى
وﻟﻣﺎ ﻛﺎﻧت ﻫﻧﺎك ﻣﻘﺎطﻊ ﻟﻠﻛﺎﺑﻼت ﺗﺷﺗرك ﻓﻰ ﻧﻔس ﻋدد اﻟﺷﻌﯾرات ﻣﻣﺎ ﯾﺻﻌب ﻣﻌﻪ
ﺗﺣدﯾد ﻣﺳﺎﺣﺔ اﻟﻘطﻊ ﻣن ﺧﻼل ﻋدد اﻟﺷﻌﯾرات وﯾﺳﺗﻠزم ذﻟك ﻣﻌرﻓﺔ ﻗطر اﻟﻣوﺻل ﻟﺗﺳﺎﻋد ﻋﻠﻰ
وﻣن ﺧﻼل اﻟﺟدول اﻟذى ﯾوﺿﺢ ﻣﺳﺎﺣﺎت اﻟﻣﻘطﻊ وﻋدد اﻟﺷﻌﯾرات وأﻗطﺎر اﻟﻣوﺻﻼت
ﺳﯾﺗم اﺧﺗﺑﺎر أﺣد اﻟﻣﻘﺎطﻊ ﻟﺣﺳﺎب ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟﻣوﺻل ﻣن ﺧﻼل ﻗطر اﻟﻣوﺻل .
ﻣﺛﺎل :
٢
ﻧﺟد أن ﻋدد اﻟﺷﻌﯾرات ١٩ ﻣن اﻟﺟدول اﻟﺳﺎﺑق ﻟﻣوﺻل ﻣﺳﺎﺣﺔ ﻣﻘطﻌﻪ ٥٠ﻣم
ﺷﻌﯾرة وﻗطر اﻟﻣوﺻل ٨ﻣم وﻣن اﻟﻣﻌﻠوم أن ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟداﺋرة ) ط ﻧق ( ٢وﻟﻣﺎ ﻛﺎن
٢
ﻣﺳﺎﺣﺔ ﻣﻘطﻊ اﻟﻣوﺻل = ط ﻧق
٢
= ( ٤ ) × ٣.١٤
٢
= ٥٠.٢٤ = ١٦ × ٣.١٤ﻣم
٢
إذا ﻣﻘطﻊ اﻟﻛﺎﺑل ٥٠ × ٣ﻣم
وﯾﺗﺿﺢ ﻟﻧﺎ أن اﻟرﻗم اﻟﺧﺎرج ﻣن ﺣﺳﺎب ﻣﺳﺎﺣﺔ اﻟﻣﻘطﻊ ﻟﯾس اﻟرﻗم اﻟﺻﺣﯾﺢ وﻟﻛﻧﻪ
ﻗرﯾب ﻣن اﻟرﻗم اﻟﻣدون ﺑﺎﻟﺟدول وﯾﻣﻛن ﺗطﺑﯾق اﻟﻘﺎﻧون ﻋﻠﻰ أى ﻗطر ﻷي ﻣوﺻل .
٢٦
إﻻ اﻧﻪ ﺑﺎﻟﻧﺳﺑﺔ ﻟذوى اﻟﺧﺑرة اﻟطوﯾﻠﺔ ﻓﻰ ﻣﺟﺎل اﻟﻛﺎﺑﻼت وﻣن ﻛﺛرة اﻟﺗﻌرض ﻟﻠﻣﻘﺎطﻊ
اﻟﻣﺧﺗﻠﻔﺔ ﻓﻰ اﻟﻌﻣل ﯾﺻﺑﺢ اﻷﻣر ﺑﺎﻟﻧﺳﺑﺔ ﻟﻬم ﻟﺗﺣدﯾد ﻣﺳﺎﺣﺔ اﻟﻣﻘطﻊ ﺳﻬل وﯾﺳﯾر ﺑﻣﺟرد
اﻟﻧظر
اﻟﻣوﺻــﻼت
ﻣﺎدة ﻟﻬﺎ ﻣﻘﺎوﻣﺔ ﻧوﻋﯾﺔ ﺻﻐﯾرة " ﻣوﺻﻠﯾﺔ ﻋﺎﻟﯾﺔ " ﺗﺳﻣﺢ ﺑﻣرور اﻟﺗﯾﺎر اﻟﻛﻬرﺑﻰ ﻣن ﺧﻼﻟﻬﺎ
ﺑﺳﻬوﻟﺔ .
(١اﻟﻔﺿـــــــــﺔ .
(٢اﻟﻧﺣـــــــــﺎس .
(٣اﻷﻟوﻣﻧﯾـــــوم .
إﻻ أﻧﻪ ﯾﻼﺣظ أن اﻟﻧﺣﺎس واﻷﻟوﻣﻧﯾوم ﻫﻣﺎ اﻟﻣوﺻﻼن اﻟﻠذان ﯾﺳﺗﺧدﻣﺎن ﻛﻣوﺻﻼت ﻓﻰ
اﻟﻛﺎﺑﻼت اﻷرﺿﯾﺔ إو ذا أردﻧﺎ ﻋﻣل ﺗرﺗﯾب ﻟﻠﻣوﺻﻼت ﻣن ﺣﯾث اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ اﻷﻗل ﻓﺎﻷﻛﺛر
٢٧
ﻧﺟد أن اﻟﻔﺿﺔ ﻫﻰ أﻗل ﻣوﺻل ﻟﻪ ﻣﻘﺎوﻣﺔ ﻧوﻋﯾﺔ ﺛم اﻟﻧﺣﺎس ﺛم اﻷﻟوﻣﻧﯾوم وﻟذﻟك ﻓﺄن اﻟﻔﺿﺔ
وﯾﺳﺗﺧدم اﻟﻧﺣﺎس واﻷﻟوﻣﻧﯾوم ﻓﻘط ﻛﻣوﺻﻼت ﻟﻠﻛﺎﺑﻼت واﻟﺟدول اﻟﺗﺎﻟﻰ ﯾوﺿﺢ اﻟﻔرق ﺑﯾن
٣ ٣
٢.٧ﺟم /ﺳم ٨.٩ﺟم/ﺳم اﻟﻛﺛﺎﻓﺔ ﻋﻧد ٥ ٢٠م ٣
٢ ٢
٦١ﻣﺗر /أو م .ﻣم ٩٧ﻣﺗر /أو م .ﻣم اﻟﻣوﺻﻠﯾﺔ ٥
٢ ٢
١٠ﻛﺟم /ﻣم ١٩ﻛﺟم /ﻣم اﻟﺷد اﻟﻣﺳﻣوح ﺑﻪ ٦
٢ ٢
١٨ﻛﺟم /ﻣم ٤٠ﻛﺟم /ﻣم أﻗﺻﻰ ﺷد ٧
ﯾﻔﻘد ﻟﻣﻌﺎﻧﺔ ﺑﺳرﻋﺔ وﯾﻐطﻰ ﺑطﺑﻘﺔ ﻣن ﯾﻐطﻰ ﺑطﺑﻘﺔ ﺻدأ ﻟوﻧﻬﺎ أﺧﺿر ﻣن ﻗﺎﺑﻠﯾﺔ اﻟﺻــدأ ﻋﻧد ٩
أﻛﺳﯾد اﻷﻟوﻣﻧﯾوم وﻫﻰ ﻣﺎدة ﻋﺎزﻟﺔ أﻛﺳﯾد اﻟﻧﺣﺎس وﻫﻰ ﻣﺎدة ﻋﺎزﻟﺔ اﻟﺗﻌرض ﻟﻠﻌواﻣل اﻟﺟوﯾﺔ
ﺧطوط ﻫواﺋﯾﺔ -ﻛﺎﺑﻼت -ﺳراﻓﯾل ﺧطوط ﻫواﺋﯾﺔ -ﻛﺎﺑﻼت -ﺳراﻓﯾل -ﻛوس اﻻﺳﺗﺧدام ١٠
٢٨
-ﻛوس -ﻛﻠﺑﺳﺎت -ﻛﻠﺑﺳﺎت -ﻗواﻋد ﻣﺻﻬرات -ﺑﺎرات
ﻣوﺻل ﺟﯾد -طرى -ﺧﻔﯾف اﻟوزن- ﻣوﺻل ﺟﯾد -ﯾﺗﺣﻣل اﺟﺗﻬﺎدات ﻋﺎﻟﯾﺔ اﻟﻣﻣﯾزات ١١
رﺧﯾص اﻟﺛﻣن
٢٩
EARTHING
٣٠
اﻟﺗﺄرﯾض earthing
ﺗﻌرﯾف /ﯾﻌرف اﻟﺗﺄرﯾض ﺑﺄﻧﻪ ﺗوﺻﯾل ﻣﺗﻌﻣد ﻟﺟزء ﻣن ﻧظﺎم أو ﻣﻌدة ﺗوﺻﯾﻼ ﻣﺑﺎﺷ ار ﺑﺎﻷرض
ﺑدون وﺟود ﻓﯾوز أو ﻣﻔﺗﺎح أو ﻗﺎطﻊ ﻓﻲ ﻫذا اﻻﺗﺻﺎل اﻷرﺿﻲ.
ﯾﺗم ﺗﺄرﯾض دواﺋر اﻷﺟﻬزة اﻟﻣﺧﺗﻠﻔﺔ ﻟﻠﺣد ﻣـن ارﺗﻔـﺎع اﻟﺟﻬـد اﻟﻧـﺎﺗﺞ ﻣـن ﺗـﺄﺛﯾر اﻟﺻـواﻋق أو
ﺗﻼﻣس ﻣوﺻﻼت اﻟدواﺋر ﻣﻊ ﻣوﺻﻼت ذات ﺟﻬد أﻋﻠﻰ .ﻛﻣﺎ ﯾﺳﺗﺧدم اﻟﺗﺄرﯾض ﻓـﻲ اﻟﻣﺣﺎﻓظـﺔ
ﻋﻠﻰ ﺛﺑﺎت اﻟﺟﻬد أﺛﻧﺎء اﻟﺗﺷﻐﯾل اﻟﻌﺎدي وﺗﺳﻬﯾل ﻋﻣل ﻗواطﻊ اﻟوﻗﺎﯾﺔ ﻣن اﻟﺗﺳرب اﻷرﺿﻲ .
ﻣوﺻـل اﻟﺗــﺄرﯾض ﻫــو ﻣوﺻـل ﻣــن اﻟﻧﺣــﺎس أو اﻷﻟﻣﻧﯾــوم ﻣﻌـزول ﺑــﺎﻟﻠون اﻷﺧﺿــر أو اﻟﻠــون
اﻷﺧﺿر /اﻷﺻﻔر وﯾﺗم ﺗﻣدﯾدﻩ ﻣﻊ ﻣوﺻﻼت اﻟدواﺋر اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﯾﻣﺎ ﺑﯾن ﻟوﺣﺔ اﻟﺗوزﯾـﻊ اﻟﻔرﻋﯾـﺔ
واﻟﻣﺧرج اﻟﻛﻬرﺑﺎﺋﻲ أﻣﺎ ﻣوﺻل ﺗﺄرﯾض اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ واﻟﻌﻣوﻣﯾﺔ ﻓﯾﺗم ﺗﻣدﯾـدﻩ ﻋـن ﻣوﺻـﻼت
اﻟﻧﺣﺎس أو اﻷﻟﻣﻧﯾوم إو ﻣﺎ أن ﯾﻛون ﻋﺎرﯾﺎً أو ﻣﻌزوﻻً ﻣﺻﻣﺗﺎً أو ﻣﺟدوﻻً ﯾرﺑط اﻟﻠوﺣـﺎت اﻟﻔرﻋﯾـﺔ
ﻣــﻊ اﻟﻠوﺣــﺎت اﻟﻌﻣوﻣﯾــﺔ ﻣــن ﺟﻬــﺔ وﯾــرﺑط اﻟﻠوﺣــﺎت اﻟﻌﻣوﻣﯾــﺔ ﻣــﻊ ﻗطــب اﻟﺗــﺄرﯾض ﻣــن اﻟﺟﻬــﺔ
اﻷﺧرى .وﯾوﺿﺢ اﻟﺟدول اﻟﺗـﺎﻟﻲ ﻣﻘـﺎطﻊ ﻣوﺻـﻼت اﻟﺗـﺄرﯾض ﺑﺎﻟﻧﺳـﺑﺔ ﻟﻣﻘطـﻊ اﻟﻣوﺻـل اﻟﺣﺎﻣـل
ﻟﻠﺗﯾﺎر :
١ ١
١.٥ ١.٥
٢.٥ ٢.٥
٤ ٤
٣١
٦ ٦
١٠ ١٠
١٦ ١٦
١٦ ٢٥
١٦ ٣٥
٢٥ ٥٠
٣٥ ٧٠
٥٠ ٩٥
٧٠ ١٢٠
٧٠ ١٥٠
٩٥ ١٨٥
١٢٠ ٢٤٠
١٥٠ ٣٠٠
١٨٥ ٤٠٠
ﻟﻌﻣل ﺷﺑﻛﺔ ﺗﺄرﯾض ﺟﯾدة ﻟﻠﻣﺑﻧﻰ ﻓﺈﻧﻪ ﻣن اﻟﺿروري أن ﯾﺗم ﺗﺄرﯾض اﻟﻌﻧﺎﺻر اﻟﺗﺎﻟﯾﺔ :
-ﻛل اﻷﺟﺳﺎم اﻟﻣﻌدﻧﯾﺔ رأﺳﯾﺎً وﯾزﯾد طوﻟﻬﺎ ﻋن ٢٤٠ﺳم أو اﻟﻣﻣدة أﻓﻘﯾـﺎً وﯾزﯾـد طوﻟﻬـﺎ ﻋـن
-ﻛل اﻷﺟﻬزة اﻟﻛﻬرﺑﺎﺋﯾﺔ . ١٥٠ﺳم واﻟﻣﻌرﺿﺔ ﻟﻠﻣﻼﻣﺳﺔ .
٣٢
-٢ﻗطب اﻟﺗﺄرﯾض ): (GROUNDING ELECTRODE
-٣ﻣوﺻل ﻣﻌدﻧﻲ ﯾﺗم ﺗﻣدﯾدﻩ ﺣول اﻟﻣﺑﻧﻰ وﻋﻠﻰ ﻻ ﯾﻘل ﻋن ٧٥ﺳم ﻣن ﺳطﺢ اﻷرض.
وﻫــو ﻋﺑــﺎرة ﻋــن ﻗﺿــﯾب أو ﻣﺎﺳــورة ﻣﻌدﻧﯾــﺔ ﻻ ﯾﻘــل طوﻟﻬــﺎ ٢٤٠ﺳــم ﺗــدﻓن رأﺳــﯾﺎً ﻣﻼﻣﺳــﺔ
ﻟﻠﺗرﺑﺔ إﻻ إذا ﻛﺎﻧت اﻷرض ﺻﺧرﯾﺔ ﻓﯾﻣﻛن وﺿﻌﻬﺎ ﻣﺎﺋﻠﺔ ٤٥درﺟﺔ ﻋﻠـﻰ اﻟﻣﺳـﺗوى اﻟرأﺳـﻲ أو
ﺗدﻓن ﻓﻲ ﺧﻧدق ﻋﻠﻰ ﻋﻣق ٧٥ﺳم ﻣن ﺳطﺢ اﻷرض ﻋﻠﻰ اﻷﻗل.
وﻫو ﻋﺑﺎرة ﻋن ﻟوح ﻣﻌدﻧﻲ ﻗد ﯾﻛون ﻣن اﻟﻧﺣﺎس ﯾﺳﻣك ١.٥ﻣم أو ﻣـن اﻟﺣدﯾـد ﺑﺳـﻣك ﻻ
ﯾﻘل ﻋن ٦.٣٥ﻣم .وﯾﺟب أﻻ ﺗﻘل اﻟﻣﺳﺎﺣﺔ اﻟﻣﻌرﺿﺔ ﻟﻠﺗرﺑﺔ ﻋن ٠.١٨٦م.٢
وﻋﻣوﻣﺎً ﯾﺟب أن ﯾﻛون ﻗطب اﻟﺗﺄرﯾض اﻟﻣﻼﻣـس ﻟﻠﺗرﺑـﺔ ﺧﺎﻟﯾـﺎً ﻣـن اﻟﺷـﺣوم أواﻟزﯾـوت ﻷﻧﻬـﺎ
ﺗﺿﻌف ﺧﺻﺎﺋص ﻗﺎﺑﻠﯾﺔ اﻟﺗﺄرﯾض ﻟﻠﺗوﺻﯾل اﻟﻛﻬرﺑﺎﺋﻲ .
ﺑﻌد اﻻﻧﺗﻬﺎء ﻣن ﺗﺄرﯾض اﻟﻣﺑﻧﻰ واﻟﻠوﺣﺎت اﻟﻌﻣوﻣﯾـﺔ واﻟﻔرﻋﯾـﺔ ﯾـﺗم ﻗﯾـﺎس ﻣﻘﺎوﻣـﺔ اﻟﺗـﺄرﯾض
ﺑواﺳطﺔ أﺟﻬزة ﺧﺎﺻـﺔ ﺑـذﻟك ﻓـﺈذا ﻟـوﺣظ أﻧﻬـﺎ ﺗزﯾـد ﻋـن اﻟﺣـد اﻟﻣﺳـﻣوح ﺑـﻪ وﻫـو ٢٥أوم ﻓﺈﻧـﻪ
ﯾﻠزم ﺧﻔض ﻫذﻩ اﻟﻘﯾﻣﺔ ﺑﺎﺳﺗﺧدام طرﯾﻘﺔ أو أﻛﺛر ﻣن اﻟطرق اﻟﺗﺎﻟﯾﺔ :
زﯾــﺎدة ﻗطــر ﻗﺿــﯾب اﻟﺗــﺄرﯾض ﻟﺗزﯾــد اﻟﻣﺳــﺎﺣﺔ اﻟﻣﻌرﺿــﺔ ﻟﻣﻼﻣﺳــﺔ اﻟﺗرﺑــﺔ إﻻ أن زﯾــﺎدة ﻗطــر
اﻟﻘﺿﯾب ﻻ ﯾﺗﺑﻌﻬﺎ ﺧﻔض ﻣﻠﻣوس ﻓﻲ ﻣﻘﺎوﻣﺔ اﻟﺗـﺄرﯾض ﺑﺎﻹﺿـﺎﻓﺔ إﻟـﻰ أﻧـﻪ ﻻ ﯾﻔﺿـل اﺳـﺗﺧدام
أﻗطﺎر أﻛﺑر ﻣن ١٨ﻣم.
٣٣
ﯾﻣﻛن أن ﯾﺗم رﺑط أﻛﺛر ﻣن ﻗﺿﯾب ﻋن طرﯾق ﺟﻠﺑﻪ وﺻل ﻣن ﻧﻔس اﻟﻣﻌـدن ﻟﻠﺣﺻـول ﻋﻠـﻰ
اﻟطــول اﻟﻣﻧﺎﺳــب ورﻏــم أن اﻟطــول اﻟﻣوﺻــﻰ ﺑﺎﺳــﺗﺧداﻣﻪ ﻓــﻲ ) (NECﻫــو ٢٤٠ﺳــم ﻟﻠﺗرﺑــﺔ
اﻟﻌﺎدﯾﺔ إﻻ أﻧﻪ ﯾﻣﻛن زﯾﺎدة ﻫذا اﻟطول إﻟﻰ ١٥ﻣﺗر ﻷﻧواع اﻟﺗرﺑﺔ اﻟردﯾﺋﺔ.
ﯾﻣﻛن اﺳﺗﺧدام أﻛﺛر ﻣن ﻗﺿﯾب ﻣدﻓون ﻓﻲ اﻷرض ﻋﻠﻰ ﻣﺳﺎﻓﺎت ﻻ ﺗﻘل ﻋن ٢٤٠ﺳـم ﺑـﯾن
اﻟﻘﺿﯾب واﻵﺧر وذﻟك ﻟﻠﺣﺻول ﻋﻠﻰ أﻓﺿل ﻗﯾﻣﺔ ﻣﻣﻛﻧﺔ ﻟﻣﻘﺎوﻣﺔ اﻟﺗﺄرﯾض.
ﺗﻌــﺎﻟﺞ اﻟﺗرﺑــﺔ اﻟﻣﺣﯾطــﺔ ﺑﻘﺿــﯾب اﻟﺗــﺄرﯾض ﻛﯾﻣﯾﺎﺋﯾ ـﺎً ﻟﻠﺣﺻــول ﻋﻠــﻰ ﻣﻘﺎوﻣــﺔ ﻟﻠﺗــﺄرﯾض ﺑﺄﺣــد
اﻟطرق اﻟﺗﺎﻟﯾﺔ-:
أ( ﺗﻌﻣــل ﺣﻔــرﻩ ﻣﺟــﺎورة ﻟﻘﺿــﯾب اﻟﺗــﺄرﯾض وﺗﺑﻌــد ﻋﻧــﻪ ﺑﻣﺳــﺎﻓﺔ ﻻ ﺗزﯾــد ﻋــن ١٠ﺳــم وﺗﻣ ـﻼً
ﺑﺄﻣﻼح ﻛﺑرﯾﺗـﺎت اﻟﻣﻐﻧﯾﺳـﯾوم أو ﻛﺑرﯾﺗـﺎت اﻟﻧﺣـﺎس أو ﻣﻠـﺢ ﺻـﺧري ﺣﺗـﻰ ﻣﻧﺳـوب ٣٠ﺳـم ﻣـن
ﺳــطﺢ اﻷرض وﯾﺻــﻌب ﺗﻧﻔﯾــذ ﻫــذﻩ اﻟطرﯾﻘــﺔ ﻓ ـﻲ ﺣﺎﻟــﺔ ﻋــدم ﺗــوﻓر ﻓ ـراغ ﻛــﺎﻓﻲ ﺑﺟ ـوار ﻗﺿــﯾب
اﻟﺗﺄرﯾض .
ب( أو ﯾﺗم ﻋﻣل ﺧﻧدق داﺋري ﺣول ﻗﺿـﯾب اﻟﺗـﺄرﯾض ﺑﺣﯾـث ﻻ ﯾﻘـل اﻟﻘطـر اﻟـداﺧﻠﻲ ﻟﻠﺧﻧـدق
ﻋن ٤٥ﺳم وﻋﻣق ٣٠ﺳم .وﯾﻣﻸ ﻫذا اﻟﺧﻧـدق ﺑـﺎﻟﻣواد اﻟﻛﯾﻣﯾﺎﺋﯾـﺔ اﻟﺳـﺎﺑق ذﻛرﻫـﺎ .وﯾﺟـب أﻻ
ﯾﻛون ﻫﻧﺎك اﺗﺻﺎل ﻣﺑﺎﺷر ﺑﯾن اﻟﻣواد اﻟﻛﯾﻣﺎﺋﯾﺔ وﻗﺿـﯾب اﻟﺗـﺄرﯾض ﺣﺗـﻰ ﻻ ﯾﺗﺳـﺑب ﻓـﻲ ﺗﻛـوﯾن
طﺑﻘﺔ ﻣن اﻟﺻدأ ﻋﻠﻰ ذﻟك اﻟﻘﺿـﯾب .واﻟﻛﻣﯾـﺔ اﻟﺗـﻲ ﯾﻔﺿـل وﺿـﻌﻬﺎ ﺗﻛـون ﻓـﻲ ﺣـدود ١٨إﻟـﻰ
٤٠ﻛﯾﻠو ﺟرام ﻣن ﻣﺎدة ﻛﺑرﯾﺗﺎت اﻟﻧﺣـﺎس ﻟـرﺧص ﺛﻣﻧﻬـﺎ وﺟـودة ﺗوﺻـﯾﻠﻬﺎ اﻟﻛﻬرﺑـﺎﺋﻲ وﯾﺳـﺗﻣر
ﻣﻔﻌول ﻫذﻩ اﻟﻛﻣﯾﺔ ﻟﻣدة ﺳﻧﺗﯾن ﺛم ﯾﻛرر وﺿﻌﻬﺎ ﻣرة أﺧرى .وﯾﺗم ﻏﻣر ﺑﺋر اﻟﺗﺄرﯾض ﻓﻲ ﺑﺎدئ
اﻷﻣر ﺑﺎﻟﻣﺎء ﺣﺗﻰ ﯾﺳﺎﻋد ﻋﻠﻰ ﺗﺳرب اﻟﻣواد اﻟﻛﯾﻣﯾﺎﺋﯾﺔ ﻟﻠﺗرﺑﺔ أﻣـﺎ ﺑﻌـد ذﻟـك ﻓـﺈن ﻣﯾـﺎﻩ اﻷﻣطـﺎر
ﻛﺎﻓﯾﺔ ﻟﻠﻘﯾﺎم ﺑﻬذﻩ اﻟﻌﻣﻠﯾﺔ.
ﺗﺧﺗﻠف اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ ﻟﻠﺗرﺑﺔ ﺣﺳب ﻧوﻋﻬﺎ ودرﺟـﺔ اﻟرطوﺑـﺔ وﻓـق ﻣـﺎ ﯾﺗﺿـﺢ ﻣـن اﻟﺟـدول
اﻟﺗﺎﻟﻲ :
٣٤
اﻟﻣﻘﺎوﻣﺔ اﻟﻧوﻋﯾﺔ
ﻣﻘﺎوﻣﺔ ﻋﺎﻟﯾﺔ
ﺗرﺑﺔ ﺻﺧرﯾﺔ
ﺟداً
٣٥
٣٧٠٠ ٥٥٠٠ ٢٠٠ ٢٨٠ ٣٥
ﯾﺗم ﺣﻣﺎﯾﺔ اﻟدواﺋر اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻔرﻋﯾﺔ ﺑﻘواطـﻊ ﻓرﻋﯾـﺔ ﻋﺎدﯾـﺔ ﺳـﻌﺔ ١٥أﻣﺑﯾـر أو ٢٠أﻣﺑﯾـر إﻻ
أﻧﻬــﺎ ﻗﯾﻣــﺔ ﻣرﺗﻔﻌــﺔ ﺟــداً ﺑﻣﻘﺎرﻧﺗﻬــﺎ ﺑﻣــﺎ ﯾﻧــﺗﺞ ﻋﻧﻬــﺎ ﻣــن أﺧطــﺎر ﺣﯾــث أن ﻣــرور ﺗﯾــﺎر ﻛﻬرﺑــﺎﺋﻲ
ﺻﻐﯾر ﻓﻲ ﺣدود ٦٠ﻣﻠﻠﻲ أﻣﺑﯾر ﻓﻲ ﺟﺳم اﻹﻧﺳﺎن ﯾﺳﺑب وﻓﺎﺗﻪ.
وﻟﻬــذا ﯾﻔﺿــل اﺳــﺗﺧدام ﻗواطــﻊ اﻟﺣﻣﺎﯾــﺔ ﻣــن ﺗﯾــﺎر اﻟﺗﺳــرب اﻷرﺿــﻲ ،وﻫــذﻩ اﻟﻘواطــﻊ ﻣﻣﺎﺛﻠــﺔ
ﻟﻠﻘواطﻊ اﻟﻌﺎدﯾﺔ ﻣن ﺣﯾث اﻟﺷﻛل إﻻ أﻧﻬﺎ ﺣﺳﺎﺳﺔ ﺟداً ﻟﻣرور اﻟﺗﯾـﺎر اﻟﻛﻬرﺑـﺎﺋﻲ )ﻣﻬﻣـﺎ ﺻـﻐرت
ﻗﯾﻣﺗﻪ( ﻓﻲ أي ﻣﺳﺎر ﯾﺧﺗﻠف ﻋن اﻟﻣوﺻـل اﻟﻣﺣـدد ﻟﻣـرورﻩ ﻛـﺎن ﯾﻛـون ﻫـذا اﻟﻣﺳـﺎر ﻣـن ﺧـﻼل
ﺟﺳم اﻹﻧﺳﺎن ﻣﺛﻼً .وﻓﻲ ﻫذﻩ اﻟﺣﺎﻟﺔ ،ﻋﻧد ﻣـرور ﺗﯾـﺎر ﺑﺳـﯾط ﻗـد ﯾﺻـل إﻟـﻰ ﺟـزء ﻣـن اﻟﻣﻠﻠـﻲ
أﻣﺑﯾر ﻓﺈن ﻫذا اﻟﻧوع ﻣن اﻟﻘواطﻊ ﯾﻔﺻل اﻟداﺋرة .
٣٦
اﻟﻧوع اﻷول :ﯾﺳﺗطﯾﻊ ﻓﺻل اﻟداﺋرة ﻋﻧدﻣﺎ ﺗﻛون ﻗﯾﻣﺔ اﻟﺗﯾﺎر اﻟﻣﺎر ﻓﯾﻬﺎ ﺑﺣدود ٦ﻣﻠﻠﻲ أﻣﺑﯾر.
اﻟﻧوع اﻟﺛﺎﻧﻲ :ﯾﺻـﻠﺢ ﻟﻔﺻـل اﻟـدواﺋر اﻟﺗـﻲ ﯾزﯾـد ﺗﯾﺎرﻫـﺎ ﻋـن ٢٠ﻣﻠﻠـﻲ أﻣﺑﯾـر وﯾوﺻـﻲ )(NEC
ﺑﺎﺳــﺗﺧدام ﻗواطــﻊ اﻟﺣﻣﺎﯾــﺔ ﻣــن ﺗﯾــﺎر اﻟﺗﺳــرب اﻷرﺿــﻲ ﻓــﻲ ﺑﻌــض اﻟــدواﺋر اﻟﻛﻬرﺑﺎﺋﯾــﺔ ﻟﻠﻣﺑــﺎﻧﻲ
اﻟﺗﺟﺎرﯾﺔ واﻟﺳﻛﻧﯾﺔ وﺧﺎﺻﺔ اﻟﻣوﺟودة ﻓﻲ اﻷﻣﺎﻛن اﻟﻣﺑﺗﻠﺔ.
-٣اﻟﻌﻼﻗﺔ ﺑﯾن ﺷدة ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ وﻣدة ﺳرﯾﺎﻧﻪ ﻓﻲ ﺟﺳم اﻹﻧﺳﺎن .
ﻓﯾﻣﺎ ﯾﻠﻲ ﺟدول ﯾوﺿﺢ ﺗﺄﺛﯾر ﻣرور ﺗﯾﺎر اﻟﺗﺳرب اﻷرﺿﻲ ﻓﻲ ﺟﺳم اﻹﻧﺳﺎن :
ﻋدم اﻧﺗظﺎم ﻧﺑض اﻟﻘﻠب – ﯾرﺗﻔﻊ ﺿﻐط ﺑﺿﻊ ﺛواﻧﻲ ٥٠ – ٣٠
اﻟدم ﻣﻊ إﻏﻣﺎء
٣٧
اﻟﻧﺑﺿﺔ
أ( ﯾﻣﻛــن أن ﯾوﺿــﻊ ﻗــﺎطﻊ ) (Elcbﻋﻠــﻰ اﻟﺧــط اﻟرﺋﯾﺳــﻲ ﻟﻠوﺣــﺔ اﻟﺗوزﯾــﻊ وﻓــﻲ ﻫــذﻩ اﻟﺣﺎﻟــﺔ
ﺗﻛون ﺣﻣﺎﯾﺗﻪ ﺷﺎﻣﻠﺔ ﻟﺟﻣﯾﻊ اﻟدواﺋر .
وﻣن ﻣﺳﺎويء ﻫذﻩ اﻟطرﯾﻘﺔ أﻧﻪ ﻟو ﻛﺎن ﻫﻧﺎك أي ﺗﺳرب ﻟﻸرض ﻣن وﺣدة إﺿﺎءة ﻣﺛﻼً ﻓـﺈن
ذﻟك ﯾﺗﺳﺑب ﻓﻲ ﻗطﻊ اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻲ ﻋن ﻛل اﻟﻠوﺣﺔ.
ب( أن ﯾﻛــون ﻫﻧــﺎك ﻟوﺣﺗــﺎن ﻣﺗﺟﺎورﺗــﺎن إﺣــداﻫﻣﺎ ﻟﻺﺿــﺎءة واﻷﺧــرى ﻟﻠﻘــوى وﯾوﺿــﺢ ﻗــﺎطﻊ
) (Elcbﻗﺑــل ﻟوﺣــﺔ اﻟﻘــوى ﺑﺣﯾــث ﯾﺣﻣــﻲ ﻓﻘــط اﻷﺟﻬــزة واﻵﻻت اﻟﻛﻬرﺑﺎﺋﯾــﺔ اﻟﺗــﻲ ﺗﺗﺻــل ﺑــدواﺋر
اﻟﻘوى.
٣٨
ج( ﯾﻣﻛــن أن ﯾﺳــﺗﺧدم ﻗــﺎطﻊ ) (Elcbﻟﺣﻣﺎﯾــﺔ ﺟﻬــﺎز ﻣﻌــﯾن ﻓﻘــط ﻛﻐﺳــﺎﻟﺔ ﻣــﺛﻼً وﯾــﺗم ذﻟــك
ﺑﺗوﺻﯾﻠﺔ ﻗﺑل اﻟﻣﺂﺧـذ اﻟﻛﻬرﺑﺎﺋﯾـﺔ )اﻟﺑرﯾـزة( واﻟﻐﺳـﺎﻟﺔ أو أي ﺟﻬـﺎز آﺧـر ﯾـراد ﺣﻣﺎﯾﺗـﻪ ﺑﺷـرط أن
ﯾﺗم ﺗوﺻﯾل اﻟﺟﻬﺎز ﺑﺎﻷرض .
٣٩
٤٠
٤١
أﻧظﻣﺔ اﻟﺗﺄرﯾض اﻟوﻗﺎﺋﻰ :
اﻟﻐرض ﻣﻧﻪ:
-١ﺣﻣﺎﯾﺔ اﻷﻓراد )ﻣواطﻧﯾن – ﻋﻣﺎل ( ﻣن اﻟﺻدﻣﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ.
-٢ﺣﻣﺎﯾﺔ اﻟﻣﻌدات اﻟﻛﻬرﺑﯾﺔ واﻟﻣﻧﺷﺂت ﻣن اﻟﺗﻠف.
-٣ﻣﻧﻊ ﺟﻬد اﻟﺟﺳم ﻣن اﻹرﺗﻔﺎع إﻟﻰ ﻗﯾﻣﺔ ﻗد ﺗﺷﻛل ﺧطر ﻋﻠﻰ اﻹﻧﺳﺎن.
-٤اﻟﺳﻣﺎح ﺑﻣرور ﺗﯾﺎر ﻟﻸرض ﻟﻪ ﻗﯾﻣﺔ ﻛﺎﻓﯾﺔ ﻟﺗﺷﻐﯾل اﻷﺟﻬزة اﻟوﻗﺎﺋﯾﺔ )ﻣﺻﻬرات – ﻗواطﻊ(
أو أﺟﻬزة اﻟوﻗﺎﯾﺔ ﺑﻪ ﻟﻠﺗﺳرب اﻷرﺿﻰ.
ﯾﺗم ﻋﻣل ﻗﺻر ﻋﻠﻰ ﺟﻣﯾﻊ اﻷوﺟﻪ وﺗﺄرﯾﺿﻬﺎ ﺑﺄرﺿﻰ ﻣؤﻗت ﺑﻌد ﻓﺻل اﻟﺗﯾﺎر أﺛﻧﺎء اﺟراء
اﻟﺻﯾﺎﻧﺔ أو أﺛﻧﺎء ﻋﻣل اﻟﻣﻧﺎورة اﻟـﻼزﻣﺔ ﻟﺗﺣدﯾد اﻟﻌطل وذﻟك ﻗﺑل وﺑﻌد ﻣﻧطﻘﺔ اﻟﻌﻣل ﻟﺣﻣﺎﯾﺔ
اﻟﻌﺎﻣﻠﯾن ﺿد ﻋودة اﻟﺗﯾﺎر ﺑطرﯾق ﺧﺎطﻰء أو أى ﺳﺑب أﺧر.
وﺑﺗﺣﻠﯾل أﺳﺑﺎب اﻟﺣوادث اﻟﺗﻰ ﺗﺗﺳﺑب ﻓﻰ وﻓﺎة اﻟﻌﺎﻣﻠﯾن ﻧﺟد أﻧﻪ ﻟم ﯾﺗم ﻋﻣل ﻫذا اﻟﻧوع ﻣن
٤٢
اﻷرﺿﻰ ﻗﺑل وﺑﻌد ﻣﻧطﻘﺔ اﻟﻌﻣل.
٤٣
ﻧﺟد أن اﻟﻣﻧﺎطق ﻛﺑﯾرة اﻻﺳﺗﺧدام و ﻟﯾس اﻻﺳﺗﻬﻼك ﻣﺛل ﻣﺣطﺎت
اﻟﺗوﻟﯾد أو ﻣﺣطﺎت اﻟﻣﺣوﻻت ﻋﺎﻟﯾﻪ و ﻓﺎﺋﻘﺔ اﻟﺟﻬد أﻛﺛر ﺗﻌرﺿﺎ ﻟﺗﯾﺎرات
اﻟﻘﺻر و ﺗﺄﺛﯾرﻫﺎ اﻟﺧطر وﻟذﻟك ﻧﺟد أن ﻫذﻩ اﻟﻣﺣطﺎت ﺗﺧﺿﻊ ﻟﻧظﺎم أﺧر
ﻣن اﻟﺗﺄرﯾض وﻫو اﻟﻣﻌروف ﺑﺎﺳم ﺷﺑﻛﺔ اﻟﺗﺄرﯾض ﺣﯾث ﺗﻛون اﻟﺗﯾﺎرات
اﻟﻘﺻرﯾﺔ ﻫﺎﺋﻠﺔ اﻟﻘﯾﻣﺔ وﺗﻌطﻰ ﺟﻬدا ﺧط ار ﻣﻊ أﻗل اﻟﻣﻘﺎوﻣﺎت وﯾﻛون
ﻓوق اﻟﺗﺻور إذا ﻣﺎ أﻫﻣل ﻫذا اﻟﺑﻧد وﯾﻛون اﻟﺿﺣﯾﺔ ﻫم اﻟﻌﺎﻣﻠون ﻓﻰ
اﻟﻣﺣطﺔ أو اﻟﻣﺗواﺟدﯾن أﺣﯾﺎﻧﺎ.
ﻋﻠﻰ اﻟﺟﺎﻧب اﻟﺗﻘﻧﻰ ﻓﺈن ﻫذﻩ اﻟﻣﺷﻛﻠﺔ ﺳﻬﻠﺔ اﻟﺣل ﺣﯾث ﯾﺗم وﺿﻊ
ﻣﻘﺎوﻣﺔ ﺗﺄرﯾض ﻣﺗﻧﺎﻫﯾﺔ اﻟﺻﻐر وﻫو ﻣﺎ ﯾﻣﻛن ﺗﺣﻘﯾﻘﺔ ﻣن ﺧﻼل اﻟﻘﺎﻋدة
اﻟﺑﺳﯾطﺔ اﻟﺗﻰ ﺗﻘﻠل ﻗﯾﻣﺔ اﻟﻣﻘﺎوﻣﺔ وذﻟك ﻣن ﺧﻼل اﻟﺗوﺻﯾﻼت ﺗوازى
ﻟﻠﻣﻘﺎوﻣﺎت ﻓﻌﻧد ﺗوﺻﯾل ﻣﻘﺎوﻣﺗﺎن ﻣﺗﺳﺎوﯾﺗﺎن ﻣﻌﺎ ﻋﻠﻰ اﻟﺗوازى ﺗﻘل
اﻟﻘﯾﻣﺔ اﻟﻔﻌﻠﯾﺔ ﻟﻬﻣﺎ ﻣﻌﺎ إﻟﻰ اﻟﻧﺻف إﻣﺎ اﻟﺛﻼث ﻓﺗﻛون اﻟﺛﻠث وﻫﻛذا وﻣن
ﻫﻧﺎ أﻣﻛن اﻟﺧروج ﻣن اﻟﻣﺄزق اﻟﺧطﯾر وﻣﻌﺎﻟﺟﺔ ﻗﯾﻣﺔ ﻣﻘﺎوﻣﺔ اﻷرﺿﻰ
ﻟﺗﺻﺑﺢ أﻗل ﻣﺎ ﯾﻣﻛن ﻣن ﺧﻼل وﺿﻊ ﺷﺑﻛﺔ أﻓﻘﯾﺔ ﺗﺣت ﺳطﺢ اﻷرض
ﻧﺣﺎﺳﯾﺔ طﺑﻌﺎ ﯾﺧرج ﻣﻧﻬﺎ أﻗطﺎﺑﺎ رأﺳﯾﺔ ﻟﺗﻛون ﻓﻰ ﺣﻛم اﻟﺗوﺻﯾل ﻋﻠﻰ
اﻟﺗوازى ﻓﺗﻘل اﻟﻘﯾﻣﺔ اﻟﻣﺣﺻﻠﺔ ﻟﻬم ﺟﻣﯾﻌﺎ.
ﻛﻣﺎ أﻧﻪ ﯾﻣﻛن ﺗﻘﻠﯾل ﻫذﻩ اﻟﻘﯾﻣﺔ اﻟﻣﺣﺻﻠﺔ ﻋﻠﻰ اﻟﺗوازي ﻓﻲ اﻟﺷﺑﻛﺔ
اﻟﺗﺄرﯾﺿﯾﺔ ﺑﺄن ﺗﺳﺗﻐل اﻷﻗطﺎب اﻟرأﺳﯾﺔ ﻟﯾﺧرج ﻣﻧﻬﺎ ﻋﻠﻰ طول ارﺗﻔﺎﻋﻬﺎ
ﻋددا أﺧر ﻣن اﻷﻗطﺎب اﻷﺻﻐر ﻟﺗﻛون أﻓﻘﯾﺔ اﻟوﺿﻊ ﻓﺗﺻﺑﺢ ﻛﻠﻬﺎ ﺗوازﯾﻪ
اﻟﺗوﺻﯾل ﻟﺗﻘل اﻟﻣﻘﺎوﻣﺔ ﻟﻛل ﻗطب رأﺳﻲ وﻧﺻل إﻟﻰ اﻟﺣدود اﻟدﻧﯾﺎ ﻣن
ﻗﯾﻣﺔ اﻟﻣﻘﺎوﻣﺔ اﻷرﺿﯾﺔ وﻧﻛون ﻗد ﺑﻠﻐﻧﺎ اﻟﻬدف دون ﺗﻛﻠﻔﺔ ﺗذﻛر وﻫذا
ﻫو ﻣﺎ ﯾﺗم ﺑﺎﻟﻔﻌل ﻓﻲ اﻟﻣﺣطﺎت اﻟﻘﺎﺋﻣﺔ وﻫﻛذا ﯾﻛون ﺟﻬد اﻟﺗﻼﻣس ﻏﯾر
ﺧطﯾر أو ﺿﺎر وﺗﺻﺑﺢ ﻧﻘطﺔ اﻟﺗﻌﺎدل داﺧل اﻟﻣﺣطﺔ أﻣﻧﺔ وﯾﺳﺗطﯾﻊ اﻟﻔرد
أن ﯾﺗﻌﺎﻣل ﻣﻌﻬﺎ دون ﺧوف وﺑﺄﻣﺎن ﻛﺎﻣل.
٤٤
ETERNAL ENGINEERS GROUP
01007200959-01114911166
٤٥
ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة
ﯾــؤﺛر اﻧﺧﻔــﺎض ﻣﻌﺎﻣــل اﻟﻘــدرة ﺳــﻠﺑﺎ ﻋﻠــﻰ أداء اﻟﻣﻧظوﻣــﺔ اﻟﻛﻬرﺑﯾــﺔ وﯾﻌﺗﻣــد ذﻟــك ﻋﻠــﻰ
طﺑﯾﻌـﺔ اﻷﺣﻣـﺎل ﻣـن ﺣﯾـث ﻛوﻧﻬـﺎ أﺣﻣـﺎل ﺧطﯾـﺔ ) (Resistive loadsأو أﺣﻣـﺎل ﺣﺛﯾـﻪ ﻏﯾـر
ﺧـطﯾــﺔ ) ( Inductive loadsﻣﺛل ) اﻟﻣﺣوﻻت ،اﻟﻣﺣرﻛﺎت اﻟﺣﺛﯾـﺔ ،اﻟﻣﺻـﺎﺑﯾﺢ اﻟﻔﻠورﯾـﺔ ،
اﻟﻣوﺣدات ،اﻷﻓران اﻟﻛﻬرﺑﺎﺋﯾﺔ ،أﻓران اﻟﺣث ... ،اﻟﺦ (.ﺣﯾث ﺗؤدى اﻟطﺑﯾﻌﺔ ﻏﯾر اﻟﺣﺛﯾـﺔ ﻟﻬـذﻩ
اﻷﺣﻣﺎل إﻟﻰ ﺗﺑدﯾد ﺟزء ﻣن اﻟطﺎﻗﺔ اﻟﻣﻐذﯾﺔ ﻟﻬﺎ ﻓﻲ ﺻورة ﻗدرة ﻏﯾر ﻓﻌﺎﻟـﺔ ﺗﺳـﺗوﺟب اﻟﻌﻣـل ﻋﻠـﻰ
اﺳﺗﯾﻌﺎﺑﻬﺎ ،وذﻟك ﻋن طرﯾـق ﺗﻌـوﯾض ﻫذا اﻟﺟزء ﺑواﺳطﺔ ﻣﺻدر ﺧﺎرﺟﻲ ﯾﻌﻣل ﻛﻣوﻟد ﻟﻠﻘدرة ﻏﯾر
اﻟﻔﻌﺎﻟﺔ ) (KVAR-Generatorﻹﺿﺎﻓﺔ ﻗدرة ﻏﯾر ﻓﻌﺎﻟﺔ ﻟﻣﻧظوﻣﺔ اﻟﻘـدرة اﻟﻛﻬرﺑﺎﺋﯾـﺔ وﯾﻛـون
ﻋﺎدة ﻋن طرﯾق ﻣﻛﺛف ﯾﺗم ﺗوﺻﯾﻠﻪ ﻋﻠﻰ اﻟﺗوازى ﻣﻊ اﻟﺣﻣل اﻟﻣراد ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ﻟﻪ.
ﯾؤدى ﺗرﻛﯾب اﻟﻣﻛﺛف ﻣﻊ اﻷﺣﻣﺎل اﻟﺣﺛﯾﺔ ﻓﻰ ﻧﻔس اﻟداﺋرة إﻟﻰ ﺗﺑﺎدل اﻟﺗﯾـﺎر ﺑﯾﻧﻬﻣـﺎ ﻋﻠـﻰ
ﻧﺣـو ﯾﺟﻌـل اﻟﺗﯾـﺎر اﻟﻣﺗﻘـدم ) (Leading currentاﻟﻣﺳـﺣوب ﺑواﺳـطﺔ اﻟﻣﻛﺛـف ﯾﻌـﺎدل ﺟـزء
(Laggingﻟﻸﺣﻣــﺎل اﻟﺣﺛﯾ ـﺔ اﻟــﻼزم ﻟﻠﻣﻐﻧطــﺔ ﻓﻠــذا ﯾﻌﺗﺑــر ﻣــن اﻟﺗﯾــﺎر اﻟﻣﺗــﺄﺧر ) current
اﻟﻣﻛﺛف ﻫو اﻷداة اﻷﺳﺎﺳﯾﺔ اﻟﺗﻲ ﺗﺳﺗﺧدم ﻟﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ،وﯾﻧﻌﻛس ذﻟك اﻧﻌﻛﺎﺳﺎ إﯾﺟﺎﺑﯾــﺎً
ﻋﻠﻰ أداء اﻟﻣﻧظوﻣﺔ ﻣن ﺣﯾث ﺗﺧﻔﯾض اﻟطﺎﻗﺔ اﻟﻣﻔﻘـودة ﻓـﻲ اﻟﻛـﺎﺑﻼت واﻟﺧطـوط وزﯾـﺎدة ﺳـﻌﺎﺗﻬﺎ
ﻋﻧـــد ﻧﻔــس اﻟﺣﻣــل ،ﺣﯾــث ﯾﻣﻛــن ﻟﻬــذﻩ اﻟﻛــﺎﺑﻼت واﻟﺧطــوط ﺗﺣﻣــل ﻧﻘــل ﻗــــدرات إﺿﺎﻓﯾــــﺔ ﻷﺣﻣـــﺎل
(Apparent powerﻟـذﻟك اﻟﺣﻣـل، إﺿﺎﻓﯾــﺔ ،ﻛﻣــﺎ ﺗـﻧﺧﻔض اﻟﻘـدرة اﻟظﺎﻫرﯾـﺔ )kVA
وﻛذﻟك ﺗزداد اﻟﻘدرة اﻟﻣﺗﺎﺣﺔ ﻓﻲ اﻟﻣﺣوﻻت اﻟﻣﺳـﺗﺧدﻣﺔ ﻓـﻲ اﻟﺷـﺑﻛﺔ وﺗﺗﺣﺳـن اﻟﺟﻬـود ﻋﻧـد ﻣراﻛـز
اﻷﺣﻣﺎل.
وﺑذﻟك ﯾﻛـون ﻟﺗﺣﺳـﯾن ﻣﻌﺎﻣـل اﻟﻘـدرة ﻓـﻲ ﻣﻧظوﻣـﺔ ﻧﻘـل وﺗوزﯾـﻊ اﻟﻘـوى اﻟﻛﻬرﺑﺎﺋﯾـﺔ ﻓﺎﺋـدة
ﻗﺻــوى ﺣﯾــث ﯾﺗــﯾﺢ اﻻﺳــﺗﻔﺎدة ﻣــن ﻓــﺎﺋض اﻟﺳــﻌﺔ ﻟﻣﻬﻣــﺎت اﻟﺷــﺑﻛﺎت اﻟﻘﺎﺋﻣــﺔ ﻓــﻲ ﺗﻐذﯾــﺔ أﺣﻣــﺎل
إﺿﺎﻓﯾﺔ دون اﻟﺣﺎﺟﺔ إﻟﻰ ﺗوﺳـﻌﺗﻬﺎ أو إﻋـﺎدة ﻫﯾﻛﻠﺗﻬـﺎ ،وﻛـذﻟك إﻟـﻰ ﺗـوﻓﯾر ﻧﻔﻘـﺎت إﻧﺷـﺎء ﺷـﺑﻛﺎت
ﺟدﯾدة وﺗوﺟﯾﻬﻬﺎ ﻻﺳﺗﺛﻣﺎرات أﺧرى ﻋﻠﻰ اﻟﻣﺳﺗوى اﻟﻘوﻣﻲ.
٤٦
اﺳﺗﺑدال اﻟﻣﻌدات اﻟﻣﺳﺗﺧدﻣﺔ ﺑﺄﺧرى ذات ﻣﻌﺎﻣل ﻗدرة أﻋﻠﻰ ،ﻣﺛل اﺳـﺗﺑدال اﻟﻛـﺎﺑﺢ
اﻟﻣﻐﻧﺎطﯾﺳﻰ ﻟﻠﻣﺻﺎﺑﯾﺢ اﻟﻔﻠورﯾﺔ ﺑﻛﺎﺑﺢ إﻟﻛﺗروﻧﻰ.
-ﯾـؤدى اﻟﺗﺧطﯾط اﻟﺟﯾد ﻟﻠﺷﺑﻛﺎت اﻟداﺧﻠﯾﺔ ﻟﻠﻣﻧﺷﺂت أﺛﻧﺎء ﻣرﺣﻠﺔ اﻟﺗﺻﻣﯾم ﺑﺗﻘﺳﯾم
اﻷﺣﻣﺎل إﻟﻰ ﻣﺟﻣوﻋﺎت ﺑﺣﯾث ﺗﺣﺗوى ﻛل ﻣﺟﻣوﻋﺔ ﻋﻠﻰ ﻛل ﻣن اﻷﺣﻣﺎل اﻟﺗﺄﺛﯾرﯾﺔ
واﻟﺳـــﻌوﯾﺔ ﻣﻌـــﺎ ،إﻟـــﻰ ﺧﻔـــض اﻟﻘـــدرة ﻏﯾـــر اﻟﻔﻌﺎﻟـــﺔ اﻟﻣﺳـــﺗﻬﻠﻛﺔ ﺑواﺳـــطﺔ اﻟﺣﻣـــل
اﻻﺟﻣــﺎﻟﻰ ،ﺣﯾــث ﺗﻘــوم اﻷﺣﻣــﺎل اﻟﺳــﻌوﯾﺔ ﺑﺗﻌــوﯾض اﻟﺷــﺑﻛﺔ ﺑﺟــزء ﻣــن اﻟﻘــدرة ﻏﯾــر
اﻟﻔﻌﺎﻟـــﺔ اﻟﻣطﻠوﺑــــﺔ ﻟﻠﺣﻣــــل إﺟﻣـــﺎﻻً ،وﺑﺎﻟﺗــــﺎﻟﻲ ﺗﻧﺧﻔــــض اﻟﻘــــدرة اﻟظﺎﻫرﯾـــﺔ اﻟﻛــــﻠﯾﺔ
) (Total apparent powerﻋﻧــد ﻧﻘطــﺔ اﻟﺗوﺻــﯾل اﻟﻣﺧﺗــﺎرة ﻣــﻊ ﺷــﺑﻛﺔ
اﻟﺗﻐذﯾﺔ ﻟﻠﻘدرة اﻟﻛﻬرﺑﺎﺋﯾﺔ .
-ﯾﻌﺗﺑر ﺗﺣدﯾد ﺳﻌﺔ اﻟﻣﺣرﻛﺎت واﻟﻣﺣوﻻت ﺑﺷﻛل ﻣﻧﺎﺳب وﻛذﻟك ﻋدم ﺗﺷﻐﯾﻠﻬﺎ ﻓـﻲ
اﻟوﻗــت اﻟــذي ﻻ ﺗﺣﺗﺎﺟــﻪ اﻟﻌﻣﻠﯾــﺎت ،ﻣــن أﻫــم ﻋواﻣــل ﺗﺣﺳــﯾن ﻣﻌﺎﻣــل اﻟﻘــدرة ﻓــﻲ
اﻟﺷﺑﻛﺎت اﻟﻣﻐذﯾﺔ ﻟﻬﺎ.
ﻣﻠﺣوظﺔ:
ﯾﺟــب ﻓــﻰ ﻛــل اﻷﺣ ـوال دراﺳــﺔ ﺗﺣدﯾــد اﻟﻌﺎﺋـــد اﻻﻗﺗﺻــﺎدى اﻟﻣﺗرﺗــب ﻋﻠــﻰ )(١
إﺿﺎﻓـﺔ أﺣﻣـﺎل ﺳﻌوﯾـﺔ ﻟﻣﻧظوﻣﺔ اﻟﻘدرة واﺧﺗﯾﺎر اﻟﺣــﻣل اﻟﺳـﻌوى اﻟﻣﻧﺎﺳـب ﻟﻛــل
ﺣﺎﻟﺔ ،ﺳواء ﻛﺎﻧـت ﻣﺟﻣوﻋﺎت ﻣﻛﺛﻔﺎت اﺳﺗﺎﺗﯾﻛﯾﺔ (Static condenser
Synchronous ) banksأو اﺳـــــﺗﺧدام اﻟﻣﻛﺛﻔـــــﺎت اﻟﻣﺗزاﻣــــــﻧﺔ* )
(condenserﺧﺻوﺻــﺎ ﻓــﻲ ﻣﺣطــﺎت اﻟﻘــوى اﻟﻔرﻋﯾــﺔ اﻟﺗــﻲ ﺗﻐــذى ﺗﺟﻣﻌــﺎت
رﺋﯾﺳﯾﺔ .
) (٢ﯾﺑــــﯾن اﻟﺷــــﻛل وﺣــــدة ذات ﻣﻠــــف وﻣﻛﺛــــف ﻟﻠﺣــــد ﻣــــن ﺗــــﺄﺛﯾر ﻣﺣﺗــــوى
اﻟﺗواﻓﻘﯾﺎت ) (Harmonic contentsوﻛذﻟك ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة.
ﻣﻛﺛف
ﻛوﻧﺗﺎﻛﺗور
ﻣرﺷﺢ
)(detuned filter
ث
.
٤٧
اﻟﻣﻛﺛﻔﺎت اﻟﻣﺗزاﻣﻧﺔ ﻋﺑﺎرة ﻋن ﻣﺣرﻛﺎت ﺗزاﻣﻧﯾﺔ ) (Synchronous motorsﺗﻌﻣل *
ﺑدون ﺣﻣل
ﯾﺟــب ﺗـواﻓر اﻟﺧﺻــﺎﺋص اﻟﺗﺎﻟﯾــﺔ ﻓــﻰ اﻟﻣﻛﺛﻔــﺎت اﻟﻣﺳــﺗﺧدﻣﺔ ﻓــﻰ ﺗﺻــﺣﯾﺢ ﻣﻌﺎﻣــل -
اﻟﻘدرة:
٤٨
ﯾﻛون اﻟﻔﻘد اﻟﺧـﺎص ﺑـﺎﻟﻣﻛﺛف ﻣﻧﺧﻔﺿـﺎ )ﻓـﻲ ﺣـدود ٠.٥ -٠.٤وات / )(١
ك.ﻓﺎر( ﻣﻣﺎ ﯾؤدى إﻟﻰ ﺗﺧﻔـﯾض اﻟﺗﻛﻠﻔـﺔ اﻟﺟﺎرﯾـﺔ ) ،(Running costواﻟﺣـد
ﻣن اﻻرﺗﻔﺎﻋﺎت ﻓـﻲ درﺟـﺎت اﻟﺣـرارة ﻟﺿـﻣﺎن ﺳـﻼﻣﺔ اﻟﻌـزل اﻟﺧـﺎص ﺑـﺎﻟﻣﻛﺛف ،
وﻛذا ﺿﻣﺎن ﺷروط ﺗﺷﻐﯾل ﻣﻧﺎﺳﺑﺔ ﻟﻠﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ .
إﺿﺎﻓﺔ ﻣﻘﺎوﻣﺔ ﺗﻔرﯾﻎ )أوﻣﯾـﺔ( ﻣﺳـﺗﻘﻠﺔ )(Discharge resistor )(٢
ﻟﻛل وﺣدة ﻣﻛﺛف ﻣن ﻣﺟﻣوﻋﺔ وﺣدات اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳـﺗﺧدﻣﺔ ﺣﯾـث ﯾـؤدى ذﻟـك
إﻟﻰ أﻧﻪ ﻓﻲ ﺣﺎﻟﺔ ﺣدوث اﻧﻬﯾﺎر ﻹﺣدى ﻣﻘﺎوﻣﺎت اﻟﺗﻔرﯾﻎ أو أﻛﺛـر ﯾﻣﻛـن ﻟﺑـﺎﻗﻲ
اﻟوﺣدات اﻻﺳﺗﻣرار ﻓﻲ ﺗﻔرﯾـﻎ اﻟﺷـﺣﻧﺎت ﻣـن ﺧـﻼل ﻣﻘﺎوﻣـﺎت اﻟﺗﻔرﯾـﻎ اﻟﺧﺎﺻـﺔ
ﺑﻬﺎ ،ﺑﻣﺎ ﻓﻲ ذﻟك اﻟﻣﻛﺛﻔﺎت اﻟﺗﻲ اﻧﻬﺎرت ﻣﻘﺎوﻣﺎت اﻟﺗﻔرﯾﻎ ﻟﻬﺎ .
ﯾﺟب أن ﯾﺗﺿﻣن ﺗﺻﻣﯾم ﻛـل ﻣﻛﺛـف ﺧﺎﺻـﯾﺔ اﻻﻟﺗﺋـﺎم اﻟـذاﺗﻲ ) Self )(٣
،(healingاﻟﺗــﻲ ﺗــؤدى إﻟــﻰ اﻟﺗﺋــﺎم اﻟﻌــزل ﺗﻠﻘﺎﺋﯾــﺎ ﻋﻧــد ﺗﻌــرض أﺟــزاء ﻣﻧــﻪ
ﻟﻠﺗﺻــدع ﻧﺗﯾﺟــﺔ اﻟﺗﻌــرض ﻟﺟﻬــود زاﺋــدة ﻣؤﻗﺗــﺔ ،ﻛﺎرﺗﻔﺎﻋــﺎت اﻟﺟﻬــد اﻟﺗــﻲ ﺗﺣــدث
أﺛﻧﺎء ﻣراﺣل اﻟﺗﺷﻐﯾل ﻏﯾر اﻟﻌﺎدﯾﺔ ﻟﻣﻧظوﻣـﺔ اﻟﻘـدرة ،ﻣﺛﻠﻣـﺎ ﯾﺣـدث ﻓـﻲ اﻟﺣـﺎﻻت
اﻟﻌـــﺎﺑرة ) ،(Transientsواﻟظـــواﻫر اﻷﺧـــرى اﻟﺗـــﻲ ﺗﺗﻌـــرض ﻟﻬـــﺎ اﻟﻣﻧظوﻣـــﺔ
وﺗﺣدث ﺑﻬﺎ ارﺗﻔﺎﻋﺎت ﻣﻔﺎﺟﺋﺔ ﻟﻠﺟﻬد .
ﯾﺟب أن ﺗزود ﻛل وﺣـدة ﻣﻛﺛﻔـﺎت ﺑـﺄداة ﻓﺻـل )ﻗـﺎطﻊ ﺗﯾـﺎر أو ﻓﯾـوزات( )(٤
) (Breaker or fusesﺑﺷــﻛل ﻣﺳــﺗﻘل ،ﺣﺗــﻰ ﯾﻣﻛــن ﻓﺻــل اﻟﺗﯾــﺎر ﻋــن
وﺣـــدة أو ﻣﺟﻣوﻋـــﺔ اﻟﻣﻛﺛﻔـــﺎت اﻟﺗـــﻲ ﯾﺣـــدث ﺑﻬـــﺎ ﺧﻠـــل ،ﻛـــﺄن ﯾﺗﻌـــرض ﻋزﻟﻬـــﺎ
ﻟﻼﻧﻬﯾﺎر ،ﻣﻊ اﺳﺗﻣرار ﺑﺎﻗﻲ اﻟوﺣدات ﻓﻲ اﻟﻌﻣل دون أن ﺗﺗﺄﺛر اﻟﻣﻧظوﻣﺔ ﻟﺣﯾن
إﺟ ـراء اﻟﺻــﯾﺎﻧﺔ اﻟﻼزﻣــﺔ ﻟﻠوﺣــدة اﻟﺗــﻰ ﺑﻬــﺎ ﻋطــب إن أﻣﻛــن أو ﺗﻐﯾﯾــر اﻟــﻼزم ،
وﻫــذا ﯾﺳــﺎﻫم ﺑﺷــﻛل إﯾﺟــﺎﺑﻲ ﻓــﻲ زﯾــﺎدة اﻟﺛﻘــﺔ واﻟﻌــول ) ( Reliabilityﻓــﻰ
ﻣﻧظوﻣﺔ اﻟﻘدرة وزﯾﺎدة ﻓرص ﺗﻌﺎﻓﯾﻬﺎ ﻓﻲ ﻣواﺟﻬﺔ اﻵﺛـﺎر اﻟﺳـﻠﺑﯾﺔ اﻟﻧﺎﺟﻣـﺔ ﻋـن
ظروف اﻟﺗﺷﻐﯾل ﻏﯾر اﻟﻌﺎدﯾﺔ ﻟﺿﻣﺎن ﺗﻐذﯾﺔ ﻛﻬرﺑﺎﺋﯾﺔ ﺟﯾدة ﻟﻸﺣﻣﺎل ﻋﻠﻰ وﺟـﻪ
اﻟﻌﻣوم .
ﯾﺟـب أن ﯾﺣﺗـوى ﻛـل ﻣﻛﺛــف ﺑﺷـﻛل ﻣﺳـﺗﻘل ﻋﻠــﻰ أداة ﻓﺻـل ﻋﻧـد زﯾــﺎدة )(٥
اﻟﺿﻐط ) (Over pressure deviceداﺧل اﻟوﻋﺎء ﻟﺿﻣﺎن ﻋـدم ﺗﻌـرض
اﻟﻣﻛﺛف ﻻﻧﻬﯾﺎر ﯾﺗﻌذر ﺗدارﻛﻪ ﻋن طرﯾق ﺧﺎﺻﯾﺔ اﻻﻟﺗﺋﺎم اﻟذاﺗﻲ ﻟﻠﻣﻛﺛف .
ﯾﺟــب اﻟﺗﺄﻛﯾــد ﻋﻠــﻰ ﺿــﻣﺎن ﻗــوة اﻟﻌــزل اﻟﻛﻬرﺑــﺎﺋﻲ ﻟﻠﻣﻛﺛــف ،واﺳــﺗﻘرارﻩ ، )(٦
وزﯾﺎدة ﻋﻣرﻩ اﻻﻓﺗراﺿﻲ ،ﻣـن ﺧـﻼل اﺧﺗﺑـﺎرات اﻟﺟﻬـود اﻟﻌﺎﻟﯾـﺔ اﻟﺗـﻲ ﺗﺟـرى ﻟـﻪ
طﺑﻘﺎ ﻟﺣدود اﻟﻘﯾﺎﺳﺎت اﻟﻣﻧﺻوص ﻋﻠﯾﻬﺎ ﻓﻲ اﻟﻣواﺻـﻔﺎت اﻟﻣطﻠـوب ﺗواﻓرﻫـﺎ ﻓـﻲ
٤٩
اﻟﻣﻛﺛــف ،وذﻟــك ﺣﺗــﻰ ﻻ ﺗﺗــﺄﺛر ﺳــﻼﻣﺗﻪ أﺛﻧــﺎء ﻋﻣﻠﯾــﺎت اﻟﻔﺻــل ﻋﻧــد اﻟﺟﻬــود
اﻟزاﺋدة ﺑواﺳطﺔ وﺳﯾﻠﺔ اﻟﻔﺻل اﻟﻣﺳﺗﺧدﻣﺔ وﻣﺎ ﻗد ﯾﻧﺟم ﻋﻧﻬـﺎ ﻣـن ﺷـرر ﯾﻣﻛـن
أن ﯾﺗﺳﺑب ﻓﻲ اﻧﻬﯾﺎرات ﺟزﺋﯾﺔ )ﺗﺻدﻋﺎت( ﻟﻠﻌزل ،أو ﺗﻌرﺿﻪ ﻟﻼﻧﻬﯾﺎر اﻟﺷﺎﻣل
ﻓﻲ ﺣﺎﻟﺔ ﺿـﻌﻔﻪ وﻋـدم ﻗدرﺗـﻪ ﻋﻠـﻰ ﺗﺣﻣـل درﺟـﺎت اﻟﺣـرارة اﻟﻌﺎﻟﯾـﺔ اﻟﻧﺎﺗﺟـﺔ ﻋـن
اﻟﺷرارة ﻗﺑل إطﻔﺎءﻫﺎ .
P1
)(KW Vref
Q1
S1 )(KVAR
)(KVA
و اﻟﺣﺎﻟــﺔ اﻟﺛﺎﻧﯾــﺔ اﻟﺗــﻲ ﯾﺗﻘــدم ﻓﯾﻬــﺎ اﻟﺗﯾــﺎر ﻋــن اﻟﺟﻬــد ﻓــﻲ زاوﯾــﺔ اﻟطــور ﻧﺗﯾﺟــﺔ ﻟﻣــرورﻩ ﺧــﻼل
اﻟﻣﻣﺎﻧﻌﺔ اﻟﺳﻌوﯾﺔ ﻟﻠﻣﻛﺛﻔﺎت ،وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﯾﻣﻛن اﻋﺗﺑﺎر اﻟﻣﻛﺛف ﻋﻧﺻر إﺿـﺎﻓﺔ ﻟﻠﻘـدرة ﻏﯾـر
اﻟﻔﻌﺎﻟﺔ ،وﯾﻣﻛن ﺣﺳﺎب ﻣﻌﺎﻣل اﻟﻘدرة ) (p.f2ﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﻣن اﻟﻣﻌﺎدﻟﺔ:
Active Power ) P (kW
p .f 2 cos 2 2
)Apparent Power S 2 (kVA
٥٠
S2
)(kVA Q2
)(kVAR
Vref
P2
)(kW
وﺣﯾث أن اﻟﻘدرة اﻟﻔﻌﺎﻟﺔ ) (Active Powerﺛﺎﺑﺗﺔ ﻓﻲ اﻟﺣﺎﻟﺗﯾن ،ﺑﯾﻧﻣﺎ ﺗﺗﻐﯾـر ﻛـل ﻣـن
اﻟﻘــدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ واﻟﻘــدرة اﻟظﺎﻫرﯾــﺔ ﺑﺗﻐﯾــر ﻣﻌﺎﻣــل اﻟﻘــدرة ،ﻟــذا ﻓــﯾﻣﻛن اﻟﺗﻌﺑﯾــر ﻋــن اﻟﻌﻼﻗــﺔ
اﻟرﯾﺎﺿﯾﺔ اﻟﺗﻲ ﯾﺣﺳب ﻣﻧﻬﺎ ﻣﻌﺎﻣل اﻟﻘدرة ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻲ ﻣن اﻟﻣﻌﺎدﻟﺔ
Reactive Power (kVAR) Active Power (kW) tan
وﻋﻠﯾﻪ ﯾﻣﻛن اﺳﺗﻧﺗﺎج ﻗﯾﻣﺔ اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻗﺑل وﺑﻌد ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣـل اﻟﻘـدرة ﻛﻣـﺎ ﻫـو
ﻣوﺿﺢ ﺑﺎﻟﺷﻛل ):(٥ -٩
)P (kW Vref
Q2
)(kVAR
S2
)(kVA )Q1 (kVAR
S1 Qc
)(kVA )(kVAR
ﺣﯾث أن :
ﻣﻌﺎﻣل اﻟﻘدرة ﻗﺑل اﻟﺗﺻﺣﯾﺢ ) = 1 cos( p. f 1
ﻣﻌﺎﻣل اﻟﻘدرة ﺑﻌد اﻟﺗﺻﺣﯾﺢ ) = 2 cos ( p. f 2
1 tan اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻋﻧد ﻣﻌﺎﻣل اﻟﻘدرة ) = ( p. f 1اﻟﻘدرة اﻟﻔﻌﺎﻟﺔ ×
اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ ﻋﻧد ﻣﻌﺎﻣل اﻟﻘدرة ) = ( p. f 2اﻟﻘدرة اﻟﻔﻌﺎﻟﺔ × 2 tan
وﺑذﻟك ﺗﺻﺑﺢ ﻗﯾﻣﺔ اﻟﻘدرة ﻏﯾر اﻟﻔﻌﺎﻟﺔ اﻟﻼزﻣﺔ ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ﻫﻲ ) (Qcواﻟﺗﻲ
ﯾﻣﻛن ﺣﺳﺎﺑﻬﺎ ﻣن اﻟﻣﻌﺎدﻟﺔ
Qc(kVAR) = P(kW) × 1 tan [ ] 2 -tan
٥١
وﯾﺗﺿﺢ ﻣن اﻟﺷﻛل أﯾﺿﺎً اﻧﺧﻔﺎض اﻟﻘـدرة اﻟظﺎﻫرﯾـﺔ ) S1 (kVAﻟﺗﺻـﺑﺢ ﻋﻧـد اﻟﻘﯾﻣـﺔ
) ، S2 (kVAوذﻟــك ﻧﺗﯾﺟــﺔ ﺗﺻــﺣﯾﺢ ﻣﻌﺎﻣــل اﻟﻘــدرة وﻫــو ﻣــﺎ ﯾﻌـود ﺑﺎﻹﯾﺟــﺎب ﻋﻠــﻰ زﯾــﺎدة ﺳــﻌﺔ
ﻣﻬﻣﺎت ﺷﺑﻛﺔ اﻟﺗﻐذﯾﺔ )اﻟﻣﺻدر( ﻣـن ﻣﺣـوﻻت وﻛـﺎﺑﻼت ،ﻛﻣـﺎ ﯾﻔﯾـد اﻟﻣﺷـﺗرك )اﻟﺣﻣـل( ﻓـﻲ زﯾـﺎدة
اﻟﻘــدرة اﻟﻣﺗﺎﺣــﺔ ﻟﻠﺷــﺑﻛﺔ اﻟداﺧﻠﯾــﺔ ﻟﻠﻣﻧﺷــﺄة ،إو ﺗﺎﺣــﺔ إﺿــﺎﻓﺔ أﺣﻣــﺎل أﺧــرى ﻟﻬــﺎ دون اﻟﺣﺎﺟــﺔ إﻟــﻰ
إﻧﺷﺎء ﺷﺑﻛﺎت إﺿﺎﻓﯾﺔ .
ﯾﻣﻛن ﺗﺣدﯾد ﺳﻌﺔ اﻟﻣﻛﺛﻔﺎت اﻟﻣطﻠوب ﺗوﺻﯾﻠﻬﺎ ﻋﻠﻰ اﻟﺗوازي ﻣﻊ اﻟﺣﻣل ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣـل
اﻟﻘدرة ﻣن اﻟﺟدول اﻟﺗﺎﻟﻲ ،واﻟذي ﯾﺣﺗوى ﻋﻠﻰ ﻗـﯾم ﺳـﻌﺎت اﻟﻣﻛﺛﻔـﺎت ﻧظﯾـر ﻛـل ﺣﻣـل ﺣﺛـﻲ ﻋﻠـﻰ
ﺿوء ﻣﻌﺎﻣل اﻟﻘدرة اﻟﺧﺎص ﺑذﻟك اﻟﺣﻣل واﻟﻣطﻠوب ﺗﺻﺣﯾﺣﻪ ،وﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف .
ﻋﻠﻰ ﺳﺑﯾل اﻟﻣﺛﺎل إذا ﻛﺎن ﻣﻌﺎﻣل اﻟﻘدرة ) (cos Φاﻷﺻـﻠﻰ ﻣﺳـﺎوﯾﺎً ) (٠.٧واﻟﻣطﻠـوب
ﺗﺣﺳﯾﻧﻪ إﻟﻰ ) (٠.٩٣ﺗﻛون ﺳﻌﺔ اﻟﻣﻛﺛﻔﺎت اﻟﻣطﻠوﺑﺔ ) (٠.٦٢٥ك.ﻓﺎر ﻟﻛل ﻛﯾﻠـووات ،ﺑﯾﻧﻣـﺎ إذا
ﻛــﺎن ﻣطﻠــوب ﺗﺣﺳــﯾن ﻣﻌﺎﻣــل اﻟﻘــدرة إﻟــﻰ ) (٠.٩٥ﺗﻛــون ﺳــﻌﺔ اﻟﻣﻛﺛﻔــﺎت اﻟﻣطﻠوﺑــﺔ )(٠.٦٩١
ك.ﻓﺎر ﻟﻛل ﻛﯾﻠووات وﻫﻛذا .
٥٢
before kVAR rating of capacitor bank to Install per kW, to Improve Cos Φ (the power factor) or tan
compensation Φ, to a given value
tan Φ 0,75 0.59 0.48 0.46 0.43 0.40 0.36 0.33 0.29 0.25 0.20 0.14 0.0
tan Φ cos Φ
cos Φ 0.80 0.86 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1
2.29 0.40 1.557 1.691 1.805 1.832 1.861 1.895 1.924 1.959 1.998 2.037 2.085 2.146 2.28
222 0.41 1474 1.625 1.742 1.769 1.798 1.831 1.840 1.896 1.935 1.973 2.021 2082 8
2.22
2-16 0.42 1.413 1.561 1.681 1.709 1.738 1.771 1.800 1.836 1.874 1.913 1.961 2.022 5
2.16
2-10 0.43 1.356 1.499 1.624 1.651 1.680 1.713 1.742 1.778 1.816 1.855 1.903 1.964 4
2.10
204 0.44 1.290 1.441 1.558 1-585 1.614 1.647 1.677 1.712 1.751 1.790 1.837 1.899 7
2.041
198 0.45 1.230 1.384 1.501 1.532 1.561 1.592 1.628 1.659 1.695 1.737 1.784 1.846 1.98
1.93 0.46 1.179 1.330 1.446 1.473 1.502 1.533 1-567 1.600 1.636 1.677 1.725 1.786 8
1.92
1.88 0.47 1.130 1.278 1.397 1.425 1.454 1.485 1.519 1.532 1.588 1.629 1.677 1.758 9
1.881
1.83 0.48 1.076 1.228 1.343 1.370 1.400 1.430 1.464 1.497 1.534 1.575 1.623 1.684 1.826
1.78 0.49 1.030 1.179 1.297 1.326 1.355 1.386 1.420 1.453 1.489 1.530 1.578 1.639 1.782
1.73 0.50 0.982 1 232 1.248 1.276 1.303 1.337 1.369 1.403 1.441 1.481 1.529 1390 1.732
1-69 0.51 0.936 1.087 1.202 1.230 1.257 1.281 1.323 .357 1.395 1.435 1.483 1.544 1.686
164 0,52 0.894 1.043 1.160 1.188 1.215 1.249 1.281 .315 1.353 1.393 1.441 1.502 1.644
1.60 0.53 0.850 1.000 1.116 1.144 1.171 1.205 1.237 .271 1.309 1.349 1.397 1.458 1.600
1.56 0.54 0.809 0.959 1.075 1.103 1.130 1.164 1.196 .230 1.268 1.308 1.356 1.417 1.559
1.52 0.55 0.769 0.918 1.035 1.063 1.090 1.124 1.156 .190 1.228 1.266 1.316 1.377 1.519
1.48 0.56 0.730 0879 0.996 1.024 1.051 1.085 1.117 .151 1.189 1.229 1.277 1.338 1.480
1.44 0.57 0.692 0.841 0.958 0.986 1.013 1.047 1.079 .113 1.151 1-191 1.239 1.300 1.442
1.40 0.58 0.665 O.805 0.921 0-949 0.976 1.010 1-042 .076 1.114 1.154 1.202 1263 1.405
1.37 0.59 0.618 0.768 0.884 0.912 0.939 0.973 1.005 .039 1.077 1.117 1.165 1.226 1.368
1.33 0.60 0.584 0.733 0.849 0-878 0.905 0.939 0.971 .00S 1-043 1.083 1.131 1.192 1.334
1.30 0.61 0.549 0.699 0.815 0.843 0.870 0.904 0.936 0.970 1.008 1.048 1.096 1.157 1.29
1.27 0.62 0.515 0.665 0.781 0.809 0.836 0.870 0.902 0.936 0.974 1.014 1.062 1.123 9
1.26
1.23 0.63 0.483 0.633 0.749 0.777 0.804 0.838 0.870 0.904 0-942 0.962 1.030 1.091 5
1.23
1.20 0.64 0.450 0.601 0.716 0.744 0.771 0.805 0.837 0.871 0.909 0.949 0.997 1.058 3
1.20
1.17 0.65 0.419 0.569 0.685 0.713 0.740 0.774 0.806 0.840 0.878 0-918 0.966 1.007 0
1.16
1.14 0.66 0.388 0.538 0.654 0.662 0.709 0.743 0.775 0.609 0.847 0.887 0.935 0.996 9
1.13
1.11 0.67 0.358 0.508 0.624 0.652 0.679 0.713 0.745 0.779 0.817 0.857 0.905 0.966 8
1.10
1.08 0.68 0.329 0.478 0.595 0.623 0.650 0.684 0-716 0.750 0.788 0.828 0.876 0.937 8
1.07
1.05 0.69 0.299 0.449 0.565 0.593 0.620 0.654 0.666 0.720 0.758 0.798 0.840 0.907 9
1.04
1.02 0,70 0.270 0.420 0.536 0.564 0.591 0.625 0.657 0.691 0.729 0.769 0.811 0-878 9
1.02
0.99 0.71 0.242 0.392 0.508 0.536 0.563 0.597 0.629 0.663 0.701 0.741 0.783 0.850 0
0.99
0.96 0.72 0.213 0.364 0.479 0.507 0.534 0.566 0.600 0.634 0.672 0.712 0.754 0.821 2
0.96
0.94 0.73 0.186 0.336 0.452 0.480 0.507 0.541 0.573 0.607 0.645 0.685 0.727 0-794 3
0.93
0.91 0.74 0.159 0.309 0.425 0.453 0.480 0.514 0.546 0.580 0.618 0.658 0.700 0.767 6
0.90
0.88 0.7S 0.132 0.82 0.396 0.426 0.453 0.487 0.519 0.553 0.591 0.631 0.673 0.740 9
0.88
0.86 0.76 0.105 0.255 0.371 0.399 0.426 0.460 0.492 0.526 0.564 0.6O4 0.652 0.713 2
0-
0.83 0.77 0.079 0.229 0.345 0.373 0.400 0.434 0.466 0.500 0.538 0.578 0.620 0.687 855
0.82
0.80 0.78 0053 0.202 0.319 0.347 0.374 0.408 0.440 0.474 0.512 0.552 0.594 0.661 9
0.80
0.78 0.79 0.026 0.176 0.292 0.320 0.347 0.381 0.413 0.447 0.485 0.525 0.567 0.634 3
0-
0.75 0.80 0.150 0.266 0.294 0.321 0.355 0.387 0.421 0.459 0.499 0.541 0.608 776
0.750
0.72 0.81 0.124 0.240 0.268 0.295 0.329 0.361 0.395 0.433 0.473 0.515 0-582 0.72
0.70 0.82 0.098 0.214 0.242 0.269 0.303 0.335 0.369 0.407 0.447 0-489 0.556 4
0.698
0.67 0.83 0.072 0.188 0.216 0.243 0.277 0.309 0.343 0.381 0.421 0.463 0.530 0.67
0.65 0.84 0.046 0.162 0.190 0.217 0.251 0.263 0.317 0.355 0.395 0.437 0.504 2
0.645
0.62 085 0.020 0.136 0.164 0-191 0.225 0.257 0.291 0.329 0.369 0-417 0.478 0.620
0.59 0.66 0.109 0.140 0.167 0.198 0.230 0.264 0.301 0.343 0-390 0.450 0.593
0.57 0.87 0.083 0.114 0.141 0.172 0.204 0.238 0.275 0317 0.364 0.424 0.56
0.54 0.88 0.054 0.O85 0.112 0.143 0.175 0.209 0.246 0.288 0.335 0.395 7
0.53
0.51 0.89 0.028 0.059 0.086 0.117 0149 0.183 0.230 0.262 0.309 0.369 8
0.51
0.48 0.90 0.031 0.058 0.089 0.121 0.155 0.192 0.234 0.281 0.341 2
0.48
4
٥٣
ﺗﺣدﯾد ﻣواﻗﻊ اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻰ ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة
ﯾﺗم ﺗرﻛﯾب ﻣﺟﻣوﻋﺎت اﻟﻣﻛﺛﻔﺎت ﻋﺎدة ﺑﻌد اﻟﻌدادات اﻟﻣرﻛﺑﺔ ﻟـدى اﻟﻣﺷـﺗرك ،وﻋﻠـﻰ ﺛﻼﺛـﺔ
ﻣﺳﺗوﯾﺎت ﻣﺗﺑﺎﯾﻧﺔ ﻟﻠﺗرﻛﯾﺑﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟداﺧﻠﯾﺔ ﻟﻠﻣﻧﺷﺄة ﻛﻣﺎ ﯾﻠﻲ-:
ﻋﻧــد ﻟوﺣـﺔ اﻟﻣﻔﺎﺗﯾـﺢ اﻟرﺋﯾﺳﯾﺔ ﻟﻠوﺣﺔ اﻟﺟﻬد اﻟﻣﻧﺧﻔض ﻛﻣﺎ ﻫو ﻣوﺿـﺢ )(١
Tr
S
C
ﯾﺣﻘق اﻟﺗرﻛﯾب ﻓﻲ ﻫذا اﻟﻣوﺿﻊ اﺳﺗﯾﻌﺎﺑﺎ ﺷﺎﻣﻼ ﻟﻣﺣﺗوﯾﺎت أﺣﻣﺎل اﻟﻣﻧﺷﺄة وﺧﻔض ﺣﻣل
اﻟﻣﺣول ﻛﻣﺎ ﺗﻘل اﻟﺳﻌﺎت اﻟﻣطﻠوب ﺗواﻓرﻫـﺎ ﻓـﻲ ﻗواطـﻊ اﻟـداﺋرة اﻟﻣﺳـﺗﺧدﻣﺔ وﯾﺳـﻬل ﻣﻌـﻪ إﻣﻛﺎﻧﯾـﺔ
ﻓﺣص وﺣدات ﻣﺟﻣوﻋﺔ اﻟﻣﻛﺛﻔﺎت أو ﻣﻠﺣﻘﺎﺗﻬﺎ ﻟوﺟودﻫﺎ ﻣﺟﺗﻣﻌﺔ ﻓﻲ ﻣﻛﺎن واﺣـد ﻛﻣـﺎ ﯾﻣﻛــن ﻓـﻲ
ﻫـذﻩ اﻟﺣﺎﻟـﺔ أﯾﺿـﺎً إﺿﺎﻓﺔ أﯾـﺔ ﺗرﻛﯾﺑﺎت أو ﺗوﺳﻌﺎت ﺟدﯾدة ﻟﻠﺷﺑﻛﺔ اﻟداﺧﻠﯾــــﺔ ﻟﻠﻣﻧﺷـﺄة ﺑﺳﻬوﻟــــﺔ،
وﯾﻌﯾـــب ﻣوﻗـــﻊ اﻟﻣﻛﺛﻔـــﺎت ﻓـﻲ ﻫـــذﻩ اﻟﺣﺎﻟـﺔ ﻋـدم اﻟـﺗﺧﻠص ﻣــن اﻟﻔﻘـد ) (Losses = I2R
Reactive current اﻟﻧﺎﺗــــﺞ ﻋــــــن ﻣــــرور ﻣرﻛﺑــــﺔ اﻟﺗﯾـــــﺎر ﻏﯾـــــر اﻟﻔﻌـــــــﺎل )Ir
(componentﻓﻰ اﻟﺗرﻛﯾﺑﺎت اﻟﻣﺣﺻورة ﺑﯾن ﻫذا اﻟﻣوﻗﻊ ﻟﻠﻣﻛﺛﻔﺎت وﻣواﻗﻊ اﻷﺣﻣﺎل.
ﺗرﻛﯾـــب ﻣﺟﻣوﻋـــﺎت اﻟﻣﻛﺛﻔـــﺎت ﻓـــﻲ ﺣـــدود ﻣﻧـــﺎطق ﺗوزﯾـــﻊ ﻣﺟﻣوﻋـــﺎت )(٢
اﻷﺣﻣﺎل ،ﻛﻣﺎ ﻫو ﻣوﺿﺢ
Tr
S
C1 C2
٥٤
ﺗرﻛﯾب اﻟﻣﻛﺛﻔﺎت ﺑﺟوار ﻧﻘﺎط اﻟﺗوزﯾﻊ إﻟﻰ اﻷﺣﻣﺎل
Tr
S
ﺗﻧﺎﺳــب طرﯾﻘــﺔ اﻟﺗرﻛﯾــب ﻫــذﻩ ﺣﺎﻟــﺔ اﻷﺣﻣــﺎل ﻓــﻰ اﻟﻣﻧــﺎطق اﻟﺻــﻧﺎﻋﯾﺔ اﻟﻣطﻠــوب ﺗﺻــﺣﯾﺢ
ﻣﻌﺎﻣـــل اﻟﻘـــدرة ﻋﻧـــدﻫﺎ ﻋﻠـــﻰ وﺟـــﻪ اﻟﺧﺻـــوص ،ﺣﯾـــث ﯾـــﺗم ﺗرﻛﯾـــب اﻟﻣﻛﺛﻔـــﺎت ﻋﻧـــد ﻧﻘطـــﺔ ﺗﻐذﯾـــﺔ
اﻟﻣﺣرﻛﺎت ذات اﻟﻘدرات اﻟﻛﺑﯾـرة ﻧﺳـﺑﯾﺎ ،وﻫـﻰ اﻟطرﯾﻘـﺔ اﻷﻛﺛـر ﻓﺎﻋﻠﯾـﺔ ﻣـن ﻧﺎﺣﯾـﺔ ﻣوﻗـﻊ اﻟﻣﻛﺛﻔـﺎت
وذﻟك ﻷن اﻟﻘدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﻣوﻟـدة ﺑواﺳـطﺔ اﻟﻣﻛﺛـف ﯾـﺗم اﺳـﺗﻬﻼﻛﻬﺎ ﻣﺑﺎﺷـرة ﺑواﺳـطﺔ اﻟﺣﻣـل
اﻟﺣﺛﻰ )اﻟﻣﺣرك( وﺑذﻟك ﯾﻘل اﻟﻔﻘد ﻓﻲ اﻟﺧطوط وﻛذﻟك ﯾﻘل
ﻫﺑــوط اﻟﺟﻬــد إﻟــﻰ اﻟﺣــد اﻷدﻧــﻰ ،ﻛﻣــﺎ ﯾــﻧﺧﻔض اﻟﺗﯾــﺎر ﻓــﻲ ﺷــﺑﻛﺔ اﻟﺗوزﯾــﻊ ﻣﻣــﺎ ﯾــؤدى إﻟــﻰ ﺧﻔــض
ﺗﻛﺎﻟﯾف ﺗوزﯾﻊ اﻟﻘدرة.
٥٥
وﺗﺗﻣﯾز ﻫذﻩ اﻟطرﯾﻘﺔ ﺑﺎﻧﻌدام ﻣرور اﻟﺗﯾﺎر ﻏﯾر اﻟﻔﻌﺎل ) (Irﻓﻲ ﻛﺎﺑﻼت اﻟﺗرﻛﯾﺑﺎت وﺑـذﻟك
ﯾﻘل اﻟﻔﻘد ﻓﻰ اﻟﺧطوط ) (I2Rﺑﺷﻛل ﻣﻠﺣوظ .
ﻣﻠﺣوظﺔ:
ﯾﺟب ﻓﻰ ﺟﻣﯾﻊ اﻷﺣـوال دراﺳـﺔ ﻣزاﯾـﺎ ﺗرﻛﯾـب ﻣﺟﻣوﻋـﺎت اﻟﻣﻛﺛﻔـﺎت ﻓـﻲ اﻟﻣواﻗـﻊ اﻟﻣﺧﺗـﺎرة
دراﺳﺔ اﻗﺗﺻﺎدﯾﺔ ﻣﺗﺄﻧﯾﺔ ،ﻣن ﺣﯾث اﻟﺗﻛﺎﻟﯾف اﻟﻼزﻣﺔ ﻋﻧد ﻛل ﺣﺎﻟﺔ واﻟﻣردود اﻻﻗﺗﺻﺎدي ﻟﺗﺣﺳـﯾن
ﻣﻌﺎﻣل اﻟﻘدرة ﺣﺳب ﻛل ﻣوﻗﻊ أﺧذا ﻓﻲ اﻻﻋﺗﺑﺎر طﺑﯾﻌﺔ اﻷﺣﻣﺎل اﻟﻣراد ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة ﻟﻬـﺎ
وظروف ﺗﺷﻐﯾﻠﻬﺎ ﺑﻣﺎ ﯾﺣﻘق أﻛﺑر ﻓﺎﺋدة ﻟﻛل ﻣن ﻣرﻓق اﻟﻛﻬرﺑﺎء واﻟﻣﻧﺗﻔﻌﯾن ﺑﻬﺎ ﻣﻌﺎ ﻟﻣﺎ ﻓـﻲ ذﻟـك
ﻣن ﻣدﻟول اﻗﺗﺻﺎدي إﯾﺟﺎﺑﻲ ﻋﻠﻰ ﻣﺳﺗوى اﻟﻧﺎﺗﺞ اﻟﻘوﻣﻲ ﺑﺻﻔﺔ ﻋﺎﻣﺔ .
٥٦
ﯾﺟب اﺳﺗﻧﺗﺎج ﻣﻧﺣﻧﯾﺎت اﻟﺣﻣل ) ( Load Curvesﻟﻛل ﻣن اﻟﻘدرة اﻟﻔﻌـــــﺎﻟﺔ
) (kWواﻟﻘــدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ ) (kVARﻟﻠﺷــﺑﻛﺔ أو ﻟﻸﺣﻣــﺎل اﻟﻣطﻠــوب ﺗﺻــﺣﯾﺢ
ﻣﻌﺎﻣــل اﻟﻘــدرة ﻟﻬــﺎ ﻣــن ﺧــﻼل اﻟﻘﯾﺎﺳــﺎت اﻟﺗــﻲ أﻣﻛــن اﻟﺣﺻــول ﻋﻠﯾﻬــﺎ ﺧــﻼل ﻓﺗــرة
اﻟﻘﯾﺎس ﻻﺳﺗﻧﺗﺎج ﻣدى ﺗﺑﺎﯾن اﻟﺣﻣل ﺗﺣت ظروف اﻟﺗﺣﻣﯾل اﻟﻣﺧﺗﻠﻔﺔ.
ﻣﻌﺎﻣﻼت ﺗﺑﺎﯾن اﻟﺣﻣل) : ( Load diversity factors *
ﯾــﺗم اﺳــﺗﺧﻼص ﻣﻌــﺎﻣﻼت ﺗﺑــﺎﯾن اﻟﺣﻣــل ﻣــن ﺧــﻼل اﻟﻘ ـراءة اﻟدﻗﯾﻘــﺔ ﻟﻣﻧﺣﻧﯾــﺎت
اﻟﺣﻣل ،وﻫذﻩ اﻟﻣﻌﺎﻣﻼت ﺗﻛﺗﺳب أﻫﻣﯾﺔ ﺧﺎﺻﺔ ﻟﻛوﻧﻬﺎ ﻛﺎﺷﻔﺔ ﻟﻠﻣﺗﻐﯾرات اﻟﻛﻬرﺑﺎﺋﯾﺔ
ﺑﺎﻟﺷﺑﻛﺔ ﻧﺗﯾﺟﺔ ﻟﺗﺑﺎﯾن ظروف اﻟﺗﺣﻣﯾل اﻟﻣﺗﻌﻠﻘﺔ ﺑطﺑﯾﻌﺔ اﻟﺣﻣـل ،وﻋﻠـﻰ ﺿـوء ﻫـذﻩ
اﻟﻣﻌﺎﻣﻼت ﯾﻣﻛن ﺗﺣدﯾد ﻣواﻗﻊ اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة .
ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف : *
ﺑﻌد ﻗﯾـﺎس ﻣﻌﺎﻣل اﻟﻘدرة ﻟﻠﺣﻣل ﻗﺑل اﻟﺗﺻﺣﯾﺢ ﯾﺗم ﺗﺣدﯾد ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣطﻠوب
اﻟﻣﺳﺗﻬدف ) (Target P.f.وﺑﺎﺳﺗﺧدام اﻟﺟدول اﻟﺳﺎﺑق ﯾﻣﻛن اﻟﺣﺻول ﻋﻠـﻰ
اﻟﻣﻌﺎﻣــل Kاﻟــذي ﯾﺟــب ﺿــرﺑﻪ ﻓــﻲ ﻗﯾﻣــﺔ اﻟﻘــدرة اﻟﻔﻌﺎﻟــﺔ ﻟﺗﺣدﯾــد ﻗﯾﻣــﺔ اﻟﻘــدرة ﻏﯾــر
اﻟﻔﻌﺎﻟﺔ ) (kVARاﻟﻣطﻠوب إﻧﺗﺎﺟﻬﺎ ﺑواﺳطﺔ اﻟﻣﻛﺛف أو ﻣﺟﻣوﻋﺔ اﻟﻣﻛﺛﻔﺎت ،وﻣن
ﺛم ﺳﻌﺔ ﻛل ﻣﻛﺛف واﻟﺗﻲ ﯾﻣﻛن ﺣﺳﺎﺑﻬﺎ ﻣن اﻟﻣﻌﺎدﻟﺔ
2 - [ × )tan 1 tan Q (kVAR) = P(kW
)Q (kVAR) = K P(kW
ﺣﯾث أن :
] 2- [ =tan 1 tan K
وﯾوﺻﻰ ﺑﺎن ﯾﺗراوح ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻣﺳﺗﻬدف ﻣـﺎ ﺑـﯾن ٠.٩إﻟـﻰ ٠.٩٥ﻟﺿـﻣﺎن
اﻟﺣﺻول ﻋﻠﻰ أﻛﺑر ﻋﺎﺋد ﻣﻣﻛن ﻧﺗﯾﺟﺔ ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة .
ﻣواﺻﻔﺎت اﻟﻣﻛﺛﻔﺎت اﻟﻣﺳﺗﺧدﻣﺔ ﻟﺗﺻﺣﯾﺢ ﻣﻌﺎﻣل اﻟﻘدرة
ﺑﻌد اﻻﻧﺗﻬﺎء ﻣن ﺗﺣدﯾد اﻷﺳـﻠوب اﻷﻣﺛـل ﻟﺗﻌـوﯾض اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ ﻛﻣرﺣﻠـﺔ اﺑﺗداﺋﯾـﺔ
ﻣن ﻣراﺣل ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ﻓﻲ ﺷﺑﻛﺎت اﻟﺗوزﯾﻊ ،ﺗﺑدأ ﻣرﺣﻠـﺔ ﺗوﺻـﯾف اﻟﻣﻛﺛﻔـﺎت وﻣﻠﺣﻘﺎﺗﻬـﺎ
ﻟﺗﺻـﺑﺢ ﻣطﺎﺑﻘـﺔ ﻟﻠﻣﻧﺻـوص ﻋﻠﯾـﻪ ﺑﺎﻟﻣواﺻـﻔﺎت اﻟﻘﯾﺎﺳـﯾﺔ ﻟﺗﻛـون ﻫـذﻩ اﻟﻣواﺻـﻔﺎت ﻫـﻲ اﻷﺳـﺎس
اﻟذي ﯾﺗم اﻟﻣﻔﺎﺿﻠﺔ ﻋﻠﯾﻪ ﻋﻧـد ﺗﺣﻠﯾـل ﻋـروض اﻷﺳـﻌﺎر اﻟﺧﺎﺻـﺔ ﺑﺎﻟﺗورﯾـد و اﻟﺗرﻛﯾـب اﻟﺗـﻲ ﺗﻘـدم
ﻣن اﻟﺷرﻛﺎت اﻟﻣﺧﺗﺻﺔ ﻓﻲ ﻫذا اﻟﻣﺟﺎل ،ﻋﻠﻰ أن ﺗﻛون اﻟﻣﻛﺛﻔﺎت اﻟﻣطﻠوﺑـﺔ ﻗـﺎدرة ﻋﻠـﻰ اﻟﺗﺷـﻐﯾل
اﻟﻣﺳﺗﻣر دون اﻹﺧﻼل ﺑﺎﻟﺷروط اﻵﺗﯾﺔ-:
* ﯾﺟــب أن ﯾﻛــون اﻟﺗﺻــﻧﯾﻊ و اﻻﺧﺗﺑــﺎرات ﻟوﺣــدات اﻟﻣﻛﺛﻔــﺎت طﺑﻘــﺎ ﻟﻠﻣواﺻــﻔﺎت
اﻟدوﻟﯾﺔ اﻟﻛﻬروﺗﻘﻧﯾﺔ . IEC 60831
٥٧
ﻣــن اﻟﺗﯾــﺎر اﻟﻣﻘــﻧن ﻟﻠﺗﺷــﻐﯾل ﻧﺗﯾﺟــﺔ ﻟوﺟــود * ﯾﺟــب أن ﯾﺗﺣﻣــل اﻟﻣﻛﺛــف ٪١٣٠
ﺗﯾﺎرات ﺗواﻓﻘﯾﺎت .
* ﯾﺟـب أن ﯾراﻋــﻰ ﻓــﻲ ﻣرﺣﻠــﺔ اﻟﺗﺻـﻣﯾم أن ﯾﻛــون اﻟﻣﻛﺛــف أو ﻣﺟﻣوﻋــﺔ اﻟﻣﻛﺛﻔــﺎت
ﻣـــن اﻟﻘﯾﻣـــﺔ ﻗـــﺎدرة ﻋﻠـــﻰ إﻧﺗـــﺎج ﻗـــدرة ﻏﯾـــر ﻓﻌﺎﻟـــﺔ ) (KVARﺑﻧﺳـــﺑﺔ ٪١٣٥
اﻟﻣﺣﺳــوﺑﺔ ،ﻟﺗﺷــﻣل اﻟﻘ ـدرة ﻏﯾــر اﻟﻔﻌﺎﻟــﺔ اﻹﺿــﺎﻓﯾﺔ اﻟﺗــﻲ ﺗﺻــﺎﺣب اﻟﺟﻬــود اﻟزاﺋــدة
ﻧﺗﯾﺟﺔ ﻟظروف اﻟﺗﺷﻐﯾل ﻏﯾر اﻟﻌﺎدﯾﺔ اﻟﺗـﻲ ﺗﻣـر ﺑﻬـﺎ اﻟﻣﻧظوﻣـﺔ ،ﺑﺷـرط أﻻ ﺗﺗﺟـﺎوز
اﻟزﯾﺎدة اﻟﺟﻬد اﻟﻣﻌدل اﻟﻣﻧﺻوص ﻋﻠﯾﻪ أﯾﺿﺎ ﻋﻠﻰ ﻟوﺣﺔ اﻟﺗوﺻﯾف.
ﻣــــن اﻟﻘﯾـﻣـــﺔ اﻟﻣـﺗوﺳطـــﺔ ﻟﻠـﺟـــﻬد اﻟﻣﻌﺗـــﺎد ﻋﻠــــﻰ أﺳــﺎس * ﺗﻘـــدر ﻧﺳــﺑﺔ ٪١١٥
) ،(Rated voltage r.m.sﻋﻠﻣـﺎ ﺑـﺎن ﻗﯾﻣـﺔ اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﻣطﻠوﺑـﺔ
ﻟﻠﺗﺣﺳــﯾن ﺗﺣﺳــب ﻋﻧــد ﺟﻬــد اﻟﺗﺷــﻐﯾل وﻫــو ٤٠٠ﻓوﻟــت ،ﻛﻣــﺎ ﯾﻣﻛــن زﯾــﺎدة ﻫــذﻩ
اﻟﻘﯾﻣﺔ ﻟﻠﺟﻬد إﻟﻰ ٤٤٠ﻓوﻟت ﻓﻲ ﺣﺎﻟﺔ ﺗﺑﯾن وﺟـود ﻣﺣﺗـوى ﺗواﻓﻘﯾـﺎت ﺟﻬـد أﺛﻧـﺎء
اﻟﻘﯾﺎس.
* ﯾﺗم ﺗﺣدﯾد درﺟﺎت اﻟﺣرارة اﻟﺗﻲ ﯾﺗﺣﻣﻠﻬﺎ اﻟﻣﻛﺛـف طﺑﻘـﺎ ﻟظـروف اﻟﻣﻛـﺎن اﻟﻣوﺟـود
ﺑﻪ ﻟوﺣﺔ اﻟﺟﻬد اﻟﻣﻧﺧﻔض ،وﻣن ﺛـم اﻟﻣوﻗـﻊ اﻟﻣﺧﺗـﺎر ﻟﺗرﻛﯾـب اﻟﻣﻛﺛﻔـﺎت ﻣـن ﺣﯾـث
ﺟودة اﻟﺗﻬوﯾﺔ ،ﻋﻠﻰ أن ﺗﺗراوح ﻣﺎ ﺑﯾن ْ٥ -إﻟﻰ ◌ْ ◌ْ ٥٥ +
٥٨
اﻟﻣﻼﻣﺳﺎت واﻟﻣﺻﺎﻫر اﻟﻣﺳﺗﺧدﻣﺔ
ﻣﻊ ﻣﺟﻣوﻋﺔ ﻣﻛﺛﻔﺎت ﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة
٥٩
ﯾﻔﺿـــل اﺳـــﺗﺧدام اﻟﻣﻛﺛﻔـــﺎت ﻣـــن اﻟﻧـــوع اﻟﻘﺎﺑـــل ﻟﻠﻔﺻـــل *
واﻟﺗوﺻﯾل ﺣﯾث ﯾﻣﻛن اﻟﺗﺣﻛم ﻓﻲ إﺿـﺎﻓﺔ ﻗﯾﻣـﺔ اﻟﻘـدرة ﻏﯾـر اﻟﻔﻌﺎﻟـﺔ اﻟﻼزﻣـﺔ
ﻟﻠﺷﺑﻛﺎت اﻟﻛﻬرﺑﯾﺔ ﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ،وﺑذﻟك ﯾﺗﺣﺳن اﻟﺟﻬد وﯾﻘل اﻟﻔﻘد .
إذا ﻛﺎﻧــت اﻷﺣﻣــﺎل ﺗﺗﻐﯾــر ﺑﺻــﻔﺔ ﻣﺳــﺗﻣرة ﺧــﻼل ﻓﺗ ـرات *
اﻟﺗﺷﻐﯾل ،ﻓﺈﻧﻪ ﯾﺗم ﺗرﻛﯾب ﻣﻛﺛﻔﺎت ﻣن اﻟﻧوع اﻟﻘﺎﺑل ﻟﻠﻔﺻل واﻟﺗوﺻﯾل .وﻓـﻲ
ﺣﺎﻟﺔ اﻷﺣﻣﺎل اﻟﺗﻲ ﺗﺟﻣﻊ ﺑﯾن اﻟﺣﺎﻟﺗﯾن اﻟﺳﺎﺑﻘﺗﯾن ) أﺣﻣـﺎل ﺛﺎﺑﺗـﺔ +أﺣﻣـﺎل
ﻣﺗﻐﯾرة ( ﻓﺈﻧﻪ ﯾﻣﻛن ﺗرﻛﯾب ﻣﻛﺛﻔﺎت ﺗﺣﺗوي ﻋﻠﻰ ﺟزء ﺛﺎﺑت وﺟزء ﻣـن اﻟﻧـوع
اﻟﻘﺎﺑل ﻟﻠﻔﺻل واﻟﺗوﺻﯾل.
ﺗﻘﺳم اﻟﻣﻛﺛﻔﺎت ﻣن اﻟﻧوع اﻟﻘﺎﺑل ﻟﻠﻔﺻل واﻟﺗوﺻﯾل إﻟـﻰ *
أﺟزاء ﺗﺳﻣﻰ ﻣراﺣل ) (Stepsﻟﻬﺎ ﻗدرات ) ك .ﻓﺎر ( ﻣﺣددة ﺣﯾـث ﯾـﺗم
اﻟـــﺗﺣﻛم ﻓـــﻲ دﺧـــول ﻣرﺣﻠـــﺔ أو أﻛﺛـــر ﻋـــن طرﯾـــق أﺟﻬـــزة اﻟـــﺗﺣﻛم اﻵﻟـــﻲ )
( Automatic Regulatorﻣـن ﺧـﻼل ﻣﻼﻣـس ) ( Contactor
ﻟﻛل ﻣرﺣﻠﺔ .
٦٠
وﯾﺑــﯾن اﻟﺟــدول اﻟﺗــﺎﻟﻲ ﻣﻘﻧﻧــﺎت اﻟﻣﺻــﺎﻫر وﻣﻘــﺎطﻊ ﻣوﺻــﻼت
اﻟﻛﺎﺑﻼت اﻟﻣﺳﺗﺧدﻣﺔ.
٦١
5
60 -- -- -- 86.6 16 70 83.5 160 70
0
66.7 -- -- -- 96.3 16 70 92.8 160 70
0
70 -- -- -- 101 16 70 97 160 70
0
75 -- -- -- 108 16 70 104 160 70
0
83.3 -- -- -- 120 20 95 116 200 95
0
100 -- -- -- 144 25 120 139 250 120
0
وﻓﻰ ﺣﺎﻟﺔ زﯾﺎدة ﻣﻌﺎﻣل اﻟﻘدرة ﻋن ) ٠.٩٢ﻣﺎ ﺑـﯾن ٠.٩٢و (٠.٩٥ﻓﺳـوف ﺗـﻧﺧﻔض
اﻟﺗﻌرﯾﻔــﺔ ﺑﻣﻘــدار ٪٠.٥ﻟﻛــل ٠.٠١زﯾــﺎدة ﻓــﻰ ﻣﻌﺎﻣــل اﻟﻘــدرة أﻛﺛــر ﻣــن ٠.٩٢وﯾﻣﻛــن ﺣﺳــﺎب
ﺗﻛﻠﻔﺔ ﺣﺎﻓز ) (Bonusزﯾﺎدة ﻣﻌﺎﻣل اﻟﻘدرة ﻣن اﻟﻣﻌﺎدﻟﺔ ﻛﺎﻵﺗﻰ:
P.f - 0.92
( Annual cos t of bonous 0.005 x ) x Annual consumptio n(kwhr) x tariff
0.01
٦٢
ﻟﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة ﯾﺗم ﺗوﺻﯾل ﻣﻛﺛف ﻋﻠـﻰ اﻟﺗـوازى -
ﻣﻊ اﻟﺣﻣل )ﻣﺣرﻛﺎت ﻛﻬرﺑﺎﺋﯾﺔ أو ﻣﺻﺎﺑﯾﺢ ﺗﻔرﯾﻎ ﻛﻬرﺑﻰ(.
ﯾﻣﻛــن ﺣﺳــﺎب زﯾــﺎدة اﻟﻧﺳــﺑﺔ اﻟﻣﺋوﯾــﺔ ﻟﺗﻘﻠﯾــل اﻟﻔﻘــد ﻓــﻰ -
اﻟﻘدرة اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻋﻧدﻣﺎ ﯾﺗﺣﺳن ﻣﻌﺎﻣل اﻟﻘدرة ﻣن cos 1إﻟـﻰ cos 2ﻣـن
اﻟﻣﻌﺎدﻟﺔ ) (٨-٩ﻛﺎﻵﺗﻲ:
٦٣
٠.١٥أﻣﺑﯾــر ٠أﻣــﺎ إذا اﺳــﺗﺧدم ﻣﻛﺛــف ﺳــﻌﺔ ٥ﻣﯾﻛروﻓــﺎراد ﻣــﻊ ﻣﺻــﺑﺎح
ﻓﻠورى ﺑطول ١٢٠ﺳم ﻗدرة ٤٠وات ،ﻓﯾﺗﺣﺳن ﻣﻌﺎﻣل اﻟﻘـدرة ﻣـن ٠.٤٨
إﻟﻰ ٠.٩٣وﺗﺗﻐﯾر ﻗﯾﻣﺔ اﻟﺗﯾﺎر ﻣن ٠.٤٠٤أﻣﺑﯾر إﻟﻰ ٠.٢٠١أﻣﺑﯾر.
ﺑﻧك ﻣﻛﺛﻔﺎت ﻣﻊ اﻟﻠوﺣﺔ اﻟرﺋﯾﺳﯾﺔ )ب(
ﻟﺗﺣﺳﯾن ﻣﻌﺎﻣل اﻟﻘدرة اﻟﻛﻠﻰ ﻓﺈﻧـﻪ ﯾﻣﻛـن اﺳـﺗﺧدام ﺑﻧـك -
ﻣﻛﺛﻔﺎت )ﺛﺎﺑت أو ﻣﺗﻐﯾر( ﻣﻊ اﻟﻠوﺣﺔ اﻟرﺋﯾﺳﯾﺔ ﺑدﻻ ﻣن وﺿﻊ ﻣﻛﺛـف ﻣﻧﻔـرد
ﻋﻠﻰ اﻟﺗوازى ﻣﻊ ﻛل ﺣﻣل.
ﯾﻣﻛــــن ﺗﺣدﯾــــد ﻗﯾﻣــــﺔ اﻟﻘــــدرة ﻏﯾــــر اﻟﻔﻌﺎﻟــــﺔ ﻟﻠﻣﻛﺛﻔــــﺎت -
اﻟﻣطﻠوﺑـﺔ (kVAR)cﻟﺗﺣﺳـﯾن ﻣﻌﺎﻣـل اﻟﻘـدرة ﻣـن P.f 1إﻟـﻰ P.f 2
ﻣن اﻟﻣﻌﺎدﻟﺔ ﻛﺎﻵﺗﻲ :
kVAR c kVA P.f1 tan cos -1 P. f1 - kVA P.F2 tan cos -1 P. f 2
٦٤
GENERATORS
٦٥
ﻧظﺎم اﻟﺑطﺎرﯾﺎت اﻟﻣرﻛزى
-ﯾﺳﺗﺧدم ﻫذا اﻟﻧظﺎم ﻛﻣﺻدر ﺑدﯾل ﻹﻧﺎرة اﻟطوارئ وﯾﻌﺗﻣد ﻋﻠﻰ ﺗوﻓﯾر ﻣﺻدرﻟﺗﻐذﯾﺔ وﺣدات
إﻧﺎرة طوارئ ﺗﻌﻣل ﻋﻠﻰ اﻟﺗﯾﺎر اﻟﻣﺳﺗﻣر ). (DC
-ﯾﻛون اﺳﺗﺧدام ﺑطﺎرﯾﺎت ﺗظل ﻣﺷﺣوﻧﺔ إﻟﻰ اﻟدرﺟﺔ اﻟﺗﻰ ﺗﻛﻔﻰ ﻟﺗﻐذﯾﺔ ﻣﻌظم اﻷﺣﻣﺎل
اﻟﻣطﻠوﺑﺔ ﻟﻠﺧدﻣﺔ ﺑﻛﺎﻣل اﻟﻣﺑﻧﻰ ﺻﻌﺑًﺎ ﻣن اﻟﻧﺎﺣﯾﺔ اﻟﻌﻣﻠﯾﺔ وﻟﻛﻧﻬﺎ ﺗﺻﻠﺢ ﻓﻘط ﻟﺗﻐذﯾﺔ ﻧظم
إﻧﺎر ة اﻟطوارئ اﻟﺗﻰ ﺗﻌﺗﻣد ﺑدرﺟﺔ ﻛﺑﯾرة ﻋﻠﻰ ﻣدى ﺷﺣن ﻫذﻩ اﻟﺑطﺎرﯾﺎت واﻟﺗﻰ ﻋﻧد اﻧﺗﻬﺎء
ﺷﺣﻧﺗﻬﺎ ﯾﺗوﻗف ﻣﻌﻬﺎ اﻟﻧظﺎم وﺗﻛون إﻋﺎدة اﺳﺗﺧداﻣﻬﺎ ﺑﻌد ذﻟك ﻣرﺗﺑطﺎً ﺑطول ﻣدة ﻋطل
ﻣﺻدر ﺗﯾﺎر اﻟﻣدﯾﻧﺔ ﺛم إﻋﺎدة ﺷﺣن اﻟﺑطﺎرﯾﺎ ت .وﺑﺎﻟﺗﺎﻟﻰ ﻓﺈن ﻫذا اﻟﻧظﺎﻣﻬذا اﻟﻧظﺎم ﻏﯾر
آﻣن وﻻ ﯾﺣﻘق اﻟﻐرﺿﻣﻧﻪ ﻓﻰ ﺣﺎﻟﺔ ﻋطل اﻟﻣﺻدر ﻟﻣدد طوﯾﻠﺔ.
-ﻫﻰ ﻣوﻟدات اﻟﻘوى اﻻﺣﺗﯾﺎطﯾﺔ اﻟﺗﻰ ﺗﻌﻣل ﺑﺎﻟدﯾزل وﯾﻣﻛن ﺗرﻛﯾﺑﻬﺎ ﻓﻰ اﻟﻣﺑﺎﻧﻰ ﻹﻣدادﻫﺎ
ﺑﺎﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ ﻓﻰ ﺣﺎﻟﺔ اﻧﻔﺻﺎل أو ﺗﻌطل ﻣﺻﺎدر اﻟﻣدﯾﻧﺔ وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﺗﺣﻘق ﺿﻣﺎن
ﻛﺎﻣل ﻟﻠﺣﻣﺎﯾﺔ ﻣن ﻓﺻل أو ﻋطل ﻣﺻﺎدر اﻟﺗﻐذﯾﺔﻣن اﻟﻣدﯾﻧﺔ.
-ﯾﻣﻛن أن ﯾﻛون اﻟﻣوﻟد اﻻﺣﺗﯾﺎطﻰ ﺑﺳﻌﺔ ﺗﻛﻔﻰ ﻣﺟﻣوع اﻷﺣﻣﺎل ﺑﺎﻟﻣﺑﻧﻰ وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ
ﯾﻣﻛن أن ﯾﺗﺻل ﻣﺑﺎﺷرة ﺑﺎﻟﻠوﺣﺔ اﻟﻌﻣوﻣﯾﺔ ﻟﻠﻣﺑﻧﻰ ﺑﻌد ﻋداد اﺗﺣﺳﺎب اﻟطﺎﻗﺔ اﻟﺧﺎﺻﺔ ﺑﺷرﻛﺔ
اﻟﺗوزﯾﻊ ﻟﺗﻐذﯾﺔ ﻛﺎﻣل اﻟﻣﺑﻧﻰ ﺑﻛل أﺣﻣﺎﻟﻪ ،وﯾﺗم ذﻟك ﻋن طرﯾق ﺳﻛﯾﻧﺔ ﻗﻼب ﯾدوﯾﺔ أو
ﺑﺎﺳﺗﺧدام ﻣﻔﺗﺎح ﺗﺣوﯾل ﺗﻠﻘﺎﺋﻰ
-ﯾﻣﻛن اﺳﺗﺧدام ﻣوﻟد طوارئ ﻟﺗﻐذﯾﺔ اﻷﺣﻣﺎل اﻟﻬﺎﻣﺔ ﺑﺎﻟﻣﺑﻧﻰ ﻓﻘط وﻗت اﻧﻘطﺎع ﻣﺻدر
اﻟﻣدﯾﻧﺔ ،وﻓﻰ ﻫذﻩ اﻟﺣﺎﻟﺔ ﯾﺗﺑﻊ أﺳﻠوب اﻟﺗوزﯾﻊ ﻟﺗﻐذﯾﺔ اﻷﺣﻣﺎل ﺑﺣﯾث ﯾﺗم ﻧﻘل اﻟﺗﻐذﯾﺔ ﻣن
ﻣﺻدر اﻟﻣدﯾﻧﺔ إﻟﻰ اﻟﻣوﻟد اﻻﺣﺗﯾﺎطﻲ ﻣن ﻣرﻛز ﺗوزﯾﻊ واﺣد ﻟﺗﻐذﯾﺔ ﺟﻣﯾﻊ أﺣﻣﺎل وﺧدﻣﺎت
اﻟطوارئ وذﻟك ﺑﺄن ﺗﻘﺳم اﻷﺣﻣﺎل ﻋﻧد ﻣﺻدر اﻟﺗﻐذﯾﺔ إﻟﻰ ﻗﺳﻣﯾن أﺣدﻫﻣﺎ ﻟﻸﺣﻣﺎل وﯾﺗﺻل
ﻓﻘط اﻟﻬﺎﻣﺔ واﻷﺧرى ﻟﻸﺣﻣﺎل ﻏﯾر اﻟﻬﺎﻣﺔ ﻗﺳم اﻷﺣﻣﺎل اﻟﻬﺎﻣﺔ ﺑﻣﺻدرى اﻟﺗﻐذﯾﺔ ﻣﺻدر
اﻟﻣدﯾﻧﺔ وﻣﺻدر اﻟﻣوﻟد اﻻﺣﺗﯾﺎطﻰ ﺑﯾﻧﻣﺎ ﯾﺗﺻل ﻗﺳم اﻷﺣﻣﺎل ﻏﯾر اﻟﻬﺎﻣﺔ ﺑﻣﺻدر اﻟﻣدﯾﻧﺔ
ﻓﻘط ﻋﻠﻰ اﻟﻧﺣو اﻟﻣوﺿﺢ ﺑﺎﻷﺷﻛﺎل اﻟﺗﺎﻟﻰ
٦٦
٦٧
٦٨
-ﯾﻣﻛن ﺑدء ﺗﺷﻐﯾل ﻣﺎﻛﯾﻧﺎت اﻟدﯾزل ﻹدارة ﻣوﻟدات اﻟطوارئ ﯾدوﯾًﺎ أو ﺗﻠﻘﺎﺋﯾًﺎ،وﺑﺎﻟرﻏم
ﻣن ﺑﺳﺎطﺔ اﻟﺑدء ﯾدوﯾًﺎ وﻗﻠﺔ ﺗﻛﻠﻔﺗﻪ إﻻ أﻧﻪ ﺑطﺊ ﻧﺳﺑﯾًﺎ ﻣﻣﺎ ﯾﺳﺑب إﺑﻘﺎء اﻟﻣﺑﻧﻰ
دون ﻣﺻدر ﻛﻬرﺑﺎﺋﻰ ﻟﻔﺗرة زﻣﻧﯾﺔ إﻟﻰ أن ﯾﺗم إدارة اﻟوﺣدة ﺑﯾﻧﻣﺎ ﯾﻘﻠل اﻟﺑدء ﺗﻠﻘﺎﺋﯾًﺎ
ﻣن ﻫذﻩ اﻟﻣدة وﯾطﻠق ﻋﻠﻰ ﻣﺎﻛﯾﻧﺔ إدارة ﻣوﻟد اﻟطوارئ اﻟﻣزودة ﺑﺑدء ﺗﻠﻘﺎﺋﻰ ﺑﺄﻧﻬﺎ
ﻣزودة ﺑﻧظﺎم ﺗﺣﻛم ﺗﻠﻘﺎﺋﻰ ﻋﻧد ﺳﻘوط اﻟﻣﺻدر .(Automatic mains
)failure-AMF-
٦٩
-وﯾوﺿﺢ اﻟﺷﻛل اﻟﻘﺎدم داﺋرة ﺗﺣﻛم ﺑدء ﺣرﻛﺔ ﻣﺎﻛﯾﻧﺔ اﻟدﯾزل ﻟﻣوﻟد اﻟطوارئ ﻋﻧد
ﺳﻘوط ﺗﯾﺎر اﻟﻣﺻدر ) (Mains failure control circuitﻛﯾﻔﯾﺔ ﻋﻣل
اﻟداﺋرة
-ﺗﻛون ﻓﺗﺣﺎت اﻟﺗﻬوﯾﺔ ﻓﻰ ﻋﻛس اﺗﺟﺎﻩ ﻫﺑوب اﻟرﯾﺎح ﺑﺣﯾث ﺗﺳﻣﺢ ﺑﺎﻧدﻓﺎع اﻟﻬواء
اﻟﺳﺎﺧن إﻟﻰ اﻟﺧﺎرج وﺗﺳﺎﻋد ﺣرﻛﺔ اﻟﻬواء ﻋﻠﻰ ﺳﺣﺑﺔ،ﻛﻣﺎ ﺗﻛون ﻓﺗﺣﺔ ﺧروج
اﻟﻌﺎدم ﻓﻰ ﻋﻛس ﻫﺑوب اﻟرﯾﺎح.
٧٠
Uninterruptible Power Supply ( ﻣﺻدر ﺗﻐذﯾﺔ ﻗوى ﻋدﯾم اﻻﻧﻘطﺎع
UPS)
٧١
-ﻫو ﻋﺑﺎرة ﻋن وﺣدة ﺗﺗﻛون ﻣن ﻣﻘوم ﺗﯾﺎر Rectifieو ﻣﺟﻣوﻋﺔ ﺑطﺎرﯾﺎت وﻣﻐﯾر
) (MSﻟﻠﻧﻘل ﻣن ﺗﯾﺎر ﻣن ﻣﺳﺗﻣر إﻟﻰ ﻣﺗردد ﻣن ) (Inverterوﻣﯾﻛروﺳوﯾﺗس
اﻟﺑطﺎرﯾﺎت إﻟﻰ اﻟﻣﺻدر أو اﻟﻌﻛس). (MS
٧٢
ﺗﺣﺗوى ﻫذﻩ اﻟوﺣدات ﻋﻠﻰ ﺷﺎﺣن وﺑطﺎرﯾﺎت ﺗﻌﻣل ﻟﻣدد ﻣﺣددة ﺑﻛﺎﻓﺔ أﻧواﻋﻬﺎ وﯾﻣﻛن
اﺳﺗﺧداﻣﻬﺎ ﻟﻺﻧﺎرة وﺗﺳﻬﯾل ﺣرﻛﺔ اﻷﺷﺧﺎص ﻓﻰ ﺑﻌض اﻷﻣﺎﻛن ﻓﻰ ﻓﺗرات اﻻﻧﺗﻘﺎل ﻣﺎ ﺑﯾن
ﻣﺻدر اﻟﻣدﯾﻧﺔ وﻣﺻدر ﻣوﻟدات اﻟطوارئ.
-اﻟظروف اﻟﻌﺎدﯾﺔ:
ﯾﻛون اﻟﻘﺎﺑض ﻣﻔﺻو ﻻ واﻟﻣﺣرك ﻣﺗﺻﻼ ﺑﻣﺻدر ﺗﯾﺎر اﻟﻣدﯾﻧﺔ وﯾﻌﻣﻼن ﻫو واﻟﻣوﻟد
واﻟﺣداﻓﺔ ﻣﻌًﺎ ﻓﯾﻘوم اﻟﻣوﻟد ﺑﺗوﻟﯾد اﻟﺗﯾﺎر اﻟﻼزم ﻟﺗﻐذﯾﺔ أﺣﻣﺎل اﻟطوارئ ﺑﺻﻔﺔ داﺋﻣﺔ.
٧٣
ﺗظل اﻟﺣداف ة ﻛﻛﺗﻠﺔ ﻋﺎﻟﯾﺔ اﻟوزن )اﻟﻘﺻور اﻟذاﺗﻰ ﻟﻠﺣداﻓﺔ ﻓﻰ ﺣدود 1300ﻛﺞ م( ٢
ﻓﻰ إدارة اﻟﻣﺣرك واﻟﻣوﻟد وﯾﻘوم اﻟﻣوﻟد ﺑﺗوﻟﯾد اﻟﻘوى اﻟﻼزﻣﺔ ﻷﺣﻣﺎل اﻟطوارئ ﻟﻌدة ﺛوان
ﯾﺳﻣﺢ ﻓﯾﻬﺎ ﺑﺎﻧﺧﻔﺎض اﻟﺟﻬد واﻟﺗردد) ﺣﺗﻰ (٪ 5ﯾﻣﻛن اﺧﺗﯾﺎر اﻟﻣﺎﻛﯾﻧﺔ ﺑﺄن ﯾﻛون ﻫذا
اﻻﻧﺧﻔﺎض ﻣﺎ ﺑﯾن ٪ 1و ( 5واﻟذى ﯾﺗﺣدد ﻣﻧﻪ وزن اﻟﺣداﻓﺔ وﻧوﻋﯾﺔ أﻋﻣدة اﻟﻣﺣﺎور
اﻟﻣﺳﺗﺧدم ة )وﻓﻰ
ﻧﻔس اﻟوﻗت ﯾﻧﻘﺑض اﻟﻘﺎﺑض اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﻲ وﺗﻘوم اﻟﺣداﻓﺔ ﺑﻣﺎ ﺗﺣﺗوﯾﻪ ﻣن ﻗﺻور ذاﺗﻰ
ﻋﺎﻟﻰ ﺑﺈدارة ﻣﺎﻛﯾﻧﺔ اﻟدﯾزل ﺗﻣﻬﯾدًا ﻟﺑدء ﺣرﻛﺗﻬﺎ ﻟﺗﻐذﯾﺔ اﻟﻣﺟﻣوﻋﺔ ﻛﻠﻬﺎ ﺑﺎﻟﺣرﻛﺔ)اﻟﺣداﻓﺔ
واﻟﻣﺣرك واﻟﻣوﻟد( وﻋﻧد ذﻟك ﯾﺳﺗﻣر اﻟﻣوﻟد ﻓﻰ إﻣداد اﻷﺣﻣﺎل ﺑﺎﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ.
ﯾﻔﺻل اﻟﻘﺎﺑض اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﻲ وﺑﻌد ﻓﺗرة ﺗﺗوﻗف اﻟﻣﺎﻛﯾﻧﺔ اﻟدﯾزل وﯾﺳﺗﻣر اﻟﻌﻣل ﺑواﺳطﺔ
ﻣﺻدر اﻟﻣدﯾﻧﺔ ﻋﻠﻰ اﻟﻧﺣو اﻟﺳﺎﺑق.
-ﯾﻌﻣل ﻣﻊ اﻟﻣﺎﻛﯾﻧﺔ اﻟدﯾزل ﻓﻰ ﻫذا اﻟﻧظﺎم ﺑطﺎرﯾﺎت ﻗوﯾﺔ وﺷﺎﺣن ﺑطﺎرﯾﺎت ﯾﺗم
ﺗﻐذﯾﺗﻪ ﺳواء ﻣن ﻣﺻدر اﻟﻣدﯾﻧﺔ أو ﻣن ﻣوﻟد اﻟﻣﺎﻛﯾﻧﺔ وﺗﻘوم ﻫذﻩ اﻟﺑطﺎرﯾﺎت ﺑﺗﻐذﯾﺔ
اﻟﻘﺎﺑض اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﻲ وﻛذا ﺗﻐذﯾﺔ ﺳﺧﺎﻧﺎت اﻟﻣﺎﻛﯾﻧﺔ اﻟدﯾزل اﻟﻣوﺟودة ﻓﻰ دورة
اﻟزﯾت واﻟﻣﯾﺎﻩ ﻟﺟﻌﻠﻬﺎ داﺋﻣًﺎ ﺑدرﺟﺔ ﻋﺎﻟﯾﺔ ﻟﻼﺳﺗﺟﺎﺑﺔ ﻓﻰ ﺑدء اﻟﺣرﻛﺔ ﻟﻘﺑول اﻷﺣﻣﺎل
ﺑﻣﺟرد وﺻول ﺳرﻋﺗﻬﺎ إﻟﻰ ﺳرﻋﺔ اﻟﺗزاﻣن.
-ﺗوﺟد ﻓﻰ اﻷﺳواق وﺣدات ﻟﻣﺻﺎدر اﻟﺗﻐذﯾﺔ ﻋدﯾﻣﺔ اﻻﻧﻘطﺎع اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ )(NBDD
ﺑﻘدرات ﺣﺗﻰ 2500ك.ف.أ .ﻋﻧد ﺟﻬد ٣/٥٠/ ٣٨٠ﻓوﻟت 3/50/11000
ﻓوﻟت ) (Synchronous machineﺗﻘوم ﺑﺎﻟﻌﻣل ﺑﻬﺎ آﻟﺔ ﻣﺗزاﻣﻧﺔ واﺣدة ﺗﻌﻣل
ﻛﻣﺣرك وﻣو ﻟد ﻓﻰ اﻟﻧظﺎم ،وﻛﻣﺎ ﻫو ﻣوﺿﺢ ﻓﻰ اﻟﺷﻛل اﻟﻘﺎدم .
٧٤
أﺣﻣﺎل اﻟطوارئ ﻓﻰ اﻟﻣﺑﺎﻧﻰ
-أﺣﻣﺎل اﻹﻧﺎرة
ﯾﺟب اﺳﺗﺧدام ﻣﺻﺎدر اﻟﺗﻐذﯾﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﻰ ﺣﺎﻻت اﻟطوارئ ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻰ:
٧٥
-ﺗﺧﺻص أﺟزاء ﻣن أﺣﻣﺎل اﻹﻧﺎرة ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻹدارﯾﺔ واﻟﺗﺟﺎرﯾﺔ واﻟﻔﻧدﻗﯾﺔ
واﻟﺻﺣﯾﺔ)ﻣﺳﺗﺷﻔﯾﺎت( ﻟﺗﺳﻬﯾل ﺣرﻛﺔ اﻷﺷﺧﺎص ﺑﺎﻟﻣﺑﻧﻰ.
-ﯾﺟب ﻋﻠﻰ اﻷﻗل إﻧﺎرة اﻟﻣداﺧل واﻟﺳﻼﻟم ﺑﺎﻷدوار وﺳﻼﻟم اﻟﻬروب وﺧﺎﺻﺔ
ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻟﺳﻛﻧﯾﺔ.
-ﯾﺟب إﻧﺎرة ﺟزء ﻣن إﻧﺎرة ﻏرف اﻹﻗﺎﻣﺔ ﺑﺎﻟﻔﻧﺎدق واﻟﻣﺳﺗﺷﻔﯾﺎت.
-ﯾﺟب إﻧﺎرة ﺟزء ﻣن اﻟﻣﻧﺎطق اﻟﻌﺎﻣﺔ ﺑﺎﻟﻣﺑﺎﻧﻰ وأﻣﺎﻛن اﻻﺳﺗﻘﺑﺎل وأﻣﺎﻛن
اﻻﻧﺗظﺎر وﻛذا دورات اﻟﻣﯾﺎﻩ.
-إﻧﺎرة أى أﺟزاء ذات أﻫﻣﯾﺔ ﺧﺎﺻﺔ ﻓﻰ اﻟﻣﺑﺎﻧﻰ.
-ﯾﺧﺻص ﺟزء ﻣن إﻧﺎرة اﻟدور اﻟﺳﻔﻠﻰ )اﻟﺑدروم( وﺧﺻوﺻًﺎ ﻓﻰ اﻟﻣﺑﺎﻧﻰ
ﻣﺗﻌددة اﻟﺑدروﻣﺎت.
-ﯾﺟب إﻧﺎرة أﺟزاء ﻣن ﻣﺑﺎﻧﻰ اﻟﺳﺟون وﻣﺎ ﺷﺎﺑﻬﻬﺎ.
-ﯾﺟب إﻧﺎرة ﻏرف ﻣﺎﻛﯾﻧﺎت اﻟﻣﺻﺎﻋد وﻏرف اﻟﻣﺣوﻻت وﻟوﺣﺎت اﻟﺗوزﯾﻊ
اﻟرﺋﯾﺳﯾﺔ وﻏرف اﻟﻣوﻟدات اﻻﺣﺗﯾﺎطﯾﺔ.
-وﻻ ﺑد ﻣن اﺧﺗﯾﺎر أﺟزاء ﻣن طرﻗﺎت ﺣرﻛﺔ اﻷﻓراد ﺑﺎﻷدوار ﻹﻧﺎرﺗﻬﺎ ﻣن
ﻣﺻدر اﻟطوارئ وﺧﺎﺻﺔ ﻓﻰ اﻟﻔﻧﺎدق و اﻟﻣﺳﺗﺷﻔﯾﺎت.
-ﯾﺟب اﺧﺗﯾﺎر إﻧﺎرة أﺟزاء ﻣن دور اﻟﻌر ض وﻣداﺧﻠﻬﺎ وﻣﺧﺎرﺟﻬﺎ وﻛذا أﻣﺎﻛن
ﻟﻌب اﻷطﻔﺎل ﻹﻧﺎرﺗﻬﺎ ﻣن ﻣﺻدر اﻟطوارئ.
-ﯾﺗم اﺧﺗﯾﺎر أﺟزاء ﻣن اﻹﻧﺎرة اﻟﺧﺎرﺟﯾﺔ ﻟﺗﺄﻣﯾن ﺣرﻛﺔ اﻷﻓراد ﺧﺎرج اﻟﻣﺑﻧﻰ
إو ﻧﺎرﺗﻬﺎ ﻣن ﻣﺻدر اﻟطوارئ.
-ﯾﺟب إﻧﺎرة أﻧﻔﺎق اﻟﺳﯾﺎرات واﻟﻣﺷﺎة وﻣﺣطﺎت ﻣﺗرو اﻷﻧﻔﺎق وﻣﺎ ﺷﺎﺑﻬﻬﺎ ﻣن
ﻣﺻدر اﻟطوارئ.
أﺣﻣﺎل اﻟﻣﻌدات
ﯾﺟب ﺑﺎﻹﺿﺎﻓﺔ إﻟﻰ ﺗﻐذﯾﺔ اﻟﻣﻌدات اﻟﻬﺎﻣﺔ ﻣن ﻣﺻدر اﻟطوارئ أن ﯾﺗم ﺗﻐذﯾﺔ اﻹﻧﺎرة
اﻟﻣﻧﺎﺳﺑﺔ ﻟﻬﺎ أﯾﺿًﺎ ﻣن ﻣﺻدر اﻟطوارئ ﻛﻰ ﯾﺗﺣﻘق أداء اﻟﻐرض ﻣن ﺗﻐذﯾﺔ اﻟطوارئ وﻣن
ﺑﯾن ﻫذﻩ اﻟﻣﻌدات:
-ﻣﺻﺎﻋد اﻟرﻛﺎب ﺑﺎﻟﻣﺑﺎﻧﻰ اﻟﻣﺧﺗﻠﻔﺔ وﻣﺻﺎﻋد اﻟﻣرﺿﻰ ﺑﺎﻟﻣﺳﺗﺷﻔﯾﺎت.
-اﻟﺛﻼﺟﺎت ﺑﻣطﺎﺑﺦ اﻟﻔﻧﺎدق واﻟﻣﺳﺗﺷﻔﯾﺎت وﻛذا ﺛﻼﺟﺎت ﺣﻔظ اﻟﺟﺛث.
٧٦
-ﻣﺣطﺎت طﻠﻣﺑﺎت رﻓﻊ اﻟﻣﯾﺎﻩ وطﻠﻣﺑﺎت اﻟﺻرف أو اﻟﻧزح وﻛذا طﻠﻣﺑﺎت إطﻔﺎء اﻟﺣرﯾق.
-ﻣراوح ﺳﺣب اﻟدﺧﺎن ﻣن ﺳﻼﻟم وﻣﻣرات اﻟﻬروب.
-أﺟزاء ﻣن ﻣﻌدات اﻟﻣطﺎﺑﺦ ﻓﻰ اﻟﻣﺳﺗﺷﻔﯾﺎت واﻟﻔﻧﺎ]دق.
-ﺑﻌض اﻟﻣﻌد ات ﺑﺎﻟﻣﺻﺎﻧﻊ وﺧﺎﺻﺔ ﻓﻰ ﻣﺻﺎﻧﻊ اﻟﻣﻌﺎﻟﺟﺎت اﻟﻛﯾﻣﺎوﯾﺔ وﻣﺻﺎﻧﻊ
اﻟﺑﻼﺳﺗﯾك واﻟﺗﻰ ﺗﺗﺄﺛر ﺑﺄﺿرار ﻛﺑﯾرة ﻋﻧد اﻧﻘطﺎع اﻟﺗﯾﺎر اﻟﻛﻬرﺑﺎﺋﻰ.
ﯾﺟب ﺗﻐذﯾﺔ اﻟﻣﻌدات اﻟﻬﺎﻣﺔ اﻟﻣوﺟودة داﺧل اﻷﻣﺎﻛن اﻟﺗﺎﻟﯾﺔ وﻛذﻟك وﺣدات اﻹﻧﺎرة ﺑﻬﺎ وﻛذﻟك
ﯾﺟب ﺗدﺑﯾر أﺣد ﻣﺻﺎدر ﻋدم اﻧﻘطﺎع اﻟﺗﯾﺎر ﻟﻣﺛل ﻫذﻩ اﻟﻣﻌدات ﻣﺛل ).(UPS or NBG
-أﻧظﻣﺔ وأﺟﻬزة ﺗﺄﻣﯾن اﻟﻣﺑﺎﻧﻰ ﺿد اﻟﺳرﻗﺔ أو اﻻﺧﺗراق وأﺟﻬزة اﻷﻣن ﺑوﺟﻪ ﻋﺎم
ﻟﻠﻣﺑﻧﻰ.
-أﻧظﻣﺔ وأﺟﻬزة اﻟﺗﻧﺑﯾﻪ واﻹﻧذار ﺑﺎﻟﻣﺑﺎﻧﻰ.
-أﻧظﻣﺔ اﻟﺗﻠﯾﻔوﻧﺎت وﺳﻧﺗراﻻﺗﻬﺎ ﺑﺎﻟﻣﺑﺎﻧﻰ.
-أﻧظﻣﺔ اﻹذاﻋﺔ اﻟداﺧﻠﯾﺔ ﺑﺎﻟﻣﺑﺎﻧﻰ.
-أﻧظﻣﺔ إﻧذار اﻟﺣرﯾق ﺑﺎﻟﻣﺑﺎﻧﻰ.
-أﻧظﻣﺔ اﻟﻬواﺋﻰ اﻟﻣرﻛزى وﻣﺣطﺎت اﺳﺗﻘﺑﺎل اﻟﻘﻧوات اﻟﻔﺿﺎﺋﯾﺔ ﺑﺎﻟﻣﺑﺎﻧﻰ.
٧٧
-أﻧظﻣﺔ إﻧﺎرة ﻏرف اﻟﻌﻣﻠﯾﺎت واﻻﺳﺗدﻋﺎء اﻟﺻوﺗﻰ واﻟﺿوﺋﻰ ﺑﺎﻟﻣﺳﺗﺷﻔﯾﺎت وﻛذﻟك أﻧظﻣﺔ
ﺷﺎﺷﺎت اﻟﻣﺗﺎﺑﻌﺔ ﺑﻐرف اﻟﻌﻣﻠﯾﺎت وأﺟﻬزة اﻻﺗﺻﺎل ﺑﻬﺎ واﻷﺟﻬزة اﻟﻣوﺟودة ﺑﻐرف ال ﻋﻧﺎﯾﺔ
اﻟﻣرﻛزة واﻷﺟﻬزة اﻟﻣﺗﺻﻠﺔ ﺑﺎﻟﻣرﺿﻰ ﻟﻣراﻗﺑﺔ وظﺎﺋف اﻟﺟﺳم.
-أﻧظﻣﺔ وأﺟﻬزة اﻟﻛوﻣﺑﯾوﺗر وﺧﺻوﺻًﺎ ﻓﻰ اﻟﻣﺑﺎﻧﻰ اﻟﻌﺎﻣﺔ )إدارﯾﺔ – ﺗﺟﺎرﯾﺔ
–ﺑﻧوك – ﻣﺳﺗﺷﻔﯾﺎت – ﻓﻧﺎدق – واﻟﻣﺻﺎﻧﻊ اﻟﺗﻰ ﺗﻌﺗﻣد ﻋﻠﻰ اﻟﻛوﻣﺑﯾوﺗر ﻓﻰ إدارﺗﻬﺎ
وأﻧظﻣﺔ اﻟﺗﺣﻛم ﻓﻰ إدارة اﻟﻣﺑﻧﻰ )Power management system (PMS
-ﺗﻐذﯾﺔ إﻧﺎرة اﻟﻣراﻗﺑﺔ وأﺑراج اﻟﻣراﻗﺑﺔ ﺑﺎﻟﻣطﺎرات.
-ﺗﻐذﯾﺔ إﻧﺎرة ﻣﻣرات وأﺟﻬزة وأﻧظﻣﺔ اﻟﻬﺑوط وأﻧظﻣﺔ ﺷﺎﺷﺎت اﻟﻣراﻗﺑﺔ وأﺑراﺟﻬﺎ ﺑﺎﻟﻣطﺎرات.
-ﺗﺷﻐﯾل ﻣراﻛز اﻟﻘﯾﺎدة وأﺟﻬزﺗﻬﺎ وﺷﺎﺷﺎﺗﻬﺎ وأﺟﻬزة اﺗﺻﺎﻟﻬﺎ اﻟﻣﺧﺗﻠﻔﺔ.
٧٨
اﻟﻠوﺣﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ واﻟﻘواطﻊ اﻟﻛﻬرﺑﺎﺋﯾﺔ
٧٩
ﻣواﺻﻔﺎت اﻟﻘواطﻊ اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻣطﻠوﺑﺔ:
ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﺣرارﯾﺔ وﻣﻐﻧﺎطﯾﺳﯾﺔ ﻋﯾﺎرﯾﺔ ﺣﺳب اﻟﻌﯾﺎرات اﻟﻣطﻠوﺑﺔ ﻓﻲ
اﻟﻣﺧططﺎت أو اﻟﺟداول .وﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ذو ﺟودة ﻋﺎﻟﯾﺔ وﺑﺄﻧواع ﻏرﺑﯾﺔ
ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن اﻷﻧظﻣﺔ اﻟﻌﺎﻟﻣﯾﺔ.IEC 947 , VDE 0660 :
٨٠
اﻟﻘواطﻊ اﻟﻣﻘوﻟﺑﺔ MCCBﻓﻲ اﻟﻠوﺣﺎت اﻟرﺋﯾﺳﯾﺔ
٨١
.١٣ﺟﻣﯾﻊ اﻟﻘواطﻊ اﻟﺗﻲ ﻧوع اﻟﺣﻣﺎﯾﺔ ﻓﯾﻬﺎ إﻟﻛﺗروﻧﻲ ﯾﺟب أن ﺗﻛـون ﻣـزودة ﺑﻣﺄﺧـذ ﻹﻣﻛﺎﻧﯾـﺔ
رﺑطﻬﺎ ﻣﻊ اﻟﺣﺎﺳوب.
.١٤إﻣﻛﺎﻧﯾﺔ ﺗرﻛﯾب اﻛﺳﺳوارات ﻋﻠﻰ اﻟﻘواطـﻊ ﺣﺳـب ﺣﺎﺟـﺔ اﻟﻌﻣـل ﻣﺛـل :ﻣﺣرﻛـﺎت ،ﺗﻣﺎﺳـﺎت
ﻣﺳﺎﻋدة ،وﺷﯾﻌﺔ ﻫﺑوط ﺟﻬد أو وﺷﯾﻌﺔ ﻓﺻل ﻋن ﺑﻌد.
٨٢
ﻣواﺻﻔﺎت اﻟﻘواطﻊ اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﻲ اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ
.١ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﺣرارﯾﺔ وﻣﻐﻧﺎطﯾﺳﯾﺔ ﺣﺳب اﻟﻌﯾﺎرات اﻟﻣدوﻧﺔ ﻋﻠﻰ
اﻟﻣﺧططﺎت.
ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ذو ﺟودة ﻋﺎﻟﯾﺔ وﺑﺄﻧواع ﻏرﺑﯾﺔ ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن .٢
اﻷﻧظﻣﺔ اﻟﻌﺎﻟﻣﯾﺔ . IEC 947, VDE 0660
.٣ﯾﺟب أن ﺗﻛون اﻟﻘواطﻊ ﺑﻌﯾﺎر ٨٠أﻣﺑﯾر ﻓﻣﺎ ﻓوق ﻗواطﻊ ﺣرارﯾﺔ ﻣﻐﻧﺎطﯾﺳﯾﺔ ﻋﯾﺎرﯾﺔ
ﻣن ﻧوع ) MCCBوﻟﻛن ﺗﻘﺑل اﻟﻘواطﻊ اﻟﻐﯾر اﻟﻌﯾﺎرﯾﺔ MCBﻟﻐﺎﯾﺔ ١٢٥أﻣﺑﯾر ﻓﻲ
ﺣﺎل ﻛﺎﻧت اﻟﻠوﺣﺎت ﺗﺳﺗﺧدم ﻟﺣﻣﺎﯾﺔ دارات اﻹﻧﺎرة(.
ﺗﻛون اﻟﻘواطﻊ اﻟﻣﻐذﯾﺔ ﻟدارات اﻹﻧﺎرة واﻟﻣﺂﺧذ ﻣﺎ ﺑﯾن اﻟﻌﯾﺎرات ٦٣ – ٦أﻣﺑﯾر ﻣن ﻧوع .٤
MCB
Miniature circuit breakerوﺑﺄﻗطﺎب أﺣﺎدي ،ﺛﻧﺎﺋﻲ ،ﺛﻼﺛﻲ ﺣﺳب ﻣﺎ ﻫو
ﻣطﻠوب ﻓﻲ اﻟﻣﺧططﺎت.
ﺗﻛون اﻟﻘواطﻊ اﻟﻣﻐذﯾﺔ ﻟﻠﻣﺣرﻛﺎت )ﺛﻼﺛﯾﺔ اﻷﻗطﺎب( ﻣﺎ ﺑﯾن ) (٢٠٠-١أﻣﺑﯾر ﻣن .٥
ﻧوع Motor protective circuit breakerﺗﺳﺗﺧدم ﺑﺷﻛل ﺧﺎص ﻟﺣﻣﺎﯾﺔ
اﻟﻣﺣرﻛﺎت.
-ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻘواطﻊ ﺣرارﯾﺔ ﻣﻐﻧﺎطﯾﺳﯾﺔ ﻣﺻﻧّﻌﺔ وﻣﻘﺑوﻟﺔ ﻣن ﻗﺑـل اﻷﻧظﻣـﺔ اﻟﻌﺎﻟﻣﯾـﺔ
.IEC947…, VDE 0660
ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﻘواطﻊ ﻋﯾﺎرﯾﺔ ﺑﺎﻟﻣﺟﺎﻟﯾن اﻟﺣراري واﻟﻣﻐﻧﺎطﯾﺳﻲ ﻛل ﻋﻠﻰ ﺣدى. -
اﻟﻘواطﻊ ﻟﻐﺎﯾﺔ ٢٥٠أﻣﺑﯾر ﯾﺟب أن ﯾﻛون اﻟﻌﯾﺎر اﻟﺣراري ﻣن 0.8 – 1 x In
واﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن 6 – 10 x In
0.5 – 1 x In اﻟﻘواطﻊ ﻣن ٤٠٠أﻣﺑﯾر ﻓﻣﺎ ﻓوق ﯾﺟب أن ﯾﻛون اﻟﻌﯾﺎر اﻟﺣراري ﻣن
واﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ ﻣن 2 – 10 x In
-اﺧﺗﺑﺎر اﻟﺗوﺗر اﻟﻧﺑﺿﻲ ﻟﻠﻘواطﻊ ٦٠٠٠ﻓوﻟط أو ٨٠٠٠ﻓوﻟط
درﺟﺔ اﻟﺣرارة ٤٠+ ، ٢٥- :درﺟﺔ ﻣﺋوﯾﺔ ﻓﻲ ﺣﺎﻟﺔ وﺳط ﻣﻐﻠق. -
٨٣
-ﺷدة اﻟﻘطﻊ ﻟﻠﻘواطﻊ ........ :ﻛﯾﻠو أﻣﺑﯾر .ICU = ICS
-اﻣﺎ ﻓﻲ ﺣﺎل ﻛﺎﻧت اﻟﻘواطﻊ اﻟﻣطﻠوﺑـﺔ ﻓـﻲ اﻟﻣﺧططـﺎت ﻣـن ﻧـوع MCCBوﺑﺷـدة ﻗطـﻊ ١٨
ﻛﯾﻠـــو أﻣﺑﯾـــر وﺗﺳـــﺗﺧدم ﻟﺣﻣﺎﯾـــﺔ اﻟﻛـــﺑﻼت ﯾﻣﻛـــن أن ﺗﻛـــون اﻟرﯾﻠﯾـــﻪ اﻟﺣـــراري ﻋﯾـــﺎري ﻟﻛـــن
اﻟﻣﻐﻧﺎطﯾﺳﻲ ﺛﺎﺑت.
-درﺟﺔ اﻟﺗﻠوث ﻟﻠﻘواطﻊ ﯾﺟب أن ﺗﻛون ﻣن اﻟدرﺟﺔ اﻟﺛﺎﻟﺛﺔ وﺗﺳﺗﺧدم ﻟﻸﻏراض اﻟﺻﻧﺎﻋﯾﺔ.
-ﺗوﺗر اﻟﻌﻣل ٦٩٠ :ﻓوﻟط ٥٠ ،ﻫرﺗز.
ﯾﺟب أن ﺗﻛون اﻟﻘواطﻊ ﺧﺎﺿﻌﺔ ﻟﻠﺗﺟﺎرب اﻟﻣﻧﺎﺧﯾﺔ IEC60068 -
-ﺗﻐذﯾﺔ اﻟﻘواطﻊ :ﻣن اﻷﻋﻠﻰ أو اﻷﺳﻔل.
ﺗﻛون اﻟﻘواطـﻊ ﻗﺎﺑﻠـﺔ ﻟﻠﺗرﻛﯾـب ﻋﻠﯾﻬـﺎ اﻹﻛﺳﺳـوارات اﻟﺿـرورﯾﺔ ﻣـن ﺗﻣﺎﺳـﺎت ﻣﺳـﺎﻋدة ،ﻗﻔـل -
ﻣﯾﻛﺎﻧﯾﻛﻲ ،وﺷﯾﻌﺔ ﻫﺑوط ﺟﻬد اﻟﺦ …..
٨٤
اﺧﺗﺑﺎر اﻟﺗوﺗر اﻟﻧﺑﺿﻲ ٦٠٠٠ :ﻓوﻟط. -
درﺟﺔ اﻟﺗﻠوث :ﻣن اﻟدرﺟﺔ اﻟﺛﺎﻟﺛﺔ وﺗﺳﺗﺧدم ﻷﻏراض ﺻﻧﺎﻋﯾﺔ. -
ﺗوﺗر اﻟﻌﻣل ٦٩٠ :ﻓوﻟط ٥٠ ،ﻫرﺗز. -
اﻟﻌﯾﺎر اﻟﺣراري :ﯾﻣﻛن ﺗﻌﯾﯾرﻫﺎ ﻣﺎ ﺑﯾن 0.6 – 1 x Iu -
اﻟﻌﯾﺎر اﻟﻣﻐﻧﺎطﯾﺳﻲ :ﺛﺎﺑت ١٤ﻣرة x Iu 14ﺑﺣﯾث ﺗﺗﺣﻣل إﻗﻼﻋﺎت اﻟﻣﺣرﻛﺎت. -
اﻟﻘواطــﻊ ﯾﺟــب أن ﺗﻛــون ﻟــﻪ ﻣﯾــزة ) Phase-failure sensitivityﺣﺳﺎﺳــﯾﺔ اﻧﻘطــﺎع -
اﻟﻔﺎز( وﻓق ﻧظﺎم IEC/EN 60947-4-1
ﻣواﺻﻔﺎت اﻟﻠوﺣﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ
اﻟﻐﺎﯾﺔ ﻣن اﻟﻣﺷروع:
ﺗﻘدﯾم وﺗﻧﻔﯾذ اﻟﻠوﺣﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟرﺋﯾﺳﯾﺔ واﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ ﺑﺣﯾث ﺗﻛون ﺟﺎﻫزة ﻟﻠﺗرﻛﯾب واﻟﺗﺷﻐﯾل
ﺣﺳب اﻟﻣواﺻﻔﺎت واﻟﺷروط اﻟﻔﻧﯾﺔ اﻟﻣطﻠوﺑﺔ.
ﺳــﺗﻛون ﻫــذﻩ اﻟﻠوﺣــﺎت ﻣﺟﻬــزة ﺑﺟﻣﯾــﻊ اﻟﻘواطــﻊ اﻟﻛﻬرﺑﺎﺋﯾــﺔ اﻟﻣطﻠوﺑــﺔ ﻓــﻲ اﻟﻣﺧططــﺎت واﻟﺑــﺎرات
اﻟﻧﺣﺎﺳﯾﺔ وأﺟﻬزة اﻟﻘﯾﺎس ﺟﺎﻫزة ﻟﻠﺗرﻛﯾب واﻟﺗﺷﻐﯾل.
اﻟﺧﻼﯾــﺎ ﯾﺟــب أن ﺗﻛــون ﻣــن اﻟﺻــﻧﺎﻋﺔ اﻟﻣﺣﻠﯾــﺔ وﻣــن اﻟﻧــوع اﻟﺗــﻲ ﺗﺳــﺗﺧدم ﻟﺗوزﯾــﻊ اﻟطﺎﻗــﺔ
اﻟﻛﻬرﺑﺎﺋﯾﺔ
Power distribution boardأي ﻣﺻﻧوﻋﺔ وﻓق اﻟﻧظﺎم اﻟﻛﻬرﺑﺎﺋﻲ .IEC439-1
ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻠوﺣﺎت ﻋﻠﻰ ﺷﻛل ﺧﻠﯾـﺔ ﻣﺳـﺗﻘﻠﺔ أو ﺧﻼﯾـﺎ ﻛﻬرﺑﺎﺋﯾـﺔ ﻗﺎﺑﻠـﺔ ﻟﻠﺗﺟﻣﯾـﻊ ﻣـﻊ
ﺑﻌﺿﻬﺎ اﻟﺑﻌض وﯾﻛون ﻋدد اﻟﺧﻼﯾـﺎ ﺣﺳـب اﻟﻘواطـﻊ اﻟﺗـﻲ ﺳـﺗرﻛب ﺿـﻣﻧﻬﺎ ﻣـﻊ ﻣراﻋـﺎة ﻋﻣﻠﯾـﺔ
اﻟﺗوﺳﯾﻊ إو ﺿﺎﻓﺔ ﺧﻼﯾﺎ ﺟدﯾدة ﻣﺳﺗﻘﺑﻼً.
٨٥
اﻟﻘواطﻊ ﺑﺎﺳﺗطﺎﻋﺔ ٨٠٠أﻣﺑﯾر وﻣﺎ ﻓوق ﯾﺟـب أن ﺗُرﻛـب ﺿـﻣن ﺧﻠﯾـﺔ ﻣﺳـﺗﻘﻠﺔ .أﻣـﺎ
إذا ﻛﺎن اﻟﻘﺎطﻊ اﻟرﺋﯾﺳـﻲ ﻟﻠوﺣـﺔ ٦٣٠أﻣﺑﯾـر وﻣـﺎ دون ﯾﻣﻛـن أن ﯾُرﻛـب ﻣـﻊ اﻟﻘواطـﻊ
اﻟﻔرﻋﯾﺔ ﺿﻣن ﺧﻠﯾﺔ واﺣدة.
ﯾﺟب أن ﺗﺻﻧﻊ اﻟﺧﻼﯾﺎ ﻣن أﻟواح اﻟﺻـﺎج اﻟﻔوﻻذﯾـﺔ ﺑﺳـﻣﺎﻛﺔ ٢ﻣﻠـم وﻫـﻲ ﻋﺑـﺎرة ﻋـن
ﻫﯾﻛـل ﻣــن اﻟﺻــﺎج ﺑﺳــﻣﺎﻛﺔ ٢ﻣﻠــم وﻣﻠﺣوﻣــﺔ ﻣـﻊ ﺑﻌﺿــﻬﺎ ﺑﺷــﻛل ﻣﺗــﯾن ﺑﺣﯾــث ﺗﺷــﻛل
ﻫﯾﻛــل اﻟﻠوﺣــﺔ ،وﯾﻛــون اﻟﻐطــﺎء اﻟﺧﻠﻔــﻲ ﻗطﻌــﺔ واﺣــدة وﻣــزودة ﺑﺄﻏطﯾــﺔ ﺟﺎﻧﺑﯾــﺔ ﻋﻠــﻰ
طرﻓﻲ ﻧﻬﺎﯾﺔ اﻟﻠوﺣﺔ ﺑﺣﯾث ﯾﻣﻛن ﻓﻛﻬﺎ ﺣﺳب اﻟﺣﺎﺟﺔ.
ﺗُرﻛب اﻷﺑواب اﻷﻣﺎﻣﯾـﺔ ﻋﻠـﻰ اﻟﻬﯾﻛـل ﺑﻣﻔﺻّـﻼت ﺧﺎﺻـﺔ وﺗﻔـﺗﺢ اﻷﺑـواب ﺑزاوﯾـﺔ ١٢٠
درﺟﺔ ﻟﺳﻬوﻟﺔ اﻟﻌﻣـل ﺿـﻣﻧﻬﺎ .وﺗﻛـون ﻫـذﻩ اﻷﺑـواب ﻣـزودة ﺑﺟواﻧـﺎت ﻣطﺎطﯾـﺔ ﻋﻠـﻰ
إطﺎرات اﻷﺑواب ﻣن أﺟل ﺗﺣﻘﯾق ﻛﺗﺎﻣﺔ ﻋﺎﻟﯾﺔ.
ﯾﺟب أن ﯾﻛـون ارﺗﻔـﺎع ﻛـل ﺧﻠﯾـﺔ ﻣـن اﻟﺧﻼﯾـﺎ )ﺳـﺗﺎﻧدر( ٢ﻣﺗـر وﻻ ﯾﻘـل ﻋﻣﻘﻬـﺎ ﻋـن
٦٠ﺳم .أﻣﺎ اﻟﻌرض ﻓﯾﻛون ﺣﺳب اﻟﻘواطﻊ اﻟﺗﻲ ﺳﺗرﻛب ﺿـﻣﻧﻬﺎ ﺑﺣﯾـث ﻻ ﯾﻘـل ﻋـن
٥٠ﺳم ) ٦٠٠×٥٠٠×٢٠٠٠ﻣﻠم(.
ﺗﻛون اﻟﻠوﺣﺔ ﻣﻐﻠﻘﺔ وﻛﺗﯾﻣﺔ ﻣن ﺟﻣﯾـﻊ اﻟﺟﻬـﺎت ﻣـﺎ ﻋـدا اﻷﺳـﻔل ﺣﯾـث ﺗﻛـون ﻣﻔﺗوﺣـﺔ
ﻟدﺧول وﺧروج اﻟﻛﺎﺑﻼت .ﻛﻣﺎ ﺗزود اﻟﻠوﺣﺔ ﺑﻘﺎﻋدة ﻣﻌدﻧﯾﺔ ﻋﻠﻰ طوﻟﻬﺎ ﺑﺳﻣﺎﻛﺔ ٢ﻣﻠم
وﺑﺎرﺗﻔﺎع ١٠ﺳم ﻣن أﺟل ﺗﺛﺑﯾﺗﻬﺎ ﻋﻠـﻰ اﻟﻘﺎﻋـدة اﻻﺳـﻣﻧﺗﯾﺔ ﺛـم ﺗوﺿـﻊ وﺗﺛﺑـت اﻟﻠوﺣـﺔ
ﻋﻠﻰ ﻫذﻩ اﻟﻘﺎﻋدة اﻟﻣﻌدﻧﯾﺔ.
ﯾﺟب أن ﺗزود ﻛﺎﻓﺔ اﻟﻠوﺣﺎت ﺑﻘﻔل أﺟﻧﺑﻲ ﻣوﺣد.
ﻟون اﻟﻠوﺣﺔ ﻋﺎﺟﻲ وﺗدﻫن ﻋن طرﯾق ﺑﺦ ﺑودرة إﻟﻛﺗروﺳﺗﺎﺗﯾﻛﻲ.
ﯾﺟــب أن ﯾﻛــون اﻟﺗﻘﺳــﯾم اﻟــداﺧﻠﻲ ﻟﻠوﺣــﺎت اﻟرﺋﯾﺳــﯾﺔ ﻻ ﯾﻘــل ﻋــن ) (Form 2ﺣﺳــب
اﻟﻧظﺎم IEC439ﺑﺣﯾث ﯾﻛون ﺣﺳب اﻵﺗﻲ:
٨٦
ﺗﻛون اﻟﺧﻠﯾﺔ ﻣﻘﺳﻣﺔ داﺧﻠﯾﺎً إﻟﻰ ﺛﻼث ﺣﺟرات وﻛل ﺣﺟرة ﻣﻔﺻوﻟﺔ داﺧﻠﯾﺎً ﻋن اﻷﺧر وﻟﻬﺎ ﺑﺎﺑﻬﺎ
اﻟﻣﺳﺗﻘل:
٨٧
اﻟﻣواﺻﻔﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻟﻠّوﺣﺎت:
.١ﯾﺟب أن ﺗﺻﻧﻊ وﺗﺟﻣﻊ اﻟﻠوﺣﺎت وﻓق اﻟﺷروط اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻌﺎﻟﻣﯾﺔ .IEC 439
.٢ﺗرﻛب ﺟﻣﯾﻊ اﻟﺗﺟﻬﯾـزات اﻟﻛﻬرﺑﺎﺋﯾـﺔ )اﻟﻘواطـﻊ …اﻟـﺦ (.اﻟﻣـذﻛورة ﻓـﻲ اﻟﻣﺧططـﺎت ﺿـﻣن
ﻫذﻩ اﻟﻠوﺣﺔ وﻟﻛـن ﯾﺟـب اﻷﺧـذ ﺑﻌـﯾن اﻻﻋﺗﺑـﺎر أن ﺗرﻛﯾـب اﻟﻘواطـﻊ ﺿـﻣن اﻟﺧﻼﯾـﺎ وﺗﺻـﻣﯾم
اﻟﻠوﺣﺔ وﻋدد اﻟﺧﻼﯾﺎ ﯾﻛون ﺑﺷـﻛل ﻓﻧـﻲ وﻣـدروس ﻣـﻊ ﻣراﻋـﺎة ﺷـروط اﻟﻧﺷـر اﻟﺣـراري و ﻻ
ﺗرﻛب اﻟﻘواطﻊ ﺿﻣن اﻟﺧﻠﯾﺔ ﺑﻛﻣﯾﺎت ﻋﺷواﺋﯾﺔ دون دراﺳﺔ اﻟﻧﺷر اﻟﺣراري.
.٣ﯾﺟب أن ﺗﺗﺣﻣل اﻟﻠوﺣﺔ ﺷدة ﻗطﻊ ﻋﺎﻟﯾﺔ.
.٤درﺟﺔ اﻟﻛﺗﺎﻣﺔ ﻟﻠوﺣﺎت.IP 40 :
.٥ﺗوﺗر اﻟﻌﻣل (٤٠٠ – ٣٨٠) :ﻓوﻟط ٥٠ ،ﻫرﺗز.
.٦ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ ٦٩٠ﻓوﻟط.
.٧ﺧطوط اﻟﺷﺑﻛﺔ )اﻟﺑﺎرات( :ﺧﻣس ﺧطوط . L1, L2, L3, N, PE
.٨ﯾﺟب ﺣﻣﺎﯾﺔ ﺟﻣﯾﻊ دارات اﻟﺗﺣﻛم ﺑواﺳطﺔ ﻓﯾوز /١/أﻣﺑﯾر ﺑﺷدة ﻗطﻊ ﻋﺎﻟﯾﺔ.
ﺗ ﺷﻛل ﻧظﺎم اﻟﺑﺎرات ﻓﻲ اﻟﻠوﺣﺔ اﻟﻛﻬرﺑﺎﺋﯾﺔ أﻫﻣﯾـﺔ ﻛﺑﯾـرة ﻟﺿـﻣﺎن اﺳـﺗﻣرارﯾﺔ ﻋﻣـل اﻟﻠوﺣـﺔ .وﯾﺟـب
أن ﯾﻛــون ﻫــذا اﻟﻧظــﺎم ﻣطﺎﺑﻘ ـﺎً ﻟﻠﻧظــﺎم اﻟﻛﻬرﺑــﺎﺋﻲ ،IEC 439-1وذات وﺛوﻗﯾــﺔ ﻋﺎﻟﯾــﺔ ﺗﺣﻘــق
ﻣﺗطﻠﺑﺎت اﻻرﺗﻔﺎع اﻟﺣراري ﻟﻠﺑﺎرات وﺷدة ﺗﯾﺎر اﻟﻘﺻر ﻟﻣدة ﺛﺎﻧﯾﺔ واﺣدة.
ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﺑﺎرات ﺿﻣن اﻟﻠوﺣﺎت ﻧﺣﺎﺳﯾﺔ إﻟﻛﺗروﻟﯾﺗﯾﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ وﺑﻛﺛﺎﻓـﺔ ﺗﯾـﺎر ﻻ
ﺗزﯾد ﻋن ١.٦أﻣﺑﯾر/ﻣم. ٢
إن ﺗﺻﻣﯾم ﻧظﺎم اﻟﺑﺎرات ﺿﻣن اﻟﻠوﺣﺔ ﯾﻌﺗﻣد ﻋﻠﻰ اﻟﺗوﺿﻊ اﻷﻓﻘﻲ واﻟﺷﺎﻗوﻟﻲ .
ﻓـﻲ ﺣـﺎل ﻛـون اﻟﻠوﺣـﺔ ﺗﺗـﺄﻟف أﻛﺛـر ﻣـن ﺧﻠﯾـﺔ ﯾـﺗم ﺗﻣرﯾـر اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ L1, L2, L3ﻋﺑـر
اﻟﺧﻼﯾﺎ ﺑﺷﻛل أﻓﻘﻲ ﻟﺗﻐذي اﻟﺑﺎرات اﻟﺷﺎﻗوﻟﯾﺔ اﻟﺗﻲ ﺗﺗﻐذى ﻣﻧﻬﺎ اﻟﻘواطﻊ ﻓﻲ اﻟﺧﻼﯾﺎ اﻟﺗـﻲ ﺗﺗﺿـﻣن
ﻗواطﻊ ﺑﻌﯾﺎرات ٦٣٠أﻣﺑﯾر وﻣﺎ دون.
٨٨
وﯾرﻛب أﯾﺿﺎً ﻓﻲ اﻷﺳﻔل وﻋﻠﻰ طـول اﻟﻠوﺣـﺔ ﺑـﺎر ﺣﯾـﺎدي –N-ﻣﺛﺑـت ﻋﻠـﻰ ﺣﻣـﺎﻻت ﺑـﺎرات وﺑـﺎر
أرﺿﻲ .PE-
ﺗﺛّﺑت اﻟﺑﺎرات ﻋﻠﻰ ﺣﻣـﺎﻻت ﺧﺎﺻـﺔ أﺟﻧﺑﯾـﺔ اﻟﺻـﻧﻊ ﺗﺗﺣﻣـل اﺟﻬـﺎدات دﯾﻧﺎﻣﯾﻛﯾـﺔ ﻋﺎﻟﯾـﺔ أﺛﻧـﺎء دارة
اﻟﻘﺻر.
وﯾﺗم ﺗﺻﻧﯾﻊ ﺣﺎﻣﻼت اﻟﺑﺎرات ﻣن ﺑـوﻟﯾﻣﯾرات ﻋﺎﻟﯾـﺔ اﻟﺟـودة واﻟﺗـﻲ ﺗـؤﻣن ﻋﺎزﻟﯾـﺔ ﻛﻬرﺑﺎﺋﯾـﺔ ﻋﺎﻟﯾـﺔ
ﻟﻠﻘﺿــﺑﺎن اﻟﻧﺣﺎﺳــﯾﺔ ،وﺗﺗﺣﻣــل ﺑﺷــﻛل ﺟﯾــد اﻻﺟﻬــﺎدات اﻟﺣرارﯾــﺔ واﻟﻣﯾﻛﺎﻧﯾﻛﯾــﺔ اﻟﻧﺎﺗﺟــﺔ ﻋــن ﺗﯾــﺎرات
اﻟﻘﺻر ﻛﻣﺎ ﺗﺗﺣﻣل اﻟﺗﻐﯾﯾرات اﻟﺣرارﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻋن اﻟﺗﺷﻐﯾل.
ﯾﺟب أن ﺗﻛون ﺟﻣﯾﻊ اﻟﺗﻣدﯾدات ﺿﻣن اﻟﻠوﺣﺎت ﺑطرﯾﻘﺔ ﻓﻧﯾﺔ وﺻﺣﯾﺣﺔ ﺑﺣﯾث ﺗﻛون ﺗﻐذﯾﺔ
اﻟﻘواطﻊ ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﺣﺳب اﻵﺗﻲ:
ﯾــﺗم ﺗﻐذﯾــﺔ اﻟﻘواطــﻊ ٢٠٠أﻣﺑﯾــر وﻣــﺎ دون ﻣــن اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ ﺑواﺳــطﺔ ﻛــﺑﻼت
ﺷﻌرﯾﺔ ﺑﻌﺎزﻟﯾﺔ ٦٩٠ﻓوﻟط وﺑﻣﻘﺎطﻊ ﻣﻧﺎﺳـﺑﺔ ﺣﺳـب ﺗﯾـﺎرات اﻟﻘواطـﻊ وﻧظـﺎم IEC
.439
٨٩
وﺗﻐذﯾﺔ اﻟﻘواطﻊ ٢٥٠أﻣﺑﯾر وﻟﻐﺎﯾﺔ ٦٣٠أﻣﺑﯾر ﻣن اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ ﯾـﺗم ﺑواﺳـطﺔ
ﺑﺎرات ﻣرﻧﺔ ﻣﻌزوﻟﺔ ﺧﺎﺻﺔ ﺗﺳﺗﺧدم ﻟﻠﺗﻣدﯾـدات ﺿـﻣن اﻟﻠوﺣـﺎت ﺑﻌﺎزﻟﯾـﺔ ٦٩٠ﻓـوﻟط
وﺑﻣﻘﺎطﻊ ﻣﻧﺎﺳﺑﺔ ﺣﺳب ﺗﯾﺎرات اﻟﻘواطﻊ.
وﺗﻐذى اﻟﻘواطﻊ ﺑﺗﯾﺎر اﺳﻣﻲ أﻋﻠﻰ ﻣن ٦٣٠أﻣﺑﯾر ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﺑواﺳطﺔ
ﺑﺎرات ﻧﺣﺎﺳﯾﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ أو ﺑﺎرات ﻣرﻧﺔ أﺟﻧﺑﯾﺔ اﻟﺻﻧﻊ وﺣﺳب اﻟﻣﻘﺎطﻊ
اﻟﻣﻧﺎﺳﺑﺔ.
إن ﻋﻣﻠﯾﺔ ﺗﻔرﯾﻊ اﻟﻛﺑﻼت اﻟﺷﻌرﯾﺔ واﻟﺑﺎرات اﻟﻣرﻧﺔ ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳـﯾﺔ ) (L1-L2-L3ﺗـﺗم
ﻋﺑر ﻣﻘﺎﻣط )ﻛﻠﯾﺑﺳـﺎت( ﺧﺎﺻـﺔ ﺗرﻛـب ﻋﻠـﻰ اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ وﺗﻔـرّع ﻣﻧﻬـﺎ اﻟﻛـﺑﻼت واﻟﺑـﺎرات
اﻟﻣرﻧﺔ ﻟﺗﻐذﯾﺔ اﻟﻘواطﻊ وﻻ ﯾﺳﻣﺢ ﺑﺗﺛﻘﯾب اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﻟﻠﺗﻔرﯾﻊ ﻣﻧﻬﺎ.
اﻟﻠوﺣﺎت اﻟﻔرﻋﯾﺔ:
ﯾﺟـــب أن ﺗﻛـــون ﻫـــذﻩ اﻟﻠوﺣـــﺎت ﻣﺟﻬـــزة ﺑﺟﻣﯾـــﻊ اﻟﻘواطـــﻊ واﻟﺗﺟﻬﯾـــزات اﻟﻛﻬرﺑﺎﺋﯾـــﺔ اﻟﻣطﻠوﺑـــﺔ ﻓـــﻲ
اﻟﻣﺧططــﺎت وﻣﺻ ـﻧّﻌﺔ وﻓــق اﻟﻣواﺻــﻔﺎت اﻟﻣطﻠوﺑــﺔ ﻓــﻲ دﻓﺗــر اﻟﺷــروط
اﻟﻔﻧﯾﺔ ﻛﺎﻣﻠﺔ ﺟﺎﻫزة ﻟﻠﺗرﻛﯾب واﻻﺳﺗﺛﻣﺎر.
٩٠
ﻫﯾﻛل اﻟﺻﺎج ﻟﻠّوﺣﺎت:
ﯾﺟب أن ﺗﻛون ﻫذﻩ اﻟﻠوﺣﺎت ﺟدارﯾﺔ أو ﻟوﺣﺎت ﺗرﻛﯾب أرﺿﻲ ﺣﺳب ﻣواﻗﻊ ﺗرﻛﯾﺑﻬـﺎ ﻣﺻـﻧّﻌﺔ ﻣـن
أﻟواح اﻟﺻﺎج اﻟﻔوﻻذﯾﺔ ﺑﺳﻣﺎﻛﺔ ١.٥ﻣﻠم.
ﺗﻛون اﻟﻠوﺣﺎت ﻣﻐﻠﻘﺔ وﻛﺗﯾﻣﺔ ﻣن ﺟﻣﯾﻊ اﻟﺟﻬﺎت وﺗزود ﻓﻲ أﻋﻠﻰ وأﺳﻔل اﻟﻠوﺣﺎت ﺑﺄﻏطﯾﺔ ﯾﻣﻛـن
ﻓﻛﻬﺎ ﻟدﺧول اﻟﻛﺑﻼت.
أﻣﺎ ﻋﻠﻰ اﻟ ﻬﯾﻛل اﻟﺧﺎرﺟﻲ ﺗُﺛﺑت اﻷﺑواب ﻋﺑر ﻣﻔﺻﻼت ﺧﺎﺻﺔ ،وﺗﻔﺗﺢ اﻷﺑواب ﺑزاوﯾﺔ أﻛﺛر ﻣن
١٢٠درﺟﺔ ﻟﺗﺳﻬﯾل ﻋﻣﻠﯾﺔ اﻟﺻﯾﺎﻧﺔ ﻓﻲ داﺧل اﻟﻠوﺣﺔ وﺗزود ﻋﻠﻰ إطﺎرات اﻷﺑواب ﺟواﻧﺎت
ﻣطﺎطﯾﺔ )ﻛﺎوﺗﺷوﻛﯾﺔ( ﻣن أﺟل ﺗﺣﻘﯾق ﻛﺗﺎﻣﺔ ﻋﺎﻟﯾﺔ.
ﺗﻛون اﻟﻠوﺣﺎت ﻣﺻﻧّﻌﺔ ﺑﺑﺎب أو ﻏطﺎء داﺧﻠﻲ ﯾﻐطﻲ اﻟﺗﺟﻬﯾزات اﻟﻣرﻛﺑﺔ ﻓﻲ اﻟداﺧل واﻟذي ﺗظﻬر
ﻣﻧﻪ ﺻواﻋد اﻟﻘواطﻊ اﻟﺻﻐﯾرة وﺑﺎب ﺛﺎﻧﻲ ﺧﺎرﺟﻲ ﺷﻔﺎف ﻋﻠﻰ طول اﻟﻠوﺣﺔ.
أﺑﻌﺎد اﻟﻠوﺣﺎت ﯾﺟب أن ﺗﻛون ﺑﺄﺑﻌﺎد ﻧظﺎﻣﯾﺔ وﻓق اﻟﻘواطﻊ واﻟﺗﺟﻬﯾزات اﻟﺗﻲ ﺳﺗرﻛب ﺿﻣﻧﻬﺎ
وﺑﻘﯾﺎﺳﺎت )ﺳﺗﺎﻧدرد( وﻣن ﻣﺿﺎﻋﻔﺎت ٢٠ﺳم ﺑﺣﯾث ﻻ ﯾﻘل ﻋرض اﻟﻠوﺣﺎت ﻋن ٦٠ﺳم.
)اﻟﻣﻘﺻود ﻣن ﻣﺿﺎﻋﻔﺎت ٢٠ﺳم ﻣﺛﺎل ٢٠٠×٦٠٠×١٠٠٠ :طول × ﻋرض × ﻋﻣق(.
ﯾرﻛب داﺧل اﻟﻠوﺣﺔ ﻫﯾﻛل ﻣﻌدﻧﻲ ﻣﺗﺣرك ﻣﺻﻧوع ﻣـن اﻟﺻـﺎج اﻟﻣزﯾﺑـق ﺑﺳـﻣﺎﻛﺔ ١.٥ﻣﻠـم ﺑﺣﯾـث
ﺗرﻛب ﻋﻠﯾﻬﺎ اﻟﻘواطﻊ واﻟﺗﺟﻬﯾزات اﻟﻛﻬرﺑﺎﺋﯾﺔ اﻟﻣطﻠوﺑﺔ وﯾﻛون ﺗرﺗﯾب اﻟﺗﺟﻬﯾزات ﻓﻲ داﺧـل اﻟﻠوﺣـﺔ
ﺣﺳب اﻵﺗﻲ:
-اﻟﻘﺳم اﻟﻌﻠوي ﻣـن اﻟﻠوﺣـﺔ ﺗرﻛـب اﻟﺑـﺎرات اﻟرﺋﯾﺳـﯾﺔ )إن وﺟـدت( L1, L2, L3ﻣﺛﺑﺗـﺔ ﻋﻠـﻰ
ﺣﻣﺎﻻت ﺑﺎرات ﺧﺎﺻﺔ ﺗﺗﺣﻣل اﻹﺟﻬﺎدات اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎرات اﻟﻘﺻر.
اﻟﻘﺳــم اﻷوﺳــط ﺗرﻛــب اﻟﻘواطــﻊ واﻟﺗﺟﻬﯾ ـزات اﻟﻛﻬرﺑﺎﺋﯾــﺔ اﻟﻣطﻠوﺑــﺔ اﻟﺗــﻲ ﺗﺛﺑــت ﻋﻠــﻰ ﺻــﻔﺎﺋﺢ -
ﻓوﻻذﯾﺔ ﻣزﯾﺑﻘﺔ ﺑﺳﻣﺎﻛﺔ ١.٥ﻣﻠم.
اﻟﻘﺳم اﻟﺳﻔﻠﻲ ﺗرﻛـب ﻣـراﺑط )ﺟﻧﻛﺳـﯾوﻧﺎت( اﻟـدﺧل واﻟﺧـرج ﻟﻸﺳـﻼك ﺣﯾـث ﯾﻛـون ﻟﻛـل ﻗـﺎطﻊ -
ﻣرﺑط ﺧﺎص ﺑﻪ وﯾرﻛب أﯾﺿﺎً ﻓﻲ اﻷﺳﻔل وﻋﻠﻰ طول اﻟﻠوﺣﺔ ﺑﺎر اﻟﺣﯾﺎدي Nوﺑﺎر اﻷرﺿﻲ.
أﻣــﺎ ﻓــﻲ ﺣــﺎل ﻛﺎﻧــت اﻟﻠوﺣــﺎت اﻟﻣطﻠوﺑــﺔ ﺻــﻐﯾرة ﻟــدارات اﻹﻧــﺎرة ﻓــﯾﻣﻛن اﻻﺳــﺗﻐﻧﺎء ﻋــن اﻟﺑــﺎرات
اﻟرﺋﯾﺳﯾﺔ . L1, L2, L3
٩١
اﻟﻣواﺻﻔﺎت اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻟﻠوﺣﺎت:
-ﺗرﻛب اﻟﺗﺟﻬﯾزات اﻟﻛﻬرﺑﺎﺋﯾﺔ ﻓﻲ اﻟﻠوﺣﺎت ﺑﺷﻛل ﻓﻧﻲ وﻣدروس وﺑﺣﯾث ﺗوﺻﱠل ﺟﻣﯾﻊ اﻟﻘواطـﻊ
ﻣن ﻣﺧﺎرﺟﻬﺎ إﻟﻰ ﻣراﺑط )ﺟﻧﻛﺳﯾوﻧﺎت( ﺧﺎﺻﺔ ﻟﻛل ﻗﺎطﻊ.
ﯾﺟب أن ﺗﺗﺣﻣل اﻟﻠوﺣﺎت ﺷدة ﻗطﻊ ﻋﺎﻟﯾﺔ. -
ﺗوﺗر اﻟﻌﻣل ٦٩٠ – ٣٨٠ :ﻓوﻟط ٥٠ ،ﻫرﺗز. -
-ﺗوﺗر اﻟﻌﺎزﻟﯾﺔ ٦٩٠ :ﻓوﻟط.
-ﺧطوط اﻟﺷﺑﻛﺔ :ﻓﻲ ﺣﺎل وﺟـود ﻗواطـﻊ ﻋدﯾـدة ﻓـﻲ اﻟﻠوﺣـﺎت وﯾﺳـﺗدﻋﻲ وﺟـود ﺑـﺎرات رﺋﯾﺳـﯾﺔ
ﻓﯾﺟب أن ﺗﻛون ﺧﻣس ﺧطوط L1-L2-L3-N+PE
-ﯾﺟـب أن ﺗﻛــون اﻟﺑــﺎرات اﻟرﺋﯾﺳـﯾﺔ ﻧﺣﺎﺳــﯾﺔ إﻟﻛﺗروﻟﯾﺗﯾــﺔ أﺟﻧﺑﯾــﺔ اﻟﺻـﻧﻊ وﺑﻛﺛﺎﻓــﺔ ﺗﯾــﺎر ﻻ ﺗزﯾــد
ﻋن ٢أﻣﺑﯾر/ﻣم.٢
-ﺣﻣــﺎﻻت اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ :ﯾﺟــب أن ﺗﻛــون أﺟﻧﺑﯾــﺔ اﻟﺻــﻧﻊ ﻣــن إﺣــدى اﻟﺷــرﻛﺎت اﻟﻌﺎﻟﻣﯾــﺔ
وﺗﺗﺣﻣل اﻹﺟﻬﺎدات اﻟدﯾﻧﺎﻣﯾﻛﯾﺔ اﻟﻌﺎﻟﯾﺔ اﻟﻧﺎﺗﺟﺔ ﻋن ﺗﯾﺎرات اﻟﻘﺻر.
ﺗُﺣﻣﻰ ﺟﻣﯾﻊ دارات اﻟﺗﺣﻛم ﺿﻣن اﻟﻠوﺣﺎت ﺑﻔﯾوزات ١أﻣﺑﯾر. -
اﻟﻣراﺑط :ﯾﺟب أن ﺗﺳﺗﺧدم ﻓﻲ اﻟﻠوﺣﺎت ﻣراﺑط ﺧﺎﺻـﺔ ﺗرﻛـب ﻋﻠـﻰ ﺳـﻛﺔ ﻟﻠﻣﻘـﺎطﻊ ﻟﻐﺎﯾـﺔ ٧٠ -
ﻣﻠـم وﻣـراﺑط ﺻــﻧﺎﻋﯾﺔ ﺧﺎﺻــﺔ ﻟﻣﻘــﺎطﻊ ٧٠ﻣﻠــم ﻓﻣـﺎ ﻓــوق وﺗﻛــون ﻫــذﻩ اﻟﻣـراﺑط ﻣــن
أﺟود اﻷﻧواع اﻟﻐرﺑﯾﺔ ﻣﺻﻧوﻋﺔ وﻣﻘﺑوﻟﺔ ﻣن اﻟﻣواﺻﻔﺎت اﻟﻌﺎﻟﯾﺔ . IEC, VDE
٩٢
إن ﻋﻣﻠﯾﺔ ﺗﻔرﯾﻊ اﻟﻛﺑﻼت اﻟﺷﻌرﯾﺔ واﻟﺑﺎرات اﻟﻣرﻧﺔ ﻣن اﻟﺑﺎرات اﻟرﺋﯾﺳـﯾﺔ ) (L1-L2-L3ﺗـﺗم
ﻋﺑــر ﻣﻘــﺎﻣط )ﻛﻠﯾﺑﺳــﺎت( ﺧﺎﺻــﺔ ﺗرﻛــب ﻋﻠــﻰ اﻟﺑــﺎرات اﻟرﺋﯾﺳــﯾﺔ وﺗﻔــرّع ﻣﻧﻬــﺎ اﻟﻛــﺑﻼت واﻟﺑــﺎرات
اﻟﻣرﻧﺔ وﻻ ﯾﺳﻣﺢ ﺑﺗﺛﻘﯾب اﻟﺑﺎرات اﻟرﺋﯾﺳﯾﺔ ﻟﻠﺗﻔرﯾﻊ ﻣﻧﻬﺎ.
ﺗﺳــﺗﺧدم ﺟﻣﯾــﻊ اﻷﺳــﻼك ﺿــﻣن اﻟﻠوﺣــﺎت ﺑــﺎﻟﻠون اﻷﺳــود ﻣــﺎ ﻋــدا أﺳــﻼك اﻟــﺗﺣﻛم ﺑــﺎﻟﻠون -
اﻷﺣﻣر وأﺳﻼك اﻟﺣﯾﺎدي ﺑﺎﻟﻠون اﻷزرق.
ﺗﻛون ﺟﻣﯾﻊ اﻷﺳﻼك ﻓﻲ ﻧﻬﺎﯾﺗﻬﺎ ﻣرﻗﻣﺔ ﺑﺣﯾث ﯾﺳﻬل ﻋﻣﻠﯾﺔ اﻟﺻﯾﺎﻧﺔ ﻓﻲ اﻟﻣﺳﺗﻘﺑل. -
٩٣
TRANSFORMER
٩٤
اﻟﻣﺣوﻻت اﻟﻛﻬرﺑﯾﺔ
ﺗﻌرﯾف اﻟﻣﺣول:
ﻫو ﻣﻌدة ﺳﺎﻛﻧﺔ ﻻ ﺗﺣﺗوى ﻋﻠﻰ أي أﺟزاء ﻣﺗﺣرﻛﺔ ﺗﺳﺗﺧدم ﻟﻧﻘل اﻟﻘدرة اﻟﻛﻬرﺑﯾﺔ ﻣن ﺟﻬﺔ إﻟﻰ
ﺟﻬﺔ أﺧري وذﻟك ﺑﺗﻐﯾﯾر ﻗﯾم ﻣﻛوﻧﺎت ﻫذﻩ اﻟﻘدرة )اﻟﺟﻬد واﻟﺗﯾﺎر ( ﻣﻊ اﻟﻣﺣﺎﻓظﺔ ﻋﻠﻰ اﻟﺗردد .
وﻋﺎدة ﯾﺳﻣﻲ اﻟﻣﻠف اﻟﻣﺗﺻل ﺑﻣﺻدر اﻟﺟﻬد ﺑﺎﻟﻣﻠف اﻻﺑﺗداﺋﻲ ﻛﻣﺎ ﯾﺳﻣﻲ اﻟﻣﻠف اﻟﻣﺗﺻل ﺑﺎﻟﺣﻣل
ﺑﺎﻟﻣﻠف اﻟﺛﺎﻧوي.
اﺳﺗﺧداﻣﺎت اﻟﻣﺣوﻻت:
1.ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻟﻧﻘل اﻟﻘدرة اﻟﻛﻬرﺑﯾﺔ ﻟﻣﺳﺎﻓﺎت ﺑﻌﯾدة ﻣن أﻣﺎﻛن ﺗوﻟﯾدﻫﺎ إﻟﻰ أﻣﺎﻛن
ﺗوزﯾﻌﻬﺎ واﺳﺗﺧداﻣﻬﺎ.
2.ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻣﻊ أﺟﻬزة اﻟﻘﯾﺎس واﻟوﻗﺎﯾﺔ ﻋﻧدﻣﺎ ﺗﻛون اﻟﺗﯾﺎرات واﻟﺟﻬود اﻟﻛﻬرﺑﯾﺔ ﻋﺎﻟﯾﺔ
وذﻟك ﺑﺧﻔض ﻗﯾم اﻟﺗﯾﺎرات أو اﻟﺟﻬود إﻟﻰ ﻗﯾم ﺻﻐﯾرة ﯾﻣﻛن ﻗﯾﺎﺳﻬﺎ واﻟﺗﻌﺎﻣل ﻣﻌﻬﺎ.
3.ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻓﻲ اﻟﻌزل اﻟﻛﻬرﺑﺎﺋﻲ ﺑﻐرض ﻣﻧﻊ اﻟﺷوﺷرة اﻟﻛﻬروﻣﻐﻧﺎطﯾﺳﯾﺔ ﻓﻲ اﻟدواﺋر
اﻹﻟﻛﺗروﻧﯾﺔ.
4.ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت ﻓﻲ اﻏﻠب اﻷﺟﻬزة اﻟﻛﻬرﺑﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ ﻟﻠﺣﺻول ﻋﻠﻰ ﺟﻬود ﺗﺷﻐﯾل ﻫذﻩ
اﻷﺟﻬزة واﻟﺗﻲ ﺗﻌﺗﺑر ﺻﻐﯾرة ﺟدا ﺑﺎﻟﻣﻘﺎرﻧﺔ ﺑﺟﻬد اﻟﻣﺻدر.
5.ﺗﺳﺗﺧدم اﻟﻣﺣوﻻت أﯾﺿﺎ ﻟﻠﻣواﺋﻣﺔ ) اﻟﺗوﻓﯾق ( ﺑﯾن اﻟﻣﻣﺎﻧﻌﺎت.
ﺗرﻛﯾب اﻟﻣﺣول:
ﯾﺗرﻛب اﻟﻣﺣول ﻋﻣوﻣﺎ ﻣن:
1-ﻗﻠب ﺣدﯾدي ﻣﺻﻧوع ﻣن رﻗﺎﺋق ﻣن اﻷﻟواح اﻟﻣﺻﻧوﻋﺔ ﻣن اﻟﺻﻠب اﻟﺳﻠﯾﻛوﻧﻲ.
2-ﻣﻠﻔﯾن ﻣن اﻷﺳﻼك اﻟﻛﻬرﺑﯾﺔ اﻟﻣﻌزوﻟﺔ اﺣدﻫﻣﺎ ﻫو اﻟﻣﻠف اﻻﺑﺗداﺋﻲ واﻵﺧر ﻫو اﻟﻣﻠف
اﻟﺛﺎﻧوي وﯾﺗم ﻟﻔﻬﻣﺎ ﻋﻠﻰ ﺟﺎﻧﺑﻲ اﻟﻘﻠب اﻟﺣدﯾدي.
أي اﻧﻪ ﯾﻣﻛن اﻋﺗﺑﺎر اﻟﻣﺣول ﻣﻛون ﻣن داﺋرﺗﯾن اﺣداﻫﻣﺎ داﺋرة ﻣﻐﻧﺎطﯾﺳﯾﺔ واﻷﺧرى داﺋرة ﻛﻬرﺑﯾﺔ
ﺣﯾث ﯾﻣﺛل اﻟﻘﻠب اﻟﺣدﯾدي اﻟداﺋرة اﻟﻣﻐﻧﺎطﯾﺳﯾﺔ و ﺗﻣﺛل اﻟﻣﻠﻔﺎت اﻟداﺋرة اﻟﻛﻬرﺑﯾﺔ.
اﻧﻧﺎ ﻓﻲ اﻟﻣﻧﺗدى ﻏﺎﻟﺑﺎ ﻣﺎﻧﺗﺎول ﺟواﻧب اﻟﻧﺻب واﻟﺗﺷﻐﯾل واﻟﻔﺣص واﻟﺻﯾﺎﻧﺔ وﻗﻠﯾﻼ ﻣﺎ ﻧﻧظر اﻟﻰ
اﻟﺟﺎﻧب اﻟﺗﺻﻧﯾﻌﻲ ﻣن اﻟﻣﺣوﻟﺔ وﺳﺎﺣﺎول ﻓﻲ اﻟﻣﺷﺎرﻛﺎت ادﻧﺎﻩ ﺷرح اﻟﻣواد اﻟﻼزﻣﺔ ﻻﻧﺗﺎج
ﻣﺣوﻻت اﻟﺗوزﯾﻊ واﻟﻘدرة ﻣرﻛ از ﻋﻠﻰ اﻟﻣﺣوﻻت اﻟﺷﺎﺋﻌﺔ اﻻﺳﺗﺧدام واﻟﻣﺑردة ﺑﺎﻟزﯾت
٩٥
اوﻻ :اﻟﻣواد واﻻﺟﻬزة اﻻزﻣﺔ ﻻﻧﺗﺎج اﻟﻣﺣوﻻت ﺑﺻورة ﻋﺎﻣﺔ ﻫﻲ
-١اﻟﺣدﯾد اﻟﻛﻬرﺑﺎﺋﻲ
-٢اﻟﻣوﺻﻼت
-٣اﻟﻌوازل
-٤زﯾوت اﻟﻌزل
-٥ﻣﺂﺧذ اﻟﺗﯾﺎر )اﻟﺑوﺷﻧﺟﺎت(
-٦ﻣﻐﯾرات اﻟﺟﻬد
-٧اﺟﻬزة وﻣﺗﺣﺳﺳﺎت ﻣﻠﺣﻘﺔ ﻣﺛل ﻣزﯾﻼت اﻟرطوﺑﺔ وﻣﻌدات اﻟﺳﯾطرة ﻋﻠﻰ ﺗدﻓق اﻟزﯾوت وﻏﯾرﻫﺎ
-٨ﺣدﯾد ﺧزان اﻟﺗﺑرﯾد وﻣواد ﻣﺗﻌﻠﻘﺔ ﺑﺎﻟﺧزان واﻟﺗﺟﻣﯾﻊ اﻟﻣﯾﻛﺎﻧﯾﻛﻲ ﻟﻪ
وﺳﺎﺣﺎول ﻻﺣﻘﺎ ﺗﻔﺻﯾل ﻛل ﻣن اﻟﻔﻘرات اﻋﻼﻩ
٩٦
اﻟﺣﺎﺟﺔ ﺑﺎﻟﻣﺻﻧﻊ وﺳﻣﻛﻪ ﺣواﻟﻲ ) (mm٠.٣واﻟﺣدﯾد ﻫذا ﻣﻌزول ﺑطﺑﻘﺔ طﻼء ﻣؤﻛﺳد ﻟﻠﺷرﯾﺣﺔ
وﻣﻌﺎﻣل اﻟﺗﺟﻣﯾﻊ ﻟﻪ ﻓﻲ اﻟﻣﺣوﻻت ﺑﻌد اﻟﺗﻘطﯾﻊ ).(٠.٩٧ -٠.٩٥
-٣اﻟﻌوازل :
ﻣن اﻟﻣواد اﻻوﻟﯾﺔ اﻟداﺧﻠﺔ ﺑﺻﻧﺎﻋﺔ اﻟﻣﺣوﻻت ﻫﻲ اﻟﻌوازل اﻟﻣﺧﺗﻠﻔﺔ اﻟﻣﺳﺗﺧدﻣﺔ ﻻﻏراض اﻟﻌزل
اﻟﻣﺧﺗﻠﻔﺔ داﺧل اﻟﻣﺣوﻟﺔ ،ﺑﻌض ﻫذﻩ اﻟﻌوازل ورﻗﯾﺔ او ﻗد ﺗﻛون طﺑﻘﺎت ﻣن اﻟورق اﻟﻣﻘوى وﻗد
ﺗﺎﺧذ اﺷﻛﺎﻻ ﻣﺧﺗﻠﻔﺔ ﻣﺛل اﺷﻛﺎل ﻣﺟﺎري اﻟزﯾت واﻻﺷﻛﺎل اﻻﺳطواﻧﯾﺔ وﻏﯾرﻫﺎاﻟﻛﺛﯾر .
ﯾﻣﻛن ﺗﻘﺳﯾم اﻧواع اﻟﻌوازل اﻟﻰ :
-١ﻋوازل ﻣن اﻟﺧﺷب اﻟﻣﺿﻐوط )(Densified Wood
-٢ﻋوازل ورق ﻣﺿﻐوط واﻟواح ﻣﺿﻐوطﺔ )(Presspaper & Pressboard
-٣اﻟورق واﻻﻟواح اﻟﻣﺿﻐوطﺔ اﻻرﻣﯾدﯾﺔ )(Pressboard & Aramid Presspaper
-٤ﻋوازل ﻣرﻧﺔ
وﻟﻠﻌوازل اﺻﻧﺎف ﻣﻘﺳﻣﺔ ﺑﺎﻻﻋﺗﻣﺎد ﻋﻠﻰ اﻟﺣرارة اﻟﺗﻲ ﺗﺗﺣﻣﻠﻬﺎ ﻣﻧﻬﺎ
٩٧
(C°١٠٥) Class A
(Class B (130°C
(Class F (155°C
(C°١٨٠) Class H
ﻫﻧﺎك اﻧواع ﻟﻣﺎرﻛﺎت ﻣﺳﺟﻠﺔ ﻟورق اﻟﻌزل اﻟﻣﺳﺗﺧدم ﻟﻌزل اﻟﺷراﺋﺢ واﻟﻣﻘﺎطﻊ اﻟﻣوﺻﻠﺔ
اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺻﻧﻊ اﻟﻣﻠﻔﺎت ﺑﻌﺿﻬﺎ ﻟﻪ ﺧﺻﺎﺋص ﻣﺳﺎﻣﯾﺔ ﺗؤﻫﻠﻪ ﻻﻣﺗﺻﺎص اﻟزﯾت واﻋطﺎء
ﺧﺻﺎﺋص ﻋزل ﻣﻣﺗﺎزة ﻟﻣﺣوﻻت اﻟزﯾت ،واﻟﺑﻌض اﻻﺧر ﯾﺳﺗﻌﻣل ﻣﻊ اﻟﻣﺣوﻻت اﻟﺟﺎﻓﺔ وﻫذﻩ
ﺑﻌض ﻣﻧﻬﺎ :
• Kraft Paper
• Thermally upgraded paper
• Crepe paper
• Lumirror
• Nomex
٩٨
: Silicon Oilوﻫﻲ زﯾوت ﻏﯾر ﺳﺎﻣﺔ اﻣﯾﻧﺔ وﻣﺳﺗﻘرة ﻟدرﺟﺎت ﺣرارة واﺳﻌﺔ وﻣﻘﺎوﻣﺔ ﻟﻠﺗﺎﻛﺳد
وﻟﻬﺎ ﺧﺻﺎﺋص ﺟﯾدة .
: Natural Esterوﻫﻲ زﯾوت ﻧﺑﺎﺗﯾﺔ ﻻﺗﺣﺗوي اي ﻣواد ﻫﺎﻟوﺟﯾﻧﯾﺔ او ﺑﺗروﻟﯾﺔ او ﺳﻠﯾﻛوﻧﯾﺔ
وﻫﻲ ﻏﯾر ﺳﺎﻣﺔ ﻟﻬﺎ درﺟﺎت ﺗوﻫﺞ ﻋﺎﻟﯾﺔ )ﺣواي ٣٣٠درﺟﺔ( وﺑﺳﺑب طﺑﯾﻌﺗﻬﺎ ﻟﻬﺎ ﺧﺻﺎﺋص
ﺻدﯾﻘﺔ ﻟﻠﺑﯾﺋﺔ وﺗﻌﺗﺑر اﻛﺛر اﻣﺎﻧﺎ ﻣن ﻧﺎﺣﯾﺔ اﻻﺣﺗراق وﻣن اﻟﻧﺎﺣﯾﺔ اﻟﻛﯾﻣﯾﺎﺋﯾﺔ.
• اﻟﻧوع اﻻول ﻓﯾﻪ ﻗﺿﯾب اﻟﺗوﺻﯾل ﻣﻠﺣوم ﻟﻧﻬﺎﯾﺔ اﻟﻣﻠف ،وﯾﺧﺗرق اﻟﺗوﺻﯾل اﻟﺑورﺳﻠﯾن
اﻟﻣﺛﻘوب ﻣن اﻟوﺳط ﻟﯾوﻓر ﻣﻧﻔذا ﻟﻠﺗﯾﺎر ﻓﻲ ﻧﻬﺎﯾﺗﻪ ﻣﻌزوﻻ ﻋن اﻟﺟﺳم اﻟﻣﺣﯾط ﺑﻪ .ﺗﺛﺑت ﻧﻬﺎﯾﺔ
اﻟﻘﺿﯾب ﺑﺎﻟﺑورﺳﻠﯾن ﻋﺑر ﻏﺷﺎء ﻛﺎزﻛﯾت ﻟﻣﻧﻊ اﻟزﯾت ﻣن اﻟﺗﺳرب وﯾﺗم ﺷد اﻟﻧﻬﺎﯾﺎت ﺑﺑراﻏﻲ
ﺗوﺻﯾل
• اﻟﻧوع اﻟﺛﺎﻧﻲ ﯾﻛون ﻓﯾﻪ اﻟﺑوﺷﻧﺞ اﻟﺑورﺳﻠﯾﻧﻲ واﻟﻣوﺻﻼت ﻣﺻﺑوﺑﺔ وﯾﺗم اﺟراء اﻟﺗوﺻﯾل
ﻟﻠﻣﻠﻔﺎت واﻟﻘﺎﺑﻠوات ﻋﺑر ﺑراﻏﻲ وﺻﺎﻣوﻻت ﻣرﺑوطﺔ ﻓﻲ طرﻓﻲ اﻟﺗوﺻﯾل ﻟﻠﺑوﺷﻧﺞ
• اﻟﻧوع اﻻﺧﯾر ﻋﺑﺎرة ﻋن ﻧﺎﻗل ﺗﯾﺎر ) (bus barﻣﺻﺑوب ﺑﺎﻻﯾﺑوﻛﺳﻲ وﯾﺳﺗﻌﻣل ﻣﻊ ﻧوع
اﻟﻣﺣوﻻت اﻟﻣوﺻﻠﺔ ﻋﺑر ﺻﻧدوق ﺗﻐطﯾﺔ .
٩٩
اﺷﻛﺎل ﻣﺗﻧوﻋﺔ .
• Changer On Circuit Tap
وﻫذا اﻟﻧوع اﻻﺧر ﻣن ﻣﻐﯾرات اﻟﺟﻬد ﯾﻣﻛن ﻓﯾﻪ ﺗﻐﯾﯾر اﻟﺟﻬد واﻟﻣﺣوﻟﺔ ﺑﺣﺎﻟﺔ اﻻﺷﺗﻐﺎل وﻟﻣﻧﻊ
ﺣﺻول اﻟﺷرارة ﯾﺟب وﺟود زﯾت ﻓﻲ ﺻﻧدوق ﻣﻐﯾر اﻟﺟﻬد .وﯾﻛون ﻫذا اﻟﻧوع ﻣن ﻣﻐﯾرات اﻟﺟﻬد
اﻣﺎ ﻣﺳﺗﻘﻼ ﻣﻌزوﻻ ﻋن ﺧزان اﻟﻣﺣوﻟﺔ او ﯾﻧﺻب ﺑﺧزان اﻟﻣﺣوﻟﺔ وﻫﻧﺎك ﻣﺣرك ﯾﻘوم ﺑﻌﻣﻠﯾﺔ
ﺗﻐﯾﯾر اﻟﺟﻬد .
-٨اﻟﻣواد اﻟﻣﺗﻌﻠﻘﺔ ﺑﺧزان اﻟﺗﺑرﯾد ﻓﻲ اﻟﻣﺣوﻻت اﻟزﯾﺗﯾﺔ واﻟﻘطﻊ اﻟﻣرﺑوطﺔ ﻣﻌﻪ :
وﻫﻲ ﻣواد ﻛﺛﯾرة ﺗﺷﻣل اوﻻ اﻟﺣدﯾد اﻟﻼزم ﻟﺻﻧﻊ ﺧزان اﻟﺗﺑرﯾد واﻟﺧزان اﻻﺣﺗﯾﺎطﻲ وﺻﻧدوق
ﺗوﺻﯾﻼت اﻟﻣﺣوﻟﺔ واﻟذي ﯾﺻﻧﻊ ﻣن اﻟواح اﻟﺣدﯾد اﻟﺻﻠب ) (plate steelوﺑﺎﺳﻣﺎك ﻣﺧﺗﻠﻔﺔ
ﺣﺳب اﻟﺗﺻﻣﯾم ،وﻫﻧﺎك اﯾﺿﺎ ﻣﻘﺎطﻊ ﺣدﯾدﯾﺔ ﺑﺎﺷﻛﺎل ﻣﺗﻧوﻋﺔ ﻣﺛل chanels Uوﺑراﻏﻲ ﺷد
وﺻﺎﻣوﻻت ﻻﺣﻛﺎم رﺑط اﻟﺣدﯾد اﻟﻛﻬرﺑﺎﺋﻲ وﻟﻌﻣل ﻗﺎﻋدة اﻟﺟزء اﻟﻔﻌﺎل ﻣن اﻟﻣﺣوﻟﺔ وﻟﺻﻧﺎﻋﺔ
ﺣﻠﻘﺎت اﻟرﻓﻊ ﻟﻠﻣﺣوﻟﺔ ) (lifting lugsوﺑﻛرات ارﺟل اﻟﻣﺣوﻟﺔ اﻟﺣدﯾدﯾﺔ.
وﻟﻌﻣﻠﯾﺔ ﻟﺣﺎم اﻟﺧزان وﺗﻘطﯾﻊ ﻗطﻊ اﻟﺣدﯾد اﻟﻣﺧﺗﻠﻔﺔ ﻧﺣﺗﺎج ﻏﺎزات ﺻﻧﺎﻋﯾﺔ ﻣﺛل اﻻرﻛون
واﻻوﻛﺳﺟﯾن واﻟﻣﺳﺗﺧدﻣﺔ ﻟﻌﻣﻠﯾﺔ اﻟﻠﺣﺎم واﻟﻘطﻊ وﻛذﻟك اﺳﻼك ﻟﺣﺎم .
١٠٠
وﻫﻧﺎك اﯾﺿﺎ ﻣرﺗﺑط ﺑﺎﻟﺧزان اﻧﺎﺑﯾب ﻣﻌدﻧﯾﺔ ﺑﺎﻗطﺎر ﻣﺧﺗﻠﻔﺔ وﻓﻠﻧﺟﺎت وﺻﻣﺎﻣﺎت اﻟﻘﻔل اﻟﻣﯾﻛﺎﻧﯾﻛﯾﺔ
ﻟﻼﻧﺎﺑﯾب واﻟﺗﻲ ﻋن طرﯾﻘﻬﺎ ﯾﺗم اﻣﻼء وﺗﻔرﯾﻎ اﻟﻣﺣوﻻت ﻣن اﻟزﯾت .
وﻟﻠﻣﺳﺎﻋدة ﻋﻠﻰ اﺣﻛﺎم ﻗﻔل اﻟﺧزان ﻧﺣﺗﺎج اﻟﻰ اﺷﻛﺎل ﻣﺧﺗﻠﻔﺔ ﻣن اﻟﻣطﺎط اﻟﺻﻧﺎﻋﻲ اﻟﻣﺳﻣﻰ
) (neoprene casketﻓﻲ ﻣﻧﺎطق اﻻﻗﻔﺎل ﻟﻠﺑوﺷﻧﺟﺎت واﻟﻐطﺎء اﻟﻌﻠوي ﻟﻠﺧزان واي ﻣﻧﻔذ ﻣﺎﺑﯾن
ﺟﺳم اﻟﻣﺣوﻟﺔ اﻟﺧﺎرﺟﻲ واﻟﺟزء اﻟﻔﻌﺎل .
وﻓﻲ اﻟﻣﺣوﻻت اﻟﺿﺧﻣﺔ ﻗد ﺗﺣﺗﺎج اﻟﻰ ﻣراوح ﻫواء ﻟﺗﺑرﯾد اﻟﺧزان او ﻣﺿﺧﺎت ﻟﺗدوﯾر اﻟزﯾت
ﻗﺳرﯾﺎ .
واﺧﯾ ار ﻻﻧﻧﺳﻰ اﻻﺻﺑﺎغ اﻟﺗﻲ ﺗطﻠﻰ ﺑﻬﺎ اﻟﻣﺣوﻟﺔ ﺑﻌد اﻛﻣﺎل ﺗﺻﻧﯾﻊ اﻟﺧزان ،وﻟوﺣﺔ ﺗﻌﻠﯾم
اﻟﻣﺣوﻟﺔ ) (plate nameاﻟﻣطﺑوﻋﺔ ﻋﻠﻰ اﻟﺣدﯾد وﻓﯾﻬﺎ ﻣواﺻﻔﺎت اﻟﻣﺣوﻟﺔ.
ﺗﺻﻣﯾم اﻟﻣﺣوﻻت
ﯾﺗم ﺗﺣدﯾد ﺳﻌﺔ ﻣﺣول اﻟﺗوزﯾﻊ اﻟﻼزم ﻟﺗﻐذﯾـﺔ اﻟﻣﻧﺷـﺄة ﺑﻧـﺎ ًء ﻋﻠـﻰ أﻗﺻـﻰ طﻠـب )أ(
ﻛﻬرﺑﻲ ﻣﺗوﻗﻊ ﻟﻬذﻩ اﻟﻣﻧﺷﺄة وذﻟك طﺑﻘﺎً ﻟﻣﺎ ﯾﻠﻲ:
ﺳــﻌﺔ اﻟﻣﺣــول= ×١.٢٥أﻗﺻــﻰ طﻠــب ﻛﻬرﺑــﻲ )ك.ف.أ( )ﺑﻣﻌﻧــﻰ أن اﻟﻣﺣــول
ﯾﺣﻣل ﻓﻘط ﺑـ ٪٨٠ﻣن ﺳﻌﺗﻪ(
)ب( ﺗﻛــون اﻟﺣــدود اﻟﻣﺳــﻣوح ﺑﻬــﺎ ﻟﻼرﺗﻔــﺎع ﻓــﻲ درﺟــﺔ ﺣـرارة ﻣﺣــوﻻت اﻟﺗوزﯾــﻊ ﻋﻧــد
ﺗﺣﻣﯾﻠﻬــﺎ ﺑﺎﻟﺳــﻌﺔ اﻹﺳــﻣﯾﺔ ﻟﻬــﺎ ﺑﺻــﻔﺔ ﻣﺳــﺗﻣرة )ﻟﻣــدة ﻻ ﺗﻘــل ﻋــن ٦ﺳــﺎﻋﺎت(
ﻋﻠﻰ اﻟﻧﺣو اﻟﺗﺎﻟﻰ:
) (١ﯾﺟــب أﻻ ﯾﺗﺟــﺎوز اﻻرﺗﻔــﺎع ﻓــﻲ درﺟــﺔ ﺣ ـرارة اﻟزﯾــت أﻋﻠــﻰ ﺧ ـزان اﻟﺗﻣــدد
ْ٤٥م.
ﯾﻛون ﻣﺗوﺳط اﻻرﺗﻔﺎع ﻓﻲ درﺟﺔ ﺣرارة اﻟﻣﻠﻔﺎت )واﻟﺗﻲ ﺗﻘﺎس ﻋن طرﯾق
ﻗﯾﺎس ﻣﻘﺎوﻣﺔ اﻟﻣﻠﻔﺎت( °٦٠م.
) (٢ﻻ ﯾﺟب أن ﺗرﺗﻔﻊ درﺟﺔ ﺣرارة اﻟزﯾت ﻓﻰ ﺧزان اﻟﺗﻣدد وﻛذﻟك اﻟﺗوﺻﯾﻼت
اﻟﻛﻬرﺑﯾﺔ ﺑﺣﯾث ﻻ ﺗﺳﺑب ﺿر ارً ﻋﻠﻰ اﻟﻣﺣﯾط اﻟﺧﺎرﺟﻲ.
وﯾــﺗم ﻋﻣوﻣ ـﺎً إﺗﺑــﺎع اﻹرﺷــﺎدات اﻟﺧﺎﺻــﺔ ﺑﺎﻟﻣﺻــﻧﻊ ﻓــﻲ ﺗرﻛﯾــب وﺗﺷــﻐﯾل
اﻟﻣﺣول.
١٠١
ﯾﺣـدد اﻟﻣﺻــﻧﻊ طرﯾﻘـﺔ ﺗﺑرﯾــد اﻟﻣﺣـول ،ﺑﺎﺳــﺗﺧدام أرﺑـﻊ ﺣــروف ،ﯾرﻣـز اﻟﺣرﻓــﺎن
اﻷوﻻن إﻟﻲ اﻟﻣواﺋﻊ اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﺗﺑرﯾد اﻟﻣﻠﻔﺎت داﺧل اﻟﻣﺣول ،ووﺳﯾﻠﺔ دﻓﻊ
ﻫذﻩ اﻟﻣواﺋـﻊ ،و ﯾرﻣـز اﻟﺣرﻓـﺎن اﻵﺧـران إﻟـﻲ اﻟﻣواﺋـﻊ اﻟﻣﺳـﺗﺧدﻣﺔ ﻟﺗﺑرﯾـد ﺟﺳـم
اﻟﻣﺣــول ﻣــن اﻟﺧــﺎرج ،ووﺳــﯾﻠﺔ دﻓــﻊ اﻟﻣواﺋــﻊ ،و ﯾﺣﺗــوي اﻟﺟــدول ﻋﻠــﻲ اﻟرﻣــوز
اﻟﻣﺳﺗﺧدﻣﺔ ﻓﻲ ﻫذا اﻟﻧظﺎم
ﻣﺛﺎل:
ﻣﺣــول زﯾﺗــﻲ )ﯾﺑــرد داﺧﻠﯾ ـﺎً ﺑﺳــرﯾﺎن اﻟزﯾــت ﺳــرﯾﺎﻧﺎً طﺑﯾﻌﯾ ـﺎً وﯾﺑــرد : ONAN
اﻟﺟﺳم ﻣن اﻟﺧﺎرج ﺑﺳرﯾﺎن اﻟﻬواء ﺣوﻟﻪ ﺳرﯾﺎﻧﺎً طﺑﯾﻌﯾﺎً أﯾﺿﺎً(
أﻗﺻﻰ ﺗﺣﻣﯾل ﯾوﻣﻰ ﻟﻠﺣﻔﺎظ ﻋﻠﻰ ﺳﻼﻣﺔ اﻟﻣﺣوﻻت
Daily Peak Load of Transformer Nameplate Rating to Give Normal
Life Expectancy
) (١ﯾﻣﻛــن ﺗﺷــﻐﯾل اﻟﻣﺣــوﻻت ﻋﻧــد درﺟــﺎت ﺣــرارة اﻟزﯾــت أﻋﻠــﻰ ﻣــن ْ٩٥م،
ﻟﻔﺗرات ﻗﺻﯾرة ﻣﺣددة ﺑدون أن ﺗﺳﺑب ﻣﺧﺎطر ﺗذﻛر ﻋﻠﻰ اﻟﻣﺣول ،ﻛذﻟك
ﯾﻣﻛن ﺗﺷﻐﯾﻠﻬﺎ ﻟﻔﺗرات أطول ﻋﻧد درﺟﺎت ﺣرارة أﻗل ﻣن ْ٩٥م.
ﻋﺎدة ﺗﺗﻛـون دورة اﻟﺗﺣﻣﯾـل اﻟﯾـوﻣﻰ ) (Daily loadﻣـن أﺣﻣـﺎل ﻣﺗﻐﯾـرة
ﺧــﻼل اﻟﯾــوم ،وﯾﻣﻛــن أن ﻧﻘﺳــم اﻟــدورة إﻟــﻰ ﻣراﺣــل ﺑﺣﯾــث ﯾﻛــون اﻟﺣﻣــل
١٠٢
ﺛﺎﺑﺗ ـﺎً ﺗﻘرﯾﺑ ـﺎً ﻓــﻰ ﻛــل ﻣرﺣﻠــﺔ ،ﻛﻣــﺎ ﯾﻣﻛــن ﺣﺳــﺎب اﻟﺣﻣــل اﻟﻣﻛــﺎﻓﺊ ﻟــدورة
اﻟﺗﺣﻣﯾل اﻟﯾوﻣﻰ ﻣن اﻟﻣﻌﺎدﻟﺔ :
ﺣﯾث:
أﺣﻣﺎل اﻟﻣراﺣل اﻟﻣﺧﺗﻠﻔﺔ L1 , L2 , Ln
ﻓﺗرة ﻛل ﻣرﺣﻠﺔ t1 , t 2 , t n
) (٢ﯾﺟب ﻋﻧد ﺗﺣﻣﯾل اﻟﻣﺣوﻻت ﻋﻧد درﺟﺎت ﺣرارة أﻛﺑر ﻣن ْ٥٠م أﻻ ﺗﺗﻌدى
ﺣــــدود اﻟﺗﺣﻣﯾــــل ﻓﺗــــرة زﻣﻧﯾــــﺔ ﻣﻌﯾﻧــــﺔ ،ﻣﺣــــددة ﺑﺎﻟﻣواﺻــــﻔﺎت اﻟﻘﯾﺎﺳــــﯾﺔ
اﻟﻌﺎﻟﻣﯾــﺔ ،ﺣﺗــﻰ ﻻ ﯾﺗــﺄﺛر اﻟﻣﺣــول وﯾﻘــل ﻋﻣــرﻩ اﻻﻓﺗراﺿ ـﻰ ،وﯾﺟــب ﻋﻣــل
ﺗـوازن ﻟــدورة اﻟﺣﻣــل اﻟﯾــوﻣﻰ ،ﺑﺣﯾــث ﯾــﺗم ﺗﺣﻣﯾــل اﻟﻣﺣــول ﺑﺣﻣــل ﺻــﻐﯾر
ﻟﻔﺗرات أﺧرى ،ﺛم ﺗﺣﻣﯾﻠﻪ ﻟﻔﺗرة زﻣﻧﯾﺔ ﺻﻐﯾرة ﺑﺎﻟﺣﻣل اﻟزاﺋد ،وﯾﺗم اﻟﻛﺷف
ﻋﻠــﻰ ﺟﻣﯾــﻊ أﺟــزاء اﻟﻣﺣـــول ،ﺑﻌــد ﺗﺷــﻐﯾﻠﻪ ﺑزﯾـــﺎدة ﺣﻣــل )ﻣﺛــل :ﻧﻬﺎﯾـــﺔ
اﻟﻛﺎﺑﻼت – ﻧﻘط اﻟﺗﻘﺳﯾم ،إن أﻣﻛن ،ﻋوازل اﻻﺧﺗراق .(....
ﯾوﺿــﺢ اﻟﺟــدول اﻟﺗــﺎﻟﻲ أﻗﺻــﻰ ﺗﺣﻣﯾــل ﯾــوﻣﻰ ﻟﻠﻣﺣــوﻻت ﺑدﻻﻟــﺔ درﺟــﺔ اﻟﺣ ـرارة
اﻟﻣﺣﯾط ﻟﻠﺣﻔﺎظ ﻋﻠﻰ ﻋﻣرﻫﺎ اﻻﻓﺗراﺿﻰ٠
Daily peak load of Transformer nameplate rating to give normal life
expectancy
١٠٣
ﺟدول أﻗﺻﻰ ﺣﻣل ﯾوﻣﻰ ﻛﻧﺳﺑﺔ ﻣن اﻟﺣﻣل اﻟﻣﻘﻧن اﻟﻣذﻛور ﺑﻠوﺣﺔ ﺑﯾﺎن
اﻟﻣﺣول ،ﻟﺣﻔﺎظ ﻋﻠﻰ ﻋﻣر اﻟﻣﺣول
زﻣﻦ
أﻗﺼﻰ
ﺣﻤﻞ
)ﺳﺎﻋﺔ(
درﺟﺔ اﻟﺣرارة اﻟﻣﺣﯾطﺔ ) ◌ْ م( درﺟﺔ اﻟﺣرارة اﻟﻣﺣﯾطﺔ ) ◌ْ م( درﺟﺔ اﻟﺣرارة اﻟﻣﺣﯾطﺔ ) ◌ْ م(
١٠٤
اﻟﺗﺣﻣﯾل اﻟزاﺋد ﻟﻠﻣﺣوﻻت
اﻟﻣﺣوﻻت اﻟﻣﻐﻣورة ﻓﻰ اﻟزﯾت )أ(
اﻟﺟــدول اﻟﺗــﺎﻟﻲ ﯾﺣﺗــوى ﻋﻠــﻰ ﻗــدرة اﻟﺗﺣﻣﯾــل اﻟزاﺋــد )ﻛﻧﺳــﺑﺔ ﻣــن اﻟﻘــدرة اﻟﻣﻘﻧﻧــﺔ
ﻟﻠﻣﺣوﻻت اﻟﻣﻐﻣـورة ﻓـﻰ اﻟزﯾـت ،طﺑﻘـﺎً ﻟﻠﻣواﺻـﻔﺎت اﻟﻘﯾﺎﺳـﯾﺔ اﻷﻟﻣﺎﻧﯾـﺔ )(DIN
ﯾﺟب أﻻ ﺗﺗﻌدى ﻣﺗوﺳط درﺟـﺔ ﺣـرارة اﻟﻣﻠﻔـﺎت ْ١٠٥م ،إذا ﻛـﺎن ﻣﺗوﺳـط درﺟـﺔ
وﺳــط اﻟﺗﺑرﯾــد ﺧــﻼل اﻟــدورة ْ٢٥م ،إو ذا ﻛﺎﻧــت اﻟﻣﺣــوﻻت ﻣﺟﻬــزة ﺑﻣـراوح ﺗﺑرﯾــد
وﻟﻛـــن اﻟﻣـــراوح ﻣﻌزوﻟـــﺔ ﻓﯾﺟـــب أن ﯾﻛـــون اﻟﺗﺣﻣﯾـــل ٪٦٠ﻣـــن اﻟﻘـــدرة اﻟﻣﻘﻧﻧـــﺔ
ﻟﻠﻣﺣول.
ﻣدة اﻟﺗﺣﻣﯾل اﻟزاﺋد ﺑﺎﻋﺗﺑﺎر اﻟﺣﻣل اﻟزاﺋد ﻧﺳﺑﺔ درﺟﺔ ﺣرارة اﻟزﯾتْ م ﻋﻧد
ﻣن اﻟﻣﻘﻧن ﺑداﯾﺔ زﯾﺎدة اﻟﺣﻣل ﺗﺑﻌﺎً ﻧﺳﺑﺔ اﻟﺗﺣﻣﯾل
ﻟﺣﺎﻟﺔ اﻟﺗﺑرﯾد اﻟﺳﺎﺑﻘﺔ ٪ﻣن
٪٥٠ ٪٤٠ ٪٣٠ ٪٢٠ ٪١٠ ﺗﺑرﯾد ﻣﯾﺎﻩ – ﺗﺑرﯾد ﻫواء ﻗﯾﻣﺔ ﻗدرة
ﺗﺑرﯾد زﯾت طﺑﯾﻌﻰ أو اﻟﻣﺣول
دﻗﯾﻘﺔ دﻗﯾﻘﺔ دﻗﯾﻘﺔ ﺳﺎﻋﺔ ﺳﺎﻋﺔ
وﻫواء ﻣدﻓوع ﻣراوح
١٥ ٣٠ ٦٠ ١.٥ ٣ ٤٩ ٥٥ ٥٠
٨ ١٥ ٣٠ ١ ٢ ٦٠ ٦٨ ٧٥
٤ ٨ ١٥ ٠.٥ ١ ٦٨ ٧٨ ٩٠
١٠٥
ﻓﺗرة زﯾﺎدة اﻟﺣﻣل ﻟﻠﻣﺣوﻻت اﻟﺟﺎﻓﺔ ذات ﻋزل درﺟﺔ )(A
إذا ﻛﺎﻧت درﺟﺔ ﺣرارة اﻟﻬواء ﻣﺧﺗﻠﻔﺔ ﻋن اﻟﻘﯾم اﻟﻘﯾﺎﺳﯾﺔ اﻟﻣﺳـﺗﺧدﻣﺔ ﻟﻠﻣﺣـوﻻت
ﻓﯾﺗم اﻟرﺟوع إﻟﻰ اﻟﺟدول اﻟﺗﺎﻟﻲ ﻟﻠﻣﺣوﻻت اﻟﻣﻐﻣورة ﻓﻰ اﻟزﯾت – ﺗﺑرﯾد اﻟﻬواء.
ﻣﻼﺣظﺎت
PILLAR -١
ﺻﻧدوق اﻟﺗوزﯾﻊ اﻟﻣﻐذى ﻣﺑﺎﺷرة ﻣن اﻟﻣﺣول
COFFREE -٢
١٠٦
اﻟﻠوﺣﺔ اﻟﻣﻐذﯾﺔ ﻟﻠﻣﻧﺷﺄة
اﻟﻘرار اﻟوزاري -٣
ﻫو اﻟﻣﺣور اﻷﺳﺎﺳﻲ ﻟﺗﺻﻣﯾم اﻟﺷﺑﻛﺎت